Attachment 23 - Asbestos Survey and Lead Paint Report.pdf

PDF 6 MB Posted

Attached to
36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI Federal contract opportunity
Solicitation number
36C77623B0011
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This is a solicitation for a firm-fixed-price design-bid-build contract to provide EHRM infrastructure upgrades at the Madison VA Medical Center in Madison, Wisconsin. The scope of work includes general construction and replacement of all telecommunications cable, outlets, and associated equipment for multiple buildings on the VA campus. The Department of Veterans Affairs Technology Acquisition Center Austin will award a single contract. Bids are due by the date specified. The contractor will furnish all labor, materials, equipment, and supervision to complete the project in accordance with provided drawings and specifications.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI, newest first.
File Type Posted
36C77623B0011 0004_REVISED.pdf PDF
36C77623B0011 0004.pdf PDF
36C77623B0011 0003.pdf PDF
Attachment 32 - CATV rack1btm.jpg JPG image
Attachment 33 - CATV rack2top.jpg JPG image
Attachment 34 - CATV rack2btm.jpg JPG image
Attachment 27 - Technical Questions and Answers Volume 2.pdf PDF
Attachment 30 - Existing Column Load Summary.pdf PDF
Attachment 28 - Strengthening of Concrete with FRP.docx DOCX document
Attachment 29 - Sheet 1-S-15 from Ref_Existing - D - Wing_Addition.pdf PDF
Attachment 31 - CATV rack1top.jpg JPG image
Attachment 35 - CATV back of rack.jpg JPG image
Attachment 24 - EHRM Madison - Floor to Finish Heights.pdf PDF
36C77623B0011 0002.pdf PDF
Attachment 25 - EHRM Madison - Attendance Sheet.pdf PDF
Attachment 26 - Technical Questions and Answers.pdf PDF
36C77623B0011 0001.pdf PDF
S02 - Solicitation - 36C77623B0011 - EHRM Infrastructure Upgrades - Madison.pdf PDF
Attachment 01 - EHRM Madison - Specifications.pdf PDF
Attachment 13 - EHRM Madison - Drawings - Building 07.pdf PDF
Attachment 14 - EHRM Madison - Drawings - Building 12.pdf PDF
Attachment 17 - EHRM Madison - Drawings - IFC - SITE.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 22 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 03 - EHRM Madison - Drawings - Building 01 - Part 2.pdf PDF
Attachment 05 - EHRM Madison - Drawings - Building 01 - Part 4.pdf PDF
Attachment 15 - EHRM Madison - Drawings - Building 15.pdf PDF
Attachment 11 - EHRM Madison - Drawings - Building 05.pdf PDF
Attachment 12 - EHRM Madison - Drawings - Building 06.pdf PDF
Attachment 02 - EHRM Madison - Drawings - Building 01 - Part 1.pdf PDF
Attachment 04 - EHRM Madison - Drawings - Building 01 - Part 3.pdf PDF
Attachment 06 - EHRM Madison - Drawings - Building 01 - Part 5.pdf PDF
Attachment 08 - EHRM Madison - Drawings - Building 01 - Part 7.pdf PDF
Attachment 09 - EHRM Madison - Drawings - Building 02.pdf PDF
Attachment 10 - EHRM Madison - Drawings - Building 04.pdf PDF
Attachment 16 - EHRM Madison - Drawings - Building 22.pdf PDF
Attachment 19 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 20 - Dane County - Wage Rates.pdf PDF
Attachment 21 - SOW - EHRM Infrastructure Upgrades - Madison.pdf PDF
Attachment 07 - EHRM Madison - Drawings - Building 01 - Part 6.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

13400 15th Ave North Minneapolis, MN 55441 P (763) 489-3100

Prepared for:

Triple C – The A&E Group

410 East Grand Avenue, Suite 201C

Laramie, Wyoming 82070-3701

Asbestos and Lead- Based Paint Inspection Pre-Renovation

January 4, 2023 | Report Number: MP227415

13400 15th Ave North Minneapolis, MN 55441

P (763) 489-3100

F (763) 489-3101

Terracon.com

Facilities | Environmental | Geotechnical | Materials

January 4, 2023

Triple C – The A&E Group 410 East Grand Avenue, Suite 201C Laramie, Wyoming 82070-3701

Attn: Kevin Luke P: (307) 460-2054 E: kevin.luke@tripleCaeg.com

Re: Pre-Renovation Asbestos and Lead-Based Paint Inspection Madison VA Hospital – EHRM Infrastructure Upgrades (607-21-700) 2500 Overlook Terrace Madison, Wisconsin 53705 Terracon Project No. MP227415

Dear Mr. Kevin Luke, Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above referenced site. The purpose of this report is to present the results of the Pre-Renovation Asbestos and Lead-Based Paint Inspection (Inspection) performed on December 20, 2022. This Inspection was conducted in general accordance with proposal number PMP227415, dated December 14, 2022.

Asbestos-containing materials (ACM) were identified in the samples collected from the subject building. Lead-Based Paint (LBP) was not identified during the Inspection. Please refer to the attached report for details.

Terracon appreciates the opportunity to provide this service to Triple C – The A&E Group. If you have any questions regarding this report, or if you need assistance with development of asbestos abatement specifications, project oversight or air monitoring, please contact the undersigned at

(763) 489-3126.

