Addendum 4. 271313 - Communications Copper Backbone Cabling.pdf

PDF 277 KB Posted

Attached to
Palmer Courthouse Expansion Construction
Solicitation number
Not on record
Issued by
Matanuska-Susitna Borough, Alaska

About this file

This is an Addendum to technical specifications for the Palmer Courthouse Renovation & Expansion project, prepared by Stantec for the Alaska Court System. Section 271313 establishes comprehensive requirements for communications copper backbone cabling installation, including Category 6 and Category 6a unshielded twisted pair (UTP) cables, connecting hardware, patch panels, cross-connects, plugs, jacks, and associated grounding and identification systems. The specification mandates compliance with multiple industry standards including TIA-568-C.1, TIA-568-C.2, TIA-569-D, TIA-607-B, and TIA-606-B, along with NECA/BICSI 568 installation protocols. All cabling must be plenum-rated with flame-spread index of 25 or less and smoke-developed index of 50 or less per ASTM E84 testing. Installation requires BICSI-certified personnel, with shop drawings reviewed and stamped by a Registered Communications Distribution Designer (RCDD), Level 2 Installers supervising on-site work, and RCDD-certified testing supervisors overseeing field quality control. The specification includes detailed requirements for cable routing, separation from electromagnetic interference (EMI) sources with specific minimum distances based on electrical equipment ratings, service loops, proper bending radii, grounding bus bar installation with minimum No. 4 AWG electrode conductors, and comprehensive labeling per TIA-606-B Administration Class 2 standards.

Field quality control encompasses visual inspections of NRTL certification markings, color-coding compliance, cable placement, termination quality, and comprehensive testing for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors using test instruments meeting TIA-568-C.2 requirements. Defective cabling must be removed and replaced. All test data must be documented and submitted in summary reports formatted similarly to BICSI's Telecommunications Distribution Methods Manual Table 10.1. The specification requires identification of system components complying with TIA-606-B, with cables labeled within 4 inches of each termination and at intervals not exceeding 15 feet in exposed applications. Additional requirements address firestopping compliance per Section 078413 and TIA-569-D Annex A, installation of 10-foot service loops in communications equipment rooms, and separation of communications cabling from potential EMI sources including electrical motors and transformers requiring minimum 48-inch separation.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Stantec Alaska Court System Project No. 2014331970 Palmer Courthouse Renovation & Expansion 5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 1

SECTION 271313

COMMUNICATIONS COPPER BACKBONE CABLING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Category 6 twisted pair cable.

2. Category 6a twisted pair cable.

3. Twisted pair cable hardware, including plugs, jacks, patch panels, and cross-connects.

4. Grounding provisions for twisted pair cable.

5. Cabling identification products.

6. Source quality control requirements for twisted pair cable.

B. Related Requirements:

1. Section 260519 "Low-Voltage Electrical Power Conductors and Cables" for data cabling associated with system panels and devices.

1.2 COPPER BACKBONE CABLING DESCRIPTION

A. Copper backbone cabling system shall provide interconnections between communications equipment rooms, main terminal space, and entrance facilities in the telecommunications cabling system structure. Cabling system consists of backbone cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for backbone-to-backbone cross-connection.

B. Backbone cabling cross-connects may be located in communications equipment rooms or at entrance facilities. Bridged taps and splitters shall not be used as part of backbone cabling.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: Reviewed and stamped by RCDD.

1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner.

2. Cabling administration Drawings and printouts.

3. Wiring diagrams to show typical wiring schematics, including the following:

a. Telecommunications rooms plans and elevations.

b. Telecommunications pathways.

c. Telecommunications system access points.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 2

d. Telecommunications grounding system

e. Cross-connects.

f. Patch panels.

g. Patch cords.

4. Cross-Connects and Patch Panels: Detail mounting assemblies, and show elevations and physical relationship between the installed components.

C. Twisted pair cable testing plan.

D. Sustainable Design Submittals:

1.4 INFORMATIONAL SUBMITTALS

A. Source quality-control reports.

B. Field quality-control reports.

C. Product Certificates: For each type of product.

1.5 CLOSEOUT SUBMITTALS

A. Maintenance data.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.

1. Layout Responsibility: Preparation of Shop Drawings and cabling administration Drawings, cabling administration Drawings, and field testing program development] by an RCDD.

2. Installation Supervision: Installation shall be under the direct supervision of Level 2 Installer, who shall be present at all times when Work of this Section is performed at Project site.

3. Testing Supervisor: Currently certified by BICSI an RCDD to supervise on-site testing.

B. Testing Agency Qualifications: Testing agency must have personnel certified by BICSI on staff.

1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD.

1.7 COORDINATION

A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 3

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. General Performance: Backbone cabling system shall comply with transmission standards in TIA-568-C.1, when tested according to test procedures of this standard.

B. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 50 or less.

C. Telecommunications Pathways and Spaces: Comply with TIA-569-D.

D. Grounding: Comply with TIA-607-B.

2.2 GENERAL CABLE CHARACTERISTICS

A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with the applicable standard and NFPA 70 for the following types:

1. Communications, Plenum Rated: Type CMP complying with UL 1685 or Type CMP in listed plenum communications raceway

2. Communications, Plenum Rated: Type CM, Type CMG, Type CMP, Type CMR, or Type CMX in metallic conduit installed according to NFPA 70, Article 300.22, "Wiring in Ducts, Plenums, and Other Air-Handling Spaces."

3. Communications, Riser Rated: Type CMR complying with UL 1666 and ICEA S-103- 701.

4. Communications, Riser Rated: Type CMP or Type CMR in listed plenum or riser communications raceway.

5. Communications, Riser Rated: Type CMP or Type CMR in metallic conduit installed according to NFPA 70, Article 300.22, "Wiring in Ducts, Plenums, and Other Air- Handling Spaces."

B. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: 25 or less.

2. Smoke-Developed Index: 50 or less.

C. RoHS compliant.

2.3 CATEGORY 6 TWISTED PAIR CABLE

A. Description: 100-ohm, 23 AWG, four unshielded twisted pairs (UTP) plenum-rated cable, with internal spline, covered with a blue thermoplastic jacket.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 4

B. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568-C.2 for Category 6 cables.

2.4 CATEGORY 6a TWISTED PAIR CABLE

A. Description: 100-ohm, 23 AWG, four unshielded twisted pairs (UTP) plenum-rated, with internal spline, covered with blue thermoplastic jacket.

B. Standard: Comply with TIA-568-C.2 for Category 6a cables.

2.5 TWISTED PAIR CABLE HARDWARE

A. General Requirements for Cable Connecting Hardware:

1. Twisted pair cable hardware shall meet the performance requirements of Category 6.

2. Comply with TIA-568-C.2, IDC type, with modules designed for punch-down caps or tools.

3. Cables shall be terminated with connecting hardware of same category or higher.

4. Source Limitations: Obtain twisted pair cable hardware from same manufacturer as twisted pair cable, from single source.

B. Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare, integral with connector bodies, including plugs and jacks where indicated.

C. Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.

1. Number of Terminals per Field: One for each conductor in assigned cables.

D. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.

1. Features:

a. Universal T568A and T568B wiring labels.

b. Labeling areas adjacent to conductors.

c. Replaceable connectors.

d. 24 or 48 ports.

2. Construction: 16-gauge steel and mountable on 19-inch (483 mm) equipment racks.

3. Number of Jacks per Field: One for each four-pair cable indicated.

E. Plugs and Plug Assemblies:

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 5

1. Male; eight position (8P8C); color coded modular telecommunications connector designed for termination of a single four-pair 100 ohm unshielded or shielded twisted pair cable.

2. Standard: Comply with TIA-568-C.2.

3. Marked to indicate transmission performance.

F. Jacks and Jack Assemblies:

1. Female; eight position; modular; fixed telecommunications connector designed for termination of a single four-pair 100-ohm unshielded or shielded twisted pair cable.

