Attach 10 - Tower 5 Inspection Report (90354).pdf

PDF 2 MB Posted

Attached to
Water Tower Maintenance IDIQ Federal contract opportunity
Solicitation number
FA441720R0009
Issued by
Department of the Air Force Special Operations Command

View the file

Other files for this federal contract opportunity

Other files attached to Water Tower Maintenance IDIQ, newest first.
File Type Posted
Solicitation Amendment FA441720R00090004 SF 30.pdf PDF
Attach 01 - REVISED Bid Schedule 3 AUG 2020.pdf PDF
Solicitation Amendment - FA441720R00090004.pdf PDF
Solicitation Amendment - FA441720R00090003.pdf PDF
Solicitation Amendment FA441720R00090003 SF 30.pdf PDF
Questions and Answers FA441720R0009.docx DOCX document
Attach 22 - Lead Based Paint Survey.pdf PDF
Solicitation Amendment - FA441720R00090002.pdf PDF
Solicitation Amendment FA441720R00090002 SF 30.pdf PDF
Site Visit SIGN-IN ROSTER 9 July 2020.pdf PDF
Pre-Proposal Site Visit Water Tower Mx IDIQ.pdf PDF
Solicitation Amendment FA441720R00090001 SF 30.pdf PDF
Solicitation Amendment - FA441720R00090001.pdf PDF
Attach 02 - Master Specifications 01 June 20.pdf PDF
Attach 18 - SEED Project OP1020558 - WTA.pdf PDF
Attach 08 - Tower 2 (90335) Graphics.pdf PDF
Attach 05 - Specs - Tower 5 (90354).pdf PDF
Attach 11 - Tower 7 Inspection Report (91134).pdf PDF
Attach 15 - Tower 7 (91134) Location.pdf PDF
Attach 09 - Tower 2 Inspection Report (90335).pdf PDF
Attach 13 - Tower 2 (90335) Location.pdf PDF
Attach 16 - Tower 808 (90808) Location.pdf PDF
Attach 21 - Financial Reference Sheet.pdf PDF
Attach 04 - Specs - Tower 2 (90335).pdf PDF
Attach 01 - Bid Schedule.pdf PDF
Attach 03 - Master SOW 04 June 20.pdf PDF
Attach 19 - WD FL20190217 - 21 Feb 20.pdf PDF
Attach 20 - Past Present Performance Questionnaire.pdf PDF
Solicitation - FA441720R0009.pdf PDF
Attach 06 - Specs - Tower 7 (91134).pdf PDF
Attach 17 - SEED Project OP1020558 - SOW 18 Jun 20.pdf PDF
Attach 07 - Specs - Tower 808 (90808).pdf PDF
Attach 12 - Tower 808 Inspection Report (90808).pdf PDF
Attach 14 - Tower 5 (90354) Location.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8/29/19 10:30 AMInspection Date:

Inspector:

Tank Foundation:

The foundation in in good condition.

*The upper wind rods ans riser rods are rusting badly.

*The catwalk has rust occurring in multiple locations.

*The exterior coatings are failing.

Inspection of accessories:

*Vent is in good condition *The exterior ladder is in good condition. Interior ladder is in good condition.

*The top hatch is in good condition.

inspection of sanitary conditions:

*The tank interior floor had a minimal amount of silt

Inspection of OSHA-related accessories:

*Cable safety climb in place on leg ladder. Top portion of leg ladder is in poor condition.

Inspection of cathodic protection:

*Cathodic protection system should be removed and holes should have plates welded to seal tank.

Interior inspection:

* Interior coatings are in good condition Overflow Protection:

Overflow flap is working properly.

Vent screen:

Screen is in good condition.

Average Exterior DFT

Tank legs: 12 mils, Tank Side Shell: 14 mils, Tank Top: 30 mils, Tank Interior: 16 mils

On July 29th 2019 a visual inspection of the above referenced water storage tank was done. This is a annual inspection to check the integrity of the coating system and components.

The tank was full during this inspection. Only the interior ceiling could be seen. The interior coatings are in good condition.

The exterior coatings are failing. The upper riser rods and wind rods are rusting badly with significant sectional loss occurring. When the tank is rehabilitated some of these rods will need to be replaced. A detailed inspection could be done with ropes to determine what rods need to be replaced for the bids documents if requested. There are also spots of rust occurring on the tank catwalk.

Inspection of the tank support tower:

Inspect the tank's balconies and handrails:

Inspection of the exterior tank:

Exterior Coatings Adhesion:

Fair

Tower Security Fence: Tank has external fence that was locked.

Ladder Gate: Ladder gate in place with lock.

Top Hatch: Top hatch had non utility owned lock, lock was cut off and replaced with utility owned lock.

See pictures below for more information

Tower # 5

Tank leg DFT reading

Overflow Protection:

Screen on overflow

Exterior coatings adhesion test

Rust on anchor bolt

Support tower

Riser manhole

Safety cable on ladder leg

2nd riser manhole

Rusty conduit missing caps

Rust on leg

Strut

Rust on top of strut

Top portion of leg ladder is in poor condition

Upper rods in poor condition

Under catwalk

Upper riser rods in poor condition

Rust under catwalk

Rust on catwalk handrail

DFT reading tank side shell

Rust on catwalk

DFT reading tank side shell

Safety cable on knuckle ladder

Rust on tank side shell

Knuckle

Top of tank

Vent

Vent screen

Rust around vent attachment point

Holes in top of tank not covered

Obstruction light not mounted properly

Top of tank

DFT reading top of tank

Non utility owned hatch lock

Top hatch

Interior DFT reading

Interior ceiling

Minimal sediment on tank floor

Interior floor

Interior walls

Hatch locked with utility owner lock

Tower #2- - 8-29-19