Sincerely, Terracon Consultants, Inc.

Jon Litchy Mike Willey Field Scientist Department Manager D (763) 489-3121 D (763) 489-3126 M (763) 843-8567 M (612) 269-3439 Jonathon.litchy@Terracon.com mike.willey@Terracon.com

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

1.3 Standard of Care

2.0 PROJECT DESCRIPTION

2.1 Building Description

2.2 Existing Documents

3.0 SCOPE OF SERVICES

3.1 Asbestos Inspection

3.2 Sampling for Lead in Paints and Coatings

4.0 REGULATORY REVIEW

4.1 Asbestos

4.2 Lead-Based Paints or Coatings

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos Inspection Findings

5.2 Lead-Based Paint Inspection Findings

5.3 Beneficial Reuse

5.4 Additional Services

6.0 GENERAL REPORTING LIMITATIONS

APPENDICES

APPENDIX A EXHIBIT 1 PROPERTY LOCATION MAP

EXHIBIT 2 PROPERTY LAYOUT MAP

EXHIBIT 3 BASEMENT SAMPLE LOCATION MAP

EXHIBIT 4 GROUND FLOOR SAMPLE LOCATION MAP

EXHIBIT 5 FIRST FLOOR SAMPLE LOCATION MAP

EXHIBIT 6 SECOND FLOOR SAMPLE LOCATION MAP

EXHIBIT 7 THIRD FLOOR SAMPLE LOCATION MAP

EXHIBIT 8 FOURTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 9 FIFTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 10 SIXTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 11 SEVENTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 12 EIGHTH FLOOR SAMPLE LOCATION MAP

APPENDIX B TABLE I: ASBESTOS ASSESSMENT BY FUNCTIONAL AREA

TABLE II: LEAD BASED PAINT ASSESSMENT

APPENDIX C ASBESTOS BULK SAMPLE LABORATORY ANALYTICAL REPORT

APPENDIX D PHOTO LOG OF CONFIRMED ACM

APPENDIX E CERTIFICATIONS

Responsive ■ Resourceful ■ Reliable 1

PRE-RENOVATION ASBESTOS AND LEAD-BASED PAINT

INSPECTION

Madison VA Hospital 2500 Overlook Terrace

Madison, Wisconsin 53705 Terracon Project No. MP227415

January 4, 2023

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) was retained by Triple C – The A&E Group (Client) to conduct a Pre-Renovation Asbestos and Lead-Based Paint Inspection (Inspection) and to prepare this report (Inspection Report) for select locations of Building 01 at the Madison VA Hospital (Building) addressed as 2500 Overlook Terrace, Madison, Wisconsin 53705 (Property). Exhibit 1 in Appendix A shows the location of the Property. Exhibit 2 in Appendix A is an aerial photograph of the Property showing the Building and surrounding features. Exhibits 3 - 12 in Appendix A show the location of sampled materials and the boundary of the Inspection area (Inspection Area).

The Inspection was conducted on December 20, 2022, by a State of Wisconsin certified asbestos inspector Jon Litchy in general accordance with proposal number PMP227415 dated December 14, 2022. A copy of his inspector certificate is included in Appendix E.

1.1 Project Objective

The objective of the Inspection Report is to identify the presence, quantity, and location of asbestos-containing materials (ACM), and location of lead-based paint (LBP) in coatings on building components or substrates that may be subject to beneficial reuse within the Inspection Area at the time of the field assessment, subject to the stated reporting and sampling limitations.

1.2 Reliance

This report is for the exclusive use of Client for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and Client. Reliance on this report by Client and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and Terracon’s Agreement for Services. The limitations of liability defined in Terracon’s Agreement for Services are the aggregate limit of Terracon’s liability to Client.

Pre-Renovation Asbestos and Lead-Based Paint Inspection Madison VA Hospital | Madison, Wisconsin January 4, 2023 | Project No. MP227415

1.3 Standard of Care

This Inspection was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our Inspection of the building. The information contained in this report is relevant to the date on which this Inspection was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Client for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

2.0 PROJECT DESCRIPTION

Terracon understands the Inspection was requested due to planned renovation activities regarding EHRM infrastructure upgrades as shown in drawings associated with project number 607-21-700, dated July 22, which require management, documentation, and communication of various building materials present within the Inspection Area on the Property. The project objective is based upon information required to communicate for compliance with the following summarized requirements:

The Environmental Protection Agency (EPA) regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM (RACM) be identified, classified and quantified prior to planned disturbances or demolition activities.

The Occupational Safety and Health Administration (OSHA) 29 CFR 1926.1101 Subpart Z, Asbestos; regulates asbestos exposure during renovation/demolition activities and requires building and facility owners to determine the presence, location and quantity of Asbestos Containing Materials (ACM) and/or Presumed ACM (PACM) prior to renovation/demolition activities.

OSHA 29 CFR 1926.62 Subpart D, Lead, applies to all renovation/demolition where an employee may be occupationally exposed to lead. The employer shall communicate information concerning lead hazards and communicating information concerning hazards and appropriate protective measures to employees including training.