2. Designed to snap-in to a patch panel or faceplate.

3. Standard: Comply with TIA-568-C.2.

4. Marked to indicate transmission performance.

G. Patch Cords: Factory-made, four-pair cables in 36-inch (900-mm) 48-inch (1200-mm) lengths;

terminated with an eight-position modular plug at each end.

1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6 performance. Patch cords shall have latch guards to protect against snagging.

2. Patch cords shall have color-coded boots for circuit identification.

H. Faceplates:

1. Four port, vertical single gang faceplates designed to mount to single gang wall boxes.

2. Eight port, vertical double gang faceplates designed to mount to double gang wall boxes.

3. Plastic Faceplate: High-impact plastic. Coordinate color with Section 262726 "Wiring Devices."

4. Metal Faceplate: Stainless steel, complying with requirements in Section 262726 "Wiring Devices."

5. For use with snap-in jacks accommodating any combination of twisted pair, optical-fiber, and coaxial work-area cords.

a. Flush-mount jacks, positioning the cord at a 45-degree angle.

I. Legend:

1. Factory labeled by silk-screening or engraving for stainless steel faceplates.

2. Machine printed, in the field, using adhesive-tape label.

3. Snap-in, clear-label covers and machine-printed paper inserts.

2.6 GROUNDING

A. Comply with requirements in Section 270526 "Grounding and Bonding for Communications Systems" for grounding conductors and connectors.

B. Comply with TIA-607-B.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 6

2.7 SOURCE QUALITY CONTROL

A. Factory test cables on reels according to TIA-568-C.1.

B. Factory test cables according to TIA-568-C.2.

C. Cable will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

PART 3 - EXECUTION

3.1 ENTRANCE FACILITIES

A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider.

3.2 WIRING METHODS

A. Wiring Method: Install cables in raceways and cable trays, except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, attics, and gypsum board partitions where unenclosed wiring method may be used. Conceal raceway and cables, except in unfinished spaces.

1. Install plenum cable in environmental air spaces, including plenum ceilings.

B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.

Provide and use lacing bars and distribution spools. Install cables parallel with or at right angles to sides and back of enclosure.

3.3 INSTALLATION OF PATHWAYS

A. Comply with requirements for demarcation point, cabinets, and racks specified in Section 271100 "Communications Equipment Room Fittings."

B. Comply with Section 270529 "Hangers and Supports for Communications Systems."

C. Comply with Section 270536 "Cable Trays for Communications Systems."

D. Drawings indicate general arrangement of pathways and fittings.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 7

3.4 INSTALLATION OF COPPER BACKBONE CABLES

A. Comply with NECA 1 and NECA/BICSI 568.

B. General Requirements for Cabling:

1. Comply with TIA-568-C.0, TIA-568-C.1, and TIA-568-C.2.

2. Comply with BICSI's "Information Transport Systems Installation Manual," Ch. 6, "Cable Termination Practices."

3. Install 110-style IDC termination hardware unless otherwise indicated.

4. Do not untwist twisted pair cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry.

5. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.

6. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches

(760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals.

7. Install lacing bars to restrain cables, prevent straining connections, and prevent bending cables to smaller radii than minimums recommended by manufacturer.

8. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI's "Information Transport Systems Installation Manual," Ch. 6, "Cable Termination Practices." Use lacing bars and distribution spools.

9. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.

10. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.

11. In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of cable.

12. Pulling Cable: Comply with BICSI's "Information Transport Systems Installation Manual," Ch. 4, "Pulling Cable." Monitor cable pull tensions.

C. Open-Cable Installation:

1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.

2. Suspend twisted pair cabling, not in a wireway or pathway, a minimum of 8 inches (200

mm) above ceilings by cable supports not more than 60 inches (1524 mm) apart.

3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.

