This document contains drawings and schedules for the mechanical systems in a computer server room as part of a federal contract opportunity. The drawings show the layout of new and existing HVAC equipment, including computer room air conditioning (CRAC) units, condensing units, ductwork, and controls. The equipment schedules provide technical details on the HVAC units such as capacity, airflow, electrical data, and refrigerant information. The control diagram outlines the sequence of operations for the CRAC units, including teamwork mode, safety interlocks, and integration with the building automation system. The related federal contract opportunity is Solicitation Number 36C77624B0004_1 for the EHRM Infrastructure Upgrades - Main Building Construction project in Big Spring, TX, issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1" CD
/8
R
L
/8
R G
SERVER ROOM
105A
/4
N
P W
FOR CONTINUATION REFER TO 3/M-103
11 11
OFF
S
/8
R
L
/8
R G
CRAC-4-1 CRAC-4-2
3/4" CD
3/4" CD1/2" NPW
1/2" DCW
CU-4-1 CRAC-4-2
30 / 30 SA
2' - 10" 2' - 10"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
TYP.9
T
T
T
H
H
H
MECH RM
4' - 0"
PROVIDE NEW 2" DOWN SPOUT NOZZLE
WITH RODENT MESH AT NEW 2" DRAIN
LINE PENETRATION OF FOUNDATION WALL
CORE DRILL EXISTING EXPOSED FOUNDATION
WALL UNDER FLOOR LEVEL AND INSTALL NEW
2" DRAIN LINE TO NEW FLOOR DRAIN.
CORE DRILL EXISTING SLAB AND INSTALL
NEW 2" FLOOR DRAIN WITH TRAP GUARD.
/8
R
L
/8
R G
/8
R
L
/8
R G
CRAC (E)CRAC (E)
CU (E)
CU (E)
1 1
7 7
TYP.9
TYP.9
SERVER RM
105A
MECH RM
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ENGINEER:
HUITT-ZOLLARS
500 W. 7th St., Ste. 300 Fort Worth, TX 76102 817-335-3000
ARCHITECT:
CB DESIGN GROUP
421 King St., Ste. 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
West Texas VA Health Care System Big Spring, TX 79720
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CIVIL/STRUCTURAL:
H2B 1225 N Loop W, Suite 800
HOUSTON, TX 77008
713-864-2900
12/23/2022
519-21-900
EALJW
VA BSP EHRM INFRASTRUCTURE
UPGRADES
CONSTRUCTION DOCUMENTS
HVAC ENLARGED PLAN
M-404
-2
-9
M -4
/2
/2
.p d f
1/4" = 1'-0"
BUILDING 4 - ROOM 105A NEW WORK
1/4" = 1'-0"
BUILDING 4 - ROOM 105A DEMO
2' 4' 8'0'
1/4" =1'-0"SCALE
NOTES BY SYMBOL
APPLIES TO SHEET M-404
NOTE DESCRIPTION
DETAIL
SHEET
SCHEDULE
SHEET
CONTROLS
SHEET
COORDINATE WITH ARCHITECT TO PATCH HOLES IN EXTERIOR WALLS.
FINISH TO MATCH EXISTING
COORDINATE WITH ARCHITECT TO PATCH EXISTING INTERIOR PARTITION
PENETRATION. FINISH TO MATCH EXISTING.
DEMOLISH EXISTING CRAC UNITS IN ROOM 106. DISCONNECT EXISTING
ELECTRICAL CONNECTIONS. EXISTING DISCONNECT SWITCH AND
CIRCUITS SHALL REMAIN FOR CONNECTION TO NEW UNIT.
DEMOLISH ALL PIPING INCLUDING EXISTING REFRIGERANT AND
CONDENSATE DRAIN PIPING FROM CONDENSING UNITS TO CRAC UNITS.
DEMOLISH ALL EXISTING DUCTWORK IN MECHANICAL ROOM FROM CRAC
UNIT TO DEMISING WALL.
DEMOLISH EXISTING WALL MOUNTED RETURN AIR GRILL. REUSE AND
ENLARGE OPENING FOR NEW GRILL.
DEMOLISH EXISTING CRAC CONDENSING UNITS AND ASSOCIATED PIPING.
DISCONNECT EXISTING ELECTRICAL CONNECTIONS. DISCONNECT
SWITCH AND CIRCUITS SHALL REMAIN FOR CONNECTION TO NEW UNIT.
8 EXISTING CONCRETE PAD TO REMAIN AND BE REUSED. - - -
EXISTING DUCTWORK, FLEX DUCT, AND AIR DEVICES, ABOVE RIGID
CEILING, IN SERVER ROOM TO REMAIN.
REUSE AND ENLARGE EXISTING REFRIGERANT PIPING PENETRATION
FOR NEW REFRIGERANT PIPING.
AE500 - -
NEW CONDENSING UNIT FOR CRAC. PROVIDE 3FT CLEAR ON ALL SIDES.
CONNECT EXISTING ELECTRICAL CIRCUIT TO NEW UNIT. EXTEND
EXISTING CIRCUIT AS NEEDED TO ACCOMMODATE NEW UNIT. FIELD
VERIFY EXISTING CIRCUIT CONDITION AND CAPACITY ARE ADEQUATE
FOR NEW UNIT AND REPLACE CIRCUITS IF NEEDED. CIRCUIT SHALL BE A
MINIMUM OF 3#12,#12G, 3/4" C. AND A 15A/3P CIRCUIT BREAKER.
- M-602 M-701
NEW 40 IN X 30 IN, WALL MOUNTED RETURN GRILL. REUSE EXISTING
GRILL OPENING AND ENLARGE TO NEW DIMMENSIONS.
ROUTE NON-POTABLE WATER LINE SUSPENDED FROM ROOF STRUCTURE
TO CRAC INLET FOR HUMIDIFIER MAKE-UP WATER.
- M-601 -
PROVIDE NEW UPFLOW CRAC UNITS AS SCHEDULED. INSTALL
EQUIPMENT SUCH THAT SERVICE CLEARANCES ARE UNOBSTRUCTED.
CONNECT EXISTING ELECTRICAL CIRCUIT TO NEW UNIT. EXTEND
EXISTING CIRCUIT AS NEEDED TO ACCOMMODATE NEW UNIT. FIELD
VERIFY EXISTING CIRCUIT CONDITION AND CAPACITY ARE ADEQUATE
FOR NEW UNIT AND REPLACE IF NEEDED. CIRCUIT SHALL BE A MINIMUM
OF 3#3, #8G, 1-1/4”C. AND AN 80A/3P CIRCUIT BREAKER.
- M-602 M-701
15 PROVIDE EMERGENCY OFF SWITCH NEAR DOOR ON WALL 4 FT AFF.
16 PROVIDE SMOKE SENSOR MOUNTED IN SUPPLY DUCT. - - 1/M-701
CONNECT NEW DUCT TO EXISTING MAIN ABOVE MECHANICAL ROOM
CEILING
ROUTE REFRIGERANT PIPING OVERHEAD USING EXISTING WALL
PENETRATIONS. VERIFY PIPE ROUTING SIZES AND INSTALLATION WITH
MANUFACTURER'S INSTALLATION MANUAL.
PROVIDE ROOM TEMPERATURE SENSOR. MOUNTED 4 FT AFF. SENSOR
MUST BE ABLE TO REPORT TEMPERATURE DATA TO LIEBERT ICOM OR
CRAC MANUFACTURER'S CONTROLLER.
PROVIDE ROOM HUMIDITY SENSOR. MOUNTED 4 FT AFF. SENSOR MUST
BE ABLE TO REPORT TEMPERATURE DATA TO LIEBERT ICOM OR CRAC
MANUFACTURER'S CONTROLLER.
ADDENDUM 01 08/22/20231
EXTERNAL STATIC PRESSURE - IN WG
FACE VELOCITY - FPM
COIL FACE AREA - SQUARE FEET
MOTOR HORSEPOWER
NUMBER OF ROWS / FINS PER INCH
FAN DATA -
EVAPORATOR
UNIT WEIGHT - LBS
AIRFLOW - CFM
UNIT TAG
MODEL NUMBER
MANUFACTURER
AREA SERVED
GENERAL
9,134
2,070
CRAC-4-1
BLDG 4 RM 105A
LEIBERT
VS070AD
COMPUTER ROOM AIR-CONDITIONING UNIT SCHEDULE
CAPACITY - kW
LAT DB/WB - °F
EAT DB/WB - °F
TOTAL CAPACITY - KW
EVAPORATOR
COOLING
COIL
ELECTRIC
REHEAT COIL
SENSIBLE CAPACITY - KW
REFRIGERANT CHARGE / CIRCUIT - LB
NOTES
FILTERS
FILTER EFFICIENCY MERV 8
FILTER TYPE 4 IN PLEATED
NOTES:
1. PROVIDE MANUFACTURER'S CONDENSATE PUMP.
2. PROVIDE (6) 25X20 IN FILTERS.
3. INSULATE BOTH REFRIGERANT GAS AND LIQUID PIPING SEPARATELY.
4. PROVIDE ADDITIONAL REFRIGERANT CHARGE FOR INTERCONNECTED PIPING. CONTRACTOR SHALL
CALCULATE ACTUAL CHARGE BASED ON INSTALLED LENGTH ACCORDING TO MANUFACTURER'S
INSTALLATION MANUAL.
5. PROVIDE NEMA 4 DISCONNECT SWITCH FOR OUTDOOR UNIT.
6. PROVIDE NEMA 12 DISCONNECT SWITCH FOR INDOOR UNIT.
7. PROVIDE MANUFACTURER'S BMS COMMUNICATION CARD FOR BACNET/IP INTEGRATION WITH BMS.
8. PROVIDE CRAC WITH U2U NETWORKING FOR ICOM CONTROLLER.
9. CONFIRM REFRIGERANT CHARGE WITH MANUFACTURER.
3 / 12
24.65
58.7 / 54.3
73.2
85 / 63.8
71.2
8.0
1,2,3,4,5,6,7,8
85,300
9.6
22.0
9,134
7.5
0.5
AIRFLOW - CFM
CAPACITY - BTU/H
INFRARED
HUMIDIFIER
CAPACITY - kW
CAPACITY - LBS/HR
AIR-COOLED
CONDENSING
UNIT
DESIGN AMBIENT AIR TEMPERATURE - °F 105
NOMINAL TONS 20
ELECTRICAL DATA - MCA 6.3
ELECTRICAL DATA - FLA 5.6
ELECTRICAL DATA - VOLTAGE/PHASE 460/3
ELECTRICAL DATA - MOCP 15
REFRIGERANT PIPE CONNECTION SIZE - LIQUID 5/8
REFRIGERANT PIPE CONNECTION SIZE - GAS 7/8
MINIMUM SENSIBLE COP 2.42
WEIGHT - LBS. 602
MODEL NUMBER MCL110E8
ELECTRICAL
DATA MOCP
MCA
VOLTAGE/PHASE
75.9
460 / 3
LOW AMBIENT AIR TEMPERATURE - °F 0
UNIT TAG CU-4-1
REFRIGERANT CHARGE / CIRCUIT- LB 7.5
FLA 62.9
9,134
2,070
CRAC-4-2
BLDG 4 RM 105A
LEIBERT
VS070AD
MERV 8
4 IN PLEATED
3 / 12
24.65
58.7 / 54.3
73.2
85 / 63.8
71.2
8.0
1,2,3,4,5,6,7,8
85,300
9.6
22.0
9,134
7.5
0.5
6.3
5.6
460/3
5/8
7/8
2.42
MCL110E8
75.9
460 / 3
CU-4-2
7.5
62.9
REFRIGERANT TYPE R407C R407C
1,350
CRAC-1-1
BLDG 1 RM 98A
LEIBERT
MT036
MERV 8
2 IN PLEATED
3 / 12
3.1
58.7 / 54.3
9.8
80 / 62.7
9.2
NOTE 9
1,3,4,5,6,7,8
7.4 (kw)
1,350
0.5
0.2
15.3
12.6
460/3
1/2
7/8
PFD037A-H
8.1
460 / 3
CU-1-1
NOTE 9
6.5
R410A
HVAC DUCT SCHEDULE
NOTESEQUIPMENT TYPEUNIT TAG
PRESSURE
CLASS
(IN WG)
SEAL
CLASS
NOTES:
1. PROVIDE 2 INCH THICK ACOUSTICAL FLEXIBLE ELASTOMERIC DUCT LINER IN SUPPLY AIR DUCT CONNECTED TO CRAC UNITS.
2. ROUND AND OVAL SPIRAL SEAM DUCTS DO NOT REQUIRE SEALING OF THE SPIRAL SEAM.
3. TRANSVERSE SEALING WITH MASTICS IS NOT REQUIRED WHERE JOINT CONSTRUCTION IS AN ENGINEERED PRODUCT MEETING SEAL CLASS A (LEAKAGE CLASS 3/6) PERFORMANCE. SUBMIT PRODUCT DATA FOR APPROVAL.
4. PROVIDE DUAL WALL DUCT. PEROFRATE INNER WALL OF DUCT FOR ACOUSTICAL PERFORMANCE.
DUCT TYPE
LEAKAGE
CLASS
(ROUND/
RECT)
LEAK
PRESSURE
TESTING
REQUIRED
AIR TEMP
RANGE
(°F)
CRAC UNIT
CRAC-96A (E),
CRAC-96B (E)
+ 1.0 3/6ASUPPLY NO 1,2,3,450-55
INSULATION
INSTALLED
R-VALUE
R-6
DUCT MATERIAL
ALUMINUM
DUCT LOCATION
INTERIOR
DUCT CONSTRUCTION
RECTANGULAR /
ROUND SPIRAL SEAM
DUCT
THICKNESS
(GAGE)
SMACNA
MIN. 26
GAGE
DIFFUSER AND GRILLE SCHEDULE
DESIGNATION
MODEL
MANUFACTURER
NOTES
VOLUME CONTROL
NOTES:
1. RUNOUT DUCT SIZES ARE THE SAME CLEAR AREA SIZE AS THE NECK SIZE OF AIR DISTRIBUTION DEVICE, UNLESS NOTED OTHERWISE. ROUND FLEXIBLE (MAXIMUM 5 FEET LONG) OR METAL DUCTS CAN BE PUSHED INTO AN OVAL
CONFIGURATION, WHERE NEEDED, PROVIDED NET CLEAR INSIDE AREA IS MAINTAINED.
DL
DUCT MOUNTED DRUM LOUVERS
CFM NECK SIZE
10 x 4150
DL
TITUS
12 x 6300
MATERIAL
SERVICE
STEEL
DEVICE
DESCRIPTION
PERFORMANCE
SCHEDULE
SUPPLY
G1
DUCT MOUNTED SUPPLY GRILLES
18 x 18500
CFM NECK SIZE
10 x 4150
20 x 201,350
24 x 242,800
RS
TITUS
STEEL
SUPPLY
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ENGINEER:
HUITT-ZOLLARS
500 W. 7th St., Ste. 300 Fort Worth, TX 76102 817-335-3000
ARCHITECT:
CB DESIGN GROUP
421 King St., Ste. 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
West Texas VA Health Care System Big Spring, TX 79720
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CIVIL/STRUCTURAL:
H2B 1225 N Loop W, Suite 800
HOUSTON, TX 77008
713-864-2900
12/23/2022
519-21-900
EALJW
VA BSP EHRM INFRASTRUCTURE
UPGRADES
CONSTRUCTION DOCUMENTS
HVAC SCHEDULES
M-602
-2
-9
M -6
/2
/2
.p d f
ADDENDUM 01 08/22/20231
CRAC INPUT/OUTPUT POINTS SCHEDULE
NOTESPOINT DESCRIPTION CALCULATED
VALUE
ANALOG
INPUT
UNIT
TAG
SYSTEM START/STOP
ANALOG
OUTPUT
BINARY
INPUT
BINARY
OUTPUT
SUPPLY FAN STATUS
C R
A C
-4 -1
, C R
A C
-4 -2
, C R
A C
-4 -3
C
R A
C -1
-1 , C
R A
C -1
-2
CRAC SEQUENCE OF OPERATIONS
CRAC-4-1, CRAC-4-2
SUPPLY FAN FAULT
RACK AIR TEMPERATURE
A. The Computer Room Air-Conditioning units are up flow units with electric reheat and humidification capabilities. The CRAC units are split system direct expansion units. These units will operate according to manufacturer's control algorithms. The contractor is responsible for providing additional sensors, unit controllers, and interlocks required to meet sequence requirements. The CRAC units must be provided with iCOM U2U communication which will allow operation of units in Teamwork, Standby, and Cascade modes. All control points available through the manufacturer's controller shall be able to be integrated into the existing campus Metasys
BMS.
B. The CRACs must operate in "Teamwork" operation.
C. If any active unit suffers an alarm or failure the remaining unit(s) provide capacity for full load except for:
1. Room air smoke detection
D. Mode of Operations:
1. Occupied mode: 24 hour operation
E. General Operation
1. The master unit controller monitors all rack mounted sensors and sets fan operating speed for all
CRAC fans based on the highest temperature reading.
2. Compressor capacity is controlled individually by each unit controller to maintain supply air temperature set point at CRAC discharge.
3. CRAC humidifier is controlled independently by each CRAC controller based on its humidity sensor and set point.
F. The supply fan must de-energize, and an alarm signal must be sent to DDC system if any of the following conditions occur:
1. Manufacturer safety prevents safe operation (including condensate pump failure).
2. Smoke is detected in the server room.
G. An alarm signal must be sent to DDC system if any of the following conditions occur:
1. Rack air temperature is greater than 81°F (adj.)
2. Rack relative humidity is greater than 60% (adj.)
3. Rack relative humidity is less than 30% (adj.)
H. Emergency shut-off button must turn off CRAC units in the event it is manually activated.
I. BMS Operator Station Display:
1. System status
2. Rack air temperature (highest of 3 sensors deg F)
3. Rack air temperature setpoint in degrees F
4. Rack air humidity in % RH
5. Rack air humidity setpoint in % RH
6. Unit safety shutdown (Smoke, HVAC shutdown, manufacturer safety)
7. System run time in hours
ROOM SMOKE DETECTOR
RL
RG
TXV
DX SF
CT
BI - SUPPLY FAN STATUS
ECM
BI - SUPPLY FAN FAULT
BO - SUPPLY FAN START/STOP
M
(1) EACH UNIT
(1) EACH UNIT
(1) EACH UNIT
(3) CRAC-4-1,2
(2) CRAC-4-3,CRAC-1-1,2
SA
CRAC-4-1, CRAC-4-2 (CRAC-4-3 SIMILAR)
RA
Ƨ
SN
RACK AIR TEMPERATURE SETPOINT
(3) CRAC-4-1,2
(2) CRAC-4-3,CRAC-1-1,2
(1) EACH UNIT
RACK AIR HUMIDITY
RACK AIR HUMIDITY SETPOINT
(1) EACH UNIT
RACK TEMPERATURE SENSOR
T
T
RACK
(3) TEMPERATURE PROBES, AND (1)
HUMIDITY PROBE PER SENSOR. LOCATED
AT TOP, MIDDLE, AND BOTTOM OF FRONT
FACE OF RACK.
1 FT MAX FROM TOP OF RACK
APPROX. CENTER OF RACK
(1) EACH UNIT
SYSTEM RUNTIME
EACH UNIT
MANUFACTURER SAFETY10
OFF
11 EMERGENCY SHUT-OFF SWITCH (1) FOR ALL UNITS
T
1 FT. MAX FROM BOTTOM OF RACK
H
RL
RG
TXV
DX
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
ENGINEER:
HUITT-ZOLLARS
500 W. 7th St., Ste. 300 Fort Worth, TX 76102 817-335-3000
ARCHITECT:
CB DESIGN GROUP
421 King St., Ste. 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
West Texas VA Health Care System Big Spring, TX 79720
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CIVIL/STRUCTURAL:
H2B 1225 N Loop W, Suite 800
HOUSTON, TX 77008
713-864-2900
12/23/2022
519-21-900
EALJW
VA BSP EHRM INFRASTRUCTURE
UPGRADES
CONSTRUCTION DOCUMENTS
CONTROL DIAGRAMS
M-701
-2
-9
M -7
/1
/1
.p d f
NOT TO SCALE
COMPUTER ROOM AIR-CONDITIONING UNIT
CONTROL DIAGRAM AND SEQUENCE OF OPERATIONS
ADDENDUM 01 08/22/20231
| Sheets |
| M-404 - HVAC ENLARGED PLAN |
| M-602 - HVAC SCHEDULES |
| M-701 - CONTROL DIAGRAMS |