2.1 Building Description

Building description and general construction information for the structure assessed on the Property include:

Madison VA Hospital – 2500 Overlook Terrace, Madison, Wisconsin 53705

Building Use:

Medical - Commercial

Occupancy Status: Occupied

Date of Construction:

1941 Renovation Dates: Unknown

No. of Floors 11 Building Square Footage:

Unknown

Main Structure:

Poured Concrete foundation with concrete masonry unit (CMU) walls, brick and mortar façade.

Exterior Finishes: CMU, brick, and mortar façade.

Interior Finishes:

Sheetrock and plaster walls & ceilings, carpet, vinyl and/or ceramic tile flooring, suspended ceiling tiles.

Roofing System: Not Assessed

2.2 Existing Documents

No existing documents were provided to Terracon for the Inspection Area.

3.0 SCOPE OF SERVICES

3.1 Asbestos Inspection

The Inspection was conducted by State of Wisconsin certified asbestos inspectors in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763, the Asbestos Hazard Emergency Response Act (AHERA). A summary of Inspection activities is provided below.

3.1.1 Visual Assessment

Inspection activities were initiated with visual observation of the Inspection Area to identify accessible homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.

3.1.2 Physical Assessment

A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material that when dry, may be crumbled, pulverized, or reduced to powder by hand pressure, including previously non-friable material when the material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure. Friability was assessed by physically touching suspect materials. The materials were classified into the three following condition categories:

Not Damaged condition (ND); material with less than or equal to one percent damage or deterioration for the subject surface.

Damaged condition (D); materials which greater than one percent although less than ten percent distributed damage or less than twenty five percent localized damage. Damage is determined when deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that its bond to the substrate (adhesion) is inadequate or which for any other reason lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage;

significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM; or damage to jacketing or coatings; and

Significantly Damaged condition (SD); materials where damage impacts at least ten percent of a localized subject surface area or if the damage is evenly distributed representing an area of at least twenty-five percent of the subject surface area.

3.1.3 Sample Collection

Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each HA. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker. The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon collected eighty-nine (89) bulk samples of suspect ACM from the Property that were separated by the analytical laboratory into one hundred sixty-five (165) individual layers for analysis.

3.1.4 Sample Analysis

Bulk samples were submitted under chain of custody to an analytical laboratory accredited by the National Institute of Standards and Technology (NIST) under the National Voluntary Laboratory Accreditation Program (NVLAP), for analysis by polarized light microscopy per EPA methodology

EPA/600/R-93/116.

The percentage of asbestos, where applicable, was determined by microscopic visual estimation or point counting. The DHS, OSHA and EPA define ACM as a material which contains greater than one percent asbestos by qualitative or quantitative analysis techniques. The EPA NESHAP requires quantitative analysis, commonly referred to as a “point count”, for all qualitative analysis results when asbestos is detected in concentrations less than one to ten percent. However, under common practice, qualitative results greater than three and less than ten percent are often accepted to be ACM.

3.2 Sampling for Lead in Paints and Coatings

The Inspection was conducted with the intent of identifying lead in painted/coated building materials that might be subject to processing for beneficial reuse, and for providing information useful in the communication of lead hazards to workers and other occupants. A summary of Inspection activities is provided below.

3.2.1 Visual Assessment

Inspection activities were initiated with visual observation within the Inspection Area to identify accessible homogeneous areas of coated building components. Homogenous coatings were defined as areas of similar coating/painting history, such as color, building component, and location.

3.2.2 Physical Assessment

A physical assessment of each homogeneous coating was conducted to assess the condition of the coating, and its potential for creating lead dust. The coatings were classified into the three following condition categories:

Intact condition: surface is intact.

Fair condition: damage/deterioration limited to less than 10 square feet on large surface exterior components or 2 square feet on large surface interior components, or less than 10 percent of small surface interior/exterior components; and

Poor condition; damage/deterioration greater than 10 square feet on large surface exterior components or 2 square feet on large surface interior components, or greater than 10 percent of small surface interior/exterior components.

3.2.3 Sample Analysis

Coating materials were analyzed using a SciAps X-550 series multi-element spectrum analyzer, Serial No. 910-500137. The SciAps X-550 is a field portable x-ray florescence (XRF) spectrum analyzer capable of identifying lead concentrations in coatings and paint, which are expressed in units of milligrams per square centimeter (mg/cm2). The XRF was calibrated as per manufacturer recommendations before and after use.

4.0 REGULATORY REVIEW

4.1 Asbestos

The following are regulations impacting the methods and findings of this Inspection. It is not a comprehensive list of all asbestos regulations.

4.1.1 Federal Asbestos Regulations

The asbestos portion of NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos-containing material (RACM).

The asbestos NESHAP regulation classifies ACM as either RACM, Category I non-friable ACM or Category II non-friable ACM. RACM includes all friable ACM, along with Category I and Category II non-friable ACM that has become friable, will be or has been subjected to sanding, grinding, cutting, or abrading, or ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics and asphalt roofing products that contain more than 1% asbestos.

Category II non-friable ACMs are all non-friable ACMs that are not Category I non-friable ACM.

In their interpretation of layered drywall systems (joint compound, tape, wall board substrates), the EPA has ruled that unless the entire wall system contains more than 1% friable or potentially friable ACM (verified by Point Count analysis), then the total wall system is not considered RACM and is not subject to NESHAP regulations. However, OSHA 29 CFR 1926.1101 requires that workers performing construction-related activities (including demolition) be protected from asbestos fibers in excess of the permissible exposure limit of 0.1 fibers/cc air, regardless of the source of the asbestos fibers.

