ATTACHMENT 10 ADDENDUM 02 PLAN UPDATES Project XGFG182011 Dated 03 March 2022.pdf
PDF 8 MB Posted
- Solicitation number
- W50S9F-22-B-0002
- Issued by
-
Department of the Army National Guard
About this file
This solicitation document requests bids for a firm fixed-price construction contract to build a new warehouse addition and renovate existing facilities at Dane County Regional Airport in Madison, Wisconsin. Key details include:
-
The project scope includes constructing a new 5,150 square foot warehouse addition, renovating approximately 20,000 square feet of existing warehouse, and renovating around 8,150 square feet of administrative offices. Work includes minor demolition, site work, mechanical, electrical and plumbing systems upgrades, and architectural finishes.
-
The base contract line items are for renovation and new construction work. There are also three options for communication cabling/equipment, replacing existing windows, and temporary facilities.
-
The pre-bid conference will be held on-site with attendance required. The bid opening will follow standard FAR and DFARS procedures.
-
The estimated contract value is between $5-10 million. The NAICS code is 236220 with a $39.5 million size standard.
-
Award will be to the responsive and responsible lowest bidder. A small business subcontracting plan is required from the apparent low bidder. The contract duration is 365 days from notice to proceed.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAN
SS
WV
WVWV
WV
WV
SAN
POST
AGPOST
POST
POST
BLDG
AG BLDG
WV
BLDG
AG
AGAG BLDG
BLDG
AG
SAN
SAN
BLDG
BLDGBLDG
BLDG
WV
GV
SAN
UT
BLDG
POST
AGPOSTPOST
POST
AGPOST
UT
BLDGBLDG
POST
POST
BLDG
A/C
UT
POST BLDG
A/CA/C
BLDG
BLDGBLDG
BLDGBLDG
POSTBLDG
SS
SS
SS
SS
SS
SSSSSS
E
E
G
E
E
E E
E
EE
SAN
SAN
SAN
SAN
SAN
SA
N
SA
N
SA
N
SA
N
SA
N
SANSANSAN
SAN SAN SAN
SAN SAN SAN
G G
G G
G G
G
G
E
EE
WW
W
W
W
W
W
W W
SAN SAN SAN SAN
SAN SAN SAN
T
T T
T
T
T
T
T T
T
W W
W
W
W
E
E
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSSSSSSSSSSSS
STAGING AREA
BUILDING 510
H O
FF
M
AN
S
T.
BECKER ST.
BENSON ST.
TEMPORARY ADMIN
TRAILER. SEE NOTE 3.
TEMPORARY ALASKAN
TRAILER PROVIDED BY
GOVERNMENT. SEE NOTE 3.
TEMPORARY
READINESS TRAILER.
SEE NOTE 3.
XGFG182011
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4 sheets
127591 date detailed checkeddesigned ofsheet project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
SYM DATE DESCRIPTION APR
ISSUED FOR BID
F-35 ADAL B510
WAREHOUSE AND SUPPLY
A1 STAGING AND LAYDOWN PLAN
SCALE: 1"=20'
N
NOTES:
1. SEE CIVIL LEGEND ON GC002. SEE LOCATION
PLAN AND VICINITY MAP ON GC001.
2. COORDINATE FINAL STAGING AREA WITH
CONTRACTING OFFICER.
3. TEMPORARY ELECTRICITY, COMMUNICATIONS,
AND PORTABLE RESTROOM FACILITIES ARE
REQUIRED. COORDINATE CONNECTIONS FOR
TEMPORARY UTILITIES WITH THE CONTRACTING
OFFICER, AND MG&E FOR ELECTRICAL
SERVICES.
20' 40'0
STAGING AREA
LEGEND:
STAGING AND LAYDOWN PLAN
GC003 1
XX -
127591GC003-B510.DWG
02-08-2021 C. FRANZEN
S. WAGNER M. SCHRAEDER
0 ISSUED FOR BID09/17/2021
1 ADDENDUM 0102/22/2022
TOC
100' - 0"
MQ
TOW EL 118' - 0"
57' - 2" 7' - 0"
8' - 4"
OPNG
5' - 0" 8' - 8"
OPNG
14' - 0"
OPNG
3' - 4"
2"
3' - 10"
OPNG
5' - 0"
O P
N G
"O
P N
G
TOC EL 92' - 0"
12" CMU
TOW EL 121' - 8"
8" CMU
N1
N2
N3
N4 BEHIND, TYP
N5
A2
A1
E1
E2
E6
E3
E5
E8
E7
N7 BEHIND
A4
A6 A6
M.3
10"
O P
N G
L-2
L-2L-2
L-4
J -4
J -4
J -1
J -1
J -2
J -2
J -2
J -2
TOC
100' - 0"
5 6.13.9
40' - 0" 40' - 0"
TOC EL 92' - 0"
N1
N2
N3
N5
12" CMU
8" CMU
TOW EL 121' - 8"
TOW EL 118' - 0"
N7 BEHIND
1/2" / 1'-0" 1/2" / 1'-0"
TOC
100' - 0"
M Q
57' - 2"7' - 0"
10"
TOC EL 92' - 0"
TOW EL 118' - 0"
E1
E2
E4
E3
E5
E8
E7
N1
N2
N3
N4 BEHIND, TYP
N5
12" CMU
8" CMU
TOW EL 121' - 8"
TOW EL 118' - 0"
N7 BEHIND
M.3
7' - 0"
TOC EL 93' - 4"
TOC
100' - 0"
344.1 3.1
8' - 0"
OPNG
7' - 4"
OPNG
3' - 4"
1' - 8" 18' - 6" 1' - 11"
TOC EL 109' - 6"
A1
N10
N11
N1
E3 TYP
E1 TYP
E5
N13
O P
N G
A3
TOW EL 107' - 4"
N12
J
J
TOC
100' - 0"
344.1 3.1
TOC EL 109' - 6"
1' - 8" 18' - 6" 1' - 11"
TOC EL 98' - 8"
N10
N11
N1
E3
E1
E5
N13
N14
N15
TOW EL 108' - 8"
N16 BEYOND
TOC
100' - 0"
3 4 4.13.1
1' - 11" 18' - 6" 1' - 8"
TOC EL 109' - 6"
TOC EL 98' - 8"
N11
N1
E3
E1
E5
N14
N15
TOW EL 108' - 8"
N16 BEYOND
TOC
100' - 0"
GG.7 F.6
N11
N12
N16
N15
TOW EL 109' - 6"
TOC EL 108' - 8"
TOC EL 98' - 8"
5' - 8"14' - 8"
N16
TYP
TYP
N13 TYP
TOC
100' - 0"
FG E D.6G.7 F.6
OPNG
6' - 4"3' - 0"
OPNG
4' - 0"3' - 0"
8' - 10"20' - 0"14' - 4"5' - 8"14' - 8"
O P
N G
TOC EL 109' - 6"
TOC EL 98' - 8"
A4 N11
N1
N14
E3
E1
N15
N10
A1 A1
E9 E9
E9
TOW EL 108' - 8"
O P
N G
E.6
N12
L-2
J -2
J -2
TOC
100' - 0"
344.1 3.1
1' - 8" 18' - 6" 1' - 11"
N10
N11
N1
E3
TYP
E1
E5
N13
N14
TOW EL 108' - 8"
TOC EL 109' - 6"
S c a le F o r
M ic ro fi lm in g
In c h e s
M il lim e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD
BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9400 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
CMU AND CONCRETE WALL ELEVATIONS -
NEW
XGFG182011
S-201
09/17/2021
S. BADE W. BAILEY
D. BRICE
SCALE: 3/16" = 1'-0"A1
GRID LINE 6.1 CMU WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"B1
GRID LINE Q CMU WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"A3
GRID LINE 3.9 CMU WALL ELEVATION - NEW
0 4' 8' 12'
0 4' 8' 12'0 4' 8' 12'
NOTES:
1. SEE DRAWING S-121 FOR NOTES.
KEYED NOTES:
1. SEE DRAWING S-121 FOR KEYED NOTES.
SCALE: 3/16" = 1'-0"D1
GRID LINE D.6 CMU WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"D3
GRID LINE F.6 CONCRETE WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"D5
GRID LINE G.7 CONCRETE WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"B4
GRID LINE 3.1 CMU AND CONCRETE WALL ELEVATION - NEW
SCALE: 3/16" = 1'-0"C4
GRID LINE 4.1 CMU AND CONCRETE WALL ELEVATION - NEW
0 4' 8' 12' 0 4' 8' 12' 0 4' 8' 12'
0 4' 8' 12'
0 4' 8' 12'
SCALE: 3/16" = 1'-0"D2
GRID LINE E.6 CONCRETE WALL ELEVATION - NEW
0 4' 8' 12'
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02
TOC
6.1 3.9
80' - 0"
1/2" / 1'-0"1/2" / 1'-0"
40' - 0"40' - 0"
RIDGE
8" CMU
12" CMU
TOW EL 121' - 8"
TOW EL 118' - 0"
TOC EL 92' - 0"
N2TYP
N4
N1TYP
N3TYP
N5
N6
N7
A1TYP
A2
A3TYP
C1
S-511
TYP
D3
S-512
BOS EL 119' - 7 15/16"
N10
D1
S-512
TYP
TOC
100' - 0"
M Q
64' - 2"
TOW EL 121' - 8"
TOW EL 118' - 0"
N2
N4
N1
N3
N5
N6
N7
A1
A2
TYP
E2
E4
E1
E3
E5
E6
E7
A3
TOC EL 92' - 0"
M.3
11 SPA @ 4' - 10"
53' - 2"4' - 0"5' - 8"
TOS EL 119' - 7 239/256"
N10N10
N11
N9
N8
TOC EL 98' - 6"
C1
S-512
A3
S-511
D5
S-512
C2
S-511
S c a le F o r
M ic ro fi lm in g
In c h e s
M il lim e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD
BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9400 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
NEW ADDITION BUILDING SECTIONS
XGFG182011
S-301
09/17/2021
S. BADE W. BAILEY
D. BRICE
SCALE: 1/4" = 1'-0"A1
BUILDING SECTION
SCALE: 1/4" = 1'-0"C1
BUILDING SECTION
0 2' 4' 8'
0 2' 4' 8'
NOTES:
1. SEE DRAWINGS S-001 & S-002 FOR GENERAL NOTES, LEGEND & ABBREVIATIONS.
2. SEE DRAWING S-501 THROUGH S-504 FOR STANDARD CONCRETE, MASONRY,
ROOF DECK & JOIST DETAILS.
3. MASONRY DIMENSIONS ARE NOMINAL, GENERAL CONTRACTOR COORDINATE
WITH ARCHITECTURAL DRAWINGS & FINAL CMU LAYOUT.
4. SEE OTHER DISCIPLINE DRAWINGS FOR LOCATIONS OF PIPE, DUCT, AND CONDUIT
PENETRATIONS THROUGH NEW CONSTRUCTION.
5. COORDINATE UTILITIES WITH FOUNDATIONS. CONTRACTOR RESPONSIBLE FOR
STEPPING FOUNDATIONS WHERE REQUIRED.
KEYED NOTES (EXISTING):
E1 EXISTING CONCRETE WALL FOOTING.
E2 EXISTING CONCRETE FOUNDATION WALL.
E3
E4
EXISTING CMU WALL.
E5
EXISTING CMU WALL PILASTER.
E6
E7
EXISTING SLAB-ON-GRADE, SEE PLANS FOR ELEVATION.
KEYED NOTES (NEW CONSTRUCTION):
N1 NEW REINFORCED CONCRETE WALL FOOTING PER PLAN.
N2 NEW 12" THICK REINFORCED CONCRETE FOUNDATION WALL PER PLAN.
N3 NEW 12" NOMINAL REINFORCED CMU WALL PER PLAN.
KEYED NOTES (INTERDISCIPLINE):
A1
A2
N5
N4
NEW STEEL ROOF JOIST PER PLAN.
NEW 8" NOMINAL REINFORCED CMU PARAPET ABOVE JOIST BEARING PER PLAN. EXISTING STEEL AND JOIST ROOF FRAMING.
EXISTING METAL DECK, ELEVATION VARIES.
N6
NEW 20 GAGE WIDE RIB METAL ROOF DECK PER PLAN.
NEW 8" REINFORCED CONCRETE SLAB-ON-GRADE PER PLAN.
N7
METAL WALL PANEL, SEE ARCHITECTURAL DRAWINGS.
MEMBRANE ROOF SYSTEM, SEE ARCHITECTURAL DRAWINGS.
A3 PAVEMENT OR FINISHED GRADE, SEE CIVIL DRAWINGS.
NEW STEEL ROOF FRAMING PER PLAN.N10
NEW HSS12X12X5/8 PER PLAN.N11
NEW REINFORCED CONCRETE PEDESTAL PER PLAN.N8
NEW REINFORCED CONCRETE COLUMN FOOTING PER PLAN.N9
NEW CMU PILASTER PER PLAN.N12
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02
DN
W
J MK.5
6.1
3.9
Q
30' - 0" 30' - 0" 64' - 2"
EXISTING RAMP
EXISTING LOADING
DOCK
STORAGE
WAREHOUSE
WAREHOUSE
WAREHOUSE
COLLATERAL
STORAGE
151A
126B
154A
154B
F .V
F .V
24' - 8" 36' - 0" 3"
M1CA
11' - 4"
2' - 0"
150A 150B
INFILL SLAB,
RE: STRUCT.
3' - 3" 8' - 9" 3' - 6" 12' - 0" 5' - 9"
A-201
D1
A-201
C3
A-202
B1
A-201
C1
EXP. JT.
EXP. JT.
D4
A-412
A-202
B5
A1
A-312 A1
A-314
A2
A-314
17' - 4" 3' - 6" 7' - 0" 13' - 4"
L01 L01
DOCK LEVELER AND
DOCK BUMPERS
A-341
A4
A-341
A1M1CA
M1CA
M1CA
A2
A-313
1' - 0"
M1CA
3 SIDES
6.5
RAMP SLOPE
RE: STRUCT
EXISTING DOCK
LEVELER
A2
A-315
ABOVEABOVE
B1
A-352
PLAN
NORTH
KEY PLAN
B C
A
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
GROUND FLOOR PLAN - AREA C
XGFG182011
127591_B510_A_CENTRAL
A-103
03/01/22
S. WILLIAMSON M. TOLBERT
S. WILLIAMSON
SCALE 1/8" = 1'-0"
B1
GROUND FLOOR PLAN - AREA C
0 4' 8' 16'
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID MT
1 03/01/2022 ADDENDUM 02 MT
GROUND FLOOR
T.O. LOW JOIST
110' - 10 1/2"
T.O. JOIST
120' - 2 1/2"
2 3 7
D1
A-301
2.2 6.13.9 4.1
INSULATED METAL PANEL,
R-14 MIN.
EXISTING EIFS
FACADE TO REMAIN
EXISTING EIFS
FACADE TO REMAIN
PREFINISHED METAL
COPING
PREFABRICATED GALV.
STEEL STAIR AND
RAILINGS
EQ 10' - 0" TYP EQ
3.1 6.5
GROUND FLOOR
100' - 0"
A
T.O. JOIST
120' - 2 1/2"
GHJM K.5 B.1B.5C.2C.8D.2D.8E.4E.9
C1
A-301
C3
A-301
Q D.7F.6G.7
INSULATED METAL
PANEL, R-14 MIN.
154A154B 148A
EXISTING EIFS
FACADE TO REMAIN
23' - 4"20' - 0"
PREFINISHED
ALUMINUM SCUPPER
AND DOWNSPOUT
PREFINISHED METAL
COPING
PREFABRICATED GALV.
STEEL STAIR AND
RAILINGS
PREFABRICATED GALV.
STEEL STAIR AND
RAILINGS
T Y
P
3' - 7"
10' - 0" TYP 10' - 0"
EJ
INFILL WALL WITH INSULATED METAL PANEL,
R-19 MIN. ON COLD-FORMED METAL FRAMING.
OUTSIDE FACE OF METAL PANEL TO ALIGN
WITH FACE OF ADJACENT EIFS FINISH.
L01 L01
DOCK LEVELER AND
DOCK BUMPERS
10' - 0" 10' - 0"
GROUND FLOOR
100' - 0"
T.O. JOIST
120' - 2 1/2"
C1
A-301
Q
INSULATED METAL
PANEL, R-14 MIN.
23' - 4" 20' - 0"
PREFINISHED
ALUMINUM SCUPPER
AND DOWNSPOUT
PREFINISHED METAL
COPING
EJ
T Y
P
3' - 7"
10' - 0" TYP10' - 0"
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
EXTERIOR BUILDING ELEVATIONS - BASE
BID
XGFG182011
127591_B510_A_CENTRAL
A-201
03/01/22
S. WILLIAMSON M. TOLBERT
S. WILLIAMSON
SCALE 3/32" = 1'-0"
C3
EAST ELEVATION - BASE BID
SCALE 3/32" = 1'-0"
D1
NORTH ELEVATION - BASE BID
SCALE 3/32" = 1'-0"
C1
SOUTH ADDITION ELEVATION - BASE BID
0 8' 16' 24'
0 8' 16' 24' 0 8' 16' 24'
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID MT
1 03/01/2022 ADDENDUM 02 MT
GROUND FLOOR
C1
A-412
EXISTING LOADING
DOCK
148A
INSULATED METAL
PANEL, R-19 MIN. ON
COLD-FORMED METAL
FRAMING. OUTSIDE
FACE OF METAL PANEL
TO ALIGN WITH FACE OF
ADJACENT EIFS FINISH.
PREFAB ALUM. STAIR
AND RAILINGS
B1
A-622
A3
A-412
SIM
OPP
B3
A-352
D1
A-622
EXISTING E.F.I.S.
SYSTEM
GROUND FLOOR
100' - 0"
44.1
REMOVABLE GUARD
RAILS AT EDGE OF
CONCRETE CAP
SENSITIVE
UNCLASSED
STORAGE
WAREHOUSE
C2
A-411
GROUND FLOOR
100' - 0"
T.O. LOW JOIST
110' - 10 1/2"
CHANGING ROOM
INSULATED METAL
PANEL, R-19 MIN. ON 4"
COLD-FORMED METAL
FRAMING
107' - 4"
EXISTING SOFFIT
A2
A-352
B2
A-352
GROUND FLOOR
100' - 0"
EXISTING LOADING
DOCK
EXISTING E.F.I.S.
SYSTEM
INSULATED METAL
PANEL, R-19 MIN. ON
COLD-FORMED METAL
FRAMING. OUTSIDE
FACE OF METAL PANEL
TO ALIGN WITH FACE OF
ADJACENT EIFS FINISH.
A3
A-352
B3
A-352
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
WALL SECTIONS
XGFG182011
127591_B510_A_CENTRAL
A-312
03/01/22
S. WILLIAMSON M. TOLBERT
S. WILLIAMSON
SCALE 3/4" = 1'-0"
A3
WALL SECTION
0 1' 2' 3'0 1' 2' 3'
SCALE 3/4" = 1'-0"
B5
WALL SECTION
SCALE 3/4" = 1'-0"
B4
WALL SECTION
SCALE 3/4" = 1'-0"
A1
WALL SECTION
0 1' 2' 3' 0 1' 2' 3'
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID MT
1 03/01/2022 ADDENDUM 02 MT
CONTINUOUS 22 GA PRE-FINISHED
PARAPET COPING
CONTINUOUS 22 GA METAL OUTSIDE
HOLD DOWN CLEAT
CONTINUOUS SEALANT OVER
BACKER ROD
EXTERIOR GLASS MAT
SHEATHING
ROOFING MEMBRANE -
RETURN UNDER COPING
3/8" DIAMETER GALVANIZED
CONCRETE ANCHORS @ 1'-6" O.C.
CONTINUOUS TREATED 2x2
TREATED WOOD BLOCKING
CONTINUOUS 1.5" RIGID INSULATION
TERMINATE ROOFING MEMBRANE
SLOPE
TIE NEW EPDM INTO EXISTING
EPDM ROOF SYSTEM
METAL DECK, GALV. AND
PAINTED; RE: STRUCT.
6" STEEL CHANNELS;
RE: STRUCT. FOR
ATTACHMENT TO CMU
CMU WALL; RE: FLOOR
PLANS FOR PARTITION TYPE
CONT. BENT PLATE
RE: STRUCT.
T.O. STEEL
112' - 8"
GROUND FLOOR
100' - 0"
CONCRETE WALL;
RE: STRUCTURAL
GALVANIZED METAL FLASHING
PREFINISHED METAL PANEL
CLOSURE TRIM
INSULATED METAL PANEL, R-19 MIN.
OUTSIDE FACE OF METAL PANEL TO
ALIGN WITH FACE OF ADJACENT
EIFS FINISH.
EXTEND DAMPPROOFING 12" UP
WALL FACE MIN.
COLD-FORMED METAL FRAMING
EXISTING WALL
INSULATED METAL PANEL, R-19 MIN.
OUTSIDE FACE OF METAL PANEL TO
ALIGN WITH FACE OF ADJACENT
EIFS FINISH.
CONTINUOUS SEALANT
COLD-FORMED FRAMING ANCHORED
TO EXISTING WALL ABOVE
EXISTING STRUCTURAL FRAMING
PRE-FINISHED METAL FLASHING
PRE-FINISHED METAL PANEL
CLOSURE TRIM
GROUND FLOOR
100' - 0"
4" COLD-FORMED FRAMING ANCHORED
TO EXISTING CONCRETE SLAB
5/8" GYPSUM BOARD
SCHEDULED BASE
CONTINUOUS BED OF SEALANT
INSULATED METAL PANEL, R-19 MIN.
CONTINUOUS VAPOR BARRIER
EXISTING EIFS SOFFIT - CUT BACK
AS SHOWN TO ALLOW NEW METAL
WALL FRAMING ATTACHMENT
4" COLD-FORMED FRAMING ANCHORED
TO EXISTING FRAMING ABOVE
CONTINUOUS SEALANT
5/8" GYPSUM BOARD TO 6" ABOVE CEILING
SUSPENDED ACOUSTICAL CEILING -
RE: REFLECTED CEILING PLANS
FILL GAP WITH BATT INSULATION
PREFINISHED METAL PANEL
CLOSURE TRIM
INSULATED METAL PANEL, R-19 MIN.
CONT. SEALANT
ISOLATION STRIP
CONCRETE FLOOR
SLAB, RE: STRUCT.
VAPOR BARRIER;
RETURN UP SLAB EDGE
GRANULAR FILL
1/2"
EXISTING CMU WALL
EXISTING WALL
INSULATED METAL PANEL,
R-19 MIN.
CONTINUOUS SEALANT
COLD-FORMED FRAMING
PRE-FINISHED METAL
PANEL CLOSURE TRIM
OUTSIDE FACE OF METAL
PANEL TO ALIGN WITH FACE
OF ADJACENT EIFS FINISH.
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
ISSUED FOR BID
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
SECTION DETAILS
XGFG182011
127591_B510_A_CENTRAL
A-352
03/01/22
S. WILLIAMSON M. TOLBERT
B. NEEDLE
SCALE 6" = 1'-0"
C2
COPING DETAIL
0 1" 2" 4"3"
SCALE 3" = 1'-0"
C5
LID EDGE DETAIL
0 3" 6" 9"
SCALE 3" = 1'-0"
A3
INFILL BASE DETAIL
0 3" 6" 9"
SCALE 3" = 1'-0"
B3
INFILL HEAD DETAIL
0 3" 6" 9"
0 3" 6" 9"
SCALE 3" = 1'-0"
A2
WALL BASE DETAIL
0 3" 6" 9"
SCALE 3" = 1'-0"
B2
WALL HEAD DETAIL
SCALE 3" = 1'-0"
D5
ISOLATION STRIP AT NEW ADDTION
0 3" 6" 9"
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID MT
1 03/01/2022 ADDENDUM 02 MT
SCALE 3" = 1'-0"
B1
INFILL PLAN DETAIL
0 3" 6" 9"
J K L M N P Q
M A
T C
H L
IN
E S
E E
S H
E E
T M
-1 F
O R
C O
N T
IN
U
A T
IO
N
MATCHLINE SEE SHEET M-111 FOR CONTINUATION
UH-110
UH-111
UH-112 UH-113
UH-114
UH-115
UH-116
UH-118UH-117
UH-119
UH-120 UH-121
24"x24" EA UP
TO REF-103
24"x24" EA UP
TO REF-104
24"x24" EA UP
TO REF-105
20"x16" SA
15' - 4" BOD EL
16"x14" SA
16' - 2" BOD EL
20"x20" SA
15' - 2" BOD EL
25"x23" SA UP
TO MAU-101
30"x30" EA UP
TO REF-106
30"x30" EA UP
TO REF-107
18"x18" EA
16' - 6" BOD EL
18"x18" EA
(4)730-24"x16"
EA-J
18"x18" EA
16' - 8" BOD EL
18"x18" EA
18"x18" EA
16' - 8" BOD EL
18"x18" EA
20"x18" EA
15' - 9" BOD EL
(4)925-30"x16"
EA-J
20"x18" EA
20"x18" EA
16' - 8" BOD EL
(2)360-12"x10"
SA-B
580-18"x12"
SA-B
(4)925-30"x16"
EA-J
(4)730-24"x16"
EA-J
(4)730-24"x16"
EA-J
60"x36" OA60"x36" OA
OA LOUVER OA LOUVER
MM
CF-109
CF-110
CF-111 CF-112
"x
S A
165-8"x8"
SA-B
M
CF-105
CF-106
CF-108CF-107
1 1
2CD-24
M CD-08
CD-13 CD-14
MM CD-12CD-11
M
CD-09
MCD-10
20"x18" EA
20"x20" SA
15' - 2" BOD EL
UH-124
UH-125
UH-126
UH-127
20"x16" SA
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
NOT FOR
CONSTRUCTION
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
HVAC PLAN - AREA C
XGFG182011
M-113
01/20/21
C. DAZE R. WEAVER
B. POOLE
1/8" = 1'-0"A3
GROUND FLOOR - HVAC PLAN AREA C
GENERAL NOTES:
1.
2.
SEE SHEET M-001 FOR NOTES, LEGEND, SYMBOLS
AND ABBREVIATIONS.
SEE HVAC PIPING PLANS FOR THERMOSTAT AND
SWITCH LOCATIONS.
KEYED NOTES:
COORDINATE LOCATION OF DESTRATIFICATION
FAN WITH WAREHOUSE SHELVING LAYOUT.
LOCATE FANS IN WAREHOUSE AISLES.
EXISTING LOUVER AND MOTORIZED DAMPER.
WALL OPENING FOR DUCT SHALL BE LESS THAN 96
SQ. IN. IN TOTAL AREA.
8'4' 16'0
SCALE: 1/8"=1'-0"
PLAN NORTH
PLAN
NORTH
KEY PLAN
B
A
C
1 1
ROOM SCHEDULE - AREA C
Number Name
148 EXISTING LOADING DOCK
149 EXISTING RAMP
150 STORAGE
151 COLLATERAL STORAGE
152 WAREHOUSE
153 WAREHOUSE
154 WAREHOUSE
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02 CD
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
NOT FOR
CONSTRUCTION
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
MECHANICAL SCHEDULES
XGFG182011
M-601
01/20/21
C. DAZE R. WEAVER
B. POOLE
AIR HANDLING UNIT SCHEDULE (AHU & MAU) 1/3
TAG NO. LOCATION
ALTITUDE
(FT)
MAX.
AIRFLOW
(CFM)
MIN.
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
INTERNAL
STATIC
PRESSURE
(IN. W.C.)
TOTAL
STATIC
PRESSURE
(IN. W.C.)
SUPPLY FAN SUPPLY FAN MOTOR
MAX
BHP
OUTLET
VELOCITY
(FPM)
FAN
RPM TYPE
WHEEL
DIAMETER
(IN.)
VOLUME
CONTROL MOTOR HP
MOTOR
RPM
MOTOR
TYPE
AHU-101 128 - EXISTING MECH 886 9,000 2,660 1,600 3.6 2.95 6.55 15.6 1300 2000 DDP 24.5 VFD 20 1800 ODP
MAU-101 ROOF 886 2,250 2,250 2,250 0.5 0.69 1.19 0.79 1000 1724 DIRECT DRIVE 15 NONE 1 1800 ODP
AIR HANDLING UNIT SCHEDULE (AHU & MAU) 2/3
TAG NO. TYPE
COOLING COIL HEATING COIL
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EAT DB
(°F)
EAT WB
(°F.) LAT DB (°F)
LAT WB
(°F)
MAX. FACE
VELOCITY
(FPM)
MIN.
ROWS /
MAX. FPI
HEATING
AIRFLOW
(CFM) COIL TYPE
AIRSIDE HYDRONIC
CAPACITY
(MBH)
EAT (DEG
F)
LAT (DEG
F)
ROWS /
FPI MAX
EWT (DEG
F)
LWT (DEG
F)
FLUID
FLOW
(GPM)
MAX WATER
PRESSURE
DROP (FT)
AHU-101 DIRECT EXPANSION 400.6 251.7 78.5 66.8 53 52.4 500 6 / 8 3,000 HYDRONIC 110 24 60 1 / 7 160 120 5.8 1.00
MAU-101 NONE 0 0 87 73 87 73 0 N/A 2,250 NATURAL GAS 175 -5 65 N/A 0 0 0.0 0.00
AIR HANDLING UNIT SCHEDULE (AHU & MAU) 3/3
TAG NO.
PRE-FILTER FINAL FILTER
MCA VOLT PHASE
APPROX. UNIT
WEIGHT (LBS) NOTESTYPE
MERV
RATING
DIRTY PRESSURE
DROP
(IN. W.C.) TYPE
MERV
RATING
DIRTY PRESSURE
DROP
(IN. W.C.)
AHU-101 PLEATED 8 1 PLEATED 13 1 72 208 3 2750 1,3,4,5,6
MAU-101 NONE 0 0 PLEATED 8 0.6 7.7 208 3 1250 2,3,7,8,9,10
NOTES:
1. PROVIDE WITH MANUFACTURER'S DISCONNECT, VFD, AND SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.
2. PROVIDE WITH MANUFACTURER'S DISCONNECT, STARTER, AND SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.
3. PRESSURE DROPS ASSOCIATED WITH DIRTY FILTERS, COILS, ETC. SHALL BE INCLUDED IN THE TOTAL INTERNAL STATIC CALCULATION BY THE UNIT
MANUFACTURER. (NOT INCLUDED IN EXTERNAL STATIC PRESSURE SCHEDULED.)
4. HEATING WATER OPERATING FLUID IS 40% PROPYLENE GLYCOL.
5. PROVIDE AHU WITH INTEGRAL RETURN AIR DAMPER.
6. PROVIDE AHU WITH MANUFACTURER'S 6" HIGH BASE FRAME.
7. PROVIDE MAU WITH MODULATING INDIRECT FIRED NATURAL GAS BURNER WITH MINIMUM 8:1 TURNDOWN.
8 PROVIDE MAU WITH WEATHERHOOD AND ALUMINUM BIRD SCREEN WITH INTEGRATED INSULATED DAMPER ON OUTSIDE AIR INTAKE.
8. PROVIDE MAU WITH ROOF CURB AND EXTENDED BASE FRAME FOR TOTAL 14 INCH RISE ABOVE ROOF.
9 OUTDOOR UNIT
CONDENSING UNIT SCHEDULE (CU)
TAG NO. SERVICE
COOLING
CAPACITY
(BTU/H)
COMPRESSOR
TYPE
MIN.
EFFICIENCY
(EER)
RATED
OUTDOOR DB
(°F)
REFRIGERANT
TYPE
UNIT ELECTRICAL
WEIGHT
(LBS)
SIZE
(H X L X W) (IN) NOTESVOLT PH. MOP
CU-101 AHU-101 400,000 SCROLL 11.4 90 R-410A 208 3 175 2000 75 X 90 X 60 1,2
CU-102 DSS-1 18,000 SCROLL 14 95 R-410A 208 1 20 125 28 X 34 X 16 1,3,4
NOTES:
1. SINGLE POINT POWER CONNECTION IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.
2. MANUFACTURER PROVIDED DISCONNECT.
3. DISCONNECT PROVIDED PER DIVISION 26.
4. PROVIDE POWER AND CABLING TO PAIRED INDOOR UNIT.
HOT WATER BOILER SCHEDULE (HWB)
TAG NO. LOCATION TYPE
ALTITUDE
(FT.)
PRESSURE
RATING
(PSIG) FUEL SOURCE
NOMINAL
BURNER
INPUT
(MBH)
MIN.
GROSS
OUTPUT
(MBH)
AHRI
EFFICIENCY
(%) FLUID
DESIGN
FLOW
(GPM)
LTW
(°F)
EWT
(°F)
MAX. WPD
(FT. W.C.) MCA VOLTS PHASE NOTES
HWB-101 128 - EXISTING MECH CONDENSING 886 125 NATURAL GAS 1000 850 94 40% PROPYLENE GLYCOL 65 160 130 15 20 120 1 1,2,3,4,5
HWB-102 128 - EXISTING MECH CONDENSING 886 125 NATURAL GAS 1000 850 94 40% PROPYLENE GLYCOL 65 160 130 15 20 120 1 1,2,3,4,5
NOTES:
1. PROVIDE CONDENSATE NEUTRALIZATION KIT.
2. PROVIDE WITH GAS PRESSURE REGULATING VALVE.
3. MINIMUM TURN DOWN RATION SHALL BE 5:1.
4. DISCONNECT PER DIV. 26.
5. PROVIDE CONTROLS WITH INTERFACE TO DDC SYSTEM VIA BACNET PROTOCOL.
VARIABLE AIR VOLUME BOX SCHEDULE (VAV)
TAG NO. TYPE
MAX DESIGN
AIRFLOW
(CFM)
MIN DESIGN
AIRFLOW
(CFM)
HEATING COIL VAV BOX
INLET
DIAMETER
(IN.)
MIN.
INLET
PRESS
(IN. W.C.)
SOUND
LEVEL NOTES
MAX HEATING
AIRFLOW
(CFM)
CAPACITY
(BTUH)
MINIMUM INLET
AIR TEMP.
(°F)
DISCHARGE
AIR TEMP.
(°F)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
AIR PRESSURE
DROP
(IN. W.C.)
MAX. WATER
PRESSURE DROP
(FT. W.C.) ROWS
VAV-101 SHUT-OFF SINGLE DUCT 290 60 60 1750 55 80 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4
VAV-102 SHUT-OFF SINGLE DUCT 205 80 125 3500 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-103 SHUT-OFF SINGLE DUCT 250 80 80 2500 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-104 SHUT-OFF SINGLE DUCT 1120 270 270 7500 55 80 160 140 0.8 0.20 5.0 1 10 0.75 30 1,2,3,4
VAV-105 SHUT-OFF SINGLE DUCT 600 125 125 3500 55 80 160 140 0.5 0.20 5.0 1 8 0.75 30 1,2,3,4
VAV-106 SHUT-OFF SINGLE DUCT 250 50 155 6000 55 90 160 140 0.7 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-107 SHUT-OFF SINGLE DUCT 250 50 145 5500 55 90 160 140 0.6 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-108 SHUT-OFF SINGLE DUCT 670 150 150 4250 55 80 160 140 0.5 0.20 5.0 1 8 0.75 30 1,2,3,4
VAV-109 SHUT-OFF SINGLE DUCT 350 100 100 2750 55 80 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4
VAV-110 SHUT-OFF SINGLE DUCT 525 160 230 8250 55 88 160 140 0.9 0.20 5.0 1 7 0.75 30 1,2,3,4
VAV-111 SHUT-OFF SINGLE DUCT 125 60 60 2250 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4
VAV-112 SHUT-OFF SINGLE DUCT 100 55 55 2000 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4
VAV-113 SHUT-OFF SINGLE DUCT 165 35 35 1500 55 88 160 140 0.5 0.20 5.0 1 4 0.75 30 1,2,3,4
VAV-121 SHUT-OFF SINGLE DUCT 310 120 120 4500 55 88 160 140 0.5 0.20 5.0 1 6 0.75 30 1,2,3,4
VAV-122 SHUT-OFF SINGLE DUCT 260 110 110 3000 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-123 SHUT-OFF SINGLE DUCT 480 235 235 6500 55 80 160 140 0.7 0.20 5.0 1 7 0.75 30 1,2,3,4
VAV-124 SHUT-OFF SINGLE DUCT 225 115 115 3250 55 80 160 140 0.5 0.20 5.0 1 5 0.75 30 1,2,3,4
VAV-125 SHUT-OFF SINGLE DUCT 260 145 145 5250 55 88 160 140 0.6 0.20 5.0 1 5 0.75 30 1,2,3,4
NOTES:
1. OPERATING FLUID IS 40% PROPYLENE GLYCOL.
2. CONTROL POWER TRANSFORMER SHALL BE PROVIDED. PROVIDE DISCONNECT AND CONNECT TO 120V POWER CONNECTION PROVIDED PER DIV 26.
3. CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLS UTILIZING BACNET PROTOCOL.
4. MINIMUM INLET STATIC PRESSURE INCLUDES PRESSURE DROPS ACROSS THE VAV BOX.
FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE (FPVAV)
TAG NO. TYPE
PRIMARY AIRFLOW FAN HEATING COIL
VAV BOX
INLET
DIAMETER
(IN.)
MIN.
INLET
PRESS
(IN. W.C.)
SOUND
LEVEL
ELECTRICAL
NOTES
MAX
(CFM)
MIN
(CFM)
AIRFLOW
(CFM)
EXT.
STATIC
PRESS.
(IN. W.C.) TYPE
MOTOR
HP
CAPACITY
(BTUH)
AIRSIDE HYDRONIC SIDE
FLA VOLT PH
AIRFLOW
(CFM)
MINIMUM INLET
AIR TEMP.
(°F)
DISCHARGE
AIR TEMP.
(°F)
MAX. PRESSURE
DROP
(IN. W.C.)
FLOW
(GPM)
EWT
(°F)
LWT
(°F)
MAX. PRESSURE
DROP
(FT WG)
MIN. ROWS /
MAX. FPI
FPVAV-101 PARALLEL 630 150 1225 0.25 ECM 0.33 32000 1375 66.5 88 0.50 3.3 160 140 5 2 / 10 8 0.75 30 4.3 120 1 1,2,3,4,5
FPVAV-102 PARALLEL 1350 380 495 0.25 ECM 0.33 24500 875 62.4 88 0.50 2.5 160 140 5 2 / 10 12 0.75 30 4.3 120 1 1,2,3,4,5
FPVAV-103 PARALLEL 390 80 200 0.25 ECM 0.33 7250 280 64.3 88 0.50 0.8 160 140 5 1 / 10 6 0.75 30 4.3 120 1 1,2,3,4,5
FPVAV-104 PARALLEL 245 50 1030 0.25 ECM 0.33 24250 1080 67.4 88 0.50 2.5 160 140 5 2 / 10 5 0.75 30 4.3 120 1 1,2,3,4,5
NOTES:
1. OPERATING FLUID IS 40% PROPYLENE GLYCOL.
2. CONTROL POWER TRANSFORMER SHALL BE PROVIDED.
3. CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLS UTILIZING BACNET PROTOCOL.
4. MINIMUM INLET STATIC PRESSURE INCLUDES PRESSURE DROPS ACROSS THE VAV BOX.
5. AIRFLOWS SHOWN ON PLANS ARE MAX. HEATING AIRFLOWS (MIN. PRIMARY FLOW PLUS FAN AIRFLOW).
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02 CD
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
NOT FOR
CONSTRUCTION
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
MECHANICAL SCHEDULES
XGFG182011
M-602
01/20/21
C. DAZE R. WEAVER
B. POOLE
FAN SCHEDULE (EF)
TAG NO. AREA SERVED
SERVICE USED
FOR FAN TYPE
ALTITUDE
(FT.)
AIRFLOW
(CFM)
FAN
SPEED
(RPM)
SPEED
CONTROL
EXTERNAL
STATIC
PRESSURE
(IN. W.G.)
SOUND
LEVEL
(LWA)
MOTOR
STARTER /
DISCONNECT
PROVIDED BY
INTERLOCK
WITH
DRIVE
TYPE
WEIGHT
(LBS) NOTESMIN. HP
OPERATING
BHP TYPE VOLTS PHASE
REF-101 140 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7000 311 NONE 0.3 62 0.75 0.52 ODP 208 1 MANUFACTURER N/A BELT 225 1,3,4,5
REF-102 140 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7000 311 NONE 0.3 62 0.75 0.52 ODP 208 1 MANUFACTURER N/A BELT 225 1,3,4,5
REF-103 153 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5
REF-104 152 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5
REF-105 152 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 2920 503 NONE 0.3 66 0.33 0.3 ODP 208 1 MANUFACTURER N/A BELT 125 1,3,4,5
REF-106 154 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 3700 363 NONE 0.3 60 0.5 0.36 ODP 208 1 MANUFACTURER N/A BELT 150 1,3,4,5
REF-107 154 - WAREHOUSE VENTILATION ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 3700 363 NONE 0.3 60 0.5 0.36 ODP 208 1 MANUFACTURER N/A BELT 150 1,3,4,5
REF-108 110 - LOCKERS EXHAUST ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 860 792 NONE 0.35 61 0.25 0.12 ODP 208 1 MANUFACTURER AHU-101 BELT 75 1,3,4,5
RF-101 AHU-101 RELIEF AIR ROOF-MOUNTED CENTRIFUGAL DOWNBLAST 886 7400 739 VFD 1.25 77 3 2.76 ODP 208 3 MANUFACTURER AHU-101 BELT 225 2,3,4,5,7
SF-101 128 - MECHANICAL VENTILATION CENTRIFUGAL INLINE 886 1750 1054 UNIT MOUNTED 0.25 70 0.75 0.23 ODP 208 1 MANUFACTURER N/A DIRECT 100 1,3,8
NOTES:
1. PROVIDE WITH MANUFACURER'S DISCONNECT.
2. MANUFACTURER PROVIDED VFD AND DISCONNECT WITH 0-10V DC SPEED CONTROL INPUT.
3. PROVIDE WITH CONTROL TRANSFORMER AND AUXILIARY CONTACT FOR RUN STATUS MONITORING TO THE DDC SYSTEM AND INTERLOCK AS NOTED.
4. PROVIDE WITH MANUFACTURER'S INSULATED ROOF CURB.
5. PROVIDE FAN WITH BELT GUARD AND BIRDSCREEN.
6. NOT USED.
7. PROVIDE WITH MANUFACTURERS INSULATED 16 INCH ROOF CURB.
8. PROVIDE DIRECT DRIVE FAN WITH UNIT MOUNTED SPEED CONTROLLER.
UNIT HEATER SCHEDULE (UH)
TAG NO. LOCATION
AIRFLOW
CONFIGURATION
MOUNTING
HEIGHT AFF
HEATING
CAPACITY
(MBH) (NOTE 5)
AIRFLOW
(CFM)
EWT
(DEG F)
LWT
(DEG F)
WATER
FLOW
(GPM)
WATER PRESS
DROP
(FT)
WEIGHT
(LBS)
ELECTRICAL
NOTESHP VOLTS PHASE
CUH-101 100 - VEST CABINET 0' - 0" 12.6 250 160 130 0.8 3.8 100 0.03 120 1 1,3,6
CUH-102 123 - VEST CABINET 0' - 0" 12.6 250 160 130 0.8 3.8 100 0.03 120 1 1,3,6
UH-101 128 - EXISTING MECH HORIZONTAL 10' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-102 140 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.03 120 1 1,2,3,4
UH-103 140 - WAREHOUSE VERTICAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.03 120 1 1,2,3,4
UH-104 140 - WAREHOUSE VERTICAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-105 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-106 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-107 140 - WAREHOUSE HORIZONTAL 14' - 10" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-108 140 - WAREHOUSE HORIZONTAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-109 140 - WAREHOUSE HORIZONTAL 16' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-110 153 - WAREHOUSE VERTICAL 17' - 0" 25 1000 160 130 1.8 1.0 50 0.03 120 1 1,2,3,4
UH-111 153 - WAREHOUSE VERTICAL 17' - 0" 25 1000 160 130 1.8 1.0 50 0.03 120 1 1,2,3,4
UH-112 154 - WAREHOUSE VERTICAL 16' - 0" 65 2500 160 130 4.5 3.0 85 0.33 120 1 1,2,3,4
UH-113 154 - WAREHOUSE VERTICAL 16' - 0" 65 2500 160 130 4.5 3.0 85 0.33 120 1 1,2,3,4
UH-114 153 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-115 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-116 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-117 152 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-118 154 - WAREHOUSE HORIZONTAL 15' - 6" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-119 152 - WAREHOUSE HORIZONTAL 16' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-120 154 - WAREHOUSE HORIZONTAL 15' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-121 154 - WAREHOUSE HORIZONTAL 15' - 0" 20 1000 160 130 1.4 1.0 50 0.08 120 1 1,2,3,4
UH-122 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
UH-123 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
UH-124 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
UH-125 148 - LOADING DOCK HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
UH-126 149 - RAMP HORIZONTAL 8' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
UH-127 150 - STORAGE HORIZONTAL 12' - 4" 25 1100 160 130 1.8 1.0 50 0.08 120 1 1,2,3,4
NOTES:
1. PROVIDE WITH MANUFACTURER'S DISCONNECT FOR A SINGLE-POINT ELECTRICAL CONNECTION.
2. PROVIDE WITH MANUFACTURER'S STANDARD LOUVER AND WALL/CEILING MOUNTING BRACKET.
3. OPERATING FLUID IS 40% PROPYLENE GLYCOL.
4. PROVIDE WITH REMOTE WALL MOUNTED THERMOSTAT.
5 HEATING CAPACITY IS ACTUAL HEATING CAPACITY BASED ON INTERIOR HEATING TEMPERATURE OF 60 DEG F AND SCHEDULED OPERATING PARAMETERS.
6. PROVIDE WITH UNIT MOUNTED THERMOSTAT, AND MANUFACTURER CONTROL VALVE PACKAGE.
BASEBOARD HEATER SCHEDULE (BB)
TAG NO.
LOCATION
LENGTH
(FT)
HEATING
CAPACITY
(BTUH/FT)
(NOTE 4)
HEATING
CAPACITY
(BTUH/FT)
(NOTE 5)
EWT
(DEG. F)
FLOW
(GPM)
TUBE SIZE
(IN.)
MIN FINS
PER INCH
MOUNTING
HEIGHT
(IN.)
(NOTE 6)
NOTES
BB-101 104 - READINESS SUPER 7 1820 685 160 0.5 0.75 42 4 1,2,3
BB-102 102 - OPS OFFICER 9 1820 595 160 0.5 0.75 42 4 1,2,3
BB-103 101 - COMMANDER 16 1820 570 160 0.5 0.75 42 4 1,2,3
BB-104 113 - MOTHER'S ROOM 6 1820 490 143 0.5 0.75 42 4 1,2,3
BB-105 114 - 1ST SHIRT 6 1820 625 160 0.5 0.75 42 4 1,2,3
BB-106 115 - BREAK ROOM 25 1820 585 160 1.1 0.75 42 4 1,2,3
BB-107 116 - CHIEF ENLISTED MANAGER 8 1820 450 139 0.8 0.75 42 4 1,2,3
BB-108 117 - SUPPLY SUPER 7 1820 520 149 0.8 0.75 42 4 1,2,3
BB-109 118 - TMO SUPER 6 1820 610 160 0.8 0.75 42 4 1,2,3
BB-110 119 - WAREHOUSE SUPER 8 1820 450 137 1.0 0.75 42 4 1,2,3
BB-111 120 - LGLO SUPER 7 1820 520 145 1.0 0.75 42 4 1,2,3
BB-112 121 - OPEN OFFICE 10 1820 660 160 1.0 0.75 42 4 1,2,3
BB-113 127 - TMO OFFICE / VEHICLE OPS 17 1820 955 160 1.2 0.75 42 4 1,2,3
BB-114 129 - DEPLOYMENT CONTROL CENTER 12 1820 590 160 0.9 0.75 42 4 1,2,3
BB-115 129 - DEPLOYMENT CONTROL CENTER 7 1820 590 160 0.9 0.75 42 4 1,2,3
BB-116 130 - LOGISTICS PLAN 17 1820 540 160 0.7 0.75 42 4 1,2,3
BB-117 127 - TMO OFFICE / VEHICLE OPS 17 1820 550 160 0.7 0.75 42 4 1,2,3
NOTES:
1. PROVIDE ONE TIER SINGLE PASS COPPER TUBE WITH ALUMINUM FINS. PROVIDE ENCLOSURE WITH SLOPED TOP.
2. PROVIDE WALL BRACKETS AND HANGERS AS REQUIRED. PROVIDE EMPTY SECTIONS OF ENCLOSURE TO EXTEND FROM WALL TO WALL. PROVIDE ACCESS
DOORS FOR ALL VALVES.
3. HEATING FLUID IS 40% POLYPROPYLENE GLYCOL.
4. HEATING CAPACITY BASED ON STANDARD 1 PSI STEAM AT 65 DEG ROOM TEMP.
5. HEATING CAPACITY BASED ON SCHEDULED WATER TEMPERATURE, FLUID, HEATING ROOM TEMP OF 68 DEG F, AND ALL OTHER AS PROVIDED CONDITIONS.
6. MOUNTING HEIGHT MEASURED FROM BASE OF UNIT COVER TO FINISHED FLOOR.
DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)
TAG NO. DESCRIPTION SYSTEM NAME
MODEL THROW
PATTERN DAMPER MOUNTING
BLADE
SPACING NOTESTITUS PRICE KRUEGER
A 24"x24" PLAQUE FACE DIFFUSER SUPPLY OMNI ASPD 5PLQ 4W NONE LAY-IN - 1,5
B LOUVERED FACE GRILLE SUPPLY 272FS 22S 800 TWO WAY INTEGRAL SURFACE 3/4" 1,2,6
C 24"x24" EGGCRATE GRILLE RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,5
D 24"x24" EGGCRATE GRILLE TRANSFER 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,3,5
E 10"x10" EGGCRATE GRILLE RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE SURFACE 1/2" 1,5
F 12"x12" EGGCRATE GRILL RETURN / EXHAUST 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,5
G 24"x12" EGGCRATE GRILLE TRANSFER 45F 85 EGC545 45 DEGREE NONE LAY-IN 1/2" 1,4,5
H LOUVERED FACE GRILLE RETURN / EXHAUST 350FL 630 S80 30 DEGREE NONE SURFACE 3/4" 1,2,6
J LOUVERED FACE GRILLE RETURN / EXHAUST 350FL 630 S80 30 DEGREE NONE DUCT 3/4" 1,2,6
K LOUVERED FACE GRILLE TRANSFER 350FL 630 S80 30 DEGREE NONE SURFACE 3/4" 1,2,6
NOTES:
1. SEE PLANS FOR NECK SIZE. WHERE NOT NOTED, BRANCH DUCT SIZE SHALL BE THE SAME AS THE DIFFUSER NECK SIZE.
2. SEE PLANS FOR FACE SIZE.
3. PROVIDE WITH 10" X 10" ACOUSTICALLY LINED 90 DEG ANGLE TRANSFER AIR BOOT.
4. PROVIDE WITH 22" X 10" ACOUSTICALLY LINED 90 DEG ANGLE TRANSFER AIR BOOT.
5. FINISH TO MATCH CEILING.
6. FINISH TO MATCH WALL/STRUCTURE PAINTING.
DRAWINGS. PROVIDE TRANSFORMER IF SELECTED ACTUATORS REQUIRE.
2. PROVIDE POWER FROM UNIT SERVED OR POWER SERVICE SHOWN ON ELECTRICAL
1. EXISTING. ACTUAL DIMENSIONS MAY BE DIFFERENT THAN WHAT IS SCHEDULED.
NOTES:
CD-24 REF-104 OA 80 18 PARALLEL 1
CD-23 REF-102 OA 44 18 PARALLEL 1
CD-22 REF-101 OA 44 18 PARALLEL 1
CD-21 SF-101 EA 48 24 PARALLEL 1
CD-14 REF-107 OA 60 36 PARALLEL 2
CD-13 REF-106 OA 60 36 PARALLEL 2
CD-12 REF-107 EA 30 30 PARALLEL 2
CD-11 REF-106 EA 30 30 PARALLEL 2
CD-10 REF-105 EA 24 24 PARALLEL 2
CD-09 REF-104 EA 24 24 PARALLEL 2
CD-08 REF-103 EA 24 24 PARALLEL 2
CD-07 REF-102 EA 42 42 PARALLEL 2
CD-06 REF-101 EA 42 42 PARALLEL 2
CD-05 REF-108 EA 16 16 PARALLEL 2
CD-04 SF-101 OA 18 18 PARALLEL 2
CD-03 AHU-101 RA 48 18 OPPOSED 2
CD-02 AHU-101 OA 48 20 OPPOSED 2
CD-01 AHU-101 OA 16 14 OPPOSED 2
TAG UNIT SYSTEM
WIDTH
(IN)
HEIGHT
(IN)
BLADE
ACTUATION
REMARKS
CONTROL DAMPER SCHEDULE (CD)
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02 CD
VAV-109 & BB-117
TYPICAL FOR ALL VAV
GENERAL:
CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLLER. THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF OPERATION: UNOCCUPIED, WARM-UP, COOL-DOWN, AND OCCUPIED.
UNOCCUPIED:
UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.
VAV DAMPER SHALL BE AT MINIMUM POSITION.
IF THE ZONE TEMPERATURE FALLS BELOW OR RISES ABOVE THE UNOCCUPIED HEATING OR COOLING TEMPERATURE SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN
"OCCUPIED" MODE UNTIL THE SETPOINT HAS BEEN SATISFIED.
ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE TERMINAL UNIT SHALL GO INTO
OCCUPIED MODE FOR ONE HOUR (ADJ) AND THEN REVERT TO UNOCCUPIED MODE.
WARM-UP/COOL-DOWN:
VAV BOX DAMPER AND HEATING VALVE SHALL MODULATE AS DESCRIBED IN THE "OCCUPIED" MODE SECTION.
OCCUPIED:
OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM.
ZONE TEMPERATURE CONTROL (DUAL MAXIMUM – NO BASEBOARD HEATER): VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE VAV BOX HOT WATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW AND THE VAV BOX HOT WATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE VAV BOX HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. AS THE FIRST STAGE, THE AIRFLOW SETPOINT SHALL BE AT MINIMUM FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT. IF THE DISCHARGE AIR TEMPERATURE IS AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE AND THE ZONE IS STILL CALLING FOR HEATING, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN MINIMUM AND HEATING MAXIMUM FLOW TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT WHILE THE DISCHARGE AIR TEMPERATURE IS MAINTAINED AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE. THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT IS GIVEN IN THE VAV TERMINAL UNIT SCHEDULE.
ZONE TEMPERATURE CONTROL (PAIRED WITH BASEBOARD HEATER): VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE VAV BOX HOT WATER VALVE AND THE BASEBOARD HEATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW AND THE VAV BOX HOT WATER VALVE AND THE BASEBOARD HEATER VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE VAV BOX HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. AS THE FIRST STAGE, THE AIRFLOW SETPOINT SHALL BE AT MINIMUM FLOW AND THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT. IF THE DISCHARGE AIR TEMPERATURE IS AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE AND THE ZONE IS STILL CALLING FOR HEATING, THE BASEBOARD HEATER CONTROL VALVE SHALL BE OPENED WHILE THE DISCHARGE AIR TEMPERATURE IS MAINTAINED AT MAXIMUM HEATING SUPPLY AIR TEMPERATURE. THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT IS GIVEN IN THE VAV TERMINAL UNIT SCHEDULE.
ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED SETPOINT (CLG/HTG) PLUS/MINUS THE OCCUPANT ADJUSTMENT.
SEQUENCE OF OPERATION - VAV TERMINAL UNIT WITH HOT WATER REHEAT
SUPPLY
AIR
VAV-SA-F
H
HWR
HWS
VAV BOX DAMPER
VAV BOX
CONTROLLER
STAT
HEATING
COIL
VHTG-V-C
VAV-D-C
ZN-T
ZN-T-SP-ADJ
UNOCC-OVRD
VAV-DA-T
VHTG-V-S
HWR
BHTG-V-S
HWS
WHEN VAV TERMINAL UNIT IS
PAIRED WITH BASEBOARD HEATER
(SEE HVAC PIPING PLANS)
BHTG-V-C
BASEBOARD
HEATER
FPVAV-101
TYPICAL FOR ALL FPVAV
GENERAL:
CONTROLS CONTRACTOR TO PROVIDE UNIT CONTROLLER. THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF
OPERATION: UNOCCUPIED, WARM-UP, COOL-DOWN, AND OCCUPIED.
UNOCCUPIED:
UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.
VAV DAMPER SHALL BE CLOSED.
FAN SHALL BE OFF.
IF THE ZONE TEMPERATURE FALLS BELOW UNOCCUPIED HEATING SETPOINT, THE VAV BOX PRIMARY DAMPER SHALL CLOSE, THE FAN SHALL RUN CONTINUOUSLY, AND THE HEATING VALVE SHALL MODULATE TO MAINTAIN ZONE HEATING TEMPERATURE
SETPOINT.
IF THE ZONE TEMPERATURE RISES ABOVE THE UNOCCUPIED COOLING SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN
"OCCUPIED" MODE UNTIL THE COOLING SETPOINT HAS BEEN SATISFIED.
AFTER THE ZONE TEMPERATURE HAS BEEN WITHIN SETPOINT FOR 15 MINUTES (ADJ) THE VAV DAMPER SHALL RETURN TO
MINIMUM POSITION AND THE FAN SHALL BE OFF.
ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE TERMINAL UNIT SHALL GO INTO OCCUPIED MODE FOR ONE HOUR (ADJ) AND THEN REVERT TO UNOCCUPIED
MODE.
WARM-UP/COOL-DOWN:
VAV BOX DAMPER, HEATING VALVE, AND FAN SHALL MODULATE AS DESCRIBED IN THE "OCCUPIED" MODE SECTION.
OCCUPIED:
OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM.
ZONE TEMPERATURE CONTROL: VAV BOX DAMPER SHALL MODULATE BETWEEN MINIMUM AND MAXIMUM POSITION TO MAINTAIN VAV BOX PRIMARY SUPPLY AIR FLOW AT SETPOINT AS MEASURED BY A MULTI-POINT FLOW SENSING ELEMENT AT THE INLET OF THE VAV BOX. WHEN THE ZONE TEMPERATURE IS ABOVE THE ZONE COOLING TEMPERATURE SETPOINT, THE AIRFLOW SETPOINT SHALL BE ADJUSTED BETWEEN THE MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN THE ZONE TEMPERATURE AT THE COOLING SETPOINT. THE HOT WATER VALVE SHALL BE CLOSED AND THE FAN SHALL BE DE-ENERGIZED.
WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING AND HEATING SETPOINTS THE PRIMARY AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW, THE HOT WATER VALVE SHALL BE CLOSED, AND THE FAN SHALL BE DE-ENERGIZED. WHEN THE ZONE TEMPERATURE IS BELOW THE ZONE HEATING TEMPERATURE SETPOINT, THE PRIMARY AIRFLOW SHALL BE MAINTAINED AT MINIMUM FLOW, THE FAN SHALL RUN AT A CONSTANT SPEED, AND THE HEATING VALVE SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT. THE DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE ADJUSTED BETWEEN 55 DEGREES F (ADJ) AND THE MAXIMUM HEATING SUPPLY AIR TEMPERATURE SETPOINT TO MAINTAIN THE ZONE TEMPERATURE AT
THE HEATING SETPOINT.
ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED SETPOINT (CLG/HTG)
PLUS/MINUS THE OCCUPANT ADJUSTMENT.
SAFETY CONTROLS:
THE FAN SHALL START AND STOP AS ALLOWED BY THE INTERNAL SAFETIES OF THE VAV BOX CONTROLLER.
SEQUENCE OF OPERATION - PARALLEL FAN POWERED VAV TERMINAL UNIT WITH HOT
WATER REHEAT
SUPPLY
AIR
VAV-SA-F
H
HWR
HWS
VAV BOX DAMPER
VAV BOX
CONTROLLER
STAT
HEATING
COIL
VHTG-V-C
VAV-D-C
ZN-T
ZN-T-SP-ADJ
MS
VAV-FAN-SS
FROM
PLENUM
VAV-DA-T
PARALLEL
FAN
UNOCC-OVRD
VHTG-V-S
BB-104 ONLY
GENERAL:
THE HVAC SYSTEM SHALL HAVE THE FOLLOWING MODES OF OPERATION:
UNOCCUPIED AND OCCUPIED.
UNOCCUPIED:
UNOCCUPIED MODE SHALL BE INITIATED BY THE DDC SYSTEM.
IF THE ZONE TEMPERATURE FALLS BELOW THE UNOCCUPIED HEATING
TEMPERATURE SETPOINT, THE UNIT SHALL OPERATE AS DESCRIBED IN
"OCCUPIED" MODE UNTIL THE SETPOINT HAS BEEN SATISFIED.
ZONE UNOCCUPIED OVERRIDE: THE THERMOSTAT SHALL HAVE AN
UNOCCUPIED OVERRIDE BUTTON. UPON THE BUTTON BEING DEPRESSED THE
TERMINAL UNIT SHALL GO INTO OCCUPIED MODE FOR ONE HOUR (ADJ) AND
THEN REVERT TO UNOCCUPIED MODE.
OCCUPIED:
OCCUPIED MODE SHALL BE INITIATED BY THE CONTROLS SYSTEM. WHEN THE
ZONE TEMPERATURE IS ABOVE HEATING SETPOINT THE BASEBOARD HEATING
VALVE SHALL BE CLOSED. WHEN THE ZONE TEMPERATURE IS BELOW THE
ZONE HEATING TEMPERATURE SETPOINT, THE BASEBOARD HEATING VALVE
SHALL OPEN.
ZONE TEMPERATURE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO
ADJUST THE ZONE TEMPERATURE SETPOINT COOLER OR WARMER AT THE
THERMOSTAT. THE ZONE TEMPERATURE SETPOINT SHALL BE THE STORED
SETPOINT (CLG/HTG) PLUS/MINUS THE OCCUPANT ADJUSTMENT.
SEQUENCE OF OPERATION - INDIVIDUAL
BASEBOARD UNIT HEATER CONTROL
STAT
ZN-T
ZN-T-SP-ADJ
UNOCC-OVRD
HWR
BHTG-V-S
HWS
BHTG-V-S
BASEBOARD HEATER
S c a le
F o r M ic ro fi lm in g
In c h e s
M ill im e te rs
D
C
A
B
E
D
C
A
B
E
D
C
A
B
E
5 61 2 3 4
5 61 2 3 4
127591 date detailed checkeddesigned project contract rev.drawing file
DATEREV.
REVISIONS
DESCRIPTION INIT
TRUAX FIELD AIR NATIONAL GUARD BASE,
DANE COUNTY REGIONAL AIRPORT,
MADISON, WISCONSIN
9450 WARD PARKWAY, KANSAS
CITY, MISSOURI 64114
Project No. -
NOT FOR
CONSTRUCTION
F-35 ADAL B510 WAREHOUSE
AND SUPPLY
HVAC CONTROLS - VAV TERMINAL UNITS
XGFG182011
M-706
01/20/21
C. DAZE R. WEAVER
B. POOLE
NTSSCALE:D4
VAV TERMINAL UNIT WITH HOT WATER REHEAT
NTSSCALE:C4
PARALLEL FAN POWERED VAV TERMINAL UNIT WITH HOT
WATER REHEAT
4) ALARM CONDITIONS MARKED WITH A DOUBLE ASTERISK (**) SHALL BE ACTIVE ONLY WHEN THE SYSTEM IS IN OCCUPIED MODE AND HAS BEEN IN OCCUPIED MODE FOR MORE THAN 30 MINUTES.
3) SYS-OCC: OVERRIDE OF SYS-OCC IS ACCOMPLISHED THROUGH THE SYSTEM SCHEDULER.
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE GENERAL POINTS SCHEDULE NOTES ON THE CONTROLS LEGEND DRAWING.
NOTES:
VAV-DA-T-SP VAV DISCHARGE AIR TEMPERATURE SETPOINT ~ ~ ~ ~ X ~ ~ X ~ ~
VAV-DA-T VAV DISCHARGE AIR TEMPERATURE ~ <___> AI ~ X X ~ ~ ~ ~
VHTG-V-S VAV BOX HEATING VALVE POSITION STATUS ~ 0-100% OPEN AI ~ X ~ ~ ~ ~ ~
VHTG-V-C VAV BOX HEATING VALVE COMMAND ~ 0-100% OPEN AO ~ X ~ X X ~ ~
BHTG-V-S BASEBOARD HEATING VALVE POSITION STATUS (WHERE PAIRED) ~ OPEN/CLOSED BI ~ X ~ ~ ~ ~ ~
BHTG-V-C BASEBOARD HEATING VALVE COMMAND (WHERE PAIRED) ~ OPEN/CLOSED BO ~ X ~ X X ~ ~
VAV-D-C VAV DAMPER COMMAND ~ 0-100% OPEN AO ~ X X ~ ~ ~ ~
VAV-SA-F-SP VAV SUPPLY AIR FLOW SETPOINT ~ ~ ~ ~ X ~ ~ ~ ~ ~
VAV-SA-F VAV SUPPLY AIR FLOW ~ <___> AI ~ X ~ ~ ~ ~ ~
ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE (CLG/HTG) 80/66 DEG ~ ~ ~ X ~ X X ~ ~
ZN-T-SP-ADJ ZONE TEMPERATURE SETPOINT OCCUPANT ADJUSTMENT
OCCUPANT
ADJUSTABLE
±1 DEG F AI ~ X ~ X X ~ ~
ZN-T-SP ZONE TEMPERATURE SETPOINT (CLG/HTG) 78/68 DEG ~ ~ ~ X ~ X X ~ ~
ZONE TEMPERATURE
CONTROL
ZN-T ZONE TEMPERATURE ** ~ <___> AI ~ X X ~ ~
** ZN-T 2 DEG F MORE THAN ZN-T-SP-CLG OR LESS
THAN ZN-T-SP-HTG
INFO
EFF-OCC EFFECTIVE OCCUPANCY ~ OCC/UNOCC NVO ~ X ~ ~ ~ ~ ~
UNOCC-OVRD UNOCCUPIED OVERRIDE INPUT (OVERRIDE BUTTON ON STAT) ~ ~ BI ~ ~ ~ ~ ~ ~ ~START/STOP
SYS-OCC OCCUPANCY INPUT (FROM SYSTEM SCHEDULER) ~ ~ NVI ~ X ~ SEE NOTES ~ ~
FUNCTION NAME DESCRIPTION
SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
DISP
REQ'D
TREND
REQ'D
LDP
VIEW
REQ'D
M&C
LDP
OVRD
REQ'D
M&C
OVRD
REQ'D
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
LDP AND M&C DISPLAY OVERRIDES ALARMS
POINTS LIST SCHEDULE - VAV TERMINAL UNIT WITH HOT WATER REHEAT
NTSSCALE:C1
INDIVIDUAL BASEBOARD UNIT HEATER
SYM DATE DESCRIPTION APR
0 09/17/2021 ISSUED FOR BID
1 03/01/2022 ADDENDUM 02 CD
| GC003 STAGING AND LAYDOWN PLAN |
| S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW |
| Sheets |
| S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW |
| S-301 - NEW ADDITION BUILDING SECTIONS |
| S-301 - NEW ADDITION BUILDING SECTIONS |
| Sheets |
| S-201 - CMU AND CONCRETE WALL ELEVATIONS - NEW |
| S-301 - NEW ADDITION BUILDING SECTIONS |
| B510_ADD-02_Arch Sheets |
| Sheets |
| A-103 - GROUND FLOOR PLAN - AREA C |
| A-201 - EXTERIOR BUILDING ELEVATIONS - BASE BID |
| A-312 - WALL SECTIONS |
| A-352 - SECTION DETAILS |
| B510_M_B-3 ADDENDUM 02 |
| 127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-113 - HVAC PLAN - AREA C |
| 127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-601 - MECHANICAL SCHEDULES |
| 127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-602 - MECHANICAL SCHEDULES |
| 127591_B510_M_CENTRAL_bpoole@burnsmcd.com - Sheet - M-706 - HVAC CONTROLS - VAV TERMINAL UNITS |
File details come from the government source that posted it. Updated .