ATTACHMENT 10 ADDENDUM 02 PLAN UPDATES Project XGFG182011 Dated 03 March 2022.pdf

PDF 8 MB Posted

Attached to
F-35 Add/Alter Building 510 Base Warehouse and Supply
Solicitation number
W50S9F-22-B-0002
Issued by

About this file

This solicitation document requests bids for a firm fixed-price construction contract to build a new warehouse addition and renovate existing facilities at Dane County Regional Airport in Madison, Wisconsin. Key details include:

  • The project scope includes constructing a new 5,150 square foot warehouse addition, renovating approximately 20,000 square feet of existing warehouse, and renovating around 8,150 square feet of administrative offices. Work includes minor demolition, site work, mechanical, electrical and plumbing systems upgrades, and architectural finishes.

  • The base contract line items are for renovation and new construction work. There are also three options for communication cabling/equipment, replacing existing windows, and temporary facilities.

  • The pre-bid conference will be held on-site with attendance required. The bid opening will follow standard FAR and DFARS procedures.

  • The estimated contract value is between $5-10 million. The NAICS code is 236220 with a $39.5 million size standard.

  • Award will be to the responsive and responsible lowest bidder. A small business subcontracting plan is required from the apparent low bidder. The contract duration is 365 days from notice to proceed.

View the file

Other files

File Type Posted
Bid Opening Attendance Sheet.pdf PDF
OF 1419_ABSTRACT OF OFFERS - CONSTRUCTION Signed.pdf PDF
Appendix A Base Design Guide.pdf PDF
Question and Answers 03.pdf PDF
Question and Answers 02.pdf PDF
Site Visit Attendance Sheet.pdf PDF
F35 B510 Pre-Bid Minutes 20220517.pdf PDF
Question and Answers 01.pdf PDF
Pre-Bid Slides - F-35 510.pptx PPTX presentation
ATTACHMENT 05 ADDENDUM 01 Project XGFG182011 Dated 15 January 2022.pdf PDF
ATTACHMENT 09 ADDENDUM 02 SPEC UPDATES Project XGFG182011 Dated 03 March 2022.pdf PDF
ATTACHMENT 04 LBP AND ASBESTOS RESULTS.pdf PDF
ATTACHMENT 06 ADDENDUM 01 SECTION 11 13 19.13.pdf PDF
ATTACHMENT 16 SFS FORM 12.xlsx XLSX spreadsheet
ATTACHMENT 03 GEOTECHNICAL RESULTS Project.pdf PDF
ATTACHMENT 02 DRAWINGS Project XGFG182011 Dated September 2021 Instructions.pdf PDF
ATTACHMENT 01 PLANS AND SPECIFICATIONS Project XGFG182011 Dated September 2021.pdf PDF
ATTACHMENT 13 SINGLE SOURCE DETERMINATION ANDOVER.pdf PDF
ATTACHMENT 07 ADDENDUM 01 GC003 STAGING AND LAYDOWN PLAN.pdf PDF
W50S9F-22-B-0002.pdf PDF
ATTACHMENT 15 SINGLE SOURCE DETERMINATION MONACO.pdf PDF
ATTACHMENT 14 SINGLE SOURCE DETERMINATION MARSHALL BEST.pdf PDF
ATTACHMENT 11 ADDENDUM 03 Project XGFG182011 Dated 03 March 2022.pdf PDF
ATTACHMENT 08 ADDENDUM 02 Project XGFG182011 Dated 03 March 2022.pdf PDF
ATTACHMENT 12 ADDENDUM 03 SECTION 08 34 73 SOUND CONTROL DOOR ASSEMBLIES.pdf PDF
ATTACHMENT 17 PREBID CONFERENCE AND SITE VISIT INSTRUCTIONS.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAN

SS

WV

WVWV

WV

WV

SAN

POST

AGPOST

POST

POST

BLDG

AG BLDG

WV

BLDG

AG

AGAG BLDG

BLDG

AG

SAN

SAN

BLDG

BLDGBLDG

BLDG

WV

GV

SAN

UT

BLDG

POST

AGPOSTPOST

POST

AGPOST

UT

BLDGBLDG

POST

POST

BLDG

A/C

UT

POST BLDG

A/CA/C

BLDG

BLDGBLDG

BLDGBLDG

POSTBLDG

SS

SS

SS

SS

SS

SSSSSS

E

E

G

E

E

E E

E

EE

SAN

SAN

SAN

SAN

SAN

SA

N

SA

N

SA

N

SA

N

SA

N

SANSANSAN

SAN SAN SAN

SAN SAN SAN

G G

G G

G G

G

G

E

EE

WW

W

W

W

W

W

W W

SAN SAN SAN SAN

SAN SAN SAN

T

T T

T

T

T

T

T T

T

W W

W

W

W

E

E

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SSSSSSSSSSSSSS

STAGING AREA

BUILDING 510

H O

FF

M

AN

S

T.

BECKER ST.

BENSON ST.

TEMPORARY ADMIN

TRAILER. SEE NOTE 3.

TEMPORARY ALASKAN

TRAILER PROVIDED BY

GOVERNMENT. SEE NOTE 3.

TEMPORARY

READINESS TRAILER.

SEE NOTE 3.

XGFG182011

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4 sheets

127591 date detailed checkeddesigned ofsheet project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

SYM DATE DESCRIPTION APR

ISSUED FOR BID

F-35 ADAL B510

WAREHOUSE AND SUPPLY

A1 STAGING AND LAYDOWN PLAN

SCALE: 1"=20'

N

NOTES:

1. SEE CIVIL LEGEND ON GC002. SEE LOCATION

PLAN AND VICINITY MAP ON GC001.

2. COORDINATE FINAL STAGING AREA WITH

CONTRACTING OFFICER.

3. TEMPORARY ELECTRICITY, COMMUNICATIONS,

AND PORTABLE RESTROOM FACILITIES ARE

REQUIRED. COORDINATE CONNECTIONS FOR

TEMPORARY UTILITIES WITH THE CONTRACTING

OFFICER, AND MG&E FOR ELECTRICAL

SERVICES.

20' 40'0

STAGING AREA

LEGEND:

STAGING AND LAYDOWN PLAN

GC003 1

XX -

127591GC003-B510.DWG

02-08-2021 C. FRANZEN

S. WAGNER M. SCHRAEDER

0 ISSUED FOR BID09/17/2021

1 ADDENDUM 0102/22/2022

TOC

100' - 0"

MQ

TOW EL 118' - 0"

57' - 2" 7' - 0"

8' - 4"

OPNG

5' - 0" 8' - 8"

OPNG

14' - 0"

OPNG

3' - 4"

2"

3' - 10"

OPNG

5' - 0"

O P

N G

"O

P N

G

TOC EL 92' - 0"

12" CMU

TOW EL 121' - 8"

8" CMU

N1

N2

N3

N4 BEHIND, TYP

N5

A2

A1

E1

E2

E6

E3

E5

E8

E7

N7 BEHIND

A4

A6 A6

M.3

10"

O P

N G

L-2

L-2L-2

L-4

J -4

J -4

J -1

J -1

J -2

J -2

J -2

J -2

TOC

100' - 0"

5 6.13.9

40' - 0" 40' - 0"

TOC EL 92' - 0"

N1

N2

N3

N5

12" CMU

8" CMU

TOW EL 121' - 8"

TOW EL 118' - 0"

N7 BEHIND

1/2" / 1'-0" 1/2" / 1'-0"

TOC

100' - 0"

M Q

57' - 2"7' - 0"

10"

TOC EL 92' - 0"

TOW EL 118' - 0"

E1

E2

E4

E3

E5

E8

E7

N1

N2

N3

N4 BEHIND, TYP

N5

12" CMU

8" CMU

TOW EL 121' - 8"

TOW EL 118' - 0"

N7 BEHIND

M.3

7' - 0"

TOC EL 93' - 4"

TOC

100' - 0"

344.1 3.1

8' - 0"

OPNG

7' - 4"

OPNG

3' - 4"

1' - 8" 18' - 6" 1' - 11"

TOC EL 109' - 6"

A1

N10

N11

N1

E3 TYP

E1 TYP

E5

N13

O P

N G

A3

TOW EL 107' - 4"

N12

J

J

TOC

100' - 0"

344.1 3.1

TOC EL 109' - 6"

1' - 8" 18' - 6" 1' - 11"

TOC EL 98' - 8"

N10

N11

N1

E3

E1

E5

N13

N14

N15

TOW EL 108' - 8"

N16 BEYOND

TOC

100' - 0"

3 4 4.13.1

1' - 11" 18' - 6" 1' - 8"

TOC EL 109' - 6"

TOC EL 98' - 8"

N11

N1

E3

E1

E5

N14

N15

TOW EL 108' - 8"

N16 BEYOND

TOC

100' - 0"

GG.7 F.6

N11

N12

N16

N15

TOW EL 109' - 6"

TOC EL 108' - 8"

TOC EL 98' - 8"

5' - 8"14' - 8"

N16

TYP

TYP

N13 TYP

TOC

100' - 0"

FG E D.6G.7 F.6

OPNG

6' - 4"3' - 0"

OPNG

4' - 0"3' - 0"

8' - 10"20' - 0"14' - 4"5' - 8"14' - 8"

O P

N G

TOC EL 109' - 6"

TOC EL 98' - 8"

A4 N11

N1

N14

E3

E1

N15

N10

A1 A1

E9 E9

E9

TOW EL 108' - 8"

O P

N G

E.6

N12

L-2

J -2

J -2

TOC

100' - 0"

344.1 3.1

1' - 8" 18' - 6" 1' - 11"

N10

N11

N1

E3

TYP

E1

E5

N13

N14

TOW EL 108' - 8"

TOC EL 109' - 6"

S c a le F o r

M ic ro fi lm in g

In c h e s

M il lim e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD

BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9400 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

CMU AND CONCRETE WALL ELEVATIONS -

NEW

XGFG182011

S-201

09/17/2021

S. BADE W. BAILEY

D. BRICE

SCALE: 3/16" = 1'-0"A1

GRID LINE 6.1 CMU WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"B1

GRID LINE Q CMU WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"A3

GRID LINE 3.9 CMU WALL ELEVATION - NEW

0 4' 8' 12'

0 4' 8' 12'0 4' 8' 12'

NOTES:

1. SEE DRAWING S-121 FOR NOTES.

KEYED NOTES:

1. SEE DRAWING S-121 FOR KEYED NOTES.

SCALE: 3/16" = 1'-0"D1

GRID LINE D.6 CMU WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"D3

GRID LINE F.6 CONCRETE WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"D5

GRID LINE G.7 CONCRETE WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"B4

GRID LINE 3.1 CMU AND CONCRETE WALL ELEVATION - NEW

SCALE: 3/16" = 1'-0"C4

GRID LINE 4.1 CMU AND CONCRETE WALL ELEVATION - NEW

0 4' 8' 12' 0 4' 8' 12' 0 4' 8' 12'

0 4' 8' 12'

0 4' 8' 12'

SCALE: 3/16" = 1'-0"D2

GRID LINE E.6 CONCRETE WALL ELEVATION - NEW

0 4' 8' 12'

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02

TOC

6.1 3.9

80' - 0"

1/2" / 1'-0"1/2" / 1'-0"

40' - 0"40' - 0"

RIDGE

8" CMU

12" CMU

TOW EL 121' - 8"

TOW EL 118' - 0"

TOC EL 92' - 0"

N2TYP

N4

N1TYP

N3TYP

N5

N6

N7

A1TYP

A2

A3TYP

C1

S-511

TYP

D3

S-512

BOS EL 119' - 7 15/16"

N10

D1

S-512

TYP

TOC

100' - 0"

M Q

64' - 2"

TOW EL 121' - 8"

TOW EL 118' - 0"

N2

N4

N1

N3

N5

N6

N7

A1

A2

TYP

E2

E4

E1

E3

E5

E6

E7

A3

TOC EL 92' - 0"

M.3

11 SPA @ 4' - 10"

53' - 2"4' - 0"5' - 8"

TOS EL 119' - 7 239/256"

N10N10

N11

N9

N8

TOC EL 98' - 6"

C1

S-512

A3

S-511

D5

S-512

C2

S-511

S c a le F o r

M ic ro fi lm in g

In c h e s

M il lim e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD

BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9400 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

NEW ADDITION BUILDING SECTIONS

XGFG182011

S-301

09/17/2021

S. BADE W. BAILEY

D. BRICE

SCALE: 1/4" = 1'-0"A1

BUILDING SECTION

SCALE: 1/4" = 1'-0"C1

BUILDING SECTION

0 2' 4' 8'

0 2' 4' 8'

NOTES:

1. SEE DRAWINGS S-001 & S-002 FOR GENERAL NOTES, LEGEND & ABBREVIATIONS.

2. SEE DRAWING S-501 THROUGH S-504 FOR STANDARD CONCRETE, MASONRY,

ROOF DECK & JOIST DETAILS.

3. MASONRY DIMENSIONS ARE NOMINAL, GENERAL CONTRACTOR COORDINATE

WITH ARCHITECTURAL DRAWINGS & FINAL CMU LAYOUT.

4. SEE OTHER DISCIPLINE DRAWINGS FOR LOCATIONS OF PIPE, DUCT, AND CONDUIT

PENETRATIONS THROUGH NEW CONSTRUCTION.

5. COORDINATE UTILITIES WITH FOUNDATIONS. CONTRACTOR RESPONSIBLE FOR

STEPPING FOUNDATIONS WHERE REQUIRED.

KEYED NOTES (EXISTING):

E1 EXISTING CONCRETE WALL FOOTING.

E2 EXISTING CONCRETE FOUNDATION WALL.

E3

E4

EXISTING CMU WALL.

E5

EXISTING CMU WALL PILASTER.

E6

E7

EXISTING SLAB-ON-GRADE, SEE PLANS FOR ELEVATION.

KEYED NOTES (NEW CONSTRUCTION):

N1 NEW REINFORCED CONCRETE WALL FOOTING PER PLAN.

N2 NEW 12" THICK REINFORCED CONCRETE FOUNDATION WALL PER PLAN.

N3 NEW 12" NOMINAL REINFORCED CMU WALL PER PLAN.

KEYED NOTES (INTERDISCIPLINE):

A1

A2

N5

N4

NEW STEEL ROOF JOIST PER PLAN.

NEW 8" NOMINAL REINFORCED CMU PARAPET ABOVE JOIST BEARING PER PLAN. EXISTING STEEL AND JOIST ROOF FRAMING.

EXISTING METAL DECK, ELEVATION VARIES.

N6

NEW 20 GAGE WIDE RIB METAL ROOF DECK PER PLAN.

NEW 8" REINFORCED CONCRETE SLAB-ON-GRADE PER PLAN.

N7

METAL WALL PANEL, SEE ARCHITECTURAL DRAWINGS.

MEMBRANE ROOF SYSTEM, SEE ARCHITECTURAL DRAWINGS.

A3 PAVEMENT OR FINISHED GRADE, SEE CIVIL DRAWINGS.

NEW STEEL ROOF FRAMING PER PLAN.N10

NEW HSS12X12X5/8 PER PLAN.N11

NEW REINFORCED CONCRETE PEDESTAL PER PLAN.N8

NEW REINFORCED CONCRETE COLUMN FOOTING PER PLAN.N9

NEW CMU PILASTER PER PLAN.N12

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02

DN

W

J MK.5

6.1

3.9

Q

30' - 0" 30' - 0" 64' - 2"

EXISTING RAMP

EXISTING LOADING

DOCK

STORAGE

WAREHOUSE

WAREHOUSE

WAREHOUSE

COLLATERAL

STORAGE

151A

126B

154A

154B

F .V

F .V

24' - 8" 36' - 0" 3"

M1CA

11' - 4"

2' - 0"

150A 150B

INFILL SLAB,

RE: STRUCT.

3' - 3" 8' - 9" 3' - 6" 12' - 0" 5' - 9"

A-201

D1

A-201

C3

A-202

B1

A-201

C1

EXP. JT.

EXP. JT.

D4

A-412

A-202

B5

A1

A-312 A1

A-314

A2

A-314

17' - 4" 3' - 6" 7' - 0" 13' - 4"

L01 L01

DOCK LEVELER AND

DOCK BUMPERS

A-341

A4

A-341

A1M1CA

M1CA

M1CA

A2

A-313

1' - 0"

M1CA

3 SIDES

6.5

RAMP SLOPE

RE: STRUCT

EXISTING DOCK

LEVELER

A2

A-315

ABOVEABOVE

B1

A-352

PLAN

NORTH

KEY PLAN

B C

A

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

GROUND FLOOR PLAN - AREA C

XGFG182011

127591_B510_A_CENTRAL

A-103

03/01/22

S. WILLIAMSON M. TOLBERT

S. WILLIAMSON

SCALE 1/8" = 1'-0"

B1

GROUND FLOOR PLAN - AREA C

0 4' 8' 16'

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID MT

1 03/01/2022 ADDENDUM 02 MT

GROUND FLOOR

T.O. LOW JOIST

110' - 10 1/2"

T.O. JOIST

120' - 2 1/2"

2 3 7

D1

A-301

2.2 6.13.9 4.1

INSULATED METAL PANEL,

R-14 MIN.

EXISTING EIFS

FACADE TO REMAIN

EXISTING EIFS

FACADE TO REMAIN

PREFINISHED METAL

COPING

PREFABRICATED GALV.

STEEL STAIR AND

RAILINGS

EQ 10' - 0" TYP EQ

3.1 6.5

GROUND FLOOR

100' - 0"

A

T.O. JOIST

120' - 2 1/2"

GHJM K.5 B.1B.5C.2C.8D.2D.8E.4E.9

C1

A-301

C3

A-301

Q D.7F.6G.7

INSULATED METAL

PANEL, R-14 MIN.

154A154B 148A

EXISTING EIFS

FACADE TO REMAIN

23' - 4"20' - 0"

PREFINISHED

ALUMINUM SCUPPER

AND DOWNSPOUT

PREFINISHED METAL

COPING

PREFABRICATED GALV.

STEEL STAIR AND

RAILINGS

PREFABRICATED GALV.

STEEL STAIR AND

RAILINGS

T Y

P

3' - 7"

10' - 0" TYP 10' - 0"

EJ

INFILL WALL WITH INSULATED METAL PANEL,

R-19 MIN. ON COLD-FORMED METAL FRAMING.

OUTSIDE FACE OF METAL PANEL TO ALIGN

WITH FACE OF ADJACENT EIFS FINISH.

L01 L01

DOCK LEVELER AND

DOCK BUMPERS

10' - 0" 10' - 0"

GROUND FLOOR

100' - 0"

T.O. JOIST

120' - 2 1/2"

C1

A-301

Q

INSULATED METAL

PANEL, R-14 MIN.

23' - 4" 20' - 0"

PREFINISHED

ALUMINUM SCUPPER

AND DOWNSPOUT

PREFINISHED METAL

COPING

EJ

T Y

P

3' - 7"

10' - 0" TYP10' - 0"

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

EXTERIOR BUILDING ELEVATIONS - BASE

BID

XGFG182011

127591_B510_A_CENTRAL

A-201

03/01/22

S. WILLIAMSON M. TOLBERT

S. WILLIAMSON

SCALE 3/32" = 1'-0"

C3

EAST ELEVATION - BASE BID

SCALE 3/32" = 1'-0"

D1

NORTH ELEVATION - BASE BID

SCALE 3/32" = 1'-0"

C1

SOUTH ADDITION ELEVATION - BASE BID

0 8' 16' 24'

0 8' 16' 24' 0 8' 16' 24'

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID MT

1 03/01/2022 ADDENDUM 02 MT

GROUND FLOOR

C1

A-412

EXISTING LOADING

DOCK

148A

INSULATED METAL

PANEL, R-19 MIN. ON

COLD-FORMED METAL

FRAMING. OUTSIDE

FACE OF METAL PANEL

TO ALIGN WITH FACE OF

ADJACENT EIFS FINISH.

PREFAB ALUM. STAIR

AND RAILINGS

B1

A-622

A3

A-412

SIM

OPP

B3

A-352

D1

A-622

EXISTING E.F.I.S.

SYSTEM

GROUND FLOOR

100' - 0"

44.1

REMOVABLE GUARD

RAILS AT EDGE OF

CONCRETE CAP

SENSITIVE

UNCLASSED

STORAGE

WAREHOUSE

C2

A-411

GROUND FLOOR

100' - 0"

T.O. LOW JOIST

110' - 10 1/2"

CHANGING ROOM

INSULATED METAL

PANEL, R-19 MIN. ON 4"

COLD-FORMED METAL

FRAMING

107' - 4"

EXISTING SOFFIT

A2

A-352

B2

A-352

GROUND FLOOR

100' - 0"

EXISTING LOADING

DOCK

EXISTING E.F.I.S.

SYSTEM

INSULATED METAL

PANEL, R-19 MIN. ON

COLD-FORMED METAL

FRAMING. OUTSIDE

FACE OF METAL PANEL

TO ALIGN WITH FACE OF

ADJACENT EIFS FINISH.

A3

A-352

B3

A-352

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

WALL SECTIONS

XGFG182011

127591_B510_A_CENTRAL

A-312

03/01/22

S. WILLIAMSON M. TOLBERT

S. WILLIAMSON

SCALE 3/4" = 1'-0"

A3

WALL SECTION

0 1' 2' 3'0 1' 2' 3'

SCALE 3/4" = 1'-0"

B5

WALL SECTION

SCALE 3/4" = 1'-0"

B4

WALL SECTION

SCALE 3/4" = 1'-0"

A1

WALL SECTION

0 1' 2' 3' 0 1' 2' 3'

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID MT

1 03/01/2022 ADDENDUM 02 MT

CONTINUOUS 22 GA PRE-FINISHED

PARAPET COPING

CONTINUOUS 22 GA METAL OUTSIDE

HOLD DOWN CLEAT

CONTINUOUS SEALANT OVER

BACKER ROD

EXTERIOR GLASS MAT

SHEATHING

ROOFING MEMBRANE -

RETURN UNDER COPING

3/8" DIAMETER GALVANIZED

CONCRETE ANCHORS @ 1'-6" O.C.

CONTINUOUS TREATED 2x2

TREATED WOOD BLOCKING

CONTINUOUS 1.5" RIGID INSULATION

TERMINATE ROOFING MEMBRANE

SLOPE

TIE NEW EPDM INTO EXISTING

EPDM ROOF SYSTEM

METAL DECK, GALV. AND

PAINTED; RE: STRUCT.

6" STEEL CHANNELS;

RE: STRUCT. FOR

ATTACHMENT TO CMU

CMU WALL; RE: FLOOR

PLANS FOR PARTITION TYPE

CONT. BENT PLATE

RE: STRUCT.

T.O. STEEL

112' - 8"

GROUND FLOOR

100' - 0"

CONCRETE WALL;

RE: STRUCTURAL

GALVANIZED METAL FLASHING

PREFINISHED METAL PANEL

CLOSURE TRIM

INSULATED METAL PANEL, R-19 MIN.

OUTSIDE FACE OF METAL PANEL TO

ALIGN WITH FACE OF ADJACENT

EIFS FINISH.

EXTEND DAMPPROOFING 12" UP

WALL FACE MIN.

COLD-FORMED METAL FRAMING

EXISTING WALL

INSULATED METAL PANEL, R-19 MIN.

OUTSIDE FACE OF METAL PANEL TO

ALIGN WITH FACE OF ADJACENT

EIFS FINISH.

CONTINUOUS SEALANT

COLD-FORMED FRAMING ANCHORED

TO EXISTING WALL ABOVE

EXISTING STRUCTURAL FRAMING

PRE-FINISHED METAL FLASHING

PRE-FINISHED METAL PANEL

CLOSURE TRIM

GROUND FLOOR

100' - 0"

4" COLD-FORMED FRAMING ANCHORED

TO EXISTING CONCRETE SLAB

5/8" GYPSUM BOARD

SCHEDULED BASE

CONTINUOUS BED OF SEALANT

INSULATED METAL PANEL, R-19 MIN.

CONTINUOUS VAPOR BARRIER

EXISTING EIFS SOFFIT - CUT BACK

AS SHOWN TO ALLOW NEW METAL

WALL FRAMING ATTACHMENT

4" COLD-FORMED FRAMING ANCHORED

TO EXISTING FRAMING ABOVE

CONTINUOUS SEALANT

5/8" GYPSUM BOARD TO 6" ABOVE CEILING

SUSPENDED ACOUSTICAL CEILING -

RE: REFLECTED CEILING PLANS

FILL GAP WITH BATT INSULATION

PREFINISHED METAL PANEL

CLOSURE TRIM

INSULATED METAL PANEL, R-19 MIN.

CONT. SEALANT

ISOLATION STRIP

CONCRETE FLOOR

SLAB, RE: STRUCT.

VAPOR BARRIER;

RETURN UP SLAB EDGE

GRANULAR FILL

1/2"

EXISTING CMU WALL

EXISTING WALL

INSULATED METAL PANEL,

R-19 MIN.

CONTINUOUS SEALANT

COLD-FORMED FRAMING

PRE-FINISHED METAL

PANEL CLOSURE TRIM

OUTSIDE FACE OF METAL

PANEL TO ALIGN WITH FACE

OF ADJACENT EIFS FINISH.