4.1.2 State and County Asbestos Regulations

The Wisconsin Department of Natural Resources (WDNR) regulates renovation or demolition asbestos-related work under Wisconsin Administrative Code, NR 447.01 to 447.18. Asbestos Emissions from Demolition/Renovation Activities. The owner or operator must provide WDNR with written notification at least 10 working days prior to the commencement of any renovation or demolition work involving ACM over 260 linear feet on pipes, or 160 square feet on other facility components, or 35 cubic feet of facility components where the length or area could not be measured previously.

The Wisconsin Department of Health Services (DHS) regulates employee exposure to asbestos for demolition or renovation. Projects exceeding 3 square feet, 3 linear feet, or greater than one glovebag must be notified to DHS.

The OSHA standards 29 CFR 1910.1001 and 29 CFR 1926.1101 regulate employee exposure to asbestos. The OSHA standards require that employee exposure to airborne asbestos fibers be maintained at or below 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA), and not exceed 1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as OSHA’s permissible exposure limits (PELs). The OSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. Building owners are required to maintain buildings and equipment in a safe operating condition, including the repair, removal, encapsulation, or enclosure of damaged ACMs.

4.2 Lead-Based Paints or Coatings

Under the US EPA Hazard Standards for Lead in Paint, Dust and Soil (TSCA Section 403), lead-based paint means paint or other surface coatings that contain lead equal to or in excess of 1.0 milligrams per square centimeter or more than 0.5 percent by weight. This rule establishes standards to help property owners, lead paint professionals and government agencies identify lead hazards in residential paint, dust and soil. The rule establishes standards for lead-based paint hazards (including hazards from lead in dust and soil) in most pre-1978 housing and child-occupied facilities.

Please note that it is Terracon’s understanding that the Inspection Area does not and will not meet the definition of “target housing”. Target housing is a home or residential unit built before 1978. Therefore, the lead testing conducted herein was not intended to comply with regulations for target housing, including the HUD Lead Safe Housing Rule (LSHR) (24 CFR Part 35, subparts B-R), the EPA/HUD Lead Disclosure Rule (the identical 24 CFR 35, subpart A and 40 CFR 745, subpart F, or the EPA Renovation, Repair and Painting (RRP) Rule.

5.0 FINDINGS AND RECOMMENDATIONS

5.1 Asbestos Inspection Findings

Suspect homogeneous materials identified and subsequently sampled for asbestos content during the Inspection are listed in the Chain of Custody associated with the laboratory analytical report in Appendix C. Suspect materials identified within the Inspection Area of the Building are shown on Table I: Asbestos Assessment by Functional Space in Appendix B. Drawings showing the locations of suspect ACM samples collected are shown in Exhibits 3-12 in Appendix A.

5.1.1 Asbestos Materials Summary Table

The following Asbestos Materials Summary Table lists all identified materials requiring management due to asbestos, including confirmed asbestos-containing materials (ACM – materials containing greater than one percent asbestos), materials assumed to be ACM but were not sampled due to functional, aesthetic, or safety concerns, and materials containing less than one percent asbestos (which may be managed differently than ACM).

Table 1

Madison VA Hospital Building 01 – 2500 Overlook Terrace, Madison Wisconsin 53705

Asbestos Materials Summary Table

Confirmed Asbestos-Containing Materials (ACM)

Mastic (Black) Associated w/ Dark Gray Sheet Flooring – Room #C126

Carpet Mastic (Black) – Room #C129

Green Floor Tile and Black Mastic – Hallway #C127

Floor Tile (Tan) and associated Black Mastic (under carpet) – Room# C121 and C121A

Floor Tile and Black Mastic under Green Sheet Flooring – Room # CB1-025

12”x12” Vinyl Floor Tile White w/ Tan Streaks and Associated Black Mastic

12”x12” Vinyl Floor Tile White w/ Gray Streaks and Associated Black Mastic

9”x9” Vinyl Floor Tile – Tan and Associated Black Mastic

9”x9” Vinyl Floor Tile White w/ Tan Streaks and Associated Black Mastic

9”x9” Vinyl Floor Tile Gray w/ Black Streaks and Associated Black Mastic

Assumed Asbestos-Containing Materials

None None

Unclassified Asbestos Materials (Containing Less Than One-Percent Asbestos)* and Asbestos Content as Verified by Point Count Analysis

None None

* Materials with asbestos in concentrations of one percent or less, as verified by Point Count analysis, are not Asbestos-Containing Materials by EPA definition. However, some provisions of OSHA regulations still apply to disturbance of materials containing asbestos in any concentration, including the use of a competent person, wet methods, regulated areas, prompt cleanup, and hazard communication.

Refer to Table I in Appendix B for additional information regarding the locations and quantities of suspect ACMs assessed. Refer to Appendix C for the laboratory analytical report. Refer to Appendix D for photographs of materials that contain asbestos.

5.1.2 Asbestos-Containing Material Classifications

As discussed in Section 4.1 ACMs, identified during the Inspection, were classified as RACM (“friable”), Category I non-friable, or Category II non-friable ACM. These categories are shown on Table I in Appendix B for each applicable material. The classifications indicated are based on the material condition at the time of the Inspection. Material condition can be subject to change due to factors such as mechanical damage (impacts, grinding, sanding, crushing, etc.), moisture damage, weathering (sun) damage, etc., which may affect material classification.

