Abate Central Chase - 13 - ICRA.pdf
PDF 293 KB Posted
- Solicitation number
- 36C25626R0047
About this file
This is an Infection Prevention & Control Construction Risk Assessment (ICRA) form for the Overton Brooks Veterans Affairs Medical Center (VAMC) for the project "Abate Central Chase Replace Fire Main 667-18-111," dated September 25, 2025, and signed by Carol Phillips, Infection Prevention Officer.
The assessment determines infection control precautions required for construction activities based on two primary factors: construction project type and affected patient risk groups. The project has been classified as TYPE B (small scale, short duration activities creating minimal dust), specifically noting that cutting through plaster walls in hallway is required. The affected patient risk group is identified as HIGH Risk, which includes areas such as Emergency Rooms, Laboratories, Medical Units, Outpatient Surgery, Pharmacy, Surgical Units, and Sterile Supply storage/distribution. Using the IC Matrix that correlates construction type with patient risk, the assessment determines that Class II/II infection control precautions are required. This classification indicates the need for moderate infection control measures appropriate for a small-scale construction project in a high-risk patient care area, ensuring that dust migration can be controlled and patient safety is maintained during the fire main replacement work in the central chase space.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25626R0047 0003.pdf | ||
| 36C25626R0047 0002.docx | DOCX document | |
| Attachment No. 1 Piping Asbestos Survey.pdf | ||
| Attachment No. 2 Pre-bid Conference Sign-in Sheet.pdf | ||
| Attachment No. 3 WD LA20260031.pdf | ||
| 36C25626R0047 0002.pdf | ||
| 36C25626R0047 0001.pdf | ||
| 36C25626R0047 EXHIBIT B.docx | DOCX document | |
| 36C25626R0047 EXHIBIT D.docx | DOCX document | |
| 36C25626R0047 EXHIBIT C.docx | DOCX document | |
| 36C25626R0047.pdf | ||
| Abate Central Chase - 1- SOW.pdf | ||
| Abate Central Chase - 8 - CRA.pdf | ||
| WD LA20260031 01022026.pdf | ||
| Abate Chase - FY26 - Final Drawings.pdf | ||
| Abate Chase - FY26 - IFC Specs - Updated.pdf | ||
| Abate Central Chase - 14 - Class II Precautions.pdf | ||
| 36C25626R0047 EXHIBIT A.docx | DOCX document | |
| 36C25626R0047 EXHIBIT E.docx | DOCX document | |
| 36C25626R0047 EXHIBIT F.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Overton Brooks VAMC
Infection Prevention & Control Construction Risk Assessment (ICRA)
Project: Abate Central Chase Replace Fire Main 667-18-111 Date: 09/25/2025
STEP ONE: CIRCLE the Type of Construction Project based on scope and expected activity (Type A-D)
TYPE
A
Inspection and Non-Invasive Activities. Includes, but is not limited to:
▪ removal of ceiling tiles for visual inspection only, e.g., limited to 1 tile per 50 square feet
▪ painting (but not sanding)
▪ wallcovering, electrical trim work, minor plumbing, activities which do not generate dust or require cutting of walls or access to ceilings other than for visual inspection.
TYPE
B
Small scale, short duration activities which create minimal dust Includes, but is not limited to:
▪ installation of telephone and computer cabling
▪ access to chase spaces
▪ cutting of walls or ceiling where dust migration can be controlled.
▪ Project Specific: cutting through plaster walls in hallway required
TYPE
C
Work generates a moderate/high level of dust or requires demolition/removal of any fixed building components or assemblies Includes, but is not limited to:
▪ sanding of walls for painting or wall covering
▪ removal of floorcoverings, ceiling tiles and casework; new wall construction
▪ minor duct work or electrical work above ceilings
▪ major cabling activities
▪ any activity which cannot be completed within a single work shift.
TYPE
D
Major demolition and construction projects Includes, but is not limited to:
▪ activities which require consecutive work shifts
▪ requires heavy demolition, removal of a complete cabling system, or excavation
▪ new construction.
STEP TWO: CIRCLE the affected Patient Risk Groups. If more than one risk group will be affected, select the higher risk group.
Low Risk Medium Risk High Risk Highest Risk
▪ Office areas
▪ Kitchen storage area
▪ Public access, hallways, elevator
Lobby
▪ Non-clinical vacated engineering space
▪ Cardiology
▪ Echocardiography
▪ Endoscopy
▪ Nuclear Medicine
▪ Physical Therapy
▪ Radiology/MRI
▪ Respiratory
Therapy
▪ Kitchen – food preparation area
▪ Step Down Unit
▪ Emergency Room
▪ Laboratories (specimen)
▪ Medical Units
▪ Outpatient Surgery
▪ Pharmacy
▪ Post Anesthesia Care Unit
▪ Surgical Units
▪ Minor Procedure Rooms
▪ Sterile Supply storage/distribution
▪ Immunocompromised patient care areas
▪ Cardiac Cath Lab
▪ Sterile Processing Service
▪ Preparation Area
▪ Decontamination Area
▪ Intensive Care Unit
▪ Negative pressure isolation rooms
▪ Oncology
▪ Operating rooms
STEP THREE: Using the IC Matrix CIRCLE the Class of Precautions as determined by Construction Type and Patient Risk
Construction Project Type
Patient Risk Group TYPE A TYPE B TYPE C TYPE D
IC
M a tr ix LOW Risk Group I II II III/IV
MEDIUM Risk Group I II III IV
HIGH Risk Group I II III/IV IV
HIGHEST Risk Group II III/IV III/IV IV