Attachment 06 - EHRM Madison - Drawings - Building 01 - Part 5.pdf

PDF 16 MB Posted

Attached to
36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI Federal contract opportunity
Solicitation number
36C77623B0011
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is seeking bids for an EHRM infrastructure upgrades project at the Madison VA Medical Center in Madison, Wisconsin. The Department of Veterans Affairs, Veterans Health Administration, Program Contracting Activity Central is soliciting a single firm-fixed-price contract to furnish all labor, tools, materials, equipment, and supervision for general construction and replacement of all telecommunications cable, outlets, and associated equipment for multiple buildings on the Madison VA campus. The work will be performed according to provided drawings and specifications. The agency is the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77623B0011 - Solicitation - EHRM Infrastructure Upgrades - Madison, WI, newest first.
File Type Posted
36C77623B0011 0004_REVISED.pdf PDF
36C77623B0011 0004.pdf PDF
36C77623B0011 0003.pdf PDF
Attachment 27 - Technical Questions and Answers Volume 2.pdf PDF
Attachment 30 - Existing Column Load Summary.pdf PDF
Attachment 32 - CATV rack1btm.jpg JPG image
Attachment 33 - CATV rack2top.jpg JPG image
Attachment 34 - CATV rack2btm.jpg JPG image
Attachment 28 - Strengthening of Concrete with FRP.docx DOCX document
Attachment 29 - Sheet 1-S-15 from Ref_Existing - D - Wing_Addition.pdf PDF
Attachment 31 - CATV rack1top.jpg JPG image
Attachment 35 - CATV back of rack.jpg JPG image
Attachment 24 - EHRM Madison - Floor to Finish Heights.pdf PDF
36C77623B0011 0002.pdf PDF
Attachment 25 - EHRM Madison - Attendance Sheet.pdf PDF
Attachment 26 - Technical Questions and Answers.pdf PDF
Attachment 23 - Asbestos Survey and Lead Paint Report.pdf PDF
36C77623B0011 0001.pdf PDF
Attachment 03 - EHRM Madison - Drawings - Building 01 - Part 2.pdf PDF
Attachment 05 - EHRM Madison - Drawings - Building 01 - Part 4.pdf PDF
Attachment 15 - EHRM Madison - Drawings - Building 15.pdf PDF
Attachment 11 - EHRM Madison - Drawings - Building 05.pdf PDF
Attachment 12 - EHRM Madison - Drawings - Building 06.pdf PDF
S02 - Solicitation - 36C77623B0011 - EHRM Infrastructure Upgrades - Madison.pdf PDF
Attachment 01 - EHRM Madison - Specifications.pdf PDF
Attachment 13 - EHRM Madison - Drawings - Building 07.pdf PDF
Attachment 14 - EHRM Madison - Drawings - Building 12.pdf PDF
Attachment 17 - EHRM Madison - Drawings - IFC - SITE.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 22 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 02 - EHRM Madison - Drawings - Building 01 - Part 1.pdf PDF
Attachment 04 - EHRM Madison - Drawings - Building 01 - Part 3.pdf PDF
Attachment 08 - EHRM Madison - Drawings - Building 01 - Part 7.pdf PDF
Attachment 09 - EHRM Madison - Drawings - Building 02.pdf PDF
Attachment 10 - EHRM Madison - Drawings - Building 04.pdf PDF
Attachment 16 - EHRM Madison - Drawings - Building 22.pdf PDF
Attachment 19 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 20 - Dane County - Wage Rates.pdf PDF
Attachment 21 - SOW - EHRM Infrastructure Upgrades - Madison.pdf PDF
Attachment 07 - EHRM Madison - Drawings - Building 01 - Part 6.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01E-410

F7 01E-410

C7

TELECOM ROOM

D8000

TELECOM ROOM

B8047

TELECOM ROOM

B8000

191 SF

01E-410

F3

01E-410

C3

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

A-WING

D-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B-WING

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:4

P

M

01E-108

ELECTRICAL PLAN - EIGHTH LEVEL 607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

1" = 30'-0" F1

ELECTRICAL PLAN - EIGHTH LEVEL

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

Revisions: Date:

07/22/202207 /22

/20

C R

O S

R X

D C

ES

01E-109

C5

01E-109

C1

TELECOM ROOM

B9001A

MECHANICAL ROOM

A9012

DUMBWAITER ROOM

B9001A

MECHANICAL ROOM

B9001

MECHANICAL ROOM

D9201

Room

STAIR NO. 7

ENTRY

D9200

MECHANICAL ROOM

D9202

01E-411

C3

CU-01

01E-411

C6

CU-03

EMDP-TREQ-02

CU-B9-01

TELECOM ROOM

B9001A

150 SF

MECHANICAL ROOM

B9001

TRB9001AA

TRB9001AB

TRB9001AB- 3

TRB9001AA- 8

T R

B

1A

A

T R

B

1A

B

TRB9001AA- 8

TRB9001AB- 3

TRB9001AA- 8

TRB9001AB- 3

T R

B

1A

B

TYP.

TYP.

TRB9001AB- 8,10,12

TRB9001AA- 9,11,13

TYP.

TYP.

TRB9001AB- 2

L1

TRB9001AB- 2

L1

TRB9001AB- 2

L1

TRB9001AB- 2

L1

IU-B9000-01*

6 7

EMDP-TREQ-02

TRB9001AB- 5,7

TRB9001AA- 3,5

CU-B9-01

TRB9001AA- 7

TRB9001AB- 4,6

MECHANICAL ROOM

B9001

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

A-WING

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B-WING

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:4

P

M

01E-109

ELECTRICAL PLAN & ENLARGED PLAN -

PENTHOUSE & UPPER PENTHOUSE LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

SCALE: 1" = 30'-0"

F3

ELECTRICAL PLAN - PENTHOUSE

LEVEL

SCALE: 1/2" = 1'-0"

C5

ELECTRICAL ENLARGED PLAN -

PENTHOUSE LEVEL - ROOM B9001A -

NEW

SCALE: 1/2" = 1'-0"

C1

ELECTRICAL ENLARGED PLAN -

PENTHOUSE LEVEL - ROOM B9001A -

DEMO

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

Revisions: Date:

07/22/202207 /22

CR

E S

DC

RX

O S

TELECOM ROOM

DB2-202

99 SF

CORRIDOR

DB2-250

STAIR

TYP.

TRDB2-202B- 5

TRDB2-202A- 1

TRDB2-202A- 1

TRDB2-202B- 5

TRDB2-202B- 5

TRDB2-202B- 5

TRDB2-202A- 1

L1

L1

TRDB2-202B- 3

TRDB2-202B- 3

IU-DB2-016

TRDB2-202A- 1

TRDB2-202B- 3

L1

TYP.

TRDB2-202B- 3

TRDB2-202A- 7,9,11

TRDB2-202B- 6,8,10

L1

TYP.

TRDB2-202A

TRDB2-202B

IU-DB2-026 7

TRDB2-202B- 2,4

TRDB2-202A- 4,6

TRDB2-202B- 7,9

TRDB2-202A- 3,5

TRDB2-202B- 1

CORRIDOR

DB2-250

STAIR

TYP.

TYP.

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

EXISTING RESTROOM

DB2-202

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:5

P

M

01E-400

ELECTRICAL ENLARGED PLANS -

SUB-BASEMENT LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

SCALE: 1/2" = 1'-0"

C7

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM DB2-202 -

NEW

SCALE: 1/2" = 1'-0"

F7

ELECTRICAL ENLARGED PLAN -

SUBBASEMENT LEVEL - ROOM

DB2-202 - DEMO

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

Revisions: Date:

07/22/202207 /22

S

CR

E S

DCRX

OS

CR

O S

E S

RX

DC

OS

O S

C R

TELECOM ROOM

CB1-024

165 SF

TRCB1-024A

TRCB1-024B

TRCB1-024A- 4,6,8

TRCB1-024B- 8,10,12

T R

C B

1-

A

T R

C B

1-

B

TRCB1-024B- 3

TRCB1-024A- 2

TRCB1-024B- 3

TRCB1-024B- 3

TRCB1-024A- 2

TRCB1-024A- 2

TYP.

TYP.

TRCB1-024B- 116

3 8

IU-CB1-01*

6 7 6 7

TYP.

TYP.

L1 TRCB1-024B- 2 L1 TRCB1-024B- 2

TRCB1-024B- 2L1TRCB1-024B- 2L1

T R

C B

1-

4B

5, T R

C B

1-

4A

3, TYP.

TYP.

TYP.

TYP.

TYP.

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

TRDB1254A

TRDB1254B

TRDB1254B- 1

IU-DB1-01

L1

TRDB1254B- 3

TELECOM ROOM

DB1-254

168 SF

TRDB1254B- 11,13,15

TRDB1254A- 8,10,12

L1

TRDB1254B- 3

L1

TRDB1254B- 3

L1

TRDB1254B- 3

L1

TRDB1254B- 3

L1

TRDB1254B- 3

TYP.

TRDB1254B- 5

TRDB1254A- 1

TRDB1254B- 5

TRDB1254A- 1

TRDB1254B- 5

TRDB1254A- 1

TRDB1254B- 5

TRDB1254A- 1

TYP.

TYP.

10 8 19

TYP.

TRDB1254B- 2,4

TRDB1254A- 3,5

TRDB1254B- 7,9

TRDB1254A- 4,6

TRDB1254B- 8,10

TRDB1254A- 9,11

IU-DB1-02

6 7

6 7

IU-DB1-03

6 7

TOILET

DB1-201

TOILET

DB1-203

OFFICE

DB1-202A

90 SF

TYP.

OFFICE

DB1-202B

LPP6- 16

PPM- 59

LPP6- 16

P P

M

LP

P

6-

LPP6- 16

LP

P

6-

PPM- 59

PPM- 59

P P

M

PPM- 59

PPM- 59

TYP.

TYP.

OFFICE

DB1-254

86 SF

OFFICE

DB1-255

79 SF

EXISTING STORAGE

CB1-024

OFFICE

CB1-025

TOILET

DB1-201

TOILET

DB1-203

TR

DB1-202

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:0

P

M

01E-401A

ELECTRICAL ENLARGED PLANS - BASEMENT

LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

SCALE: 1/2" = 1'-0"

C7

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM CB1-024 -

NEW

SCALE: 1/2" = 1'-0"

C4

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM CB1-024 -

DEMO

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

SCALE: 1/2" = 1'-0"

C1

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM DB1-254 -

DEMO

SCALE: 1/2" = 1'-0"

F1

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM DB1-254 -

NEW

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

SCALE: 1/2" = 1'-0"

F7

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM DB1-202 -

NEW

SCALE: 1/2" = 1'-0"

F4

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ROOM DB1-202 -

DEMO

Revisions: Date:

07/22/202207 /22

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

ELECTRICAL

CB1-010

SWBD #9 (EP)

SWBD #5B (EP)15

CORRIDOR

BB1-02

STORAGE

CB1-039

SWBD #5A (EP)

SWBD #3 (NP)

SWBD #4 (NP)

SWBD #6 (NP)15

LS-CBL-1 NEQ-1

LS-1 NDP-N CR-1

EQ-CBL-1

SF-5A

SF-6A

SF-7A

GF-1

MTS-B108A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:0

P

M

01E-401B

ELECTRICAL ENLARGED PLANS - BASEMENT

LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

SCALE: 1/2" = 1'-0"

F6

ELECTRICAL ENLARGED PLAN -

BASEMENT LEVEL - ELECTRICAL

ROOM CB1-010

Revisions: Date:

07/22/202207 /22

CR

S

DC

RX

O S

CR

RX

O

SC

R

ES

R X

D C

C R

C R

R X

D C

ES

O S

C R

ES

R X

D C

TELECOM ROOM

DG223

179 SF

CORRIDOR

DG192

OFFICE

DG224

TRDG223A

TRDG223B

TRDG223A- 5

TRDG223B- 2

TRDG223A- 5

TRDG223B- 2

TRDG223A- 5

TRDG223B- 2

TRDG223A- 5

TRDG223B- 2

TRDG223A- 11,13,15

TRDG223B- 13,15,17

TRDG223A- 12,14,16

TRDG223B- 14,16,18

8 18

TYP.

8 19

IU-DG000-01

IU-DG000-02

6 7

6 7

TRDG223B- 1 16

TYP.

TYP.

9TYP.

L1

TRDG223B- 3

L1 TRDG223B- 3

L1TRDG223B- 3

L1TRDG223B- 3

L1

TRDG223B- 3

L1 TRDG223B- 3

L1

TRDG223B- 3

EP-TR-01D

NP-TR-01D

IU-DG000-03

6 7

TRDG223B- 4,6

TRDG223A- 2,4

TRDG223B- 9,11

TRDG223A- 7,9

TRDG223B- 5,7

TRDG223A- 8,10

BC-4 29

TRDG223B- 10,12 29

CORRIDOR

DG192

OFFICE

DG224

12 13 17

TYP.

TYP.

TYP.

TELECOM ROOM

G3

106 SF

T R

G

B

L1

T R

G 3B

T R

G 3B

TRG3A- 2

TRG3B- 3

T R

G 3A

TRG3A- 4,6,8

TRG3B- 8,10,12

T R

G 3A

TRG3B- 3

TRG3A- 2

T R

G 3B

T R

G

A

IU-G3-01*

TYP.

TYP.

T R

G 3B

TYP.

L1

T R

G 3B

L1

T R

G 3B

L1

T R

G 3B

TYP.

T R

G 3B

5, T R

G 3A

3, 26 25 30

11 12

TYP.

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

EXISTING OFFICE

DG223

EXISTING IT CLOSET

DG223A

EXISTING TELEPHONE CLOSET

G3

TYP.

TYP.

TYP.

PHONE DATA SERVER

FG645

139 SF

STORAGE

FG647

32 SF

PHONE DATA SERVER

FG645

139 SF

E P

-T R

-0 1A

N P

-T R

-0 1A

TRFG645BTRFG645A

TRFG645B- 1

TRFG645B- 3

TRFG645B- 8,10,12

TRFG645A- 4,6,8

T R

F G

5B

L1

T R

F G

5B

L1

T R

F G

5B

L1

T R

F G

5B

L1

T R

F G

5B

TRFG645B- 3

T R

F G

5B

TYP.

TRFG645A- 2

T R

F G

5A

T R

F G

5A

T R

F G

5A

TYP.

TYP.

TYP.

3 8

6 7

IU-FG-01*

T R

F G

5B

5, T R

F G

5A

3, 26 25

25 26

STORAGE

FG647

32 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:1

P

M

01E-402A

ELECTRICAL ENLARGED PLANS - GROUND

LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

SCALE: 1/2" = 1'-0"

F7

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM DG223 - NEW

SCALE: 1/2" = 1'-0"

C6

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM DG223 -

DEMO

SCALE: 1/2" = 1'-0"

F4

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM G3 - NEW

SCALE: 1/2" = 1'-0"

C4

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM G3 - DEMO

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED

SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL

DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN

SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING

SHALL BE COORDINATED WITH THE VA COR.

18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.

19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208

TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES.

20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.

21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH

EXISTING AND NEW CONDITIONS.

22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW

LOCATIONS WITH EXISTING AND NEW CONDITIONS.

23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.

24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW

LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL

EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND

EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD

COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.

29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL

SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.

30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR

ADDITIONAL INFORMATION.

31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.

32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT

AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.

CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS

AND SWITCHBOARDS.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET.

SCALE: 1/2" = 1'-0"

C1

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM FG645 -

DEMO

SCALE: 1/2" = 1'-0"

F1

ELECTRICAL ENLARGED PLAN -

GROUND LEVEL - ROOM FG645 - NEW

Revisions: Date:

07/22/202207 /22

RX DCE

SCR

OS

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

T R

B G

0A

T R

B G

0B

TRBG000B- 1

TYP.

TRBG000B- 12,14,16

TRBG000A- 7,9,11

TRBG000B- 11,13,15

TRBG000A- 4,6,8

8 19

8 18

IU-BG000-01

IU-BG000-02

IU-BG000-036 7

6 7

T R

B G

0B

T R

B G

0A

TRBG000B- 5

TRBG000A- 5

T R

B G

0B

T R

B G

0A

TRBG000B- 5

TRBG000A- 5

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TRBG000B- 3

L1

TYP.

TYP.

TYP.

TELECOM ROOM

BG000

191 SF

CONFERENCE ROOM

B93

T R

B G

0B

2, T R

B G

0A

1, T R

B G

0B

7, T R

B G

0A

0, TRBG000B- 8,10

TRBG000A- 13,15

E P

-T R

-0 1B

N P

-T R

-0 1B

CU-CB1-01 6

TRCB1-024B- 4,6

TRCB1-024A- 1 14

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M a d is o n

W I/

-2

-7

.M a d .E

H R

M .M

E P

.B

.r v t

/2

/2

:2

:1

P

M

01E-402B

ELECTRICAL ENLARGED PLANS - GROUND

LEVEL

607-21-700

07/22/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

2500 Overlook Terrace, Madison, WI 53705

1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND

CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.

2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

MORE DETAILS.

3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS

AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.

4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT

THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL

SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE

TRAY.

5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD

READER WITH PINPAD CARD, PIV READY.

6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.

PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.

BASIS OF DESIGN: E-MON D-MON.

8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL

BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-

MON.

9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL

INFORMATION.

11. REMOVE EXISTING ACCESS CONTROLS.

12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE

SPACE FOR RENOVATION.

13. REMOVE EXISTING LIGHT FIXTURES.

14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A

WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.

15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

17. UNLESS OTHERWISE…