Attachment 07 - EHRM Madison - Drawings - Building 01 - Part 6.pdf

PDF 20 MB Posted

Attached to
36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI Federal contract opportunity
Solicitation number
36C77623B0011
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is seeking bids for an EHRM infrastructure upgrades project at the Madison VA Medical Center in Madison, Wisconsin. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting a single firm-fixed-price contract for general construction and the replacement of all telecommunications cable, outlets, and associated equipment for multiple buildings on the Madison VA campus. The contractor will furnish all labor, tools, materials, equipment, and supervision consistent with the provided drawings and specifications. Bids are due in response to solicitation number 36C77623B0011 for upgrading the infrastructure at the Madison VAMC located at 2500 Overlook Terrace, Madison, WI 53705.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI, newest first.
File Type Posted
36C77623B0011 0004_REVISED.pdf PDF
36C77623B0011 0004.pdf PDF
36C77623B0011 0003.pdf PDF
Attachment 27 - Technical Questions and Answers Volume 2.pdf PDF
Attachment 30 - Existing Column Load Summary.pdf PDF
Attachment 28 - Strengthening of Concrete with FRP.docx DOCX document
Attachment 29 - Sheet 1-S-15 from Ref_Existing - D - Wing_Addition.pdf PDF
Attachment 31 - CATV rack1top.jpg JPG image
Attachment 35 - CATV back of rack.jpg JPG image
Attachment 32 - CATV rack1btm.jpg JPG image
Attachment 33 - CATV rack2top.jpg JPG image
Attachment 34 - CATV rack2btm.jpg JPG image
Attachment 24 - EHRM Madison - Floor to Finish Heights.pdf PDF
36C77623B0011 0002.pdf PDF
Attachment 25 - EHRM Madison - Attendance Sheet.pdf PDF
Attachment 26 - Technical Questions and Answers.pdf PDF
Attachment 23 - Asbestos Survey and Lead Paint Report.pdf PDF
36C77623B0011 0001.pdf PDF
Attachment 03 - EHRM Madison - Drawings - Building 01 - Part 2.pdf PDF
Attachment 05 - EHRM Madison - Drawings - Building 01 - Part 4.pdf PDF
Attachment 15 - EHRM Madison - Drawings - Building 15.pdf PDF
Attachment 11 - EHRM Madison - Drawings - Building 05.pdf PDF
Attachment 12 - EHRM Madison - Drawings - Building 06.pdf PDF
Attachment 02 - EHRM Madison - Drawings - Building 01 - Part 1.pdf PDF
Attachment 04 - EHRM Madison - Drawings - Building 01 - Part 3.pdf PDF
Attachment 06 - EHRM Madison - Drawings - Building 01 - Part 5.pdf PDF
Attachment 08 - EHRM Madison - Drawings - Building 01 - Part 7.pdf PDF
Attachment 09 - EHRM Madison - Drawings - Building 02.pdf PDF
Attachment 10 - EHRM Madison - Drawings - Building 04.pdf PDF
Attachment 16 - EHRM Madison - Drawings - Building 22.pdf PDF
Attachment 19 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 20 - Dane County - Wage Rates.pdf PDF
Attachment 21 - SOW - EHRM Infrastructure Upgrades - Madison.pdf PDF
S02 - Solicitation - 36C77623B0011 - EHRM Infrastructure Upgrades - Madison.pdf PDF
Attachment 01 - EHRM Madison - Specifications.pdf PDF
Attachment 13 - EHRM Madison - Drawings - Building 07.pdf PDF
Attachment 14 - EHRM Madison - Drawings - Building 12.pdf PDF
Attachment 17 - EHRM Madison - Drawings - IFC - SITE.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 22 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

CUBICLE 2

A7040

STAFF TOILET

A7037

CORRIDOR

A7241

OFFICE

A7044

OFFICE

A7046

SPECIALTY EQUIPMENT STORAGE

A7045

ELEVATOR

CONTROL STATION

D7200

WORKROOM

D7204

OFFICE

D7204A

STAIRS

D7263

OFFICE

D7202

CORRIDOR

D7262ELEVATOR

ELEVATOR

ELEVATOR

ELEC. ROOM

D7207

OPERATING ROOM 1

D7211

SCRUB/ EQUIP ALCOVE

D7260

CLEAN CASE STOR

D7205

SOILED HOLDING

D7203

OPERATING ROOM 1

D7227

CORRIDOR

D7255

SOILED HOLDING

D7211

SUB-STERILE ROOM

D7213

ANESTHESIA WORKROOM

D7215

FILM

D7217

MED

D7219

HSKP

D7221

EQUIPMENT ALCOVE

D7222

PUMP ROOM

D7220

EQUIPMENT ALCOVE

D7257

EQUIPMENT ALCOVE

D7223

STAIR

D7229

STERILE STORAGE

D7230

GENERAL OR 5

D7228

SPECIALTY OR 4

D7224

OPERATING ROOM 1

D7218

OPERATING ROOM 1

D7213

SCRUB

D7259

EQUIPMENT ALCOVE

D7258

EQUIPMENT ROOM

D7210E

OPERATING ROOM 1

D7210

COMM.

D7201

CUBICLE 3

A7038

C

T

-1 B

A -D

A -C

A -A

A -B

A -D

A -C

A -A

A -B

A -D

A -C

A -B

A -A

CUBICLE 1

A7042

A -E

A

-FA7044-D

A7044-E

A7044-C

A7044-B

A7044-A A7046-A

A7046-B

A7046-C

A7046-D

A7045-AP-A

A -A

D -G

D7253-AP-A

EQUIPMENT ALCOVE

D7253

D7253-AP-B

D -A

D -B

D -A

D7228-D

D7228-E

D7228-F

D7228-C

D7228-G

D7228-B

D7228-A

D7224-C

D7224-B

D7224-A

D7224-H D722F-G

D7224-F

D7224-D D7224-E

D7255-AP-A

D7219-A

D7219-B

D7219-C

NO DATA

D7255-AP-B

D7215-A

D7215-B

D7213-B

D7213-A

NO DATA

D7227-E

D7227-F

D7227-D

D7227-A

D7227-B D7227-C

NO DATA

NO DATA

D7220-B

D7220-C

D7220-A

NO DATA

D7255-A

D7255-B

D7261-A

CORRIDOR

D7261

D7261-B

D7261-AP-A

D7218-B D7218-A

D7218-C

D7218-D

D7218-E

D7218-F

D7218-G

D7218-H

D7218-J

D7213-E

D7258-A

D -C

D -B

D -A

D -D

D7213-F D7213-G

D7213-H

D7213-J

D7259-AP-A

D7210E-A

D7210E-B

D7210-C

D7210-B D7210-A

D7210-D

D7210-E

NO DATA

D7211-AP-A

D7211-A

D7211-B

D7211-C

D7211-D

D7211-E

D7211-F

D7211-AP-B

D7262-AP-A

D7200-A D7200-B

D -C

D -D

D -H

D

-JD

-E

D -F

D7200-B

D -C

D -B

D -A

D7263-AP-A

D A

-E

D A

-D

D A

-A

D A

-B

D A

-C

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

A7247-AP-A

CORRIDOR

A7247

TYP.

TYP.

01T-408

F1

TYP.

D -C

A M

-0

TELECOM ROOM

D7000

A -E

TELECOM ROOM

B7113

130 SF

262' - 0"

TELECOM ROOM

D7000

165 SF

TELECOM ROOM

B7000

191 SF

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

D-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:4

P

M

01T-107A

TELECOMMUNICATION PLAN - SEVENTH LEVEL 607-21-700

07/22/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW

CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET T-501

FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS AS

SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE SPECIFICATIONS.

PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND TRANSFER DATA

CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK. PROVIDE TEMPORARY

EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES AND OTHER DEVICES TO

ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING DATA CIRCUITS ARE

RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND ALL EXISTING

DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK, REMOVE THE

EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL PERMANENT

POSITION.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE UNTIL ALL EXISTING DEVICES ON THE EXISTING RACK ARE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT COORDINATION

DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. COORDINATE FIXTURES

WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR ADDITIONAL

REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD CABLE TRAY.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,

AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.

MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO

EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED SLEEVE THROUGH WALL ABOVE CEILING GRID FOR HORIZONTAL

VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH ENDS TO

PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH EXISTING

FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE OPERATIONAL.

CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

14. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENETRATIONS TO TR

ABOVE/BELOW.

15. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

16. ALL OPERATING ROOM DATA DEVICES TO BE MOUNTED AT 48" AFF.

17. AREA OF HARD CEILING. VIF - NOT ALL LOCATIONS NOTED. CONTRACTOR TO

UTILIZE CABLE HOOKS AS REQUIRED TO PROVIDE CABLE ROUTING AS INDICATED

AT PINCH POINTS WITHIN HARD CEILING SPACES.

18. EXISTING EQUIPMENT TO BE DEMOLISHED.

19. EXISTING EQUIPMENT TO BE RELOCATED TO NEW TELECOM ROOM LOCATION.

20. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

21. CATV HEAD-END EQUIPMENT. SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.

22. SATELLITE DISH FOR NEW HEAD-END FOR CATV. COORDINATE LOCATION WITH

EXISTING CONDITIONS.

23. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

SCALE: 1/8" = 1'-0"

F1

TELECOMMUNICATION PLAN -

SEVENTH LEVEL

SCALE: 1" = 100'-0"

B1

DIAMOND ANALYSIS - SEVENTH

LEVEL

GENERAL NOTES

KEYNOTES

Revisions: Date:

07/22/202207 /22

/20

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

01T-408

F8

CORRIDOR

A7241

ISOLATION

A7031

SOILED HOLDING

A7029

CLEAN SUPPLY

A7027

EQUIPMENT STORAGE

A7025

NURSE STATION

A7035

CORRIDOR

A7246

CUBICLE 3

A7038

CUBICLE 4

A7036

CUBICLE 5

A7034

CUBICLE 6

A7032

CUBICLE 7

A7030

STAFF LOUNGE

A7024

CORRIDOR

A7245

STAFF TOILET

A7023

HSKP

A7021

CORRIDOR

A7244

NOURISH ALCOVE

A7022

PREP/ PH2 ISOLATION 8

A7020

PREP/ PH2 ISOLATION 7

A7018

PREP/ PH2 ISOLATION 6

A7016

PREP/ PH2 ISOLATION 5

A7014

PREP/ PH2 ISOLATION 4

A7012

PREP/ PH2 ISOLATION 9

A7019

PREP/ PH2 ISOLATION 10

A7017

PATIENT TLT

A7015

NURSE STATION

A7013

NURSE STATION

A7011

BARIATRIC PATIENT T/S

A7009

ELEC

A7243

PREP/ PH2 ISOLATION 11

A7007

PREP/ PH2 ISOLATION 12

A7005

PREP/ PH2 ISOLATION 3

A7010

PREP/ PH2 ISOLATION 2

A7008

PREP/ PH2 ISOLATION 1

A7006

RECEPTION DESK

A7004

WAITING AREA

A7002

PUBLIC TLT

A7001

CORRIDOR

A7240

TLT

B7111

STAIR

NO.3

STORAGE

B7053

OFFICE

B7052A

TELECOM ROOM

B7113

OFFICE, SURGERY STAFF

B7052

OFFICE

B7052B OFFICE

B7052C

OFFICE

B7052D

OFFICE

B7052E

OFFICE

B7052F

CORRIDOR

B7120

ELEVATOR

ELEVATOR

ELEVATOR

ELEVATOR

HSKP

B7089

OFFICE

B7112H

ELEVATOR

5ELEVATOR LOBBY

B7109

ENTRY WAY

B7112

HSKP

B7112I

OFFICE

B7112B

OFFICE

B7112C

OFFICE

B7112D

OFFICE

B7112E

OFFICE

B7112F

OFFICE

B7112G

F

T

-1 A

F

T

-1 B

B A

-A B

-A

B -B

B -C

B -G

B -F

B -E

B -D

B7052-C

B7052B-B

B7052B-A

B7052C-B

B7052C-A

B7052C-C

B7052D-A B7052E-B

B7052E-A

B7052F-A

NO

DATA

SW3-AP-A

B -A

P -A

B7113-A

NO DATA

B7112B-C

B7112B-B

B7112B-A

B7112B-AP-A

B7112C-A

B7112C-B

B7112D-A

B7112D-B

B7112E-A

B7112E-B

B7112F-A

B7112G-B

B7112G-A

NO

DATA

NO DATA

B7112H-A

B H

-B

B H

-C

B7120-AP-A

NO DATA

A7240-AP-A

A -C

A -B

A -A

A7004-D A7004-E

A7006-B

A7006-C

A7006-D A7006-E

A7008-D

A7008-C

A7008-B A7008-A

A7010-B

A7010-C

A7010-D A7010-E

A7012-D

A7012-C

A7012-B A7012-A

A7014-B

A7014-C

A7014-D A7014-E

A7016-D

A7016-C

A7016-B A7016-A

A7018-B

A7018-C

A7018-D A7018-E

A7020-D

A7020-C

A720-B

A7020-A

A7018-AP-A

A -E

A -D

A -B

A -A

A -C

A -B

A -A

A -C

A -B

A -A

A -A

A -B

A -C

A -D

A -C

A -D

A -E

A -F

A -B

A -A

A -D

A -C

A -B

A7035-H

A -G

A -F

A7035-E

A -A

A -B

A -C

A -D

A7246-AP-A

NO DATA NO DATA NO DATA

A7241-AP-A

A7241-AP-B

NO DATA

NO DATA

A7242-AP-A CORRIDOR

A7242

A A

-B

A A

-A

CHARTING

A7242A

A B

-B

A B

-A

CHARTING

A7242B

A -C

A -B

A -D

A -E

A7019-A

A -C

A -D

A -B

A -A

A7017-E

A -D

A -C

A -A

A -B

A -C

A -D

A -E

A -F

A -G

A -H

A

-AA

-B

A7242-AP-B

A -C

A -B

A -D

A -E

A7007-A

A -C

A -D

A -B

A -A

A7005-E

01T-408

C8

TYP.

