Amendment 001.1 - Responses to RFI's 8.7.2024.xlsx

XLSX spreadsheet 38 KB Posted

Attached to
SKOV SUBSTATION TRANSFORMER PURCHASE: REQUEST FOR PROPOSAL
Solicitation number
S-R33123-00011021
Issued by
Wasco County, Oregon

About this file

This document is an amendment to a Request for Proposal (RFP) issued by Northern Wasco County PUD for the procurement of 2 transformers, 24/32/40 MVA each, for a new substation in The Dalles, Oregon. The amendment provides responses to various requests for information (RFIs) submitted by potential bidders, including clarification on transformer ratings, delivery requirements, performance bond specifications, and evaluation criteria. The PUD prefers simultaneous delivery of the transformers and may consider transformers manufactured outside the U.S., subject to exclusions on parts from certain foreign adversaries. No pre-qualifications are required to submit a proposal, but the PUD will consider past experience and references in the award determination.

The PUD will evaluate bids based on load losses, which are to be provided in an updated bid form. No-load losses may also be evaluated, but a specific dollar amount per kW has not been provided. There are no union labor requirements specified at this time. Proposals are due to the PUD, but there are no registration or qualification processes required to submit a bid.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment 001

Addendum #001.1 - RFI Responses
RFI NumberQuestionRequest DateResponse
1Will these transformers requested be replacing ones in the field or will they be new orders?7/18/24These transformers are new orders for a new substation.
2Please clarify rating and quantity of transformers being requested in this RFP.

Document 01 “RFP- NWCPUD Skov Substation Transformer Purchase” refers on page 2 under Project Description as being for Qty (2) 32/36/40 transformers.

Exhibit A – 33 73 13 Power Transformer specification on page 7 Item 2.2.A specifies transformer as being 24/32/40 MVA.7/18/24Both transformers are specified to be 24/32/40 MVA.
3Performance bond: a. What is percentage requirement ? b. Shall the bond be valid for whole warranty period too ?7/18/24The performance bond requirement is 100% of the contract value throughout the performance schedule.
4Will the PUD accept the transformers made outside the US ?7/18/24The PUD may accept transformers made outside the U.S., subject to the District's discretion. However, bids including parts procured from Foreign Adversaries (China, North Korea, Russia, Cuba, etc.) per EO 13920 will be rejected.
5Can the PUD receive the transformers at the same time , or have to deliver separately ?7/18/24We prefer that the transformers are delivered simultaneously.
6Is there any union-labor requirement at the site(s) ?7/18/24Clarification on union-labor requirements will be provided at a later date.
7Are No-Load and Load losses being evaluated as part of the bid selection process, and if they are is there a dollar amount per KW for NL and LL that will be used?7/18/24Load losses are to be provided in the updated bid form. Amendment 001.2 - Exhibit B - Revised Bid Form. The previous Exhibit B - Bid Form is overridden.
8Please confirm that "copper core" means copper windings in the coils.7/19/24"Copper core" should be understood as copper windings in the coils.
9Is it necessary that our company is registered in some database of your company to be able to send our proposal?7/19/24There are no requirements for registration in our database to submit a proposal.
10Is it necessary that our company complies with any selection or qualification process in order to submit our proposal to your company.7/19/24No pre-qualifications are required. The District will consider past experience and references in determination of award.