5.1.3 Asbestos Management Recommendations

Asbestos materials identified in Section 5.1 will require management prior to any demolition, renovation, or operations and maintenance work that might disturb identified or assumed asbestos materials.

If previously inaccessible suspected ACM is discovered during renovation/demolition activities, disturbance work should immediately stop, until representative samples can be collected by a licensed asbestos building inspector and laboratory results are available to render a determination regarding asbestos content within the material discovered. Supplemental inspection may be required by the EPA/MPCA for inaccessible areas or locations outside of the Inspection Area for inspection and sampling, as identified in Section 6.0 in this Inspection Report.

This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. For renovation or demolition projects Terracon recommends an MDH-accredited asbestos Project Designer be retained to prepare a project specific specification for the management and/or abatement of ACM identified in this Inspection Report, in accordance with applicable regulatory requirements. Additionally, the disposition of non-friable ACMs should be assessed by a Project Designer based on renovation or demolition plans, including specific considerations of potential for friability during renovation, demolition, and abatement, as well as disposal.

For long-term management in place, OSHA regulations require ACM remaining in the Building to be maintained in non-friable condition. Therefore, Terracon recommends an MDH-accredited asbestos Management Planner be retained to prepare an asbestos operations and maintenance (O&M) plan for the management and/or abatement of ACM identified in this Inspection Report.

The O&M plan would also help comply with OSHA and EPA regulations requiring any employee or contractor working in proximity to asbestos containing materials in the Building to be made aware of the asbestos inspection and its limitations and be provided a copy of this Inspection Report prior to work in contact with or proximity to asbestos materials.

Under WDNR policy, vinyl asbestos floor tile must remain intact to remain a Category I non-friable ACM. Because most removal techniques (including “hand methods”) involve breakage of the tile, removal of floor tile in quantities greater than regulated thresholds (160 square feet per calendar year) should be regarded as RACM work.

Other materials such as pliable or gummy caulks or mastics might be considered non-friable. Such Category II non-friable ACM need not be removed prior to demolition unless demolition will involve intentional burning, grinding, mechanically chipping, drilling, sand or bead blasting, explosive demolition or other methods which could mechanically powder the material or otherwise render it friable. In addition, building debris need not be disposed of as friable asbestos-containing waste material as long as the Category II ACM remains non-friable. However, the landfill operator shall be notified that the construction debris will contain non-friable asbestos-containing materials.

5.2 Lead-Based Paint Inspection Findings

Terracon conducted limited lead paint testing of pre-1978 paint/coatings within the Inspection Area, targeting building components that might be subjected to beneficial reuse applications impacted by renovation activities. Lead-based paint was not identified during the Inspection.

Refer to Table II in Appendix B for additional information regarding the locations and results of the LBP test locations.

5.2.1 LBP Recommendations

Terracon understands the Building on the Property is not currently considered Target Housing, is not being converted into housing and/or receiving federal assistance or HUD financing. These types of programs and level of assistance can affect some or all provisions of the EPA and/or HUD Guidelines. The Inspection Report would require supplemental testing and reporting to comply with all provisions of the EPA and HUD Guidelines.

Please note that LBP may be present on other coated/painted components of the Property. In accordance with OSHA regulations, sampling results (as available) should be provided to the contractor completing activities that will disturb any LBP or other coated surfaces potentially containing LBP so potential lead exposure assessment can be completed. Where lead is present, it should be assumed that workers will be exposed to lead above the action level and personal protective measures should be implemented until an exposure assessment is completed in accordance with OSHA regulation 29 CFR 1926.62.

5.3 Beneficial Reuse

This report does not constitute clearance for beneficial reuse of building materials. Beneficial reuse (recycling) of building materials during demolition may require prior removal of affixed ACM, PCB-containing materials (caulks), or stained (contaminated) concrete areas. Contact your Terracon project designers for guidance in regulatory compliance for beneficial reuse applications.

5.4 Additional Services

Terracon personnel accredited in asbestos abatement project design, management planning, inspection, and air monitoring, as well as lead remediation are available to assist with project design and risk assessment. We can help manage projects from start to finish, including development of project concepts, budgets, specifications, contractor bidding, contract management, project oversight and monitoring.

6.0 GENERAL REPORTING LIMITATIONS

The Inspection was conducted utilizing limited destructive sampling techniques. Therefore, efforts were made to determine if multiple layers of materials were present (e.g., flooring), although limited to the extent of allowable access points with hand tools without affecting security, fire and life safety, slips, trips and/or fall hazards including unacceptable aesthetic or functional damage to building surfaces and materials, as per the judgment of the inspector at the time of the Inspection. Therefore, suspect ACM may be present in concealed spaces, cavities, and plenums of the Building that were not inspected during the Inspection. Rooms, areas, and spaces outside the Inspection Area may include ACM and suspect materials not addressed by the Inspection.

Additional inspection by an accredited asbestos inspector is required by EPA prior to demolition or renovation that would impact such materials.

The following general areas (not exclusive) could be concealing additional identified ACM or suspect materials.