D. Installation of Cable Routed Exposed under Raised Floors:

1. Install plenum-rated cable only.

2. Install cabling after the flooring system has been installed in raised floor areas.

3. Coil cable 6 feet (1800 mm) long not less than 12 inches (300 mm) in diameter below each feed point.

E. Group connecting hardware for cables into separate logical fields.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 8

F. Separation from EMI Sources:

1. Comply with recommendations from BICSI's "Telecommunications Distribution Methods Manual" and TIA-569-D for separating unshielded copper communication cable from potential EMI sources, including electrical power lines and equipment.

2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm).

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches (300 mm).

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (600 mm).

3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm).

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches (150 mm).

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm).

4. Separation between communications cables in grounded metallic raceways, power lines, and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:

a. Electrical Equipment Rating Less Than 2 kVA: No requirement.

b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches (76 mm).

c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm).

5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches (1200 mm).

6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm).

3.5 FIRESTOPPING

A. Comply with requirements in Section 078413 "Penetration Firestopping."

B. Comply with TIA-569-D, Annex A, "Firestopping."

C. Comply with "Firestopping Systems" Article in BISCI's "Telecommunications Distribution Methods Manual."

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 9

3.6 GROUNDING

A. Install grounding according to the "Grounding, Bonding, and Electrical Protection" chapter in BICSI's "Telecommunications Distribution Methods Manual."

B. Comply with TIA-607-B and NECA/BICSI-607.

C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall, allowing at least a 2-inch (50-mm) clearance behind the grounding bus bar. Connect grounding bus bar to suitable electrical building ground, using a minimum No. 4 AWG grounding electrode conductor.

D. Bond metallic equipment to the grounding bus bar, using not smaller than a No. 6 AWG equipment grounding conductor.

3.7 IDENTIFICATION

A. Identify system components, wiring, and cabling complying with TIA-606-B. Comply with requirements for identification specified in Section 270553 "Identification for Communications Systems."

1. Administration Class: 2

2. Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels.

B. Cable and Wire Identification:

1. Label each cable within 4 inches (100 mm) of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.

2. Each wire connected to building-mounted devices is not required to be numbered at the device if wire color is consistent with associated wire connected and numbered within panel or cabinet.

3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 15 feet (4.5 m).

4. Label each terminal strip, and screw terminal in each cabinet, rack, or panel.

a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group, extended from a panel or cabinet to a building-mounted device, with the name and number of a particular device.

b. Label each unit and field within distribution racks and frames.

5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and -connecting hardware.

Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service.

C. Labels shall be preprinted or computer-printed type, with a printing area and font color that contrast with cable jacket color but still comply with TIA-606-B requirements for the following:

1. Cables use flexible vinyl or polyester that flexes as cables are bent.

Stantec Alaska Court System

5/13/2026 100% Construction Documents

COMMUNICATIONS COPPER BACKBONE CABLING 271313 - 10

3.8 FIELD QUALITY CONTROL

A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections.

B. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

C. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.

D. Perform tests and inspections

E. Retain "Tests and Inspections" Paragraph below to describe tests and inspections to be performed.

F. Tests and Inspections:

1. Visually inspect jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments and inspect cabling connections for compliance with TIA-568-C.1.

2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.

3. Test copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection.

a. Test instruments shall meet or exceed applicable requirements in TIA-568-C.2.

Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

G. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similarly to Table 10.1 in BICSI's "Telecommunications Distribution Methods Manual," or shall be transferred from the instrument to the computer, saved as text files, printed, and submitted.

