Attach 09 - Tower 2 Inspection Report (90335).pdf

PDF 4 MB Posted

Attached to
Water Tower Maintenance IDIQ Federal contract opportunity
Solicitation number
FA441720R0009
Issued by
Department of the Air Force Special Operations Command

View the file

Other files for this federal contract opportunity

Other files attached to Water Tower Maintenance IDIQ, newest first.
File Type Posted
Solicitation Amendment - FA441720R00090004.pdf PDF
Solicitation Amendment FA441720R00090004 SF 30.pdf PDF
Attach 01 - REVISED Bid Schedule 3 AUG 2020.pdf PDF
Attach 22 - Lead Based Paint Survey.pdf PDF
Questions and Answers FA441720R0009.docx DOCX document
Solicitation Amendment - FA441720R00090003.pdf PDF
Solicitation Amendment FA441720R00090003 SF 30.pdf PDF
Solicitation Amendment FA441720R00090002 SF 30.pdf PDF
Solicitation Amendment - FA441720R00090002.pdf PDF
Pre-Proposal Site Visit Water Tower Mx IDIQ.pdf PDF
Site Visit SIGN-IN ROSTER 9 July 2020.pdf PDF
Solicitation Amendment - FA441720R00090001.pdf PDF
Solicitation Amendment FA441720R00090001 SF 30.pdf PDF
Attach 06 - Specs - Tower 7 (91134).pdf PDF
Attach 17 - SEED Project OP1020558 - SOW 18 Jun 20.pdf PDF
Attach 07 - Specs - Tower 808 (90808).pdf PDF
Attach 12 - Tower 808 Inspection Report (90808).pdf PDF
Attach 14 - Tower 5 (90354) Location.pdf PDF
Attach 11 - Tower 7 Inspection Report (91134).pdf PDF
Attach 15 - Tower 7 (91134) Location.pdf PDF
Attach 13 - Tower 2 (90335) Location.pdf PDF
Attach 16 - Tower 808 (90808) Location.pdf PDF
Attach 21 - Financial Reference Sheet.pdf PDF
Attach 10 - Tower 5 Inspection Report (90354).pdf PDF
Attach 04 - Specs - Tower 2 (90335).pdf PDF
Attach 01 - Bid Schedule.pdf PDF
Attach 03 - Master SOW 04 June 20.pdf PDF
Attach 19 - WD FL20190217 - 21 Feb 20.pdf PDF
Attach 20 - Past Present Performance Questionnaire.pdf PDF
Solicitation - FA441720R0009.pdf PDF
Attach 02 - Master Specifications 01 June 20.pdf PDF
Attach 18 - SEED Project OP1020558 - WTA.pdf PDF
Attach 08 - Tower 2 (90335) Graphics.pdf PDF
Attach 05 - Specs - Tower 5 (90354).pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8/29/19 08:30 AMInspection Date:

Inspector:

Tank Foundation:

The foundation in in good condition.

*The upper wind rods ans riser rods are rusting badly.

* the catwalk has delaminating rust occurring in multiple locations.

*The exterior coatings are failing.

Inspection of accessories:

*Vent is in good condition *The exterior ladder is in good condition. The top rungs on the interior ladder are in poor condition.

*The top hatch is in good condition.

inspection of sanitary conditions:

*The tank interior floor could not be seen.

Inspection of OSHA-related accessories:

*Cable safety climb in place on leg ladder.

Inspection of cathodic protection:

*Cathodic protection caps not covering holes and rain water can get into tank.

Interior inspection:

*The interior has some rust around the weld seams.

Overflow Protection:

The overflow screen is filled with sediment. Overflow flap is working properly.

Vent screen:

Screen is in good condition.

Average Exterior DFT

Tank legs: 20 mils, Tank Side Shell: 20 mils, Tank Top: 30 mils, Tank Interior: 7 mils

On July 29th 2019 a visual inspection of the above referenced water storage tank was done. This is a annual inspection to check the integrity of the coating system and components.

The tank was full during this inspection. Only the interior ceiling could be seen. The interior coatings are in good condition with some rust around the ceiling beams occurring.

The exterior coatings are failing. The upper riser rods and wind rods are rusting badly with significant sectional loss occurring. When the tank is rehabilitated some of these rods will need to be replaced. A detailed inspection could be done with ropes to determine what rods need to be replaced for the bids documents if requested. There are also spots of delamination occurring on the tank catwalk.

The mounts for the spot light on top of the tank are rusted through and high winds could cause catastrophic failure.

Inspection of the tank support tower:

Inspect the tank's balconies and handrails:

Inspection of the exterior tank:

Exterior Coatings Adhesion:

Fair

Tower Security Fence: Tank has external fence that was locked.

Ladder Gate: Ladder gate in place with lock.

Top Hatch: No lock on top hatch, Lock ears on hatch need to be reworked

See pictures below for more information

Tower # 2

Tank leg DFT reading

Overflow Protection:

Screen on overflow filled with sediment

Exterior coatings adhesion test

Rust on anchor bolt

Support tower

Riser manhole

Safety cable on ladder leg

Grout failing around riser

Rust on turn buckle

Riser

Rust on ladder

Strut

Conduit rusted through on ladder

Rust spot on upper leg

Upper riser rods in poor condition

Upper wind rods in poor condition

Upper wind rods in poor condition

Under catwalk

Rust under catwalk

Rust on side of catwalk

DFT reading tank side shell

Rust on catwalk

Rust on catwalk

Safety cable on knuckle ladder loose

Spotlight platform has rust spots underneath

Spotlight supports rusted through

Top hatch, Ears for locking top hatch need to be re-worked

Vent

Vent screen

Rust around vent attachment point

Top of tank

Cathodic protection cover not covering tank from rain water or insects

Top of tank

Spotlights

Obstruction lights

Obstruction lights

Top hatch

DFT reading top of tank

Rust on top ladder

Interior DFT reading

Top interior ladder rungs in poor condition

Interior ceiling

Interior ceiling

Interior side walls

Interior ceiling & side walls

Tower #2- - 8-29-19