ARFQ DEP24-61 Martinka Water Treatment Complex and F&M Shop Upgrades Plans DM signed (1).pdf
PDF 3 MB Posted
- Attached to
- OSR Martinka Complex & F&M Building Upgrades
- Solicitation number
- ARFQ 0313 DEP2400000061 7
- Issued by
- Marshall County, West Virginia
About this file
This document is a set of architectural plans and specifications prepared by the West Virginia Department of Environmental Protection, Office of Special Reclamation, Division of Land Restoration for existing building upgrades at two sites in Marion and Preston Counties, West Virginia. The project encompasses upgrades to the Martinka Water Treatment Complex (Permit # MAR1-2020) in Marion County and the F&M Coal Company shop facility (Permit # S-1073-86) in Preston County. The Martinka Water Treatment Complex improvements include a metal roof replacement with new roof trusses, gutters, and drainage systems for the control building; a rubber roof replacement with foam board insulation, new aluminum roof hatches, and interior metal brace repairs for the pump building; and electrical upgrades including 500 linear feet of wiring and conduit. The F&M Coal Company shop requires improvements including new steel exterior metal siding, replacement of an air conditioning unit with a wall-mounted heat/AC unit, garage door opener replacements, new exterior and interior LED lighting fixtures (16 four-foot LED lights and exterior utility lights), 500 linear feet of wiring and conduit, and general shop improvements. The plans were prepared in March 2024 by David B. McCoy, P.E. (West Virginia Professional Engineer Registration Number 14375).
The document provides detailed architectural drawings, elevations, roof plans, and material specifications for all proposed work at both sites but does not include pricing information, bid due dates, contract terms, funding sources, or award information. The summary of quantities table indicates materials and scope items but notes that actual bid quantities in WVOASIS may differ from the plan measurements to accommodate unforeseen field conditions. Technical specifications are referenced throughout the plans for specific components such as metal roofing panels, aluminum roof access hatches, air conditioning units, LED lighting fixtures, and steel building materials.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
WEST VIRGINIA COUNTY HIGHWAY MAP
VICINITY MAP
FELLOWSVILLE USGS 7.5' QUADRANGLE
OFFICE OF SPECIAL RECLAMATION
DIVISION OF LAND RESTORATION
West Virginia Department of Environmental Protection
HAROLD D. WARD, CABINET SECRETARY
MARION AND PRESTON COUNTIES, WEST VIRGINIA
F&M
SITE
PRESTON
COUNTY
LAT. 39° 19' 10" N
F&M
SITE
MARTINKA WATER TREATMENT COMPLEX AND F&M COAL COMPANY
MARION AND PRESTON COUTIESLONG. 79° 45' 16" W
STATE OF
NOS I
EF
RP O W
TSE
S
E NLA
REENI NGRV I
AI
G I
14375
REG I STEREDDAV I D B . MCCOY
MARCH 2024
DRAWING INDEX
DESCRIPTION SHEET NO. DESCRIPTION SHEET NO.
TITLE PAGE 1
SUMMARY OF QUANTITIES 2
MARTINKA WATER TREATMENT COMPLEX CONTROL BUILDING 3-5
MARTINKA WATER TREATMENT PUMP BUILDING 6
F&M EXISTING SHOP UPGRADES 7
PERMIT # MAR1-2020 AND S-1073-86
EXISTING BUILDING UPGRADES
F&M
SITE
MARTINKA
SITE
MARTINKA
SITE
FAIRMONT WEST USGS 7.5' QUADRANGLE
LAT. 39° 24' 50" N
LONG. 80° 07' 41W
MARTINKA
SITEMARION
COUNTY
AutoCAD SHX Text
HANCOCK
AutoCAD SHX Text
BROOKE
AutoCAD SHX Text
OHIO
AutoCAD SHX Text
MARSHALL
AutoCAD SHX Text
PRESTON
AutoCAD SHX Text
MORGAN
AutoCAD SHX Text
MONONGALIA
AutoCAD SHX Text
WETZEL
AutoCAD SHX Text
MINERAL
AutoCAD SHX Text
BERKELEY
AutoCAD SHX Text
MARION
AutoCAD SHX Text
TYLER
AutoCAD SHX Text
HAMPSHIRE
AutoCAD SHX Text
JEFFERSON
AutoCAD SHX Text
PLEASANTS
AutoCAD SHX Text
HARRISON
AutoCAD SHX Text
TAYLOR
AutoCAD SHX Text
DODDRIDGE
AutoCAD SHX Text
WOOD
AutoCAD SHX Text
RITCHIE
AutoCAD SHX Text
GRANT
AutoCAD SHX Text
BARBOUR
AutoCAD SHX Text
TUCKER
AutoCAD SHX Text
HARDY
AutoCAD SHX Text
WIRT
AutoCAD SHX Text
LEWIS
AutoCAD SHX Text
RANDOLPH
AutoCAD SHX Text
UPSHUR
AutoCAD SHX Text
GILMER
AutoCAD SHX Text
JACKSON
AutoCAD SHX Text
CALHOUN
AutoCAD SHX Text
MASON
AutoCAD SHX Text
PENDLETON
AutoCAD SHX Text
ROANE
AutoCAD SHX Text
BRAXTON
AutoCAD SHX Text
POCAHONTAS
AutoCAD SHX Text
WEBSTER
AutoCAD SHX Text
PUTNAM
AutoCAD SHX Text
CLAY
AutoCAD SHX Text
KANAWHA
AutoCAD SHX Text
CABELL
AutoCAD SHX Text
NICHOLAS
AutoCAD SHX Text
WAYNE
AutoCAD SHX Text
LINCOLN
AutoCAD SHX Text
GREENBRIER
AutoCAD SHX Text
FAYETTE
AutoCAD SHX Text
BOONE
AutoCAD SHX Text
LOGAN
AutoCAD SHX Text
RALEIGH
AutoCAD SHX Text
MINGO
AutoCAD SHX Text
SUMMERS
AutoCAD SHX Text
WYOMING
AutoCAD SHX Text
MONROE
AutoCAD SHX Text
MERCER
AutoCAD SHX Text McDOWELL
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text
DAVID B. MCCOY, PE WEST VIRGINIA PROFESSIONAL ENGINEER REGISTRATION NUMBER 14375
SPECIFICATION(S) SUMMARY OF QUANTITIES QUANTITY UNITS
MARTINKA WATER TREATMENT COMPLEX MAR1-2020
CONTROL BUILDING
13-9,13-10,13-12,13-17,13-18 METAL ROOF 1 LS
13-7 GUTTERS 155 LF
11-7 WIRING 500 LF
11-6 CONDUIT 500 LF
11-2,11-3,11-4,11-5 ELECTRICAL UPGRADES 1 LS
MARTINKA WATER TREATMENT COMPLEX MAR1-2020
PUMP BUILDING
13-12,13-13,13-17 RUBBER ROOF 1 LS
12-54 ALUMINUM ROOF HATCHES 2 EA
13-7 INTERIOR METAL BRACE REPAIR 1 LS
10-14, 13-7 BUILDING REPAIRS 1 LS
F&M COAL COMPANY S-1073-86
11-2,11-3,11-4,11-5,11-10,11-11,11-36,13-12, 13-14,13-15,13-18 SHOP IMPROVEMENTS 1 LS
11-25 4 FOOT LED LIGHTS 16 EA
11-7 WIRING 500 LF
11-6 CONDUIT 500 LF
5-5 UTILITIES NON BID ITEM
NOTE:
THE QUANTITIES SHOWN ON THE SUMMARY OF QUANTITIES REPRESENT THE AMOUNTS AS
DIRECTLY MEASURED IN THE PLANS. WHEN BIDDING IN WVOASIS THE COMMODITY LINES MAY BE
DIFFERENT AMOUNTS FROM THE PLANS TO ACCOMMODATE ANY UNFORESEEN CHANGES IN THE
FIELD. THEREFORE, ALWAYS BID ON THE QUANTITIES LISTED IN WVOASIS.
SUMMARY OF QUANTITIES
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: NTS
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
MARTINKA WATER TREATMENT COMPLEX
PERMIT # MAR1-2020
F&M COAL COMPANY PERMIT # S-1073-86
EXISTING BUILDING UPGRADES
MARION & PRESTON COUNTIES,
WEST VIRGINIA
DATE: MARCH 2024
NORTH ELEVATION
SOUTH ELEVATION
SECTION A
SECTION A
SECTION B
SECTION C
1046.00' ELEV.
1061.67' ELEV.
1067.67' ELEV.
1067.67' ELEV.
1055.33' ELEV.
SECTION C 1061.67' ELEV.
CONTROL BUILDING ELEVATIONS
NORTH AND SOUTH
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: 1:4
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
DATE: MARCH 2024
MARTINKA WATER TREATMENT COMPLEX
PERMIT # MAR1-2020
EXISTING BUILDING UPGRADES
MARION COUNTY, WEST VIRGINIA
WEST ELEVATION
SECTION B
SECTION A
1046.00' ELEV.
1067.67' ELEV.
NEW AUTOMATIC LOUVRE
ROOF EDGE DETAILS
ALL SECTIONS
WOOD TRUSS
TREATED WOOD 2"X8"
TRUSS ANCHOR BOARD
TREATED WOOD 2"X8"
FASCIA BOARD
METAL ROOF PANELS
METAL FASCIA
2" DRIP EDGE
WOOD PURLINS 2"X4"
VAPOR BARRIER
EAST ELEVATION
SECTION B
SECTION A
SECTION C
1067.67' ELEV.
1061.67' ELEV.
1046.00' ELEV.
EXISTING EXHAUST FAN
WOOD PURLINS 2"X4" (TYP.)
TREATED 2"X12"
TREAETED 2"X8"
ROOF TRUSS
TREATED 2"X4" BRACES
EXISTING CAUSTIC TANK VENT PIPES
2'-0"
8'-0"
NEW EXHAUST FAN
7'-0"
CONTROL BUILDING ELEVATIONS
EAST AND WEST
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: 1:4
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
DATE: MARCH 2024
MARTINKA WATER TREATMENT COMPLEX
PERMIT # MAR1-2020
74'-0"
13'-8"
24'-0"
43'-4"
59'-4"
ROOF PLAN VIEW
SECTION A
SECTION B
SECTION C
NEW ROOF TRUSSES
19'-4"
NOTES:
1. TREATED 2X8'S ARE TO BE ANCHORED TO TOP OF BUILDING WALLS ABOVE
EXISTING ROOF.
2. TRUSSES ARE TO ANCHORED TO NEWLY INSTALLED 2X8'S ON TWO (2)
FOOT CENTERS AT ROOF WALL TOP WITH OUTER EDGE FLUSH WITH THE
OUTSIDE BUILDING WALL SURFACE.
3. 2X4'S TO BE INSTALLED PERPENDICULAR TO NEW TRUSSES ON TWO (2)
FOOT CENTERS.
4. TREATED 2X8 FASCIA BOARD TO BE VERTICALLY INSTALLED AT TOP OF
BUILDING WALL AND FLUSH UNDER ROOF PANELS.
5. TYVEK OR ENGINEER APPROVED EQUAL VAPOR BARRIER TO BE
INSTALLED UNDER ROOF SHEET METAL.
6. METAL ROOFING PANEL TO BE INSTALLED USING METAL LEAK SHIELD
GASKETED SCREWS WITH A ONE AND A HALF (1.5) INCH OVERHANG PAST
THE TOP EDGE OF THE 2X8 FASCIA BOARD.
8. DIAGONALLY PLACED 2x4 WOOD CROSS BRACES TO BE INSTALLED FROM
EACH BUILDING CORNER TO ROOF CENTERLINE.
9. ALL GABLE ENDS SHALL HAVE METAL COVERING INSTALLED IN THE
VERTICAL DIRECTION. METAL STARTER STRIPS OR J-CHANNEL SHALL BE
USED ON BOTTOM TRIM.
10. ALL GABLE ENDS SHALL HAVE END RAKES WITH SOLID FOAM CLOSURE
STRIPS ON VERTICAL SIDES.
11. SECTIONS A AND C SHALL HAVE METAL RIDGE CAPS WITH SOLID FOAM
CLOSURE STRIPS.
12. SECTIONS B AND C SHALL HAVE METAL FLASHING TO SEAL AGAINST
EXISTING BLOCK WALLS. SEALANT AND SCREWS SHALL BE USED TO
ATTACH FLASHING TO WALL. SECTION B FLASHING SHALL BE SIX (6)
INCHES. SECTION C FLASHING SHALL BE THREE (3) INCHES TO ALLOW
ROOM FOR NEW EXHAUST FAN.
13. EXISTING EXHAUST FAN TO BE REMOVED AND OPENING BLOCKED IN.
EXISTING CAUSTIC TANK VENT PIPES TO REMAIN WHERE CURRENTLY
LOCATED.
14. NEW EXHAUST FAN TO BE INSTALLED WITH CENTERLINE SEVEN (7) FEET
FROM THE RIGHT EDGE OF SECTION A WALL AND CLEARING SECTION C
FLASHING. TRIANGLE ENGINEERING OF ARKANSAS, INC. FAN MODEL GPX
1611 TO BE INSTALLED OR ENGINEER APPROVED EQUAL.
15. NEW AUTOMATIC LOUVRE TO BE INSTALLED ON WEST SIDE OF BUILDING
ACROSS FROM EXISTING EXHAUST FAN.
16. OUTSIDE LIGHTS SHALL BE REMOVED AND REINSTALLED AFTER NEW
ROOF IS FINISHED.
17. ANY OTHER ITEMS ATTACHED TO THE BUILDING SHALL BE REMOVED AND
REINSTALLED AS NEEDED.
18. ABOVE ITEMS 13-17 SHALL BE INCIDENTAL TO BID ITEM "ELECTRICAL
UPGRADES".
19. EXISTING GUTTERS ARE TO BE USED; SOUTH SIDE OF SECTION C TO HAVE
NEW GUTTER AND DOWNSPOUT INSTALLED.
CONTROL BUILDING ROOF PLAN VIEW DETAIL
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: 1:4
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
DATE: MARCH 2024
MARTINKA WATER TREATMENT COMPLEX
PERMIT # MAR1-2020
NOTES:
1. TREATED 2X8 FASCIA BOARD TO BE INSTALLED ALONG THE OUTSIDE TOP EDGE OF
BUILDING WALLS IN PLACE OF EXISTING 10" BLACK METAL FASCIA AND COVERED
WITH NEW METAL ROOFING IN A FASHION SIMILAR TO THAT OF THE CONTROL
BUILDING (SEE SHEET 4 FOR DETAILS).
2. ROCKS TO BE REMOVED FROM ROOF ALONG WITH ANY UNDERLAYMENT DOWN TO
BASE METAL Q-DECKING LAYER.
3. ANY DAMAGED AND RUSTED METAL Q-DECKING AT REAR EAST SIDE OF BUILDING TO
BE SPOT REMOVED AS NEEDED AND REPLACED WITH NEW.
4. 3 4" RIGID FOAM BOARD INSULATION TO BE INSTALLED ON TOP OF Q-DECKING OVER
ENTIRE ROOF SURFACE FOLLOWED BY 3 4" OSB AND TOPPED WITH FINAL RUBBER
ROOFING LAYER WITH CURRENT ROOF SLOPE TO BE MAINTAINED; ADD DRIP EDGE TO
REAR EAST SIDE OF ROOF AND ADD BATTEN STRIP AROUND HATCH OPENINGS WITH
RUBBER ROOFING WRAPPING AROUND DRIP EDGE AND BATTEN STRIPPED TO
OUTSIDE FASCIA.
5. BOTH EXISTING BILCO HATCHES TO BE REPLACED WITH NEW OF SIMILIAR STYLE AND
DIMENSION IN CURRENT LOCATION. SEE TECHNICAL SPECIFICATION 12-54 ALUMINUM
ROOF ACCESS HATCH FOR DETAILS.
6. EXISTING ALUMINUM GUTTER RUNNING ALONG THE REAR EAST ELEVATION OF
BUILDING TO BE REPLACED ALONG WITH NEW DRAIN PIPE INSTALLED AND
DAYLIGHTED TO EXISTING DITCH AT FRONT WEST SIDE OF BUILDING. NEW GUTTERS
ONLY TO BE INCLUDED IN CONTROL BUILDING BID ITEM "GUTTERS"; DRAIN PIPE TO BE
PAID UNDER PUMP BUILDING BID ITEM "BUILDING REPAIRS".
7. METAL CROSS BRACES RUNNING THE WIDTH OF THE INSIDE OF THE BUILDING TO
HAVE NEW METAL ENDS WELDED IN PLACE AND SECURELY ANCHORED TO THE TOP
OF THE CONCRETE BLOCK WHERE ALREADY RESTING.
8. ALL EXISTING INSIDE WOODEN ROOF LEVELING SPACERS TO BE REPLACED WITH
HDPE.
9. NEW SEAL AND DOOR SWEEP TO BE INSTALLED AT BOTTOM OF ENTRANCE DOOR.
10. ALL CRACKS AND GAPS FOUND ALONG ROOF EDGES OUTSIDE TO BE CAULKED AND
INSIDE THE BUILDING SHALL BE SEALED WITH SPRAY FOAM.
11. EXISTING INTERIOR 12" METAL OVERFLOW PIPE EXTERIOR DISCHARGE POINT TO BE
FIELD LOCATED AND A FLAPPER CHECK VALVE INSTALLED. SEE TECHNICAL
SPECIFICATION 13-7 MISCELLANEOUS SPECIALTIES FOR DETAILS.
EXISTING 42" METAL ENTRANCE DOOR
CURRENT ROOF SLOPE APPROXIMATELY 2.5%
EXISTING 4'X4' ALUMINUM BILCO HATCHES
EXISTING 10" METAL FACIA
WEST ELEVATION SOUTH ELEVATION
ROOF FLOOR PLAN
20'-0"
19'-4"
ALUMINUM ROOF ACCESS HATCH DETAIL
PUMP BUILDING
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: 1:3
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
DATE: MARCH 2024
MARTINKA WATER TREATMENT COMPLEX
PERMIT # MAR1-2020
EXISTING BUILDING UPGRADES
MARION COUNTY, WEST VIRGINIA
AutoCAD SHX Text
FRAME OPENING WIDTH
AutoCAD SHX Text
OVER ALL
AutoCAD SHX Text
FRAME OPENING LENGTH
AutoCAD SHX Text
OVER ALL
AutoCAD SHX Text R
AutoCAD SHX Text
GUIDE ARM
AutoCAD SHX Text 4'-7" [1395mm]
AutoCAD SHX Text
BILCLIP
AutoCAD SHX Text
FLASHING SYSTEM
AutoCAD SHX Text 4'-7" [1395mm]
AutoCAD SHX Text 4'-0" [1220mm]
AutoCAD SHX Text 4'-0" [1220mm]
AutoCAD SHX Text
1" [25] RIGID FIBERBOARD INSULATION
AutoCAD SHX Text
SPRING LIFTING MECHANISM
AutoCAD SHX Text
PINTLE HINGE
AutoCAD SHX Text
1" [25] THICK FIBERGLASS COVER INSULATION
AutoCAD SHX Text
COVER
AutoCAD SHX Text
INSIDE & OUTSIDE HANDLES W/ PADLOCK HASPS
AutoCAD SHX Text
NEOPRENE GASKET
AutoCAD SHX Text
LOCK STRIKE & PADLOCK HASP
AutoCAD SHX Text
FRAME W/ CAPFLASHING (CORNERS FULL WELDED)
AutoCAD SHX Text
COVER HOLD CHAIN (2) REQ'D PER COVER (1) @ EACH END
AutoCAD SHX Text
HEAVY DUTY HOLD OPEN ARM
AutoCAD SHX Text
RED VINYL GRIP
AutoCAD SHX Text
COVER LINER
AutoCAD SHX Text
ARM GUIDE BRACKET
AutoCAD SHX Text
GASKET (ALL AROUND COVER)
AutoCAD SHX Text
SLAM LATCH
14.00' 12.00'
14.00' 3.00'
61.00'
61.00'
40.50'
UPGRADES TO BE COMPLETED:
1. SEAL ROOF AROUND PROTRUSIONS AND AT BUILDING EDGES AND THEN PAINT THE
ROOF.
2. CLEAN AND INSPECT EXISTING SEPTIC TANK.
3. REPLACE EXISTING EXTERIOR METAL SIDING WITH NEW STEEL PANELS, SEALS, AND
ANCHORS. SEE TECHNICAL SPECIFICATION 13-18 STEEL BUILDINGS FOR DETAILS.
4. REPLACE FOAM SEAL ON BUILDING EXTERIOR WHERE THE WALL MEETS THE ROOF.
5. INSTALL NEW CREE LIGHTING FIXTURES WHERE INDICATED IN RED ON EXTERIOR.
6. REPLACE EXISTING AIR CONDITIONER IN THE OFFICE WITH WALL MOUNTED HEAT/AC
UNIT. SEE TECHNICAL SPECIFICATION 11-36 AIR CONDITIONER-ELECTRIC HEATER
UNIT FOR DETAILS.
7. REPLACE GARAGE DOOR OPENERS.
8. THE ABOVE ITEMS SHALL BE INCIDENTAL TO BID ITEM "SHOP IMPROVEMENTS".
9. INSTALL NEW FOUR (4) FOOT LED LIGHTING PANELS WHERE INDICATED IN RED ON
INTERIOR. THIS ITEM SHALL BE PAID UNDER BID ITEM "NEW 4 FOOT LED LIGHTS".
16.00'
4' LED LIGHT
(TYPICAL)
OFFICE
BATHROOM
GARAGE BAY
EXISTING AIR CONDITIONER TO BE
REPLACED WITH NEW HEATING AND
COOLING UNIT (WALL KNOCK OUT
DIMENSIONS TO BE DETERMINED BY
VENDOR)
APPROXIMATE LOCATION
OF 1-PHASE POWER AND
METER FOR BUILDING
NEW LED 100 WATT
CREE UTILITY LIGHTS
(TYPICAL)
F&M EXISTING SHOP UPGRADES
TOTAL
SHT. NO.
OFFICE OF SPECIAL RECLAMATION
SCALE: NTS
47 SCHOOL STREET, SUITE 301
PHILIPPI, WV 26416
OFFICE: 1-304-457-3219
FAX: 1-304-457-5613
Division of Land Restoration Office of Special Reclamation
West Virginia Department of Environmental Protection
DATE: MARCH 2024
F&M COAL COMPANY
PERMIT # S-1073-86
PRESTON COUNTY, WEST VIRGINIA
| Sheet 1-TITLE PAGE |
| Sheets and Views |
| TITLE PAGE |
| SHEET 02 SUMMARY OF QUANTITIES |
| SHEET 3 CONTROL BUILDING ELEVATIONS NORTH AND SOUTH |
| SHEET 04 CONTROL BUILDING ELEVATIONS EAST AND WEST |
| SHEET 05 CONTROL BUILDING ROOF PLAN VIEW DETAIL |
| SHEET 06 PUMP BUILDING |
| SHEET 07 F&M EXISTING SHOP UPGRADES |