A&E ARCHITECTS P.C. US DEPARTMENT OF AGRICULTURE
IDAHO PANHANDLE NATIONAL FOREST
INRC WAREHOUSE (NORTH) AND SITE WORK – PHASE I
COEUR D’ALENE, IDAHO
DOOR HARDWARE 087100 - 1
SECTION 087100 - DOOR HARDWARE
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Commercial door hardware for the following:
a. Doors to the extent indicated.
2. Electrified door hardware.
B. Related Sections include the following:
1. Division 08 Section "Hollow Metal Doors and Frames"
2. Division 08 Section “Wood Doors”
3. Division 28 Section “Access Control”
1.3 SUBMITTALS
A. Product Data: Include construction and installation details, material descriptions, dimensions of individual components and profiles, and finishes.
B. Shop Drawings: Details of electrified door hardware, indicating the following:
1. Wiring Diagrams: Power, signal, and control wiring. Include the following:
a. System schematic.
b. Point-to-point wiring diagram.
c. Riser diagram.
d. Elevation of each door.
2. Detail interface between electrified door hardware and access control system.
3. Operation Narrative: Describe the operation of doors controlled by electrified door hardware.
C. Samples for Initial Selection: For each finish, color, and texture required for each type of door hardware indicated.
D. Samples for Verification: For exposed door hardware of each type, in specified finish, full size. Tag with full description for coordination with the door hardware sets. Submit Samples before, or concurrent with, submission of the final door hardware sets as requested by the Architect.
mshoup Text Box Amendment #5.
DOOR HARDWARE 087100 - 2
1. Samples will be returned to Contractor. Units that are acceptable and remain undamaged through submittal, review, and field comparison process may, after final check of operation, be incorporated into the Work, within limitations of keying requirements.
E. Product Certificates: For electrified door hardware, signed by product manufacturer.
F. Qualification Data: For Installer and Architectural Hardware Consultant.
G. Product Test Reports: Based on evaluation of comprehensive tests performed by manufacturer and witnessed by a qualified testing agency, for locks.
H. Maintenance Data: For each type of door hardware to include in maintenance manuals. Include final hardware schedule.
I. Warranty: Special warranty specified in this Section.
J. Other Action Submittals:
1. Door Hardware Sets: Prepared by or under the supervision of Architectural Hardware
Consultant, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final door hardware sets with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.
a. Format: Comply with scheduling sequence and vertical format in DHI's "Sequence and Format for the Hardware Schedule." Double space entries, and number and date each page.
b. Format: Use same scheduling sequence and format and use same door numbers as in the Contract Documents.
c. Content: Include the following information:
1) Identification number, location, hand, fire rating, and material of each door and frame.
2) Type, style, function, size, quantity, and finish of each door hardware item. Include description and function of each lockset and exit device.
3) Complete designations of every item required for each door or opening including name and manufacturer.
4) Fastenings and other pertinent information.
5) Location of each door hardware set, cross-referenced to Drawings, both on floor plans and in door and frame schedule.
6) Explanation of abbreviations, symbols, and codes contained in schedule.
7) Mounting locations for door hardware.
8) Door and frame sizes and materials.
9) Description of each electrified door hardware function, including location, sequence of operation, and interface with other building control systems.
a) Sequence of Operation: Include description of component functions that occur in the following situations: authorized person wants to enter; authorized person wants to exit; unauthorized person wants to enter; unauthorized person wants to exit.
10) List of related door devices specified in other Sections for each door and frame.
d. Submittal Sequence: Submit initial draft of final schedule along with essential Product
Data to facilitate the fabrication of other work that is critical in Project construction schedule. Submit the final door hardware sets after Samples, Product Data, coordination
DOOR HARDWARE 087100 - 3
with Shop Drawings of other work, delivery schedules, and similar information has been completed and accepted.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: An employer of workers trained and who have been installing door hardware for at least five years.
1. Installer's responsibilities include installing door hardware and being available during the course of the Work to consult with Contractor, Architect, and Contracting Officer about door hardware.
B. Supplier Qualifications: A distributor of commercial door hardware in the project vicinity for at least five years. The supplier must have a factory direct status with the approved manufacturers and have an Architectural Hardware Consultant on staff.
C. Architectural Hardware Consultant Qualifications: A person who is currently certified by DHI as an Architectural Hardware Consultant and who is experienced in providing consulting services for door hardware installations that are comparable in material, design, and extent to that indicated for this Project.
D. Source Limitations: Obtain each type and variety of door hardware from a single manufacturer, unless otherwise indicated.
1. Provide electrified door hardware from same manufacturer as mechanical door hardware, unless otherwise indicated.
E. Electrified Door Hardware: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
F. Preinstallation Conference: Conduct conference at Project site to comply with requirements in Division 01 Section "Project Management and Coordination." Review methods and procedures related to electrified door hardware including, but not limited to, the following:
1. Inspect and discuss electrical roughing-in and other preparatory work performed by other trades.
2. Review sequence of operation for each type of electrified door hardware.
3. Review and finalize construction schedule and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.
4. Review required testing, inspecting, and certifying procedures.
G. Keying conference:
1. Upon approval of hardware schedule and before ordering locking hardware and key system, conduct a keying meeting complying with Division 01 Section “Project Management and Coordination.”
2. Discuss key system requirements and incorporate decisions made during the meeting into the keying schedule submittal.
a. Review each locking function and determine degree of security required at each opening.
b. Review function of building, flow of traffic, and purpose of each area.
DOOR HARDWARE 087100 - 4
c. Determine degree of security at each opening.
d. Determine requirements for future expansion.
e. Discuss requirements for shipping and delivery of keys and cylinders/cores.
f. Discuss requirements to interface new cylinders/cores with owner’s existing key system.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Inventory door hardware on receipt and provide secure lock-up for door hardware delivered to Project site.
B. Tag each item or package separately with identification related to the final door hardware sets, and include basic installation instructions, templates, and necessary fasteners with each item or package.
1.6 COORDINATION
A. Templates: Distribute door hardware templates for doors, frames, and other work specified to be factory prepared for installing door hardware. Check Shop Drawings of other work to confirm that adequate provisions are made for locating and installing door hardware to comply with indicated requirements.
B. Electrical System Roughing-in: Coordinate layout and installation of electrified door hardware with connections to power supplies and access control system.
1.7 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of door hardware which fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures including excessive deflection, cracking, or breakage.
b. Faulty operation of operators and door hardware.
c. Deterioration of metals, metal finishes, and other materials beyond normal weathering and use.
d. Ordinary wear and tear shall not be excluded from any warranty since the hardware should hold up to normal use.
2. Warranty Period: One year from date of Substantial Completion, except as follows:
a. Exit Devices: 10 years from date of Substantial Completion.
b. Manual Closers: 10 years from date of Substantial Completion.
c. Locksets: 10 years from date of Substantial Completion.
d. Auto Operators: 2 years from date of Substantial Completion.
e. Electronic Hardware: 1 year from date of Substantial Completion.
1.8 MAINTENANCE SERVICE
DOOR HARDWARE 087100 - 5
A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Contracting Officer 's continued adjustment, maintenance, and removal and replacement of door hardware.
PART 2 - PRODUCTS
2.1 SCHEDULED DOOR HARDWARE
A. General: Provide door hardware for each door to comply with requirements in this Section and door hardware sets indicated in door and frame schedule.
1. Door Hardware Sets: Provide quantity, item, size, finish or color indicated, and products complying with BHMA standard referenced.
2. Sequence of Operation: Provide electrified door hardware function, sequence of operation, and interface with other building control systems indicated.
2.2 LOCKS AND LATCHES, GENERAL
A. Accessibility Requirements: Where indicated to comply with accessibility requirements, comply with the U.S. Architectural & Transportation Barriers Compliance Board's "Americans with Disabilities Act (ADA), Accessibility Guidelines for Buildings and Facilities (ADAAG)."
1. Provide operating devices that do not require tight grasping, pinching, or twisting of the wrist and that operate with a force of not more than 5 lbf (22 N).
B. Latches and Locks for Means of Egress Doors: Comply with NFPA 101. Latches shall not require more than 15 lbf (67 N) to release the latch. Locks shall not require use of a key, tool, or special knowledge for operation.
C. Electrified Locking Devices: BHMA A156.25.
D. Lock Trim:
1. Levers: Cast.
2. Escutcheons (Roses): Stamped.
3. Dummy Trim: Match lever lock trim and escutcheons.
4. Lockset Designs: Falcon ‘Avalon-Gala.
E. Rabbeted Meeting Doors: Provide special rabbeted front and strike on locksets for rabbeted meeting stiles.
F. Backset: 2-3/4 inches (70 mm), unless otherwise indicated.
G. Strikes: Manufacturer's standard strike with strike box for each latchbolt or lock bolt, with curved lip extended to protect frame, finished to match door hardware set, and as follows:
1. Flat-Lip Strikes: For locks with three-piece antifriction latchbolts, as recommended by manufacturer.
2. Extra-Long-Lip Strikes: For locks used on frames with applied wood casing trim.
3. Aluminum-Frame Strike Box: Manufacturer's special strike box fabricated for aluminum framing.
DOOR HARDWARE 087100 - 6
2.3 KEYING
A. Key cylinders into a Schlage Everest Primus 29 XP master key system or equivalent by Medeco. All cylinders shall be meet UL437 security requirements. Furnish final keying system as directed by Contracting Officer.
1. Split Key Temporary Keying: Provide conventional type cylinders with “Split Key” type construction keying for the construction period.
a. Temporary plastic cores or keys are not allowed.
2. All keys shall be stamped with “Government Property Do Not Duplicate”.
3. Furnish the following key quantities:
a. Construction keys: (12) keys.
b. Master keys: (6) keys.
c. Change keys: (3) per lock or cylinder.
d. Spare keys: (10) keys to be added to building inventory.
e. Split Key Extractor Tool: (2)
2.4 PANIC HARDWARE
A. Provide exit devices tested to ANSI/BHMA A156.3 Grade 1, and UL listed for Panic Exit or Fire Exit Hardware. Cylinders: Refer to “KEYING” article, herein.
B. Provide touchpad type exit devices, fabricated of brass, bronze, stainless steel, or aluminum, plated to standard architectural finishes to match balance of door hardware.
C. Touchpad: Extend minimum of one half of door width. Match exit device finish, stainless steel for US26, US26D, US28, US32, and US32D finishes; and for all other finishes, provide compatible finish to exit device. Provide compression springs in devices, latches, and outside trims or controls; tension springs also acceptable.
D. Provide exit devices with deadlatching feature for security and for future addition of alarm kits and/or other electrified requirements.
E. Provide exit devices with manufacturer’s approved strikes.
F. Provide exit devices cut to door width and height. Locate exit devices at height recommended by exit device manufacturer, allowable by governing building codes, and approved by Architect.
2.5 CLOSERS
A. Accessibility Requirements: Where handles, pulls, latches, locks, and other operating devices are indicated to comply with accessibility requirements, comply with the U.S. Architectural & Transportation Barriers Compliance Board’s “Americans with Disabilities Act (ADA), Accessibility Guidelines for Buildings and Facilities (ADAAG).”
DOOR HARDWARE 087100 - 7
B. Size of Units: Unless otherwise indicated, comply with manufacturer’s written recommendations for size of door closers depending on size of door, exposure to weather, and anticipated frequency of use.
Provide factory-sized closers, adjustable to meet field conditions and requirements for opening force.
C. Surface Closers: BHMA A156.4, Grade 1 Provide type of arm required for closer to be located on non-public side of door, unless otherwise indicated.
D. Closer arms shall be extra duty where noted in the hardware schedule.
2.6 AUTOMATIC OPERATORS
A. Provide low energy automatic operator units with hydraulic closer complying with ANSI/BHMA A156.19.
B. Hydraulic Fluid: Fireproof, passing requirements of UL10C, and requiring no seasonal closer adjustment for temperatures ranging from 120 degrees F to -30 degrees F.
C. Provide units with conventional door closer opening and closing forces unless power operator motor is activated. Provide door closer assembly with adjustable spring size, back-check, and opening and closing speed adjustment valves to control door
D. Provide units with on/off switch for manual operation, motor start up delay, vestibule interface delay, electric lock delay, and door hold open delay.
E. Provide units with conventional door closer opening and closing forces unless power operator motor is activated. Provide door closer assembly with adjustable spring size, back-check valve, sweep valve, latch valve to control door.
F. Provide drop plates, brackets, or adapters for arms as required for details.
G. Provide hard-wired actuator switches for operation as specified.
H. Provide weather-resistant actuators at exterior applications.
I. Provide complete assemblies of controls, switches, power supplies, relays, and parts/material recommended and approved by manufacturer of automatic operator for each individual leaf. Actuators control both doors simultaneously at pairs. Sequence operation of exterior and vestibule doors with automatic operators to allow ingress or egress through both sets of openings as directed by Architect.
Locate actuators, key switches, and other controls as directed by Architect.
2.7 MISCELLANEOUS DOOR HARDWARE
A. Boxed Power Supplies: Modular unit in NEMA ICS 6, Type 4 enclosure; filtered and regulated; voltage rating and type matching requirements of door hardware served; and listed and labeled for use with fire alarm systems.
2.8 FABRICATION
A. Base Metals: Produce door hardware units of base metal, fabricated by forming method indicated, using manufacturer’s standard metal alloy, composition, temper, and hardness. Furnish metals of a
DOOR HARDWARE 087100 - 8
quality equal to or greater than that of specified door hardware units and BHMA A156.18. Do not furnish manufacturer’s standard materials or forming methods if different from specified standard.
B. Fasteners: Provide door hardware manufactured to comply with published templates generally prepared for machine, wood, and sheet metal screws. Provide screws according to commercially recognized industry standards for application intended, except aluminum fasteners are not permitted.
Provide Phillips flat-head screws with finished heads to match surface of door hardware, unless otherwise indicated.
1. Concealed Fasteners: For door hardware units that are exposed when door is closed, except for units already specified with concealed fasteners. Do not use through bolts for installation where bolt head or nut on opposite face is exposed unless it is the only means of securely attaching the door hardware. Where through bolts are used on hollow door and frame construction, provide sleeves for each through bolt.
2. Spacers or Sex Bolts: For through bolting of hollow-metal doors.
2.9 FINISHES
A. Standard: BHMA A156.18, as indicated in door hardware sets.
B. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
C. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
2.10 ACCEPTABLE MANUFACTURERS
A. Substitutions to the list below will be considered if submitted at least (7) days prior to bid date and on a standard CSI substitution request form. Include documentation to show that the requested approval is equal to or performs better than the specified products.
Product Specified Manufacturer Approved Manufacturer
Hinges Ives (IVE) Bommer, Stanley
Power Transfers Von Duprin (VON) Stanley
Flushbolts, Dust Proof Strikes, Coordinators
Door Controls (DCI) Ives, Trimco
Locksets Falcon (FAL) Best, Dorma
Panic Hardware Falcon (FAL) Precision/Stanley, Dorma
Cylinders/Keying Schlage (SCH) Medeco
DOOR HARDWARE 087100 - 9
Decorative Pulls Forms+Surfaces (FOR) Rockwood
Push/Pulls Ives (IVE) Tice, Trimco
Closers Falcon (FAL) Norton
Auto Operators & Components
LCN Norton
Overhead Stops Glynn Johnson (GLY) ABH, Rixson
Edge Astragals National Guard (NGP) Markar
Wall Stops Ives (IVE) Trimco
Kickplates Ives (IVE) Tice, Trimco
Thresholds, Seals, Door Bottoms
National Guard (NGP) Pemko
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine doors and frames, with Installer present, for compliance with requirements for installation tolerances, labeled fire door assembly construction, wall and floor construction, and other conditions affecting performance.
B. Examine roughing-in for electrical power systems to verify actual locations of wiring connections before electrified door hardware installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Steel Doors and Frames: Comply with DHI A115 Series.
1. Surface-Applied Door Hardware: Drill and tap doors and frames according to ANSI A250.6.
3.3 INSTALLATION
A. Mounting Heights: Mount door hardware units at heights indicated as follows unless otherwise indicated or required to comply with governing regulations.
1. Standard Steel Doors and Frames: DHI's "Recommended Locations for Architectural Hardware for Standard Steel Doors and Frames."
DOOR HARDWARE 087100 - 10
2. Wood Doors: DHI WDHS.3, "Recommended Locations for Architectural Hardware for Wood Flush Doors."
B. Install each door hardware item to comply with manufacturer's written instructions. Where cutting and fitting are required to install door hardware onto or into surfaces that are later to be painted or finished in another way, coordinate removal, storage, and reinstallation of surface protective trim units with finishing work specified in Division 09 Sections. Do not install surface-mounted items until finishes have been completed on substrates involved.
1. Set units level, plumb, and true to line and location. Adjust and reinforce attachment substrates as necessary for proper installation and operation.
2. Drill and countersink units that are not factory prepared for anchorage fasteners. Space fasteners and anchors according to industry standards.
C. Boxed Power Supplies: Locate power supplies as indicated or, if not indicated, above accessible ceilings. Verify location with Architect.
1. Configuration: Provide the least number of power supplies required to adequately serve doors with electrified door hardware.
3.4 FIELD QUALITY CONTROL
A. Independent Architectural Hardware Consultant: Contractor will engage a qualified independent Architectural Hardware Consultant to perform inspections and to prepare inspection reports.
1. Independent Architectural Hardware Consultant will inspect door hardware and state in each report whether installed work complies with or deviates from requirements, including whether door hardware is properly installed and adjusted.
3.5 ADJUSTING
A. Initial Adjustment: Adjust and check each operating item of door hardware and each door to ensure proper operation or function of every unit. Replace units that cannot be adjusted to operate as intended. Adjust door control devices to compensate for final operation of heating and ventilating equipment and to comply with referenced accessibility requirements.
1. Door Closers: Unless otherwise required by authorities having jurisdiction, adjust sweep period so that, from an open position of 70 degrees, the door will take at least 3 seconds to move to a point 3 inches (75 mm) from the latch, measured to the leading edge of the door.
B. Occupancy Adjustment: Approximately three months after date of Substantial Completion, Installer shall examine and readjust, including adjusting operating forces, each item of door hardware as necessary to ensure function of doors, door hardware, and electrified door hardware.
3.6 CLEANING AND PROTECTION
A. Clean adjacent surfaces soiled by door hardware installation.
B. Clean operating items as necessary to restore proper function and finish.
DOOR HARDWARE 087100 - 11
C. Provide final protection and maintain conditions that ensure that door hardware is without damage or deterioration at time of Substantial Completion.
3.7 DEMONSTRATION
A. Engage a factory-authorized service representative to train Contracting Officer's maintenance personnel to adjust, operate, and maintain door hardware and door hardware finishes. Refer to Division 01
Section "Demonstration and Training."
3.8 HARDWARE SETS – See Next Page
DOOR HARDWARE 087100 - 12
Hardware Group No. 01 For use on mark/door #(s):
113.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HW HINGE 5BB1HW 4.5 X 4.5 NRP 630 IVE
1 EA POWER TRANSFER EPT10 689 VON
1 EA ELEC PANIC
HARDWARE
RX-EL-25-R-NL 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY PS914 900-2RS LGR VON
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
DIAGRAM
BY SECURITY CONTRACTOR
Operational Description
1. Free egress at all times.
2. Authorized credential momentarily retracts latchbolt, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
5. On loss of power, electrified hardware is disabled. Door is latched. Trim remains secure.
6. Opening requires integration with access control system.
Hardware Group No. 01.01
122A.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HW HINGE 5BB1HW 4.5 X 4.5 NRP 630 IVE
1 EA PANIC HARDWARE 25-R-NL 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
DOOR HARDWARE 087100 - 13
Hardware Group No. 02
116.1 117.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA STOREROOM LOCK MA581L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
1 EA DOOR POSITION
SWITCH
1076D SEN
1. Door Contact monitors when door opens and closes.
2. Opening requires integration with access control system.
Hardware Group No. 03
125.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
2 EA HINGE 5BB1 4.5 X 4.5 630 IVE
1 EA ELECTRIC HINGE 5BB1 4.5 X 4.5 TW8 630 IVE
1 EA EU STOREROOM
LOCK
MA881L-RX AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA WALL STOP WS406/407CCV 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY BY SECURITY CONTRACTOR
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
DOOR HARDWARE 087100 - 14
2. Authorized credential momentarily releases outside lever, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
Hardware Group No. 04
118.1 126.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
2 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA ELECTRIC HINGE 5BB1 4.5 X 4.5 TW8 630 IVE
1 EA EU STOREROOM
LOCK
MA881L-RX AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY BY SECURITY CONTRACTOR
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
2. Authorized credential momentarily releases outside lever, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
Hardware Group No. 05
123.2
EACH TO HAVE:
DOOR HARDWARE 087100 - 15
Qty Description Catalog Number FIN Mfr
2 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA ELECTRIC HINGE 5BB1 4.5 X 4.5 TW8 630 IVE
1 EA EU STOREROOM
LOCK
MA881L-RX AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA ARMOR PLATE 8400 34" X 2" LDW B-CS 630 IVE
1 EA WALL STOP WS401/402CCV 626 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY BY SECURITY CONTRACTOR
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
2. Authorized credential momentarily releases outside lever, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
Hardware Group No. 06
123.1 123.3
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA ARMOR PLATE 8400 34" X 2" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GY IVE
Hardware Group No. 07
124.2
DOOR HARDWARE 087100 - 16
6 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
2 EA CONSTANT LATCHING
FLUSH BOLT
845 626 DCI
1 EA DUST PROOF STRIKE DP1 626 IVE
1 EA STOREROOM LOCK MA581L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA COORDINATOR COR X FL X MB AS REQ'D 628 IVE
2 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
2 EA ARMOR PLATE 8400 34" X 1" LDW B-CS 630 IVE
1 EA DRIP CAP 16A CL NGP
1 SET SEALS 700NA @ HEAD & JAMBS CL NGP
1 EA OVERLAPPING
ASTRAGAL
139SP 600 NGP
2 EA DOOR SWEEP C627A CL NGP
1 EA THRESHOLD 425HD AL NGP
2 EA DOOR POSITION
SWITCH
1076D SEN
1. Door Contact monitors when door opens and closes.
2. Opening requires integration with access control system.
Hardware Group No. 08
112.1 123A.1 129.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
Hardware Group No. 09
125.3
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
DOOR HARDWARE 087100 - 17
Hardware Group No. 10
103.1 103.2
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
Hardware Group No. 11
101.2 103.4
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
Hardware Group No. 12
121.1 121.2
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
HOLD OPEN)
SC71 HW/PA 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
Hardware Group No. 13
DOOR HARDWARE 087100 - 18
103A.1
Qty Description Catalog Number FIN Mfr
6 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA MANUAL FLUSH BOLT FB358
(TOP BOLT ONLY)
626 IVE
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
2 EA OH STOP 450S 630 GLY
2 EA SILENCER SR64 GY IVE
Hardware Group No. 14
124.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
6 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA CONSTANT LATCHING
FLUSH BOLT
(TOP BOLT ONLY)
626 DCI
1 EA CLASSROOM LOCK MA561L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA COORDINATOR COR X FL X MB AS REQ'D 628 IVE
2 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
2 EA ARMOR PLATE 8400 34" X 1" LDW B-CS 630 IVE
Hardware Group No. 15
104.1 105.1 106.1 127.1 128.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA OFFICE LOCK MA521L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
Hardware Group No. 16
103.3 107.1 109.1 126.2
DOOR HARDWARE 087100 - 19
2 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA ELECTRIC HINGE 5BB1 4.5 X 4.5 TW8 652 IVE
1 EA EU STOREROOM
LOCK
MA881L-RX AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GY IVE
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY BY SECURITY CONTRACTOR
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
2. Authorized credential momentarily releases outside lever, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
Hardware Group No. 17
202.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
2 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA ELECTRIC HINGE 5BB1 4.5 X 4.5 TW8 652 IVE
1 EA EU STOREROOM
LOCK
MA881L-RX AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
3 EA SILENCER SR64 GY IVE
1 EA CARD READER BY SECURITY CONTRACTOR
1 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY BY SECURITY CONTRACTOR
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
DOOR HARDWARE 087100 - 20
2. Authorized credential momentarily releases outside lever, allowing entry.
3. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
4. Door Contact monitors when door opens and closes.
Hardware Group No. 18
201.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA STOREROOM LOCK MA581L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
1 EA SURFACE CLOSER (W/
SPRING STOP)
SC71 SS 689 FAL
Hardware Group No. 19
203.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
6 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA MANUAL FLUSH BOLT FB358
(TOP BOLT ONLY)
626 IVE
1 EA STOREROOM LOCK MA581L AG 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
2 EA OH STOP 450S 630 GLY
Hardware Group No. 20
119.1 120.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HW HINGE 5BB1HW 4.5 X 4.5 652 IVE
1 EA PUSH PLATE 8200 6" X 16" 630 IVE
1 EA PULL PLATE 8303 10" 6" X 16" 630 IVE
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
DOOR HARDWARE 087100 - 21
Hardware Group No. 21
114.1 115.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HW HINGE 5BB1HW 4.5 X 4.5 630 IVE
1 EA PUSH PLATE 8200 6" X 16" 630 IVE
1 EA PULL PLATE 8303 10" 6" X 16" 630 IVE
1 EA SURFACE CLOSER SC71 RW/PA
(INSTALL CLOSER ON PULL SIDE)
689 FAL
Hardware Group No. 22
110.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA PRIVACY LOCK MA301 AG 626 FAL
1 EA SURFACE CLOSER SC71 RW/PA 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
DOOR HARDWARE 087100 - 22
Hardware Group No. AL-01
101.1
EACH TO HAVE:
Qty Description Catalog Number FIN Mfr
2 EA CONT. HINGE 112HD EPT 628 IVE
2 EA POWER TRANSFER EPT10 689 VON
1 EA ELEC PANIC
HARDWARE
RX-EL-24-C-C-718 626 FAL
1 EA ELEC PANIC
HARDWARE
RX-EL-24-C-EO 626 FAL
1 EA PRIMUS MORT. CYL. 20-500 XP X CAM AS REQ'D 626 SCH
2 EA DOOR PULL 920003-36" X (2) 920014 STAND-OFF 630 FOR
1 EA OH STOP 100S ADJ 630 GLY
1 EA OH STOP 100SE ADJ
(USE WITH AUTO OPERATOR)
630 GLY
1 EA SURFACE CLOSER SC71 RW/PA
(INSTALL TOP JAMB)
689 FAL
1 EA SURF. AUTO
OPERATOR
4642 WMS 689 LCN
1 SET CLOSER BRACKET(S) AS REQ'D TO INSTALL CLOSER 689 FAL
1 EA WEATHER RING 8310-801 PLA LCN
2 EA ACTUATOR, WALL
MOUNT
8310-853T 630 LCN
2 EA FLUSH MOUNT BOX 8310-867F 689 LCN
1 SET AUTO OPERATOR
BRACKETS
AS REQ'D TO INSTALL AUTO OPER LCN
1 EA SEALS DOOR/FRAME MFG STANDARD
2 EA DOOR SWEEP DOOR/FRAME MFG STANDARD
1 EA THRESHOLD 425HD AL NGP
1 EA CARD READER BY SECURITY CONTRACTOR
2 EA DOOR POSITION
SWITCH
1076D SEN
1 EA POWER SUPPLY PS914 900-2RS LGR VON
1 SET WIRING, PT TO PT
DIAGRAM &
ELEVATION
A) SET OVERHEAD STOP TO STOP THE DOOR JUST AFTER THE OPERATOR REACHES FULL OPEN
POINT.
DOOR HARDWARE 087100 - 23
2. Authorized credential momentarily retracts latchbolt, allowing entry.
3. During open hours, access control system time clock electrically keeps latch retracted, allowing entry.
4. Outer actuator is disabled after hours by access control time clock. Valid credential at card reader enables outer actuator.
5. Inner actuator is always enabled.
6. If door is latched when enabled actuator is depressed, operator retracts latches prior to opening.
7. RX switch (Integral to locking hardware) will shunt the door contact and allow for authorized egress.
8. Door Contact monitors when door opens and closes.
9. On loss of power, electrified hardware is disabled. Door is latched. Trim remains secure.
10. Opening requires integration with access control system.
Hardware Group No. OH-01
125.2
EACH TO HAVE:
1 SET CYLINDER(S) AS REQ'D BY LOCKING MECHANISM 626
A) BALANCE OF HARDWARE BY OVERHEAD DOOR MANUFACTURER.
END OF SECTION