Atch A - SOW Atch 2 - Bldg 222 Build Out Package (54 pages).pdf

PDF 15 MB Posted

Attached to
C1DZ--618-20-111, Renovate Bldg 223 for Pandemic Storage *DESIGN-BUILD*
Solicitation number
36C26321R0043
Issued by

About this file

This document is a statement of work attachment for a design-build solicitation to renovate Building 223 at a Veterans Affairs medical center for pandemic storage. The solicitation is seeking proposals to convert approximately 10,000 square feet of existing office space into storage areas for medical supplies and equipment to support pandemic response efforts. Proposals are due by July 15, 2020, with award anticipated by August 15, 2020. The project is to be completed within 180 calendar days of award. The work will be overseen by the VA Veterans Integrated Service Network 23 and is set aside for verified service-disabled veteran-owned small businesses.

View the file

Other files

File Type Posted
36C26321R0043 0001.docx DOCX document
RFP 36C26321R0043 Questions and Responses (1 page).pdf PDF
36C26321R0043_1.docx DOCX document
Atch C - PPQ (3 pages).pdf PDF
Atch A - Scope of Work (SOW) FINAL 2.8.2021 (14 pages).pdf PDF
Atch A - SOW Atch 12a - SHPO Request for Project Review (2 pages).pdf PDF
Atch A - SOW Atch 12b - SHPO Scope of Work Form (4 pages).pdf PDF
Atch A - SOW Atch 9 - Mpls VA Design Standards (10 pages).pdf PDF
Atch F - Wage Determination SCA 2015-4945 12.21.2021 (12 pages).pdf PDF
Atch E - Wage Determination Davis Bacon MN20210107 01.01.2021 (7 pages).pdf PDF
Atch B - Contractor Safety and EMR (2 pages).pdf PDF
Atch A - SOW Atch 8 - Minneapolis VA Revit Model Standards V1 (15 pages) (1).pdf PDF
Atch A - SOW Atch 5a - Convert Building 220-223 Concept Plans (9 pages) (1).pdf PDF
Atch A - SOW Atch 10 - Minneapolis Specific Standards (zip file).zip ZIP file
Atch A - SOW Atch 3 - Building 222 Roads and Grounds (23 pages).pdf PDF
Atch A - SOW Atch 3 - Building 222 Roads and Grounds (23 pages) (1).pdf PDF
Atch A - SOW Atch 4 - Bldg 223 Final LEAD Report (22 pages).pdf PDF
Atch A - SOW Atch 11 - Mpls Detail Drawings (zip file).zip ZIP file
Atch A - SOW Atch 6 - VA Barrier Free Design Standard (7 pages).pdf PDF
Atch D - VA6500.6 Appendix C 2 3a-5h-6a-7a-7d-9, Appendix D (7 pages).pdf PDF
Atch A - SOW Atch 1 - Fort Snelling West District Report (40 pages).pdf PDF
Atch A - SOW Atch 5b - Convert Building 220-223 Pictures (1 page).pdf PDF
Atch A - SOW Atch 7 - Minneapolis VA BIM Management Plan Worksheet - Form (3 pages).pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

07-21-2017

/2

/2

:0 :4

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-GI001

COVER SHEET

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

ARCHITECT

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

CONTACT: TOM OLESAK

PHONE: 763-412-4000

MECHANICAL/PLUMBING

ENGINEER

DUNHAM

50 SOUTH 6th STREET SUITE 1100

MINNEAPOLIS, MN 55402

CONTACT: JASON GOTTWALT

PHONE: 612-465-7648

ELECTRICAL ENGINEER

DUNHAM

50 SOUTH 6th STREET SUITE 1100

MINNEAPOLIS, MN 55402

CONTACT: CURT BARLAGE

PHONE: 612-465-7641

STRUCTURAL ENGINEER

LHB INC

701 WASHINGTON AVENUE NORTH

SUITE 200

MINNEAPOLIS, MN 55401

CONTACT: STEPHEN W. HEARN

PHONE: 612-752-6932

OWNER:

DEPARTMENT OF VETERANS AFFAIRS

708 S. THIRD STREET, SUIT 200

MINNEAPOLIS, MN 55415

CONTACT: RYAN VAN SCHYNDEL

PHONE: 612-467-2484

FAX:

COST CONSULTANT

CPMI

3265 NORTHWOOD CIRCLE

SUITE 170

EAGAN, MN 55121

CONTACT: BRYAN BERTRAND

PHONE: 952-854-3663

PLAN

NORTH

TR

U E

N O R

TH

TRUE

NORTH

TRUE

NORTH

VA PROJECT NUMBER:

OWNER & CONSULTANTS

VICINITY MAP SITE LOCATION MAPFORT SNELLING SITE AREA MAP

EXISTING

BUILDING

GOLF COURSE

PARK

EXISTING

BUILDING

B L O

O M

IN

G

T O

N R

D

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

BUILDING 222, BUILD OUT PACKAGE

FORT SNELLING

618-18-100

ENVIRONMENTAL CONSULTANT

INSTITUTE FOR ENVIROMENT

ASSESSMENT

9201 WEST BROADWAY

BROOKLYN PARK, MN 55445

CONTACT: BILL DOLD

PHONE: 763-315-7900

ROOT HOUSE

65% Design Concurrence

End User:

1969 Union:

3669 Union:

Logistics:

SPS:

EMS:

BIS:

95% Design Concurrence

End User:

1969 Union:

3669 Union:

Shops:

Safety Committee:

BIS:

Project Approval:

End User:

1969 Union:

3669 Union:

Engineering Project Chief

Engineering Director

No. Revisions Date

ACCESSIBLITY SYMBOLOGY LEGEND

DOOR CLEARANCES.

FRONT APPROACHES INDICATED,

SEE PLANS AND CODES FOR SIDE

APPROACHES.

ø 5' - 0"

4' - 0"

1' - 0"

1' - 6"

CLEAR FLOOR SPACE

TURNING SPACE

1' - 0" 3' - 0" 1' - 0"

5' - 0"

IF BOTH CLOSER AND LATCH PROVIDED

DETAIL INDICATOR-PLAN

ARCHITECTURAL SYMBOLS

1 View Name

1/8" = 1'-0"A101

INTERIOR ELEVATION INDICATOR

ELEVATION INDICATOR

ROOM NAME & NUMBER

DRAWING BLOCK TITLE

SECTION INDICATOR

Room name

WALL PARTITION TYPE

NORTH ARROW

NORTH

PROPERTY LINE

DOOR OPENING IDENTIFIER

WINDOW TYPE IDENTIFIER

DIMENSION LINE1' - 6"

MATERIAL SYMBOLS

BASE COURSE

CONCRETE

EARTH

SAND / MORTARBRICK

CONCRETE MASONRY

UNIT

STONE

STEEL / ALUMINUM

EXIST CONSTRUCTION

TO BE REMOVED

WOOD

PLYWOOD

BATT INSULATION

CENTER LINE INDICATOR

CONTRACT LIMIT LINE

DEMOLITION LINE

FEATURES ABOVE LINE

HIDDEN FEATURES LINE

MATCHLINE

EXIST CONSTRUCTION

TO REMAIN

VV ITEM - VA SUPPLIED &

INSTALLED

CC ITEM - VA SUPPLIED &

INSTALLED

VC ITEM - VA SUPPLIED &

CONTRACTOR INSTALLED

A2

A-202 D B

A

C

1A KEYNOTE

ROOM FINISH TAG

EXISTING DOOR TO REMAIN

CEILING

WALLS

FLOORING

BASE TRIM

WXXX

PXX

XXXX

AS101

AS101

Name Elevation

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

07-21-2017

/2

/2

:0 :4

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-GI002

SHEET INDEX, SYMBOLS AND

MATERIALS

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

SHEET INDEX

Current sheet No

Drawing Number Drawing Title

53 MR3101 MECHANICAL PLAN - ROOF

09 ELECTRICAL

54 E3000 ELECTRICAL TITLE SHEET

55 ED3101 ELECTRICAL DEMOLITION PLAN - LOWER LEVEL

56 ED3102 ELECTRICAL DEMOLITION PLAN - MAIN LEVEL

57 ED3103 ELECTRICAL DEMOLITION PLAN - ATTIC LEVEL

58 EL3101 LIGHTING PLAN - LOWER LEVEL

59 EL3102 LIGHTING PLAN - MAIN LEVEL

60 EL3103 LIGHTING PLAN - ATTIC LEVEL

61 EP3101 POWER PLAN - LOWER LEVEL

62 EP3102 POWER PLAN - MAIN LEVEL

63 EP3103 POWER PLAN - ATTIC LEVEL

64 ES3101 SIGNAL PLAN - LOWER LEVEL

65 ES3102 SIGNAL PLAN - MAIN LEVEL

66 ES3103 SIGNAL PLAN - ATTIC LEVEL

67 E3201 ELECTRICAL DETAILS

68 E3301 ELECTRICAL RISER DIAGRAM

69 E3401 ELECTRICAL SCHEDULES

70 E3402 LIGHTING SCHEDULES

71 E3501 ENLARGED ELECTRICAL PLANS

SHEET INDEX

Current sheet No

Drawing Number Drawing Title

01 GENERAL

1 GI001 COVER SHEET

2 GI002 SHEET INDEX, SYMBOLS AND MATERIALS

3 GI003 ABBREVIATIONS

05 ARCHITECTURAL

4 AS001 LIFE SAFETY PLAN - LOWER LEVEL

5 AS002 LIFE SAFETY PLAN - MAIN LEVEL

6 AS003 LIFE SAFETY PLAN - ATTIC LEVEL

7 AS101 DEMOLITION PLAN AND FLOOR PLAN - LOWER LEVEL

8 AS102 DEMOLITION PLAN AND FLOOR PLAN - MAIN LEVEL

9 AS103 DEMOLITION PLAN AND FLOOR PLAN - ATTIC LEVEL

AS104 NOT USED

10 AS105 REFLECTED CEILING PLAN - LOWER LEVEL

11 AS106 REFLECTED CEILING PLAN - MAIN LEVEL

12 AS107 REFLECTED CEILING PLAN -ATTIC LEVEL

13 AS401 ENLARGED PLANS AND INTERIOR ELEVATIONS

14 AS402 INTERIOR ELEVATIONS AND SECTIONS

15 AS601 INTERIOR DETAILS

16 AS602 INTERIOR DETAILS

17 AS701 INTERIOR PARTITION TYPES AND DETAILS

18 AS702 OPENING SCHEDULE AND DETAILS

19 AF100 FINISH SCHEDULE

20 AF101 FINISHES PLAN- LOWER LEVEL

21 AF102 FINISHES PLAN - MAIN LEVEL

22 AF103 FINISHES PLAN - ATTIC LEVEL

23 AF104 SIGNAGE - LOWER LEVEL

24 AF105 SIGNAGE - MAIN LEVEL

25 AF106 SIGNAGE - ATTIC LEVEL

06 INTERIORS

26 IF101 FURNITURE AND EQUIPMENT PLAN - LOWER LEVEL

27 IF102 FURNITURE AND EQUIPMENT PLAN - MAIN LEVEL

28 IF103 FURNITURE AND EQUIPMENT PLAN - ATTIC LEVEL

08 MECHANICAL

29 M3000 MECHANICAL TITLE SHEET

30 M3201 MECHANICAL DETAILS AND DETAIL VIEWS

31 M3202 VRF REFRIGERANT PIPING SCHEMATIC

32 M3301 WATER RISER DIAGRAMS

33 M3302 WASTE AND VENT RISER DIAGRAMS

34 M3401 MECHANICAL SCHEDULES

35 M3501 MECHANICAL AND ELECTRICAL SCHEDULES

36 MD3100 MECHANICAL DEMOLITION PLANS

37 MF3101 FIRE PROTECTION PLAN - LOWER LEVEL

38 MF3102 FIRE PROTECTION PLAN - MAIN LEVEL

39 MF3103 FIRE PROTECTION PLAN - ATTIC LEVEL

40 MH3101 HVAC PLAN - LOWER LEVEL

41 MH3102 HVAC PLAN - MAIN LEVEL

42 MH3103 HVAC PLAN - ATTIC LEVEL

43 MM3101 HEATING PIPING PLAN - LOWER LEVEL

44 MM3102 HEATING PIPING PLAN - MAIN LEVEL

45 MM3103 HEATING PIPING PLAN - ATTIC LEVEL

46 MM3201 REFRIGERATION PIPING PLAN -LOWER LEVEL

47 MM3202 REFRIGERATION PIPING PLAN -MAIN LEVEL

48 MM3203 REFRIGERATION PIPING PLAN -ATTIC LEVEL

49 MP3100 PLUMBING PLAN - UNDERGROUND

50 MP3101 PLUMBING PLAN - LOWER LEVEL

51 MP3102 PLUMBING PLAN - MAIN LEVEL

52 MP3103 PLUMBING PLAN - ATTIC LEVEL

GENERAL CLEANING NOTES

1. REMOVE DEBRIS FROM BUILDING.

2. REMOVE LOOSE CHIPPED OR PEELING PAINT AND OTHER

SURFACE RESIDUE FROM EXIST EXPOSED SURFACES.

3. CLEAN EXISTING SURFACES SCHEDULED TO REMAIN.

4. VACUUM CLEAN EXPOSED STRUCTURAL ELEMENTS TO REMAIN

EXPOSED.

5. VACUUM CLEAN "UNASSIGNED" SPACES GENERALLY ACCESSIBLE

TO BUILDING OCCUPANTS.

6. AT COMPLETION OF WORK, REMOVE REMAINING WASTE

MATERIALS, RUBBISH, TOOLS, EQUIPMENT, MACHINERY AND

SURPLUS MATERIALS. CLEAN ALL EXPOSED SURFACES. LEAVE

PROJECT CLEAN AND READY FOR OCCUPANCY PROVIDE FINAL

CLEANING IN ACCORDANCE WITH ASTM E1971.

A. DAMP MOP RESILIENT, TILE AND WOOD FLOORS.

B. VACUUM CLEAN CARPETED FLOORS.

C. CLEAN CERAMIC TILE WALLS.

D. CLEAN WINDOWS MIRRORS AND OTHER GLAZED

SURFACES.

GENERAL NOTE:

ITEMS IDENTIFYING A SPECIFIC MANUFACTURER AND MODEL ARE

FOR REFERENCE ONLY. ITEMS FROM OTHER MANUFACTURERS

WHICH MEET THE PERFORMANCE CRITERIA OF THE NAMED

MANUFACTURER CAN BE SUBSTITUTED WITH PRIOR APPROVAL OF

THE COR.

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

ABC AGGREGATE BASE COURSE

ACI AMERICAN CONCRETE INSTITUTE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT

ADMIN ADMINISTRATION

ADB AUTOMATIC DOOR BOTTOM

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGA AMERICAN GAS ASSOCIATION

AGC ASSOCIATED GENERAL CONTRACTORS

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURSIDICATION

AHR ANCHOR

AHU AIR HANDLING UNIT

AIA AMERICAN INSTITUTE OF ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL CONST

ALT ALTERNATE

ALUM ALUMINUM

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL STADARDS INSTITUTE

ANT ANTENNA

AP ACCESS PANEL

APPD APPROVED

APPROX APPROXIMATE

AR AS REQUIRED

ARCH ARCHITECT(URAL)

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION

ASKLR AUTOMATIC SPRINKLER

ASPH ASPHALT

ASSOC ASSOCIATION

ASTM AMERICAN SOCIETY FOR TESTING &

MATERIALS

ATCH ATTACHMENT

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AVE AVENUE

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL WOODWORKING INSTITUTE

AWPA AMERICAN WOOD PRESERVERS' ASSOC

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B LABEL CLASS B DOOR

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD BOARD

BD FT BOARD FEET (FOOT)

