8/29/19 08:30 AMInspection Date:
Inspector:
Tank Foundation:
The foundation in in good condition.
*The upper wind rods ans riser rods are rusting badly.
* the catwalk has delaminating rust occurring in multiple locations.
*The exterior coatings are failing.
Inspection of accessories:
*Vent is in good condition *The exterior ladder is in good condition. The top rungs on the interior ladder are in poor condition.
*The top hatch is in good condition.
inspection of sanitary conditions:
*The tank interior floor could not be seen.
Inspection of OSHA-related accessories:
*Cable safety climb in place on leg ladder.
Inspection of cathodic protection:
*Cathodic protection caps not covering holes and rain water can get into tank.
Interior inspection:
*The interior has some rust around the weld seams.
Overflow Protection:
The overflow screen is filled with sediment. Overflow flap is working properly.
Vent screen:
Screen is in good condition.
Average Exterior DFT
Tank legs: 20 mils, Tank Side Shell: 20 mils, Tank Top: 30 mils, Tank Interior: 7 mils
On July 29th 2019 a visual inspection of the above referenced water storage tank was done. This is a annual inspection to check the integrity of the coating system and components.
The tank was full during this inspection. Only the interior ceiling could be seen. The interior coatings are in good condition with some rust around the ceiling beams occurring.
The exterior coatings are failing. The upper riser rods and wind rods are rusting badly with significant sectional loss occurring. When the tank is rehabilitated some of these rods will need to be replaced. A detailed inspection could be done with ropes to determine what rods need to be replaced for the bids documents if requested. There are also spots of delamination occurring on the tank catwalk.
The mounts for the spot light on top of the tank are rusted through and high winds could cause catastrophic failure.
Inspection of the tank support tower:
Inspect the tank's balconies and handrails:
Inspection of the exterior tank:
Exterior Coatings Adhesion:
Fair
Tower Security Fence: Tank has external fence that was locked.
Ladder Gate: Ladder gate in place with lock.
Top Hatch: No lock on top hatch, Lock ears on hatch need to be reworked
See pictures below for more information
Tower # 2
Tank leg DFT reading
Overflow Protection:
Screen on overflow filled with sediment
Exterior coatings adhesion test
Rust on anchor bolt
Support tower
Riser manhole
Safety cable on ladder leg
Grout failing around riser
Rust on turn buckle
Riser
Rust on ladder
Strut
Conduit rusted through on ladder
Rust spot on upper leg
Upper riser rods in poor condition
Upper wind rods in poor condition
Upper wind rods in poor condition
Under catwalk
Rust under catwalk
Rust on side of catwalk
DFT reading tank side shell
Rust on catwalk
Rust on catwalk
Safety cable on knuckle ladder loose
Spotlight platform has rust spots underneath
Spotlight supports rusted through
Top hatch, Ears for locking top hatch need to be re-worked
Vent
Vent screen
Rust around vent attachment point
Top of tank
Cathodic protection cover not covering tank from rain water or insects
Top of tank
Spotlights
Obstruction lights
Obstruction lights
Top hatch
DFT reading top of tank
Rust on top ladder
Interior DFT reading
Top interior ladder rungs in poor condition
Interior ceiling
Interior ceiling
Interior side walls
Interior ceiling & side walls
Tower #2- - 8-29-19