This document is a Pre-Construction Risk Assessment and Exposure Control Checklist for a federal contract opportunity related to the VA Caribbean Healthcare System in San Juan, Puerto Rico. The project involves EHRM Infrastructure Upgrades across multiple buildings, including general construction, infrastructure upgrades, reconfiguration, and renovation work. Key hazards identified include asbestos, dust, moisture/water leaks, vapors/fumes, noise, vibration, air pressure relationships, and proximity to immune-suppressed patients. Control measures are detailed, such as asbestos abatement, dust containment, negative air pressure, scheduling work after hours, and relocating patients. The related federal contract opportunity is Solicitation Number 36C77624B0012 for the "EHRM Infrastructure Upgrades Construction San Juan" project, which is being solicited by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files for this federal contract opportunity
Show all 39
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT Z
CENTER MEMORANDUM NO. 00-16-81
APRIL 2016
VA CARIBBEAN HEALTHCARE SYSTEM
SAN JUAN, PUERTO RICO
PRECONSTRUCTION RISK ASSESSMENT AND EXPOSURE CONTROL CHECKLIST
Project Name: 672-21-700 EHRN Infrastructure Upgrade San Juan PR Date: 01/19/2024
Hazard Concern?
(Y/N)
Control
Measure Remarks
Asbestos Y h, a Asbestos will be removed only on new Telecommunication Rooms
Dust Y a, e, f
Moisture/Water Leaks Y a
Vapors/Fumes Y b
Noise Y b Moderated Noise Level
Vibration Y b
Air Pressure Relationships Y a
Traffic Flow Y b
Open Outside Walls N
Impact to Levels Above and Below Y a, b
Proximity of Air Intakes N
Pest Control Within Construction Area Y b
Proximity of Immune Suppressed Patients N
Approval Signatures:
Project Manager: _________________________________
Chief Engineering Section: __________________________
Infection Control: __________________________________
Industrial Hygienist: ________________________________
Contractor: ____________________________________
Service/Section/Program Chief: _________________________
APRIL 2016
Control Measures
Asbestos
a. Contractor has hired an asbestos abatement contractor for control and cleanup.
b. VA to hire independent Industrial Hygienist to inspect and clear area for re-occupancy based on monitoring and/or professional judgment.
c. Published asbestos protocol to be followed for work through ceilings.
d. Published asbestos protocol to be followed for work above ceilings.
e. Perimeter barrier will be constructed in the interstitial space to isolate the construction area with other areas in the interstitial.
f. Project area will be encased with spray-applied hard surface encasement material.
g. Provide mini containments under negative air in public areas.
h. Sealed gypsum board barrier will be constructed to isolate the construction area from the public.
i. Transit panels will be removed, which is considered Class B removal.
Dust
a. Sealed gypsum board barrier will be constructed to isolate the construction area from the public.
b. Trash carts will be covered when transported through the building.
c. Provide negative air machine exhausted to outside.
d. Provide mini containments under negative air in public areas.
e. Provide negative air machine in space as air scrubber.
f. Provide walk off mats at entrances to work area.
g. Perimeter barrier will be constructed in the interstitial space to isolate the construction area with other areas in the interstitial.
Moisture Water Leaks
a. Contain any water from core drilling activities.
b. Dike any floor penetrations to minimize risk of leaks from construction zone.
Vapors/Fumes
a. Use of products with low Volatile Organic Compounds (VOCs).
b. Provide negative air in construction zone exhausted to outside, away from intakes.
c. Seal work area airtight barrier.
d. Cut all metal outside the building.
e. Seal any floor penetrations to minimize risk of fumes through construction zone.
f. Shut down air handler to minimize infiltration of fumes from outside.
Noise
Schedule demolition work after normal work hours.
Cut all metal outside the building.
Vibration
a. Schedule demolition work after normal work hours.
b. Coordinate with occupants in surrounding areas to explain the work occurring.
a.
b.
APRIL 2016
Air Pressure Relationships
a. Provide negative air during asbestos abatement.
b. Provide negative air during construction.
c. Seal off supply and exhaust Heating, Ventilation, and Air Conditioning (HVAC) registers.
d. Provide anteroom under negative pressure at entrance to project zone.
Traffic Control
Access construction area via exterior door.
Schedule delivery of large quantities of material and demolition haul out after hours.
Open Outside Walls
a. Construct temporary outside wall to limit the infiltration of wind, air, and temperature differences into the project site.
Impact to Levels Above and Below
a. Coordinate with occupants in surrounding areas to explain the work occurring.
b. Follow asbestos protocol when doing under floor work.
c. Vacate areas when doing below floor work off of the catwalk.
Proximity of Air Intakes
a. Shut down air handlers to reduce infiltration of fumes from exterior activities such as painting, gasoline powered engines, roofing operations, equipment, etc.
Pest Control within Construction Area
a. Provide barriers to any open outside walls.
b. Contact pest controller if any evidence of pests is found during the course of the work.
Proximity of Immune Suppressed Patients
a. Relocate patients away from construction zone for entire project.
b. Relocate patients away from construction zone during demolition operations.
a.
b.
| 2024-01-19T15:21:25-0400 | |
| RADAMES PERDOMO |
| 2024-01-19T15:28:31-0400 | |
| VICTOR MEDINA-MASSANET |
| 2024-01-22T06:22:00-0400 | |
| NANCY ROMAN-DE LEON |
| 2024-01-22T11:18:47-0400 | |
| RICHARD CINTRON-ORTIZ |
| 2024-01-22T13:51:40-0400 | |
| WILFREDO QUINONES MENDEZ |
File details come from the government source that posted it. Updated .