TYP.

TYP.

B7113-CAM-01

A7006-AA7008-EA7010-A

A7012-EA7014-A

A7016-EA7018-A

A7020-E

A7021-A

A7021-B

A7021-C

A -C

A -D

OFFICE

B7058

OFFICE

B7057

OFFICE

B7059

BEDROOM

B7060

PATIENT TLT

B7060A

PATIENT TLT

B7061A

BEDROOM

B7061

BEDROOM

B7062

PATIENT TLT

B7062A

PATIENT TLT

B7063A

BEDROOM

B7063

BEDROOM

B7064

PATIENT TLT

B7064A

PATIENT TLT

B7065A

BEDROOM

B7065

BEDROOM

B7066

PATIENT TLT

B7066A

PATIENT TLT

B7067A

BEDROOM

B7067

PATIENT TLT

B7068A

OFFICE

B7068

OFFICE

B7069

PATIENT TLT

B7069A

OFFICE

B7070

PATIENT TLT

B7070A

MONITOR LAB

B7071

CLEAN ROOM

B7071B

STORAGE

B7071A STAIR

D7265

CORRIDOR B-WING

B7121

PHYSICAL THERAPY

B7072

OFFICE

B7073

STORAGE

B7074

CONFERENCE ROOM

B7075

STAFF TOILET

B7075A

NOURISHMENT CENTER

B7076

CONSULT ROOM

B7077

NURSE STATION

B7078

MEDICATION PREP

B7079CLEAN UTILITY

B7080

CLEAN LINEN

B7081

SOILED UTILITY

B7082

STAIR

D7264

BEDROOM

B7083

PATIENT TLT

B7083A

PATIENT TLT

B7084A

BEDROOM

B7084

BEDROOM

B7085

PATIENT TLT

B7085A

PATIENT TLT

B7086A

BEDROOM

B7086

EQUIPMENT ROOM

B7087

HSKP

B7088

C

T

-1 B

B7088-AP-A

B -E

B -A

NO DATA

NO DATA

B7086-B

B7086-A

B7085-D

B7085-C

B7085-B

B7085-A

B7084-A

B7084-B

B7084-C

B -D

B7083-C

B7083-A B7079-A

B7078-K

B7078-J

B7078-H

B7078-G

B7078-F

B7078-E

B -D

B -C

B -A

B -B

B7078-L

B7077-D

B7077-C B7077-B

B7077-A

NO DATA

NO DATA

B7075-A

NO DATA

B -D

B -C

B7121-AP-F

B7121-AP-G

B7073-A

B7073-B

B7073-C

B7073-D

B7073-E

B7072-AP-A

B -B

B -A

D7265-AP-A

B A

-A

NO DATA

B7071-A

B7071-B

B7071-C

B7071-DB7069-A

B7069-B

B7070-A

B7070-B

B7068-C

B7068-B

B7067-C

B7067-D

B7066-B

B7066-C

B7065-B

B7065-A

B7121-AP-CB

-B

B7064-A

B7064-B

B7064-C

B7064-D

B7063-F

B7063-E

B7063-D

B7063-C

B7062-B

B7062-C

B7061-B

B7061-A

B7060-A

B7060-B

B7060-C

B7060-D

B7059-A

B7059-B

B7059-C

B7059-D

B7059-E

B7057-A

B7058-A

B7121-AP-A

NO

DATA

NO DATA

NO DATA

NO DATA

NO

DATANO DATANO DATA

NO DATA

NO DATANO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

B7121-AP-D

B7121-AP-E

B7080-AP-A

B7121-AP-BB7121-A

TYP.

TYP.

D7264-AP-A

01T-408

F5

TELECOM ROOM

B7000

191 SF

TYP.

B -C

A M

-0

B7083-B

B7064-F

B7086-C

B -E

B -F

B -E

B -F

B7070-C

B7069-CB7068-A

B7067-A

B7067-B

B7066-A

B7063-A

B7063-B

B7062-AB7061C

B7060-E

B7060-F

B7064-E

B7065-C

B7067-E

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

A-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B-WING

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:5

P

M

01T-107B

TELECOMMUNICATION PLAN - SEVENTH LEVEL 607-21-700

07/22/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW

CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET T-501

FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS AS

SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE SPECIFICATIONS.

PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND TRANSFER DATA

CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK. PROVIDE TEMPORARY

EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES AND OTHER DEVICES TO

ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING DATA CIRCUITS ARE

RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND ALL EXISTING

DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK, REMOVE THE

EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL PERMANENT

POSITION.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE UNTIL ALL EXISTING DEVICES ON THE EXISTING RACK ARE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT COORDINATION

DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. COORDINATE FIXTURES

WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR ADDITIONAL

REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD CABLE TRAY.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,

AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.

MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO

EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED SLEEVE THROUGH WALL ABOVE CEILING GRID FOR HORIZONTAL

VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH ENDS TO

PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH EXISTING

FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE OPERATIONAL.

CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

14. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENETRATIONS TO TR

ABOVE/BELOW.

15. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

16. ALL OPERATING ROOM DATA DEVICES TO BE MOUNTED AT 48" AFF.

17. AREA OF HARD CEILING. VIF - NOT ALL LOCATIONS NOTED. CONTRACTOR TO

UTILIZE CABLE HOOKS AS REQUIRED TO PROVIDE CABLE ROUTING AS INDICATED

AT PINCH POINTS WITHIN HARD CEILING SPACES.

18. EXISTING EQUIPMENT TO BE DEMOLISHED.

19. EXISTING EQUIPMENT TO BE RELOCATED TO NEW TELECOM ROOM LOCATION.

20. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

21. CATV HEAD-END EQUIPMENT. SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.

22. SATELLITE DISH FOR NEW HEAD-END FOR CATV. COORDINATE LOCATION WITH

EXISTING CONDITIONS.

23. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

SCALE: 1/8" = 1'-0"

C1

ET_08 SEVENTH LEVEL - A WING

SCALE: 1/8" = 1'-0"

F1

ET_08 SEVENTH LEVEL - B WING

GENERAL NOTES

KEYNOTES

Revisions: Date:

07/22/202207 /22

WAP

WAP

WAP

WAP

WAP

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

OFFICE

A8006

OFFICE

A8008OFFICE

A8004

OFFICE

A8002

RECOVERY ROOM

A8001

Room

B8054

MECHANICAL ROOM

D8206

DUMBWAITER

D8208

STORAGE / SUPPLY

D8009

CORRIDOR

D8205

ELEC

D8003

TELE

D8204

ELEVATOR HOISTWAY

D8202

CORRIDOR

D8200

MECHANICAL

D8201

Room

STAIR 7

MECHANICAL ROOM

D8207

CLEAN SUPPLY ROOM

A8003

C

T

-1 B

D -A

P -A

D8205-AP-A

D8206-AP-A

D8202-AP-A

STAIR7-AP-A

A8001-AP-A

A -D

A8001-C

A8001-B

A8001-A

A -A

A8002-A

A8002-C

A8002-AP-A

A8002-B

A -A

A -B

A8006-A

A8006-B A8006-C

A8006-D

A8006-E

A8008-C

A8008-B

A8008-D

A8008-E

A -A

TYP.

TYP.

01T-409

F1

TELECOM ROOM

D8000

TYP.

D -C

A M

-0

TELECOM ROOM

B8047

136 SF

262' - 0"

TELECOM ROOM

D8000

166 SF

TELECOM ROOM

B8000

191 SF

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

D-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:5

P

M

01T-108A

TELECOMMUNICATION PLAN - EIGHTH LEVEL 607-21-700

07/22/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW

CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET T-501

FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS AS

SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE SPECIFICATIONS.

PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND TRANSFER DATA

CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK. PROVIDE TEMPORARY

EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES AND OTHER DEVICES TO

ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING DATA CIRCUITS ARE

RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND ALL EXISTING

DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK, REMOVE THE

EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL PERMANENT

POSITION.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE UNTIL ALL EXISTING DEVICES ON THE EXISTING RACK ARE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT COORDINATION

DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. COORDINATE FIXTURES

WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR ADDITIONAL

REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD CABLE TRAY.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,

AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.

MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO

EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED SLEEVE THROUGH WALL ABOVE CEILING GRID FOR HORIZONTAL

VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH ENDS TO

PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH EXISTING

FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE OPERATIONAL.

CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

14. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENETRATIONS TO TR

ABOVE/BELOW.

15. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

16. ALL OPERATING ROOM DATA DEVICES TO BE MOUNTED AT 48" AFF.

17. AREA OF HARD CEILING. VIF - NOT ALL LOCATIONS NOTED. CONTRACTOR TO

UTILIZE CABLE HOOKS AS REQUIRED TO PROVIDE CABLE ROUTING AS INDICATED

AT PINCH POINTS WITHIN HARD CEILING SPACES.

