Attachment 10 - Drawing 7 of 7.pdf
PDF 4 MB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrade Construction Fort Meade VAMC Federal contract opportunity
- Solicitation number
- 36C77622B0055
About this file
This document package includes construction drawings and specifications for electrical infrastructure upgrades at the Veterans Affairs Medical Center in Fort Meade, South Dakota. The project involves upgrades to electrical systems in multiple buildings on the campus including installation of new electrical panels and switchboards, replacement of telecommunications cabling and equipment, addition of backup generators and UPS systems, and HVAC and cooling system improvements. Detailed drawings and schedules provide layouts and requirements for equipment to be installed in various buildings. Specifications identify scope of work, contractor responsibilities, and guidelines for routing utilities and conduits. The solicitation seeks bids for construction of the infrastructure upgrades outlined in the engineering documents.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANEL '113-UPS1-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-169-1A SPEC 2,333 2,333 SPEC RK-TCS103-1A 30 3 2
3 3 30 ^^^ SPEC 2,333 2,333 SPEC ^^^ 30 3 4
5 3 30 ^^^ SPEC 2,333 2,333 SPEC ^^^ 30 3 6
7 3 30 ZP-192-1A SPEC 2,333 SPARE 20 1 8
9 3 30 ^^^ SPEC 2,333 SPARE 20 1 10
11 3 30 ^^^ SPEC 2,333 SPARE 20 1 12
13 3 20 RK-ECIE-1A SPEC 1,167 SPARE 20 1 14
15 3 20 ^^^ SPEC 1,167 SPACE - 1 16
17 3 20 ^^^ SPEC 1,167 SPACE - 1 18
19 1 20 SPARE SPACE - 1 20
21 1 20 SPARE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 8,167 8,167 8,167 24,500 VA
TOTAL AMPS 68 68 68 68 A
A.I.C. RATING: 22,000
MISC RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.50 24.5 KVA 68 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.50 24.5 KVA 68 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.50 24.5 KVA 68 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
PANEL '113-UPSB-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 20 RK-B01-1A SPEC 1,167 SPARE 20 1 2
3 3 20 ^^^ SPEC 1,167 SPARE 20 1 4
5 3 20 ^^^ SPEC 1,167 SPARE 20 1 6
7 1 20 SPARE SPACE - 1 8
9 1 20 SPARE SPACE - 1 10
11 1 - SPACE SPACE - 1 12
13 1 - SPACE SPACE - 1 14
15 1 - SPACE SPACE - 1 16
17 1 - SPACE SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 1,167 1,167 1,167 3,500 VA
TOTAL AMPS 10 10 10 10 A
A.I.C. RATING: 22,000
MISC RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.50 3.5 KVA 10 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.50 3.5 KVA 10 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.50 3.5 KVA 10 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
NEW DP '145-EQDP-T1'
MFR/MODEL: SQUARE 'D' TYPE I-LINE VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A
MTG SPACE: AS REQUIRED VOLT-AMPS MTG: SURFACE
N O
T E
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
N O
T E a 3 * PANEL '145-EQ1-T1' FEDR 9709 9681 FEDR PANEL '145-EQ2-T1' * 3 a a 3 * ^^^ FEDR 11477 9619 FEDR ^^^ * 3 a a 3 * ^^^ FEDR 9481 7367 FEDR ^^^ * 3 a a 3 * PANEL '145-EQ3-T1' FEDR 9501 SPACE - 1 a 3 * ^^^ FEDR 7005 SPACE - 1 a 3 * ^^^ FEDR 4985 SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPCAE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
TOTAL V-A 28892 28102 21834 78,827 VA
TOTAL AMPS 241 234 182 219 A
AVAILABLE FAULT CURRENT : 22,000 A AIC RATING:
LTG REC MOTR LG MTR MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 KVA 0 A
CONNECTED LOAD IN KVA (BRANCH PANELS) 0.47 4.86 52.50 2.24 7.00 0.00 0.00 14.00 78.8 KVA 225 A
TOTAL CONNECTED LOAD IN KVA: 0.47 4.86 52.50 2.24 7.00 0.00 0.00 14.00 78.8 KVA 219 A
DEMAND LOAD IN KVA: 0.59 4.86 52.50 2.24 7.00 0.00 0.00 10.00 77.2 KVA 214 A
PANEL NOTES: PANEL OPTIONS:
a SEE ONE-LINE 1/EK-003 FOR BREAKER SIZE MAIN LUGS ONLY
PANEL '145-EQ1-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-122B-1B SPEC 2,333 720 RECP TELECOM RM 122B E. RECP 20 1 2
3 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM 122B W. RECP 20 1 4
5 3 30 ^^^ SPEC 2,333 180 RECP 145-RECP-1 20 1 6
7 2 50 145-IU-1 MOTR 3,952 208 LTG LTG RM 122B 20 1 8
9 2 50 ^^ MOTR 3,952 SPARE 20 1 10
11 2 45 145-CU-1 MOTR 2,496 SPARE 20 1 12
13 2 45 ^^ MOTR 2,496 SPARE 20 1 14
15 2 60 145-IU-4 MOTR 4,472 SPACE - 1 16
17 2 60 ^^ MOTR 4,472 SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 9,709 11,477 9,481 30,668 VA
TOTAL AMPS 81 96 79 85 A
A.I.C. RATING: 22,000
TOTAL LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.21 1.62 21.84 2.24 0.00 0.00 0.00 7.00 30.7 KVA 85 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.21 1.62 21.84 2.24 0.00 0.00 0.00 7.00 30.7 KVA 85 A
DEMAND LOAD IN KVA: 0.26 1.62 21.84 2.24 0.00 0.00 0.00 7.00 33.0 KVA 91 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:3
A
M
EK-009
PANEL SCHEDULES - BLDGS 113 &
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
Revisions: Date:
PANEL '145-EQ2-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-229A-1B SPEC 2,333 720 RECP TELECOM RM 229A E. RECP 20 1 2
3 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM 229A W. RECP 20 1 4
5 3 30 ^^^ SPEC 2,333 104 LTG RM 229A LTG 20 1 6