Areas outside the Inspection Area

Above Hard Ceilings in CB1-025 and CB1-024

Inside Clay Block and Mortar Walls

APPENDIX A

EXHIBIT 1 PROPERTY LOCATION MAP

EXHIBIT 2 PROPERTY LAYOUT MAP

EXHIBIT 3 BASEMENT SAMPLE LOCATION MAP

EXHIBIT 4 GROUND FLOOR SAMPLE LOCATION MAP

EXHIBIT 5 FIRST FLOOR SAMPLE LOCATION MAP

EXHIBIT 6 SECOND FLOOR SAMPLE LOCATION MAP

EXHIBIT 7 THIRD FLOOR SAMPLE LOCATION MAP

EXHIBIT 8 FOURTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 9 FIFTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 10 SIXTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 11 SEVENTH FLOOR SAMPLE LOCATION MAP

EXHIBIT 12 EIGHTH FLOOR SAMPLE LOCATION MAP

PROPERTY LOCATION MAP

Triple C - The A&E Group - 607-21-700

Madison VA - ACM LBP Sampling 2500 Overlook Terrace

Madison, WI

TOPOGRAPHIC MAP IMAGE COURTESY OF THE U.S. GEOLOGICAL SURVEY

QUADRANGLES INCLUDE: MADISON WEST, WI (1/1/1983).

13400 15th Ave N Plymouth, MN 55441-4532

MP227415

Project Manager:

Drawn by:

Checked by:

Approved by:

JAL

MJW

MJW

1”=2,000’ Ex 1&2

12/2022

Project No.

Scale:

File Name:

Date:

ExhibitMJW

APPROXIMATE

SITE LOCATION

PROPERTY LAYOUT MAP

Triple C - The A&E Group - 607-21-700

Madison VA - ACM LBP Sampling 2500 Overlook Terrace

Madison, WI

13400 15th Ave N Plymouth, MN 55441-4532

DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS

NOT INTENDED FOR CONSTRUCTION PURPOSES

MP227415

AERIAL PHOTOGRAPHY PROVIDED

BY MICROSOFT BING MAPS

JAL

MJW

MJW

AS SHOWN

Ex 1&2

12/2022

Scale:

ExhibitProject Manager:

Drawn by:

Checked by:

Approved by:

Project No.

File Name:

Date:

MJW

BUILDING 01 –

Veterans Hospital

DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS NOT

INTENDED FOR CONSTRUCTION PURPOSES

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Basement jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 3 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

jalitchy Callout 3,16 jalitchy Callout 21,22 jalitchy Callout 33,34,43 jalitchy Callout 42,44 jalitchy Callout jalitchy Callout 65,66,67,68 jalitchy Callout

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Ground Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 4 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

jalitchy Stamp

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - First Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 5 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Second Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 6 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Third Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 7 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Forth Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 8 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Fifth Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 9 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Sixth Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 10 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Seventh Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 11 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

13400 15th Avenue N. Minneapolis, MN 55441

PH. (763) 489-3100

ExhibitProject Manager:

Drawn by:

Checked by:

Arranged by:

Project No.

Scale:

File Name:

Date:

jalitchy Typewriter Sample Location Map - Eighth Floor jalitchy Typewriter Triple C - The A&E Group - 607-21-700 Madison VA - ACM LBP Sampling jalitchy Typewriter 2500 Overlook Terrace Madison, Wisconsin jalitchy Typewriter jalitchy Typewriter

MJW

jalitchy Typewriter

MJW

jalitchy Typewriter

JAL

jalitchy Typewriter

JAL

jalitchy Typewriter Exhibit 12 jalitchy Typewriter 1/4/23 jalitchy Typewriter N.T.S jalitchy Typewriter

MP227415

jalitchy Rectangle jalitchy Typewriter Inspection Area jalitchy Typewriter Suspect ACM Sample Location jalitchy Callout jalitchy Typewriter

LEGEND

APPENDIX B

TABLE I: ASBESTOS ASSESSMENT BY FUNCTIONAL AREA

TABLE II: LEAD-BASED PAINT ASSESSMENT

Table I: Asbestos Assessment by Functional Space

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

Skim Coat and Plaster 3 Ref 1,2,4-7 No -- -- -- -- Clay Block and Mortar 16 Ref 17,18 No -- -- -- --

Covebase Adhesive (Tan) 33,34 No -- -- -- -- 2'x2' Ceiling Tile (Pinhole) 41,42 No -- -- -- --

2'x2' Ceiling Tile (Rough - White) 43,44 No -- -- -- -- Green Sheet Flooring w/ Gray

Mastic 65,66 No -- -- -- --

Floor Tile Under Green Sheet Flooring w/ Black Mastic 67,68 Yes Cat. I 250 Sq. Ft. ND

Skim Coat and Plaster 7 Ref 1-6 No -- -- -- -- Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Terrazo Flooring (Black) 21,22 No -- -- -- -- Tan Ceramic Wall Block and Grout Ref 53,54 No -- -- -- --

Skim Coat and Plaster 1 Ref 2-7 No -- -- -- -- Clay Block and Mortar Ref 16,17,18 No -- -- -- -- Paper Duct Insulation 23 Ref 24,25 No -- -- -- --