BEV BEVEL

BHMA BUILDER'S HARDWARE MANUFACTURER'S

ASSOCIATION

BI FLD DR BIFOLDING DOORS

BITUM BITUMINOUS

BKG BACKING

BLD BUILD

BLDG BUILDING

BLKT BLANKET

BLVD BOULEVARD

BM BEAM

BOT BOTTOM

BR BEDROOM

BRCG BRACING

BRDG BRIDGING

BRG BEARING

BRG PL BEARING PLATE

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

C CELSIUS

C LABEL CLASS C DOOR

C TO C CENTER TO CENTER

CAB CABINET

CAC CEILING ATTENUATION CLASS

CB CATCH BASIN OR CORNER BEAD

CBB CEMENTITIOUS (BACKER) BOARD

CC CLEAR COAT

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CD CONSTRUCTION DOCUMENTS

CEM CEMENT

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFLG COUNTERFLASHING

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CHEM CHEMICAL

CHFR CHAMFER

CHK CHECK

CI CAST IRON

CIP CAST-IN-PLACE

CIR CIRCLE

CIRC CIRCULAR

CONST J CONSTRUCTION JOINT

CJ CONTROL JOINT

CL CENTER LINE

CLDG CLADDING

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CM CONSTRUCTION MANAGEMENT

CMU CONCRETE MASONRY UNIT

CNR CORNER

CNTR COUNTER

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC CONCRETE

COND CONDENSER

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CPRS COMPRESSIBLE

CPT CARPET

CRS COLD ROLLED STEEL

CRSI CONCRETE REINFORCING STEEL

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSI CONSTRUCTION SPECIFICATIONS INSTITUTE

CSK COUNTER SUNK

CSMT CASEMENT

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTG COATING

CTR CENTER

CTRL CONTROL

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CU IN CUBIC INCH

CU YD CUBIC YARD

CURT CURTAIN

CYL CYLINDER

CYL L CYLINDER LOCK

D DEPTH

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL DOUBLE

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE

DL DEAD LOAD

DOC DOCUMENT

DOUG FIR DOUGLAS FIR

DOZ DOZEN

DR DOOR

DR CL DOOR CLOSER

DR FR DOOR FRAME

DR OPNG DOOR OPENING

DS DOWNSPOUT

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

DWTR DUMBWAITER

E EAST

E LABEL CLASS E DOOR

EA EACH

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

EIFS EXTERIOR INSULATION AND FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELAST ELASTOMERIC

ELEC ELECTRIC

ELEV ELEVATOR

EMER EMERGENCY

EMER SHR EMERGENCY SHOWER

ENCL ENCLOSURE

ENGR ENGINEER

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION AGENCY

EPDM ETHYLENE PROPYLENE DIENE MONOMER

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE BOARD (INSUL)

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ERD EXISTING ROOF DRAIN

ESC ESCAPE

ESCAL ESCALATOR

ESMT EASEMENT

ESP ESPECIALLY

EST ESTIMATE

ETC ET CETERA

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXP BT EXPANSION BOLT

EXST GR EXISTING GRADE

EXT EXTERIOR

F FAHRENHEIT

FA FIRE ALARM

FAB FABRIC

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FAS BD FASCIA BOARD

FCO FLOOR CLEANOUT

FCTY FACTORY

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FFE FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FH FLAT HEAD

FHC FIRE HOSE CABINET

FHP FULL HEIGHT PARTITION

FIG FIGURE

FIL FILLET

FIN FINISH

FIN GR FINISH GRADE

FIN WD FINISH WOOD

FIXT FIXTURE

FL FLOOR

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR SK FLOOR SINK

FLUOR FLUORESCENT

FM FACTORY MUTUAL

FO FINISHED OPENING

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FOUNT FOUNTAIN

FOW FACE OF WALL

FP FIREPROOF

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FIRE RATING

FRMG FRAMING

FRP FIBER REINFORCED PLASTIC

FRZ FREEZER

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET OR FOOT

FTG FOOTING

FURG FURRING

FURN FURNISH

FUT FUTURE

FWC FABRIC WALLCOVERING

GA GAGE

GAL GALLON

GALV GALVANIZED

GALV STL GALVANIZED STEEL

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GUARD

GDR GUARD RAIL

GEN GENERAL

GI GALVANIZED IRON

GL GLASS

GL BLK GLASS BLOCK

GLU LAM GLUED LAMINATED WOOD

GR FL GROUND FLOOR

GRAN GRANITE

GRTG GRATING

GSB GYPSUM SHEATHING BOARD

GSM GALVANIZED SHEET METAL

GT GROUT

GUAR GUARANTEE

GUT GUTTER

GYP GYPSUM

GYP BD GYPSUM BOARD

GYP PLAS GYPSUM PLASTER

H HIGH

H PLAM HIGH PRESSURE PLASTIC LAMINATE

HAZ MAT HAZARDOUS MATERIALS

HB HOSE BIBB

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD DOOR

HDBD HARDBOARD

HDNR HARDENER

HDO HIGH DENSITY OVERLAY

HDR HEADER

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE AIR

(FILTER)

HF HIGH FREQUENCY

HGR HANGER

HM HOLLOW METAL

HMD HOLLOW METAL DOOR

HMDFHOLLOW METAL DOOR AND FRAME

HMF HOLLOW METAL FRAME

HNDRL HANDRAIL

HO HOLD OPEN

HORIZ HORIZONTAL

HOSP HOSPITAL

HP HIGH POINT

HPD HYGIENE PRODUCT DISPOSAL

HPDL HIGH PRESSURE DECORATIVE LAMINATE

HQ HEADQUARTERS

HS HEAT-STRENGTHENED (GLASS)

HSKPG HOUSEKEEPING

HST HOIST

HT HEIGHT

HVAC HEATING, VENTILATING, AND A/C

HVY HEAVY

HW HOT WATER

HYD HYDRANT

HYDR HYDRAULIC

I INTERSTATE

IAQ INDOOR AIR QUALITY

IBC INTERNATIONAL BUILDING CODE

ID IDENTIFICATION

ID NO IDENTIFICATION NUMBER

ILLUM ILLUMINATION

INCL INCLUDED

IND INDEPENDENT

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

INTERCOM INTERCOMMUNICATION

INTL INTERNATIONAL

IRMA INVERTED ROOF MEMBRANE ASSEMBLY

IWH INSTANTANEOUS WATER HEATER

JAN JANITOR

J-BOX JUNCTION BOX

KD KNOCKED DOWN

KIT KITCHEN

KO KNOCKOUT

KPL KICKPLATE

L ANGLE

LAB LABORATORY

LAD LADDER

LAM LAMINATE

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

LB POUND

LD BRG LOAD-BEARING

LDR LEADER

LED LIGHT EMITTING DIODE

LF LINEAR FEET

LH LEFT HAND

LHR LEFT HAND REVERSE

LIB LIBRARY

LIN LINEAR

LINO LINOLEUM

LIQ LIQUID

LKR LOCKER

LKR LOCKER ROOM

LKWASH LOCKWASHER

LL LEAD LINED

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMST LIMESTONE

LNDSCP LANDSCAPE

LR LIVING ROOM

LRG LARGE

LRV LOUVERED ROOF VENT

LS LUMP SUM

LT LIGHT

LT GA LIGHT GAGE

LT WT LIGHTWEIGHT

LTG LIGHTING

LTNG LIGHTNING

LVD LOUVERED

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

LWIC LIGHTWEIGHT INSULATING CONCRETE

LYR LAYER

MACH MACHINE

MACH RM MACHINE ROOM

MAINT MAINTENANCE

MAN MANUAL

MATL MATERIAL

MAX MAXIMUM

MB MACHINE BOLT

MCB METAL CORNER BEAD

MD METAL DECK

ME MECHANICAL ENGINEER

MEAS MEASURE

MECH MECHANICAL

MED MEDICAL MEDIUM

MEL MELAMINE

MEMB MEMBRANE

MEMO MEMORANDUM

MEZZ MEZZANINE

MF MILL FINISH

MFD MANUFACTURED

MFG MANUFACTURING

MFR MANUFACTURER

MFR REC MANUFACTURER'S RECOMMENDATION

MGT MANAGEMENT

MH MANHOLE

MIC MICROPHONE

MID MIDDLE

MIN MINIMUM

MIRR MIRROR

MISC MISCELLANEOUS

MIT MITER

MKR MARKER

ML METAL LATH

MLDG MOLDING (MOULDING)

MLWK MILLWORK

mm MILLIMETER

MO MASONRY OPENING

MOD MODIFY

MOD BIT MODIFIED BITUMEN

MON MONITOR

MOPR MOP RACK

MR MOISTURE RESISTANT

MS MOP SINK

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

N NORTH

NA NOT APPLICABLE

NAAMM NATIONAL ASSOCIATION OF

ARCHITECTURAL METAL MANUFACTURERS

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEC NATIONAL ELECTRICAL CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NRC NOISE REDUCTION COEFFICIENT

NRCA NATIONAL ROOFING CONTRACTORS ASSOC

NRP NONREMOVABLE

NS NARROW STILE

NUM NUMERAL

O/O OUT TO OUT

O OXYGEN

OA OUTSIDE AIR OR OVERALL

OC ON CENTER

OCC OCCUPY

OCT OCTAGON

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OFF OFFICE

OH OVERHANG

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM

ORD OVERFLOW ROOF DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINSTRATION

OUT OUTLET

OZ OUNCE

PAR PARALLEL

PARA PARAGRAPH

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PED PEDESTAL

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PHAR PHARMACY

PHOTO PHOTOGRAPH

PHS PHILLIPS HEAD SCREW

PKG PACKAGE

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLYWD PLYWOOD

PMTL PAINT METAL

PNEU PNEUMATIC

PNL PANEL

PO POST OFFICE

POLY POLYETHYLENE (PLASTIC)

PR PAIR

PRCST PRECAST

PREFAB PREFABRICATE

PREFIN PREFINISH

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

PRMLD PREMOLDED

PROJ PROJECT

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTM PATCH TO MATCH EXISTING

PTN PARTITION

PVC POLYVINYL CHLORIDE

PVG PAVING

PWR POWER

QA/QC QUALITY ASSURANCE/QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RADIUS

RA RETURN AIR

RAD RADIATOR

RB RESILIENT BASE

RB HK ROBE HOOK

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RC REMOTE CONTROL

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECD RECEIVED

RECPT RECEPTACLE

RECT RECTANGLE

REF REFERENCE

REFR REFRIGERATION

REG REGISTER

REINF REINFORCE

REP REPAIR

REPL REPLACE

REQ/D REQUIRE/REQUIRED

RESIL RESILIENT

RET RETURN

REV REVISION

RF RADIO FREQUENCY

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RHR RIGHT HAND REVERSE

RHWS ROUND HEAD WOOD SCREW

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

SA SUPPLY AIR

SALV SALVAGE

SAMP SAMPLE

SAN SANITARY

SAT SUSPENDED ACOUSTICAL TILE

SB SPLASH BLOCK

SBS STYRENE BUTADIEN STYRENE

SBSTR SUBSTRATE

SC SHADING COEFFICIENT OR SOLID CORE

SCH SCHOOL

SCHED SCHEDULE

SCHEM SCHEMATIC

SCP SCUPPER

SCRN SCREEN

SCT STRUCTURAL CLAY TILE

SCWD SOLID CORE WOOD DOOR

SD SMOKE DETECTOR, OR SOAP

DISPENSER

SDG SIDING

SECT SECTION

SEG SEGMENT

SEL SELECT

SEP SEPARATE

SF SQUARE FOOT (FEET)

SFTWD SOFTWOOD

SGD SLIDING GLASS DOOR

SGL SINGLE

SHR SHOWER

SHR HD SHOWER HEAD

SHRD SHOWER DRAIN

SHT SHEET

SHTHG SHEATHING

SHV SHELVING

SIM SIMILAR

SJ SCORED JOINT

SJI STEEL JOIST INSTITUTE

SK SKETCH

SKLT SKYLIGHT

SLD WDW HORIZONTAL SLIDING WINDOW

SLDG SLIDING

SLNT SEALANT

SM SHEET METAL

SMK SMOKE

SND SANITARY NAPKIN DISPENSER

SND INS SOUND INSULATION

SNDU SANITARY NAPKIN DISPOSAL UNIT

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SPLY SUPPLY

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SANITARY SEWER

SST STAINLESS STEEL

ST STAIRS OR STREET

STC SOUND TRANSMISSION CLASS

STD STANDARD

STIF STIFFENER

STL JST STEEL JOIST

STL LNTL STEEL LINTEL

STNLS STAINLESS

STOR STORAGE

STRUCT STRUCTURAL

SUB SUBSTITUTE

SURF SURFACE

SUSP SUSPEND

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SW SWITCH

SWDR SWING DOOR

SYM SYMBOL

SYNTH SYNTHETIC

SYS SYSTEM

T TREAD

T&G TONGUE AND GROOVE

T&M TIME AND MATERIALS

TB THROUGH BOLT OR TOWEL BAR

TCA TILE COUNCIL OF AMERICA

TD TOWEL DISPENSER

TECH TECHNICAL

TEL TELEPHONE

TEMP TEMPERATURE

TMPRY TEMPORARY

TER TERRAZZO

THD THREAD

THERM THERMAL

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

THRUOUT THROUGHOUT

TK BD TACKBOARD

TMPD TEMPERED

TO TOP OF ___

TO FDN TOP OF FOUNDATION

TOB TOP OF BEAM

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOS TOP OF STEEL

TOW TOP OF WALL

TPD TOILET PAPER DISPENSER

TPH TOILET PAPER HOLDER

TR TOWEL RACK

TRANS TRANSOM

TRANS WD FIN TRANSPARENT WOOD FINISH

TRTD TREATED

TS TUBE STEEL

TSTAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

U HEAT TRANSFER COEFFICIENT

UC UNDERCUT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORIES

ULT ULTIMATE

UNFIN UNFINISH

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UR URINAL

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VAC VACUUM

VAR VARIES

VCT VINYL COMPOSITION TILE

VEH VEHICLE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VFAT VINYL FACED ACOUSTICAL TILE

VIC VICINITY

VID VIDEO

VIF VERIFY IN FIELD

VNR VENEER

VOC VOLATILE ORGANIC COMPOUND

VOL VOLUME

VOLT VOLTAGE

VP VENEER PLASTER

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

VWF VINYL WALL FABRIC

W WIDE

W/ WITH

W/O WITHOUT

WARR WARRANTY

WBL WOOD BLOCKING

WC WATER CLOSET

WCHR WATER CHILLER

WCL WATER COOLER

WD WOOD

WDW WINDOW

WF WIDE FLANGE

WFR WOOD FRAME

WFS WOOD FURRING STRIPS

WH WATER HEATER

WHSE WAREHOUSE

WLD WELDED

WM WIRE MESH

WP WATERPROOFING

WPM WATERPROOF MEMBRANE

WR WEATHER RESISTANT

WS WEATHERSTRIP

WSCT WAINSCOT

WT WEIGHT

WWF WELDED WIRE FABRIC

X BRACE CROSS BRACE

XPS EXTRUDED POLYSTYRENE BOARD (INSUL)

YD YARD

YR YEAR

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

07-21-2017

/2

/2

:0 :4

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-GI003

ABBREVIATIONS

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 713No. Revisions Date

UP

UP

DN

UP

UP

UP

UP

FD

FD

FD

FD

7 8 9 10

B

C

11 12 13 14 15 16 17 18 20 21 226321 5

A

D

1.1 3.1 3.2 3.3 3.4

F

H

J

K

L

19.1

19.1

E

I

19 21.2 21.3

G

7.1 9.1 11.1 13.1 15.1 17.15.1

I.1

K.1

L.1

H

R E

X

IT

P A

S S

A G

E W

A Y

FEC

FEC FEC

EXIT 1:

(EXIST)

60"

EXIT 2:

(EXIST)

34"

EXIT 3:

(EXIST)

73"

EXIT 4:

(EXIST)

36"

F E

C

EXISTING OPEN

OFFICE

EXISTING

CONFERENCE

102 EXISTING OPEN

OFFICE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

BREAK

EXISTING

VEST

EXISTING

WOMEN

EXISTING

MEN

EXISTING

LOBBY

EXISTING

VESTIBULE

EXISTING

ELEV EQUIP

EXISTING

WORK ROOM

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

CONFERENCE

EXISTING

PASSAGE

EXISTING

OPEN OFFICE

EXISTING

CONFERENCE

EXISTING

PASSAGE

EXISTING

OFFICE

EXISTING

OFFICE

E X

IS

T

IN

G

P A

S S

A G

E

EXISTING

BREAK

EXISTING

WOMEN

EXISTING

MEN

EXISTING

HSKPG

EXISTING

STORAGE

E X

IS

T

IN

G

E X

IT

P

A S

S A

G E

W A

Y

EXISTING

DATA

EXISTING BOILER

ROOM

EXISTING

WAREHOUSE

EXISTING

ELECTRICAL

ROOM

EXISTING

LOBBY

EXISTING

STAIR A

EXISTING

ELECT

EXISTING

VESTIBULE

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

OFFICE

OFFICE

OPEN OFFICE

EXISTING

STAIR B

EXISTING VESTIBULE

ELEC

CLOSET

144A

ELEV

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:2 :3

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS001

LIFE SAFETY PLAN - LOWER

LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

LIFE SAFETY PLAN - LOWER

LEVEL

Building Code Review

a) Sec 304 Occupancy Group B

b) Sec 508.3 Mixed Occupancy: No separation required between B and S-1

c) Sec 602.3 Type of Construction Type IIIB, fully sprinklered: (exterior walls constructed of non-combustible materials, interior elements constructed of any material allowed by the Code.)

d) Sec 502.1 Allowable Height: 55 feet, 3 stories (existing building is 35 feet at highest ridge)

e) Sec 503 Allowable Floor Area: 19,000 sq ft

f) Sec 506.2 Allowable Area Increase

Aa = {At + [At x If] + [At x Is]}, where If = [F/P - .25] W/30 Aa = {19,000 + [19,000 x .5383] + [19,000 x 2]}