18. EXISTING EQUIPMENT TO BE DEMOLISHED.

19. EXISTING EQUIPMENT TO BE RELOCATED TO NEW TELECOM ROOM LOCATION.

20. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

21. CATV HEAD-END EQUIPMENT. SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.

22. SATELLITE DISH FOR NEW HEAD-END FOR CATV. COORDINATE LOCATION WITH

EXISTING CONDITIONS.

23. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

SCALE: 1/8" = 1'-0"

F3

TELECOMMUNICATION PLAN - EIGHTH

LEVEL

SCALE: 1" = 100'-0"

B1

DIAMOND ANALYSIS - EIGHTH LEVEL

GENERAL NOTES

KEYNOTES

Revisions: Date:

07/22/202207 /22

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP WAP

WAP WAP

WAP

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

BEDROOM

B8060

BEDROOM

B8062

BEDROOM

B8064

BEDROOM

B8066

BEDROOM

B8068

BEDROOM

B8072

BEDROOM

B8074

BEDROOM

B8076

BEDROOM

B8080

BEDROOM

B8082

BEDROOM

B8084

BEDROOM

B8086

BEDROOM

B8088 BEDROOM

B8092

BEDROOM

B8094

BEDROOM

B8096

STAFF LOUNGE

B8099

FAMILY ROOM

B8097

TOILET

B8095

NOURISHMENT

B8091A

NURSE STATION

B8091

MED PREP ENTRY

B8089

MED PREP

B8089A

CLEAN UTILITY ROOM

B8087

EQUIPMENT

B8085

CLEAN LINEN

B8083

EQUIPMENT

B8081

SOILED UTILITY

B8079

Room

STAIR 2

FAMILY ROOM

B8073

TOILET

B8071

OFFICE

B8069A

NURSE STATION

B8069

MED PREP ENTRY

B8067

MED PREP

B8067A

CLEAN LINEN

B8061

CLEAN UTILITY

B8065

SUPPLIES

B8059

Room

STAIR 2

CORRIDOR

B8045

CORRIDOR

B8048

OFFICE

B8063

CORRIDOR

B8045

/C1 01T-108B

B -C

B8063-B

B8063-A

B -A

B8067A-A

B8067-B

B8067-A

B -D

B -E

B -C

B -B

B

-AB8069-L

B8069-K

B -J

B -H

B -G

B -F

B8069-N A8069-OB8069-M

B -R

B -Q

B -P

B8073-A

B -A

B8079-A

NO DATA

NO DATA

B8081-D

B8081-C

B8081-B

B8081-A

NO DATA

B8085-A

B8087-A

B8089-A

NO DATA

B8091-T

B8091-S

B8091-Q

B8091-R

B -P

B8091-N

B8091-O

B8091-L

B8091-M

B8091-J

B8091-K B8091-G

B8091-H

B -F

B -E

B -A

B -B

B -C

B8091-D

NO DATA

NO DATA

B8097-B

B8097-A

B -A

B -B

B -H

B -G

B -F

B -E

B -D

B -C

B -B

B -A

B -A

B8096-C B8096-D B8096-E

B8096-F B8096-G B8096-H

B8096-J B8096-K B8096-L

B -L

B8094-J B8094-H B8094-G

B8094-F B8094-E B8094-D

B8094-C B8094-B B8094-A

B -A

B8092-C B8092-D B8092-E

B8092-F B8092-G B8092-H

B8092-J B8092-K B8092-L

B -M

B8088-G

B8088-F

B8088-J

B8088-D B8088-E

B8088-C B8088-B B8088-A

B8088-H B8086-C B8086-D B8086-E

B8086-F B8086-G B8086-H

B8086-J B8086-K B8086-L

B -A

B -L

B8084-H

B8084-F

B8084-J

B8084-D B8084-E

B8084-C B8084-B B8084-A

B8084-G

B8082-C B8082-D B8082-E

B8082-F B8082-G

B8082-H

B8082-J B8082-K B8082-L

B -A

B -L

B8080-J B8080-H B8080-G

B8080-F B8080-E B8080-D

B8080-C B8080-B B8080-A

B8076-D B8076-E B8076-F

B8076-G

B8076-H B8076-J

B8076-K B8076-L B8076-M

B -A

B -F

B -E

B -L

B8074-J B8074-H B8074-G

B8074-F B8074-E B8074-D

B8074-C B8074-B B8074-A

B8072-C B8072-D B8072-E

B8072-F

B8072-G

B8072-H

B8072-J B8072-K B8072-L

B -A

B -D

B -C

B -B

B -A

B -L

B8068-J B8068-H B8068-G

B8068-F B8068-E B8068-D

B8068-C B8068-B B8068-A

B8066-C B8066-D B8066-E

B8066-F B8066-G

B8066-H

B8066-J B8066-K B8066-L

B -A

B8062-C

B8062-D B8062-E

B8062-F B8062-G B8062-H

B8062-J B8062-K B8062-L

B -A

B -M

B8064-H

B8064-F

B8064-J

B8064-D B8064-E

B8064-C B8064-B B8064-A

B8064-G

B8060-D B8060-C

B8060-E

B8060-F B8060-G B8060-H

B8060-J

B8060-K

B8060-LB8060-A

B8045-AP-B

B8048-AP-A

B8048-AP-B

B8048-AP-C

B8048-AP-D

B8045-AP-A

NO DATA

NO DATA

B8081-AP-A

B8099-AP-A

TYP.