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

ISSUED FOR BID

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

SECTION DETAILS

XGFG182011

127591_B510_A_CENTRAL

A-352

03/01/22

S. WILLIAMSON M. TOLBERT

B. NEEDLE

SCALE 6" = 1'-0"

C2

COPING DETAIL

0 1" 2" 4"3"

SCALE 3" = 1'-0"

C5

LID EDGE DETAIL

0 3" 6" 9"

SCALE 3" = 1'-0"

A3

INFILL BASE DETAIL

0 3" 6" 9"

SCALE 3" = 1'-0"

B3

INFILL HEAD DETAIL

0 3" 6" 9"

0 3" 6" 9"

SCALE 3" = 1'-0"

A2

WALL BASE DETAIL

0 3" 6" 9"

SCALE 3" = 1'-0"

B2

WALL HEAD DETAIL

SCALE 3" = 1'-0"

D5

ISOLATION STRIP AT NEW ADDTION

0 3" 6" 9"

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID MT

1 03/01/2022 ADDENDUM 02 MT

SCALE 3" = 1'-0"

B1

INFILL PLAN DETAIL

0 3" 6" 9"

J K L M N P Q

M A

T C

H L

IN

E S

E E

S H

E E

T M

-1 F

O R

C O

N T

IN

U

A T

IO

N

MATCHLINE SEE SHEET M-111 FOR CONTINUATION

UH-110

UH-111

UH-112 UH-113

UH-114

UH-115

UH-116

UH-118UH-117

UH-119

UH-120 UH-121

24"x24" EA UP

TO REF-103

24"x24" EA UP

TO REF-104

24"x24" EA UP

TO REF-105

20"x16" SA

15' - 4" BOD EL

16"x14" SA

16' - 2" BOD EL

20"x20" SA

15' - 2" BOD EL

25"x23" SA UP

TO MAU-101

30"x30" EA UP

TO REF-106

30"x30" EA UP

TO REF-107

18"x18" EA

16' - 6" BOD EL

18"x18" EA

(4)730-24"x16"

EA-J

18"x18" EA

16' - 8" BOD EL

18"x18" EA

18"x18" EA

16' - 8" BOD EL

18"x18" EA

20"x18" EA

15' - 9" BOD EL

(4)925-30"x16"

EA-J

20"x18" EA

20"x18" EA

16' - 8" BOD EL

(2)360-12"x10"

SA-B

580-18"x12"

SA-B

(4)925-30"x16"

EA-J

(4)730-24"x16"

EA-J

(4)730-24"x16"

EA-J

60"x36" OA60"x36" OA

OA LOUVER OA LOUVER

MM

CF-109

CF-110

CF-111 CF-112

"x

S A

165-8"x8"

SA-B

M

CF-105

CF-106

CF-108CF-107

1 1

2CD-24

M CD-08

CD-13 CD-14

MM CD-12CD-11

M

CD-09

MCD-10

20"x18" EA

20"x20" SA

15' - 2" BOD EL

UH-124

UH-125

UH-126

UH-127

20"x16" SA

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

NOT FOR

CONSTRUCTION

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

HVAC PLAN - AREA C

XGFG182011

M-113

01/20/21

C. DAZE R. WEAVER

B. POOLE

1/8" = 1'-0"A3

GROUND FLOOR - HVAC PLAN AREA C

GENERAL NOTES:

1.

2.

SEE SHEET M-001 FOR NOTES, LEGEND, SYMBOLS

AND ABBREVIATIONS.

SEE HVAC PIPING PLANS FOR THERMOSTAT AND

SWITCH LOCATIONS.

KEYED NOTES:

COORDINATE LOCATION OF DESTRATIFICATION

FAN WITH WAREHOUSE SHELVING LAYOUT.

LOCATE FANS IN WAREHOUSE AISLES.

EXISTING LOUVER AND MOTORIZED DAMPER.

WALL OPENING FOR DUCT SHALL BE LESS THAN 96

SQ. IN. IN TOTAL AREA.

8'4' 16'0

SCALE: 1/8"=1'-0"

PLAN NORTH

PLAN

NORTH

KEY PLAN

B

A

C

1 1

ROOM SCHEDULE - AREA C

Number Name

148 EXISTING LOADING DOCK

149 EXISTING RAMP

150 STORAGE

151 COLLATERAL STORAGE

152 WAREHOUSE

153 WAREHOUSE

154 WAREHOUSE

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02 CD

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

NOT FOR

CONSTRUCTION

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

MECHANICAL SCHEDULES

XGFG182011

M-601

01/20/21

C. DAZE R. WEAVER

B. POOLE

AIR HANDLING UNIT SCHEDULE (AHU & MAU) 1/3

TAG NO. LOCATION

ALTITUDE

(FT)

MAX.

AIRFLOW

(CFM)

MIN.

AIRFLOW

(CFM)

OUTSIDE

AIRFLOW

(CFM)

EXTERNAL

STATIC

PRESSURE

(IN. W.C.)

INTERNAL

STATIC

PRESSURE

(IN. W.C.)

TOTAL

STATIC

PRESSURE

(IN. W.C.)

SUPPLY FAN SUPPLY FAN MOTOR

MAX

BHP

OUTLET

VELOCITY

(FPM)

FAN

RPM TYPE

WHEEL

DIAMETER

(IN.)

VOLUME

CONTROL MOTOR HP

MOTOR

RPM

MOTOR

TYPE

AHU-101 128 - EXISTING MECH 886 9,000 2,660 1,600 3.6 2.95 6.55 15.6 1300 2000 DDP 24.5 VFD 20 1800 ODP

MAU-101 ROOF 886 2,250 2,250 2,250 0.5 0.69 1.19 0.79 1000 1724 DIRECT DRIVE 15 NONE 1 1800 ODP

AIR HANDLING UNIT SCHEDULE (AHU & MAU) 2/3

TAG NO. TYPE

COOLING COIL HEATING COIL

TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

EAT DB

(°F)

EAT WB

(°F.) LAT DB (°F)

LAT WB

(°F)

MAX. FACE

VELOCITY

(FPM)

MIN.

ROWS /

MAX. FPI

HEATING

AIRFLOW

(CFM) COIL TYPE

AIRSIDE HYDRONIC

CAPACITY

(MBH)

EAT (DEG

F)

LAT (DEG

F)

ROWS /

FPI MAX

EWT (DEG

F)

LWT (DEG

F)

FLUID

FLOW

(GPM)

MAX WATER

PRESSURE

DROP (FT)

AHU-101 DIRECT EXPANSION 400.6 251.7 78.5 66.8 53 52.4 500 6 / 8 3,000 HYDRONIC 110 24 60 1 / 7 160 120 5.8 1.00

MAU-101 NONE 0 0 87 73 87 73 0 N/A 2,250 NATURAL GAS 175 -5 65 N/A 0 0 0.0 0.00

AIR HANDLING UNIT SCHEDULE (AHU & MAU) 3/3

TAG NO.

PRE-FILTER FINAL FILTER

MCA VOLT PHASE

APPROX. UNIT

WEIGHT (LBS) NOTESTYPE

MERV

RATING

DIRTY PRESSURE

DROP

(IN. W.C.) TYPE

MERV

RATING

DIRTY PRESSURE

DROP

(IN. W.C.)

AHU-101 PLEATED 8 1 PLEATED 13 1 72 208 3 2750 1,3,4,5,6

MAU-101 NONE 0 0 PLEATED 8 0.6 7.7 208 3 1250 2,3,7,8,9,10

NOTES:

1. PROVIDE WITH MANUFACTURER'S DISCONNECT, VFD, AND SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.

2. PROVIDE WITH MANUFACTURER'S DISCONNECT, STARTER, AND SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.

3. PRESSURE DROPS ASSOCIATED WITH DIRTY FILTERS, COILS, ETC. SHALL BE INCLUDED IN THE TOTAL INTERNAL STATIC CALCULATION BY THE UNIT

MANUFACTURER. (NOT INCLUDED IN EXTERNAL STATIC PRESSURE SCHEDULED.)

4. HEATING WATER OPERATING FLUID IS 40% PROPYLENE GLYCOL.

5. PROVIDE AHU WITH INTEGRAL RETURN AIR DAMPER.

6. PROVIDE AHU WITH MANUFACTURER'S 6" HIGH BASE FRAME.

7. PROVIDE MAU WITH MODULATING INDIRECT FIRED NATURAL GAS BURNER WITH MINIMUM 8:1 TURNDOWN.

8 PROVIDE MAU WITH WEATHERHOOD AND ALUMINUM BIRD SCREEN WITH INTEGRATED INSULATED DAMPER ON OUTSIDE AIR INTAKE.

8. PROVIDE MAU WITH ROOF CURB AND EXTENDED BASE FRAME FOR TOTAL 14 INCH RISE ABOVE ROOF.

9 OUTDOOR UNIT

CONDENSING UNIT SCHEDULE (CU)

TAG NO. SERVICE

COOLING

CAPACITY

(BTU/H)

COMPRESSOR

TYPE

MIN.

EFFICIENCY

(EER)

RATED

OUTDOOR DB

(°F)

REFRIGERANT

TYPE

UNIT ELECTRICAL

WEIGHT

(LBS)

SIZE

(H X L X W) (IN) NOTESVOLT PH. MOP

CU-101 AHU-101 400,000 SCROLL 11.4 90 R-410A 208 3 175 2000 75 X 90 X 60 1,2

CU-102 DSS-1 18,000 SCROLL 14 95 R-410A 208 1 20 125 28 X 34 X 16 1,3,4

NOTES:

1. SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.

2. MANUFACTURER PROVIDED DISCONNECT.

3. DISCONNECT PROVIDED PER DIVISION 26.

4. PROVIDE POWER AND CABLING TO PAIRED INDOOR UNIT.

HOT WATER BOILER SCHEDULE (HWB)

TAG NO. LOCATION TYPE

ALTITUDE

(FT.)

PRESSURE

RATING

(PSIG) FUEL SOURCE

NOMINAL

BURNER

INPUT

(MBH)

MIN.

GROSS

OUTPUT

(MBH)

AHRI

EFFICIENCY

(%) FLUID

DESIGN

FLOW

(GPM)

LTW

(°F)

EWT

(°F)

MAX. WPD

(FT. W.C.) MCA VOLTS PHASE NOTES

HWB-101 128 - EXISTING MECH CONDENSING 886 125 NATURAL GAS 1000 850 94 40% PROPYLENE GLYCOL 65 160 130 15 20 120 1 1,2,3,4,5

HWB-102 128 - EXISTING MECH CONDENSING 886 125 NATURAL GAS 1000 850 94 40% PROPYLENE GLYCOL 65 160 130 15 20 120 1 1,2,3,4,5

NOTES:

1. PROVIDE CONDENSATE NEUTRALIZATION KIT.

2. PROVIDE WITH GAS PRESSURE REGULATING VALVE.

3. MINIMUM TURN DOWN RATION SHALL BE 5:1.

4. DISCONNECT PER DIV. 26.

5. PROVIDE CONTROLS WITH INTERFACE TO DDC SYSTEM VIA BACNET PROTOCOL.

VARIABLE AIR VOLUME BOX SCHEDULE (VAV)

TAG NO. TYPE

MAX DESIGN

AIRFLOW

(CFM)

MIN DESIGN

AIRFLOW

(CFM)

HEATING COIL VAV BOX

INLET

DIAMETER

(IN.)

MIN.

INLET

PRESS

(IN. W.C.)

SOUND

LEVEL NOTES

MAX HEATING

AIRFLOW

(CFM)

CAPACITY

(BTUH)

MINIMUM INLET

AIR TEMP.

(°F)

DISCHARGE

AIR TEMP.

(°F)

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

AIR PRESSURE

DROP

(IN. W.C.)

MAX. WATER

PRESSURE DROP

(FT. W.C.) ROWS

VAV-101 SHUT-OFF SINGLE DUCT 290 60 60 1750 55 80 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4

VAV-102 SHUT-OFF SINGLE DUCT 205 80 125 3500 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-103 SHUT-OFF SINGLE DUCT 250 80 80 2500 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-104 SHUT-OFF SINGLE DUCT 1120 270 270 7500 55 80 160 140 0.8 0.20 5.0 1 10 0.75 30 1,2,3,4

VAV-105 SHUT-OFF SINGLE DUCT 600 125 125 3500 55 80 160 140 0.5 0.20 5.0 1 8 0.75 30 1,2,3,4

VAV-106 SHUT-OFF SINGLE DUCT 250 50 155 6000 55 90 160 140 0.7 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-107 SHUT-OFF SINGLE DUCT 250 50 145 5500 55 90 160 140 0.6 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-108 SHUT-OFF SINGLE DUCT 670 150 150 4250 55 80 160 140 0.5 0.20 5.0 1 8 0.75 30 1,2,3,4

VAV-109 SHUT-OFF SINGLE DUCT 350 100 100 2750 55 80 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4

VAV-110 SHUT-OFF SINGLE DUCT 525 160 230 8250 55 88 160 140 0.9 0.20 5.0 1 7 0.75 30 1,2,3,4

VAV-111 SHUT-OFF SINGLE DUCT 125 60 60 2250 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4

VAV-112 SHUT-OFF SINGLE DUCT 100 55 55 2000 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4

VAV-113 SHUT-OFF SINGLE DUCT 165 35 35 1500 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4

VAV-121 SHUT-OFF SINGLE DUCT 310 120 120 4500 55 88 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4

VAV-122 SHUT-OFF SINGLE DUCT 260 110 110 3000 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-123 SHUT-OFF SINGLE DUCT 480 235 235 6500 55 80 160 140 0.7 0.20 5.0 1 7 0.75 30 1,2,3,4

VAV-124 SHUT-OFF SINGLE DUCT 225 115 115 3250 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4

VAV-125 SHUT-OFF SINGLE DUCT 260 145 145 5250 55 88 160 140 0.6 0.20 5.0 1 5 0.75 30 1,2,3,4

NOTES:

1. OPERATING FLUID IS 40% PROPYLENE GLYCOL.

2. CONTROL POWER TRANSFORMER SHALL BE PROVIDED. PROVIDE DISCONNECT AND CONNECT TO 120V POWER CONNECTION PROVIDED PER DIV 26.

3. CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLS UTILIZING BACNET PROTOCOL.

4. MINIMUM INLET STATIC PRESSURE INCLUDES PRESSURE DROPS ACROSS THE VAV BOX.

FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE (FPVAV)

TAG NO. TYPE

PRIMARY AIRFLOW FAN HEATING COIL

VAV BOX

INLET

DIAMETER

(IN.)

MIN.

INLET

PRESS

(IN. W.C.)

SOUND

LEVEL

ELECTRICAL

NOTES

MAX

(CFM)

MIN

(CFM)

AIRFLOW

(CFM)

EXT.

STATIC

PRESS.

(IN. W.C.) TYPE

MOTOR

HP

CAPACITY

(BTUH)

AIRSIDE HYDRONIC SIDE

FLA VOLT PH

AIRFLOW

(CFM)

MINIMUM INLET

AIR TEMP.

(°F)

DISCHARGE

AIR TEMP.

(°F)

MAX. PRESSURE

DROP

(IN. W.C.)

FLOW

(GPM)

EWT

(°F)

LWT

(°F)

MAX. PRESSURE

DROP

(FT WG)

MIN. ROWS /

MAX. FPI

FPVAV-101 PARALLEL 630 150 1225 0.25 ECM 0.33 32000 1375 66.5 88 0.50 3.3 160 140 5 2 / 10 8 0.75 30 4.3 120 1 1,2,3,4,5

FPVAV-102 PARALLEL 1350 380 495 0.25 ECM 0.33 24500 875 62.4 88 0.50 2.5 160 140 5 2 / 10 12 0.75 30 4.3 120 1 1,2,3,4,5

FPVAV-103 PARALLEL 390 80 200 0.25 ECM 0.33 7250 280 64.3 88 0.50 0.8 160 140 5 1 / 10 6 0.75 30 4.3 120 1 1,2,3,4,5

FPVAV-104 PARALLEL 245 50 1030 0.25 ECM 0.33 24250 1080 67.4 88 0.50 2.5 160 140 5 2 / 10 5 0.75 30 4.3 120 1 1,2,3,4,5

NOTES:

1. OPERATING FLUID IS 40% PROPYLENE GLYCOL.

2. CONTROL POWER TRANSFORMER SHALL BE PROVIDED.

3. CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLS UTILIZING BACNET PROTOCOL.

4. MINIMUM INLET STATIC PRESSURE INCLUDES PRESSURE DROPS ACROSS THE VAV BOX.

5. AIRFLOWS SHOWN ON PLANS ARE MAX. HEATING AIRFLOWS (MIN. PRIMARY FLOW PLUS FAN AIRFLOW).

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02 CD

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

NOT FOR

CONSTRUCTION

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

MECHANICAL SCHEDULES

XGFG182011

M-602

01/20/21

C. DAZE R. WEAVER

B. POOLE

FAN SCHEDULE (EF)

TAG NO. AREA SERVED

SERVICE USED

FOR FAN TYPE

ALTITUDE

(FT.)

AIRFLOW

(CFM)

FAN

SPEED

(RPM)

SPEED

CONTROL

EXTERNAL

STATIC

PRESSURE

(IN. W.G.)