7 2 50 145-IU-2 MOTR 3,952 180 RECP 145-RECP-2 20 1 8
9 2 50 ^^ MOTR 3,952 180 RECP 145-RECP-3 20 1 10
11 2 45 145-CU-2 MOTR 2,496 SPARE 20 1 12
13 2 45 ^^ MOTR 2,496 SPACE - 1 14
15 2 45 145-CU-4 MOTR 2,434 SPACE - 1 16
17 2 45 ^^ MOTR 2,434 SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 9,681 9,619 7,367 26,667 VA
TOTAL AMPS 81 80 61 74 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.10 1.80 17.76 1.98 0.00 0.00 0.00 7.00 26.7 KVA 74 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.10 1.80 17.76 1.98 0.00 0.00 0.00 7.00 26.7 KVA 74 A
DEMAND LOAD IN KVA: 0.13 1.80 17.76 1.98 0.00 0.00 0.00 7.00 28.7 KVA 80 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
PANEL '145-EQ3-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-329-1B MISC 2,333 720 RECP TELECOM RM 329 E. RECP 20 1 2
3 3 30 ^^^ MISC 2,333 720 RECP TELECOM RM 329 W. RECP 20 1 4
5 3 30 ^^^ MISC 2,333 156 LTG LTG RM 329 20 1 6
7 2 50 145-IU-3 MOTR 3,952 SPARE 20 1 8
9 2 50 ^^ MOTR 3,952 SPARE 20 1 10
11 2 45 145-CU-3 MOTR 2,496 SPARE 20 1 12
13 2 45 ^^ MOTR 2,496 SPACE - 1 14
15 1 - SPACE SPACE - 1 16
17 1 - SPACE SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 9,501 7,005 4,985 21,492 VA
TOTAL AMPS 79 58 42 60 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.16 1.44 12.90 1.98 7.00 0.00 0.00 0.00 21.5 KVA 60 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.16 1.44 12.90 1.98 7.00 0.00 0.00 0.00 21.5 KVA 60 A
DEMAND LOAD IN KVA: 0.20 1.44 12.90 1.98 7.00 0.00 0.00 0.00 23.5 KVA 65 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
DISTRIBUTION PANEL 'UPSDP-1'
MFR/MODEL: SQUARE 'D' TYPE I-LINE VOLTS: 277/480V,3PH,4W ENCLOSURE: NEMA 1 400 A
MTG SPACE: AS REQUIRED VOLT-AMPS MTG: SURFACE
N O
T E
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
N O
T E a 3 * PANEL 'UPS-A' FEDR 34700 9333 FEDR PANEL '113-UPSDP-T1' * 3 a a 3 * ^^^ FEDR 34700 9333 FEDR ^^^ * 3 a a 3 * ^^^ FEDR 34700 9333 FEDR ^^^ * 3 a
1 - SPACE 7000 FEDR PANEL '148-UPS-T1' * 3 a
1 - SPACE 7000 FEDR ^^^ * 3 a
1 - SPACE 7000 FEDR ^^^ * 3 a
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
TOTAL V-A 51033 51033 51033 153,100 VA
TOTAL AMPS 184 184 184 184 A
AVAILABLE FAULT CURRENT : 22,000 A AIC RATING:
LTG REC MOTR LG MTR MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 KVA 0 A
CONNECTED LOAD IN KVA (BRANCH PANELS) 0.00 0.00 0.00 0.00 79.60 0.00 0.00 73.50 153.1 KVA 184 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 73.50 153.1 KVA 184 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 52.50 132.1 KVA 159 A
PANEL NOTES: PANEL OPTIONS:
a SEE ONE-LINE 1/EK-002 FOR BREAKER SIZE MAIN LUGS ONLY
PANEL 'UPS-A'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E b 1 3 * BUS A-1 MISC 4667 10933 MISC BUS A-2 * 3 2 b b 3 3 * ^^^ MISC 4667 10933 MISC ^^^ * 3 4 b b 5 3 * ^^^ MISC 4667 10933 MISC ^^^ * 3 6 b b 7 3 * BUS A-3 MISC 10933 2333 SPEC ZP-229A-1A 30 3 8 b 9 3 * ^^^ MISC 10933 2333 SPEC ^^^ 30 3 10 b 11 3 * ^^^ MISC 10933 2333 SPEC ^^^ 30 3 12
13 3 30 ZP-122B-1A SPEC 2333 1167 SPEC BLDG 146 RK 108-1A 20 3 14
15 3 30 ^^^ SPEC 2333 1167 SPEC ^^^ 20 3 16
17 3 30 ^^^ SPEC 2333 1167 SPEC ^^^ 20 3 18
19 3 30 ZP-329-1A SPEC 2333 SPACE - 1 20
21 3 30 ^^^ SPEC 2333 SPACE - 1 22
23 3 30 ^^^ SPEC 2333 SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 34700 34700 34700 104,100 VA
TOTAL AMPS 289 289 289 289 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 79.60 0.00 0.00 24.50 104.1 KVA 289 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 24.50 104.1 KVA 289 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 17.50 97.1 KVA 270 A
PANEL NOTES: PANEL OPTIONS:
a FED FROM 'UPS-A' MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE) b SEE BUSWAY DETAILS ON SHEET 145-EP-100 FOR SIZE PROVIDE WITH 200% RATED NEUTRAL
PROVIDE WITH CONTINUOUS HINGED TRIM
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:3
A
M
EK-010
PANEL SCHEDULES - BLDG 145 EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
PANEL 'UPS-B'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E b 1 3 * BUS B-1 MISC 4667 10933 MISC BUS B-2 * 3 2 b b 3 3 * ^^^ MISC 4667 10933 MISC ^^^ * 3 4 b b 5 3 * ^^^ MISC 4667 10933 MISC ^^^ * 3 6 b b 7 3 * BUS B-3 MISC 10933 SPARE 1 8 b 9 3 * ^^^ MISC 10933 SPARE 1 10 b 11 3 * ^^^ MISC 10933 SPARE 1 12
13 1 SPACE SPACE 1 14
15 1 SPACE SPACE 1 16
17 1 SPACE SPACE 1 18
19 1 SPACE SPACE 1 20
21 1 SPACE SPACE 1 22
23 1 SPACE SPACE 1 24
25 1 SPACE SPACE 1 26
27 1 SPACE SPACE 1 28
29 1 SPACE SPACE 1 30
31 1 SPACE SPACE 1 32
33 1 SPACE SPACE 1 34
35 1 SPACE SPACE 1 36
37 1 SPACE SPACE 1 38
39 1 SPACE SPACE 1 40
41 1 SPACE SPACE 1 42
TOTAL V-A 26533 26533 26533 79,600 VA
TOTAL AMPS 221 221 221 221 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 79.60 0.00 0.00 0.00 79.6 KVA 221 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 0.00 79.6 KVA 221 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 79.60 0.00 0.00 0.00 79.6 KVA 221 A
PANEL NOTES: PANEL OPTIONS:
a FED FROM 'UPS-B' MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE) b SEE BUSWAY DETAILS ON SHEET 145-EP-100 FOR SIZE PROVIDE WITH 200% RATED NEUTRAL