H. Remove and replace cabling where test results indicate that they do not comply with specified requirements.

I. End-to-end cabling will be considered defective if it does not pass tests and inspections.

J. Prepare test and inspection reports.

END OF SECTION 271313

PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Category 6 twisted pair cable.
2. Category 6a twisted pair cable.
3. Twisted pair cable hardware, including plugs, jacks, patch panels, and cross-connects.
4. Grounding provisions for twisted pair cable.
5. Cabling identification products.
6. Source quality control requirements for twisted pair cable.
B. Related Requirements:
1. Section 260519 "Low-Voltage Electrical Power Conductors and Cables" for data cabling associated with system panels and devices.
1.2 COPPER BACKBONE CABLING DESCRIPTION
A. Copper backbone cabling system shall provide interconnections between communications equipment rooms, main terminal space, and entrance facilities in the telecommunications cabling system structure. Cabling system consists of backbone cables, inter...
B. Backbone cabling cross-connects may be located in communications equipment rooms or at entrance facilities. Bridged taps and splitters shall not be used as part of backbone cabling.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Reviewed and stamped by RCDD.
1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner.
2. Cabling administration Drawings and printouts.
3. Wiring diagrams to show typical wiring schematics, including the following:
a. Telecommunications rooms plans and elevations.
b. Telecommunications pathways.
c. Telecommunications system access points.
d. Telecommunications grounding system
e. Cross-connects.
f. Patch panels.
g. Patch cords.

4. Cross-Connects and Patch Panels: Detail mounting assemblies, and show elevations and physical relationship between the installed components.

C. Twisted pair cable testing plan.
D. Sustainable Design Submittals:
1.4 INFORMATIONAL SUBMITTALS
A. Source quality-control reports.
B. Field quality-control reports.
C. Product Certificates: For each type of product.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.
1. Layout Responsibility: Preparation of Shop Drawings and cabling administration Drawings, cabling administration Drawings, and field testing program development] by an RCDD.
2. Installation Supervision: Installation shall be under the direct supervision of Level 2 Installer, who shall be present at all times when Work of this Section is performed at Project site.
3. Testing Supervisor: Currently certified by BICSI an RCDD to supervise on-site testing.
B. Testing Agency Qualifications: Testing agency must have personnel certified by BICSI on staff.
1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD.
1.7 COORDINATION
A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. General Performance: Backbone cabling system shall comply with transmission standards in TIA-568-C.1, when tested according to test procedures of this standard.
B. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 50 or less.
C. Telecommunications Pathways and Spaces: Comply with TIA-569-D.
D. Grounding: Comply with TIA-607-B.
2.2 GENERAL CABLE CHARACTERISTICS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with the applicable standard and NFPA 70 for the following types:
1. Communications, Plenum Rated: Type CMP complying with UL 1685 or Type CMP in listed plenum communications raceway
2. Communications, Plenum Rated: Type CM, Type CMG, Type CMP, Type CMR, or Type CMX in metallic conduit installed according to NFPA 70, Article 300.22, "Wiring in Ducts, Plenums, and Other Air-Handling Spaces."
3. Communications, Riser Rated: Type CMR complying with UL 1666 and ICEA S-103-701.
4. Communications, Riser Rated: Type CMP or Type CMR in listed plenum or riser communications raceway.
5. Communications, Riser Rated: Type CMP or Type CMR in metallic conduit installed according to NFPA 70, Article 300.22, "Wiring in Ducts, Plenums, and Other Air-Handling Spaces."
B. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 50 or less.

C. RoHS compliant.

2.3 CATEGORY 6 TWISTED PAIR CABLE
A. Description: 100-ohm, 23 AWG, four unshielded twisted pairs (UTP) plenum-rated cable, with internal spline, covered with a blue thermoplastic jacket.
B. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568-C.2 for Category 6 cables.
2.4 CATEGORY 6a TWISTED PAIR CABLE
A. Description: 100-ohm, 23 AWG, four unshielded twisted pairs (UTP) plenum-rated, with internal spline, covered with blue thermoplastic jacket.
B. Standard: Comply with TIA-568-C.2 for Category 6a cables.
2.5 TWISTED PAIR CABLE HARDWARE
A. General Requirements for Cable Connecting Hardware:
1. Twisted pair cable hardware shall meet the performance requirements of Category 6.
2. Comply with TIA-568-C.2, IDC type, with modules designed for punch-down caps or tools.
3. Cables shall be terminated with connecting hardware of same category or higher.
4. Source Limitations: Obtain twisted pair cable hardware from same manufacturer as twisted pair cable, from single source.
B. Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare, integral with connector bodies, including plugs and jacks where indicated.
C. Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.
1. Number of Terminals per Field: One for each conductor in assigned cables.
D. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.
1. Features:
a. Universal T568A and T568B wiring labels.
b. Labeling areas adjacent to conductors.
c. Replaceable connectors.
d. 24 or 48 ports.
2. Construction: 16-gauge steel and mountable on 19-inch (483 mm) equipment racks.
3. Number of Jacks per Field: One for each four-pair cable indicated.
E. Plugs and Plug Assemblies:
1. Male; eight position (8P8C); color coded modular telecommunications connector designed for termination of a single four-pair 100 ohm unshielded or shielded twisted pair cable.
2. Standard: Comply with TIA-568-C.2.
3. Marked to indicate transmission performance.
F. Jacks and Jack Assemblies:
1. Female; eight position; modular; fixed telecommunications connector designed for termination of a single four-pair 100-ohm unshielded or shielded twisted pair cable.
2. Designed to snap-in to a patch panel or faceplate.
3. Standard: Comply with TIA-568-C.2.
4. Marked to indicate transmission performance.
G. Patch Cords: Factory-made, four-pair cables in 36-inch (900-mm) 48-inch (1200-mm) lengths; terminated with an eight-position modular plug at each end.
1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6 performance. Patch cords shall have latch guards to protect against snagging.
2. Patch cords shall have color-coded boots for circuit identification.
H. Faceplates:
1. Four port, vertical single gang faceplates designed to mount to single gang wall boxes.
2. Eight port, vertical double gang faceplates designed to mount to double gang wall boxes.
3. Plastic Faceplate: High-impact plastic. Coordinate color with Section 262726 "Wiring Devices."
4. Metal Faceplate: Stainless steel, complying with requirements in Section 262726 "Wiring Devices."
5. For use with snap-in jacks accommodating any combination of twisted pair, optical-fiber, and coaxial work-area cords.
a. Flush-mount jacks, positioning the cord at a 45-degree angle.
I. Legend:
1. Factory labeled by silk-screening or engraving for stainless steel faceplates.
2. Machine printed, in the field, using adhesive-tape label.
3. Snap-in, clear-label covers and machine-printed paper inserts.
2.6 GROUNDING
A. Comply with requirements in Section 270526 "Grounding and Bonding for Communications Systems" for grounding conductors and connectors.
B. Comply with TIA-607-B.
2.7 SOURCE QUALITY CONTROL
A. Factory test cables on reels according to TIA-568-C.1.
B. Factory test cables according to TIA-568-C.2.
C. Cable will be considered defective if it does not pass tests and inspections.
D. Prepare test and inspection reports.
PART 3 - EXECUTION
3.1 ENTRANCE FACILITIES
A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider.
3.2 WIRING METHODS
A. Wiring Method: Install cables in raceways and cable trays, except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, attics, and gypsum board partitions where unenclosed wiring method may be used. Conceal racewa...
1. Install plenum cable in environmental air spaces, including plenum ceilings.
B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.
C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. Install ca...
3.3 INSTALLATION OF PATHWAYS
A. Comply with requirements for demarcation point, cabinets, and racks specified in Section 271100 "Communications Equipment Room Fittings."
B. Comply with Section 270529 "Hangers and Supports for Communications Systems."
C. Comply with Section 270536 "Cable Trays for Communications Systems."
D. Drawings indicate general arrangement of pathways and fittings.
3.4 INSTALLATION OF COPPER BACKBONE CABLES
A. Comply with NECA 1 and NECA/BICSI 568.
B. General Requirements for Cabling:
1. Comply with TIA-568-C.0, TIA-568-C.1, and TIA-568-C.2.
2. Comply with BICSI's "Information Transport Systems Installation Manual," Ch. 6, "Cable Termination Practices."
3. Install 110-style IDC termination hardware unless otherwise indicated.
4. Do not untwist twisted pair cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry.
5. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.
6. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals.
7. Install lacing bars to restrain cables, prevent straining connections, and prevent bending cables to smaller radii than minimums recommended by manufacturer.
8. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI's "Information Transport Systems Installation Manual," Ch. 6, "Cable Termination Practic...
9. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.
10. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.
11. In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of cable.
12. Pulling Cable: Comply with BICSI's "Information Transport Systems Installation Manual," Ch. 4, "Pulling Cable." Monitor cable pull tensions.
C. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.
2. Suspend twisted pair cabling, not in a wireway or pathway, a minimum of 8 inches (200 mm) above ceilings by cable supports not more than 60 inches (1524 mm) apart.
3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.
D. Installation of Cable Routed Exposed under Raised Floors:
1. Install plenum-rated cable only.
2. Install cabling after the flooring system has been installed in raised floor areas.
3. Coil cable 6 feet (1800 mm) long not less than 12 inches (300 mm) in diameter below each feed point.
E. Group connecting hardware for cables into separate logical fields.
F. Separation from EMI Sources:
1. Comply with recommendations from BICSI's "Telecommunications Distribution Methods Manual" and TIA-569-D for separating unshielded copper communication cable from potential EMI sources, including electrical power lines and equipment.
2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm).
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches (300 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (600 mm).
3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm).
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches (150 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm).
4. Separation between communications cables in grounded metallic raceways, power lines, and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: No requirement.
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches (76 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm).
5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches (1200 mm).
6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm).
3.5 FIRESTOPPING
A. Comply with requirements in Section 078413 "Penetration Firestopping."
B. Comply with TIA-569-D, Annex A, "Firestopping."
C. Comply with "Firestopping Systems" Article in BISCI's "Telecommunications Distribution Methods Manual."
3.6 GROUNDING
A. Install grounding according to the "Grounding, Bonding, and Electrical Protection" chapter in BICSI's "Telecommunications Distribution Methods Manual."
B. Comply with TIA-607-B and NECA/BICSI-607.
C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall, allowing at least a 2-inch (50-mm) clearance behind the grounding bus bar. Connect grounding bus bar to suitable electrical building ground, using a minimum No. ...
D. Bond metallic equipment to the grounding bus bar, using not smaller than a No. 6 AWG equipment grounding conductor.
3.7 IDENTIFICATION
A. Identify system components, wiring, and cabling complying with TIA-606-B. Comply with requirements for identification specified in Section 270553 "Identification for Communications Systems."
1. Administration Class: 2
2. Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels.
B. Cable and Wire Identification:
1. Label each cable within 4 inches (100 mm) of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.
2. Each wire connected to building-mounted devices is not required to be numbered at the device if wire color is consistent with associated wire connected and numbered within panel or cabinet.
3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 15 feet (4.5 m).
4. Label each terminal strip, and screw terminal in each cabinet, rack, or panel.
a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group, extended from a panel or cabinet to a building-mounted device, with the name and number of a particular device.
b. Label each unit and field within distribution racks and frames.

5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and -connecting hardware. Where similar jacks and plugs are used for both voice and data communication ca...

C. Labels shall be preprinted or computer-printed type, with a printing area and font color that contrast with cable jacket color but still comply with TIA-606-B requirements for the following:
1. Cables use flexible vinyl or polyester that flexes as cables are bent.
3.8 FIELD QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections.
B. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
C. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
D. Perform tests and inspections
E. Retain "Tests and Inspections" Paragraph below to describe tests and inspections to be performed.
F. Tests and Inspections:
1. Visually inspect jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments and inspect cabling connections for compliance with TIA-568-C.1.
2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.
3. Test copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection.
a. Test instruments shall meet or exceed applicable requirements in TIA-568-C.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measure...
G. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similarly to Table 10.1 in BICSI's "Telecommunications Distribution Methods Manual," or shall be transferred from the instrume...
H. Remove and replace cabling where test results indicate that they do not comply with specified requirements.
I. End-to-end cabling will be considered defective if it does not pass tests and inspections.
J. Prepare test and inspection reports.