HVAC CASINGS 233119 - Page 1 of 7
SECTION 233119 - HVAC CASINGS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Factory-fabricated, field-assembled, [single- and double-wall casings for HVAC equipment.
1.2 PERFORMANCE REQUIREMENTS
A. Structural Performance:
1. Casings shall be fabricated to withstand 133 percent of the indicated static pressure without structural failure. Wall and roof deflection at the indicated static pressure shall not exceed 1/8 inch per foot of width.
B. Seismic Performance: HVAC casings shall withstand the effects of earthquake motions determined according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible".
1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified."
1.3 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: For HVAC casings. Include plans, elevations, sections, components, and attachments to other work.
C. Field quality-control reports.
1.4 QUALITY ASSURANCE
A. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 5 - "Systems and Equipment" and Section 7 - "Construction and System Start-Up."
B. ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA 90.1, Section
6.4.4 - "HVAC System Construction and Insulation."
HVAC CASINGS 233119 - Page 2 of 7
PART 2 - PRODUCTS
2.1 GENERAL CASING FABRICATION REQUIREMENTS
A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 9, "Equipment and Casings," for acceptable materials, material thicknesses, and casing construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.
1. Fabricate casings with more than 3-inch wg negative static pressure according to SMACNA's "Rectangular Industrial Duct Construction Standards."
2. Casings with more than 2-inch wg positive static pressure may be fabricated according to SMACNA's "Rectangular Industrial Duct Construction Standards."
B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.
1. Exterior Surface Galvanized Coating Designation: G60.
2. Interior Surface Galvanized Coating Designation:
a. Sections Not Exposed to Moisture: G60.
b. Sections Housing and Downstream from Cooling Coil and Humidifiers: G90.
C. Reinforcement Shapes and Plates: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.
D. Sealing Requirement: SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Seal Class A. Seal all seams, joints, connections, and abutments to building.
E. Penetrations: Seal all penetrations airtight. Cover with escutcheons and gaskets, or fill with suitable compound so there is no exposed insulation. Comply with requirements for escutcheons specified in Division 23 Section "Escutcheons for HVAC Piping." Provide shaft seals where fan shafts penetrate casing.
F. Access Doors: Fabricate access doors according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 9-15, "Casing Access Doors - 2-inch wg (500 Pa)," and Figure 9-16, "Casing Access Doors - 3-10-inch wg (750-2500 Pa)"; and according to pressure class of the plenum or casing section in which access doors are to be installed.
1. Size: 20 by 54 inches.
2. Vision Panel: Double-glazed, wire-reinforced safety glass with an airspace between panes and sealed with interior and exterior rubber seals.
3. Hinges: Piano or butt hinges and latches, number and size according to SMACNA's
"HVAC Duct Construction Standards - Metal and Flexible."
4. Latches: Minimum of two wedge-lever-type latches, operable from inside and outside.
5. Neoprene gaskets around entire perimeters of door frames.
6. Doors shall open against air pressure.
HVAC CASINGS 233119 - Page 3 of 7
G. Condensate Drain Pans: Formed sections of G90 coated, galvanized sheet steel complying with requirements in ASHRAE 62.1. Pans shall extend a minimum of 12 inches past coil.
1. Double-wall construction shall have space between walls filled with foam insulation and sealed moisture tight.
2. Intermediate drain pan or drain trough shall collect condensate from top coil for units with stacked coils or stacked eliminators.
3. Insulation: Polystyrene or polyurethane.
4. Slopes shall be in a minimum of two planes to collect condensate from cooling coils
(including coil piping connections and return bends), eliminators, and humidifiers when units are operating at maximum catalogued face velocity across cooling coil.
5. Each drain pan connection shall have a trap. Drain traps with depth and height differential between inlet and outlet equal or greater to the design static pressure plus 2-inch wg. Include slab height in trap calculation.
2.2 MANUFACTURED CASINGS
A. Description: Double-wall, insulated, pressurized equipment casing.
B. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. Acoustical Surfaces, Inc.
2. AeroSonics, Inc.; a division of TUTCO, Inc.
3. Buffalo Air Handling.
4. CertainTeed Corp.; Insulation Group.
5. CLEANPAK International.
6. D&D Sound Control.
7. IACL.
8. Industrial Noise Control, Inc.
9. McGill AirSilence LLC.
10. SEMCO Incorporated.
11. Vibro-Acoustics.
C. Double-Wall Panel Fabrication: Solid, galvanized sheet steel exterior wall and solid, galvanized sheet steel interior wall; with space between wall filled with insulation.
1. Wall Thickness: 2 inches.
2. Fabricate with a minimum number of joints.
3. Weld exterior and interior walls to perimeter; to interior, longitudinal, galvanized-steel channels; and to box-end internal closures. Paint welds.
4. Sheet metal thickness shall comply with SMACNA's "HVAC Duct Construction
Standards - Metal and Flexible" for static-pressure class indicated for casing.
5. Sheet Metal Thicknesses:
a. Exterior Wall Thickness: 0.040 inch minimum.
b. Interior Wall Thickness: 0.034 inch minimum.
6. Double-Wall Casing Inner Panel: Solid sheet steel.
HVAC CASINGS 233119 - Page 4 of 7
7. Fill each panel assembly with insulating material that is noncombustible, inert, mildew resistant, and vermin proof and that complies with NFPA 90A.
8. Fabricate panels with continuous tongue-and-groove or self-locking joints effective inside and outside each panel.
D. Trim Items: Fabricate from a minimum of 0.052-inch galvanized sheet steel, furnished in standard lengths for field cutting.
2.3 CASING LINER
A. Flexible-Elastomeric Casing Liner: Preformed, cellular, closed-cell, sheet materials complying with ASTM C 534, Type II, Grade 1, and with NFPA 90A or NFPA 90B.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Aeroflex USA Inc.
b. Armacell LLC.
c. Rubatex International, LLC.
d. Available thicknesses are 3/8, 1/2, 3/4, and 1 inch (9.5, 13, 19, and 25 mm).
Indicate thickness on Drawings.
2. Surface-Burning Characteristics: Maximum flame-spread index of 25 and maximum smoke-developed index of 50 when tested according to UL 723; certified by an NRTL.
3. Liner Adhesive: As recommended by insulation manufacturer and complying with NFPA 90A or NFPA 90B.
a. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
b. Adhesive shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."
B. Insulation Pins and Washers:
1. Cupped-Head, Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully annealed for capacitor-discharge welding, 0.106-inch- diameter shank, length to suit depth of insulation indicated with integral 1-1/2-inch galvanized carbon-steel washer.
2. Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch- thick, galvanized steel, with beveled edge sized as required to hold insulation securely in place but not less than 1-1/2 inches in diameter.
C. Shop or Factory Application of Casing Liner: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 7-11, "Flexible Duct Liner Installation."
HVAC CASINGS 233119 - Page 5 of 7
1. Adhere a single layer of indicated thickness of casing liner with at least 90 percent adhesive coverage at liner contact surface area. Attaining indicated thickness with multiple layers of casing liner is prohibited.
2. Apply adhesive to transverse edges of liner facing upstream that do not receive metal nosing.
3. Butt transverse joints without gaps, and coat joint with adhesive.
4. Fold and compress liner in corners of casings or cut and fit to ensure butted-edge overlapping.
5. Apply adhesive coating on longitudinal seams in casings with air velocity of 2500 fpm.
6. Secure liner with mechanical fasteners 4 inches from corners and at intervals not exceeding 12 inches transversely; at 3 inches from transverse joints and at intervals not exceeding 18 inches longitudinally.
7. Secure transversely oriented liner edges facing the airstream with metal nosings that have either channel or "Z" profiles or are integrally formed from casing wall. Fabricate edge facings at the following locations:
a. Fan discharges.
b. Intervals of lined casing preceding unlined duct.
c. Upstream edges of transverse joints in casings where air velocities are higher than
2500 fpm or where indicated.
8. Secure insulation between perforated sheet metal inner wall of same thickness as specified for outer wall. Use mechanical fasteners that maintain inner wall at uniform distance from outer wall without compressing insulation.
2.4 SEALANT MATERIALS
A. General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index of 50 when tested according to UL 723; certified by an NRTL.
B. Water-Based Joint and Seam Sealant:
1. Application Method: Brush on.
2. Solids Content: Minimum 65 percent.
3. Shore A Hardness: Minimum 20.
4. Water resistant.
5. Mold and mildew resistant.
6. VOC: Maximum 75 g/L (less water).
7. For indoor applications, use sealant that has a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
8. Sealant shall comply with the testing and product requirements of the California
Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."
9. Maximum Static-Pressure Class: 10-inch wg, positive or negative.
10. Service: Indoor or outdoor.
11. Substrate: Compatible with galvanized sheet steel.
HVAC CASINGS 233119 - Page 6 of 7
C. Flanged Joint Sealant: Comply with ASTM C 920.
1. General: Single component, acid curing, silicone, elastomeric.
2. Type: S.
3. Grade: NS.
4. Class: 25.
5. Use: O.
6. For indoor applications, use sealant that has a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
7. Sealant shall comply with the testing and product requirements of the California
Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."
D. Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install casings according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
B. Apply sealant to joints, connections, and mountings.
C. Field-cut openings for pipe and conduit penetrations; insulate and seal according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
D. Support casings on floor or foundation system. Secure and seal to base.
E. Support components rigidly with ties, braces, brackets, and anchors of types that will maintain housing shape and prevent buckling.
F. Align casings accurately at connections, with 1/8-inch misalignment tolerance and with smooth interior surfaces.
3.2 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. Perform field tests and inspections according to SMACNA's "HVAC Air Duct Leakage Test Manual."
2. Test the following systems:
a. Systems required by ASHRAE/IESNA 90.1.
b. Supply Air: 50 percent of total installed duct area with a pressure class of 3-inch wg or higher.
HVAC CASINGS 233119 - Page 7 of 7
3. Conduct tests at static pressures equal to maximum design pressure of system or section being tested. If pressure classes are not indicated, test entire system at maximum system design pressure. Do not pressurize systems above maximum design operating pressure.
Give seven days' advance notice for testing.
4. Determine leakage from entire system or section of system by relating leakage to surface area of test section. Comply with requirements for leakage classification of ducts connected to casings.
5. Disassemble, reassemble, and seal segments of systems to accommodate leakage testing and for compliance with test requirements.
B. HVAC casings will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports.
3.3 CLEANING
A. Comply with in Division 23 Section "Metal Ducts."
END OF SECTION 233119