PROVIDE WITH CONTINUOUS HINGED TRIM
PANEL '146-EQ1-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 20 RK-108-1B SPEC 1,167 720 RECP TELECOM RM 108 E. RECP 20 1 2
3 3 20 ^^^ SPEC 1,167 720 RECP TELECOM RM 108 W. RECP 20 1 4
5 3 20 ^^^ SPEC 1,167 720 RECP 146-RECP-1 20 1 6
7 2 50 146-IU-1 MOTR 3,952 102 LTG LTG ROOM 108 20 1 8
9 2 50 ^^ MOTR 3,952 SPARE 20 1 10
11 2 45 146-CU-1 MOTR 2,496 SPARE 20 1 12
13 2 45 ^^ MOTR 2,496 SPARE 20 1 14
15 1 - SPACE SPACE - 1 16
17 1 - SPACE SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 8,437 5,839 4,383 18,658 VA
TOTAL AMPS 70 49 37 52 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.10 2.16 12.90 1.98 0.00 0.00 0.00 3.50 18.7 KVA 52 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.10 2.16 12.90 1.98 0.00 0.00 0.00 3.50 18.7 KVA 52 A
DEMAND LOAD IN KVA: 0.13 2.16 12.90 1.98 0.00 0.00 0.00 3.50 20.7 KVA 57 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
PANEL '148-EQ1-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 225 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-A114-1B SPEC 2,333 720 RECP TELECOM RM A114 E. RECP 20 1 2
3 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM A114 W. RECP 20 1 4
5 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM C106A E. RECP 20 1 6
7 3 30 ZP-C106A-1B SPEC 2,333 720 RECP TELECOM RM C106A W. RECP 20 1 8
9 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM F108 E. RECP 20 1 10
11 3 30 ^^^ SPEC 2,333 720 RECP TELECOM RM F108 W. RECP 20 1 12
13 3 30 ZP-F108-1B SPEC 2,333 180 RECP 148-RECP-1 20 1 14
15 3 30 ^^^ SPEC 2,333 180 RECP 148-RECP-2 20 1 16
17 3 30 ^^^ SPEC 2,333 104 LTG TELECOM RM A114A 20 1 18
19 2 50 148-IU-1 MOTR 3,952 104 LTG TELECOM RM C106A 20 1 20
21 2 50 ^^ MOTR 3,952 104 LTG TELECOM RM F108 20 1 22
23 2 50 148-IU-2 MOTR 3,952 180 RECP 148-RECP-3 20 1 24
25 2 50 ^^ MOTR 3,952 SPARE 20 1 26
27 2 50 148-IU-3 MOTR 3,952 SPARE 20 1 28
29 2 50 ^^ MOTR 3,952 SPACE - 1 30
31 2 45 148-CU-1 MOTR 2,496 SPACE - 1 32
33 2 45 ^^ MOTR 2,496 SPACE - 1 34
35 2 45 148-CU-2 MOTR 2,496 SPACE - 1 36
37 2 45 ^^ MOTR 2,496 SPACE - 1 38
39 2 45 148-CU-3 MOTR 2,496 SPACE - 1 40
41 2 45 ^^ MOTR 2,496 SPACE - 1 42
TOTAL V-A 21,620 21,620 21,620 64,860 VA
TOTAL AMPS 180 180 180 180 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.31 4.86 38.69 1.98 0.00 0.00 0.00 21.00 64.9 KVA 180 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.31 4.86 38.69 1.98 0.00 0.00 0.00 21.00 64.9 KVA 180 A
DEMAND LOAD IN KVA: 0.39 4.86 38.69 1.98 0.00 0.00 0.00 21.00 66.9 KVA 186 A
PANEL NOTES: PANEL OPTIONS:
MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)
RELOCATED PANEL 'M'
MFR/MODEL: SIEMENS I-T-E SERIES 8 VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E b 1 3 * 145-CRAC-1 MOTR 14291 14291 MOTR 145-CRAC-2 * 3 2 b b 3 3 * ^^^ MOTR 14291 14291 MOTR ^^^ * 3 4 b b 5 3 * ^^^ MOTR 14291 14291 MOTR ^^^ * 3 6 b b 7 3 25 DC-1 MISC 2736 2736 MISC DC-2 25 3 8 b b 9 3 25 ^^^ MISC 2736 2736 MISC ^^^ 25 3 10 b b 11 3 25 ^^^ MISC 2736 2736 MISC ^^^ 25 3 12 b b 13 3 15 145-PB-1 MOTR 624 SPACE - 1 14 b 15 3 15 ^^^ MOTR 624 SPACE - 1 16 b 17 3 15 ^^^ MOTR 624 CONSOLE LIGHT 20 1 18 a b 19 3 15 145-PB-2 MOTR 624 PBX ROOM LIGHTS 20 1 20 a b 21 3 15 ^^^ MOTR 624 PBX ROOM LIGHTS 20 1 22 a b 23 3 15 ^^^ MOTR 624 AC UNIT 143 20 1 24 a
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 35301 35301 35301 105,903 VA
TOTAL AMPS 294 294 294 294 A
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 89.49 10.72 16.42 0.00 0.00 0.00 105.9 KVA 294 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 89.49 10.72 16.42 0.00 0.00 0.00 105.9 KVA 294 A
DEMAND LOAD IN KVA: 0.00 0.00 89.49 10.72 16.42 0.00 0.00 0.00 116.6 KVA 324 A
PANEL NOTES: PANEL OPTIONS:
a EXISTING LOAD TO REMAIN MAIN LUGS ONLY b INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE PANEL. THE NEW CIRCUIT
BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND
SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RAITING TO MATCH THE LOWEST RATED EXISTING
DEVICE IN THE PANEL.
* 150A, 3-POLE BREAKER
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:3
A
M
EK-011
PANEL SCHEDULES - BLDG 145,
146, & 148
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
(E)PANEL '359-156'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/240V,1PH,3W ENCLOSURE: NEMA 1 100 A
TYPE: PANELBOARD VOLT-AMPS MTG: RECESSED
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 1 15 STREET LIGHTING GARAGE 358 20 2 2
3 1 20 STREET LIGHTING ^^ 20 2 4
a 5 1 20 RK-101A-1A MISC 1,920 GARAGE 359 20 2 6
7 1 20 SPARE ^^ 20 2 8
9 1 15 SPARE SPACE 20 1 10
11 1 15 SPACE SPACE 20 1 12
13 1 15 SPACE SPACE 20 1 14
15 1 15 SPACE SPACE 20 1 16
17 1 30 SPACE SPACE 20 1 18
TOTAL V-A 1,920 0 1,920 VA
TOTAL AMPS 16 0 8 A
A.I.C. RATING: 10,000
LTG RECP MOTR LG.MT MISC SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 1.92 0.00 1.9 KVA 8 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 1.92 0.00 1.9 KVA 8 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 1.92 0.00 1.9 KVA 8 A
PANEL NOTES: PANEL OPTIONS:
a INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILIBLE IN PANEL.
THE NEW CIRCUIT BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RATING TO MATCH THE LOWEST RATED DEVICE IN THE
PANEL.
100 AMP SERVICE DISCONNECT
PANEL '148-UPS1-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 3 30 ZP-A114-1A SPEC 2,333 SPARE 20 1 2
3 3 30 ^^^ SPEC 2,333 SPARE 20 1 4
5 3 30 ^^^ SPEC 2,333 SPARE 20 1 6
7 3 30 ZP-C106A-1A SPEC 2,333 SPACE - 1 8
9 3 30 ^^^ SPEC 2,333 SPACE - 1 10
11 3 30 ^^^ SPEC 2,333 SPACE - 1 12
13 3 30 ZP-F108-1B SPEC 2,333 SPACE - 1 14
15 3 30 ^^^ SPEC 2,333 SPACE - 1 16
17 3 30 ^^^ SPEC 2,333 SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 - SPACE SPACE - 1 30
31 1 - SPACE SPACE - 1 32
33 1 - SPACE SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
TOTAL V-A 7,000 7,000 7,000 21,000 VA
TOTAL AMPS 58 58 58 58 A
A.I.C. RATING: 22,000
TOTAL LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.00 21.0 KVA 58 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.00 21.0 KVA 58 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.00 21.0 KVA 58 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
DISTRIBUTION PANEL 'TDP-1'
MFR/MODEL: SQUARE 'D' TYPE I-LINE VOLTS: 277/480V,3PH,4W ENCLOSURE: NEMA 1 400 A
MTG SPACE: AS REQUIRED VOLT-AMPS MTG: SURFACE
N O
T E
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
N O
T E a 3 * PANEL 'UPSDP-1' FEDR 51033 16628 MOTR CRAC-3 80 3 a 3 * ^^^ FEDR 51033 16628 MOTR ^^^ 80 3 a 3 * ^^^ FEDR 34700 16628 MOTR ^^^ 80 3
3 70 RTU-1 MOTR 13524 1429 MISC DC-3 15 3
3 70 ^^^ MOTR 13524 1429 MISC ^^^ 15 3
3 70 ^^^ MOTR 13524 1429 MISC ^^^ 15 3
3 15 154-PB-3 MOTR 721 SPACE - 1
3 15 ^^^ MOTR 721 SPACE - 1
3 15 ^^^ MOTR 721 SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
1 - SPACE SPACE - 1
TOTAL V-A 83334 83334 67001 233,670 VA
TOTAL AMPS 301 301 242 281 A
AVAILABLE FAULT CURRENT : 22,000 A AIC RATING:
LTG REC MOTR LG MTR MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL) 0.00 0.00 92.62 12.47 4.29 0.00 0.00 0.00 96.9 KVA 117 A
CONNECTED LOAD IN KVA (BRANCH PANELS) 0.00 0.00 0.00 0.00 79.60 0.00 0.00 73.50 153.1 KVA 184 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 92.62 12.47 83.89 0.00 0.00 73.50 250.0 KVA 301 A
DEMAND LOAD IN KVA: 0.00 0.00 92.62 12.47 83.89 0.00 0.00 52.50 241.5 KVA 290 A
PANEL NOTES: PANEL OPTIONS:
a SEE ONE-LINE 1/EK-002 FOR BREAKER SIZE MAIN LUGS ONLY
(E)PANEL '147-A'
MFR/MODEL: GE A SERIES VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 225 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E a 1 1 20 SUP/LOCKER RM LTG CORR. LTG 20 1 2 a a 3 1 20 ISSUE/BRK RM LTG RECEIVING RM LTG 20 1 4 a a 5 1 20 EXTERIOR LTG BATH RM LTG/ EX FAN 20 1 6 a a 7 1 20 SUPERVISOR RECP BATH RM RECP 20 1 8 a a 9 1 20 LOCKER RM RECP BATH RM RECP 20 1 10 a a 11 1 20 CORR/EXTERIOR RECP RECEIVING RECP 20 1 12 a a 13 1 20 BREAK RM RECP ISSUE RECP 20 1 14 a a 15 1 20 BREAK RM COUNT RECP ISSUE RECP 20 1 16 a a 17 1 20 BREAK RM VENDING DOCK LEVELER-SOUTH 20 3 18 a a 19 1 20 BREAK RM REFRIGERATOR ^^^ 20 3 20 a a 21 2 50 BREAK ROOM OVEN ^^^ 20 3 22 a a 23 2 50 ^^ DOCK LEVELER-NORTH 20 3 24 a a 25 1 20 VAV CONTROL PANEL ^^^ 20 3 26 a a 27 1 20 UH-L, EF-1 ^^^ 20 3 28 a a 29 1 20 P-2, EF-2, UH-2 WATER HEATER 20 1 30 a a 31 3 35 RTU-1 P-1 20 1 32 a a 33 3 35 ^^^ P-2 20 1 34 a a 35 3 35 ^^^ MICROWAVE 20 1 36 a b 37 1 20 RK-109-1A MISC 1920 SPACE 1 38 b 39 1 20 RK-109-1B MISC 1920 SPACE 1 40
41 1 20 SPACE SPACE 1 42
TOTAL V-A 1920 1920 0 3,840 VA
TOTAL AMPS 16 16 0 11 A
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 3.84 0.00 0.00 0.00 3.8 KVA 11 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 3.84 0.00 0.00 0.00 3.8 KVA 11 A
DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 3.84 0.00 0.00 0.00 3.8 KVA 11 A
PANEL NOTES: PANEL OPTIONS:
a EXISTING LOAD TO REMAIN MAIN LUGS ONLY b INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE PANEL. THE NEW CIRCUIT
BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND
SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RAITING TO MATCH THE LOWEST RATED EXISTING
DEVICE IN THE PANEL.
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:4
A
M
EK-012
PANEL SCHEDULES - BLDGS 145,
147, 148, & 359
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
(E)PANEL '296-A'
MFR/MODEL: SIEMENS P1 VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 250 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
A M
P S
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E a 1 1 20 GARGAE DOOR 3 BAY LTG 20 1 2 a a 3 1 20 GARGAE DOOR 2 EXISTING LOAD 20 1 4 a a 5 1 20 GARGAE DOOR 1 FIRE PANEL 20 1 6 a a 7 1 20 SPARE WASHER 20 1 8 b a 9 1 20 EXISITNG LOAD LTG 20 1 10 a a 11 1 20 EXISTING LOAD EXISITNG LOAD 20 1 12 a a 13 1 20 EXISTING LOAD SIREN 40 3 14 a a 15 1 20 BUNK ROOM RECP ^^^ 40 3 16 a a 17 1 20 BUNK & CHIEF ROOM RECP ^^^ 40 3 18 a c 19 3 100 (N) PANEL '296-T1' FEDR 7615 EXISTING LOAD 20 1 20 a c 21 3 100 ^^^ FEDR 7615 LIVING ROOM RECEP 20 1 22 b c 23 3 100 ^^^ FEDR 1347 FIRE ALARM SYSTEM RECP 20 1 24 a a 25 1 20 KITCHEN REFRIGERATOR BAY 4 RECP DOOR OPENER 20 1 26 a a 27 1 20 KITCHEN RECPS BAY 4 RECP 20 1 28 a a 29 1 20 MICROWAVE EXISTING LOAD 20 1 30 a a 31 3 50 SCBA COMPRESSOR LIVING ROOM RECEP 20 1 32 b a 33 3 50 ^^^ TOOL ROOM 20 1 34 a a 35 3 50 ^^^ HEATER 20 1 36 a c 37 3 20 RK-104-1B SPEC 1167 DRYER 30 2 38 a c 39 3 20 ^^^ SPEC 1167 ^^ 30 2 40 a c 41 3 20 ^^^ SPEC 1167 HEATER 15 1 42 a
TOTAL V-A 8781 8781 2513 20,076 VA
TOTAL AMPS 73 73 21 56 A
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.50 3.5 KVA 10 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.00 0.00 12.90 1.98 0.00 0.00 0.00 3.50 16.4 KVA 51 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 12.90 1.98 0.00 0.00 0.00 7.00 19.9 KVA 55 A
DEMAND LOAD IN KVA: 0.00 0.00 12.90 1.98 0.00 0.00 0.00 5.00 19.9 KVA 55 A
PANEL NOTES: PANEL OPTIONS:
a EXISTING LOAD TO REMAIN MAIN LUGS ONLY b RELOCATED EXISTING LOAD c INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE PANEL. THE NEW CIRCUIT
BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND
SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RAITING TO MATCH THE LOWEST RATED EXISTING
DEVICE IN THE PANEL.
PANEL '296-T1'
MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A
VOLT-AMPS MTG: SURFACE
N O
T E
C
IR
C
P O
LE
SERVICE TYPE A B C TYPE SERVICE A
M
P S
P O
LE
C
IR
C
N O
T E
1 2 50 T296-IU-1 MOTR 3,952 2,496 MOTR T296-CU-1 45 2 2
3 2 50 ^^ MOTR 3,952 2,496 MOTR ^^ 45 2 4
5 3 20 RK-104-1A SPEC 1,167 180 SPARE 20 1 6
7 3 20 ^^^ SPEC 1,167 SPARE 20 1 8
9 3 20 ^^^ SPEC 1,167 SPARE 20 1 10
11 1 - SPACE SPACE - 1 12
13 1 - SPACE SPACE - 1 14
15 1 - SPACE SPACE - 1 16
17 1 - SPACE SPACE - 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 - SPACE SPACE - 1 24
25 1 - SPACE SPACE - 1 26
27 1 - SPACE SPACE - 1 28
29 1 SPACE SPACE - 1 30
TOTAL V-A 7,615 7,615 1,347 16,576 VA
TOTAL AMPS 63 63 11 46 A
A.I.C. RATING: 22,000
LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS
CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 12.90 1.98 0.00 0.00 0.00 3.50 16.4 KVA 46 A
CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A
TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 12.90 1.98 0.00 0.00 0.00 3.50 16.4 KVA 46 A
DEMAND LOAD IN KVA: 0.00 0.00 12.90 1.98 0.00 0.00 0.00 3.50 18.4 KVA 51 A
PANEL NOTES: PANEL OPTIONS:
MAIN LUGS ONLY
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:4
A
M
EK-013
PANEL SCHEDULES - BLDG T296 EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
EHED
CR
DC
K
PLAN VIEW
SECURED SIDE
UNSECURED SIDE
44"
ELEVATION VIEW
ROUTE CABLE FROM BOX BACK TO
ACCESS CONTROL PANEL. CABLE
PATHWAY SHALL BE J-HOOKS THROUGH
ACCESSIBLE CEILING AREAS AND IN
CONDUIT IN AREAS WITH INACCESSIBLE
CEILINGS. SEE SPECIFICATIONS FOR
ADDITIONAL ROUTING REQUIREMENTS.
INSTALL 1-GANG CUT-IN BOX FOR CARD
READER FLUSH MOUNT ROUGH-IN.
MOUNT CARD READER ON WALL ON
UNSECURED SIDE OF DOOR, AS SHOWN
ON PLANS. MOUNT FLUSH IN WALL. CUT
AND PATCH WALL AS REQUIRED.
CONTINUE UP TO READER CONTROLLER
JUNCTION BOX ABOVE DOOR. WHERE
NOTED IN SCHEDULE, PROVIDE MULLION
CARD READER.
ALL CONDUIT/WIRE SHALL BE
CONCEALED IN WALLS OR ABOVE
ACCESSIBLE CEILING AS MUCH AS
POSSIBLE.
ACCESS CONTROL JUNCTION BOX
INSTALLED CONCEALED WITHIN
ACCESSIBLE CEILING. WHERE CEILING
IS INACCESSIBLE, MOUNT BOX ON WALL
WITHIN NEAREST STORAGE ROOM,
JANITOR CLOSET, MECHANICAL ROOM,
ETC. JUNCTION BOXES SHALL NOT BE
INSTALLED ON WALLS WITHIN PUBLIC
SPACES.
NEW RECESSED DOOR CONTACT.
ELECTRIC KEY SWITCH ON THE
INSIDE OF THE BUILDING.
NEW ELECTRIC HINGE.
NEW ELECTRIFIED EXIT DEVICE
WITH LATCHBOLT MONITORING AND
REQUEST-TO-EXIT SWITCH.
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e
S D
/E S
E R
IE
S
D
E T
A
IL
S
R
.r v t
/2
/2
:4
:4
A
M
EK-014
POWER AND ELEVATION
SCHEMATIC FOR TR RACK
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
Project Director
LKA, CKJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
NOT TO SCALE1 CONTROLLED DOOR- SINGLE DOOR, ELECTRIFIED EXIT DEVICE
NOT TO SCALE2 TYPICAL POWER ELEVATION AND SCHEMATIC FOR A ONE RACK TR
NOT TO SCALE3 TYPICAL POWER ELEVATION AND SCHEMATIC FOR A TWO RACK TR
SHEET NOTES:
1. BUILDINGS 113, 145, 146, AND 148 WILL HAVE A CENTRALIZED UPS SYSTEM
AND WILL NOT REQUIRE RACK-MOUNTED UPS.
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
RK-102A-1A TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 40-A - 37 0.75"C,1#12,1#10 NEUT, 1#12 GND -
RK-102A-1B TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 40-A - 39 0.75"C,1#12,1#10 NEUT, 1#12 GND -
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
RK-107-1A
RK-107-1B
MASON
SHOP
102A
BREAK
ROOM
PAINT SHOP
LUMBER
STORAGE
PAINT
BOOTH
103A
OFFICE
103B
TOILET
101A
STORAGE
100B
OFFICE
100A
ELECT
100A1
LOCK SHOP
100C
CARPENTER
SHOP
(E) PANEL '40-A'
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:2
:3
A
M
040-EP-011
40-ELECTRICAL REMODEL PLAN -
FIRST FLOOR
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 40
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
EQUIPMENT SCHEDULE
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 40 FIRST FLOOR
RK-B105-1BRK-B105-1A
VAULT
B105
E
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
RK-B105-1A TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 46 - DOCK - 14 0.75"C,1#12,1#10 NEUT, 1#12 GND -
RK-B105-1B TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 46 - DOCK - 17 0.75"C,1#12,1#10 NEUT, 1#12 GND -
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:2
:3
A
M
046-EP-0B1
46-ELECTRICAL REMODEL PLAN -
BASEMENT
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 46
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 46 BASEMENT
EQUIPMENT SCHEDULE GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
RK-B102A-1B
RK-B102A-1A
STORAGE
AREA
B101
STORAGE
AREA
B100
STAIR
B000
STORAGE
AREA
B102STORAGE
AREA
B102A
E
1TYP
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
RK-B102A-1A TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 50A - 21 0.75"C,1#12,1#10 NEUT, 1#12 GND -
RK-B102A-1B TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A 50B - 9 0.75"C,1#12,1#10 NEUT, 1#12 GND -
STORAGE
201A
SAFETY
OFFICE
SAFETY
SUPERVISOR
OFFICE
201B
POST
OFFICE
VESTIBULE
RESTROOM
202A
BREAK
ROOM
VESTIBULE
POST
OFFICE
102A
POST
OFFICE
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:4
:5
A
M
050-EP-011
50-ELECTRICAL REMODEL PLAN EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 50
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 50 BASEMENT
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
EQUIPMENT SCHEDULE
SHEET NOTES:
1. PROVIDE NEW BREAKERS IN (E) PANELS FOR NEW LOADS. REMOVE
SPARE BREAKERS TO MAKE ROOM FOR NEW BREAKERS. BREAKERS
SIZES AS FOLLOWS:
RK-B102A-1A - 20A, 1P IN PANEL 50A
RK-B102B-1A - 20A, 1P IN PANEL 50B
1/8" = 1'-0"2 ELECTRICAL REMODEL PLAN - BLDG 50 FIRST FLOOR
J
OS
CR
J
053-EP-0B1
TR
TCB1
WORKOUT
AREA
B105
STORAGE
HCB1
MECH ROOM
B105A
ELEC
CLOSET
ECB1
RESTROOM
B104
TCB8
B100
UNUSED
SPACE
B100A
UNUSED
SPACE
B100A1
STORAGE
AREA
B102
STORAGE
AREA
B101
STORAGE
AREA
B103
STORAGE
AREA
B103A
STORAGE
AREA
B103B
STORAGE
B103C
STORAGE
B103D
STORAGE
B103E
STORAGE
AREA
PCB1
EM
RK-TCB1-1A
RK-TCB1-1B
53-IU-1
TYP
A
3TYP
TR
TCB1
4TYP
(E) PANEL '53-C'
53-CU-1
PAYROLL
OFFICE
CONTRACTING
OFFICE
CONTRACTING
OFFICE
CONTRACTING
OFFICE
CONTRACTING
OFFICE
CONTRACTING
OFFICE
OFFICE
WOMEN
MEN
UNUSED
SPACE
BREAK
ROOM
MSA
CUBICLES
(x6)
CONFERENCE
ROOM
OFFICE
COPIER
PRINTERS
FINANCE
OFFICE
CONTRACTING
OFFICE
114A
CONTRACTING
OFFICE
114B
OFFICE
114C
OFFICE
114DFILE
STORAGE
114E
CONTRACTING
OFFICE
114F
STORAGE
113A
VEST
C100
CORRIDOR
C101
ROOM
C102
CORRIDOR
C103
ELEC
CLOSET
107A
53-RECP-1
1TYP
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
53-IU-1 AC INDOOR UNIT - 38 - - 208 1 X D-7,9 0.75"C, 2#6, 1#10 GND INTEGRAL CONTROLLER
53-CU-1 CONDENSING UNIT - 24 - - 208 1 X C-1,3 0.75"C, 2#10, 1#10 GND INTEGRAL CONTROLLER
RK-TCB1-1A TELECOM RACK RECEPTACLE - 3500 - 208 3 N/A C-5,7,9 0.75"C, 3#10, 1#8 NEUT, 1#12 GND PROVIDE NEMA L21-20R
RK-TCB1-1B TELECOM RACK RECEPTACLE - 3500 - 208 3 N/A D-1,3,5 0.75"C, 3#10, 1#8 NEUT, 1#12 GND PROVIDE NEMA L21-20R
53-RECP-1 CONVENIENCE RECEPTACLE - - - 180 120 1 N/A D-42 0.75"C, 2#10, 1#10 GND PROVIDE WEATHERPROOF CONVENIENCE RECEPTACLE
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:0
:0
A
M
053-EP-0B1
53-ELECTRICAL REMODEL PLAN -
BASEMENT AND FIRST FLOOR
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 53
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BUILDING 53 BASEMENT
1/2" = 1'-0"3 ENLARGED ROOM - TCB1 ELECTRICAL REMODEL
1/8" = 1'-0"2 ELECTRICAL REMODEL PLAN - BUILDING 53 FIRST FLOOR
SHEET NOTES:
1. PROVIDE NEW BREAKERS IN (E) PANELS FOR NEW LOADS. REMOVE
EXISTING SPARE BREAKERS TO MAKE ROOM FOR NEW BREAKERS.
BREAKERS SIZES AS FOLLOWS:
53-IU-1 - 50A, 2P IN PANEL D
53-CU-1 - 45A, 2P IN PANEL C
RK-TCB1-1A - 30A, 2P IN PANEL C
RK-TCB1-1B - 30A, 2P IN PANEL D
53-RECP-1 - 20A, 1P IN PANEL C
TO ACCOMODATE FOR NEW BREAKERS, IN PANEL C, RELOCATE EXISTING
BREAKER AND LOAD FROM SPACE 3 TO SPACE 6.
2. PROVIDE RACEWAY AND BOXES FOR ACCESS CONTROLS SYSTEM
COMPONENTS. SEE EK-010 FOR TYPICAL DOOR DETAIL.
3. CONNECT NEW RECEPTACLES, LIGHTING, AND SWITHCES TO EXISITNG
CIRCUITS IN AREA. EXTEND CONDUIT AND CONDUCTORS TO NEW
LOCATIONS.
4. CONNECT TO EXISTING LOCAL LIGHTING CIRCUIT. EXTEND CONDUIT AND
CONDUCTORS AS NECESSARY.
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE LIGHTING LAYOUT WITH RACK AND CABLE TRAY LOCATIONS
TO PROVIDE ILLUMINATION ON EQUIPMENT PER LIGHTING DESIGN
REQUIREMENTS.
C. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
EQUIPMENT SCHEDULE
(E) PANEL '53-D'
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:0
:0
A
M
053-EP-021
53- ELECTRICAL REMODEL PLAN -
SECOND FLOOR AND ATTIC
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 53
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BUILDING 53 SECOND FLOOR
DN
J
CR
OS
J
J
TR
B102D
088-EP-011
88-CU-1 88-RECP-1
(E) PANEL '88-1'
(E) PANEL '88-4'
ELECTRIC UNIT HEATER
R
TYP
A
RK-B102D-1A
RK-B102D-1B
88-IU-1
TR
B102D
EM
3 TYP
1TYP
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
88-IU-1 AC INDOOR UNIT - 38 - - 208 1 X 88-4-18,20 0.75"C, 2#6, 1#10 GND INTEGRAL CONTROLLER
88-CU-1 CONDENSING UNIT - 24 - - 208 1 X 88-4-22,24 0.75"C, 2#10, 1#10 GND INTEGRAL CONTROLLER
RK-B102D-1A TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A 88-1-25,27,29 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
RK-B102D-1B TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A 88-4 - 17,19,21 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
88-RECP-1 CONVENIENCE RECEPTACLE - - - 180 120 1 N/A 88-4-23 0.75"C, 2#10, 1#10 GND PROVIDE WEATHERPROOF CONVENIENCE RECEPTACLE
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:1
:0
A
M
088-EP-011
088 - ELECTRICAL REMODEL PLAN EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 88
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 88 FIRST FLOOR
1/2" = 1'-0"2 ENLARGED ROOM - B102D ELECTRICAL REMODEL
SHEET NOTES:
1. PROVIDE NEW BREAKERS IN (E) PANELS FOR NEW LOADS. REMOVE
EXISTING SPARE BREAKERS TO MAKE ROOM FOR NEW BREAKERS.
BREAKERS SIZES AS FOLLOWS:
88-IU-1 - 45A, 1P IN PANEL 88-4 GENERAL ELECTRIC, AF37S
83-CU-1 - 45A, 2P IN PANEL 88-4 GENERAL ELECTRIC, AF37S
RK-B102D-1A - 20A, 3P IN PANEL 88-1 GENERAL ELECTRIC, AF37S
RK-B102D-1B - 20A, 3P IN PANEL 88-4 GENERAL ELECTRIC, AF37S
88-ACP-1 - 20A, 1P IN PANEL 88-4 GENERAL ELECTRIC, AF37S
2. PROVIDE RACEWAY AND BOXES FOR ACCESS CONTROLS SYSTEM
COMPONENTS. SEE EK-010 FOR TYPICAL DOOR DETAIL.
3. CONNECT NEW RECEPTACLES, LIGHTING, AND SWITHCES TO EXISITNG
CIRCUITS IN AREA. EXTEND CONDUIT AND CONDUCTORS TO NEW
LOCATIONS.
4. RECONNECT UNIT HEATER TO EXISTING UNIT HEATER CIRCUIT. PROVIDE
JUNCTION BOXES, CONDUIT AND WIRE AS REQUIRED.
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE LIGHTING LAYOUT WITH RACK AND CABLE TRAY LOCATIONS
TO PROVIDE ILLUMINATION ON EQUIPMENT PER LIGHTING DESIGN
REQUIREMENTS.
C. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
D. SEE TJ-004 FOR TYPICAL NEW 1&2 RACK TELECOM ROOM POWER
SYSTEMS LAYOUT.
EQUIPMENT SCHEDULE:
O S
CR
J
J
(E) PANEL 'MDP'(E) PANEL '89-A'
89-CU-2
89-RECP-2
TR
ATTIC
089-EP-011
TR
TYP
A
RK-202-1A
RK-202-1B
89-IU-1
EM
PANEL '89-N2-T1'
89-N2-T1-2
89-N2-T1-2
89-N2-T1-4
89-N2-T1-4
89-N2-T1- 14
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
89-IU-1 AC INDOOR UNIT - 38 - - 208 1 X 89-N2-T1-7,9 0.75"C,2#6,1#10 GND INTEGRAL CONTROLLER
89-CU-1 CONDENSING UNIT - 24 - - 208 1 X 89-N2-T1-11,13 0.75"C, 2#10, 1#10 GND INTEGRAL CONTROLLER
RK-202-1A TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A 89-A - 36,38,40 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
RK-202-1B TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A 89-N2-T1-1,3,5 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
89-RECP-1 CONVENIENCE RECEPTACLE - - - 180 120 1 N/A 89-N2-T1-5 0.75"C, 2#10, 1#10 GND PROVIDE WEATHERPROOF CONVENIENCE RECEPTACLE
(E)MDP
WESTINGHOUSE 'FDP'
60/2
NEW PANEL '89-N2-T1'
100A, 120/208V, 3Ø, 4W 10KAIC
1"C, 4#6, #8 GND, CU, XHHW
EXISTING FEEDER FROM BUILDING SERVICE DISCONNECT
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:1
:3
A
M
089-EP-011
BLDG 89 ELECTRICAL REMODEL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 89
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 89 FIRST FLOOR
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE LIGHTING LAYOUT WITH RACK AND CABLE TRAY LOCATIONS
TO PROVIDE ILLUMINATION ON EQUIPMENT PER LIGHTING DESIGN
REQUIREMENTS.
C. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
1/8" = 1'-0"2 ELECTRICAL REMODEL PLAN - BLDG 89 SECOND FLOOR
1/2" = 1'-0"3 ENLARGED ROOM - 202 ELECTRICAL REMODEL
SHEET NOTES:
1. PROVIDE RACEWAY AND BOXES FOR ACCESS CONTROLS SYSTEM
COMPONENTS. SEE EK-010 FOR TYPICAL DOOR DETAIL.
2. PROVIDE 60A RATED FUSES IN EXISTING FUSED SWITCH BOARD.
3. PROVIDE NEW 3Ø CIRCUIT FROM EXISTING PANELBOARD '89-A'
EQUIPMENT SCHEDULE:
NOT TO SCALE4 BUILDING 89 PARTIAL ONE-LINE DIAGRAM
J
CR
O S
090-EP-011
(E) PANEL '2'
(E) PANEL '1'(E) PANEL 'MDP'
90-CU-1
(E) PANEL 'A'
TR
102A
RESEARCH
OFFICE
EDUCATION
CLASSROOM
EDUCATION
CLASSROOM
SIMULATION
LAB
STAIR 1
ST1
CORRIDOR
C102
STORAGE
111A
RESTROOM
RESTROOM
COMPUTER
EDUCATION
CLASSROOM
115 STORAGE
MECH ROOM
OFFICE
CORRIDOR
C103
VESTIBUILE
MECH.
ROOM
KITCHEN
CORRIDOR
C101
RESTROOM
RESTROOM
OFFICE
107C
OFFICE
107B3
CONFERENCE
ROOM
107B
RECEPTIONIST
WORK AREA
VESTIBULE
107B2
OFFICE
107B1
OFFICE
107A
90-RECP-1
90-IU-1
RK-102A-1A
RK-102A-1B
TR
102A
TYP
A
EM
2TYP
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
90-IU-1 AC INDOOR UNIT - 38 - - 208 1 X A-27,29 0.75"C, 2#6, 1#10 GND INTEGRAL CONTROLLER
90-CU-1 CONDENSING UNIT - 24 - - 208 1 X A-28,30 0.75"C, 2#10, 1#10 GND INTEGRAL CONTROLLER
RK-102A-1A TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A 1-33,35,37 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
RK-102A-1B TELECOM RACK RECEPTACLE - - 3500 - 208 3 N/A A- 21,23,25 0.75"C, 3#12, 1#10 NEUT, 1#12 GND PROVIDE NEMA L21-20R
90-RECP-1 CONVENIENCE RECEPTACLE - - - 180 120 1 N/A A-22 0.75"C, 2#10, 1#10 GND PROVIDE WEATHERPROOF CONVENIENCE RECEPTACLE
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S
B L D
G
R
.r v t
/2
/2
:0
:4
A
M
090-EP-011
090 - ELECTRICAL REMODEL PLAN EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 90
Project Director
CK,LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 90 FIRST FLOOR
1/2" = 1'-0"2 ENLARGED ROOM - 102A ELECTRICAL REMODEL
SHEET NOTES:
1. PROVIDE RACEWAY AND BOXES FOR ACCESS CONTROLS SYSTEM
COMPONENTS. SEE EK-010 FOR TYPICAL DOOR DETAIL.
2. CONNECT NEW RECEPTACLES, LIGHTING, AND SWITHCES TO EXISITNG
CIRCUITS IN AREA. EXTEND CONDUIT AND CONDUCTORS TO NEW
LOCATIONS.
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE LIGHTING LAYOUT WITH RACK AND CABLE TRAY LOCATIONS
TO PROVIDE ILLUMINATION ON EQUIPMENT PER LIGHTING DESIGN
REQUIREMENTS.
C. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
EQUIPMENT SCHEDULE:
ENTRY
OFFICE
ROOM
ROOM
ROOM
ROOM
RK-102-1A
RK-102-1B
VA MEDICAL CENTER
FORT MEADE, SD
NORTH
PROJECT KEY PLAN
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
RK-102-1A TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A - 0.75"C,1#12,1#10 NEUT, 1#12 GND -
RK-102-1B TELECOM CABINET RECEPTACLE - - 1920 - 120 1 N/A - 0.75"C,1#12,1#10 NEUT, 1#12 GND -
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
5/25/22
EE-113847
B
IM
/2
V
A M e d ic a l C e n te r
F t M e a d e S
D /E
S E
R
IE
S B
L D
G
R
.r v t
/2
/2
:3
:1
A
M
110-EP-011
110-ELECTRICAL REMODEL PLAN -
FIRST FLOOR
EHRM INFRASTRUCTURE
UPGRADES
FORT MEADE, SOUTH DAKOTA
568-21-701
BLDG 110
Project Director
LKAJAM05/25/2022
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A/E:
1/8" = 1'-0"1 ELECTRICAL REMODEL PLAN - BLDG 110 FIRST FLOOR
GENERAL NOTES:
A. SEE EQUIPMENT SCHEDULE ON THIS SHEET FOR POWER REQUIREMENTS.
B. COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS
AND CONDUIT/PIPE ROUTING PRIOR TO ROUGH-IN.
EQUIPMENT SCHEDULE:
SHEET NOTES:
1. PROVIDE (2) NEW 20A, 1P CIRCUITS FROM NEAREST AVAILABLE PANEL
WITH CAPACITY. PROVIDE JUNCTION BOXES, CONDUIT AND WIRE AS
REQUIRED.
OS
J
113-EP-001
(E) PANEL 'CRITICAL DP'
PANEL '113-UPSDP-T1'
PANEL '113-EQDP-T1'
(EM) MAIN SWBD BLDG 113 (NORMAL) MAIN SWBD BLDG 113
PANEL '113-UPSB-T1'
PANEL '113-EQB-T1'
RK-B01-1A
RK-B01-1B
EM
113-IU-B
113-NB-T1-2
113-NB-T1-2
113-NB-T1-4
113-NB-T1-4
TR
B01
ID TAG EQUIPMENT DESCRIPTION ELECTRICAL DATA REQUIRES
DISCONNECT
PANEL / CIRCUIT CONDUIT / CONDUCTOR SIZE NOTES
HP AMP WATT VA VOLT Φ
113-IU-B AC INDOOR UNIT - 38 - - 208 1 X 113-EQB-T1 - 7,9 0.75"C,2#6,1#10 GND INTEGRAL CONTROLLER
113-IU-1 AC INDOOR UNIT - 38 - - 208 1 X 113-EQ1-T1 - 13,15 0.75"C,2#6,1#10 GND INTEGRAL CONTROLLER
113-IU-2 AC INDOOR UNIT - 38 - - 208 1 X 113-EQ1-T1 - 17,19 0.75"C,2#6,1#10 GND INTEGRAL CONTROLLER
113-CU-B CONDENSING…
This is the start of the file's text. The full file is on GovTribe.