Covebase Adhesive (Dark Brown) 31,32 No -- -- -- --

2'x2' Ceiling Tile (Pin and Crevasse) 45 Ref 46 No -- -- -- --

Carpet Mastic (Tan/Black) 59,60

Black Mastic -

Yes Tan Mastic -

No

Cat. I 200 Sq. Ft. ND

Skim Coat and Plaster 2 Ref 1, 3-7 No -- -- -- -- Clay Block and Mortar Ref 16,17,18 No -- -- -- -- Paper Duct Insulation 24,25 Ref 23 No -- -- -- --

Covebase Adhesive (Beige) Ref 35,36 No -- -- -- --

2'x2' Ceiling Tile (Pin and Crevasse) Ref 45,46 No -- -- -- --

Dark Gray Sheet Flooring and Mastic 57,58

Sheet Flooring -

No Mastic -

Yes

Cat. I 115 Sq. Ft. ND

Room #C126

Basement

Room # CB1-025

Room # CB1-024

Ground Floor

Room # C129

1 Refer to Section 4.1 for regulatory classification 2 Refer to Section 3.1.2 for Condition Information

Facilities | Environmental | Geotechnical | Materials Page 1 of 8

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Clay Block and Mortar Ref 16,17,18 No -- -- -- --

2'x2' Ceiling Tile (Pin and Crevasse) Ref 45,46 No -- -- -- --

Green Floor Tile w/ Black Mastic 61,62 Yes Cat. I 125 Sq. Ft. ND

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound 8 Ref 9-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- -- Covebase Adhesive (Beige) 35,36 No -- -- -- --

2'x2' Ceiling Tile (Pin and Crevasse) 46 Ref 45 No -- -- -- --

Floor Tile under Carpet (Glue, Tile, Black Mastic) 63,64

Tile and Black

Mastic - Yes

Glue - No

Cat. I 125 Sq. Ft. ND

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound 9 Ref 8,10-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Covebase Adhesive (Beige) Ref 35,36 No -- -- -- --

2'x2' Ceiling Tile (Pin and Crevasse) Ref 45,46 No -- -- -- --

Floor Tile under Carpet (Glue, Tile, Black Mastic) Ref 63,64

Tile and Black

Mastic - Yes

Glue - No

Cat. I 175 Sq. Ft. ND

Sheetrock, Tape and Joint Compound Ref 8-12 No -- -- -- --

Firestop Caulk (Red) 29 Ref 30 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Room # C127 (Hallway)

Room # C121

Room # C121A

Room # FG645

Room # FG647

1 Refer to Section 4.1 for regulatory classification

Facilities | Environmental | Geotechnical | Materials Page 2 of 8

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

Skim Coat and Plaster 4 Ref 1-3, 5-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

6" Brown Ceramic Tile, Grout and Adhesive 55,56 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- -- 6" Brown Ceramic Tile, Grout and

Adhesive Ref 55,56 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound 11 Ref 8-10,12 No -- -- -- --

White Wall Mortar 13,14,15 No -- -- -- --

Clay Block and Mortar 17 Ref 16,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Covebase Adhesive (Gray) 39,40 No -- -- -- -- 12"x12" Vinyl Floor Tile White w/ Tan Streaks and Black Mastic

75,76 Ref 77 Yes Cat. I 80 Sq. Ft. ND

Skim Coat and Plaster 5 Ref 1-4, 6,7 No -- -- -- --

Sheetrock, Tape and Joint Compound 10 Ref 8,9,11,12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Tan Ceramic Wall Block and Grout Ref 53,54 No -- -- -- --

Room # B3110A

First Floor

Room # B1121

Room #B1122

Second Floor

Room # B2053

Third Floor

1 Refer to Section 4.1 for regulatory classification

Facilities | Environmental | Geotechnical | Materials Page 3 of 8

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

Room # B3110A 12"x12" Vinyl Floor Tile White w/ Gray Streaks and Black Mastic

78,79,80 Yes Cat. I 80 Sq. Ft. ND

Skim Coat and Plaster 6 Ref 1-5,7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar 18 Ref 16,17 No -- -- -- --

Firestop Caulk (Red) 30 Ref 29 No -- -- -- --

Tan Ceramic Wall Block and Grout Ref 53,54 No -- -- -- -- 9"x9" Vinyl Floor Tile (Tan) w/

Black Mastic 81,82 Ref 83 Yes Cat. I 80 Sq. Ft. ND

2'x2' Ceiling Tile (Smooth White) 47,48 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- -- 12"x12" Vinyl Floor Tile White w/ Tan Streaks and Black Mastic

77 Ref 75,76 Yes Cat. I 80 Sq. Ft. ND

Tan Ceramic Wall Block and Grout 53,54 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Room # B5114

Fourth Floor

Room # B4110A

Room # C4109 (adjoining wall to B4110A)

Fifth Floor

Room # B5110

1 Refer to Section 4.1 for regulatory classification

Facilities | Environmental | Geotechnical | Materials Page 4 of 8

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

12"x12" Vinyl Floor Tile White w/ Tan Streaks and Black

Mastic Ref 75,76,77 Yes Cat. I 55 Sq. Ft. ND

Tan Ceramic Wall Block and Grout Ref 53,54 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- -- Brown Sheet Flooring w/ Tan

Adhesive 69,70 No -- -- -- --

2'x2' Ceiling Tile (Smooth White) Ref 47,48 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Light Gray Sheet Flooring 71,72 No -- -- -- --

Carpet Mastic (Green/Yellow) Ref 73,74 No -- -- -- -- 2'x2' Ceiling Tile (Pin, Crevasse, Wavy) Ref 49,50 No -- -- -- --

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Carpet Mastic (Green/Yellow) 73,74 No -- -- -- -- 2'x2' Ceiling Tile (Pin, Crevasse, Wavy) Ref 49,50 No -- -- -- --

Room #B6113 Skim Coat and Plaster Ref 1-7 No -- -- -- --

Room # B6112B

Room # B5114

Sixth Floor

Room # B6110/B6108D

Room # B6112

1 Refer to Section 4.1 for regulatory classification

Facilities | Environmental | Geotechnical | Materials Page 5 of 8

01/04/2023 | Project No. MP227415

Location/Functional Space Suspect Material Description Sample Number Asbestos Content

RACM, Cat. I or Cat. II Non-

Friable1

Estimated Quantity Units Condition2

Sheetrock, Tape and Joint Compound Ref 8-12 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Covebase Adhesive (Light Brown) 37,38 No -- -- -- --

9"x9" Vinyl Floor Tile Gray w/ Black Streaks and Black Mastic 87,88,89 Yes Cat. I 75 Sq. Ft. ND

Sheetrock, Tape and Joint Compound Ref 8-12 No -- -- -- --

2'x2' Ceiling Tile (Pin, Crevasse, Wavy) 49,50 No -- -- -- --

9"x9" Vinyl Floor Tile White w/ Tan Streaks and Black Mastic 84,85,86 Yes Cat. I 120 Sq. Ft. ND

Skim Coat and Plaster Ref 1-7 No -- -- -- -- Sheetrock, Tape and Joint

Compound 12 Ref 8-11 No -- -- -- --

Clay Block and Mortar Ref 16,17,18 No -- -- -- --

Firestop Caulk (Red) Ref 29,30 No -- -- -- --

Duct Sealant Gray 26,27,28 No -- -- -- --

Tan Ceramic Wall Block and Grout 53,54 No -- -- -- -- 9"x9" Vinyl Floor Tile (Tan) w/

Black Mastic 83 Ref 81,82 Yes Cat. I 80 Sq. Ft. ND

Sheetrock, Tape and Joint Compound Ref 8-12 No -- -- -- --

Concrete Masonry Unit 19,20 No -- -- -- -- 2"x2" Brown Ceramic Floor Tile, Grout and Thinset 51,52 No -- -- -- --

Room # B8047

Room #B6113

Seventh Floor

Room # B7112A

Room # B7113

Eighth Floor

1 Refer to Section 4.1 for regulatory classification

Facilities | Environmental | Geotechnical | Materials Page 6 of 8

Table II: Lead Analysis Results

01/04/2023 | Project No. MP227415

Sample Number Location Building Component Substrate Color Condition1

Analysis2

Result (mg/cm2)(3)

LBP4

Yes/N o

Notes: Quantity, Occurrence by Component with LBP

1 -- PCS Calibration -- Red -- 1.0 -- Passed Calibration 2 Room # C129 Wall Plaster White Intact 0.0 No 3 Room # C129 Wall Plaster White Intact 0.0 No 4 Room # C129 Ceiling Plaster White Intact 0.1 No 5 Room # C129 Ceiling Plaster White Intact 0.3 No 6 Room # C129 Ceiling Plaster White Intact 0.0 No 7 Room # C129 Door Frame Metal White Intact 0.0 No 8 Room # C126 Door Frame Metal White Intact 0.0 No 9 Room # C126 Wall Plaster White Intact 0.0 No 10 Room # C126 Wall Plaster White Intact 0.0 No 11 Room # C126 Ceiling Plaster White Intact 0.0 No 12 Room # C126 Ceiling Plaster White Intact 0.0 No 13 Room # C121 Door Frame Metal White Intact 0.0 No 14 Room #C121 Wall Plaster White Intact 0.0 No 15 Room # CB1-025 Door Frame Metal White Intact 0.1 No 16 Room # CB1-025 Wall Plaster White Intact 0.0 No 17 Room # CB1-025 Wall Plaster White Intact 0.0 No 18 Room # CB1-025 Ceiling Plaster White Intact 0.0 No 19 Room # CB1-025 Ceiling Plaster White Intact 0.1 No 20 Room #CB1-024 Wall Plaster White Intact 0.0 No 21 Room #CB1-024 Wall Plaster Brown Intact 0.0 No

22 Room #CB1-024 Wall Ceramic Block Tan Intact 0.0 No

23 Room #CB1-024 Wall Ceramic Block Tan Intact 0.0 No

24 Room # B1121 Door Frame Metal White Intact 0.0 No 25 Room # B1121 Wall Plaster White Intact 0.0 No 26 Room # B1121 Wall Plaster White Intact 0.0 No 27 Room # B2053 Door Frame Metal White Intact 0.0 No 28 Room # B2053 Wall Plaster White Intact 0.0 No 29 Room # B2053 Wall Plaster White Intact 0.1 No 30 Room # B3110A Door Frame Metal White Intact 0.0 No 31 Room # B3110A Wall Plaster White Intact 0.0 No 32 Room # B3110A Wall Plaster White Intact 0.0 No 33 Room # B4110A Door Frame Metal White Intact 0.0 No 34 Room # B4110A Wall Plaster White Intact 0.1 No