TYP.

01T-409

F4

TELECOM ROOM

B8000

191 SF

TYP.

B8000-CAM-01

ELEC ROOM

B8075

B8096-B B8094-K

B8092-B

B8088-K

B8088-LB8086-BB8084-KB8082-B

B8080-K

B8076-B

B8076-CB8074-KB8072-BB8068-K

B8066-B

B8064-K

B8064-LB8062-B

01T-409

F8

OFFICE

A8010

CLEAN SUPPLY ROOM

A8003

CORRIDOR

A8000

WAITING ROOM

B8052

OFFICE

B8056

STAFF LOUNGE

B8058

MECH ROOM

B8057

MEDICAL GAS

B8057A

MECHANICAL ROOM

B8049

ELEVATOR LOBBY

B8044

OFFICE

A8012

WOMENS TOILET

A8018A

WOMENS LOCKER ROOM

A8018

ENTRY

A8020

OFFICE

A8022

OFFICE

A8024

OFFICE

A8026

OFFICE

A8028

OFFICE

A8030

OFFICE

A8032

OFFICE

A8034

OFFICE

A8036

OFFICE

A8038

OFFICE

A8040

OFFICE

A8042

OFFICE

A8044 DUMBWAITER

B8046

TELECOM ROOM

B8047

Room

STAIR 3

OFFICE

A8043

OFFICE

A8043A

WOMENS TOILET

A8041

MENS TOILET

A8039

CONFERENCE ROOM

A8035

ELECTRICAL

A8033

OFFICE

A8029

HAC

A8031

MENS TOILET

A8019A

ENTRY

A8023

MENS LOCKER ROOM

A8019

STOR.

A8021

CORRIDOR

A8025

F

T

-1 B

F

T

-1 A

A -B

A -C

A8003-AP-A

A -A

A8010-B A8012-A A

-D

A8012-B

A8012-AP-A

A8012-C

A8019-C

A -A

A -B

A -A

A -B

A -A

A -A

A -A

A -F

A -G

A8035-E

A8035-D

A -C

A8035-AP-A

A8035-A

A8035-B

A8043-B

A8043-A

A8043A-A

A8043A-AP-A

A8018-A

A8018-B

A8020-A

A8020-B

A8022-B

A8022-A

A8022-C

A8022-D

A8024-B

A8024-A

A8024-C

A8024-D

A8026-B

A8026-A

A8026-C

A8026-D

A8026-AP-A

A8028-B

A8028-A

A8030-C

A8030-A

A8030-D

A8030-E

A8030-B

A8032-A

A8032-C

A8032-D

A8032-B

A8034-A

A8034-C

A8034-D

A8034-B

A8036-A

A8036-C

A8036-D

A8036-B

A8038-AP-A

A8038-B

A8038-A

A8040-B

A8040-A A8042-B

A8042-A

A8044-A

A -A

B8044-A

B -A

B8044-AP-A

B -A

B -A

B

-BB8058-A

NO DATA

NO DATA NO DATA

NO DATA NO DATA

NO DATA

NO DATA

B -B

01T-409

C8

TYP.

B8047-CAM-01

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

A-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B-WING

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:0

P

M

01T-108B

TELECOMMUNICATION PLAN - EIGHTH LEVEL 607-21-700

07/22/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW

CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET T-501

FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS AS

SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE SPECIFICATIONS.

PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND TRANSFER DATA

CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK. PROVIDE TEMPORARY

EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES AND OTHER DEVICES TO

ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING DATA CIRCUITS ARE

RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND ALL EXISTING

DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK, REMOVE THE

EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL PERMANENT

POSITION.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE UNTIL ALL EXISTING DEVICES ON THE EXISTING RACK ARE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT COORDINATION

DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. COORDINATE FIXTURES

WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR ADDITIONAL

REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD CABLE TRAY.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,

AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.

MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO

EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED SLEEVE THROUGH WALL ABOVE CEILING GRID FOR HORIZONTAL

VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH ENDS TO

PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH EXISTING

FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE OPERATIONAL.

CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

14. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENETRATIONS TO TR

ABOVE/BELOW.

15. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

16. ALL OPERATING ROOM DATA DEVICES TO BE MOUNTED AT 48" AFF.

17. AREA OF HARD CEILING. VIF - NOT ALL LOCATIONS NOTED. CONTRACTOR TO

UTILIZE CABLE HOOKS AS REQUIRED TO PROVIDE CABLE ROUTING AS INDICATED

AT PINCH POINTS WITHIN HARD CEILING SPACES.

18. EXISTING EQUIPMENT TO BE DEMOLISHED.

19. EXISTING EQUIPMENT TO BE RELOCATED TO NEW TELECOM ROOM LOCATION.

20. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

21. CATV HEAD-END EQUIPMENT. SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.

22. SATELLITE DISH FOR NEW HEAD-END FOR CATV. COORDINATE LOCATION WITH

EXISTING CONDITIONS.

23. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

SCALE: 1/8" = 1'-0"

F1

TELECOMMUNICATION PLAN - EIGHTH

LEVEL

SCALE: 1/8" = 1'-0"

C1

TELECOMMUNICATION PLAN - EIGHTH

LEVEL

TYP.

TYP.

GENERAL NOTES

KEYNOTES

Revisions: Date:

07/22/202207 /22

RX

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

D9202-A

MECHANICAL ROOM

D9201

MECHANICAL ROOM

D9202

Room

STAIR NO. 7

ENTRY

D9200

D9202-B

D9202-C

D9202-D

D9201-A

F

T

-1

MECHANICAL ROOM

B9001

DUMBWAITER ROOM

B9001A

Room

B9004

ENTRY

B9000

MECHANICAL ROOM

A9012

DB2-241-A-AB

-A

B A

-A

A9012-A

B9001-A

01T-109

C6

TELECOM ROOM

B9001A

150 SF

C

T

-1

B9001A-CAM-01

TELECOM ROOM

B9001A

150 SF

TYP.

TYP.

TYP.

TYP.

TYP.

B A

-C A

M -0

TYP.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

A-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B-WING

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:0

P

M

01T-109

TELECOMMUNICATION PLANS - PENTHOUSE 607-21-700

07/22/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW

CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET T-501

FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS AS

SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE SPECIFICATIONS.

PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND TRANSFER DATA

CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK. PROVIDE TEMPORARY

EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES AND OTHER DEVICES TO

ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING DATA CIRCUITS ARE

RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND ALL EXISTING

DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK, REMOVE THE

EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL PERMANENT

POSITION.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE UNTIL ALL EXISTING DEVICES ON THE EXISTING RACK ARE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT COORDINATION

DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. COORDINATE FIXTURES

WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR ADDITIONAL

REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD CABLE TRAY.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,

AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.

MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO

EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED SLEEVE THROUGH WALL ABOVE CEILING GRID FOR HORIZONTAL

VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH ENDS TO

PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH EXISTING

FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE OPERATIONAL.

CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

14. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENETRATIONS TO TR

ABOVE/BELOW.

15. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

16. ALL OPERATING ROOM DATA DEVICES TO BE MOUNTED AT 48" AFF.

17. AREA OF HARD CEILING. VIF - NOT ALL LOCATIONS NOTED. CONTRACTOR TO

UTILIZE CABLE HOOKS AS REQUIRED TO PROVIDE CABLE ROUTING AS INDICATED

AT PINCH POINTS WITHIN HARD CEILING SPACES.

18. EXISTING EQUIPMENT TO BE DEMOLISHED.

19. EXISTING EQUIPMENT TO BE RELOCATED TO NEW TELECOM ROOM LOCATION.

20. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

21. CATV HEAD-END EQUIPMENT. SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.

22. SATELLITE DISH FOR NEW HEAD-END FOR CATV. COORDINATE LOCATION WITH

EXISTING CONDITIONS.

23. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

SCALE: 1/8" = 1'-0"

C4

TELECOMMUNICATIONS PLAN -

PENTHOUSE LEVEL

SCALE: 1/8" = 1'-0"

F1

TELECOMMUNICATIONS PLAN -

PENTHOUSE LEVEL

SCALE: 1/2" = 1'-0"

C6

TELECOMMUNICATION ENLARGED

PLAN - PENTHOUSE LEVEL - ROOM

B9001A - NEW

GENERAL NOTES

KEYNOTES

Revisions: Date:

07/22/202207 /22

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

ELEVATOR EQUIPMENT

B9002

B9002-B

B -A

B9002-AP-A

TYP.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

A-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:3

:1

P

M

01T-110

TELECOMMUNICATION PLANS - UPPER

PENTHOUSE LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMU…