Alvin C York Generator Information FY21.xls
XLS spreadsheet 37 KB Posted
- Solicitation number
- 36C24921Q0588
About this file
This document contains details for a federal contract solicitation to provide emergency generator maintenance services at various facilities of the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The solicitation includes a base year and four option years of services. Specific requirements include annual and periodic maintenance for 16 generators across multiple buildings at the York, Pennsylvania campus and 5 generators across various buildings at the Nashville, Tennessee campus. Maintenance includes services such as inspections, load testing, fuel quality testing, battery replacements, and cooling system work. Pricing is to be provided for the base year and each option year by individual line item corresponding to each generator location.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24921Q0588 0003_1.docx | DOCX document | |
| 36C24921Q0588 0002_1.docx | DOCX document | |
| Line Item Breakdown Revised.xlsx | XLSX spreadsheet | |
| 36C24921Q0588 0001_1.docx | DOCX document | |
| S02-36C24921Q0588.pdf | ||
| Line Item Breakdown.xlsx | XLSX spreadsheet | |
| 36C24921Q0588.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Location | Description | Voltage | Rated Amperage | Fuel tank size (gallons) | Fuel Consumption | Full load run time | Average Load | Peak Recorded Load | Bldg. Served | Model/Serial |
| Bldg. 2 Inst. 5/12/11 | Onan/Cummins 750kw/930kva EE 110151 | 480 | 1127 30% = 338 amps | 3800 Belly tank | 50g/hr @ 100% | 80 hrs | 360 amps 172.8kw 298.9kva | 500 amps 332.5kw 415.7kva | 1, 2, 9, 120 | MOD: DQFAA-4387274 SER:F100131582 |
| Bldg. 5 Inst. 12/2015 | Kohler 500kw//625kva EE135484 | 480 | 752 30% = 225 amps | 2600 Belly tank | 35.5g/hr @ 100% | 73 hrs | 100 amps 48kw 83kva | 150 amps 72kw 124.5kva | 4, 5, 6, 107 | MOD:500REOZVC SER: SGM32CP73 |
| Bldg. 7 Inst. 4/30/03 | Generac 230kw/288kva EE 67324 | 208 | 798 30% = 239 amps | 1000 UST | 18.6g/hr @ 100% | 53 hrs | 160 amps 46.1kw 57.7kva | 210 amps 60.5kw 75kva | 7 | MOD:2665670100 SER:2068977 |
| Bldg. 8 Inst. 6/1/04 | Generac 250kw/312kva EE 72659 | 208 | 866 30% = 259 amps | 1000 UST | 20.3g/hr @ 100% | 49 hrs | 100 amps 28.75kw 36kva | 150 amps 43.25kw 54kva | 8 | MOD:2665510100 SER:2069467 |
| Bldg. 16 Inst. 11/2/12 | Onan/Cummins 250kw/312kva EE 115223 | 480 | 375.9 30% = 113amps | 1340 Belly tank | 20.3g/hr @ 100% | 49 hrs | 160 amps 76.8kw 132.8kva | 210 amps 100.8kw 174kva | 15 & 16 | MOD:DQDAA-6258531 SER:A110185070 |
| Bldg. 16 Acqd. 8/2011 | Caterpillar 1600kw/200kva EE135556 | 4160 | 278 | Natural gas fed | 1600kw | 1600kw | Entire Facility primary power-non emergency | ENGINE MOD: G3520C SER#:GZL00146 GEN.MOD.#:SR4B GEN.SER.#: 9W200986 | ||
| Bldg. 16 | Portable fuel tank EE88578 | 0 | 0 | 300 | 0 | 0 | 0 | 0 | All deisel gensets | MOD:FB312DW SER:S30134 |
| Bldg. 105 Inst. 8/1/2011 | Onan/Cummins 750kw/930kva EE 111088 | 480 | 1127 30% = 338 amps | 3800 Belly tank | 50g/hr @ 100% | 80 hrs | 280 amps 186.2kw 232.8kva | 500 amps 332.5kw 415.7kva | 3, 10, 11, 105, 117, 149 | MOD: DQFAA-5991125 SER: L100175525 |
| Bldg. 112 Inst. 6/1/04 | Caterpillar 350kw/438kva EE 72854 | 208 | 1220 30% = 366amps | 3000 Belly tank | 29.2g/hr @ 100% | 102 hrs | 560 amps 161.4kw 201.7kva | 1010 amps 291kw 363.8kva | 112, 146, & 147 | MOD:3406 SER:1DZO7276 |
| Bldg. 116 Inst. 6/1/88 | John Deere 75kw/93kva EE 60782 | 208 | 260 30% = 78amps | 400 AST | 15g/hr @ 100% | 36 hrs | 60 amps 17.2kw 21.6kva | 185 amps 53kw 66kva | 116 | MOD:HC334AS SER:P3405714 |
| 550kw Portable Purchased April 2019 | CK Power/Volvo 550kw/690kva EE155004 | 208/480 | 1950/815 30% = 245amps | 600 Belly tank | 34g/hr @100% | 17hrs | Portable | Mod: CK680VM-T4 Ser: 115563-2016123198 | ||
| 180KW Portable Acqd. 6/1/06 | Kohler/John Deere 180 KW EE 80976 | 208/240/480 | 700/650 /300 30% = 90a @ 480v | 200 Belly tank | 17g/hr @ 100% | 12 hrs | 60 ams 18kw 21.6kva | 125 amps 37.44kw 45kva | Portable | MOD:180REO2JC SER:2082925 |
&C&"-,Bold"&14Alvin C. York Generator Information
Sheet2
Sheet3