Aa = {19,000 + 10,227.7 + 38,000} Aa = 67,227.7 (existing building is 28,511)

If = [F/P - .25]W/30 If = [668.5/848 - .25]30/30 If = [.7883 - .25] 1 If = .5383

g) Sec 1004.1 Occupant Load:

Basement (incl Root House): 12,203 sq ft First Floor 8,154 Second Floor 8,154 TOTAL 28,511 sq ft Office occupancy = 100 sq ft/ person TOTAL OCCUPANT LOAD 285 occ

h) Sec 1005.1 Egress Width Stairs: Occ load x .3”

285 x .3” = 85.5” 85.5/2 = 42.75 (minimum 48” required)

Other Elements: Occ load x .2” 285 x .2” = 57” 57/2 = 28.5 (minimum 32” clear required at doors)

i) Sec 1016 Maximum travel distance = 300 feet (fully sprinklered building)

j) Sec 1017.2 Minimum aisle width = 36”

k) Sec 1018.4 Maximum “Dead End” Corridor = 20’

l) Sec 1021 Number of exits required: (Table 1021.1: occ load 1-500, then 2 exits required per floor (story)

LIFE SAFETY ZONE LEGEND

RATED FIRE PARTITION

= 1 HR FIRE PARTITION

SYMBOL LEGEND

FIRE EXTINGUISHER CABINETFEC

XXX NUMBER OF OCCUPANTS PASSING THROUGH DOOR

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

GENERAL NOTES

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. FILL HOLES AND OPENINGS IN EXISTING FLOOR WITH A TESTED AND

APPROVED FIRE STOPPING SYSTEM.

EXIT SIGN

4No. Revisions Date

JTuchtenhagen Line

JTuchtenhagen Line

JTuchtenhagen Line

JTuchtenhagen Line

DN

DN

DN

DN

DN

FD

FD

7 8 9 10

B

C

11 12 13 14 15 16 17 18 20 21 2265

A

D

F

H

J

K

L

19.1

19.1

E

I

19 21.2 21.3

G

7.1 9.1 11.1 13.1 15.1 17.15.1

I.1

K.1

L.1

DN

FEC

FEC

FEC

FEC

EXISTING

CONFERENCE

EXISTING

MECH

201A

EXISTING

OPEN OFFICE

EXISTING

LOBBY

EXISTING

PASSAGE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

OFFICE

EXISTING

GALLERY

EXISTING

PASSAGE

EXISTING

TEAM

EXISTING

TEAM

EXISTING

OPEN OFFICE

EXISTING

PASSAGE

EXISTING

MEN

EXISTING

WOMEN

EXISTING

BREAK ROOM

E X

IS

T

IN

G

P A

S S

A G

E

PASSAGE

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

EXISTING

ELECTRICAL

EXISTING

LOADING DOCK

ATTIC SPACE

CONSULT

ROOM

CONSULT

ROOM

226CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

OPEN OFFICE

PASSAGE

CONFERENCE

CONSULT

ROOM

PASSAGE

CONSULT

ROOM

MECH

TOILET

OFFICE

UP

ELEC

CLOSET

244A

ELEV

WAREHOUSE

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:2 :3

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS002

LIFE SAFETY PLAN - MAIN

LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

LIFE SAFETY PLAN - MAIN

LEVEL

LIFE SAFETY ZONE LEGEND

RATED FIRE PARTITION

= 1 HR FIRE PARTITION

SYMBOL LEGEND

FIRE EXTINGUISHER CABINETFEC

XXX NUMBER OF OCCUPANTS PASSING THROUGH DOOR

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

GENERAL NOTES

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. FILL HOLES AND OPENINGS IN EXISTING FLOOR WITH A TESTED AND

APPROVED FIRE STOPPING SYSTEM.

EXIT SIGN

5No. Revisions Date

JTuchtenhagen Line

J J J

J

J

J

J

J

J

J

J

J

J

J

J

7 8 9 10

B

C

11 12 13 14 15 16 17 18 20 21 2265 23

A

D

F

H

J

K

L

19.1

19.1

E

I

19 21.2 21.3

G

7.1 9.1 11.1 13.1 15.1 17.15.1

I.1

K.1

L.1

FEC

FEC

FEC

EXISTING

OPEN OFFICE

EXISTING

TEAM

EXISTING

DATA ROOM

301A

EXISTING

LOBBY

PASSAGE

CONFERENCE

CONSULT

ROOM

ATTIC

309A

MEN

WOMEN

ATTIC

313A

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PASSAGE

CONSULT

ROOM

ATTIC

310A

ELEV

WAREHOUSE

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:2 :3

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS003

LIFE SAFETY PLAN - ATTIC

LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

LIFE SAFETY PLAN - ATTIC

LEVEL

LIFE SAFETY ZONE LEGEND

RATED FIRE PARTITION

= 1 HR FIRE PARTITION

SYMBOL LEGEND

FIRE EXTINGUISHER CABINETFEC

XXX NUMBER OF OCCUPANTS PASSING THROUGH DOOR

GENERAL NOTES

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. FILL HOLES AND OPENINGS IN EXISTING FLOOR WITH A TESTED AND

APPROVED FIRE STOPPING SYSTEM.

EXIT SIGN

0 2' 4' 6' 8' 16' 32'

SCALE: 3/32" = 1'-0"

PLAN

NORTH

TR

U E

N O R

TH

6No. Revisions Date

JTuchtenhagen Line

UP

UP

FD

21 22

D

F

H

J

K

L

19.1

E

I

EXISTING

VESTIBULE

E X

IS

T

IN

G

E X

IT

P

A S

S A

G E

W A

Y

21.2 21.3

G

FFE=

-2'-2 3/8"

EXISTING VESTIBULE

P3

P3

AS401

5' - 0" 11' - 8 1/2"

UP

P3

P3

P3

P3

AS601

L

IM

IT

O

F W

O R

K

LIMIT OF WORK

FFE=

-2'-2 3/8"

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

P3

CONSULT

ROOM

OFFICE

OFFICE

/4

E Q

E Q

E Q

E Q

OPEN OFFICE

2 1/2" CONC

TOPPING

TO BE LEVEL

WITH EXIST

EXIT

PASSAGEWAY

P3

P3

P3

144A

" P1A

10' - 6"

P1 INFILL

EXISTING

STAIR B

REINSTALL

SALVAGED DOOR

ASSEMBLY

CENTER

PARTITION

ON COLUMN

P3

AS601

AS601

CENTER

PARTITION

ON COLUMN

P3

WALL TO ALIGN WITH

UNDERSIDE OF

BEAM SOFFIT

45.00°

45.00°

AS602

P3

ELEC

CLOSET

144A

21 22

D

F

H

J

K

L

STORE HOUSE

(F-19)

A N

N E

X

19.1

E

I

21.2 21.3

G

REMOVE EXIST

WD FLOORING

AND SLEEPERS

REMOVE DOOR ASSEMBLY.

SALVAGE FOR REUSE

AS NOTED

REMOVE PORTION OF

EXIST GYP BD ON METAL

STUD PARTITION FOR

DOOR ASSEMBLIES.

LOCATE BASED ON

DIMENSIONS AND DETAILS

PROVIDED ELSEWHERE ON

DRAWINGS

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :1

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS101

DEMOLITION PLAN AND

FLOOR PLAN - LOWER LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

FLOOR PLAN- LOWER LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

FLOOR PLAN GENERAL NOTES

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. PATCH HOLES AND SURFACES DAMAGED, ALTERED OR MODIFIED

BY THIS WORK WITH MATERIAL TO MATCH EXISTING ADJACENT

SURFACES.

3. FOR REFLECTED CEILING PLANS, SEE SHEETS AS105, AS106, AND

AS107.

4. FOR FINISH SCHEDULE, SEE SHEETS AF100, AF101, AF102, AND

AF103.

5. PARTITIONS ARE P1 UNLESS NOTED OTHERWISE. FOR PARTITION

TYPES, SEE SHEET AS701. PROVIDE TWO CONTINUOUS 6" H BANDS

OF BLOCKING AT 4'-0" AND 6'-0" A.F.F. IN PARTITION TYPE P1 IN

ROOMS LABELED "OFFICE", "TEAM", "CONFERENCE" OR "CONSULT".

