APPENDIX M - Peabody District Court - YORK Y23 Rooftop Unit O M Manual.pdf
PDF 6 MB Posted
- Solicitation number
- BD-27-1107-FREG5-ACCOU-133133
- Issued by
- Massachusetts
About this file
This document is an installation and operation manual for the YORK Millennium Model Y22/Y23/Y24 rooftop units included as Appendix M to the Massachusetts Trial Court Region 3 Chiller Service Agreement Request for Proposals (RFP). The RFP covers preventive maintenance and repair services for chiller and associated HVAC equipment at court facilities within Region 3 of the Massachusetts Trial Court system under the purview of the Commonwealth of Massachusetts. The specific unit detailed in this appendix is the YORK Y23 Rooftop Unit installed at the Peabody District Court. These single-package cooling or cooling-with-heating units are designed exclusively for outdoor rooftop installation in non-residential applications and are available in 25, 30, and 40-ton capacities. The units feature scroll compressors (ranging from 2 to 4 units depending on size), forward-curve or air foil indoor fan options (7.5 to 25 horsepower), and optional heating configurations including gas furnace (233 to 699 MBH), electric heat (40 to 108 kW), hot water, or steam heating. The manual serves as technical reference documentation for installation, startup, operation, maintenance, and troubleshooting of the equipment included in the service agreement scope.
The manual provides comprehensive electrical data across multiple voltage configurations (208/230, 460, and 575 volts, 3-phase, 60 Hz) with detailed tables specifying running load amperage (RLA), locked rotor amperage (LRA), full load amperage (FLA), minimum circuit amperage (MCA), and maximum overcurrent protection device ratings for various combinations of compressors, condenser fan motors, supply air motors, and optional electric heating elements. Refrigerant charge specifications are provided by system and capacity with R22 refrigerant charged at the factory. The document includes fan performance data across operating CFM ranges of 6,000 to 15,000 CFM for the 30-ton unit at external static pressures from 0.2 to 4.0 inches of water gauge, along with altitude and temperature correction factors for installations at elevations exceeding 1,000 feet above sea level. Installation requirements mandate compliance with National Electrical Code (ANSI/NFPA 70), National Fuel Gas Code (ANSI Z223.1), and local building codes, with specific attention to gas piping sizing, combustion air quality, vent hood installation, condensate drainage, and field wiring connections. The manual emphasizes that only trained and qualified service personnel should perform installation, repair, and service operations beyond basic maintenance functions such as filter replacement and coil cleaning.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MASSACHUSETTS TRIAL COURT | REGION 3 CHILLER
SERVICE AGREEMENT
Region 3 Chiller Service Agreement RFP | Page 23 of 30
COMMONWEALTH OF MASSACHUSETTS
MASSACHUSETTS TRIAL COURT
REQUEST FOR PROPOSALS
Region 3 Chiller and Associated HVAC Equipment Preventive Maintenance and Repair Service Agreement
APPENDIX M
Peabody District Court - YORK Y23 Rooftop Unit O&M Manual
This appendix is incorporated by reference into the Region 3 Chiller Service Agreement Request for Proposals.
Facilities Management & Capital Planning
CONTENTS
NOMENCLATURE
GENERAL
SAFETY CONSIDERATIONS
INSTALLATION
GAS HEATING
START-UP
GAS FURNACE OPERATING INSTRUCTIONS. . . 68
MILLENNIUM SEQUENCE OF OPERATION
TROUBLESHOOTING A MILLENNIUM SIMPLICITY
CONTROL
THE MILLENNIUM SIMPLICITY CONTROL
SIMPLICITY PROGRAMMING OPTIONS
SETTABLE SYSTEM PARAMETERS
SERVICE
MAINTENANCE
See the following pages for a complete Table of Contents.
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.
INSTALLATION
MANUAL
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
MILLENNIUM™ ROOFTOP
25, 30 & 40 TON
102777-YIM-E-0206
MODELS: Y22
Y23
Y24
102777-YIM-E-0206
2 Unitary Products Group
TABLE OF CONTENTS
NOMENCLATURE
GENERAL
SAFETY CONSIDERATIONS
NOTES, CAUTIONS AND WARNINGS
GAS FIRED MODELS
WHAT TO DO IF YOU SMELL GAS
ALL MODELS
INSPECTION
REFERENCE
APPROVALS
INSTALLATION
LIMITATIONS
LOCATION
RIGGING AND HANDLING
CLEARANCES
DUCTWORK
AIR HOODS FOR FIXED OUTSIDE AIR
(UNITS WITHOUT ECONOMIZER)
AIR HOODS FOR ECONOMIZER
AIR HOODS FOR EXHAUST AIR
CONDENSATE DRAIN
SERVICE ACCESS
COMPRESSORS
FILTERS
THERMOSTAT (CONSTANT VOLUME UNITS)
SPACE SENSOR (VARIABLE AIR VOLUME UNITS). . . 14
POWER AND CONTROL WIRING
POWER WIRING DETAIL
ERV
GAS HEATING
GAS PIPING
GAS CONNECTION
VENT AND COMBUSTION AIR
233 & 466 MBH HEAT
699 MBH HEAT
ELECTRIC HEAT
HOT WATER HEAT
PIPING CONNECTIONS
STEAM HEAT
PIPING CONNECTIONS
STATIC PRESSURE CONTROL PLASTIC TUBING . . . 20
EXHAUST STATIC PRESSURE
CFM, STATIC PRESSURE, AND POWER - ALTITUDE
AND TEMPERATURE CORRECTIONS
START-UP
COMPRESSOR ROTATION
SUPPLY AIR FAN INSTRUCTIONS
CHECK BLOWER BEARING SET SCREWS
CHECKING SUPPLY AIR CFM
FAN ROTATION
BELT TENSION
AIR BALANCE
CHECKING AIR QUANTITY
SUPPLY AIR DRIVE ADJUSTMENT
SYSTEM SETPOINTS
CONSTANT VOLUME AND VARIABLE AIR VOLUME:
GAS FURNACE OPERATING
INSTRUCTIONS
TO LIGHT THE MAIN BURNERS
TO SHUT DOWN
POST-START CHECKLIST (GAS)
MANIFOLD GAS PRESSURE ADJUSTMENT
BURNER INSTRUCTIONS
ADJUSTMENT OF TEMPERATURE RISE
CHECKING GAS INPUT
NATURAL GAS
ELECTRIC HEATING
COOLING OPERATING INSTRUCTIONS
COMPRESSOR
INTERNAL WIRING
CONDENSER FANS
MILLENNIUM SEQUENCE OF OPERATION
OVERVIEW
RUN SEQUENCE
UNIT CONTROLS SEQUENCE
VARIABLE AIR VOLUME UNIT (VFD & IGV)
OVERVIEW
OCCUPIED / UNOCCUPIED / MORNING WARM-UP . . 73
OCCUPIED
UNOCCUPIED
MORNING WARM-UP [MWUP]
UNIT CONTROLS
HEAD PRESSURE CONTROL
DESCRIPTION
SEQUENCE OF OPERATION - FOR HEAD PRESSURE
CONTROL
INTELLI-START
LEAD LAG
DEVICES AND RULES
AIR PROVING SWITCH
FAN DELAYS:
COMFORT VENTILATION MODE
ECONOMIZER CONTROL DURING COMFORT
VENTILATION
STAGING CONTROL DURING COMFORT VENTILATION. . 79
HYDRONIC HEAT
COOLING LOCKOUT ON OAT
WATER COIL FREEZE STAT (FSI)
CV OPERATION
THERMOSTAT OPERATION FOR COOLING WITH Y1,
Y2, Y3 AND Y4 INPUTS
GROUPING COMPRESSORS INTO STAGES
ECONOMIZER MODE
Unitary Products Group 3
OPERATION FOR HEATING WITH W1, W2, AND W3
INPUTS
SUPPLY FAN OFF DELAY
HEAT STAGE DELAYS
THERMOSTAT OPERATION WITH HYDRONIC HEAT
SENSOR OPERATION
TYPES OF SPACE SENSORS
SUPPLY FAN CONTROL WHEN USING A ZONE SENSOR . 82
SUPPLY FAN OFF DELAY
CONTROL OF COMPRESSORS WHEN USING A ZONE
SENSOR
HEATING OPERATION WITH THE SENSOR OPTION
COOLING OPERATION WITH THE SENSOR OPTION
VAV OPERATION
VAV OPERATION WITH A THERMOSTAT
VAV OPERATION WITH A ZONE SENSOR
STANDALONE VAV OPERATION
SUPPLY FAN OFF DELAY
OCCUPIED HEATING WITH A THERMOSTAT
UNOCCUPIED HEATING WITH A THERMOSTAT
OCCUPIED COOLING WITH A THERMOSTAT
UNOCCUPIED COOLING WITH A THERMOSTAT
OCCUPIED HEATING WITH A SPACE SENSOR
UNOCCUPIED HEATING WITH A SPACE SENSOR
OCCUPIED COOLING WITH A SPACE SENSOR
UNOCCUPIED COOLING WITH A SPACE SENSOR
UNOCCUPIED HEATING IN STANDALONE OPERATION . . 85
OCCUPIED COOLING IN STANDALONE OPERATION
SUPPLY DUCT PRESSURE CONTROL ALGORITHM . 85
MORNING WARM UP / VAV OCCUPIED HEATING
CONTROL ALGORITHM
STARTING MORNING WARM UP
MORNING WARM UP / VAV OCCUPIED HEATING
FUNCTION
UNOCCUPIED VAV HEATING / COOLING CONTROL
ALGORITHM WITH A SPACE SENSOR
OCCUPIED VAV HEATING / COOLING CONTROL
ALGORITHM WITH A SPACE SENSOR
CONTROLLING EXCESSIVE SAT (SUPPLY AIR
TEMPERATURE)
SAT CONTROL CONFIGURATION
SAT CONTROL FOR COOLING
ECONOMIZER LOADING OPERATION DURING AN
EXCESSIVE SAT FOR COOLING:
CV ECONOMIZER OPERATION
SAT SETPOINTS USED DURING COOLING WITH
ECONOMIZER OPERATION
DEMAND VENTILATION
EXHAUST OPERATION
TWO-POSITION CONTROL (NON MODULATING POWER
EXHAUST)
PROPORTIONAL CONTROL (FAN WITH MODULATING
EXHAUST AIR DAMPER (EAD) CONTROLLED FROM
BUILDING STATIC PRESSURE)
PROPORTIONAL CONTROL WITH VFD FAN
TWO-POSITION CONTROL (POWER EXHAUST WITH
BAROMETRIC RELIEF, CONTROLLED FROM BUILDING
STATIC PRESSURE)
ERV
SCHEDULING OPERATION
COMPRESSOR STATUS MONITORING
TROUBLESHOOTING A MILLENNIUM SIMPLICITY
CONTROL
STATUS LED CHART
FAILURE MODES AND DEFAULT OPERATION
ERROR HISTORIES
SENSOR FAILURES AND DEFAULT OPERATION . . . 95
SAT SENSOR
RAT SENSOR
OAT SENSOR
OUTSIDE AIR RELATIVE HUMIDITY SENSOR
RETURN AIR RELATIVE HUMIDITY SENSOR
SPACE TEMPERATURE SENSOR
BUILDING PRESSURE SENSOR
DUCT STATIC PRESSURE SENSOR
IAQ SENSOR
SYSTEM ERRORS
HEATING SAT FAILURE
COOLING SAT FAILURE
SUPPLY FAN FAILURE
COMPRESSOR SAFETY CHAIN TRIP
DIRTY FILTER ALARM
HIGH DUCT STATIC ALARM
HOT WATER COIL FREEZE ALARM
THE MILLENNIUM SIMPLICITY CONTROL
INTRODUCTION AND OVERVIEW
DIAGNOSTICS VIA LED
ERROR HISTORY
DIGITAL LINGO
THE PI ALGORITHM
ANALOG TO DIGITAL CONVERTER
SOFTWARE TERMINOLOGY
COMMUNICATIONS BUS
OPTIONAL MODLINC TRANSLATOR
OVERVIEW
COMPONENT DESCRIPTION
THE SIMPLICITY CONTROLLER
WIRING AND TERMINATION, COMMUNICATIONS
COMMUNICATION ADDRESS:
ACRONYMS
INPUTS
ANALOG INPUTS (AI):
BINARY INPUTS (BI):
OUTPUTS
BINARY OUTPUTS (BO)
H1-3 - HEAT STAGES 1 TO 3 [OPTIONAL]
SIMPLICITY PROGRAMMING OPTIONS
INTERACTING THROUGH THE MILLENNIUM
SIMPLICITY
SET THE CLOCK
PARAMETER SETTING
INITIAL STARTUP OPTIONS
METRIC OPERATION (ENGLISH)
4 Unitary Products Group
SETTABLE SYSTEM PARAMETERS
SERVICE
REFRIGERATION SYSTEM
COMPRESSORS
MOTORS
INDOOR BLOWER MOTORS
POWER EXHAUST OR RETURN AIR FAN MOTORS
CONDENSER FAN MOTORS
DRAFT MOTOR (GAS FURNACE)
GAS FURNACE SAFETY FEATURES
COMBUSTION AIR PROVING
ROLLOUT
MAINTENANCE
NORMAL MAINTENANCE
FILTERS
MOTORS
FAN DRIVES
OUTDOOR COIL
GAS BURNER
TO CLEAN BURNERS
COMBUSTION AIR DISCHARGE
CLEANING FLUE PASSAGES AND HEATING ELEMENTS. 132
SECURE OWNERS APPROVAL
LIST OF FIGURES
Fig. # Pg. #
1 COMPONENT LOCATION
2 TYPICAL RIGGING
3 CENTER OF GRAVITY
4 RECOMMENDED DRAIN PIPING
5 TYPICAL THERMOSTAT WIRING
6 TYPICAL GAS PIPING CONNECTION
7 VENT AND COMBUSTION AIR HOODS
8 699 MBH HEAT VENT
9 FLUE EXTENSION
10 CLEARANCES
11 HOT WATER PIPING CROSS-SECTION
12 STEAM PIPING CROSS-SECTION
13 BOTTOM SUPPLY AND RETURN
14 END RETURN, BOTTOM SUPPLY
15 BOTTOM RETURN, FRONT & REAR SUPPLY
16 END RETURN, FRONT & REAR SUPPLY
17 FIELD INSTALLED DISCONNECT
18 PARTIAL ROOF CURB MODEL 1RC0455P
19 FULL ROOF CURB MODEL 1RC0455F
20 ALTITUDE/TEMPERATURE CONVERSION FACTOR 47
21 FAN PERFORMANCE - 25 TON
22 FAN PERFORMANCE - 30 TON
23 FAN PERFORMANCE - 40 TON
24 POWER EXHAUST - ONE FORWARD CURVE FAN -
25 TONS
25 POWER EXHAUST - TWO FORWARD CURVED FANS -
30 & 40 TONS
26 BELT TENSION ADJUSTMENT
27 TYPICAL GAS VALVE
28 TYPICAL FLAME APPEARANCE
29 COMFORT VENTILATION ECONOMIZER
CONTROL
30 SAT CONTROL BAND
31 SIMPLICITY CONTROLLER
32 SIMPLICITY CONTROLS PUSH BUTTONS
33 ANALOG TO DIGITAL CONVERTER
34 VFD CONTROL WIRING
35 SEQUENCE OF SETTING THE SET POINTS
36 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 10 GPM
37 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 20 GPM
38 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 30 GPM
39 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 40 GPM
40 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 60 GPM
41 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 80 GPM
42 HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM . 121
43 HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM . 121
44 HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM . 122
45 HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM . 122
46 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM . 123
47 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM . 123
48 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM . 124
49 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM . 124
50 STEAM COIL - 25 & 30 TON (1 ROW)
51 STEAM COIL - 40 TON (1 ROW)
52 TYPICAL CONTROL WIRING
53 LEGEND
54 TYPICAL 25 TON POWER WIRING
55 TYPICAL 30/40 TON POWER WIRING
56 TYPICAL GAS HEAT WIRING
57 TYPICAL FLUE BAFFLE
58 25 TON CHARGING CURVE
59 30 TON CHARGING CURVE
60 40 TON CHARGING CURVE
61 PRESSURE DROP DRY EVAPORATOR COIL VS
SUPPLY AIR CFM - 25 TON
62 PRESSURE DROP DRY EVAPORATOR COIL VS
SUPPLY AIR CFM - 30 & 40 TON
Unitary Products Group 5
LIST OF TABLES
Tbl. # Pg. #
1 COOLING & ELECTRICAL APPLICATION
2 COOLING & ELEC. APP. LIMITATIONS
3 GAS APPLICATION DATA
4 UNIT WEIGHTS
5 SUPPLY FAN MOTOR VFD WEIGHTS
6 EXHAUST FAN MOTOR VFD WEIGHTS
7 UNIT CORNERWEIGHT
8 UNIT CENTER OF GRAVITY
9 CONTROL WIRE SIZES
10 PIPE SIZES
11 GENERAL PHYSICAL DATA
12 REFRIGERANT CHARGE
13 ELECTRICAL DATA BASIC UNIT - 25 TON
14 ELECTRICAL DATA BASIC UNIT - 30 TON
15 ELECTRICAL DATA BASIC UNIT - 40 TON
16 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC
HEAT - 25 TON
17 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC
HEAT - 30 TON
18 ELECTRICAL DATA BASIC UNIT WITH ELECTRIC
HEAT - 40 TON
19 ELECTRICAL DATA BASIC UNIT WITH POWER
EXHAUST - 25 TON
20 ELECTRICAL DATA BASIC UNIT WITH POWER
EXHAUST - 30 TON
21 ELECTRICAL DATA BASIC UNIT WITH POWER
EXHAUST - 40 TON
22 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST
& ELECTRIC HEAT - 25 TON
23 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST
& ELECTRIC HEAT - 30 TON
24 ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST
& ELECTRIC HEAT - 40 TON
25 ALTITUDE CORRECTION FACTORS
26 FAN PERFORMANCE - 25 TON
27 FAN PERFORMANCE - 30 TON
28 FAN PERFORMANCE - 40 TON
29 COMPONENT STATIC RESISTANCE
30 SUPPLY FAN MOTOR AND DRIVE DATA
31 EXHAUST FAN DRIVE DATA
32 POWER EXHAUST - ONE FORWARD CURVED FAN
25 TON
33 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TON
Tbl. # Pg. #
34 BELT ADJUSTMENT
35 BLOWER SPEED RATE OF CHANGE
36 25 TON DRIVE ADJUSTMENT
37 30 TON DRIVE ADJUSTMENT
38 40 TON DRIVE ADJUSTMENT
39 DRIVE ADJUSTMENT FOR POWER EXHAUST -
25 TON
40 DRIVE ADJUSTMENT FOR POWER EXHAUST -
30 & 40 TON
41 GAS RATE - CUBIC FEET PER HOUR
42 COOLING STAGE
43 COMPRESSOR MINIMUM OFF TIMES
44 WEEKLY SCHEDULE
45 HOLIDAY SCHEDULE
46 ALARM DEFAULT CODES
47 STATUS LED CHART
48 ACRONYMS
49 INPUT SIGNAL TO Y1 ACTUATOR POSITION
50 SIMPLICITY CONTROL INPUTS
51 SIMPLICITY CONTROL OUTPUTS
52 SETTABLE SYSTEM PARAMETERS
53 SYSTEM MOISTURE INDICATOR
54 STEAM COIL (1 ROW, 25 & 30 TON)
55 STEAM COIL (1 ROW, 40 TON)
56 STATIC RESISTANCE STEAM COIL
(25 & 30 TON)
57 STATIC RESISTANCE STEAM COIL (40 TON)
58 HOT WATER COIL (1 ROW 25 & 30 TON)
59 HOT WATER COIL (1 ROW, 40 TON)
60 WATER PRESSURE DROP (1 ROW,
25 & 30 TON)
61 WATER PRESSURE DROP (1 ROW, 40 TONS) . . . 116
62 HOT WATER COIL (2 ROW, 25 & 30 TON)
63 WATER PRESSURE DROP (2 ROW,
25 & 30 TON)
64 WATER PRESSURE DROP (2 ROW, 40 TON)
65 STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
66 STATIC RESISTANCE HOT WATER COIL
(40 TON)
67 INDOOR BLOWER BEARING LUBRICATION
SCHEDULE
6 Unitary Products Group
NOMENCLATURE
Unitary Products Group 7
FIGURE 1 - COMPONENT LOCATION
FILTER ACCESS
EVAPORATOR COIL
AND DRAINPAN ACCESS
POWER & CONTROL WIRING
COMPRESSOR ACCESS
HEAT SECTION
POWER EXHAUST ACCESS
FILTER ACCESS
EVAPORATOR COIL
AND DRAINPAN ACCESS
HEAT SECTION
SUPPLY BLOWER & MOTOR
FILTER DRIERS
RIGHT
SIDE
LEFT SIDE
FRONT
REAR
REAR
8 Unitary Products Group
GENERAL
YORK Model Y22/Y23/Y24 units are single package cooling only or cooling with gas, electric, hot water or steam heating designed for outdoor installation on a rooftop and for non-res-idential use.
The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electri-cal wiring is factory installed and tested. The units require electric power, gas, steam, or hot water connections and duct connections. Gas fired units also require installation of a flue gas outlet hood.
SAFETY CONSIDERATIONS
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if instal-lation procedure is not handled properly.
GAS FIRED MODELS
DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas sup-plier, call the fire department.
ALL MODELS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical compo-nents. Only trained and qualified service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance func-tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel.
When working on air conditioning equipment, observe pre-cautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes, including ANSI Z223.1-Latest Edi-tion: wear safety glasses and work gloves; use quenching cloth for unbrazing operations; have fire extinguisher avail-able for all brazing operations.
INSPECTION
As soon as a unit is received, it should be inspected for possi-ble damage during transit. If damage is evident, the extent of damage should be noted on the carrier’s freight bill. A sepa-rate request for inspection by the carrier’s agent should be made in writing.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping sys-tem during any pressure testing of that system at test pressures in excess of 0.5 psig. Pressures greater than 0.5 will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to a pressure greater than 0.5 psig, it must be replaced. The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pres-sure testing of that system at test pressures equal to or less than 0.5 psig.
This Furnace is not to be used for temporary heat-ing of buildings or structures under construction.
Before performing service or maintenance opera-tions on unit, turn off main power switch to unit.
Electrical shock could cause personal injury.
Improper installation, adjustment, alteration, ser-vice or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
Unitary Products Group 9
REFERENCE
Additional information is available in the following reference forms:
• 036-21091-004 - Technical Guide
• TBD - Unit Replacement Parts List (25, 30 & 40 Tons)
APPROVALS
Designed certified by CGA, ETL, CETL as follows:
1. For use as a forced air furnace with cooling unit (gas heat models).
2. For outdoor installation only.
3. For installation on combustible material and may be installed directly on combustible flooring or Class A, Class B or Class C roof covering materials.
4. For use with natural gas (convertible to LP with kit).
Not suitable for use with conventional venting systems.
INSTALLATION
LIMITATIONS
The installation of this unit must conform to local building codes, or in the absence of local codes, with ANSI Z223.1 Natural Fuel Gas Code and /or CAN/CGA B149 installation codes.
In U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70-Latest Edi-tion.
2. National Fuel Gas Code Z223.1-Latest Edition.
3. Gas-Fired Central Furnace Standard ANSI Z21.47-Lat-est Edition.
4. Local gas utility requirements.
Refer to Table 1 for Cooling and Electrical Application Data and to Table 2 for Gas Heat Application Data.
After installation, gas fired units must be adjusted to obtain a temperature rise within the range specified on the unit rating plate.
If components are to be added to a unit to meet local codes, they are to be installed at the contractor's and/or the cus-tomer's expense.
Size of unit for proposed installation should be based on heat loss / heat gain calculation made according to the methods of the Air Conditioning Contractors of America (ACCA).
LOCATION
Use the following guidelines to select a suitable location for these units:
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on either north or east side of building.
3. Suitable for roof mount on curb.
4. Roof structures must be able to support the weight of the unit and its accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.
5. Maintain level tolerance to 3/4 inches across width and 2 inches along length.
TABLE 1: COOLING & ELECTRICAL APPLICATION
UNIT POWER
SUPPLY
VOLTAGE VARIATIONS
MIN. VOLTS MAX VOLTS
575-3-60 540 630
208/230-3-60 187 252
460-3-60 432 504
TABLE 2: COOLING & ELEC. APP. LIMITATIONS
LIMITATIONS
MODEL
Y22 Y23 Y24
Supply Air CFM (min./max)
6,000- 12,5000
6,000- 15,000
8,000- 20,000
Entering Wet Bulb Temp (F°) (min./max) 57/75 57/75 57/75
Ambient Temp 40/120 40/120 40/120
Min. Air Temperature on Gas Fired Heat Exchangers (°F)
Aluminized 25 25 25
Stainless 0 0 0
10 Unitary Products Group
TABLE 3: GAS APPLICATION DATA
INPUT CAPACITY (MBH)
AVAILABLE
ON
MODELS
GAS
RATE1
(FT.3/HR.)
TEMP. RISE °F
AT FULL INPUT2 30 TO 2,000 FEET ABOVE
SEA LEVEL
3,000 FEET ABOVE
SEA LEVEL4
4,000 FEET ABOVE
SEA LEVEL4
MAX. MIN. MAX. MIN. MAX. MIN. MIN. MAX.
233 233 205 205 196 196 Y22, Y23, Y24 217 5 35
466 233 410 205 392 196 Y22, Y23, Y24 434 15 45
6995 233 615 205 587 196 Y24 650 20 50
1. Based on maximum input and 1075 Btu/Ft.3
2. The air flow must be adjusted to obtain a temperature rise within the range shown.
3. On VAV units, individual room damper boxes must go full open in heating mode to ensure airflow falls within temperature rise range.
4. For operation at elevations above 2,000 feet and, in the absence of specific recommendations from local authority having jurisdic-tion, equipment ratings shall be reduced at the rate of 4% for each 1,000 feet above sea level.
5. Minimum heating CFM for 699 MBH input heat is 11,700 CFM.
If a unit is to be installed on a roof curb other than a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit under-side.
If a unit is to be installed on an angle iron frame it is recommended that it be sized to allow the bot-tom rail to overhang to facilitate installation of con-densate drains (see Fig. 4).
FIGURE 2 - TYPICAL RIGGING
CABLES
SPREADER BARS
(3 PLACES)
20"
A
B
C
UNIT
UNIT
WEIGHT
(LB)
LIFTING LUG DIMENSIONS
A B C
25 TON
30 TON
40 TON
SEE NOTE 5
SEE NOTE 5
SEE NOTE 5
8' 4"
8' 4"
8' 4" 6' 9"
6' 9"
6' 9"
2' 3"
2' 3"
2' 3"
RIGGING:
1) RIG WITH 6 CABLES, THREE SPREADER BARS - 95" ACROSS WIDTH AND
SPREADER BARS OF LENGTH EQUAL TO "A + B".
2) CENTER OF GRAVITY INCLUDES ECONOMIZER, POWER EXHAUST AND
INLET GUIDE VANES.
3) CAUTION: ALL PANELS MUST BE SECURED IN PLACE WHEN THE UNIT
IS LIFTED.
4) CAUTION: THE CONDENSER COIL SHOULD BE PROTECTED FROM DAMAGE BY
THE RIGGING CABLES WITH PLYWOOD OR OTHER SUITABLE MATERIALS.
5) REFER TO INSTALLATION INSTRUCTIONS.
NOTICE TO RIGGERS
Unitary Products Group 11
NOTE: If the Millennium is VAV with ERV, add the weight of an exhaust VFD - it will be in the unit.
TABLE 4: UNIT WEIGHTS
COMPONENT 25 TON 30 TON 40 TON
Basic Unit 4350 4550 4950 Gas Heat
233 MBH 180 180 180
466 MBH 320 320 320
700 MBH - - 450
Electric Heat
40KW 40 40 40
80KW 105 105 105
108KW 110 110 110
Hot Water Heat
1 Row Coil 70 70 70 2 Row Coil 85 85 85
Steam Heat 1 Row Coil 85 85 85
Blower Forward Curve Fan (Std Fan) 0 0 0
FC IGV 155 155 175
Air Foil Fan 135 135 155
AF IGV 155 155 180
Motor - Supply Fan
7.5hp 110 - - 10hp 145 145 145 15hp 200 200 200 20hp 240 240 240 25hp - 300 300
Supply Fan Motor VFD See Table 5 Refrigeration
Hi Cap. Evap. Coil - 50 15 T-Coat Evap. 32 30 40 T-Coat cond. 32 30 40
Hot Gas Bypass 10 10 10 Low Ambient Head Pressure Control
208-230/380/460 5 5 5 575 25 25 25
Filters 6" Rigid 70 70 70
Exhaust1
1. If ERV and Supply Fan VAV are selected, add the weight of an Exhaust VFD, Table 5.
Exhaust Type Barometric 45 65 65 Modulated 140 275 275
Exhaust Motor 5hp 80 80 80
7.5hp 110 110 110 10hp 145 145 145 15hp 200 200 200
Exhaust Motor VFD See Table 6 Economizer
Std. Econ. 235 235 235 Econ. w/ERV 50 50 50
Control Disconnect 15 15 15 110V outlet 55 55 55 Optilogic 20 20 20
Roof Curb Partial Curb 415 415 415
Full Curb 615 615 615
TABLE 5: SUPPLY FAN MOTOR VFD WEIGHTS
Supply Fan Motor VFD 230V 460V 575V
W/O Bypass
7.5hp 60 25 30
10hp 60 25 30
15hp 75 50 60
20hp 75 50 60
25hp 115 50 60
W/Bypass
7.5hp 155 90 120
10hp 155 90 120
15hp 185 140 155
20hp 185 140 155
25hp 255 140 155
TABLE 6: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor 230V 460V 575V
W/O Bypass
5hp 15 10 20
7.5hp 50 15 20
10hp 50 15 20
15hp 65 40 50
25hp 255 140 155
FIGURE 3 - CENTER OF GRAVITY1
1. Refer to Tables 7 and 8 for A, B, C, D and X and Y data respectively.
All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from dam-age by the rigging cables with plywood or other suit-able material.
An adhesive backed cover is provided over the out-side of the combustion air inlet opening on gas fired units to prevent moisture from entering the unit which could cause damage to electrical compo-nents. Allow this closure label to remain in place until the combustion air hood is to be installed (Refer to Figures 7, 8, & 9).
RIGHT SIDE
C�E�N�T�E�R��O�F�� G�R�A�V�I�T�Y�
C�O�N�D�E�N�S�E�R� C�O�I�L��E�N�D�
LEFT SIDE
X�
Y�
8�3�"�
2�4�0�"�
A�
B�
C�
D�
12 Unitary Products Group
RIGGING AND HANDLING
This unit is not designed to be handled with a fork-truck.
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the holes pro-vided in lifting lugs. Spreaders MUST be used across the top of the unit. Refer to Figure 2.
• Rig with six cables and spread with four 95-inch spread-ers across width and two spreaders of length equal to A + B.
• Refer to Tables 4 and 7 for unit weight.
• Center of gravity includes economizer, exhaust or return air fan and inlet guide vanes (Refer to Table 8).
NOTES: Basic Unit = cooling only, 10hp FC fan.
+ Econ = +235lb + Heat = single stage gas, 180 lb + Power Exhaust = modulating 7.5hp
CLEARANCES
All units require certain clearances for proper operation and service. Installer must make provisions for adequate combus-tion and ventilation air in accordance with section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 installation codes-Latest Edition and/or applicable provisions of the local building codes. Refer to Figure 10 for clearances required for combustible construction, servicing, and proper unit operation.
TABLE 7: UNIT CORNERWEIGHT
UNIT
DESCRIPTION
25 TON 30 TON 40 TON
A B C D A B C D A B C D
Basic Unit 1033 1033 1215 1215 1079 1053 1269 1294 1131 1131 1417 1417
Basic Unit With Economizer 1112 1112 1253 1253 1185 1157 1280 1308 1205 1205 1460 1460
Basic Unit With Economizer and
Gas or Electric Heat 1162 1162 1293 1293 1209 1155 1346 1400 1255 1224 1500 1531
Basic Unit With Economizer and
Gas or Electric Heat and Power Exhaust
1284 1284 1296 1296 1359 1298 1389 1449 1416 1384 1532 1563
TABLE 8: UNIT CENTER OF GRAVITY
MODEL
25 TON 30 TON 40 TON
X Y X Y X Y
Basic Unit 99” 46” 98” 45” 93” 46"
Basic Unit With Econ. 110” 46” 108” 45” 97” 46"
Basic Unit With Econ. & Gas or
Elect. Heat, Steam or Hot Water Heat
104” 45” 102” 44” 96” 45"
Basic Unit With Econ. & Gas or Elect. Heat, &
Power Exhaust
118” 45” 112” 44” 108” 45"
(COOLING OPERATION) Do not permit overhang-ing structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent out-lets.
Unitary Products Group 13
DUCTWORK
Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).
A closed return duct system should be used. This will not pre-clude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise.
When the unit is equipped with power exhaust fans or return air fan the return duct should have a 90 elbow before opening to the building space to abate noise.
The supply and return air duct systems should be designed for the CFM and static pressure requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit.
If the unit is equipped with hot water or steam heat then the supply air direction will be down only.
AIR HOODS FOR FIXED OUTSIDE AIR
(UNITS WITHOUT ECONOMIZER)
These hoods are factory installed. The dampers may be adjusted by loosening the thumb screw, turning the lever to the desired position, and retightening the thumb screw.
AIR HOODS FOR ECONOMIZER
There are (3) economizer outside air intake hoods provided with the unit. The hood on the end of the unit is factory mounted. The (2) front and rear hoods are made operational per the following instructions.
Remove the screws holding the economizer hood shipping covers in place. Discard covers.
Rotate the hoods out (each hood is hinged in the lower cor-ner). Secure the hoods with screws along the top and sides.
Apply a bead of RTV sealer along the edge of both hoods and each pivot joint to prevent water leakage.
Seal any unused screw holes with RTV or by replacing the screw.
AIR HOODS FOR EXHAUST AIR
When furnished, these hoods and dampers are factory installed.
CONDENSATE DRAIN
There is one condensate drain connection. Trap the connec-tion per Figure 4. The trap and drain lines should be pro-tected from freezing.
Plumbing must conform to local codes. Use a sealing com-pound on male pipe threads. Install condensate drain lines from the 1-1/2 inch NPT female connections on the unit to an open drain.
(GAS HEATING OPERATION)
Excessive exposure to contaminated combustion air will result in safety and performance related problems. To maintain combustion air quality, the recommended source of combustion air is the out-door air supply.
The outdoor air supplied for combustion should be free from contaminants due to chemical exposure that may be present from the following sources:
• Commercial buildings
• Indoor pools
• Laundry rooms
• Hobby or craft rooms
• Chemical storage areas
The following substances should be avoided to maintain outdoor combustion air quality:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool cleaners
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
14 Unitary Products Group
SERVICE ACCESS
Access to all serviceable components is provided by the fol-lowing hinged doors:
• Furnace compartment
• Supply Air Fan compartment Evaporator Coil compart-ment (three doors)
• Filter compartment economizer compartment (two doors)
• Power Exhaust compartment (two doors)
• Main control panels (one door)
Refer to Figure 1 for location of these access panels.
COMPRESSORS
Units are shipped with compressor mountings factory-adjusted and ready for operation.
FILTERS
Throwaway or rigid filters are supplied with each unit. Filters must always be installed ahead of evaporator coil and must be kept clean or replaced with same size and type. Dirty fil-ters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Required filter sizes are shown in Table 11. The unit should not be operated without filters properly installed.
THERMOSTAT (CONSTANT VOLUME UNITS)
The thermostat, if used, should be located on an inside wall approximately 56 inches above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with sensor for general installation procedure (See Figure 5).
Refer to Table 9 for control wire sizing and maximum length.
SPACE SENSOR (VARIABLE AIR VOLUME UNITS)
The space sensor, if used, should be located on an inside wall approximately 56 inch above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with sensor for general installation procedure.
FIGURE 4 - RECOMMENDED DRAIN PIPING
Make sure that all screws and panel latches are replaced and properly positioned on the unit to maintain an air-tight seal.
DO NOT loosen compressor mounting bolts.
| � | � | |
| � | � | � |
FIGURE 5 - TYPICAL THERMOSTAT WIRING
TABLE 9: CONTROL WIRE SIZES
WIRE SIZE MAXIMUM LENGTH
20 AWG 100 Feet
18 AWG 150 Feet
Unitary Products Group 15
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of National Electrical Code (NEC) ANSI / NFPA 70-Latest Edition and / or local ordinances. The unit must be electrically grounded in accordance with the NEC and / or local codes. Voltage toler-ances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an integral part of the design certified unit. Field alteration to comply with electrical codes should not be required. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire.
Power supply to the unit must be NEC Class 1 and must comply with all applicable codes. A disconnect switch must be provided (factory option available). The switch must be separate from all other circuits. Wire entry at knockout open-ings requires conduit fittings to comply with NEC and/or Local Codes. Refer to Figures 13, 14, 15, and 16 for installation location of openings.
If installing a field mounted disconnect on the unit, refer to Figure 17 for the recommended mounting location. Unit-strutTM or equivalent rails should be mounted as shown to provide structure for mounting. The location of the rails should be adjusted to fit the disconnect within the dimensions shown. Conduit run from the disconnect to the power entry location in the baserail should be routed so that it does not interfere with the doors of the unit access panels.
NOTE: Since not all local codes allow the mounting of a dis-connect on the unit, please confirm compliance with local code before mounting a disconnect on the unit.
Electrical wiring must be sized properly to carry the load.
Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Refer to Figure 5 for typical field wiring and to the appropriate unit wiring diagram mounted inside control doors for control circuit and power wiring information.
POWER WIRING DETAIL
Units are factory wired for the voltage shown on the unit nameplate. The main power block requires copper wires.
Refer to Electrical Data Tables 13 through 24 to size power wiring, fuses and disconnect switch. All field supplied wiring, fuses and disconnects must comply with applicable NEC codes.
Power wiring is brought into the unit through the side of the baserail or the bottom of the unit/control box inside the curb.
The baserail has a 2-1/2” diameter hole for field wiring and a 3-5/8” hole is provided for a through-the-curb connection. A removable patch plate covers both the openings.
ERV
The ERV [Energy Recovery Ventilation] is a separate air han-dler that attaches to the exhaust end of the 25-40T Millen-nium packaged rooftop unit. The ERV is shipped separately and assembled to the Millennium at the jobsite. An 'ERV' Mil-lennium is shipped with an end configuration and electric hookups designed to mate with the ERV. This option is avail-able only with the Simplicity control, and no other power exhaust option can be supplied if an ERV is selected.
The ERV incorporates a rotating heat exchange wheel and a pair of exhaust blowers. It exhausts return air through the wheel, capturing the thermal energy of the exiting hot or cold air as it passes. As the wheel rotates, the incoming airstream, pulled through by the supply fan, regains that energy.
The Millennium ERV has a terminal block and mating con-nectors to simplify hooking up the two systems. The controls of both units are factory set to interact properly. Power for the ERV blower motors and controls is provided through the Mil-lennium unit. The Millennium /ERV dataplate information includes the ERV electrical load.
The Millennium Simplicity control has parameters for the ERV; ref. the parameter list. When economizer and ERV options are selected on the same unit, the Simplicity control and the ERV have specific connections and internal rules for that operation.
Also refer to the ERV Installation Instructions packaged with the ERV.
Use care to avoid damage when drilling holes for the disconnect mounting.
When connecting electrical power and control wir-ing to the unit, waterproof connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch.
Waterproof connections MUST be used to ensure that water cannot penetrate the roof or roof curb.
16 Unitary Products Group
GAS HEATING
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas and the length of run. National Fuel Gas Code Z223.1-Latest Edition should be followed in all cases unless superseded by local codes or gas company requirements. Refer to Table 10.
The heating value of the gas may differ with locality. The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-ing a minimum diameter for gas piping. All units require a 1-1/4 inch pipe connection at the entrance fitting. Line should not be sized smaller than the entrance fitting size.
GAS CONNECTION
The gas supply line should be routed within the space and penetrate the roof at the gas inlet connection of the unit.
Refer to Fig. 13 -- 16 to locate the access opening. Typical supply piping arrangements are shown in Figure 5.
Gas piping recommendations:
1. A drip leg and a ground joint union must be installed in the gas piping.
2. When required by local codes, a manual shut-off valve will have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only.
4. All piping should be cleaned of dirt and scale by ham-mering on the outside of the pipe and blowing out the loose particles. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under Limitations. After the gas connections have been com-pleted, open the main shutoff valve admitting normal gas pressure to the mains. Check all joints for leaks with
On VAV units with gas fired furnace, ALL INDIVID-
UAL ROOM DAMPER BOXES MUST BE CON-
TROLLED FULL OPEN DURING HEATING
OPERATION TO ENSURE PROPER AIRFLOW
OVER THE FURNACE. A control contact between D1 and D2 on TB3 is provided for the damper box interlock. This contact is normally open, thus is closed during heating operation.
TABLE 10: PIPE SIZES
LENGTH IN
FEET
NOMINAL IRON PIPE, SIZE
1-1/4 IN.1
1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas.
1-1/2 IN.1 2 IN.1
10 1,050 1,600 3,050
20 730 1,100 2,100
30 590 890 1,650
40 - 760 1,450
50 - - 1,270
60 - - 1,150
70 - - 1,050
80 - - 990
FIGURE 6 - TYPICAL GAS PIPING CONNECTION
Natural gas may contain some propane. Propane, being an excellent solvent, will quickly dissolve white lead or most standard commercial com-pounds. Therefore, a special pipe dope must be applied when wrought iron or steel pipe is used.
Shellac base compounds such as Gaskolac or Stalastic, and compounds such as Rectorseal #5, Clyde's or John Crane may be used.
Unitary Products Group 17 soap solution or other material suitable for the purpose.
NEVER USE A FLAME
6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system dur-ing any pressure testing of that system at test pressures in excess of 0.5 psig.
7. A 1/8 inch N.P.T. plugged tapping, accessible for test gage connection, must be installed immediately upstream of the gas supply connection to the furnace.
VENT AND COMBUSTION AIR
NOTE: All the hoods and hardware are shipped within the evaporator section. Each hood must be properly attached to the furnace doors to assure proper operation and compliance with CSA/ETL safety cer-tification. (Refer to Figure 7 and 8)
The products of combustion are discharged horizontally through hooded openings in the gas heat access doors.
233 & 466 MBH HEAT
(Figure 7)
1. Remove the shipping covers that are attached to the heat section door covering the flue outlets.
2. Locate the flue which is shipped in the evaporator sec-tion.
3. Place the flue over the flue outlet with the diverter angles facing up toward the top of the unit and attach with screws provided.
4. Refer to the Gas Furnace Operation Instruction in the Start-up Section of this manual for further instructions.
699 MBH HEAT
(Figure 8)
1. Remove the shipping covers that are attached to the heat section door covering the flue outlets.
2. Locate the flue duct extensions and flue which are shipped between the evaporator and filter section.
Disconnect gas piping from unit when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced.
FIGURE 7 - VENT AND COMBUSTION AIR
HOODS
FIGURE 8 - 699 MBH HEAT VENT
FIGURE 9 - FLUE EXTENSION
18 Unitary Products Group
3. Place the flue extension (Figure 9) on the flue duct of each furnace section and attach with screws provided.
4. Place the flue in position with the diverter angles facing up toward the top of the unit and attach with screws pro-vided.
5. Place the wind shield over the louvers on the right side of the burner access door and attach with screws provided.
6. Refer to the Gas Furnace Operation Instructions in the Start-up Section of this manual for further information.
ELECTRIC HEAT
Units with electric heat are fully wired and operational when shipped. Constant volume units are designed for two equal steps of capacity for 80 and 108 kWH heat; 40 kW heat is one step only. VAV units are one full step at full heat capacity.
HOT WATER HEAT
The YORK Millennium units (25, 30, and 40 Ton sizes) can be furnished with a YORK hot water coil as the heat source. One or two row coil units will be factory installed in the heating section.
NOTE: The hot water control valve will not be provided. The installer will need to purchase a hot water control valve, to connect the hot water piping and power wiring at the job site for the hot water heat section to be operational.
NOTE: For all hot water coils the entering water tempera-ture should not exceed 200°F.
The hot water coil is located downstream of the supply air fan and just above the supply air opening in the bottom of the unit.
Refer to Tables 58 through 66 and Figures 36 through 49 for flow rate and capacity.
FIGURE 10 - CLEARANCES
60"
REAR
60"
FRONT
60"
ENDS
10'
60"
ENDS
REQUIRED CLEARANCES
LEFT
RIGHT
REAR
FRONT
TOP
60" 60" 60" 60" 10'
* Right is the side with access to the Electrical / Gas Controls.
* is the side with the Condenser Coils
NOTE: DONOT use the unit roof to support any type of structure or bracing.
Front
DO NOT use hot water coils as steam coils under any circumstances.
All piping, control valves, and wiring that is field installed must be properly insulated and conform to all local and national codes.
Unitary Products Group 19
PIPING CONNECTIONS
The hot water pipping must enter the unit through the floor of the heat section compartment. The access doors to the com-partment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the space, the piping access holes should be sealed with a heat resistant mastic Figure 11 shows the location of the compart-ment and piping connections.
STEAM HEAT
The YORK Millennium units (25, 30 and 40 Ton sizes) can be furnished with a YORK single row steam coil. YORK steam coils are a factory installed option.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control valve, piping and field installed wiring con-nections are particularly vulnerable because they are installed in the vestibule outside of the condi-tioned air stream. The installing party will be responsible for properly insulating and installing power and control wiring, to the actuator and pip-ing.
In one row hot water coil systems DO NOT exceed a 40 gallons per minute flow rate.
In two row hot water coil systems Do Not exceed a 80 gallons per minute flow rate
Condensate will freeze on the control valve and piping if they are not properly insulated. Insulating the control valve and piping is the responsibility of the installing party.
Piping access holes should be sealed with a heat resistant mastic to prevent damage to equipment.
DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to tenets of the structure that is being conditioned.
FIGURE 11 - HOT WATER PIPING CROSS-SEC-
TION
FIGURE 12 - STEAM PIPING CROSS-SECTION
| � � | � � � ! " |
| � � � � | � � � ! " |
| � | � � � |
| � � |
| � | � � � |
| � � |
20 Unitary Products Group
NOTE: The steam control valve, power and control wiring to the actuator of the valve is the responsibility of the installing party.
PIPING CONNECTIONS
Refer to Tables 54 through 57 and Figures 50 and 51 for flow rate and capacity.
The steam piping must enter the unit through the floor of the heat section compartment. The access doors to the compart-ment are gasketed so the compartment can be sealed. How-ever, as added protection for condensate leakage into the space, the piping access holes should be sealed with a heat resistant mastic. The following figure illustrates the location of the compartment and piping connections.
STATIC PRESSURE CONTROL PLASTIC TUBING
On units with inlet guide vanes (IGV's) and variable fre-quency drives on the supply blower and/or power exhaust fans, pressure sensing tubing must be field supplied and installed from differential pressure switches or transducers to the locations in the building or ductwork where a constant pressure is desired, and to the atmosphere.
The supply air discharge static pressure switch or transducer is located in the blower compartment on the heat section par-tition panel. Plastic tubing (1/4") must be run from the high pressure tap of the transducer to a static pressure tap (field supplied) in the supply duct located at a point where constant pressure is desired. Tubing must also be run between the low pressure tap of the transducer to atmospheric pressure.
EXHAUST STATIC PRESSURE
If a modulating power exhaust is installed, there will be a building pressure sensor (BPS) in the control box directly below the Millennium Simplicity. This ± .25 0-5VDC trans-ducer sends a building pressure signal to the control. A sens-ing tube must be installed from a representative location in the building to the HI power of the transducer.
Changing the adjustment is done to the building pressure parameter in the control.
All piping and control valves, and wiring that is field installed must be properly insulated and con-form to all local and national codes.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control valve, piping and field installed wiring con-nections are particularly vulnerable because they are installed in the vestibule outside of the condi-tioned air stream. The installing party will be responsible for properly insulating and installing power and control wiring, to the actuator and pip-ing.
DO NOT use steam coils as hot water coils under any circumstances.
In steam coil systems, the steam pressure shall not exceed 15 PSI.
Piping access holes should be sealed with a heat resistant mastic to prevent damage to equipment.
DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to tenets of the structure that is being conditioned.
Do not run plastic tubes in the supply or return air ducts as air movement could cause erroneous sensing. If tubes penetrate bottom of unit be sure openings are sealed against air and water leak-age.
Unitary Products Group 21
TABLE 11: GENERAL PHYSICAL DATA
UNIT SIZE 25 TON 30 TON 40 TON
Unit EER 10.0 9.5 9.5
Compressor Data Number/Size 2 x 13 Ton 3 x 10 Ton 4 x 10 Ton
Type Scroll Scroll Scroll Unit Capacity Steps 50%, 100% 33%, 67%, 100% 25%, 50%, 75%, 100%
Indoor Fan and Drive Number / Type 1 / FC 1 / FC 1 / FC
Diameter x Width (inches) 22 x20 22 x 20 25 x 22 HP Range 7.5 - 20 10 - 25 10 - 25
CFM Range (full load) 6,000 - 12,500 6,000 - 15,000 8,000 - 18,000 ESP Range 0.2” - 4.0” 0.2" - 4.0” 0.2" - 4.0"
Exhaust Fan Number/Size/Type 1/FC 2/FC 2/FC
HP Range (single motor) 5 - 10 7.5 - 15 7.5 - 15
CFM 3,000 - 9,000 4,000 - 18,000 4,000 - 18,000
Standard Evaporator Coil Size (sq. ft.) 26.0 26.0 30.4 Rows/FPI 3 / 13 3 / 16 4 / 13
High Capacity Evaporator Coil Size (sq. ft.) 26.0 26.0 30.4 Rows/FPI 3/13 4 / 16 4 / 16
Condenser Coil Size (sq. ft.) 52.0 48.8 65.0 Rows/FPI 2/16 2 /16 2 /16
Condenser Fans Quantity / Diameter (inches) 4 / 24 3 / 24 4 / 24
Nominal CFM 4,600 6,800 6,800 Motor HP 3 / 4 1.0 1.0
Electric Heat kW Range 40 - 108 40 - 108 40 - 108
40 kW Capacity Steps 1 1 1 80 and 108 kW Capacity Steps (CV/VAV) 2 / 1 2 / 1 2 / 1
Natural Gas Heat 233 MBH Capacity Steps (CV/VAV) 1 / 1 1 / 1 1 / 1 466 MBH Capacity Steps (CV/VAV) 2 / 1 2 / 1 2 / 1 699 MBH Capacity Steps (CV/VAV) - 2 / 1 3 / 1
Hot Water Coil Size (inches) 22.5” X 65” 22.5" X 65" 22.5" X 65"
Capacity 25 Ton 30 Ton 40 Ton Steam Coil
Size (inches) 21" X 65" Type Steam Coil
Filters 2" Hi. Eff. TA Number / Size 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
Face Area (sq. Ft.) 30.4 30.4 30.4 Filters 2" Pleated, 65%
Number / Size 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 Face Area (sq. Ft.) 30.4 30.4 30.4
Filters 65% Rigid w/ 2" TA Prefilters Number / Size 4 / 16 x 25 & 6 / 20 x 25 4 /16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
Face Area (sq. Ft.) 30.4 30.4 30.4 Filters 95% Rigid w/ 2" TA Prefilters
Number / Size 4 / 16 x 25 / 6 / 20 x 25 4 / 16 x 25 / 6 / 20 x 25 4 / 16 x 25 / 6 / 20 x 25 Face Area (sq. Ft.) 30.4 30.4 30.4
22 Unitary Products Group
TABLE 12: REFRIGERANT CHARGE
UNIT (TONS) MODEL TYPE FACTORY/ FIELD
CHARGED
CHARGE
SYS #1 SYS #2 SYS #3 SYS #4
25 wo/HGBP R22 Factory 27 lb. / 0 oz. 26lb / 0oz - -
25 w/HGBP R22 Factory 27 lb. / 8 oz. 26 lb. / 0oz - -
30 wo/HGBP R22 Factory 13 lb. / 4 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. -
30 w/HGBP R22 Factory 14 lb. / 0 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. -
30 wo/HGBP1 R22 Factory 14 lb. / 6 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -
30 w/HGBP1 R22 Factory 15 lb. / 2 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -
40 wo/HGBP R22 Factory 15 lb. / 5 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz.
40 w/HGBP R22 Factory 15 lb. / 13 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz.
1. With high capacity evaporator coil.
TABLE 13: ELECTRICAL DATA BASIC UNIT - 25 TON
VOLTAGE
COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT
QTY. RLA LRA QTY FLA HP FLA MCA MAX OVERCURRENT
PROTECTION DEVICE
208-3-60 2 45.7 350 4 7.6 ea.
7.5 24.2 157 200
10 30.8 164 200
15 46.2 180 225
20 59.4 196 250
230-3-60 2 45.7 350 4 6.9 ea.
7.5 22.0 152 175
10 28.0 158 200
15 42.0 172 200
20 54.0 187 225
460-3-60 2 24.3 158 4 3.5 ea.
7.5 11.0 80 100
10 14.0 83 100
15 21.0 90 110
20 27.0 96 110
575-3-60 2 19.3 125 4 3.0 ea.
7.5 9.0 64 80
10 11.0 66 80
15 17.0 72 90
20 22.0 78 100
Unitary Products Group 23
TABLE 14: ELECTRICAL DATA BASIC UNIT - 30 TON
VOLTAGE
COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT
QTY. RLA LRA QTY. FLA TOTAL HP FLA MCA MAX. OVERCURRENT
PROTECTION DEVICE
208-3-60 3 38.5 228 3 4.0 ea. 12.0
10 30.8 168 200
15 46.2 185 225
20 59.4 202 250
25 74.8 221 250
230-3-60 3 38.5 255 3 3.6 ea. 10.8
10 28 164 200
15 42 179 200
20 54 194 225
25 68 211 250
460-3-60 3 18.8 127 3 2.2 ea. 6.6
10 14 81 90
15 21 88 100
20 27 96 110
25 34 104 125
575-3-60 3 15.7 100 3 1.4 ea. 4.2
10 11 66 80
15 17 73 80
20 22 79 100
25 27 85 110
TABLE 15: ELECTRICAL DATA BASIC UNIT - 40 TON
VOLTAGE
COMPRESSORS COND. FAN MOTOR SUPPLY AIR MOTOR BASIC UNIT OVERCURRENT
PROTECTION DEVICE
QTY. RLA LRA QTY. FLA TOTAL HP FLA MCA MAX. OVERCURRENT
PROTECTION DEVICE
208-3-60 4 38.5 228 4 4.0 ea. 12.0
10 30.8 210 225
15 46.2 228 250
20 59.4 244 300
25 74.8 264 300
230-3-60 4 38.5 255 4 3.6 ea. 14.4
10 28 206 225
15 42 221 250
20 54 236 250
25 68 253 300
460-3-60 4 18.8 127 4 2.2 ea. 8.8
10 14 101 110
15 21 109 125
20 27 116 125
25 34 125 150
575-3-60 4 15.7 100 4 1.4 ea. 5.6
10 11 83 90
15 17 90 100
20 22 96 110
25 27 102 125
24 Unitary Products Group
TABLE 16: ELECTRICAL DATA BASIC UNIT WITH ELECTRIC HEAT - 25 TON
VOLTAGE
ELECTRIC HEAT SUPPLY AIR MOTOR BASIC UNIT W/ ELECTRIC HEAT
NOMINAL KW APPLIED KW HP FLA MCA MAX OVERCURRENT
PROTECTION DEVICE
208-3-60
40 30
7.5 24.2 157 200 10 30.8 164 200…