This file is an Operation and Maintenance Manual for Trane Odyssey TTA Series air-cooled condensing units, incorporated as Appendix J into the Massachusetts Trial Court Region 3 Chiller Service Agreement Request for Proposals. The manual provides comprehensive technical documentation for the Trane condensing unit installed at the Newburyport Superior Court facility, which is part of the Region 3 chiller and associated HVAC equipment preventive maintenance and repair service contract. The manual covers installation, operation, and maintenance procedures for TTA models ranging from 4 to 20 tons capacity, including single-circuit, dual-circuit, and manifolded compressor configurations operating on R410A refrigerant. The document details system precautions, general information, installation guidelines, refrigerant piping specifications, charging and evacuation procedures, electrical wiring requirements, dimensional data, operational parameters, maintenance protocols, and troubleshooting guidance necessary for qualified personnel to properly service and maintain the equipment.
The manual establishes critical safety requirements stating that only qualified personnel should install and service the equipment, with specific warnings regarding improper installation, adjustment, or alteration that could result in death or serious injury. Technical specifications include refrigerant piping guidelines with maximum recommended line lengths of 200 feet, maximum suction line lift of 60 feet, and maximum liquid line lift of 60 feet, along with specific tube size requirements dependent on equipment capacity. The document mandates proper evacuation procedures to 350 microns vacuum, liquid charging procedures with specific operating pressure ranges (125–140 PSI low, 365–418 PSI high), and detailed electrical connection requirements complying with local and national codes. General data tables provide unit-specific information including power connections (380–415V/3/50 Hz), refrigerant charges, compressor specifications, coil configurations, fan characteristics, motor outputs, and dimensional and weight information for all covered TTA model sizes.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MASSACHUSETTS TRIAL COURT | REGION 3 CHILLER
SERVICE AGREEMENT
Region 3 Chiller Service Agreement RFP | Page 20 of 30
COMMONWEALTH OF MASSACHUSETTS
MASSACHUSETTS TRIAL COURT
REQUEST FOR PROPOSALS
Region 3 Chiller and Associated HVAC Equipment Preventive Maintenance and Repair Service Agreement
APPENDIX J
Newburyport Superior Court - Trane Condenser Unit O&M Manual
This appendix is incorporated by reference into the Region 3 Chiller Service Agreement Request for Proposals.
Facilities Management & Capital Planning
Manualslib.com - The Global Manuals Library
Manuals / Brands / Trane Manuals / Air Conditioner / ODYSSEY TTA Series / Installation operation & maintenance / PDF
TRANE ODYSSEY TTA SERIES INSTALLATION
OPERATION & MAINTENANCE
Quick Links Model Nomenclature Electrical Wiring Dimensional Data
Table of Contents Model Nomenclature Table of Contents System Precaution General Information Installation Refrigerant Piping Guidelines Refrigerant Charging and Evacuation General Data Refrigerant Circuit Electrical Wiring Dimensional Data Operation Maintenance Trouble Shooting Other ManualsLib Projects https://www.manualslib.com/ https://www.manualslib.com/ https://www.manualslib.com/brand/ https://www.manualslib.com/brand/trane/ https://www.manualslib.com/brand/trane/air-conditioner.html https://www.manualslib.com/products/Trane-Odyssey-Tta-Series-11473841.html https://www.manualslib.com/manual/2599264/Trane-Odyssey-Tta-Series.html https://static-data2.manualslib.com/brand/c7d/3398/trane-logo.png
May 2020 TTA-R410A 690883650001
Confidential and proprietary Trane information
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
ODYSSEY
Installation Operation
Maintenance
Light Commercial
Split System 4-20 Tons
TTA Model 50 Hz
Single Circuit
TTA 051 JDF
TTA 065 JDF
TTA 075 JDF
TTA 100 JDF
TTA 120 JDF
TTA 150 JDF
Dual Circuit
TTA 150 JD00
TTA 180 JD00
TTA 200 JD00
TTA 240 JD00
Manifolded Compr.
TTA 150 JD0G
TTA 180 JD0G
TTA 200 JD0G
TTA 240 JD0G
R410A
2 TTA-R410A
Model Nomenclature
Air-Cooled Condensing Unit Model Nomenclature
051 = 51 MBH
065 = 65 MBH
075 = 75 MBH
100 = 100 MBH
120 = 120 MBH
150 = 150 MBH
180 = 180 MBH
200 = 200 MBH
240 = 240 MBH
TTA = Cooling Only Condensing Unit Product Type
Nominal Gross Cooling Capacity (MBH)
Refrigerant Type
Service Digit
Minor Design Sequence
Electrical Characteristics
Factory Installed Options #1 (Standard Factory Installed Option)
Factory Installed Options #2 (Special Factory Installed Option)R = R22
E = R407C F = R407C Hi Eff J = R410A
= 380-415/3/50 = 230/3/60 = 380/3/60 = 460/3/60
D K
= Minor Design = Minor Design with Flex Tube
B C
= Third Design Sequence = Fourth Design Sequence = New Design 1 Fan/New comp change = Unit Hi-Ambient Temp = Fifth Design Sequence
Q R S J F
= No Option = Copper Fin = Blue Fin = Single Circuit - Manifolded Compressor
(for TTA150 to 240) = Single Circuit - Manifolded Compressor and Copper Fin
(for TTA150 to 240) = Single Circuit - Manifolded Compressor and Blue Fin
(for TTA150 to 240)
E F G
H
J
= Vertical discharge W/Service Valve (for TTA075 to 240) = Vertical discharge W/Access Valve (for TTA075 to 240) = Horizontal discharge W/Service Valve (for TTA075 to 120) = Horizontal discharge W/Access Valve (for TTA075 to 120) = Vertical discharge Service and access Valve (for TTA075 to 240) = Horizontal discharge Service and access Valve (for TTA075 to 240) = Vertical and Horizontal discharge W/Service Valve (TTA051 to 150)
A B C D E F
T T A 1 5 0 J D F 0 F C
TTA-R410A 3
Contents
Model Nomenclature
System Precaution
General Information
Installation
Refrigerant Piping Guidelines
Refrigerant Charging and Evacuation
General Data
Refrigerant Circuit
Electrical Wiring
Dimensional Data
Operation
Maintenance
Trouble Shooting
4 TTA-R410A
System Precautions
Safety Precautions
WARNING
CAUTION
• To prevent injury to the user or other people and property damage, the following instructions must be followed.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
Incorrect operation due to ingnoring of instructions may cause harm or damage. The seriousness is classified be the following indications.
WARNING
WARNING
CAUTION
CAUTION
• After reading this manual, be sure to keep it together with the Owner Manual in a handy place on the customer’s site.
Do not install the unit by yourself (customer)
Install the unit securely in a place which can bear the weight of the unit.
Incomplete installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
If the electrical cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust water, etc.
When installed in an insufficient strong place, the unit could fall causing injury.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Incomplete connecting and fixing could cause fire.
Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely.
• Locations where there may be a leakage of combustible gases.
• The place is filled with oil.
• Beachfront location.
• The place that contain sulfuric acid, such as hot springs.
• The place where high frequency devices or wireless devices are used.
Perform earthing.
Do not connect the earth wire to a gas pipe, water pipe, lightning rod or telephone earth wire. Defective earthing could cause an electric shock.
Be sure to use the part provided or specified parts for the installation work.
The use of defective parts could cause an injury due to a fire, an electric shock, the unit falling, leakage of water, etc.
Be sure to cut off the main power in case of setting up the indoor electronic control P.C. board or wiring works.
It could cause an electri shock.
Any presence of foreign substance such as air can cause abnormal pressure rise or an explosion.
The appliance shall be installed in accordance with national wiring regulations.
Do not install the unit in a place where an inflammable gas leaks.
If gas leak and accumulate in the area surrounding the unit, it could cause an explosion.
Fasten a flare nut with a torque wrench as specified in this manual.
If gas leak and accumulate in the area surrounding the unit, it could cause an explosion.
Install a earth leakage breaker depending on the install-ation place (Where it is humid).
Perform the drainage/piping work securely according to the installation manual.
If a earth leakage breaker is not installed, it could cause an electric shock.
Avoid to installing in places that may cause problems to unit.
If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
Check that the refrigerant gas due not leak after install-ation has completed.
Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet.
If refrigerant gas leaks indoors, and comes into contact with the fire of a fan heater, space heater, stove, etc..
harmful substances will be generated.
Perform the installation securely referring to the install-ation manual.
Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water
Perform electrical work according to the installation manual and be sure to use an exclusive circuit.
If the capacity of the power circuit is insufficient or there is insufficient electrical work, it could result in a fire or an electric shock.
Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections.
TTA-R410A 5
General Information
TTA 075 JDF
TTA 100 JDF
TTA 120 JDF
TTA 150 JDF
TTA 150 JD0G/00
TTA 180 JD0G/00
TTA B51 JDF
TTA B65 JDF
TTA 200 JD0G/00
TTA 240 JD0G/00 500 1102.3 462 116.5 256.8 116.5 256.8 114.5 252.4 114.5 252.4
109.0 240.3 109.0 240.3 107.0 235.9 107.0 235.9
106.0 233.7 106.0 233.7 104.0 229.3 104.0 229.3
96.5 212.7 96.5 212.7 94.5 208.3 94.5 208.3
101.5 223.2 43.4 95.4 65.9 144.9 42.3 93.1
95.6 210.8 34.7 76.5 85.6 188.7 24.1 53.1
75.8 167.1 32.4 71.4 49.2 108.5 31.6 69.7
66.2 145.9 27.8 61.3 42.8 94.4 27.2 60.0
34.1 75.2 14.6 32.2 22.3 49.1 14.0 30.9
32.1 70.7 13.8 30.4 21.0 46.3 13.1 28.9
1018.5 432 952.4 420 925.9 382 842.2 253 556.6 240 529.1 189 416.7 164 361.6 85 187.4 80 176.3
456 1005.3 444 978.9 396 873.0 264 580.8 259 571.0 201 443.1 171 377.0 91 200.6 86 189.6
Warning: open and lock unit disconnect to prevent injury or death from electric shock or contact with moving parts before attempting any installation or maintenance.
on page 20-24
This manual covers the installation of the TTAB51, TTAB65, TTA075, TTA100 ,TTA120 and TTA150 (Single Circuit) TTA150, TTA180, TTA200 and TTA240 (Dual Circuit and Manifolded- Compressor) system outdoor units.
Installation procedures should be performed in the sequence that they appear in this manual .Do not destroy or remove manual from the unit.
The manual should remain weather-protected with the unit until all installation procedures are complete.
Note: It is not the intention of this manual to cover all possible variations in systems that may occur or to provide comprehensive information concerning every possible contingency that may be encountered during an installation. If additional information is requirHG�RU�LI�VSHFL¿F problems arise that are not fully discussed in this manual, contact your local Sales of¿FH�
Note: “ Warnings” and “ Cautions” appear at appropriate places in this manual. Your personal safety and the proper operation of this machine require that you follow them carefully.
The Company assumes no liability for installations or servicing performed by
XQTXDOL¿HG�SHUVRQQHO�
Installation Checklist An “Installation Checklist” is provided at the end of the installation section of this manual. Use the checklist to verify that all necessary installation procedures have been completed.
Do not use the checklist as a substitute for reading the information contained in the manual. Read the entire manual befor beginning installation procedures.
Unit Inspection Inspect material carefully for any shipping damage. If damaged, it must be reported to, and claims made against the transportation company. Compare the information that appears on the unit nameplate with ordering and submittal data to insure the proper unit was shipped.
Available power supply must be compatible with electrical
FKDUDFWHULVWLFV�VSHFL¿HG�RQ
component nameplates.
Replace damaged parts with authorized parts only.
Inspection Checklist To protect against loss due to damage incurred in transit, complete the following checklist upon receipt of the unit.
• Inspect individual pieces of the shipment before accepting the unit.
Check for obvious damage to the unit or packing material.
• Inspect the unit for concealed damage before it is stored and as soon as possible after delivery.
Concealed damage must be reported within 15 days. If con sealed damage is discovered, stop unpacking the shipment.
Do not remove damaged material from the receiving location.
Take photos of the damage if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
• Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
• Notify the sales representative and arrange for repair. Do not repair the unit until the damage is inspected by the carrier’s representative.
6 TTA-R410A
Installation
Lifting Recommendations Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety. Because of placement of internal components, the unit weight may be unevenly distributed. Approximate unit weights are given in Table 1.
must be capable of lifting the unit weight with an adequate safety factor.
The use of under-capacity lifting devices may result in severe personal injury or death and can seriously damage the unit.
The crated unit can be moved using a forklift of suitable capacity. For lifting the unit, attach lifting straps or slings securely to the lifting holes at each corner. Use spreader bars to protect the unit casing from damage. Test lift the unit to determine proper balance and stability.
Clearances Provide enough space around the unit to allow unrestricted access to all service points. Refer to unit dimensional data for minimum required service and free air clearances. Observe the following points to insure proper unit operation.
A. Do not install the unit under a low overhang. Condenser discharge clearance is not less than 2.5 mm.
Important: Do not obstruct condenser discharge air. This can result in warm air recirculation through the coil.
B. Do not locate the unit in a position where runoff water can fall into the fan discharge openings.
C. Condenser intake air is supplied from three sides of the unit. Adhere to the minimum required clearances given in dimensional data.
Unit Mounting “For ground level installation, the unit base should be adequately supported and hold the unit near level. The installation must meet the guidelines set forth in local codes.”
The support should extend two inches beyond the unit base channels at all points. The unit and support must be isolated from any adjacent structure to prevent possible noise or vibration problems. Any ground level location must comply with required clearances given in dimensional data.
Warning: On-sight lifting equipment
Caution: Use spreader bars to prevent lifting straps from damaging the unit. Install bars between lifting straps. This will prevent the straps from crushing the unit cabinet or
GDPDJLQJ�WKH�XQLW�¿QLVK�
TTA-R410A 7
Refrigerant Piping Guidelines
Refrigerant Piping To ensure the return of oil in the refrigerant lines, it is necessary to follow these recommendations:
1. Select the tube lengths with care
DQG�WU\�WR�DYRLG�KDYLQJ�D�¿QDO�IHZ
meters of tube to use up. Refer to table 2 for tube sizes.
2. Pitch all horizontal suction lines down towards the unit to assist gravity oil drainage back to the compressor.
3. Avoid creating large oil traps in horizontal suction lines as this will reduce oil circulating in the system and may eventually lead to failure of the compressor.
4. A small oil trap at the end of a horizontal suction line before a long vertical riser (of more that 2.5 metres) has the advantage of assisting the high velocity gas to carry the oil up the vertical pipe.
5. Liquid lines require no special installation techniques as the liquid refrigerant R-22 and the oil mix.
The densities of the refrigerant and oil are near enough the same so any movement of liquid refrigerant will carry oil with it.
6. The installation of a liquid line sight is recommended. It is very useful during the maintenance procedures.
Refrigerant Piping Guidelines A. Maximum recommended line lengths: (per circuit) Maximum linear length 200 Ft.
(W/o accumulator) Maximum suction line lift 60 Ft.
Maximum liquid line lift 60 Ft.
B. Maximum allowable pressure drops (R410A):
Suction line 14 psi.
Liquid line 65 psi.
(without subcooler) Route refrigerant piping for minimum linear length, minimum number of bends and ¿WWLQJV��QR�reducers) and minimum amount of line exposed to outdoor ambients.
C. Recommended line sizes:
TTA 150-200 (Dual Circuit)
TTA B51-B65 (Single Circuit) TTA 075-100 (Single Circuit)
Suction line
Liquid line
1 1/8 inch sealed type L refrigerant tubing.
1/2 inch sealed type L refrigerant tubing.
D. Recommended line sizes:
TTA 120 (Single Circuit) TTA 240 (Dual Circuit) Suction line
Liquid line
1 3/8 inch sealed type L refrigerant tubing.
1/2 inch sealed type L refrigerant tubing.
E. Recommended line sizes:
TTA 150 (Single Circuit) TTA 150-240 (Manifolded Compressor) Suction line
Liquid line
1 5/8 inch sealed type L refrigerant tubing.
5/8 inch sealed type L refrigerant tubing.
Figure 1
Note: Insulate all refrigerant piping and connections.
TUBE CONNECTON
CAP
CHARGING
PORT
CAP VALVE PORT
BODY (FORGED)
TUBE CONNECTON
O - RING
O - RING
SEAL
PLUNGER
VALVE CORE
TTA B65 JDF 1/2 7/8 1/2 7/8 1/2 7/8 1/2 1 1/8
TTA 100 JDF 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
TTA 120 JDF 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8
TTA 150 JD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
TTA 180 JD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
TTA 200 JD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
TTA 240 JD00 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8
TTA 150 JD00 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
TTA 150 JDF 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
TTA 180 JD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
TTA 200 JD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
Table 2 - Recommended Interconnecting Lines
Notes: 1. Two line sets are required for dual circuits units.
2. For line lengths over 80 linear feet and 15 feet liquid line riser, consult your local Trane representative.
Length of Interconnecting Line (feet) 0-20 21-40 41-60 61-80
Liq. Suct. Liq. Suct. Liq. Suct. Liq. Suct.
TTA B51 JDF 1/2 7/8 1/2 7/8 1/2 7/8 1/2 7/8
TTA 075 JDF 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
Model
TTA 240 JD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
8 TTA-R410A
Refrigerant Piping Guidelines Refrigerant Piping Procedures (Outdoor units) Each TTA unit ships with dry nitrogen holding charge. Due to this minimal amount, we recommend that it be removed and the entire system evacuated (at the proper time) to avoid possible contamination.
1. Remove the compressor service access panel.
2. Locate the liquid and suction line service valves. Check that the piping connection stubs on the valves (Figure 1) line up properly with the holes in the unit cabinet.
3. Front-seat (close) both of the service valves must be closed before the system is opened.
suction line service valves before puncturing the seal caps on the connection stubs. If the seal caps are punctured with the valves open, the refrigerant contained in each circuit will be lost.
unless they have been punctured. If caps are intact, application of heat may generate excessive pressure in the connection stub, causing personal injury or death due to rupturing of components and damage to the service valve.
4. Heat and remove the seal caps.
caps from refrigerant connections unit prepared to braze refrigerant lines to the connections. Excessive exposure to atmosphere may allow moisture or dirt to contaminate the system, damaging valve seats and causing ice formation in system components.
5. *\[��Ä[�HUK�IYHaL�[\IPUN��Z[HY[PUN at the outdoor unit and work toward the indoor unit.
Note: Use long radius ells for all 90 degree bends.
Caution: Fully close the liquid and
Warning: Do not heat the seal caps
Caution: Do not remove the seal
All brazing should be done using 2
[V���WZPN�KY`�UP[YVNLU�W\YNL�ÅV^PUN
through the pipe being brazed 9 (Figure 2).
between the nitrogen source and the gauge manifold (Figure 2).
Unregulated pressures can damage system components.
protect painted surfaces from excessive heat. Heat can damage system components and the unit
ÄUPZO�
6. Shut off nitrogen supply.
7. Shut off the manifold valve for the line that is connected to the suction line service valve.
Disconnect the line from the gauge port on the value.
Refrigerant Piping Procedure (Indoor Unit) Once liquid and suction lines are complete to the refrigerant connections on the indoor unit, heat and remove the seal caps on the indoor unit connection stubs to release the dry nitrogen charge.
Caution: Install a regulating valve
Caution: Wet-wrap all valves and
1. Remove both seal caps from the indoor unit connection stubs.
2. Turn nitrogen supply on. Nitrogen enters through the liquid line gauge port.
3. Braze the liquid line connections.
4. Open the gauge port on the suction line and then braze suction line to the connection stub. Nitrogen will bleed out the open gauge port on the suction line.
5. Shut off nitrogen supply.
Leak Check After the brazing operation of refrigerant lines to both the outdoor
HUK�PUKVVY�\UP[�PZ�JVTWSL[LK��[OL�ÄLSK
brazed connections must be checked for leaks. Pressurize the system through the service valve with dry nitrogen to 400 psi. Use soap bubbles or other leak-checking methods to
LUZ\YL�[OH[�HSS�ÄLSK�QVPU[Z�HYL�SLHR�MYLL�
If not, release pressure, repair and repeat leak test.
Caution: Do not remove seal caps until prepared to braze refrigerant lines to the connections. Extended exposure to atmosphere may allow moisture or dirt to contaminate the system, damaging system components.
Figure 2
Manifold Gauge Pressure
Regulating Valve
Dry
Supply Nitrogen
Liquid Line Gauge Port
Liquid Line Service Valve Note: Detail Service valve see Fig.1
Suction Line Service Valve Note: Detail Service valve see Fig.1
Suction Line Gauge Port
TTA-R410A 9
Refrigerant Charging and Evacuation
Note: Each TTA unit ships with holding charge.
System Evacuation
1. After completion of leak check, evacuate the system.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
Note: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-22/R407C and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
4. Evacuate the system to hold a 350 micron (-76 cm.Hg) vacuum.
5. Close off valve to vacuum pump and observe the micron gauge.
If gauge pressure rised above 500 microns in one (1) minute, then evacuation is incomplete or the system has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
Caution: Do not connect a dual-circuit outdoor unit to a single circuit evaporating unit. (blower)
TTA 120 JDF
TTA 150 JDF
TTA 150 JD00
TTA 180 JD00
TTA 200 JD00
TTA 240 JD00
TTA 180 JD0G
TTA 200 JD0G
TTA 240 JD0G
TTA B51 JDF
TTA B65 JDF
TTA 075 JDF 5.40 11.90
3.30 7.27
3.90 8.60
6.30 13.89
6.30 13.89
6.10 13.45
5.40 11.90
6.75 14.88
6.75 14.88
13.50 29.76
12.60 27.78
12.20 26.90
10.30 23.81
TTA 100 JDF
Tubing Sizes Additional Additional See Suction Liquid Tubing Length Refrigerant Note 1 1/8" 3/8" 15 ft. 0 lb. 11.5 oz. (1) 1 1/8" 3/8" 25 ft. 1 lb. 3.0 oz. (1) 1 1/8" 3/8" 32 ft. 1 lb. 8.0 oz. (1) 1 1/8" 3/8" 40 ft. 1 lb. 14.0 oz. (1) 1 3/8" 1/2" 15 ft. 1 lb. 4.0 oz. (2) 1 3/8" 1/2" 25 ft. 2 lb. 1.0 oz. (2) 1 3/8" 1/2" 32 ft. 2 lb. 11.0 oz. (2) 1 3/8" 1/2" 40 ft. 3 lb. 5.0 oz. (2) 1 5/8" 5/8" 15 ft. 1 lb. 15.5 oz. (3) 1 5/8" 5/8" 25 ft. 3 lb. 5.5 oz. (3) 1 5/8" 5/8" 32 ft. 4 lb. 3.2 oz. (3) 1 5/8" 5/8" 40 ft. 5 lb. 4.0 oz. (3) of 1 1/8" and 3/8" lines.
2 Amounts shown are based on 1.33 ounces of refrigerant per foot of 1 3/8" and 1/2" lines.
3 Amounts shown are based on 2.1 ounces of refrigerant per foot of 1 5/8" and 5/8" lines.
Note: for tubing over 40 ft. calculate the additional refrigerant needed, based on notes above.
Table 4 - Additional Required Refrigerant
Amounts shown are based on 0.75 ounces of refrigerant per foot
7. Remove vacuum pump. Attach center hose of manifold gauge to cylinder, purge the charging line, open valve on cylinder and allow refrigerant pressure to build up to about 40 psig.
8. Close valve on the supply cylinder and close valves on manifold gauge.
9. Leak test the entire system. Using proper procedures and caution, repair any leaks found and repeat the leak test.
10 TTA-R410A
Refrigerant Charging and Evacuation
Liquid Charging (Figure 3) After the refrigerant pipework system has been pressure tested and evacuated, the refrigerant may be charged as follows.
1. Weigh the refrigerant cylinder on weighing scale.
2. Attach the charging line from the center hose of manifold gauge to Refrigerant cylinder.
3. Open valve on Refrigerant cylinder and purge the charging line.
4. Invert the refrigerant cylinder, open the liquid line service valve. Open manifold valve so that only liquid
^PSS�LU[LY�[OL�Z`Z[LT��;OL�Z\MÄJPLU[�
operating charge is recommended in Table 3.
Procedure
1. Open liquid valve that refrigerant go through air handler unit and open suction valve.
2. Turn on power to the unit. Allow the
Z`Z[LT�[V�Y\U�MVY�Ä]L�[V�[LU�
minutes to stabilize operating conditions.
3. 4LHZ\YL�HPYÅV^�HJYVZZ�[OL�PUKVVY�
coil. Compare the measurements with the fan performance data in the Data/Submittal or Service
-HJ[Z��6UJL�WYVWLY�HPYÅV^�PZ�
established, observe the suction and head pressure gauges on the gauge manifold.
Lo
Operating Pressure (PSI)
125 - 140
Hi 365 - 418
Pressure reading should fall approximately at the points shown by the pressure curves in Service Facts. Add or remove refrigerant (gas only) as required to obtain correct head and suction pressure.
Check suction line superheat and condenser sub-cooling to ensure the unit is operating properly.
4. Disconnect all power to the unit.
5. Remove the charging system from the unit and close the opening in the bottom of the control box with the pivotal cover before attempting to replace access panel.
6. Replace all panels.
Additional Charge Refrigerant suitable for a tube length of 12 to 25 feet is recommended in Table 3. When the tube is longer than 25 feet, additional charging is necessary. For the additional amount, using the table 4 for recommended amounts:
Caution .Freon Gas only Always evacuate air from the tubing before adding refrigerant.
Add refrigerant through the charging port of liquid line valve after the completion of evacuation.
The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer’s warranty could be cancelled.
Figure 3
LIQUID
Bottom
R410A
Manifold Gauge
Liquid Line Gauge Port
Liquid Line Service Valve Note: Detail Service valve see Fig.1
Suction Line Service Valve Note: Detail Service valve see Fig.1
Suction Line Gauge Port
TTA-R410A 11
General Data U
N
IT
M O
D
EL
S
TT
AB
JD
F
TT
AB
JD
F
PO
W
ER
C O
N N
EC
TI
O N
V/ ph
/H z
0-
5/
3/
0-
5/
3/
M C
A1 A
.2
.2
SY
ST
EM
D
AT
A
R ef rig er an t T yp e
R
0A R
0A
R ef rig er an t C on ne ct io n Ty pe
BR
AZ
E
BR
AZ
E R ef rig er an t C ha rg e lb (k
g) Si ng le
C irc ui t.
Su ct io n Li ne O
D in (m m
7/
(2 2.
2) 7/
(2
2.
2)
Li qu id li ne
O D in (m m
1/
(1 2.
7) 1/
(1
2.
7)
D ua l C irc ui t.
Su ct io n Li ne m
Li qu id li ne
O D in (m m
C
AS
IN
G M at er ia l
C ol or Ty pe o f I ns ul at io n
C O
M
PR
ES
SO
R C om pr es so r T yp e N o.
U se d
V/ ph
/H z
0/
3/
0/
3/
R
LA
/L R
A
.1 /7
.5 /7
5.
C O
IL
Tu be S iz e m
5/
(7
.9 4)
5/
(7 .9
4) Tu be T yp e
In ne r g ro ov e
In ne r g ro ov e
R ow s
Fi n Ty pe Fi ns p er in ch
R ef rig er an t F lo w C on tro l
FA
N Fa n Ty pe Pr op el le r
Pr op el le r N o.
u se d
D ia m et er in
(m m
(5
(5
N o.
o f B la de
Pi tc h
A ng le de gr ee
D riv e Ty pe D ire ct
D ire ct N om in al A irf lo w cf m
(c m h)
(4
0)
(4
0) M
O
TO
R M ot or T yp e
N o.
o f M ot or
M ot or
O ut pu t
W at t
N o.
o f S pe ed
M ot or
S pe ed rp m
V/ ph /H z
0/ 1/
0/ 1/
R
LA
/L
R A
1.
/3 .8
1.
/3
.8
D
IM
EN
SI
O N
(H xW xD
C ra te d
(S hi pp g) m m x x x x
U nc ra te d (N et m m x8 x x8 x
W
EI
G H
T C ra te d
(S hi pp in
g) kg
U nc ra te d (N et kg
1 M
C A
- M in im um
C irc ui t A m pa ci ty
2 C
FM
is ra te d w ith s ta nd ar d ai r-dr y co il.
PS
C
H ol di ng
C ha rg e
H er m et ic S cr ol l
G al va ni ze d
E le ct ro -g al va ni ze d S te el
Li gh t G ra y
U nc oa te d C or ru ga te
TT
A
5J
D F
TT
A
0J
D F
TT
A
0J
D F
TT
A
0J
D F
0-
5/
3/
0-
5/
3/
0-
5/
3/
0-
5/
3/
.8
.8
.2
.0
R
0A R
0A
R
0A R
0A
B R
A
ZE
B R
A
ZE
B R
A
ZE
B R
A
ZE
1/
(2
8.
6)
1/
(2
8.
6)
3/
(3
4.
9)
5/
(4
1.
3)
1/
(1 2.
7) 1/
(1
2.
7)
1/
(1 2.
7) 5/
(1
5.
9)
0/
3/
0/
3/
0/
3/
0/
3/
.9
.9
.4
/1
.6
5/
(7 .9
4) 5/
(7
.9 4)
5/
(7 .9
4) 5/
(7
.9 4)
P la in In ne r g ro ov e In ne r g ro ov e In ne r g ro ov e
P ro pe lle r P ro pe lle r
P ro pe lle r P ro pe lle r
(7
(7
(7
(7
D ire ct D ire ct
D ire ct D ire ct
(8
0)
(9
0)
(1
(1
0/
3/
0/
3/
0/
3/
0/
3/
1.
4.
1.
4.
1.
4.
1.
4.
x x x x x x x x x x x x x x x x
H er m et ic S cr ol l
U nc oa te d C or ru ga te
Th re e P ha se
In du ct io n M ot or
H ol di ng
C ha rg e
G al va ni ze d
E le ct ro -g al va ni ze d S te el
Li gh t G ra y
12 TTA-R410A
UNIT MODELS TTA150JD00 TTA180JD00 TTA200JD00 TTA240JD00
POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50
MCA1 A 43.28 45.53 43.28 51.15
SYSTEM DATA
Refrigerant Type R410A R410A R410A R410A Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant Charge lb (kg) Holding Charge Dual Circuit.
Suction Line OD in (mm) 1 1/8 (28.6) 1 1/8 (28.6) 1 1/8 (28.6) 1 3/8 (34.9) Liquid line OD in (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
CASING
Material Galvanized & Electro-galvanized Steel Color Light Gray Type of Insulation -
COMPRESSOR
Compressor Type Hermetic Scroll No. Used 2 2 2 2 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA 17.9 / 125 18.6 / 125 17.9 / 125 21.4 / 147
COIL
Tube Size OD in (mm) 5/16 (7.94) 5/16 (7.94) 5/16 (7.94) 5/16 (7.94) Tube Type Inner groove Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control - - - -
FAN
Fan Type Propeller Propeller Propeller Propeller No. used 2 2 2 2 Diameter in (mm) 28 (711) 28 (711) 28 (711) 28 (711) No. of Blade 4 4 4 4 Pitch Angle degree 29 29 29 29 Drive Type Direct Direct Direct Direct Nominal Airflow2 cfm (cmh) 9770 (16600) 11536 (19600) 13537 (23000) 13537 (23000)
MOTOR
Motor Type Three Phase Induction Motor No. of Motor 2 2 2 2 Motor Output Watt 520 520 520 520 No. of Speed 1 1 1 1 Motor Speed rpm 900 900 900 900 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA 1.50 / 4.8 1.50 / 4.8 1.50 / 4.8 1.50 / 4.8
DIMENSION (HxWxD) Crated (Shipping) mm 1180 x 2290 x 1140 1180 x 2290 x 1140 1180 x 2290 x 1140 1180 x 2290 x 1140 Uncrated (Net) mm 1050 x 2200 x 1050 1050 x 2200 x 1050 1050 x 2200 x 1050 1050 x 2200 x 1050
WEIGHT
Crated (Shipping) kg 393 426 439 474 Uncrated (Net) kg 382 415 428 462
1 MCA - Minimum Circuit Ampacity 2 CFM is rated with standard air-dry coil.
TTA-R410A 13
UNIT MODELS TTA150JD0G TTA180JD0G TTA200JD0G TTA240JD0G
POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50
MCA1 A 30.90 36.08 42.38 47.55
SYSTEM DATA
Refrigerant Type R410A R410A R410A R410A Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant Charge lb (kg) Holding Charge Single Circuit.
(Manifolded Compressors) Suction Line OD in (mm) 1 5/8 (41.3) 1 5/8 (41.3) 1 5/8 (41.3) 1 5/8 (41.3) Liquid line OD in (mm) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9) 5/8 (15.9)
CASING
Material Galvanized & Electro-galvanized Steel Color Light Gray Type of Insulation -
COMPRESSOR
Compressor Type Hermetic Scroll No. Used 2 2 2 2 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA 12.4/101 14.7/127 17.5/153 19.8/153
COIL
Tube Size OD in (mm) 5/16 (7.94) 5/16 (7.94) 5/16 (7.94) 5/16 (7.94) Tube Type Inner groove Inner groove Inner groove Inner groove Rows 2 2 2 2 Fin Type Uncoated Corrugate Fins per inch 16 16 16 16 Refrigerant Flow Control - - - -
FAN
Fan Type Propeller Propeller Propeller Propeller No. used 2 2 2 2 Diameter in (mm) 28 (711) 28 (711) 28 (711) 28 (711) No. of Blade 4 4 4 4 Pitch Angle degree 29 29 29 29 Drive Type Direct Direct Direct Direct Nominal Airflow2 cfm (cmh) 9770 (16600) 11536 (19600) 13537 (23000) 13537 (23000)
MOTOR
Motor Type Three Phase Induction Motor No. of Motor 2 2 2 2 Motor Output Watt 520 520 520 520 No. of Speed 1 1 1 1 Motor Speed rpm 900 900 900 900 V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA 1.50 / 4.8 1.50 / 4.8 1.50 / 4.8 1.50 / 4.8
DIMENSION (HxWxD) Crated (Shipping) mm 1180 x 2290 x 1140 1180 x 2290 x 1140 1180 x 2290 x 1140 1180 x 2290 x 1140 Uncrated (Net) mm 1050 x 2200 x 1050 1050 x 2200 x 1050 1050 x 2200 x 1050 1050 x 2200 x 1050
WEIGHT
Crated (Shipping) kg 393 426 439 474 Uncrated (Net) kg 382 415 428 462
1 MCA - Minimum Circuit Ampacity 2 CFM is rated with standard air-dry coil.
14 TTA-R410A
Refrigerant Circuit
TTA B51-B65 JDF (Single Circuit) TTA 075-150 JDF (Single Circuit) TTA 150-240 JD00 (Dual Circuit)
TTA 150-240 JD0G
(Manifolded Comp.)
Figure 4A
Figure 4B
TTA-R410A 15
Electrical Wiring
Electrical Wiring
;;(�ÄLSK�^PYPUN�JVUZPZ[Z�VM�WYV]PKPUN
WV^LY�Z\WWS`�[V�[OL�\UP[��PUZ[HSSPUN�[OL
Z`Z[LT�PUKVVY�[OLYTVZ[H[��(JJLZZ�[V
LSLJ[YPJHS�JVUULJ[PVU�SVJH[PVUZ�PZ
ZOV^U�PU�KPTLUZPVUHS�KH[H�
Unit Power Supply
;OL�PUZ[HSSLY�T\Z[�WYV]PKL�SPUL�]VS[HNL
JPYJ\P[��Z��[V�[OL�\UP[�THPU�WV^LY
[LYTPUHSZ�HZ�ZOV^U�I`�[OL�\UP[�^PYPUN
KPHNYHTZ�PU�^PYPUN��7V^LY�Z\WWS`
T\Z[�PUJS\KL�H�KPZJVUULJ[�Z^P[JO
PU�H�SVJH[PVU�JVU]LUPLU[�[V�[OL�\UP[�
.YV\UK�[OL�\UP[�HJJVYKPUN�[V�SVJHS
JVKLZ�HUK�WYV]PKL�ÅL_PISL�JVUK\P[�PM
JVKLZ�YLX\PYL�HUK�VY�PM�]PIYH[PVU
[YHUZTPZZPVU�TH`�JH\ZL�UVPZL
WYVISLTZ�
Important:�(SS�^PYPUN�T\Z[�JVTWS`
^P[O�HWWSPJHISL�SVJHS�HUK�UH[PVUHS
�5,*��JVKLZ��;`WL�HUK�SVJH[PVU�VM
KPZJVUULJ[�Z^P[JOLZ�T\Z[�JVTWS`
^P[O�HSS�HWWSPJHISL�JVKLZ�
KPZJVUULJ[�Z^P[JO�HUK�SVJR�PU�VWLU
WVZP[PVU�[V�WYL]LU[�HJJPKLU[HS�WV^LY
HWWSPJH[PVU��-HPS\YL�[V�KV�ZV�TH`
YLZ\S[�PU�WLYZVUHS�PUQ\Y`�VY�KLH[O�K\L
[V�LSLJ[YPJHS�ZOVJR�
+L[LYTPUL�WYVWLY�^PYL�ZPaLZ�HUK�\UP[
WYV[LJ[P]L�M\ZPUN�YLX\PYLTLU[Z�I`
YLMLYYPUN�[V�[OL�\UP[�UHTLWSH[L�HUK�VY
PU�;HISL���-PLSK�^PYPUN�KPHNYHTZ�MVY
HJJLZZVYPLZ�HYL�ZOPWWLK�^P[O�[OL
HJJLZZVY`�Caution:�<ZL�JVWWLY�JVUK\J[VYZ�
VUS`��<UP[�[LYTPUHSZ�HYL�UV[�KLZPNULK�
MVY�\ZL�^P[O�HS\TPU\T�JVUK\J[VYZ��
<ZL�VM�PTWYVWLY�^PYPUN�TH[LYPHSZ�JHU�
YLZ\S[�PU�LX\PWTLU[�KHTHNL�
Warning:�6WLU�[OL�LSLJ[YPJHS
342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440
TT(�����1+-
TT(�����1+-
342-440 342-440
TT(�)���1+-
TT(�)���1+-
TT(�����1+-
TT(�����1+-�
TT(�����1+�.
TT(�����1+�.
TT(�����1+�.
TT(�����1+�.
342-440 342-440 342-440 342-440
TT(�����1+��
TT(�����1+��
TT(�����1+��
TT(�����1+��
Table 5 - Electrical Data
16 TTA-R410A
INTERNAL OVERLOAD
1 ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC
OF RELAY CONTACTS.
ELECTRICAL STANDARDS.
NUMBERS AND/OR LETTERS.
4 COMPONENT TERMINAL MARKINGS ARE INDICATED BY ENCIRCLED
A TEMPERATURE RANGE OF 32°F TO 53.5°F.
7 THIS UNIT TO BE USED WITH EVAPORATORS OPERATING WITH IN
6 MOTORS ARE INHERENTLY PROTECTED.
LINE IDENTIFICATION. NUMBERS ALONG RIGHT SIDE ARE LOCATIONS
3 NUMBERS ALONG LEFT SIDE OF ELEMENTARY DIAGRAM DESIGNATE
CONDITIONING & REFRIGERATION INSTITUTE (ARI) GRAPHIC
2 DRAWING PRACTICES AND SYMBOLS ARE IN ACCORDANCE WITH AIR
CITY CODES. PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
CODE (N.E.C.) CANADIAN ELECTRIC CODE AND/OR LOCAL STATE AND
5 NUMBERS ON VERTICAL & HORIZONTAL LINE ARE CIRCUIT IDENTIFICATION.
COMPRESSOR
HTR
4 6 5
T1 T2 T3
TTA B51-B65 JDF (SINGLE CIRCUIT)
WIRING DIAGRAM
ELEMENTARY DIAGRAM
N 7A
TERMINAL
GROUND
HTR
P O
W
ER
S U
PP
LY
0V
./3
PH
./5 0H
Z.
1M-3
1M-2
1M-1
1 5
7 81R
1M
N
NEUTRAL
S
COMPR.
MOTOR
MOTOR
R
FANC
6 T3
5 T2
4 T1
1HP1LP PH
BRW
BLK
GY3
1L1
L2
L3
9B
TO
IN
D O
O R
U N
IT
C
L
0V
./3
PH
./6 0H
Z.
6A
1B
6B
9A10
9C 9 18
12 1M-1,2,3
1R-11,12
1R7 8
FAN
S
MOTOR C
9C
R 6A
CONNECTION DIAGRAM
3 1R 4 5 6
1 2
380V./3PH./50HZ.
POWER SUPPLYTO INDOOR UNIT
L1 L2 L3 NL N C BT1BT2
380V./3PH./60HZ.
7A
LP
HP
NOTES
CONTROL,HIGH PRESS.
FIELD WIRING (OPTION)
FACTORY WIRING & DEVICES BY MFR.
1TB-TERMINAL BLOCK
RELAY,CONTROL LOCKOUT
CONTROL,LOW PRESS.
CONTACTOR,COMPRESSOR
HEATER,CRANKCASE.
R22 (OPEN : 27 PSIG,CLOSE : 46 PSIG)
R22 (OPEN : 398 PSIG,CLOSE : 313 PSIG)
1R
HTR
LP
1M
HP
LEGEND
PHASE PROTECTORPH
R410A (OPEN : 600 PSIG,CLOSE : 420 PSIG)
R22 (OPEN : 59 PSIG,CLOSE : 65 PSIG)
TTA-R410A 17
A1,A2 AUXILIARY CONTACT(N.O.) OF 2M
INTERNAL OVERLOAD
ELEMENTARY DIAGRAM
1 ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC
OF RELAY CONTACTS.
ELECTRICAL STANDARDS.
NUMBERS AND/OR LETTERS.
4 COMPONENT TERMINAL MARKINGS ARE INDICATED BY ENCIRCLED
A TEMPERATURE RANGE OF 32°F TO 53.5°F.
7 THIS UNIT TO BE USED WITH EVAPORATORS OPERATING WITH IN
6 MOTORS ARE INHERENTLY PROTECTED.
LINE IDENTIFICATION. NUMBERS ALONG RIGHT SIDE ARE LOCATIONS
3 NUMBERS ALONG LEFT SIDE OF ELEMENTARY DIAGRAM DESIGNATE
CONDITIONING & REFRIGERATION INSTITUTE (ARI) GRAPHIC
2 DRAWING PRACTICES AND SYMBOLS ARE IN ACCORDANCE WITH AIR
CITY CODES. PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
CODE (N.E.C.) CANADIAN ELECTRIC CODE AND/OR LOCAL STATE AND
5 NUMBERS ON VERTICAL & HORIZONTAL LINE ARE CIRCUIT IDENTIFICATION.
LP
HP
CONTROL,HIGH PRESS.
FUSE 5 AMP.
CONTACTOR,EVAP. BLOWER MOTOR
SWITCH PUSH BOTTON
FIELD WIRING (OPTION)
FACTORY WIRING & DEVICES BY MFR.
1TB-TERMINAL BLOCK CONTROL CIRCUIT
RELAY,TIME DELAY 3 MIN.
THERMOSTAT
RELAY,CONTROL LOCKOUT
CONTROL,LOW PRESS.
CONTACTOR,COMPRESSOR
HEATER,CRANKCASE.
(OPEN : 27 PSIG,CLOSE : 46 PSIG)
(OPEN : 398 PSIG,CLOSE : 313 PSIG)
1R
COMPRESSOR
HTR
4 6 5
1PB,2PB
1TR
HTR
TH
2M
T1 T2 T3
LP
1M
HP
FU
LEGEND
NOTES
1PB
2M-A1
2PB
2M-A2
TH
1TR
1 2 15
FU
TERMINAL
GROUND
HTR
TTA 075-150 JDF (SINGLE CIRCUIT)
CONNECTION DIAGRAM
P O
W
ER
S U
PP
LY
0V
./3 P
H ./5
0H Z.
1M-3
1M-2
1M-1
WIRING DIAGRAM
EXTERNAL CONTROL
1 5
7 81R
2M 2M-11,14
6 1M-1,2,39
1R-11
N
NEUTRAL
C
COMPR.
MOTOR
MOTOR
A
FANB
6 T3
5 T2
4 T1
HPLP 11 20TP
EXTERNAL OVERLOAD, COMPRESSOR OL
THERMAL PROTECTOR, MOTOR TP
TP
8 BUILT IN THERMAL PROTECTOR CAN BE SKIP OVER THEIR CONNECTION.
0V
./3 P
H ./6
0H Z.
PHASE PROTECTORPH
OL
GY
BLK
BRWL1
L2
L3
2TB-TERMINAL BLOCK HIGH VOLTAGE
14 9 1M
18 PH
N
(HI-AMBIENT OPTION
OPEN : 460 PSIG,CLOSE : 360 PSIG)
1R7 8 12 12
1TB
FAN
C
MOTOR B
6A
5A
A 4A
1TR
15A 14A
9 9 13 13
N N
1B
FU
14A
3 1R 4 5 6
1 2
OL
380V./3PH./50HZ.
POWER SUPPLY
2TB
15A
18 TTA-R410A
CONNECTION DIAGRAM
INTERNAL OVERLOAD
COMPR. NO.1
1HTR
54 6
T3
T2T1
COMPR. NO.2
6 MOTORS ARE INHERENTLY PROTECTED. FACTORY WIRING & DEVICES BY MFR.
A TEMPERATURE RANGE OF 32°F TO 53.5°F.
7 THIS UNIT TO BE USED WITH EVAPORATORS OPERATING WITH IN AUXILIARY CONTACT(N.O.) OF 3M
FIELD WIRING (OPTION)
INTERNAL OVERLOAD
A1,A2
TERMINAL
T2
1 ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC
CODE (N.E.C.) CANADIAN ELECTRIC CODE AND/OR LOCAL STATE AND
CITY CODES. PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
2 DRAWING PRACTICES AND SYMBOLS ARE IN ACCORDANCE WITH AIR
CONDITIONING & REFRIGERATION INSTITUTE (ARI)
3 NUMBERS ALONG LEFT SIDE OF ELEMENTARY DIAGRAM DESIGNATE
LINE IDENTIFICATION. NUMBERS ALONG RIGHT SIDE ARE LOCATIONS OF
4 COMPONENT TERMINAL MARKINGS ARE INDICATED BY ENCIRCLED
5 NUMBERS ON VERTICAL & HORIZONTAL LINE ARE
EXTERNAL CONTROL
RELAY,CONTROL LOCKOUT
RELAY,TIME DELAY 4.5 MIN.
RELAY,TIME DELAY 3 MIN.
HEATER,CRANKCASE.
CONTACTOR,COMPRESSOR
CONTROL,LOW PRESS.
CONTROL,HIGH PRESS.
SWITCH PUSH BOTTON
THERMOSTAT 2 STAGES.
CONTACTOR,EVAP.BLOWER MOTOR
(OPEN : 398 PSIG,CLOSE : 313 PSIG)
(OPEN : 27 PSIG,CLOSE : 46 PSIG)
1TB-TERMINAL BLOCK CONTROL CIRCUIT
2TB-TERMINAL BLOCK HIGH VOLTAGE
2HTR
8 910
T3
1TH
1PB,2PB
3M
1HTR,2HTR
2TR
1TR
1R,2R 1M,2M
T1 T2
LEGEND
1LP,2LP
FU
1HP,2HP
FUSE 5 AMP.
GRAPHIC ELECTRICAL STANDARDS.
RELAY CONTACTS.
CIRCUIT IDENTIFICATION.
NUMBERS AND/OR LETTERS.
NOTES
1PB
3M-A2
2PB
3M-A1
FU
B MOTOR
NO.2
1TR1TH-1
1TH-2
2TR
16 21
2HTR
1HTR
C
2M-3
2M-2
2M-1
A
FAN
C
2M-8,9,10
3M 3M-16,20
2R-18
1M-1,2,3
1R-16
NO.2
T3
MOTOR
COMPR.
T1
T2
WIRING DIAGRAM TTA 150-240 JD00 (DUAL CIRCUIT)
0V
./3
PH
./5 0H
Z.
P
O W
E R
S U
PP
LY
L33
GROUND6
L2
L1 1M-1 41
3 1M-3
1M-2
FAN
MOTOR
NO.1
B
A
ELEMENTARY DIAGRAM
NEUTRAL
T3
N
MOTOR
NO.1
COMPR.
T1
20151LP 1HP
65124
7 1R 8
182LP 2HP
2R7
1OL
2OL
1LP
1HP
1TP
2LP
2HP
2TP
EXTERNAL OVERLOAD, COMPRESSOR 1OL,2OL
PHASE PROTECTORPH
1TP
2TP
0V
./3
PH
./6 0H
Z.
8 BUILT IN THERMAL PROTECTOR CAN BE SKIP OVER THEIR CONNECTION.
BRW
BLK
GY
BRW
BLK
GY
THERMAL PROTECTOR, MOTOR1TP,2TP
2M
1M
28 14PH26
27 28A
14A
14 28
(HI-AMBIENT OPTION
OPEN : 460 PSIG,CLOSE : 360 PSIG)
380V./3PH./50HZ.
POWER SUPPLY
MOTOR
NO.2
FAN
C 10A
B 9A
A 8A
2TB
1A
2A
3A
MOTOR
FAN
NO.1
6AC
B 5A
A 4A
87 1R
24A 26A
1R3 26A 5
20 1
23 23
1TB
14,14A
24 2
N
1TR
1 16
25 2
2TR
1 19
2R7 8
25A 27A
27A
1C
21 1
2R
1OL
4A
5A
6A
20 15
1 2 3
28 26
3B
1M
2B1B
2OL
8A
9A
10A
21 18
1A,1C 2A 3A
28A 27
2M
28A
25A
24A
TTA-R410A 19
ELEMENTARY DIAGRAM
WIRING DIAGRAM TTA 150-240 JD0G (Manifolded Compressor)
CONNECTION DIAGRAM
1HTR
INTERNAL OVERLOAD
COMPR. NO.1
T3
54 6
T2T1
2HTR
INTERNAL OVERLOAD
COMPR. NO.2
T3
108 9
T1 T2
34 14E~ ~
14F~35~
6 MOTORS ARE INHERENTLY PROTECTED.
A TEMPERATURE RANGE OF 32°F TO 53.5°F.
7 THIS UNIT TO BE USED WITH EVAPORATORS OPERATING WITH IN
1 ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC
CODE (N.E.C.) CANADIAN ELECTRIC CODE AND/OR LOCAL STATE AND
CITY CODES. PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
2 DRAWING PRACTICES AND SYMBOLS ARE IN ACCORDANCE WITH AIR
CONDITIONING & REFRIGERATION INSTITUTE (ARI)
3 NUMBERS ALONG LEFT SIDE OF ELEMENTARY DIAGRAM DESIGNATE
LINE IDENTIFICATION. NUMBERS ALONG RIGHT SIDE ARE LOCATIONS OF
4 COMPONENT TERMINAL MARKINGS ARE INDICATED BY ENCIRCLED
5 NUMBERS ON VERTICAL & HORIZONTAL LINE ARE
GRAPHIC ELECTRICAL STANDARDS.
RELAY CONTACTS.
CIRCUIT IDENTIFICATION.
NUMBERS AND/OR LETTERS.
NOTES
8 BUILT IN THERMAL PROTECTOR CAN BE SKIP OVER THEIR CONNECTION.
CONTACTOR,EVAP.BLOWER MOTOR
(OPEN : 398 PSIG,CLOSE : 313 PSIG)
(OPEN : 27 PSIG,CLOSE : 46 PSIG)
1TB-TERMINAL BLOCK CONTROL CIRCUIT
2TB-TERMINAL BLOCK HIGH VOLTAGE
FACTORY WIRING & DEVICES BY MFR.
1TH THERMOSTAT 2 STAGES.
FIELD WIRING (OPTION)
FU
LEGEND
1HP,2HP
1R,2R,3R
1M,2M
2TR
1TR
1HTR,2HTR
1LP,2LP
1PB,2PB
4M
CONTACTOR,COMPRESSOR
RELAY,CONTROL LOCKOUT
RELAY,TIME DELAY 4.5 MIN.
RELAY,TIME DELAY 3 MIN.
HEATER,CRANKCASE.
SWITCH PUSH BOTTON
FUSE 5 AMP.
CONTROL,LOW PRESS.
CONTROL,HIGH PRESS.
A1,A2 AUXILIARY CONTACT(N.O.) OF 4M
CONTACTOR,FAN MOTOR3M
EXTERNAL OVERLOAD, COMPRESSOR 1OL,2OL
PHASE PROTECTORPH
1LP
~24
1HP
1TP
2LP
~25
2HP
2TP
THERMAL PROTECTOR, MOTOR1TP,2TP
4M-A2
0V
./3 P
H ./5
0/
H Z.
P O
W E
R S
U P
P
LY
1M-3 NO.1
2HTR
1HTR
23 13
1TH-2
1PB
4M-A1 1TH-1
FU
GROUND
TERMINAL
L3 3
EXTERNAL CONTROL
2TR
2PB
1TR
1M 1M-1,2,3651
4M
2R
7 2R 8
14B2M 2M-5,6,7
4M-16,22
7 1R 1R
FAN
MOTOR
NO.1
A
C
2M-1
2M-3
2M-2
B
COMPR.
NO.2
T3
T2 MOTOR
T1
T3 NEUTRAL
N
L2
L1 1
ELEMENTARY DIAGRAM
1M-1
1M-2 COMPR.
T2 MOTOR
T1
3M-2 29 3M-3 30
3M-1 28
B
A
NO.2
C
FAN
MOTOR
3M
7 3R 8
3M-8,9,1031
3R-2
3R-1
3R-17,19
2R-20
1R-16
20151LP 1HP24
95 96
1OL1TP
25 182LP 2HP 21
95 96
2OL2TP
PH
BRW
BLK
GY
BRW
BLK
GY
14E
14F
14G
14C
14A
14D
N 14A
380V./3PH./50HZ.
266526A
FAN
MOTOR
NO.2
C
B
A
POWER SUPPLY
30A
29A
2TB
28A
1A 2A
3A
FAN
NO.1
MOTOR
C
B
A
24A
26A
81R
1R
315 6
1TR
23 23
14,14G,N
24, 24A
N
1TB
1 16
2TR
25, 25A 2 1 19
1B
14D26C
1D
3R7 8
26C
3 3R
2R 43
25A
27A 5
82R
27A
21 1 2 26A 27A
14 14E,14F
302928 28A 29A 30A
L3
T3
T2
L2
T1
L1
T11OL 95T2 T3
4 5 6 20 15
1 2 3
14A 26
3C
1M
26A
1C,1D
L3
T3
T2
L2
T1
L1
T12OL 95T2 T3
8 9 10 21 18
1A 2A 3A
14B 27
2M
14C 27A
1B 2B 3B2C
14B
3M
2B 3B
14C 14D
34,35
OPEN : 460 PSIG,CLOSE : 360 PSIG)
(HI-AMBIENT OPTION
20 TTA-R410A
Dimensional Data
TTA B51/B65 JDF (SINGLE CIRCUIT)
Vertical Discharge
Horizontal Discharge
A
B C
A
B
C
TTAB51
A = ELECTRIC WIRING OUTLET
B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”)
C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”)
A = ELECTRIC WIRING OUTLET
B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”)
C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”)
TTAB65
TTAB51
A = ELECTRIC WIRING OUTLET
B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”)
C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”)
A = ELECTRIC WIRING OUTLET
B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”)
C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”)
TTAB65
106.8
362442
77 77 26
722 29.529.5
781 106.8
97 15
29.5 29.5722
77 77650
TTA-R410A 21
TTA 075/100/120 JDF (SINGLE CIRCUIT)
HORIZONTAL AND VERTICAL DISCHARGE
22 TTA-R410A
TTA 150 JDF (SINGLE CIRCUIT)
HORIZONTAL AND VERTICAL DISCHARGE
TTA-R410A 23
TTA 150/180/200/240 JD00 (DUAL CIRCUIT)
24 TTA-R410A
TTA 150/180/200/240 JD0G (MANIFOLDED COMPRESSOR)
TTA-R410A 25
Operation
Sequence of Operation General Operation of the system cooling cycles is controlled by the position of the system switch on the room thermostat.
Evaporator Fan (Indoor Supply Air) The evaporator fan is controlled by an ON/AUTO switch on the room thermostat. With the switch positioned at AUTO and the system operating in the cooling mode, fan operation coincides with the cooling run cycles.
When the fan switch is positioned at ON, fan operation is continuous.
Cooling Mode With the disconnect switch in the “ON” position, current is supplied to the compressor crankcase heater
(s) and control transformer. The crankcase heater (s) supplies heat to the compressor (s) during the “OFF” cycle. With the room thermostat system switch positioned at COOL and the fan switch at AUTO, the compressor contactor energizes on a call for cooling. When the contacts of the compressor contactor energizes on a call for cooling. When the contacts of the compressor contactor close, operation of the compressor and condenser fan begins.
The evaporator fan contactor also energizes on a call for cooling and initiates evaporator fan operation.
On dual circuit units, when second stage cooling is required, Y2 from the indoor thermostat will energize 2nd compressor.
Note: With the thermostat fan switch in the ON position, the evaporator fan will operate continuously, regardless of compressor or condenser fan operation.
Safety Controls Note: All of these controls may not be installed on your unit, check electrical schematic.
Low Pressure Cut-Out (LPCO) This control’s sensor is located in the suction (gas line, near the compressor).
This control will stop the compressor and the outdoor fans in suction pressure drops below the Low Pressure Cut-Out setting.
High Pressure Cut-Out (HPCO) This control’s sensor is located in the liquid line. This device will shut off the compressor and the outdoor fan (s) if the discharge pressure exceeds the High Pressure Cut-Out’s setting.
Internal Overload Protector (IOL) This device is a current/thermal actuated warp switch, imbedded in the compressor motor windings.
If will shut off the compressor if the temperature or current of the compressor motor windings exceeds its design trip temperature.
Note: The IOL will put the compressor back in operation once the compressor motor heat has dropped below the trip setting;
however, a check of the refrigerant and electrical systems should be made to determine the cause and be corrected.
Installation Checklist Complete this checklist once the unit is installed to verify that all recommended procedures have been accomplished before starting the system. Do not operate the system until all items covered by this checklist are complete.
• Inspect unit location for proper required service clearances.
• Inspect unit location for proper free air clearances.
• Inspect unit location for secure.
Level mounting position.
Refrigerant Piping
• Performed initial leak test?
• Connected properly sized and constructed liquid and suction lines to the connection stubs at both the indoor and outdoor units?
• Insulated the entire suction line?
• Insulated portions of liquid line exposed to extremes in temperature?
• Charge each circuit with proper amount of R-22/R407C?
Electrical Wiring
• Provided unit power wiring (with disconnect) to proper terminals in the unit control Section?
• Installed system indoor thermostat?
• Installed system low voltage interconnecting wiring to proper terminals of outdoor unit, indoor unit and system thermostat?
Unit Start-Up Once the unit is properly installed and pre-start procedures are complete, start the unit by turning the System Switch on the indoor thermostat to either COOL or AUTO. The system should operate normally.
the indoor air handler is closed before operating the system. Operating the outdoor unit without the indoor fan energized, can cause unit trip-out on high pressure control and/or liquid
ÀRRG�EDFN�WR�WKH�FRPSUHVVRUV�
Evacuated each refrigerant circuit to 350 microns (-76 cm.Hg)?
Caution: Ensure the disconnect for!
26 TTA-R410A
Maintenance
Notes:
1. Perform each inspection once per month (during cooling season) while unit is operating.
Maintenance Log1
Maintenance Perform all of the indicated maintenance procedures at the intervals scheduled. This will prolong the life of the unit and reduce the possibility of costly equipment failure.
Monthly Conduct the following maintenance inspections once per month.
disconnect to prevent injury or death from electrical shock or contact with moving parts.
• ,QVSHFW�DLU�¿OWHUV�DQG�FOHDQ�LI
necessary.
• Check unit wiring to ensure all connections are tight and that the wiring insulation is intact.
• Check drain pans and condensate piping to insure they are free of obstacles.
• Manually rotate the outdoor fan to insure proper operation. Inspect the fan mounting hardware for tightness.
• Inspect the evaporator and condenser coils for dirt and debris.
If the coils appear dirty, clean them.
• With the unit operating in the cooling mode, check the suction and discharge pressures and compare them with the values provided in “Pressure Curves”.
Record these readings on the “Maintenance Log”.
• Observe indoor fan operation and correct any unusual or excessive vibration. Clean blower wheels as needed.
Annually (Cooling Season) The following maintenance procedures must be performed at the beginning of
HDFK�FRROLQJ�VHDVRQ�WR�LQVXUH�HI¿FLHQW
unit operation.
• Perform all of the monthly maintenance inspections.
• With the unit operating, check unit superheat and record the reading in the “Maintenance Log”.
• Remove any accumulation of dust and/or dirt from the unit casing.
• Remove any accumulation of dust and/or dirt from the unit casing.
• Remove corrosion from any surface and re-paint. Check the gasket around the control panel door to
LQVXUH�LW�¿WV�FRUUHFWO\�DQG�LV�LQ�JRRG
condition to prevent water leakage.
• Remove corrosion from any surface and re-paint. Check the gasket around the control panel door to
LQVXUH�LW�¿WV�FRUUHFWO\�DQG�LV�LQ�JRRG
condition to prevent water leakage.
• Inspect the evaporator fan belt. If it is worn or frayed, replace it.
• Inspect the control panel wiring to insure that all connections are tight and that the insulation is intact.
Lubricate the indoor fan motor bearings with a non-detergent, 20-weight oil. (To insure good bearing lubrication, condenser fan motor bearings should be lubricated once every six months).
Note: Some motors are permanently lubricated.
• &KHFN�UHIULJHUDQW�SLSLQJ�DQG�¿WWLQJV
for leaks.
Warning: Open and lock unit
Evaporator Ambient Entering air Compressor Superheat Subcooling
Temp Dry Wet Suction Discharge Circuit Circuit Date (F) Bulb Bulb Pressure pressure No. 1 (1) No. 1 (F)
TTA-R410A 27
Trouble Shooting
Safety recommendations To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter “Installation”.