SOUND

LEVEL

(LWA)

MOTOR

STARTER /

DISCONNECT

PROVIDED BY

INTERLOCK

WITH

DRIVE

TYPE

WEIGHT

(LBS) NOTESMIN. HP

OPERATING

BHP TYPE VOLTS PHASE

REF-101 140 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7000 311 NONE 0.3 62 0.75 0.52 ODP 208 1 MANUFACTURER N/A BELT 225 1,3,4,5

REF-102 140 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7000 311 NONE 0.3 62 0.75 0.52 ODP 208 1 MANUFACTURER N/A BELT 225 1,3,4,5

REF-103 153 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5

REF-104 152 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5

REF-105 152 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5

REF-106 154 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 3700 363 NONE 0.3 60 0.5 0.36 ODP 208 1 MANUFACTURER N/A BELT 150 1,3,4,5

REF-107 154 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 3700 363 NONE 0.3 60 0.5 0.36 ODP 208 1 MANUFACTURER N/A BELT 150 1,3,4,5

REF-108 110 - LOCKERS EXHAUST ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 860 792 NONE 0.35 61 0.25 0.12 ODP 208 1 MANUFACTURER AHU-101 BELT 75 1,3,4,5

RF-101 AHU-101 RELIEF AIR ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7400 739 VFD 1.25 77 3 2.76 ODP 208 3 MANUFACTURER AHU-101 BELT 225 2,3,4,5,7

SF-101 128 - MECHANICAL VENTILATION CENTRIFUGAL INLINE 886 1750 1054 UNIT MOUNTED 0.25 70 0.75 0.23 ODP 208 1 MANUFACTURER N/A DIRECT 100 1,3,8

NOTES:

1. PROVIDE WITH MANUFACURER'S DISCONNECT.

2. MANUFACTURER PROVIDED VFD AND DISCONNECT WITH 0-10V DC SPEED CONTROL INPUT.

3. PROVIDE WITH CONTROL TRANSFORMER AND AUXILIARY CONTACT FOR RUN STATUS MONITORING TO THE DDC SYSTEM AND INTERLOCK AS NOTED.

4. PROVIDE WITH MANUFACTURER'S INSULATED ROOF CURB.

5. PROVIDE FAN WITH BELT GUARD AND BIRDSCREEN.

6. NOT USED.

7. PROVIDE WITH MANUFACTURERS INSULATED 16 INCH ROOF CURB.

8. PROVIDE DIRECT DRIVE FAN WITH UNIT MOUNTED SPEED CONTROLLER.

UNIT HEATER SCHEDULE (UH)

TAG NO. LOCATION

AIRFLOW

CONFIGURATION

MOUNTING

HEIGHT AFF

HEATING

CAPACITY

(MBH) (NOTE 5)

AIRFLOW

(CFM)

EWT

(DEG F)

LWT

(DEG F)

WATER

FLOW

(GPM)

WATER PRESS

DROP

(FT)

WEIGHT

(LBS)

ELECTRICAL

NOTESHP VOLTS PHASE

CUH-101 100 - VEST CABINET 0' - 0" 12.6 250 160 130 0.8 3.8 100 0.03 120 1 1,3,6

CUH-102 123 - VEST CABINET 0' - 0" 12.6 250 160 130 0.8 3.8 100 0.03 120 1 1,3,6

UH-101 128 - EXISTING MECH HORIZONTAL 10' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-102 140 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.03 120 1 1,2,3,4

UH-103 140 - WAREHOUSE VERTICAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.03 120 1 1,2,3,4

UH-104 140 - WAREHOUSE VERTICAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-105 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-106 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-107 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-108 140 - WAREHOUSE HORIZONTAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-109 140 - WAREHOUSE HORIZONTAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-110 153 - WAREHOUSE VERTICAL 17' - 0" 25 1000 160 130 1.8 1.0 50 0.03 120 1 1,2,3,4

UH-111 153 - WAREHOUSE VERTICAL 17' - 0" 25 1000 160 130 1.8 1.0 50 0.03 120 1 1,2,3,4

UH-112 154 - WAREHOUSE VERTICAL 16' - 0" 65 2500 160 130 4.5 3.0 85 0.33 120 1 1,2,3,4

UH-113 154 - WAREHOUSE VERTICAL 16' - 0" 65 2500 160 130 4.5 3.0 85 0.33 120 1 1,2,3,4

UH-114 153 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-115 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-116 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-117 152 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-118 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-119 152 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-120 154 - WAREHOUSE HORIZONTAL 15' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-121 154 - WAREHOUSE HORIZONTAL 15' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4

UH-122 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

UH-123 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

UH-124 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

UH-125 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

UH-126 149 - RAMP HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

UH-127 150 - STORAGE HORIZONTAL 12' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4

NOTES:

1. PROVIDE WITH MANUFACTURER'S DISCONNECT FOR A SINGLE-POINT ELECTRICAL CONNECTION.

2. PROVIDE WITH MANUFACTURER'S STANDARD LOUVER AND WALL/CEILING MOUNTING BRACKET.

3. OPERATING FLUID IS 40% PROPYLENE GLYCOL.

4. PROVIDE WITH REMOTE WALL MOUNTED THERMOSTAT.

5 HEATING CAPACITY IS ACTUAL HEATING CAPACITY BASED ON INTERIOR HEATING TEMPERATURE OF 60 DEG F AND SCHEDULED OPERATING PARAMETERS.

6. PROVIDE WITH UNIT MOUNTED THERMOSTAT, AND MANUFACTURER CONTROL VALVE PACKAGE.

BASEBOARD HEATER SCHEDULE (BB)

TAG NO.

LOCATION

LENGTH

(FT)

HEATING

CAPACITY

(BTUH/FT)

(NOTE 4)

HEATING

CAPACITY

(BTUH/FT)

(NOTE 5)

EWT

(DEG. F)

FLOW

(GPM)

TUBE SIZE

(IN.)

MIN FINS

PER INCH

MOUNTING

HEIGHT

(IN.)

(NOTE 6)

NOTES

BB-101 104 - READINESS SUPER 7 1820 685 160 0.5 0.75 42 4 1,2,3

BB-102 102 - OPS OFFICER 9 1820 595 160 0.5 0.75 42 4 1,2,3

BB-103 101 - COMMANDER 16 1820 570 160 0.5 0.75 42 4 1,2,3

BB-104 113 - MOTHER'S ROOM 6 1820 490 143 0.5 0.75 42 4 1,2,3

BB-105 114 - 1ST SHIRT 6 1820 625 160 0.5 0.75 42 4 1,2,3

BB-106 115 - BREAK ROOM 25 1820 585 160 1.1 0.75 42 4 1,2,3

BB-107 116 - CHIEF ENLISTED MANAGER 8 1820 450 139 0.8 0.75 42 4 1,2,3

BB-108 117 - SUPPLY SUPER 7 1820 520 149 0.8 0.75 42 4 1,2,3

BB-109 118 - TMO SUPER 6 1820 610 160 0.8 0.75 42 4 1,2,3

BB-110 119 - WAREHOUSE SUPER 8 1820 450 137 1.0 0.75 42 4 1,2,3

BB-111 120 - LGLO SUPER 7 1820 520 145 1.0 0.75 42 4 1,2,3

BB-112 121 - OPEN OFFICE 10 1820 660 160 1.0 0.75 42 4 1,2,3

BB-113 127 - TMO OFFICE / VEHICLE OPS 17 1820 955 160 1.2 0.75 42 4 1,2,3

BB-114 129 - DEPLOYMENT CONTROL CENTER 12 1820 590 160 0.9 0.75 42 4 1,2,3

BB-115 129 - DEPLOYMENT CONTROL CENTER 7 1820 590 160 0.9 0.75 42 4 1,2,3

BB-116 130 - LOGISTICS PLAN 17 1820 540 160 0.7 0.75 42 4 1,2,3

BB-117 127 - TMO OFFICE / VEHICLE OPS 17 1820 550 160 0.7 0.75 42 4 1,2,3

NOTES:

1. PROVIDE ONE TIER SINGLE PASS COPPER TUBE WITH ALUMINUM FINS. PROVIDE ENCLOSURE WITH SLOPED TOP.

2. PROVIDE WALL BRACKETS AND HANGERS AS REQUIRED. PROVIDE EMPTY SECTIONS OF ENCLOSURE TO EXTEND FROM WALL TO WALL. PROVIDE ACCESS

DOORS FOR ALL VALVES.

3. HEATING FLUID IS 40% POLYPROPYLENE GLYCOL.

4. HEATING CAPACITY BASED ON STANDARD 1 PSI STEAM AT 65 DEG ROOM TEMP.

5. HEATING CAPACITY BASED ON SCHEDULED WATER TEMPERATURE, FLUID, HEATING ROOM TEMP OF 68 DEG F, AND ALL OTHER AS PROVIDED CONDITIONS.

6. MOUNTING HEIGHT MEASURED FROM BASE OF UNIT COVER TO FINISHED FLOOR.

DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)

TAG NO. DESCRIPTION SYSTEM NAME

MODEL THROW

PATTERN DAMPER MOUNTING

BLADE

SPACING NOTESTITUS PRICE KRUEGER

A 24"x24" PLAQUE FACE DIFFUSER SUPPLY OMNI ASPD 5PLQ 4W NONE LAY-IN - 1,5

B LOUVERED FACE GRILLE SUPPLY 272FS 22S 800 TWO WAY INTEGRAL SURFACE 3/4" 1,2,6

C 24"x24" EGGCRATE GRILLE RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,5

D 24"x24" EGGCRATE GRILLE TRANSFER 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,3,5

E 10"x10" EGGCRATE GRILLE RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE SURFACE 1/2" 1,5

F 12"x12" EGGCRATE GRILL RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,5

G 24"x12" EGGCRATE GRILLE TRANSFER 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,4,5

H LOUVERED FACE GRILLE RETURN / EXHAUST 350FL 630 S80 30 DEGREE NONE SURFACE 3/4" 1,2,6

J LOUVERED FACE GRILLE RETURN / EXHAUST 350FL 630 S80 30 DEGREE NONE DUCT 3/4" 1,2,6

K LOUVERED FACE GRILLE TRANSFER 350FL 630 S80 30 DEGREE NONE SURFACE 3/4" 1,2,6

NOTES:

1. SEE PLANS FOR NECK SIZE. WHERE NOT NOTED, BRANCH DUCT SIZE SHALL BE THE SAME AS THE DIFFUSER NECK SIZE.

2. SEE PLANS FOR FACE SIZE.

3. PROVIDE WITH 10" X 10" ACOUSTICALLY LINED 90 DEG ANGLE TRANSFER AIR BOOT.

4. PROVIDE WITH 22" X 10" ACOUSTICALLY LINED 90 DEG ANGLE TRANSFER AIR BOOT.

5. FINISH TO MATCH CEILING.

6. FINISH TO MATCH WALL/STRUCTURE PAINTING.

DRAWINGS. PROVIDE TRANSFORMER IF SELECTED ACTUATORS REQUIRE.

2. PROVIDE POWER FROM UNIT SERVED OR POWER SERVICE SHOWN ON ELECTRICAL

1. EXISTING. ACTUAL DIMENSIONS MAY BE DIFFERENT THAN WHAT IS SCHEDULED.

NOTES:

CD-24 REF-104 OA 80 18 PARALLEL 1

CD-23 REF-102 OA 44 18 PARALLEL 1

CD-22 REF-101 OA 44 18 PARALLEL 1

CD-21 SF-101 EA 48 24 PARALLEL 1

CD-14 REF-107 OA 60 36 PARALLEL 2

CD-13 REF-106 OA 60 36 PARALLEL 2

CD-12 REF-107 EA 30 30 PARALLEL 2

CD-11 REF-106 EA 30 30 PARALLEL 2

CD-10 REF-105 EA 24 24 PARALLEL 2

CD-09 REF-104 EA 24 24 PARALLEL 2

CD-08 REF-103 EA 24 24 PARALLEL 2

CD-07 REF-102 EA 42 42 PARALLEL 2

CD-06 REF-101 EA 42 42 PARALLEL 2

CD-05 REF-108 EA 16 16 PARALLEL 2

CD-04 SF-101 OA 18 18 PARALLEL 2

CD-03 AHU-101 RA 48 18 OPPOSED 2

CD-02 AHU-101 OA 48 20 OPPOSED 2

CD-01 AHU-101 OA 16 14 OPPOSED 2

TAG UNIT SYSTEM

WIDTH

(IN)

HEIGHT

(IN)

BLADE

ACTUATION

REMARKS

CONTROL DAMPER SCHEDULE (CD)

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02 CD

VAV-109 & BB-117

TYPICAL FOR ALL VAV

GENERAL:

CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLLER. THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF OPERATION: UNOCCUPIED, WARM-UP, COOL-DOWN, AND OCCUPIED.

UNOCCUPIED:

UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.

VAV DAMPER SHALL BE AT MINIMUM POSITION.

IF THE ZONE TEMPERATURE FALLS BELOW OR RISES ABOVE THE UNOCCUPIED HEATING OR COOLING TEMPERATURE SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN

"OCCUPIED" MODE UNTIL THE SETPOINT HAS BEEN SATISFIED.

ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE TERMINAL UNIT SHALL GO INTO

OCCUPIED MODE FOR ONE HOUR (ADJ) AND THEN REVERT TO UNOCCUPIED MODE.

WARM-UP/COOL-DOWN:

VAV BOX DAMPER AND HEATING VALVE SHALL MODULATE AS DESCRIBED IN THE "OCCUPIED" MODE SECTION.

OCCUPIED:

OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM.

ZONE TEMPERATURE CONTROL (DUAL MAXIMUM – NO BASEBOARD HEATER): VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE VAV BOX HOT WATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW AND THE VAV BOX HOT WATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE VAV BOX HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. AS THE FIRST STAGE, THE AIRFLOW SETPOINT SHALL BE AT MINIMUM FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT. IF THE DISCHARGE AIR TEMPERATURE IS AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE AND THE ZONE IS STILL CALLING FOR HEATING, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN MINIMUM AND HEATING MAXIMUM FLOW TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT WHILE THE DISCHARGE AIR TEMPERATURE IS MAINTAINED AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE. THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT IS GIVEN IN THE VAV TERMINAL UNIT SCHEDULE.

ZONE TEMPERATURE CONTROL (PAIRED WITH BASEBOARD HEATER): VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE VAV BOX HOT WATER VALVE AND THE BASEBOARD HEATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW AND THE VAV BOX HOT WATER VALVE AND THE BASEBOARD HEATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE VAV BOX HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. AS THE FIRST STAGE, THE AIRFLOW SETPOINT SHALL BE AT MINIMUM FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT. IF THE DISCHARGE AIR TEMPERATURE IS AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE AND THE ZONE IS STILL CALLING FOR HEATING, THE BASEBOARD HEATER CONTROL VALVE SHALL BE OPENED WHILE THE DISCHARGE AIR TEMPERATURE IS MAINTAINED AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE. THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT IS GIVEN IN THE VAV TERMINAL UNIT SCHEDULE.

ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED SETPOINT (CLG/HTG) PLUS/MINUS THE OCCUPANT ADJUSTMENT.

SEQUENCE OF OPERATION - VAV TERMINAL UNIT WITH HOT WATER REHEAT

SUPPLY

AIR

VAV-SA-F

H

HWR

HWS

VAV BOX DAMPER

VAV BOX

CONTROLLER

STAT

HEATING

COIL

VHTG-V-C

VAV-D-C

ZN-T

ZN-T-SP-ADJ

UNOCC-OVRD

VAV-DA-T

VHTG-V-S

HWR

BHTG-V-S

HWS

WHEN VAV TERMINAL UNIT IS

PAIRED WITH BASEBOARD HEATER

(SEE HVAC PIPING PLANS)

BHTG-V-C

BASEBOARD

HEATER

FPVAV-101

TYPICAL FOR ALL FPVAV

GENERAL:

CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLLER. THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF

OPERATION: UNOCCUPIED, WARM-UP, COOL-DOWN, AND OCCUPIED.

UNOCCUPIED:

UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.

VAV DAMPER SHALL BE CLOSED.

FAN SHALL BE OFF.

IF THE ZONE TEMPERATURE FALLS BELOW UNOCCUPIED HEATING SETPOINT, THE VAV BOX PRIMARY DAMPER SHALL CLOSE, THE FAN SHALL RUN CONTINUOUSLY, AND THE HEATING VALVE SHALL MODULATE TO MAINTAIN ZONE HEATING TEMPERATURE

SETPOINT.

IF THE ZONE TEMPERATURE RISES ABOVE THE UNOCCUPIED COOLING SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN

"OCCUPIED" MODE UNTIL THE COOLING SETPOINT HAS BEEN SATISFIED.

AFTER THE ZONE TEMPERATURE HAS BEEN WITHIN SETPOINT FOR 15 MINUTES (ADJ) THE VAV DAMPER SHALL RETURN TO

MINIMUM POSITION AND THE FAN SHALL BE OFF.

ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE TERMINAL UNIT SHALL GO INTO OCCUPIED MODE FOR ONE HOUR (ADJ) AND THEN REVERT TO UNOCCUPIED

MODE.

WARM-UP/COOL-DOWN:

VAV BOX DAMPER, HEATING VALVE, AND FAN SHALL MODULATE AS DESCRIBED IN THE "OCCUPIED" MODE SECTION.

OCCUPIED:

OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM.

ZONE TEMPERATURE CONTROL: VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX PRIMARY SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE HOT WATER VALVE SHALL BE CLOSED AND THE FAN SHALL BE DE-ENERGIZED.

WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE PRIMARY AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW, THE HOT WATER VALVE SHALL BE CLOSED, AND THE FAN SHALL BE DE-ENERGIZED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE PRIMARY AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW, THE FAN SHALL RUN AT A CONSTANT SPEED, AND THE HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT

THE HEATING SETPOINT.

ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED SETPOINT (CLG/HTG)

PLUS/MINUS THE OCCUPANT ADJUSTMENT.

SAFETY CONTROLS:

THE FAN SHALL START AND STOP AS ALLOWED BY THE INTERNAL SAFETIES OF THE VAV BOX CONTROLLER.

SEQUENCE OF OPERATION - PARALLEL FAN POWERED VAV TERMINAL UNIT WITH HOT

WATER REHEAT

SUPPLY

AIR

VAV-SA-F

H

HWR

HWS

VAV BOX DAMPER

VAV BOX

CONTROLLER

STAT

HEATING

COIL

VHTG-V-C

VAV-D-C

ZN-T

ZN-T-SP-ADJ

MS

VAV-FAN-SS

FROM

PLENUM

VAV-DA-T

PARALLEL

FAN

UNOCC-OVRD

VHTG-V-S

BB-104 ONLY

GENERAL:

THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF OPERATION:

UNOCCUPIED AND OCCUPIED.

UNOCCUPIED:

UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.

IF THE ZONE TEMPERATURE FALLS BELOW THE UNOCCUPIED HEATING

TEMPERATURE SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN

"OCCUPIED" MODE UNTIL THE SETPOINT HAS BEEN SATISFIED.

ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN

UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE

TERMINAL UNIT SHALL GO INTO OCCUPIED MODE FOR ONE HOUR (ADJ) AND

THEN REVERT TO UNOCCUPIED MODE.

OCCUPIED:

OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM. WHEN THE

ZONE TEMPERATURE IS ABOVE HEATING SETPOINT THE BASEBOARD HEATING

VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE

ZONE HEATING TEMPERATURE SETPOINT, THE BASEBOARD HEATING VALVE

SHALL OPEN.

ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO

ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE

THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED

SETPOINT (CLG/HTG) PLUS/MINUS THE OCCUPANT ADJUSTMENT.

SEQUENCE OF OPERATION - INDIVIDUAL

BASEBOARD UNIT HEATER CONTROL

STAT

ZN-T

ZN-T-SP-ADJ

UNOCC-OVRD

HWR

BHTG-V-S

HWS

BHTG-V-S

BASEBOARD HEATER

S c a le

F o r M ic ro fi lm in g

In c h e s

M ill im e te rs

D

C

A

B

E

D

C

A

B

E

D

C

A

B

E

5 61 2 3 4

5 61 2 3 4

127591 date detailed checkeddesigned project contract rev.drawing file

DATEREV.

REVISIONS

DESCRIPTION INIT

TRUAX FIELD AIR NATIONAL GUARD BASE,

DANE COUNTY REGIONAL AIRPORT,

MADISON, WISCONSIN

9450 WARD PARKWAY, KANSAS

CITY, MISSOURI 64114

Project No. -

NOT FOR

CONSTRUCTION

F-35 ADAL B510 WAREHOUSE

AND SUPPLY

HVAC CONTROLS - VAV TERMINAL UNITS

XGFG182011

M-706

01/20/21

C. DAZE R. WEAVER

B. POOLE

NTSSCALE:D4

VAV TERMINAL UNIT WITH HOT WATER REHEAT

NTSSCALE:C4

PARALLEL FAN POWERED VAV TERMINAL UNIT WITH HOT

WATER REHEAT

4) ALARM CONDITIONS MARKED WITH A DOUBLE ASTERISK (**) SHALL BE ACTIVE ONLY WHEN THE SYSTEM IS IN OCCUPIED MODE AND HAS BEEN IN OCCUPIED MODE FOR MORE THAN 30 MINUTES.

3) SYS-OCC: OVERRIDE OF SYS-OCC IS ACCOMPLISHED THROUGH THE SYSTEM SCHEDULER.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE GENERAL POINTS SCHEDULE NOTES ON THE CONTROLS LEGEND DRAWING.

NOTES:

VAV-DA-T-SP VAV DISCHARGE AIR TEMPERATURE SETPOINT ~ ~ ~ ~ X ~ ~ X ~ ~

VAV-DA-T VAV DISCHARGE AIR TEMPERATURE ~ <___> AI ~ X X ~ ~ ~ ~

VHTG-V-S VAV BOX HEATING VALVE POSITION STATUS ~ 0-100% OPEN AI ~ X ~ ~ ~ ~ ~

VHTG-V-C VAV BOX HEATING VALVE COMMAND ~ 0-100% OPEN AO ~ X ~ X X ~ ~

BHTG-V-S BASEBOARD HEATING VALVE POSITION STATUS (WHERE PAIRED) ~ OPEN/CLOSED BI ~ X ~ ~ ~ ~ ~

BHTG-V-C BASEBOARD HEATING VALVE COMMAND (WHERE PAIRED) ~ OPEN/CLOSED BO ~ X ~ X X ~ ~

VAV-D-C VAV DAMPER COMMAND ~ 0-100% OPEN AO ~ X X ~ ~ ~ ~

VAV-SA-F-SP VAV SUPPLY AIR FLOW SETPOINT ~ ~ ~ ~ X ~ ~ ~ ~ ~

VAV-SA-F VAV SUPPLY AIR FLOW ~ <___> AI ~ X ~ ~ ~ ~ ~

ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE (CLG/HTG) 80/66 DEG ~ ~ ~ X ~ X X ~ ~

ZN-T-SP-ADJ ZONE TEMPERATURE SETPOINT OCCUPANT ADJUSTMENT

OCCUPANT

ADJUSTABLE

±1 DEG F AI ~ X ~ X X ~ ~

ZN-T-SP ZONE TEMPERATURE SETPOINT (CLG/HTG) 78/68 DEG ~ ~ ~ X ~ X X ~ ~

ZONE TEMPERATURE

CONTROL

ZN-T ZONE TEMPERATURE ** ~ <___> AI ~ X X ~ ~

** ZN-T 2 DEG F MORE THAN ZN-T-SP-CLG OR LESS

THAN ZN-T-SP-HTG

INFO

EFF-OCC EFFECTIVE OCCUPANCY ~ OCC/UNOCC NVO ~ X ~ ~ ~ ~ ~

UNOCC-OVRD UNOCCUPIED OVERRIDE INPUT (OVERRIDE BUTTON ON STAT) ~ ~ BI ~ ~ ~ ~ ~ ~ ~START/STOP

SYS-OCC OCCUPANCY INPUT (FROM SYSTEM SCHEDULER) ~ ~ NVI ~ X ~ SEE NOTES ~ ~

FUNCTION NAME DESCRIPTION

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

DISP

REQ'D

TREND

REQ'D

LDP

VIEW

REQ'D

M&C

LDP

OVRD

REQ'D

M&C

OVRD

REQ'D

ALARM CONDITION

(SEE NOTES)

ALARM

PRIORITY

LDP AND M&C DISPLAY OVERRIDES ALARMS

POINTS LIST SCHEDULE - VAV TERMINAL UNIT WITH HOT WATER REHEAT

NTSSCALE:C1

INDIVIDUAL BASEBOARD UNIT HEATER

SYM DATE DESCRIPTION APR

0 09/17/2021 ISSUED FOR BID

1 03/01/2022 ADDENDUM 02 CD

GC003 STAGING AND LAYDOWN PLAN
S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW
Sheets
S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW
S-301 - NEW ADDITION BUILDING SECTIONS
S-301 - NEW ADDITION BUILDING SECTIONS
Sheets
S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW
S-301 - NEW ADDITION BUILDING SECTIONS
B510_ADD-02_Arch Sheets
Sheets
A-103 - GROUND FLOOR PLAN - AREA C
A-201 - EXTERIOR BUILDING ELEVATIONS - BASE BID
A-312 - WALL SECTIONS
A-352 - SECTION DETAILS
B510_M_B-3 ADDENDUM 02
127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-113 - HVAC PLAN - AREA C
127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-601 - MECHANICAL SCHEDULES
127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-602 - MECHANICAL SCHEDULES
127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-706 - HVAC CONTROLS - VAV TERMINAL UNITS

File details come from the government source that posted it. Updated .