Attachment 1 Vol 1b Drawings Landscape Structural.pdf
PDF 39 MB Posted
- Attached to
- WA State ANG Construct Air Support Group Operations Complex (ASOG) Solicitation Federal contract opportunity
- Solicitation number
- W50S9E23B0002
- Issued by
- Department of the Army National Guard
About this file
This file is an attachment to a federal contract solicitation. The solicitation seeks to construct an Air Support Group Operations Complex for the Washington State Air National Guard. It requests the design and construction of landscape and structural elements, as indicated by the file name and 39MB size. The solicitation was issued by the Department of the Army National Guard under number W50S9E23B0002. Responses are due based on the standard timeline for a construction solicitation of this scope. The selected contractor will be responsible for completing the project delivery within the established performance period.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
S
S
HH
HH
HH HH
S
H
H
HH
E
MH
E
MH
HH
HH
HHHH
H
H
T
INFANTRY DRIVE
BLDG 116
AMERICAN LAKE
B
L
D
G
B
B
Q U
A R
T E
R M
A S
T E
R R
O A
D
B-1
H
I
H
W
A
T E
R
M
R
K
O
B
S
E
R
V
O
R
E
L
I
N
E
B
U
F
F
L
I
N
E
AIR SUPPORT
OPERATIONS CENTER
C
O
A
T
T
I
L
L
E
Y
O
A
D
41ST DIVISION WAY
F
N
C
E
B
U
F
F
N
E
L101
L102
L103
A R
M O
R
D
R I V
E
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
6060 0
SCALE IN FEET
OVERALL PLANTING PLAN
10078627-00L100.DWG
1" = 60'
L100
GENERAL NOTES
KEY NOTES
T
R
K
O
B
S
E
R
V
O
R
E
L
I
N
E
B
U
F
F
N
E
N
C
E
B
U
F
F
N
E
HH
E
MH
HH
HHHH
H
H
FH
MH
CB
CB DIV
CB
CB
FH
LP
FH
CB
CB
MH
C
O
A
T
I
L
L
E
A
D
AIR SUPPORT OPERATIONS CENTER
Q
U
A
R
T E
R
M
A
S
T E
R
CAMPGROUND
AMERICAN
LAKE
BLDG 116
SHORELINE
B-1
B-3
B-2
R
O
A
D
GENERAL NOTES
KEY NOTES
MATCHLINE - SEE SHEET L103 MATCHLINE - SEE SHEET L102
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
05 , TYP.
05 DECIDUOUS TREE PLANTING, 5 / L501
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
PLANTING PLAN
10078627-00L101.DWG
1" = 30'
L101
T
R
K
O
B
S
E
R
V
O
R
E
L
I
N
E
B
U
F
F
N
E
N
C
E
B
U
F
F
N
E
HH
E
MH
HH
HHHH
H
H
FH
MH
CB
CB DIV
CB
CB
FH
LP
FH
CB
CB
MH
C
O
A
T
I
L
L
E
A
D
AIR SUPPORT OPERATIONS CENTER
Q
U
A
R
T E
R
M
A
S
T E
R
CAMPGROUND
AMERICAN
LAKE
BLDG 116
SHORELINE
B-1
B-3
B-2
R
O
A
D
GENERAL NOTES
KEY NOTES
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
3030 0
SCALE IN FEET
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
PLANTING PLAN
BID OPTION 1A
10078627-00L101-1A.DWG
L101-1A
T
R
K
O
B
S
E
R
V
O
R
E
L
I
N
E
B
U
F
F
N
E
N
C
E
B
U
F
F
N
E
HH
E
MH
HH
HH
HH
H
H
HHHH
H
H
HH
H
H
FH
MH
CB
LP
CB DIV
CB
CB
FH
LP
FH
CB
CB
CB
CB
MH
C
O
A
T
I
L
L
E
A
D
AIR SUPPORT OPERATIONS CENTER
Q
U
A
R
T E
R
M
A
S
T E
R
CAMPGROUND
AMERICAN
LAKE
BLDG 116
SHORELINE
B-1
B-3
B-2
R
O
A
D
GENERAL NOTES
KEY NOTES
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
3030 0
SCALE IN FEET
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
PLANTING PLAN
BID OPTION 1B
10078627-00L101-1B.DWG
L101-1B
T
R
K
O
B
S
E
R
V
O
R
E
L
I
N
E
B
U
F
F
N
E
N
C
E
B
U
F
F
N
E
HH
E
MH
HH
HH
HH
H
H
HHHH
H
H
HH
H
H
H
H
FH
LP
LP
MH
LP
CB
LP
CB DIV
CB
CB
FH
LP
FH
CB
CB
CB
CB
MH
C
O
A
T
I
L
L
E
A
D
AIR SUPPORT OPERATIONS CENTER
Q
U
A
R
T E
R
M
A
S
T E
R
CAMPGROUND
AMERICAN
LAKE
BLDG 116
SHORELINE
B-1
B-3
B-2
R
O
A
D
GENERAL NOTES
KEY NOTES
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
3030 0
SCALE IN FEET
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
PLANTING PLAN
BID OPTION 4
10078627-00L101-4.DWG
1" = 30'
L101-4
05 , TYP.
05 DECIDUOUS TREE PLANTING, 5 / L501
CO
S
S
S
HH
HH HH
HH
E
MH
HH
DRAINAGE SWALE DRAINAGE SWALE
CO
LP
FH
LP
MH
MH
CB
CB
INFANTRY DRIVE
BLDG 116
AIR SUPPORT OPERATIONS CENTER
LP
MH
MH
GENERAL NOTES
KEY NOTES
MATCHLINE - SEE SHEET L101
M A
T C
H L
I N
E
S
E
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
10 RECONSTRUCT LANDSCAPE WALL. MATCH
EXISTING SIZE, TYPE, AND HEIGHT. SEE SHEET
C102
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
08 SOIL PREPARATION 2, 2 / L502
TYP.
PLANTING PLAN
10078627-00L102.DWG
1" = 30'
L102
EXISTING TREE TO PROTECT & REMAIN, FORM
5' DIA. MULCH RING AROUND BASE, TYP.
S
S
HH
HH HH
HH
H
H
E
MH
HH
DRAINAGE SWALE DRAINAGE SWALE
CO
LP
LP
LP
LP
LP
LP
FH
LP
MH
MH
MH
CB
CB
CB
INFANTRY DRIVE
BLDG 116
AIR SUPPORT OPERATIONS CENTER
CB
LP
MH
MH
GENERAL NOTES
KEY NOTES
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
01 TRIANGULAR PLANT SPACING, 1 L501
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
02 GROUNDCOVER PLANTING, 2 / L501
04 SHRUB PLANTING, 4 / L501
05 DECIDUOUS TREE PLANTING, 5 / L501
07 SOIL PREPARATION 1, 1 / L502
08 SOIL PREPARATION 2, 2 / L502
09 LANDSCAPE MOW STRIP, 3 / L502
TYP.
09 , TYP.
TYP.
TYP.
TYP.
PLANTING PLAN
BID OPTION 2
10078627-00L102-2.DWG
1" = 30'
L102-2
CO
S
S
S
HH
HH HH
HH
E
MH
HH
DRAINAGE SWALE DRAINAGE SWALE
CO
LP
LP
FH
LP
MH
MH
CB
CB
INFANTRY DRIVE
BLDG 116
AIR SUPPORT OPERATIONS CENTER
LP
MH
MH
GENERAL NOTES
KEY NOTES
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
01 TRIANGULAR PLANT SPACING, 1 L501
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
02 GROUNDCOVER PLANTING, 2 / L501
04 SHRUB PLANTING, 4 / L501
05 DECIDUOUS TREE PLANTING, 5 / L501
07 SOIL PREPARATION 1, 1 / L502
09 LANDSCAPE MOW STRIP, 3 / L502
02 , TYP.
, TYP.
TYP.
TYP.
8'
11'
5', TYP.
TYP.
16'-6" 18' 23'
3'
TYP.
PLANTING PLAN
BID OPTION 4
10078627-00L102-4.DWG
1" = 30'
L102-4
ALIGN WITH
BLDG CORNER
ALIGN LITTLE BUNNY
FOUNTAIN GRASS
WITH WINDOWS, TYP.
SET STEM OF TREE 3'
CLEAR OF BLDG, TYP.
O
R
E
L
I
N
E
B
U
F
F
N
E
H
I
T
R
K
O
B
S
E
R
V
S
S
S
H
H
D R
A
IN
A G
E S
W A
LE
CB
MH
FH
MH
MH
MH
SHORELINE
41ST DIVISION WAY
AMERICAN
LAKE
AIR SUPPORT
OPERATIONS CENTER
BLDG 112
GENERAL NOTES
KEY NOTES
MATCHLINE - SEE SHEET L101
M A
T C
H L
I N
E
S
E
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
05 DECIDUOUS TREE PLANTING, 5 / L501
TYP.
PLANTING PLAN
10078627-00L103.DWG
1" = 30'
L103
TYP.
08 SOIL PREPARATION 2, 2 / L502
O
R
E
L
I
N
E
B
U
F
F
N
E
H
I
T
R
K
O
B
S
E
R
V
S
S
S
H
H
D R
A
IN
A G
E S
W A
LE
LP
LP
LP
LP
CB
MH
FH
MH
MH
MH
SHORELINE
41ST DIVISION WAY
AMERICAN
LAKE
AIR SUPPORT
OPERATIONS CENTER
BLDG 112
GENERAL NOTES
KEY NOTES
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
PLANTING PLAN
BID OPTION 3
10078627-00L103-3.DWG
L103-3
O
R
E
L
I
N
E
B
U
F
F
N
E
H
I
T
R
K
O
B
S
E
R
V
S
S
S
H
H
H
H
H H
D R
A
IN
A G
E S
W A
LE
CB
LP
MH
FH
MH
MH
MH
LP
SHORELINE
41ST DIVISION WAY
AMERICAN
LAKE
AIR SUPPORT
OPERATIONS CENTER
BLDG 112
GENERAL NOTES
KEY NOTES
3030 0
SCALE IN FEET
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
1. SEE SHEETS L501 AND L502 FOR LANDSCAPE
DETAILS.
2. SEE SHEET L601 FOR PLANTING SCHEDULE.
01 TRIANGULAR PLANT SPACING, 1 L501
02 GROUNDCOVER PLANTING, 2 / L501
04 SHRUB PLANTING, 4 / L501
05 DECIDUOUS TREE PLANTING, 5 / L501
07 SOIL PREPARATION 1, 1 / L502
09 LANDSCAPE MOW STRIP, 3 / L502
, TYP.
3'
3'
8'
3'-6"
6'
6'-6"
5', TYP.
, TYP.
TYP.
TYP.
PLANTING PLAN
BID OPTION 4
10078627-00L103-4.DWG
1" = 30'
L103-4
LANDSCAPE DETAILS
10078627-00L501.DWG
AS NOTED
L501
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
E
Q
EQ.
E
Q
MULCH LAYER,
KEEP AWAY FROM CROWN
REMOVE CONTAINER COMPLETELY AND
LOOSEN ROOTS PRIOR TO PLANTING
PREPARED SOIL, THOROUGHLY WATER,
SETTLE SOIL BACKFILL
EXISTING
SUBGRADE
VINE ROOTBALL SHALL ABUT SIDE OF WALL WITH
SECURELY PLACED, 3/4" DIA. WOOD STAKE
RETAINING WALL,
SCALE:
DECIDUOUS TREE PLANTING
NTS
CHAIN LOCK TREE TIE
2" DIA. WOOD TREE STAKE,
(2) PER TREE
TREE WITH STRONG
CENTRAL LEADER
MULCH LAYER, KEEP CLEAR
FROM TRUNK
4" HIGH SOIL SAUCER
BEYOND EDGE OF ROOT BALL
FINISH GRADE
3X ROOTBALL
ROOTBALL
M
I N
M
I N
H
T
M
I N
PREPARED SOIL
EXISTING SUBGRADE
REMOVE ALL TWINE, ROPE AND
BURLAP FROM TOP 1/2 OF
ROOTBALL AND FOLD DOWN
AROUND ROOTBALL. COMPLETELY
REMOVE WIRE BASKET.
TAMPED SOIL AROUND BASE
SCALE:
SHRUB PLANTING
NTS
TOP OF ROOT CROWN TO BE 1" HIGHER
THAN FINISH GRADE
FINISH GRADE
MULCH, KEEP MULCH LAYER AWAY FROM FOLIAGE
LOOSEN ROOTS OF POT BOUND PLANTS
PRIOR TO PLANTING
PREPARED SOIL COMPACTED TO
85% MAX. DENSITY
THOROUGHLY WATER, SETTLE SOIL BACKFILL
PLANTING HOLE TO BE 12" LARGER THAN ROOTBALL DIA.
SCALE:
GROUNDCOVER PLANTING
NTS
GROUNDCOVER PLANTING
PLANTING BED SLOPED FOR
ADEQUATE DRAINAGE
MULCH LAYER
PREPARED SOIL
EXISTING SUBGRADE
INSTALL TOP OF ROOT CROWN FLUSH TO FINISH GRADE
SCALE:
VINE PLANTING
NTS
LARGE SHRUB OR
TREE PLANTING
SMALL SHRUB OR
GROUNDCOVER
PLANTING
SCALE:
TRIANGULAR PLANT SPACING
NTS
L502
L502
L502
L502
L502
L502
L502
NOTE:
1. FOR TREES PLACED IN SEEDED AREAS
FORM 5' DIA. MULCH RING.
2. PROVIDE MULCH TYPE AS INDICATED IN
PLANS AND IN DETAILS 1/L502 & 2/L502.
NOTE:
PROVIDE MULCH TYPE AS INDICATED IN
PLANS AND IN DETAILS 1/L502 & 2/L502
NOTE:
PROVIDE MULCH TYPE AS INDICATED IN
PLANS AND IN DETAILS 1/L502 & 2/L502
LANDSCAPE DETAILS
10078627-00L502.DWG
AS NOTED
L502
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
INERT MULCH
TOPSOIL TYPE A
UNDISTURBED EXISTING SOIL
OR IMPORTED SOILS
COMPACTED TO 85% MAX
DENSITY
PLANTING AREA PREPARATION
CONSTRUCTION SEQUENCE:
1. AFTER CONCRETE AND OTHER
INFRASTRUCTURE WORK IS COMPLETED,
ESTABLISH SUBGRADE 15" BELOW ADJACENT
CURB OR PAVING IN MULCH AREAS.
2. REMOVE ALL DEBRIS INCLUDING STUMPS,
STICKS, ROOTS AND ROCKS OVER 1" AND
DISPOSE OFF SITE. ENG SHALL REVIEW AND
APPROVE SUBGRADE PRIOR TO
PROCEEDING WITH WORK.
3. PLACE 3" COMPACTED DEPTH OF COMPOST,
TILL INTO EXISTING SUBGRADE TO A DEPTH
OF 6". COMPACT TO 85% MAXIMUM DRY
DENSITY.
4. PLACE 12" DEPTH TOPSOIL FOR PLANTING
AREAS . COMPACT TO 85% MAXIMUM DRY
DENSITY. ENG SHALL REVIEW AND APPROVE
TOPSOIL INSTALLATION PRIOR TO
PROCEEDING WITH WORK.
5. PLACE NON-WOVEN WEED CONTROL FABRIC
SEPARATION. SEE NOTES FOR TREE
PLANTING.
6. CUT HOLE IN WEED CONTROL FABRIC 1X THE
SIZE OF SHRUB OR GROUNDCOVER
CONTAINER SIZE.
FINISH GRADE
AMENDED SUBGRADE SOILS
SCALE:
SOIL PREPARATION TYPE 1 (BUILDING PERIMETER & PARKING ISLANDS)
NTS
SCALE:
LANDSCAPE MOW STRIP
NTS
BARK MULCH
UNDISTURBED EXISTING SOIL
OR IMPORTED SOILS
COMPACTED TO 85% MAX
DENSITY
PLANTING AREA PREPARATION
CONSTRUCTION SEQUENCE:
1. AFTER CONCRETE AND OTHER
INFRASTRUCTURE WORK IS COMPLETED,
ESTABLISH SUBGRADE 6" BELOW ADJACENT
CURB OR PAVING IN MULCH AREAS.
2. REMOVE ALL DEBRIS INCLUDING STUMPS,
STICKS, ROOTS AND ROCKS OVER 1" AND
DISPOSE OFF SITE. ENG SHALL REVIEW AND
APPROVE SUBGRADE PRIOR TO
PROCEEDING WITH WORK.
3. PLACE 3" COMPACTED DEPTH OF COMPOST,
TILL INTO EXISTING SUBGRADE TO A DEPTH
OF 6". COMPACT TO 85% MAXIMUM DRY
DENSITY.
4. PLACE 3" DEPTH TOPSOIL FOR PLANTING
AREAS . COMPACT TO 85% MAXIMUM DRY
DENSITY. ENG SHALL REVIEW AND APPROVE
TOPSOIL INSTALLATION PRIOR TO
PROCEEDING WITH WORK.
5. INSTALL 3" DEPTH OF BARK MULCH FOR
TREE RINGS AND SHRUB / GROUNDCOVER
AREAS.
FINISH GRADE
AMENDED SUBGRADE SOILS
SCALE:
SOIL PREPARATION TYPE 2 (PARKING BUFFER & SEEDED LAWN)
NTS
PREPARED SOIL (TYPE 1)
THOROUGHLY WATER,
SETTLE SOIL BACKFILL
EXISTING SUBGRADE
4" DEPTH COMPACTED
SURFACING BASE COURSE
MULCH
SET MOW STRIP 1" ABOVE FINISH GRADE OF SEEDED LAWN,
MATCH INTO GRADE OF ADJACENT SIDEWALKS.
1/2" R. AT CORNERS, TYP., SEE NOTE 1.
10"
SEEDED
LAWN
6"
4"
PREPARED
SOIL
(TYPE 2)
NOTE:
PLANT TREES PRIOR TO PLACING WEED CONTROL FABRIC
FEATHER TOP OF MULCH
TO MEET TOP OF CURB
FINISH GRADE
NOTE:
PROVIDE EXPANSION JOIN SIMILAR
TO SIDEWALKS FOR EVERY 20 LINEAL
FEET OF MOW STRIP. PROVIDE CONTROL
JOINT EVERY 5 LINEAL FEET.
TOPSOIL TYPE A
M
A X
15" MIN.
QUERCUS GARRYANA /
GARRY OAK
8 5 / L501
BALLED & BURLAPPED, 2" CALIPER,
STREET TREE GRADE, SPACED PER PLANS
SYMBOL QTY. SCIENTIFIC NAME / COMMON NAME SIZE / REMARKS
PLANTING SCHEDULE: BID OPTION 2
TREES
ACER SACCHARUM 'GREEN MOUNTAIN' /
GREEN MOUNTAIN SUGAR MAPLE
QUERCUS GARRYANA /
GARRY OAK
DETAIL
5 / L501
5 / L501
BALLED & BURLAPPED, 2" CALIPER,
STREET TREE GRADE, SPACED PER PLANS
BALLED & BURLAPPED, 2" CALIPER,
STREET TREE GRADE, SPACED PER PLANS
CORNUS SERICEA 'KELSEYI' /
KELSEY DOGWOOD
RHUS AROMATICA /
FRAGRANT SUMAC
VACCINIUM OVATUM /
EVERGREEN HUCKLEBERRY
SHRUBS
#2 CONT., 3' O.C.
#3 CONT., 5' O.C.
#2 CONT., 3' O.C.
4 / L501
4 / L501
4 / L501
GROUNDCOVERS
JUNIPERUS CONFERTA 'BLUE PACIFIC' /
BLUE PACIFIC SHORE JUNIPER
191 #1 CONT., 30" O.C. 2 / L501
SYMBOL QTY. SCIENTIFIC NAME / COMMON NAME SIZE / REMARKS
PLANTING SCHEDULE: BID OPTION 4
TREES
DETAIL
ACER SACCHARUM 'GREEN MOUNTAIN' /
GREEN MOUNTAIN SUGAR MAPLE
POPULOUS TREMULOIDES 'NE-ARB' /
PRAIRIE GOLD ASPEN
5 / L501
5 / L501
BALLED & BURLAPPED, 2" CALIPER,
STREET TREE GRADE, SPACED PER PLANS
BALLED & BURLAPPED, 1.5" CALIPER,
SPACED PER PLANS
AMELANCHIER LAEVIS 'SNOWCLOUD' /
SNOWCLOUD SERVICEBERRY
12 5 / L501
BALLED & BURLAPPED, 1" CALIPER,
SPACED PER PLANS
LAVANDULA ANGUSTIFOLIA 'HIDCOTE BLUE' /
HIDCOTE BLUE ENGLISH LAVENDER
MAHONIA AQUIFOLIUM 'COMPACTA' /
COMPACT OREGON GRAPE
SHRUBS
#2 CONT., 3' O.C.
#2 CONT., 3' O.C.
4 / L501
4 / L501
ARCTOSTAPHYLOS UVA-URSI 'MASSACHUSETTS' /
MASSACHUSETTS KINNIKINNICK
GROUNDCOVERS
127 #1 CONT., 18" O.C. 2 / L501
53 SEDUM TELPHIUM 'AUTUMN JOY' /
AUTUMN JOY STONECROP
#3 CONT., 3' O.C. 2 / L501
96 PENNISETUM ALOPECUROIDES 'LITTLE BUNNY' /
LITTLE BUNNY DWARF FOUNTAIN GRASS
#1 CONT., 3' O.C.
2 / L501
SEEDED LAWN
SEEDING & RESTORATION
DRY NATIVE SEED MIX
SYMBOL SCIENTIFIC NAME / COMMON NAME SIZE / REMARKS
PLANTING SCHEDULE: BASE BID
DETAIL
SEE SPECIFICATIONS
SEE SPECIFICATIONS
2 / L502
TREES
QUERCUS GARRYANA /
GARRY OAK
16 5 / L501
BALLED & BURLAPPED, 2" CALIPER,
STREET TREE GRADE, SPACED PER PLANS
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
CAMP MURRAY
ASOG FACILITY
DATE
C
D
A
1 3 4 5 6 7 8
AIR SUPPORT
OPERATIONS CENTER
CHRIS MANZ
10078627
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
COMMUNICATIONS
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
M. ADKISON
04/30/2023 ISSUED FOR CONSTRUCTION
PLANTING SCHEDULE
10078627-00L601.DWG
NOT TO SCALE
L601
STRUCTURAL NOTES
APPLICABLE CODES AND STANDARDS:
1. INTERNATIONAL BUILDING CODE 2015.
2. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI-318-14.
3. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES ASCE 7-10.
4. AMERICAN INSTITUTE OF STEEL CONSTRUCTION AISC.
5. STEEL DECK INSTITUTE SPECIFICATIONS AND LOAD TABLES.
6. AISI SPECIFICATION FOR DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS.
7. STEEL JOISTS INSTITUTE, STANDARD SPECIFICATIONS, LOAD TABLES, AND WEIGHT TABLES
FOR STEEL JOISTS AND JOIST GIRDERS.
8. AMERICAN WELDING SOCIETY (AWS) D1.1, D1.3, D1.4.
9. ASTM MATERIAL STANDARDS AS NOTED.
10. BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES ACI
530-13 AND ACI 530.1-13.
11. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS (JUNE 2016 W/ CHANGE 2 NOV 2018).
12. UFC 3-301-01 STRUCTURAL ENGINEERING (JUNE 2013, W/ CHANGE 4 NOV 2018).
13. UFC 3-310-04 SEISMIC DESIGN FOR BUILDINGS (JUNE 2013, W/ CHANGE 1 JUNE 2016).
14. UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS (DEC 2018).
EXISTING CONDITIONS:
1. NOTIFY CONTRACTING OFFICER IMMEDIATELY IF EXISTING CONDITIONS DO NOT MATCH,
OR SEEM IN CONFLICT WITH INFORMATION SHOWN ON THE DRAWINGS.
GENERAL NOTES:
1. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE, NOT THE METHOD OF
CONSTRUCTION. SAFETY AND STRUCTURAL STABILITY DURING CONSTRUCTION ARE THE
SOLE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION,
INCLUDING BUT NOT LIMITED TO, BRACING, SHORING, FOR CONSTRUCTION LOADS AND
EQUIPMENT, ETC. THE CONTRACTOR IS RESPONSIBLE FOR THE CONTRACTOR’S MEANS
AND METHODS, SEQUENCES OF CONSTRUCTION, AND THE SAFETY PROGRAM.
OBSERVATION VISITS TO THE SITE BY THE CONTRACTING OFFICER WILL NOT INVOLVE
REVIEW OF THESE ITEMS.
2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE ARCHITECTURAL,
MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR LOCATION AND SIZE OF
OPENINGS, BLOCK OUTS, FLOOR DEPRESSIONS, CURBS, DIMENSIONS, ETC. NOT INDICATED
ON THE STRUCTURAL DRAWINGS. THE LOCATION AND SIZE OF MECHANICAL AND
ELECTRICAL OPENINGS IN SLABS, WALLS AND DECKS SHALL BE COORDINATED BY THE
CONTRACTOR. PROVIDE ALL ADDITIONAL FRAMING OR REINFORCING TO ACCOMMODATE
OPENINGS AS REQUIRED BY THE APPLICABLE STANDARD DETAILS, SECTIONS AND NOTES
AS SHOWN ON THE STRUCTURAL DRAWINGS.
3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED
CHANGES FOR APPROVAL.
4. CONTRACTOR IS TO ESTABLISH AND VERIFY EMBEDS AND INSERTS FOR ITEMS TO BE
INSTALLED BY OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND
CONSTRUCTION.
5. CONSTRUCTION MATERIAL AND EQUIPMENT PLACED ON FRAMED CONSTRUCTION SHALL
BE SUCH THAT THE LOAD DOES NOT EXCEED THE DESIGN LIVE LOAD OF THE
CONSTRUCTIONS. PROVIDE SHORING OF CONSTRUCTIONS WHERE NECESSARY FOR THE
LOADS.
6. DETAILS AND SECTIONS THAT ARE NOTED AS “TYP” ON DETAIL TITLES ARE TO BE APPLIED
TO THE PROJECT CONSTRUCTION AS GENERAL CONSTRUCTION METHODS UNLESS NOTED
OTHERWISE. THESE DETAILS ARE NOT CUT AT ALL LOCATIONS THEY OCCUR AND MAY BE
NOT CUT AT ALL.
7. CONTRACTOR TO SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING WEIGHTS,
VIBRATIONAL FORCES, SUPPORTED LOCATIONS, ALONG WITH ANY FLOOR OPENINGS,
NOTCHES, AND RECESSED REQUIRED BY SUCH EQUIPMENT. CONCRETE SUPPORT PADS
AND / OR FRAMING REQUIRED TO SUPPORT SAID EQUIPMENT SHALL NOT BE FABRICATED
AND PLACED UNTIL THE CONCRETE SUPPORT PADS AND / OR FRAMING IS APPROVED TO
SUPPORT THE EQUIPMENT.
BUILDING OCCUPANCY CATEGORY – RISK FACTOR:
1. RISK FACTOR - ASOC BUILDING: II
2. RISK FACTOR - PARKING SHEDS: II
SNOW LOAD:
1. SNOW LOADS IN ACCORDANCE WITH THE BUILDING CODE LISTED ABOVE.
2. GROUND SNOW LOAD, PG: 15 PSF
3. FLAT ROOF SNOW LOAD, PF: 9.5 PSF
4. THERMAL COEFFICIENT, Ct: 1.0
5. EXPOSURE COEFFICIENT, Ce: 0.9
WIND LOAD:
1. ASOC BUILDING
A. BASIC WIND SPEED (ULT): 110 MPH
B. EXPOSURE CATEGORY: C
C. ENCLOSED, GCP: +/- 0.18
2. PARKING SHEDS
A. BASIC WIND SPEED (ULT): 110 MPH
B. EXPOSURE CATEGORY: C
C. OPEN, GCP: 0.0
SEISMIC LOAD:
1. SPECTRAL RESPONSE ACCELERATIONS, SS: 1.291 g
2. SPECTRAL RESPONSE ACCELERATIONS, S1: 0.510 g
3. SPECTRAL RESPONSE COEFFICIENTS, SDS: 0.861 g
4. SPECTRAL RESPONSE COEFFICIENTS, SD1: 0.442 g
5. ASOC COMPLEX
A. IMPORTANCE FACTOR, IE: 1.0
B. SEISMIC DESIGN CATEGORY: D
C. SITE CLASS: C
D. SPECIAL REINFORCED MASONRY SHEAR WALLS
E. RESPONSE MODIFICATION FACTOR, R: 5
F. SEISMIC RESPONSE COEFFICIENT, CS: 0.172
G. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
6. PARKING SHELTERS
A. IMPORTANCE FACTOR, IE: 1.00
B. SEISMIC DESIGN CATEGORY: D
C. SITE CLASS: C
D. SPECIAL CANTILEVER COLUMNS
E. RESPONSE MODIFICATION FACTOR, R: 2.5
F. SEISMIC RESPONSE COEFFICIENT, CS: 0.344
MASONRY:
1. MASONRY WORK SHALL BE IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS
OF ACID 530 AND SPECIFICATION ACI 530.1.
2. THE COMPRESSIVE STRENGTH OF THE MASONRY UNITS SHALL BE 2800 PSI ON THE NET
AREA, PROVIDING A MINIMUM 28-DAY DESIGN COMPRESSIVE STRENGTH (F’M) OF 2000 PSI
BY THE UNIT STRENGTH METHOD.
3. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH (F’C) OF MASONRY GROUT SHALL BE
2700 PSI.
4. MORTAR SHALL CONFORM TO ASTM C270, TYPE M.
5. SEE TYPICAL BOND BEAM INTERSECTION DETAIL FOR MASONRY BOND BEAM DETAILS AND
COMPRESSIVE STRENGTH AND NOTES. LINTEL BLOCKS SHALL NOT BE USED AS BOND
BEAM BLOCKS EXCEPT AT OPENINGS WHERE BOND BEAMS AND LINTELS COINCIDE.
6. IF BOND BEAMS AT INTERSECTING WALLS ARE SHOWN ON THE DRAWINGS TO MEET AT
DIFFERENT ELEVATIONS, EXTEND BOND BEAM REINFORCING OF BOTH BOND BEAMS
AROUND INTERSECTING CORNER NOT LESS THAN 4 FEET IN EACH DIRECTION.
7. PROVIDE STANDARD 90 DEGREE HOOKS IN THE TOP BOND BEAM AT ALL VERTICAL WALL
REINFORCING.
8. SPLICE LENGTHS FOR MASONRY REINFORCEMENT SHALL BE 52 BAR DIAMETERS UNLESS
SHOWN OTHERWISE.
9. IN CASES WHERE REINFORCING BARS CANNOT BE EXTENDED AS FAR AS REQUIRED, THE
BARS SHALL EXTEND AS FAR AS POSSIBLE AND END WITH STANDARD HOOK.
10. MASONRY CONTRACTOR SHALL COORDINATE WITH MECHANICAL, ELECTRICAL, AND
OTHER CONTRACTORS AND BUILD IN OPENINGS FOR THE UTILITIES AND DUCTWORK
THAT EXCEED 16 INCHES IN WIDTH. PROVIDE ADDITIONAL REINFORCEMENT AT OPENINGS
AS INDICATED. DO NOT CUT REINFORCEMENT. OPENINGS SHALL BE COORDINATED
BEFORE CONSTRUCTING WALLS.
11. STRUCTURAL DRAWINGS SHOW ONE GENERIC MASONRY WALL TYPE. SEE ARCH.
DRAWINGS FOR MASONRY WALL TYPES.
STEEL BAR JOIST:
1. STEEL JOISTS ARE SIZED AS SHOWN ON THE DRAWINGS AND DESIGNED FOR LIVE LOADS
SHOWN ABOVE AND 35 PSF DEAD LOAD (ASD). SPECIAL LOADS ARE SHOWN ON THE
DRAWINGS. JOIST LABELED “SP” SHALL BE DESIGNED FOR THE CONCENTRATED AND / OR
SPECIAL LOADS INDICATED.
2. STEEL JOISTS, BRIDGING, AND BRACING SHALL BE DESIGNED BY THE MANUFACTURER TO
RESIST THE UPLIFTS SHOWN.
3. CONCENTRATED LOADS SHALL BE LOCATED WITHIN 4 INCHES OF A PANEL POINT OR
SPECIAL REINFORCEMENT MUST BE ADDED PER “TYPICAL JOIST REINFORCING @
CONCENTRATED LOAD DETAIL”.
4. SEE SPECIFICATION SECTION 01 45 35 FOR FABRICATOR SPECIAL INSPECTIONS
COMPOSITE BEAM SHEAR STUD PLACEMENT:
1. SHEAR STUDS SHALL BE 3/4 – INCH DIAMETER WITH A FINAL LENGTH OF 4-1/2 INCHES AFTER
ATTACHMENT. SEE DETAIL FOR STUD PLACEMENT.
2. WHEN NO STUDS ARE SHOWN, BEAMS ARE TO BE NON COMPOSITE BEAMS. PROVIDE SHEAR
STUDS ON ALL NON- COMPOSITE BEAMS W12 AND LARGER AT 1’-0” O.C.
STRUCTURAL FLOORS:
1. POUR CONCRETE ON FLOORS TO INDICATED ELEVATION. DUE TO THE CAMBER IN THE BEAMS, THE FINAL THICKNESS OF THE TOPPING WILL BE APPROXIMATELY AS SHOWN.
POST INSTALLED ANCHORS
1. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONTRACT
DRAWINGS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE CONTRACTING
OFFICER BEFORE INSTALLING POST INSTALLED ANCHORS FOR MISSING OR MISPLACED
CAST-IN-PLACE ANCHORS.
2. CARE SHALL BE TAKEN IN PLACING POST– INSTALLED ANCHORS TO AVOID CONFLICTS
WITH THE EXISTING REBAR. HOLES SHALL BE DRILLED AND CLEANED IN ACCORDANCE
WITH THE MANUFACTURER’S WRITTEN INSTRUCTIONS.
3. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW,
SHALL BE SUBMITTED BY THE CONTRACTOR TO THE CONTRACTING OFFICER ALONG
WITH CALCULATIONS THAT ARE PREPARED AND SEALED BY A REGISTERED
PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE
SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERTINENT EQUIVALENT DESIGN
PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE
APPROPRIATE DESIGN PROCEDURE AND/ OR STANDARDS(S). AS REQUIRED BY THE
BUILDING CODE. PRODUCT ICC-ES REPORTS SHALL BE INCLUDED WITH THE SUBMITTAL
PACKAGE.
4. UNLESS NOTED OTHERWISE ON PLANS, ACCEPTABLE CONCRETE ANCHORS PRODUCTS
SHALL BE:
A. MECHANICAL ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE
SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI
355.2 AND ICC-ES AC193. PRE-APPROVED MECHANICAL ANCHORS INCLUDE:
I. KWIK BOLT TZ (ICC-ES ESR 1917) BY HILTI, INC.
II. TRUBOLT+ (ICC-ES ESR-2427) BY ITW RAMSET/REDHEAD.
III. STRONG BOLT (ICC-ES ESR-1771) AND STRONG BOLT 2 (ICC-ES
ESR-3037) BY SIMPSON STRONG TIE ANCHOR SYSTEMS.
B. ADHESIVE ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE
SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI
308. PRE- APPROVED ADHESIVE ANCHORS INCLUDE:
I. HIT-RE-500 SD (ICC-ES ESR 2322) SYSTEM ADHESIVE ANCHORS BY
HILTI, INC.
II. EPCON G5 (ICC-ES ESR-1137) ADHESIVE ANCHORING SYSTEM BY ITW
RAMSET/REDHEAD.
III. SET-XP (ICC-ES ESR-2508) ADHESIVE ANCHORING SYSTEMS BY SIMPSON
STRONG TIE ANCHOR SYETEMS.
C. CONCRETE SCREW ANCHORS FOR USE IN CRACKED AND UNCRACKED
CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN
ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. PRE-APPROVED SCREW
ANCHORS INCLUDE:
I. KWIK HUS-EZ (ICC-ES ESR-3027) BY HILTI, INC.
II. TITAN HD (ICC-ES ESR-2713) BY SIMPSON STRONG TIE ANCHOR
SYSTEMS.
EQUIPMENT BRACING
1. MECHANICAL AND ELECTRICAL EQUIPMENT WEIGHING 31 LBS OR MORE ( EXCLUDING
DISTRIBUTED SYSTEMS SUCH AS PIPING NETWORKS THAT COLLECTIVELY EXCEED THAT
WEIGHT) SHALL BE PROVIDED WITH MOUNTINGS ABLE TO RESIST FORCES 0.5 TIMES THE
EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT
WEIGHT IN THE DOWNWARD DIRECTION IN COMPLIANCE WITH UFC 4-010-01 STANDARD 19.
OVERHEAD MOUNTED ARCHITECTURAL FEATURES:
1. OVERHEAD MOUNTED ARCHITECTURAL FEATURES WEIGHING 31 LBS OR MORE
( EXCLUDING DISTRIBUTED SYSTEMS SUCH AS SUSPENDED CEILINGS THAT
COLLECTIVELY EXCEED THAT WEIGHT) SHALL BE PROVIDED WITH MOUNTINGS ABLE TO
RESIST FORCES 0.5 TIMES THE COMPONENT WEIGHT IN ANY HORIZONTAL DIRECTION AND
1.5 TIMES THE COMPONENT WEIGHT IN THE DOWNWARD DIRECTION IN COMPLIANCE WITH
UFC 4-010-01 STANDARD 15.
LIVE LOAD:
1. AREA 'D' (FITNESS AREA, VEHICLE MAINTENANCE,
WAREHOUSE AND MISC. ROOMS AND CORIDORS: 250 PSF
2. ALL OTHER ROOMS AND CORIDORS ON GROUND FLOOR: 100 PSF
3. ROOF 20 PSF
4. HVAC EQUIPMENT PLATFORM: 125 PSF
SOILS INVESTIGATION:
1. SOILS INVESTIGATION WAS MADE BY: ASPECT CONSULTING
2. DATED: JAN 2019 (DRAFT)
3. SPREAD FOOTINGS: 4000 PSF ( DL + LL)
4. CONTINUOUS FOOTINGS: 4000 PSF ( DL + LL)
5. INDIVIDUAL FOOTINGS: 4000 PSF ( DL + LL)
6. MINIMUM BOTTOM FOOTING DEPTH 18-INCHES BELOW GRADE
7. EQUIVALENT ACTIVE FLUID PRESSURE, DRAINED: 35 PCF
8. EQUIVALENT AT REST FLUID PRESSURE, DRAINED: 55 PCF
9. COEFFICIENT OF FRICTION: 0.45
10. MINIMUM FACTOR OF SAFETY: 1.5
RETAINING WALL CONSTRUCTION:
1. WALLS TO BE DESIGNED BY CONTRACTOR. SEE SPECIFICATIONS.
CONCRETE NOTES:
1. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 301 AND
ACI 318.
2. PROVIDE A 2X4 FORMED CONSTRUCTION JOINT KEYWAY AT ALL HORIZONTAL AND
VERTICAL POURED EDGES.
3. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. REINFORCING STEEL TO BE
WELDED SHALL BE ASTM A 706, GRADE 60.
4. CONCRETE COVER REQUIREMENTS FOR REINFORCEMENT UNLESS NOTED OTHERWISE
ON THE DETAILS OR SECTIONS:
CONCRETE CAST AND PERMANENTLY EXPOSED TO EARTH: 3”
CONCRETE EXPOSED TO EARTH OR WEATHER:#6 BARS AND LARGER 2”
#5 BARS AND SMALLER 1-1/2”
CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS 1”
WALLS, BEAMS, COLUMNS 2”
MAIN STEEL 2”
5. REINFORCING BAR SPLICES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF
ACI 318 AND THE REINFORCING SPLICE LENGTHS SCHEDULE ON THE DRAWINGS.
6. ALL CAST IN PLACE CONCRETE TO HAVE A 28 DAY COMPRESSIVE STRENGTH (f`c) OF
4000 PSI.
7. ALL REINFORCEMENT FOR CAST-IN-PLACE CONCRETE SHALL BE ACCURATELY PLACED,
SUPPORTED, TIED AND SECURED INTO PLACE PRIOR TO PLACING CONCRETE. ALL
REBAR DOWELS SHALL BE TIED IN PLACE PRIOR TO CONCRETE PLACEMENT. REBAR
DOWELS SHALL NOT BE EMBEDDED AFTER CONCRETE PLACEMENT UNLESS INDICATED
ON THE DRAWINGS.
8. REFER TO OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION FOR EMBEDDED
ITEMS AND PENETRATIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS AS
REQUIRED TO ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT
DOCUMENTS AND OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY
COMPLETE PROJECT. REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL
DETAILS UNLESS OTHERWISE SHOWN.
9. PROVIDE 3/4” CHAMFERS AT ALL EXPOSED EDGES. NOT ALL CHAMFERS MAY BE SHOWN.
10. ANCHOR BOLTS NOT SPECIFIED BY THE CONTRACT DRAWINGS SHALL BE DESIGNED
AND CERTIFIED BY A REGISTERED PROFESSIONAL ENGINEER, RETAINED BY THE
CONTRACTOR IN ACCORDANCE WITH THE APPLICABLE PROJECT AND CODE
REQUIREMENTS. SUBMIT AS A SHOP DRAWING FOR REVIEW BY THE CONTRACTING
OFFICER. COORDINATE LOCATION, SIZE AND EMBEDMENT PRIOR TO CASTING
CONCRETE.
11. ALL CAST-IN-PLACE AND POST-INSTALLED ANCHORS INDICATED IN THE STRUCTURAL
DOCUMENTS SHALL COMPLY WITH ACI 318-14 CHAPTER 17 AND CHAPTER 19 OF THE
IBC. ALL EXPANSION AND ADHESIVE ANCHORS SHALL HAVE AN ICC REPORT SHOWING
EQUIVALENT LOAD CAPACITY. SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
12. PRIOR TO INSTALLING POST INSTALLED ANCHORS INTO CONCRETE, THE CONTRACTOR
SHALL LOCATE REINFORCING. DO NOT DAMAGE CONCRETE REINFORCING.
13. ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE
CONTRACTOR’S LICENSED GEOTECHNICAL ENGINEER PRIOR TO PLACING CONCRETE.
STEEL DECK:
1. THE DESIGN, FABRICATION, AND ERECTION OF METAL DECKING SHALL BE IN ACCORDANCE
WITH THE CURRENT EDITION OF THE SDI SPECIFICATIONS AND THE SDI DIAPHRAGM
MANUAL.
2. STEEL ROOF DECK IS 1-1/2 INCH DEEP, WIDE RIB METAL DECK, THICKNESS AS INDICATED ON
THE PLANS, DESIGNED FOR THE LIVE LOAD GIVEN ABOVE AND 25 PSF DEAD LOAD. MINIMUM
SECTION PROPERTIES ARE AS FOLLOWS:
18 GAGE: IP = 0.289 IN4/FT, IN = 0.295 IN4/FT, SP = 0.318 IN3/FT, SN = 0.327 IN3/FT.
3. STEEL FLOOR DECK IS A 2- INCH X 18 GAGE GALVANIZED COMPOSITE DECK, AS SHOWN ON
THE PLANS DESIGNED FOR THE LIVE LOAD GIVEN ABOVE AND 75 PSF DEAD LOAD. MINIMUM
SECTION PROPERTIES ARE AS FOLLOWS:
IP = 1.254 IN4/FT, IN = 1.252 IN4/FT, SP =0.77 IN3/FT, SN = 0.797 IN3/FT.
4. STEEL ROOF AND FLOOR DECK IS TO BE A STRUCTURAL DIAPHRAGM AND SHALL BE
FASTENED AS FOLLOWS: FASTEN FLOOR DECK PANELS TO SUPPORTING MEMBERS BY
WELDING WITH NOMINAL 5/8 INCH DIAMETER ARC SPOT WELDS. WELDED HEADED SHEAR
STUDS MAY REPLACE ARC SPOT WELDS AT THE SECOND FLOOR LEVEL. WELD EACH RIB OF
PANEL TO EACH SUPPORT. SPACE ADDITIONAL WELDS AN AVERAGE OF 12 INCHES APART,
BUT NOT MORE THAN 18 INCHES APART. FASTEN SIDE LAPS AND PERIMETER EDGES OF
PANELS BETWEEN SUPPORTS AT INTERVALS NOT EXCEEDING THE LESSER OF 1/4 THE SPAN
OR 18 INCHES. MECHANICALLY FASTEN SIDE LAPS WITH NO. 12 OR LARGER, CARBON STEEL
SCREWS OR FASTEN WITH A MINIMUM OF 1 ½ INCH LONG SEAM WELDS.
5. INDICATES SPAN DIRECTION OF ROOF DECK.
6. INDICATES SPAN DIRECTION OF COMPOSITE DECK.
7. SUSPENDED CEILINGS, LIGHT FIXTURES, DUCTS, AND OTHER UTILITIES SHALL NOT BE
SUPPORTED FROM THE STEEL FLOOR OR ROOF DECK.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL DESIGN PROPERTIES:
WIDE FLANGE AND TEE SHAPES – ASTM A992 FY = 50 KSI
ANGLES, CHANNELS AND PLATES UNO – ASTM A36 FY = 36 KSI
STEEL PLATES- ASTM A572, GRADE 50, (WHERE INDICATED AS FY=50) FY = 50 KSI
STEEL BARS - ASTM A572, GRADE 50 FY = 50 KSI
STEEL PIPE – ASTM A53, GRADE B FY = 35 KSI
COLD-FORMED HOLLOW STRUCTURAL SECTIONS, ASTM A 500, GRADE B FY = 46 KSI
BOLTS – ASTM F3125, GRADE A325
ANCHOR RODS – ASTM F1554 FY = 55 KSI
2. ALL WELDS AND WELDING PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH
APPLICABLE PROVISIONS OF AISC AND AWS WELDING PROCEDURES AND CODES
OUTLINED IN THE SPECIFICATION. ALL WELDS SHALL BE MADE WITH E-70XX ELECTRODES
AND IN ACCORDANCE WITH AWS FOR METAL ALLOY BEING WELDED UNLESS NOTED
OTHERWISE.
3. WHEN FILLET WELD SIZES ARE NOT INDICATED, PROVIDE MINIMUM WELD SIZE IN
ACCORDANCE WITH AISC SPECIFICATIONS, TABLE J2.4. OR 3/16”, WHICHEVER IS GREATER.
4. ALL GROOVE WELDS INDICATED ON THE PLANS AND SECTIONS SHALL BE COMPLETE
JOINT PENETRATION WELDS (CJP) UNLESS SPECIFICALLY INDICATED TO BE PARTIAL
PENETRATION WELDS.
5. DIMENSIONS TO CENTERLINE OF COLUMNS, BEAMS, AND BRACING AND BACKS OF
CHANNELS UNLESS NOTED OTHERWISE.
6. ALL FIELD BOLTED CONNECTIONS SHALL BE MADE WITH 3/4" DIAMETER ASTM F1554, GRADE
A325 BOLTS, UNLESS NOTED OTHERWISE. ALL FIELD BOLTED CONNECTIONS SHALL BE
SNUG TIGHTENED UNLESS INDICATED AS PRETENSIONED OR SLIP CRITICAL. ALL BOLTED
CONNECTIONS FOR “SLRS” MEMBERS SHALL BE PRE-TENSIONED. ALL FAYING SURFACES
FOR PRETENSIONED AND SLIP CRITICAL BOLTS SHALL BE CLASS A, AS REQUIRED PER THE
SPECIFICATIONS. PRETENSIONED AND SLIP CRITICAL CONNECTIONS SHALL BE TIGHTENED
USING LOAD INDICATING WASHERS. INSTALL HIGH STRENGTH BOLTS ACCORDING TO
RCSC’S “SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A 325 OR A 490 BOLTS” FOR
THE TYPE OF JOINT SPECIFIED.
7. BEAMS REQUIRING SPECIAL CAMBER ARE INDICATED ON PLANS. EXAMPLE: [C=1/2”]
INDICATES 1/2-INCH CAMBER UP.
8. DOUBLE ANGLE MEMBERS SHALL HAVE INTERMITTENT FILLER PLATES AS REQUIRED BY
SECTION E6 OF THE AISC MANUAL OF STEEL CONSTRUCTION.
9. SEE SPECIFICATION SECTION 01 45 35 FOR FABRICATOR SPECIAL INSPECTIONS
SPECIAL STRUCTURAL INSPECTIONS:
1. SPECIAL INSPECTIONS AND TESTS SHALL BE BY AN INDEPENDENT TESTING AND
INSPECTION AGENCY EMPLOYED BY THE CONTRACTOR AND APPROVED BY THE
CONTRACTING OFFICER. TEST AND INSPECTION REPORTS SHALL BE SUBMITTED FOR
REVIEW TO THE CONTRACTING OFFICER.
2. SPECIAL INSPECTIONS AND TESTS SHALL BE PERFORMED DURING CONSTRUCTION IN
ACCORDANCE WITH CHAPTER 17 AND SECTION 110 OF THE 2015 INTERNATIONAL BUILDING
CODE, STATEMENT OF SPECIAL INSPECTIONS, AND THE CONTRACT SPECIFICATIONS. THE
CONTRACTOR SHALL NOTIFY AND ACCOMMODATE THE APPLICABLE INSPECTOR DURING
APPROPRIATE PHASES OF THE WORK AS REQUIRED BY EACH TEST AND INSPECTION.
3. SPECIAL INSPECTION FOR SEISMIC RESISTNG SYSTEMS, SEE SPECIFICATION SECTION 01
45 35, SPECIAL INSPECTIONS.
4. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF SEISMIC-RESISTING
SYSTEMS, SEISMIC-RESISTING COMPONENTS OR ELEMENTS SHALL SUBMIT A WRITTEN
CONTRACTOR’S STATEMENT OF RESPONSIBILITY TO THE CONTRACTING OFFICER PRIOR
TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR ELEMENTS. THE
CONTRACTOR’S STATEMENT OF RESPONSIBILITY SHALL CONTAIN THE FOLLOWING:
A. ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS
INCLUDING THE TYPE AND FREQUNECY OF TESTING, TYPE AND
FREQUENCY OF THE SPECIAL INSPECTIONS REQUIRED, TYPE AND
FREQUENCY AND DISTRIBUTION OF TESTING AND SPECIAL REPORTS.
B. ACKNOWLEDGEMENT THAT THE CONTROL WILL BE EXERCISED TO
OBTAIN CONFORMANCE WITH THE CONTRUCTION DOCUMENTS.
C. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR’S
ORGANIZATION, THE METHOD AND FREQUENCY OF REPORTING THE
DISTRIBUTION OF REPORTS.
D. IDENTIFICATION OF QUALIFICATION OF THE PERSON (S) EXERCISING
SUCH CONTROL AND THEIR POSITION IN THE ORGANIZATION.
DEFERRED SUBMITTALS
1. DEFERRED SUBMITTALS ARE THOSE PORTIONS OF THE DESIGN WHICH ARE NOT
SUBMITTED AT THE TIME OF PERMIT APPLICATION AND WHICH ARE TO BE SUBMITTED TO
THE PERMITTING AGENCY FOR ACCEPTANCE PRIOR TO INSTALLATION OF THAT PORTION
OF THE WORK.
2. THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS THAT ARE EXPECTED TO CONTAIN
STRUCTURAL CALCULATIONS OR SAFETY RELATED SYSTEM INFORMATION FOR REVIEW
TO MEET BUILDING PERMITTING REQUIREMS FOR DESIGN SYSTEMS, PRIOR TO
INSTALLATION OF THE INDICATED STRUCTURAL ELEMENT, EQUIPMENT, DISTRIBUTION
SYSTEM, OR COMPONENT AND ITS ANCHORAGE, THE CONTRACTOR SHALL SUBMIT THE
REQUIRED CALCULATIONS AND SUPPORTING DATA AND DRAWINGS FOR REVIEW AND
ACCEPTANCE BY THE CONTRACTING OFFICER. ADDITIONALLY, ACCEPTANCE INDICATED
ON THE CONTRACTING OFFICER’S COMMENT FORM, ALONG WITH THE COMPLETED,
FINAL SUBMITTAL SHALL THEN BE FILED BY THE CONTRACTOR AND ACKNOWLEDGED AS
ACCEPTED BY THE PERMITTING AGENCY PRIOR TO INSTALLATION OF THESE ITEMS.
1. STEEL BAR JOISTS
2. EXTERIOR METAL STAIRS
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
12" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:0
A M
S001 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
GENERAL STRUCTURAL NOTES
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER NONE
04/30/2023 ISSUED FOR CONSTRUCTION
RMUNRO
Image
9 10 1174
E
F
B
H
J
/2
/2
/2
/8
105'-4" 33'-2"
4'-0 7/8"
11'-8 1/8" 11'-3"
8'-4 7/8"
18'-7 1/8" 49'-7" 38'-0" 38'-0" 39'-3"
357'-4"
2.5 7.8
F.6
C
D
A A
F.4
8.2
S502
8.5 8.88.3
G.2
D.5
106'-4 7/8" 17'-11" 65'-2"
7'-7"
1'-1 1/4" 3'-10 7/8"
5'-3"
18'-2 1/8" 131'-10"
/4
/4
/4
/8
/8
/4
F.8
E.5
D.6
G.5
B.2
2.1 8.4
K K
MASONRY WALL KEY
8" CMU
10" CMU
NOTE: COLUMNS INDICATED WITH AN ASTERISK ( )
INDICATE A MECHANICAL PLATFORM SUPPORT COLUMN.*
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
As indicatedB
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S101 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
OVERALL FOUNDATION PLAN
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
3/64" = 1'-0"
OVERALL FOUNDATION PLAN
NOT TO SCALE
MASONRY WALL OVERVIEW PLAN
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
FOUNDATION NOTES:
1. REFER TO COLUMN SCHEDULE FOR TOP OF FOOTING
ELEVATIONS AT ISOLATED SPREAD FOOTINGS.
2. ALL COLUMNS CENTERED ON FOOTINGS, TYP.
3. ALL CMU WALLS CENTERED ON FOOTINGS, TYP.
4. EXCAVATE AND PLACE FOOTINGS ON SOUND,
UNDISTURBED GLACIAL OUTWASH DEPOSITS. STRIP AND
DISPOSE OF ALL FILL AND SOILS CONTAINING ROOTS,
ORGANICS, DEBRIS OR OTHER DELETRIOUS MATERIAL.
5. WHERE IT IS IMPRACTICAL TO EXCAVATE TO UNDISTURBED
GLACIAL OUTWASH DEPOSITS OR NATIVE SOILS ARE
OTHERWISE UNSUITABLE, FOUND FOOTINGS ON A MINIMUM
OF 12" OF WELL COMPACTED STRUCTURAL FILL. SEE
SPECIFICATIONS FOR REQUIREMENTS.
6. THE GEOTECHNICAL ENGINEER OR THEIR REPRESENTATIVE
SHALL OBSERVE ALL EXCAVATIONS AND VERIFY THE
SUITABILITY OF THE PREPARED SUBGRADE PRIOR TO
PLACING REINFORCING FOR FOOTINGS AND FOUNDATIONS.
7. CONTRACTOR SHALL VERIFY WITH MECHANICAL AND
ELECTRICAL SIZE AND LOCATIONS OF OPENINGS AND
PENETRATIONS IN THE SLAB.
8. ARCHITECTURAL FINISH FLOOR ELEVATION 0’-0” EQUALS SITE
SURVEY ELEVATION 261.0'.
9. CONCRETE SPREAD FOOTINGS ARE CENTERED AT EACH
FOOTING UNLESS NOTED OTHERWISE.
10. SLAB – ON – GRADE REINFORCING: #6 @ 12” ON CENTER,
EACH WAY, U.N.O.
11. SLAB ON GRADE SHALL BE PLACED OVER A 15 MIL VAPOR
RETARDER OVER A 6-INCH COMPACTED GRANULAR FILL.
12. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF
THICKENED, SLOPED, RAISED OR DEPRESSED SLABS.
13. SEE PLUMBING SHEETS FOR FLOOR DRAINS (FD),
FLOOR CLEANOUT (CO), AND TRENCH DRAIN (TD) LOCATIONS.
14. COORDINATE SIZE AND LOCATION OF EQUIPMENT PADS WITH
MECHANICAL AND ELECTRICAL DRAWINGS. SEE STRUCTURAL
DRAWINGS FOR TYPICAL EQUIPMENT PAD DETAILS UNLESS
NOTED OTHERWISE.
COLUMN SCHEDULE
GRID COLUMN SECTION
TOP OF
BASEPLATE
ELEVATION
FOOTING
TYPE
TOP OF
FOOTING EL
B-5 HSS8x8x1/2, CONCRETE FILLED
-3" F3 -5"
B.2-2.1 HSS4x4x1/2, CONCRETE FILLED
-3" 8/S-502 SEE PLAN
B.2-8.4 HSS4x4x1/2, CONCRETE FILLED
-3" 8/S-502 SEE PLAN
C-5 HSS8x8x1/2, CONCRETE FILLED
-3" F3 -5"
D.6-4 HSS6x6x5/8 -3" 8/S-502, SIM SEE PLAN
D.6-7.8 HSS6x6x5/8 -3" 8/S-502, SIM SEE PLAN
E-2.5 HSS6x6x3/8 -3" F4 SEE PLAN
E-4 HSS6x6x3/8 -3" F4 SEE PLAN
E-7 HSS6x6x1/2, CONCRETE FILLED
-3" F4 SEE PLAN
E-7.8 HSS6x6x3/8 -3" F4 SEE PLAN
E-8.2 HSS6x6x3/8 -3" F4 SEE PLAN
E-8.5 HSS6x6x1/2, CONCRETE FILLED
-3" F4 - 7/S502 SEE PLAN
F-9 HSS6x6x1/2, CONCRETE FILLED
-3" F4 -5"
F-10 HSS6x6x1/2, CONCRETE FILLED
-3" F4 -5"
F-11 HSS6x6x1/2, CONCRETE FILLED
-3" F4 -5"
F.4-2.5 HSS6x6x1/2, CONCRETE FILLED
-3" F4 - 7/S502 SEE PLAN
F.4-4 HSS6x6x1/2, CONCRETE FILLED
-3" F3 - 7/S502 SEE PLAN
F.4-7 HSS6x6x1/2, CONCRETE FILLED
-3" F4 SEE PLAN
F.4-7.8 HSS6x6x3/8 -3" F4 SEE PLAN
F.6-4 HSS6x6x3/8 -3" F4 - 7/S502 SEE PLAN
F.6-7 HSS6x6x3/8 -3" F4 SEE PLAN
F.6-7.8 HSS6x6x3/8 -3" F4 SEE PLAN
G-2.5 HSS6x6x3/8 -3" F4 SEE PLAN
G-4 HSS6x6x1/2, CONCRETE FILLED
-3" F4 SEE PLAN
G-7 HSS6x6x1/2, CONCRETE FILLED
-3" F4 SEE PLAN
G-7.8 HSS6x6x3/8 -3" F4 SEE PLAN
G.5-4 HSS6x6x3/8 -3" 8/S-502, SIM SEE PLAN
G.5-7.8 HSS6x6x3/8 -3" 8/S-502, SIM SEE PLAN
E.5-8.2 HSS6x6x1/2, CONCRETE FILLED
-3" F4 SEE PLAN
04/30/2023 ISSUED FOR CONSTRUCTION
B
/4
/8
/2
7 1/8" 5 7/8" 47'-10 1/8" 47'-10" 22'-10"
7 1/8"
T Y
P
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
NMATCHLINE - SEE SHEET S103 FOR CONTINUATION
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
N
8" CMU WALL W/
BRICK VENEER
STOOP, TYP
STOOP
19'-11 7/8"
S502
TYP
1'-3" 4'-8"
T Y
P
C
S502
D
A
T Y
P
E X
T E
R
IO
TYP
97'-6"
MCJ MCJ MCJ MCJ
MCJ
MCJ
MCJ
MCJ
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
FINISH EL 0'-0"
/4
CJ
CJ
/4
CJ
S522
S201
S502
S502
1'-4" x 1'-4" CONC
PEDESTAL UNDER
16" x 16" CMU
COLUMN
8.8
B.2
2.1 8.4
TOF EL -2'-0", TYP
TOF EL -0'-5", TYP
INTERIOR FOOTINGS
W A
L L S
W
IT
H V
E N
E E
R
U N
O
SIM
S502
/2
10 7/8" 11 1/8" KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S102 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FOUNDATION PLAN - AREA A
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FOUNDATION PLAN - AREA A
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
2. SEE S502 FOR FOOTING SCHEDULE.
CJ
CJ
CJ
CJ
CJ
CJ
C J
C J
C J
C J
C J
C J
04/30/2023 ISSUED FOR CONSTRUCTION
E
19'-0" 18'-3" 31'-4" 15'-7" 7'-7"
1'-1"
9'-2" 18'-2"
120'-2"
/4
/4
/8
/2
/2
8" STEM WALL AT
LOWER/ UPPER
SLAB TRANSITION
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
TOP OF CONC EL -16"
COMMERCIALLY
AVAILABLE COMPUTER
ACCESS FLOOR ON TOP
OF SLAB ON GRADE
FINISH EL 0'-0"
2'-0" TYP
12" THICK CONTINUOUS
STRIP FOOTING.
MATCHLINE - SEE SHEET S105 FOR CONTINUATION
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
N
MATCHLINE - SEE SHEET S102 FOR CONTINUATION
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
N
10" CMU WALL
10" CMU WALL
2.5 7.8
F.6
S502
STOOP, TYP
S502
TYP @
STOOP
C
D
S502
C J
C J
C J
C J
C J
CJ
CJ
CJ
CJ
C J
C J
C J
TOF EL -2'-6"
TOF EL -2'-0"
MCJ MCJ
MCJ
MCJ
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
FINISH EL 0'-0"
F.4
8.2
S502
8.5 8.88.3
G.2
D.5
F.8
E.5
D.6
G.5
/2
5'-0"
TYP
S502
SIM
S202
MCJ MCJ
TOF EL -0'-5", TYP
(4 PLCS)
TOF EL -1'-9", TYP
(13 PLCS)
TYP @ STEP
S502
4'-3" TYP @ EXTERIOR
10" CMU WALL WITH
BRICK VENEER
5'-4"
WALLS WITH VENEER UNO
10" CMU WALL
T Y
P
I N
T E
R
IO
R
C M
U W
A L L
S U
N O
7 1/4" GRID TO FACE OF WALL
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S103 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FOUNDATION PLAN - AREA B
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FOUNDATION PLAN - AREA B
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
2. SEE S502 FOR FOOTING SCHEDULE.
04/30/2023 ISSUED FOR CONSTRUCTION
9 10 11
F
16'-7" 38'-0" 38'-0" 39'-3"
131'-10"
8" CMU WALL W/
BRICK VENEER
10" CMU WALL
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
N
4'-8" 1'-8" 7'-8" 2'-7"
STOOP, TYP
S502
TYP
7'-8" 14'-11" 7'-8" 15'-2" 14'-10" 7'-8"
C
D
8" CMU WALL
S502
CJ
CJ
CJ
CJ
C J
C J
C J
C J
C J
C J
MCJ
MCJ
MCJ MCJMCJ MCJ MCJ
MCJ
MCJ
MCJ
MCJ
MCJ
MCJMCJMCJMCJ
MCJMCJMCJMCJMCJ
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
FINISH EL 0'-0"
S522
S522
8.8
G.2
OPP HAND
8" CMU WALL
TYP
TOF EL -2'-0",
TYP
T Y
P
8" CMU WALL WITH
BRICK VENEER
T Y
P
I N
T E
R
IO
R
10" CMU
WALL
WITH
BRICK
VANEER
10" CMU WALL
C M
U W
A L L
S U
N O
T Y
P
E X
T E
R
IO
R
W A
L L S
W
IT
H V
E N
E E
R
U N
O
S502
TYP
/2
/2
/2
/8
/8
/8
/8
T Y
P
2'-0 1/8"16'-10 1/4"1'-3 1/8"
7 1/8"
7 1/8"
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S104 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FOUNDATION PLAN - AREA C
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FOUNDATION PLAN - AREA C
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
2. SEE S502 FOR FOOTING SCHEDULE.
04/30/2023 ISSUED FOR CONSTRUCTION
4 6
J
37'-2 7/8" 22'-11 1/8" 23'-11 7/8" 36'-0 1/8"
23'-0"
120'-2"
8" SLAB ON GRADE
REINF W/ #6@12 EW
FINISH EL 0'-0"
8" CMU WALL W/
BRICK VENEER
10" CMU WALL
8" SLAB ON GRADE
REINF W/ #6@12 EW
FINISH EL 0'-0"
TYP
10'-0"
/8
APPROACH SLAB
MATCHLINE - SEE SHEET S103 FOR CONTINUATION
7.8
TYP
5'-0"
S502
TYP @
APPROACH
SLAB
S502
TYP @ STOOP
4'-8" 28'-6 7/8" 14'-6" 4'-8"
APPROACH
SLAB
APPROACH SLAB
S502
CJ
CJ
C J
C J
C J
APPROACH SLAB
MCJ
MCJ
MCJ
MCJ
MCJ
MCJMCJ
MCJ
MCJ
MCJ
MCJ
MCJ
MCJMCJMCJ
MCJ
MCJ
MCJ
MCJ
MCJ
MCJMCJMCJ
MCJ
S522
S522
S522
S522
S522
8.8
10'-0"
STOOP, TYP UNO
C J
C J
C J
HSS COLUMN IN WALL, TYP
G.5
TOF EL -2'-0", TYP
10" CMU WALL WITH
BRICK VENEER
10" CMU WALL WITH
BRICK VENEER
8" CMU WALL WITH
BRICK VENEER
10" CMU WALL
3'-10" TYP @ INTERIOR
8" CMU WALL, TYP UNO
CMU WALLS UNO
4'-3" TYP @ EXTERIOR
WALLS WITH VENEER UNO
S502
TYP
K
/8
/8
/4
9'-7 3/4"
2'-4 5/8"
11 7/8"
16'-9 1/8"
5'-0"
2'-2 3/4" FACE OF WALL TO GRID 7.8
FACE OF WALL TO GRID 7.8
19'-5 3/4"
/8
/8
6'-5"
7'-10"
9'-7 5/8"
/4
F
A C
E O
F
W A
L L T
O G
R
ID
G
.5 KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S105 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FOUNDATION PLAN - AREA D
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FOUNDATION PLAN - AREA D
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
04/30/2023 ISSUED FOR CONSTRUCTION
TOP OF FOOTING
EL -2'-0", TYP
10" CMU WALL W/
BRICK VENEER
10" CMU WALL7
/2
105'-4" 1'-0 7/8"
M A
T C
H L
IN
E
S
E E
S H
E E
T S
F O
R C
O N
T
IN
U A
T
IO
N
STOOP, TYP
S502
TYP
4'-8"
1'-2"
17'-8" 7'-8" 16'-8" 7'-8" 32'-4" 7'-8"
T Y
P
5'-0"
S502
/8
/8
CJ
C J
CJ
C J
C J
MCJ MCJMCJMCJ
MCJ
MCJ
MCJMCJ
MCJ MCJ
MCJ
MCJMCJ
MCJ
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
FINISH EL 0'-0"
5" SLAB ON GRADE
REINF W/ #5@12 EW
CENTERED IN SLAB
FINISH EL 0'-0"
MCJ
MCJ
MCJ
S502 B.2
2.1
/8
SIM
10" CMU WALL WITH
BRICK VENEER
T Y
P
E X
T E
R
IO
R
8" CMU WALL WITH
BRICK VENEER
W A
L L
S W
IT
H
V E
N E
E R
U N
O
T Y
P
I N
T E
R
IO
R
C M
U W
A L L
S U
N O
4'-3"
S502
TYP
15'-8"
/4
36'-0"
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:1
A M
S106 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FOUNDATION PLAN - AREA E
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FOUNDATION PLAN - AREA E
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
04/30/2023 ISSUED FOR CONSTRUCTION
E
2.5
1'-5" 17'-7" 18'-3" 31'-4" 15'-7" 7'-7"
1'-1 1/4"
9'-1 3/4" 16'-9 1/4" 1'-5"
/8
/2
/8
/8
7.8
F.6
D
MCJ
MCJ
MCJ
MCJ MCJ
F.4
W21X44 W
X
W21X44
W X
W21X44 W21X44
W X
W21X44
W X
W X
W21X44W21X55
W21X44
W X
W X
W21X44 W21X44
NOTE 1
W21X62
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W21X44W21X44W21X44W21X44
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
8.2
10'-3"
W X
W X
W X
W X
W X
W X
W21X44
W21X44
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
4 EQUAL SPACES @ 4'-5"± 4 EQUAL SPACES @ 4'-7"± 7 EQUAL SPACES @ 4'-6"± 4 EQUAL SPACES @ 4'-6"±
W X
W X
W X
2'-0"4
S512
BP-5
BP-6
BP-5
BP-5
BP-5 TYPICAL THIS
BEARING LINE
BP-5 TYPICAL THIS
BEARING LINE
L2L2
L2
L
L
L2
L2
8.5 8.88.3
W X
4 3/8"
/4 " G.2
F.8
E.5
G.5
BP-7 EA END
BP-7 BP-5 EA END
SEE NOTE 6
L5
BP-7 EA END BP-7 EA END
BP-8 EA ENDBP-8 EA END
L2 L2 L2 L2 ML-6
L
L
L
L
B O
L
M L -6
L5
S202
MCJMCJ
S513
SEE 6/S521, TYP
ALL LINTELS
ALONG WALL
SEE 6/S521, TYP
ALL LINTELS
ALONG WALL
S510
TYP @ BEAM TO
COLUMN
CONNECTIONS, UNO
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
A
SHEET
C. STATSER
C. GIPSON
D. HOGAN
M. OSSANNA
T. PRICE
J. CAMPBELL
COMMUNICATIONS M. ADKISON
1/8" = 1'-0"B
IM
/1
J V
C
H M
C a m p M u rr a y A
S O
G F a c ili ty /1
-S
A .r v t
/2
/2
:5
:2
A M
S110 10078627
CHRIS MANZ
HDRE_ALL_DISCIPLINES.rte
FRAMING PLAN - HVAC PLATFORM
CAMP MURRAY
ASOG FACILITY
AIR SUPPORT
OPERATIONS CENTER
1/8" = 1'-0"
FRAMING PLAN - HVAC PLATFORM
GENERAL NOTES:
1. SEE S001 FOR GENERAL STRUCTURAL NOTES.
FRAMING AND SLAB NOTES:
1. INDICATES SPAN DIRECTION FOR 2",
18 GA. COMPOSITE METAL DECK WITH 3 1/2" NORMAL
WEIGHT CONCRETE FILL. TOTAL SLAB DEPTH = 5 1/2". DECK
TO BE VULCRAFT 2.0D DOVETAIL FORMLOCK OR APPROVED
EQUAL WITH A MINIMUM STC RATING OF 50 FOR THE
COMBINED SLAB AND DECK SYSTEM. REINFORCE WITH
6X6-W2.9 X W2.9 WELDED WIRE MESH, EXCEPT WHERE
SHOWN OTHERWISE.
2. TOC = 14'-8", TYP THIS SHEET.
3. TOS = 14'-2 1/2", TYP THIS SHEET.
4. "BP-X" EQUALS BEAM BEARING PLATE. SEE STEEL BEAM
BEARING PLATE ON MASONRY SCHEDULE.
5. 'L#' INDICATES STEEL LINTEL. SEE 5/S521.
6. EXTEND L2 LINTEL TO HSS COLUMN AND CONNECT PER
DETAIL 3/S510.
04/30/2023 ISSUED FOR CONSTRUCTION
9 10 1174
E
F
B
H
J
105'-4" 33'-2"
4'-0 7/8" 11'-8 1/8"
11'-3"
8'-4 7/8"
18'-7 1/8" 49'-7" 38'-0" 38'-0" 39'-3"
357'-4"
S P
A N
SPAN
S P
A N
SPAN
SPAN SPAN
SPAN
SPAN
SPAN
2.5 7.8
F.6
C
D
A A
F.4
8.2 8.5 8.88.3
G.2
D.5
106'-4 7/8" 17'-11" 65'-2" 7'-7"
1'-1 1/4"
3'-10 7/8"
5'-3"
18'-2 1/8" 131'-10"
F.8
E.5
D.6
G.5
B.2
2.1 8.4
S P
A N
S P
A N
K
/8
/8
/2
/2
/2
/8
/4
/8
/8
/4
/4
/4
KEY PLAN
A
C
D
B
E
MATCHLINE
MATCHLINE
M A
T C
H L
IN
E
M A
T C
H L
IN
E
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
SCALE
FILENAME
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MECHANICAL
FIRE PROTECTION
ISSUE DATE DESCRIPTION
1 2 3 4 5 6 7 8
D
C
B
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .