This solicitation is seeking bids for an EHRM infrastructure upgrades project at the Madison VA Medical Center in Madison, Wisconsin. The Department of Veterans Affairs, Veterans Health Administration, Program Contracting Activity Central is soliciting a single firm-fixed-price contract to furnish all labor, tools, materials, equipment, and supervision for general construction and replacement of all telecommunications cable, outlets, and associated equipment for multiple buildings on the Madison VA campus. The work will be performed according to provided drawings and specifications. The agency is the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
01E-410
F7 01E-410
C7
TELECOM ROOM
D8000
TELECOM ROOM
B8047
TELECOM ROOM
B8000
191 SF
01E-410
F3
01E-410
C3
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
A-WING
D-WING
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B-WING
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:4
P
M
01E-108
ELECTRICAL PLAN - EIGHTH LEVEL 607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
1" = 30'-0" F1
ELECTRICAL PLAN - EIGHTH LEVEL
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
Revisions: Date:
07/22/202207 /22
/20
C R
O S
R X
D C
ES
01E-109
C5
01E-109
C1
TELECOM ROOM
B9001A
MECHANICAL ROOM
A9012
DUMBWAITER ROOM
B9001A
MECHANICAL ROOM
B9001
MECHANICAL ROOM
D9201
Room
STAIR NO. 7
ENTRY
D9200
MECHANICAL ROOM
D9202
01E-411
C3
CU-01
01E-411
C6
CU-03
EMDP-TREQ-02
CU-B9-01
TELECOM ROOM
B9001A
150 SF
MECHANICAL ROOM
B9001
TRB9001AA
TRB9001AB
TRB9001AB- 3
TRB9001AA- 8
T R
B
1A
A
T R
B
1A
B
TRB9001AA- 8
TRB9001AB- 3
TRB9001AA- 8
TRB9001AB- 3
T R
B
1A
B
TYP.
TYP.
TRB9001AB- 8,10,12
TRB9001AA- 9,11,13
TYP.
TYP.
TRB9001AB- 2
L1
TRB9001AB- 2
L1
TRB9001AB- 2
L1
TRB9001AB- 2
L1
IU-B9000-01*
6 7
EMDP-TREQ-02
TRB9001AB- 5,7
TRB9001AA- 3,5
CU-B9-01
TRB9001AA- 7
TRB9001AB- 4,6
MECHANICAL ROOM
B9001
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
A-WING
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B-WING
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:4
P
M
01E-109
ELECTRICAL PLAN & ENLARGED PLAN -
PENTHOUSE & UPPER PENTHOUSE LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
SCALE: 1" = 30'-0"
F3
ELECTRICAL PLAN - PENTHOUSE
LEVEL
SCALE: 1/2" = 1'-0"
C5
ELECTRICAL ENLARGED PLAN -
PENTHOUSE LEVEL - ROOM B9001A -
NEW
SCALE: 1/2" = 1'-0"
C1
ELECTRICAL ENLARGED PLAN -
PENTHOUSE LEVEL - ROOM B9001A -
DEMO
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
Revisions: Date:
07/22/202207 /22
CR
E S
DC
RX
O S
TELECOM ROOM
DB2-202
99 SF
CORRIDOR
DB2-250
STAIR
TYP.
TRDB2-202B- 5
TRDB2-202A- 1
TRDB2-202A- 1
TRDB2-202B- 5
TRDB2-202B- 5
TRDB2-202B- 5
TRDB2-202A- 1
L1
L1
TRDB2-202B- 3
TRDB2-202B- 3
IU-DB2-016
TRDB2-202A- 1
TRDB2-202B- 3
L1
TYP.
TRDB2-202B- 3
TRDB2-202A- 7,9,11
TRDB2-202B- 6,8,10
L1
TYP.
TRDB2-202A
TRDB2-202B
IU-DB2-026 7
TRDB2-202B- 2,4
TRDB2-202A- 4,6
TRDB2-202B- 7,9
TRDB2-202A- 3,5
TRDB2-202B- 1
CORRIDOR
DB2-250
STAIR
TYP.
TYP.
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
EXISTING RESTROOM
DB2-202
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:5
P
M
01E-400
ELECTRICAL ENLARGED PLANS -
SUB-BASEMENT LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
SCALE: 1/2" = 1'-0"
C7
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM DB2-202 -
NEW
SCALE: 1/2" = 1'-0"
F7
ELECTRICAL ENLARGED PLAN -
SUBBASEMENT LEVEL - ROOM
DB2-202 - DEMO
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
Revisions: Date:
07/22/202207 /22
S
CR
E S
DCRX
OS
CR
O S
E S
RX
DC
OS
O S
C R
TELECOM ROOM
CB1-024
165 SF
TRCB1-024A
TRCB1-024B
TRCB1-024A- 4,6,8
TRCB1-024B- 8,10,12
T R
C B
1-
A
T R
C B
1-
B
TRCB1-024B- 3
TRCB1-024A- 2
TRCB1-024B- 3
TRCB1-024B- 3
TRCB1-024A- 2
TRCB1-024A- 2
TYP.
TYP.
TRCB1-024B- 116
3 8
IU-CB1-01*
6 7 6 7
TYP.
TYP.
L1 TRCB1-024B- 2 L1 TRCB1-024B- 2
TRCB1-024B- 2L1TRCB1-024B- 2L1
T R
C B
1-
4B
5, T R
C B
1-
4A
3, TYP.
TYP.
TYP.
TYP.
TYP.
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
TRDB1254A
TRDB1254B
TRDB1254B- 1
IU-DB1-01
L1
TRDB1254B- 3
TELECOM ROOM
DB1-254
168 SF
TRDB1254B- 11,13,15
TRDB1254A- 8,10,12
L1
TRDB1254B- 3
L1
TRDB1254B- 3
L1
TRDB1254B- 3
L1
TRDB1254B- 3
L1
TRDB1254B- 3
TYP.
TRDB1254B- 5
TRDB1254A- 1
TRDB1254B- 5
TRDB1254A- 1
TRDB1254B- 5
TRDB1254A- 1
TRDB1254B- 5
TRDB1254A- 1
TYP.
TYP.
10 8 19
TYP.
TRDB1254B- 2,4
TRDB1254A- 3,5
TRDB1254B- 7,9
TRDB1254A- 4,6
TRDB1254B- 8,10
TRDB1254A- 9,11
IU-DB1-02
6 7
6 7
IU-DB1-03
6 7
TOILET
DB1-201
TOILET
DB1-203
OFFICE
DB1-202A
90 SF
TYP.
OFFICE
DB1-202B
LPP6- 16
PPM- 59
LPP6- 16
P P
M
LP
P
6-
LPP6- 16
LP
P
6-
PPM- 59
PPM- 59
P P
M
PPM- 59
PPM- 59
TYP.
TYP.
OFFICE
DB1-254
86 SF
OFFICE
DB1-255
79 SF
EXISTING STORAGE
CB1-024
OFFICE
CB1-025
TOILET
DB1-201
TOILET
DB1-203
TR
DB1-202
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:0
P
M
01E-401A
ELECTRICAL ENLARGED PLANS - BASEMENT
LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
SCALE: 1/2" = 1'-0"
C7
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM CB1-024 -
NEW
SCALE: 1/2" = 1'-0"
C4
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM CB1-024 -
DEMO
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
SCALE: 1/2" = 1'-0"
C1
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM DB1-254 -
DEMO
SCALE: 1/2" = 1'-0"
F1
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM DB1-254 -
NEW
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
SCALE: 1/2" = 1'-0"
F7
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM DB1-202 -
NEW
SCALE: 1/2" = 1'-0"
F4
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ROOM DB1-202 -
DEMO
Revisions: Date:
07/22/202207 /22
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
ELECTRICAL
CB1-010
SWBD #9 (EP)
SWBD #5B (EP)15
CORRIDOR
BB1-02
STORAGE
CB1-039
SWBD #5A (EP)
SWBD #3 (NP)
SWBD #4 (NP)
SWBD #6 (NP)15
LS-CBL-1 NEQ-1
LS-1 NDP-N CR-1
EQ-CBL-1
SF-5A
SF-6A
SF-7A
GF-1
MTS-B108A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:0
P
M
01E-401B
ELECTRICAL ENLARGED PLANS - BASEMENT
LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
SCALE: 1/2" = 1'-0"
F6
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - ELECTRICAL
ROOM CB1-010
Revisions: Date:
07/22/202207 /22
CR
S
DC
RX
O S
CR
RX
O
SC
R
ES
R X
D C
C R
C R
R X
D C
ES
O S
C R
ES
R X
D C
TELECOM ROOM
DG223
179 SF
CORRIDOR
DG192
OFFICE
DG224
TRDG223A
TRDG223B
TRDG223A- 5
TRDG223B- 2
TRDG223A- 5
TRDG223B- 2
TRDG223A- 5
TRDG223B- 2
TRDG223A- 5
TRDG223B- 2
TRDG223A- 11,13,15
TRDG223B- 13,15,17
TRDG223A- 12,14,16
TRDG223B- 14,16,18
8 18
TYP.
8 19
IU-DG000-01
IU-DG000-02
6 7
6 7
TRDG223B- 1 16
TYP.
TYP.
9TYP.
L1
TRDG223B- 3
L1 TRDG223B- 3
L1TRDG223B- 3
L1TRDG223B- 3
L1
TRDG223B- 3
L1 TRDG223B- 3
L1
TRDG223B- 3
EP-TR-01D
NP-TR-01D
IU-DG000-03
6 7
TRDG223B- 4,6
TRDG223A- 2,4
TRDG223B- 9,11
TRDG223A- 7,9
TRDG223B- 5,7
TRDG223A- 8,10
BC-4 29
TRDG223B- 10,12 29
CORRIDOR
DG192
OFFICE
DG224
12 13 17
TYP.
TYP.
TYP.
TELECOM ROOM
G3
106 SF
T R
G
B
L1
T R
G 3B
T R
G 3B
TRG3A- 2
TRG3B- 3
T R
G 3A
TRG3A- 4,6,8
TRG3B- 8,10,12
T R
G 3A
TRG3B- 3
TRG3A- 2
T R
G 3B
T R
G
A
IU-G3-01*
TYP.
TYP.
T R
G 3B
TYP.
L1
T R
G 3B
L1
T R
G 3B
L1
T R
G 3B
TYP.
T R
G 3B
5, T R
G 3A
3, 26 25 30
11 12
TYP.
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
EXISTING OFFICE
DG223
EXISTING IT CLOSET
DG223A
EXISTING TELEPHONE CLOSET
G3
TYP.
TYP.
TYP.
PHONE DATA SERVER
FG645
139 SF
STORAGE
FG647
32 SF
PHONE DATA SERVER
FG645
139 SF
E P
-T R
-0 1A
N P
-T R
-0 1A
TRFG645BTRFG645A
TRFG645B- 1
TRFG645B- 3
TRFG645B- 8,10,12
TRFG645A- 4,6,8
T R
F G
5B
L1
T R
F G
5B
L1
T R
F G
5B
L1
T R
F G
5B
L1
T R
F G
5B
TRFG645B- 3
T R
F G
5B
TYP.
TRFG645A- 2
T R
F G
5A
T R
F G
5A
T R
F G
5A
TYP.
TYP.
TYP.
3 8
6 7
IU-FG-01*
T R
F G
5B
5, T R
F G
5A
3, 26 25
25 26
STORAGE
FG647
32 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:1
P
M
01E-402A
ELECTRICAL ENLARGED PLANS - GROUND
LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
SCALE: 1/2" = 1'-0"
F7
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM DG223 - NEW
SCALE: 1/2" = 1'-0"
C6
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM DG223 -
DEMO
SCALE: 1/2" = 1'-0"
F4
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM G3 - NEW
SCALE: 1/2" = 1'-0"
C4
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM G3 - DEMO
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE NOTED. REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO ASSOCIATED
SOURCE PANEL. ALL DEVICES/CIRCUITS NOT ASSOCIATED WITH THE LOCAL
DEMOLITION SHALL BE PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN
SERVICE AS PER CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION/PHASING
SHALL BE COORDINATED WITH THE VA COR.
18. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKERS FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-20P RECEPTACLE.
19. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A 120/208
TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES.
20. EXISTING RECEPTACLE TO REMAIN, PROTECT IN PLACE.
21. EXISTING EQUIPMENT TO BE RELOCATED TO NEW LOCATION, COORDINATE WITH
EXISTING AND NEW CONDITIONS.
22. EXISTING LIGHT SWITCH TO BE RELOCATED TO NEW LOCATION, COORDINATE NEW
LOCATIONS WITH EXISTING AND NEW CONDITIONS.
23. EXISTING FIXTURE/EQUIPMENT TO REMAIN, PROTECT IN PLACE.
24. EXISTING ADA WALL MOUNTED DOOR CONTROL TO BE RELOCATED TO NEW
LOCATION, COORDINATE WITH EXISTING AND NEW CONDITIONS.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
26. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
27. CONTRACTOR TO CONSTRUCT NEW UNISTRUT RACK, MOUNT NEW ELECTRICAL
EQUIPMENT TO UNISTRUT RACK, COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
28. PROVIDE NEW 2X2 LIGHT FIXTURES, WIRE TO EXISTING LIGHTING CIRCUIT. FIELD
COORDINATE LOCATION WITH EXISTING AND NEW CONDITIONS.
29. BRANCH CONTROLLER TO RECIEVE ELECTRICAL DISCONNECT, SEE MECHANICAL
SCHEDULE SHEET, 01M-701, FOR ADDITIONAL INFORMATION.
30. WALL MOUNTED 12RU FOR CATV SERVICE ONLY. SEE T-700 SERIES FOR
ADDITIONAL INFORMATION.
31. WALL MOUNTED EQUIPMENT TO BE RELOCATED TO NEW TR LOCATION.
32. NEW EMERGENCY OR NORMAL POWER RECEPTACLE, WIRE TO EXISTING CIRCUIT
AS INDICIATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS.
CONTRACTOR TO VERIFY IN FIELD CIRCUIT NUMBERS AND PANEL LOCATIONS.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
P. PROVIDE 30 DAY LOAD MONITORING FOR ALL EXISTING SOURCE PANELBOARDS
AND SWITCHBOARDS.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET.
SCALE: 1/2" = 1'-0"
C1
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM FG645 -
DEMO
SCALE: 1/2" = 1'-0"
F1
ELECTRICAL ENLARGED PLAN -
GROUND LEVEL - ROOM FG645 - NEW
Revisions: Date:
07/22/202207 /22
RX DCE
SCR
OS
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
T R
B G
0A
T R
B G
0B
TRBG000B- 1
TYP.
TRBG000B- 12,14,16
TRBG000A- 7,9,11
TRBG000B- 11,13,15
TRBG000A- 4,6,8
8 19
8 18
IU-BG000-01
IU-BG000-02
IU-BG000-036 7
6 7
T R
B G
0B
T R
B G
0A
TRBG000B- 5
TRBG000A- 5
T R
B G
0B
T R
B G
0A
TRBG000B- 5
TRBG000A- 5
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TRBG000B- 3
L1
TYP.
TYP.
TYP.
TELECOM ROOM
BG000
191 SF
CONFERENCE ROOM
B93
T R
B G
0B
2, T R
B G
0A
1, T R
B G
0B
7, T R
B G
0A
0, TRBG000B- 8,10
TRBG000A- 13,15
E P
-T R
-0 1B
N P
-T R
-0 1B
CU-CB1-01 6
TRCB1-024B- 4,6
TRCB1-024A- 1 14
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M a d is o n
W I/
-2
-7
.M a d .E
H R
M .M
E P
.B
.r v t
/2
/2
:2
:1
P
M
01E-402B
ELECTRICAL ENLARGED PLANS - GROUND
LEVEL
607-21-700
07/22/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
2500 Overlook Terrace, Madison, WI 53705
1. PROVIDE NEW 12" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE AND
CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
MORE DETAILS.
3. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS
AND DEVICES TO SUPPLY EACH NEW OVERHEAD L21-30P RECEPTACLE.
4. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE AUTO ON/ AUTO OFF. COORDINATE FIXTURES WITH OVERHEAD CABLE
TRAY.
5. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT, CARD
READER WITH PINPAD CARD, PIV READY.
6. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
7. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD ONLY.
PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED POWER METER.
BASIS OF DESIGN: E-MON D-MON.
8. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR SHALL
BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN: E-MON D-
MON.
9. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
10. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
11. REMOVE EXISTING ACCESS CONTROLS.
12. REMOVE EXISTING RECEPTACLES, SWITCHES AND OTHER DEVICES PREPARE
SPACE FOR RENOVATION.
13. REMOVE EXISTING LIGHT FIXTURES.
14. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
15. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
16. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
17. UNLESS OTHERWISE…