6. ALIGN FINISHED FACE OF PARTITION WITH FACE OR EDGE OF

EXISTING CONSTRUCTION, UNLESS NOTED OTHERWISE. PROVIDE

CONTINUOUS METAL J-BEAD TRIM AND 1/4" SEALANT JOINT AT

INTERFACE.

7. FOR OPENING SCHEDULE, SEE SHEET AS702.

8. IN ROOMS LABELED "HSKPG" PROVIDE MOP STRIP OVER FLOOR

SINK AND SHELF ADJACENT TO MOP STRIP, SEE 14/AS401 TYP.

9. PROVIDE SHADES ON ROOM SIDE OF BORROWED LIGHT FRAMES

THROUGHOUT.

10. UNNUMBERED DOORS/OPENINGS ARE EXISTING TO REMAIN.

11. PROVIDE ACCESS PANELS IN GYP BD PARTITIONS AND CEILINGS

WHERE SERVICE ACCESS TO MECHANICAL AND ELECTRICAL

EQUIPMENT IS REQUIRED- SEE MECHANICAL AND ELECTRICAL FOR

LOCATIONS.

DEMOLITION NOTES

1/8" = 1'-0"

DEMOLITION PLAN - LOWER

LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT IMMEDIATELY OF

ANY DISCREPANCIES.

2. REMOVE EXISTING CONSTRUCTION SHOWN DASHED AND AS NOTED, UNLESS

NOTED OTHERWISE. REMOVE ITEM OR ASSEMBLY IN ITS ENTIRETY INCLUDING

MOUNTING BRACKETS, HARDWARE, SUPPORTS AND OTHER APPURTENANCES.

SALVAGE AS NOTED OR DISPOSE OF PROPERLY.

3. PARTITIONS SHOWN TO BE REMOVED ARE WOOD PANELING, PLYWOOD OR FIBER

BOARD ON WOOD STUDS UNLESS NOTED OTHERWISE.

4. REMOVE DEBRIS, DIRT, DUST FROM EXISTING SURFACES THAT WILL

REMAIN EXPOSED AT THE COMPLETION OF WORK, OR TO PROPERLY ACCEPT

MATERIALS SPECIFIED UNDER THIS CONTRACT. ALSO SEE GENERAL CLEANING

NOTES ON SHEET GI002.

5. REMOVE MISCELLANEOUS FURRING, BRACKETS, FASTENERS, ETC. NO LONGER IN

USE FROM INTERIOR SURFACES THAT ARE SCHEDULED TO BE EXPOSED OR RECEIVE

FINISHES UNDER THIS CONTRACT.

DN

DN

UP

DN DN

21 22

D

F

H

J

K

L

EXISTING

STAIR B

EXISTING

ELEVATOR

19.1

E

I

P A

S S

A G

E

EXISTING

ELECTRICAL

21.2 21.3

G

9.1 11.1 13.1 15.1 17.1

I.1

K.1

L.1

DN

AS401

P4

P3

CONSULT

ROOM

11' - 3 1/4"

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PATCH

EXISTING

PLASTER

TO MATCH

EXISTING-

ENTIRE WALL

/4

FEC

LIMIT OF WORK

L

IM

IT

O

F W

O R

K

PROVIDE

5/8" GYP BD

OVER EXIST

WOOD

COLUMN

COVER

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONFERENCE

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PASSAGE

MECH

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PASSAGE

CONSULT

ROOM

OPEN OFFICE

10' - 0" 9' - 11" 9' - 11" 9' - 11" 9' - 11"

EQ EQ EQ

AS402

9' - 6"

ALIGN

P4

EQ

OFFICE

TOILET

AS401

/2

244A

AS601

5' - 8 1/2"

/2

6' - 0"

AS402

AS402

D1

D1 D1

D1 D1

D1D1D1 D1

D1

D1 D1 D1

D1

D1

RAMP

P1A

P1A 1' - 7"

AS401 9

INFILL/PATCH

PLASTER

TO MATCH EXISTING,

AROUND WINDOWS

AS402

AS402

AS402

AS402

AS402

P1C P1C

P1C P1A P1C

AS402

ALIGN PARTITION ON

WINDOW MUNTIN/MULLION

5' - 2"

INFILL

PLASTER AT

EXIST CMU

6' - 4"

AS401

FFE= 7'-8 1/2"

F F

E

'-2

/2

DN

AS402

AS402

P1A

P1A P1A

P1A

P1A

EXIST BATTERY

CHARGER

INFILL PLASTER

AT EXIST CMU

P1A

PATCH

EXISTING

PLASTER

TO MATCH

EXISTING ALL

AROUND-

ENTIRE WALL

P4

AS601

"3' - 8 1/4"

CENTER

PARTITION

ON COLUMN

P1C

AS402

ELEC

CLOSET

244A

21 22

D

F

H

J

K

L

WAREHOUSE

STORE HOUSE

(F-19)

19.1

E

I

21.2 21.3

G

EXISTING

ELEVATOR

EXISTING

STAIRS

9.1 11.1 13.1 15.1 17.1

I.1

K.1

L.1

REMOVE EXIST WALLS

REMOVE EXIST

QUARRY TILE

FLOORING AND

PLUMBING FIXTURES

IN THIS ROOM

REMOVE METAL HANGERS

AND UNUSED ELECTRICAL

BOXES/WIRES AT CEILING-

EXISTING METAL CEILING TO

REMAIN

REMOVE EXIST

VCT IN THIS AREA

REMOVE EXIST METAL

CEILING PANELS IN THIS

AREA - SALVAGE

FOR REUSE ELSEWHERE

ON PROJECT (EXIST

PLASTER CEILING TO

REMAIN)

REMOVE EXIST "CHAIR

RAIL" AT ENTIRE

PERIMETER OF THIS

SPACE

REMOVE

EXISTING DOOR

AND SIDELIGHTS

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :2

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS102

DEMOLITION PLAN AND

FLOOR PLAN - MAIN LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

FLOOR PLAN - MAIN LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

FLOOR PLAN GENERAL NOTES

1/8" = 1'-0"

DEMOLITION PLAN -MAIN

LEVEL

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

PLAN

NORTH

TR

U E

N O R

TH

DEMOLITION NOTES

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. PATCH HOLES AND SURFACES DAMAGED, ALTERED OR MODIFIED

BY THIS WORK WITH MATERIAL TO MATCH EXISTING ADJACENT

SURFACES.

3. FOR REFLECTED CEILING PLANS, SEE SHEETS AS105, AS106, AND

AS107.

4. FOR FINISH SCHEDULE, SEE SHEETS AF100, AF101, AF102, AND

AF103.

5. PARTITIONS ARE P1 UNLESS NOTED OTHERWISE. FOR PARTITION

TYPES, SEE SHEET AS701. PROVIDE TWO CONTINUOUS 6" H BANDS

OF BLOCKING AT 4'-0" AND 6'-0" A.F.F. IN PARTITION TYPE P1 IN

ROOMS LABELED "OFFICE", "TEAM", "CONFERENCE" OR "CONSULT".

6. ALIGN FINISHED FACE OF PARTITION WITH FACE OR EDGE OF

EXISTING CONSTRUCTION, UNLESS NOTED OTHERWISE. PROVIDE

CONTINUOUS METAL J-BEAD TRIM AND 1/4" SEALANT JOINT AT

INTERFACE.

7. FOR OPENING SCHEDULE, SEE SHEET AS702.

8. IN ROOMS LABELED "HSKPG" PROVIDE MOP STRIP OVER FLOOR

SINK AND SHELF ADJACENT TO MOP STRIP, SEE 14/AS401 TYP.

9. PROVIDE SHADES ON ROOM SIDE OF BORROWED LIGHT FRAMES

THROUGHOUT.

10. UNNUMBERED DOORS/OPENINGS ARE EXISTING TO REMAIN.

11. PROVIDE ACCESS PANELS IN GYP BD PARTITIONS AND CEILINGS

WHERE SERVICE ACCESS TO MECHANICAL AND ELECTRICAL

EQUIPMENT IS REQUIRED- SEE MECHANICAL AND ELECTRICAL FOR

LOCATIONS.

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT IMMEDIATELY

OF ANY DISCREPANCIES.

2. REMOVE EXISTING CONSTRUCTION SHOWN DASHED AND AS NOTED, UNLESS

NOTED OTHERWISE. REMOVE ITEM OR ASSEMBLY IN ITS ENTIRETY INCLUDING

MOUNTING BRACKETS, HARDWARE, SUPPORTS AND OTHER APPURTENANCES.

SALVAGE AS NOTED OR DISPOSE OF PROPERLY.

3. PARTITIONS SHOWN TO BE REMOVED ARE WOOD PANELING, PLYWOOD OR

FIBER BOARD ON WOOD STUDS UNLESS NOTED OTHERWISE.

4. REMOVE DEBRIS, DIRT, DUST FROM EXISTING SURFACES THAT WILL

REMAIN EXPOSED AT THE COMPLETION OF WORK, OR TO PROPERLY ACCEPT

MATERIALS SPECIFIED UNDER THIS CONTRACT. ALSO SEE GENERAL CLEANING

NOTES ON SHEET GI002.

5. REMOVE MISCELLANEOUS FURRING, BRACKETS, FASTENERS, ETC. NO LONGER

IN USE FROM INTERIOR SURFACES THAT ARE SCHEDULED TO BE EXPOSED OR

RECEIVE FINISHES UNDER THIS CONTRACT.

REF.

DN

C

21 22

D

F

H

J

K

L

EXISTING

STAIR B

19.1

E

I

P A

S S

A G

E

21.2 21.3

G

ATTIC

309A

AS401

E Q

E Q

CONFERENCE

CONSULT

ROOM

11' - 5"

5' - 8"

FEC

FEC

L

IM

IT

O

F W

O R

K

LIMIT OF WORK

MEN

WOMEN

HSKPG

303A

12' - 10"

A

B

7' - 1"

A

P3

ATTIC

313A

SIM

P A

S S

A G

E

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

A

P1A

P1A

P3

P1A

10' - 11 1/2"

P3

310 313

312311

1' - 5"

7' - 1"

ATTIC

310A

.1

310.1

.1

.1

T Y

P

MASONRY

INFILL

CONSULT

ROOM

INFILL AND

REPAIR DAMAGED

OR MISSING BRICK

AT WINDOW SILL

INFILL WALL ABOVE

AND AROUND 7'-0"

OPENING

AS601

PROVIDE 5/8"

GYP BD

ON EXIST

WOOD FRAMING

PROVIDE 5/8"

GYP BD

ON EXIST

WOOD FRAMING

PROVIDE 5/8"

GYP BD

ON EXIST

WOOD FRAMING

CENTER PTN

ON COLUMN

CENTER PTN

ON COLUMN

INFILL RECESS AT

BASE OF COLUMN

TO BE FLUSH WITH

ADJACENT EXIST

STRIP FLOORING -

AT EACH COLUMN FROM

GRID E TO I

AS601

ALIGN

5' - 0"

P3

P3

AS402

24"x36"

ACCESS PANEL

STORAGE

AS402

21 22

D

F

H

J

K

L

STORE HOUSE

(F-19)

A N

N E

X

19.1

E

I

21.2 21.3

G

REMOVE EXISTING

LINOLEUM

FLOORING

REMOVE EXISTING WALL

AS REQUIRED FOR NEW

OPENING

REMOVE EXISTING

FIBERBOARD AND

STUDS

REMOVE EXISTING

WALL AS REQUIRED

FOR NEW OPENING

REMOVE DOOR AND

FRAME

REMOVE EXISTING

FIBERBOARD CEILING

REMOVE EXIST LEAD

BASED PAINT FOR

EXIST MASONRY TO

REMAIN

THESE ITEMS CONTAIN

LEAD BASED PAINT.

FOLLOW PROCEDURES

OUTLINED IN SPEC

SECTION 02 83 33.13

FOR REMOVAL AND

DISPOSAL

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :2

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS103

DEMOLITION PLAN AND

FLOOR PLAN - ATTIC LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

FLOOR PLAN - ATTIC LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

FLOOR PLAN GENERAL NOTES

DEMOLITION NOTES

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

1/8" = 1'-0"

DEMOLITION PLAN - ATTIC

LEVEL

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT

IMMEDIATELY OF ANY DISCREPANCIES.

2. PATCH HOLES AND SURFACES DAMAGED, ALTERED OR MODIFIED BY

THIS WORK WITH MATERIAL TO MATCH EXISTING ADJACENT SURFACES.

3. FOR REFLECTED CEILING PLANS, SEE SHEETS AS105, AS106, AND

AS107.

4. FOR FINISH SCHEDULE, SEE SHEETS AF100, AF101, AF102, AND AF103.

5. PARTITIONS ARE P1 UNLESS NOTED OTHERWISE. FOR PARTITION

TYPES, SEE SHEET AS701. PROVIDE TWO CONTINUOUS 6" H BANDS OF

BLOCKING AT 4'-0" AND 6'-0" A.F.F. IN PARTITION TYPE P1 IN ROOMS

LABELED "OFFICE", "TEAM", "CONFERENCE" OR "CONSULT".

6. ALIGN FINISHED FACE OF PARTITION WITH FACE OR EDGE OF

EXISTING CONSTRUCTION, UNLESS NOTED OTHERWISE. PROVIDE

CONTINUOUS METAL J-BEAD TRIM AND 1/4" SEALANT JOINT AT

INTERFACE.

7. FOR OPENING SCHEDULE, SEE SHEET AS702.

8. IN ROOMS LABELED "HSKPG" PROVIDE MOP STRIP OVER FLOOR

SINK AND SHELF ADJACENT TO MOP STRIP, SEE 14/AS401 TYP.

9. PROVIDE SHADES ON ROOM SIDE OF BORROWED LIGHT FRAMES

THROUGHOUT.

10. UNNUMBERED DOORS/OPENINGS ARE EXISTING TO REMAIN.

11. PROVIDE ACCESS PANELS IN GYP BD PARTITIONS AND CEILINGS

WHERE SERVICE ACCESS TO MECHANICAL AND ELECTRICAL

EQUIPMENT IS REQUIRED- SEE MECHANICAL AND ELECTRICAL FOR

LOCATIONS.

1. VERIFY CONDITIONS NOTED AS EXISTING. NOTIFY ARCHITECT IMMEDIATELY

OF ANY DISCREPANCIES.

2. REMOVE EXISTING CONSTRUCTION SHOWN DASHED AND AS NOTED, UNLESS

NOTED OTHERWISE. REMOVE ITEM OR ASSEMBLY IN ITS ENTIRETY INCLUDING

MOUNTING BRACKETS, HARDWARE, SUPPORTS AND OTHER APPURTENANCES.

SALVAGE AS NOTED OR DISPOSE OF PROPERLY.

3. PARTITIONS SHOWN TO BE REMOVED ARE WOOD PANELING, PLYWOOD OR

FIBER BOARD ON WOOD STUDS UNLESS NOTED OTHERWISE.

4. REMOVE DEBRIS, DIRT, DUST FROM EXISTING SURFACES THAT WILL

REMAIN EXPOSED AT THE COMPLETION OF WORK, OR TO PROPERLY ACCEPT

MATERIALS SPECIFIED UNDER THIS CONTRACT. ALSO SEE GENERAL CLEANING

NOTES ON SHEET GI002.

5. REMOVE MISCELLANEOUS FURRING, BRACKETS, FASTENERS, ETC. NO LONGER

IN USE FROM INTERIOR SURFACES THAT ARE SCHEDULED TO BE EXPOSED OR

RECEIVE FINISHES UNDER THIS CONTRACT.

F

F

F

F

F

F

F

F F

F

F

F

F

F

F

F

F

FS

F S

R

20 21 22 23

D

F

H

J

K

L

19.1

19.1

E

I

E X

IS

T

IN

G

E X

IT

P

A S

S A

G E

W A

Y

EXISTING

VESTIBULE

21.2 21.3

G

EXISTING VESTIBULE

ACT @

8'-0" AFF

AS601

L

IM

IT

O

F W

O R

K

LIMIT OF WORK

ACT @

8'-0" AFF

ACT @

8'-0" AFF

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

OFFICE

OFFICE

OPEN OFFICE

AS601

EXISTING

STAIR B

ACT

INSTALL AS TIGHT

AS POSSIBLE TO

UNDERSIDE OF

WOOD BEAM

ACT

INSTALL AS TIGHT

AS POSSIBLE TO

UNDERSIDE OF

WOOD BEAM

ELEC

CLOSET

144A

REFLECTED CEILING LEGEND

LOW PROFILE 1X4 LIGHT FIXTURE

DOWNLIGHT

SUPPLY DIFFUSER/RETURN REGISTER

EMERGENCY EXIT LIGHT FIXTURES

REFLECTED CEILING

GENERAL NOTES:

1. ACT IS ACT TYPE 1 - UNO

2. COORDINATE LOCATION OF EXIT SIGNS AS SHOWN ON

ENGINEERING DRAWINGS AND LIFE SAFETY SHEETS.

3. PROVIDE ACCESS PANELS WHERE INDICATED IN

SPECIFICATION.

F

INDUSTRIAL LED LIGHT FIXTURE

F SMOKE DETECTOR

HORN/STROBE FIRE ALARM

SURFACE MOUNTED LED VANITY/SCONCE

4' SURFACE MOUNT LED

EMERGENCY LIGHT FIXTURE

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :2

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS105

REFLECTED CEILING PLAN -

LOWER LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

REFLECTED CEILING PLAN -

LOWER LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

SCALE: 1/8" = 1'-0"

10No. Revisions Date

FF

F

F

F

F

F

F

F

F

F

F

F

FF

F

FFFFF

F F F F F F

F

F S

FS

F S

F S

F S

F

R

F

F

21 22

D

F

H

J

K

L

19.1

E

I

EXISTING

ELECTRICAL

21.2 21.3

G

NO WORK

9.1 11.1 13.1 15.1 17.1

I.1

K.1

L.1

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PASSAGE

EXPOSED

STRUCTURE- PAINT

EXISTING EXPOSED

STRUCTURE- PAINT

EXPOSED BEAMS

EXISTING EXPOSED BEAMS-

PAINT, TYPICAL

EXISTING METAL COVE AND

CEILING TO REMAIN. PAINT

EXISTING

BEAM WRAP - PAINT

ACT

INSTALL AS TIGHT

AS POSSIBLE TO

UNDERSIDE OF

WOOD BEAM

ACT

INSTALL AS TIGHT

AS POSSIBLE TO

UNDERSIDE OF

WOOD BEAM

INFILL AREA WITH GYP

BD (5/8" MIN) AND

WOOD LATH TO BE

FLUSH WITH

ADJACENT EXISTING

PLASTER CEILING

SURFACES

REINSTALL SALVAGED

METAL CEILING PANELS ON

WOOD SLEEPERS (TO MATCH

EXISTING INSTALLATION

METHOD) - PAINT

L

IM

IT

O

F W

O R

K

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONFERENCE

PASSAGE

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

PASSAGE

OPEN OFFICE

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

CONSULT

ROOM

MECH

TOILET

OFFICE

LIMIT OF WORK

ACT @

8'-6" AFF

ACT @

8'-6" AFF

ACT @

8'-6" AFF

/4

/2

AS601

GYP BD

SOFFIT

GYP BD

SOFFIT

AS601

INFILL AREA WITH GYP BD

(5/8" MIN) AND WOOD

LATH TO BE FLUSH WITH

ADJACENT EXISTING

PLASTER CEILING

SURFACES

EXISTING CEILING

TO REMAIN

EXISTING EXPOSED

STRUCTURE- PAINT

AS601

ALL AROUND

AS402

8'-0" ACCOUSTICAL BAFFLES

9" OC CENTERED

IN EACH ROOM

4'-0" ACCOUSTIC

BAFFLES 9" OC

CENTERED

8'-0" ACCOUSTICAL BAFFLES

9" OC CENTERED

IN EACH ROOM

BULKHEAD CENTERED

ON DEMOUNTABLE

PARTITION- BOTTOM OF

BULKHEAD @ 8'-6" AFF

REPLACE DAMAGED

METAL CEILING PANELS

WITH SALVAGED PANELS

FROM OTHER LOCATIONS

WHERE POSSIBLE

AS602

ELEC

CLOSET

244A

REFLECTED CEILING LEGEND

LOW PROFILE 1X4 LIGHT FIXTURE

DOWNLIGHT

SUPPLY DIFFUSER/RETURN REGISTER

EMERGENCY EXIT LIGHT FIXTURES

REFLECTED CEILING

GENERAL NOTES:

1. ACT IS ACT TYPE 1 - UNO

2. COORDINATE LOCATION OF EXIT SIGNS AS SHOWN ON

ENGINEERING DRAWINGS AND LIFE SAFETY SHEETS.

3. PROVIDE ACCESS PANELS WHERE INDICATED IN

SPECIFICATION.

F

INDUSTRIAL LED LIGHT FIXTURE

F SMOKE DETECTOR

HORN/STROBE FIRE ALARM

SURFACE MOUNTED LED VANITY/SCONCE

4' SURFACE MOUNT LED

EMERGENCY LIGHT FIXTURE

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :2

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS106

REFLECTED CEILING PLAN -

MAIN LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

REFLECTED CEILING PLAN -

MAIN LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

11No. Revisions Date

F F

F

F

F

F

F

F

F

F

F

F

F

F

R

F

F

F

F SFS

F

F

R

F

20 21 22

D

F

H

J

K

L

19.1

19.1

E

I

21.2 21.3

G

ATTIC

309A

CONSULT

ROOM

CONFERENCE

P A

S S

A G

E

ACT @

8'-0" AFF

SLOPED GYP BD

PAINT

ACT @

8'-0"AFF

FLAT GYP BD

PAINT

8'-0" AFF

EXPOSED

STRUCTURE

ACT @

8'-0" AFF

EXPOSED

STRUCTURE

SLOPED GYP BD

PAINT

EXISTING

STAIR B

L

IM

IT

O

F W

O R

K

LIMIT OF WORK

MEN

WOMEN

HSKPG

303A

SLOPED GYP BD

PAINT

5/8" GYP

APPLIED TO

ROOF JOISTS

SLOPED GYP BD

PAINT

ATTIC

313A

SLOPED GYP

BD PAINT

CONSULT

ROOM

PASSAGE

CONSULT

ROOM

CONSULT

ROOM

FLAT GYP BD

PAINT

8'-0" AFF

FLAT GYP BD

PAINT

8'-0" AFF

CONSULT

ROOM

ATTIC

310A

EXIST GYP

CEILING TO

REMAIN - PAINT

AS402

AS402

REFLECTED CEILING LEGEND

LOW PROFILE 1X4 LIGHT FIXTURE

DOWNLIGHT

SUPPLY DIFFUSER/RETURN REGISTER

EMERGENCY EXIT LIGHT FIXTURES

REFLECTED CEILING

GENERAL NOTES:

1. ACT IS ACT TYPE 1 - UNO

2. COORDINATE LOCATION OF EXIT SIGNS AS SHOWN ON

ENGINEERING DRAWINGS AND LIFE SAFETY SHEETS.

3. PROVIDE ACCESS PANELS WHERE INDICATED IN

SPECIFICATION.

F

INDUSTRIAL LED LIGHT FIXTURE

F SMOKE DETECTOR

HORN/STROBE FIRE ALARM

SURFACE MOUNTED LED VANITY/SCONCE

4' SURFACE MOUNT LED

EMERGENCY LIGHT FIXTURE

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title

Approved: Project Director Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

AE PROJECT NO.: 14396

: 222

TO JT

KEY PLAN

07-21-2017

/2

/2

:0 :2

A

M C

U s e rs

\E P e te rs o n \D o c u m e n ts

\1 F o rt

S n e lli n g R

J T u c h te n h a g e n .r v t

1341-AS107

REFLECTED CEILING PLAN

-ATTIC LEVEL

BUILDING 222, BUILD OUT

PACKAGE

FORT SNELLING

07-21-2017

618-18-100

6330 BLOOMINGTON RD, ST. PAUL, MN 55111

100% CD ISSUE - BID DOCUMENTS

of 71

1/8" = 1'-0"

REFLECTED CEILING PLAN -

ATTIC LEVEL

PLAN

NORTH

TR

U E

N O R

TH

0 8' 16' 24'2' 4'

12No. Revisions Date

REF.

RAMP

1/12

FLOOR MOUNTED

HANDRAIL

PASSAGE

AS401

WALL MOUNTED

HANDRAIL

INFILL PLASTER

AT EXIST CMU

5' - 0"

D1

P3

P4

DN

/2

RAMP

6' - 0"

FFE= 7'-8 1/2"

FFE= 8'-2 1/2"

AS401

D

F

E

21.3

FEC

NIC

AS401 5

AS401 3

A

HSKPG

303A

MEN

WOMEN

8' - 2"

AS401

E Q

E Q

7' - 8 1/4"

CONFERENCE

P1A

P1A

P1A

PASSAGE

24"x36"

ACCESS PANEL

AS401

2' - 2"3' - 0"

APPLY 5/8" TYPE

'X' GYP BD OVER EXIST

WOOD FRAMING

WITHIN THIS SPACE.

EXIST

DRINKING

FOUNTAIN

L

21.317

AS401

1 1/2" OD FLOOR MOUNTED

METAL PIPE HANDRAIL,

PAINT

5…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .