A2 B901 Conference TeleComm Legend.pdf
PDF 342 KB Posted
- Attached to
- Conference Room Audio / Visual Equipment Package
- Solicitation number
- W50S8H-26-Q-0014
About this file
This document is a telecommunications general notes, abbreviations, and legend sheet for a federal construction project at the New York Air National Guard Niagara Falls Air Reserve Station. The sheet establishes naming conventions for construction drawings, provides comprehensive symbol legends for telecommunications and electronic security systems, and defines standard abbreviations used throughout the project documentation.
The project involves renovating the Operations and Training Facility in Building 901 and is divided into separate bid line items for communications systems and security systems. The base bid covers cable trays, conduit, patch panels, and pathways, while the communications and security system bid line items separately address the purchase, installation, testing, and labeling of all equipment, faceplates, and wiring for each respective system. Key technical requirements include: telecommunications equipment must connect to existing patch panels in Data Center 128 and Telecom Room 158, which must remain operational during construction; intrusion detection systems shall use Advantor equipment; access control systems shall use Sonitrol equipment; surge protection devices must comply with AFI 32-1065 and NFPA 780; all EMT conduit must be factory-painted orange for telecommunications and purple for security systems; and minimum 12-inch separation must be maintained between data outlets and power loads exceeding 5KVA. The document also establishes specific clearance and spacing requirements for telecommunications rooms, including minimum 3.28-foot clear space for cable installation and equipment mounting, 50 foot-candles of lighting at cable termination points, and prohibition of dimmers and vacancy sensors within telecommunications rooms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B7 Site Visit Q and A 2 of 2.docx | DOCX document | |
| ANG - Large Conference Room - Technical Drawings FINAL.pdf | ||
| B7 Site Visit Q and A.docx | DOCX document | |
| A2 B901 Conference Architectural Image.jpg | JPG image | |
| A2 B912 Conference Room Layout.pdf | ||
| A2 B901 Conference Electrical Image.jpg | JPG image | |
| A2 SOW Conference Rooms.docx | DOCX document | |
| A2 B901 Conference TeleComm Image.jpg | JPG image | |
| A2 B901 Conference Electrical Legend.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
T-001-01
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DESCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
2 DIGIT CONSTRUCTION
PHASE DESIGNATOR
(REFER TO A3/G-002
FOR CONSTRUCTION
PHASES)
TV
COMMUNICATIONS
COAXIAL CATV OUTLET WALL MOUNTED 60" AFF,
UIO. REFER TO DETAIL A2/T-501.
COMMUNICATIONS COMBINATION DATA OUTLET
(TWO VOICE & TWO DATA JACKS) MOUNT 18"
AFF, UIO
COMMUNICATIONS VOICE OUTLET MT 48" AFF,
UIO. REFER TO DETAIL A3/T-501.
COMMUNICATIONS DATA OUTLET, MT 18" AFF,
UIO. REFER TO DETAIL A1/T-501.
SIPR FIBER DROP, SURACE MOUNT AT 48" AFF,
UIO. REFER TO DETAIL C2/T-501.
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR. REFER TO DETAIL
A3/T-502.
COAXIAL CATV OUTLET CEILING MOUNTED
WALL MOUNTED JUNCTION BOX FOR
VOICE/DATA CONNECTION TO MODULAR
WORKSTATION FURNITURE.
CEILING MOUNTED PA SPEAKER, ONE WAY TYPE
WITH ADJUSTABLE VOLUME KNOB. PROVIDE
3/4"C TO NEAREST TELECOMM ROOM FOR GFGI
PUBLIC ADDRESS SYSTEM.
WALL MOUNTED PA SPEAKER, ONE WAY TYPE;
MT 120" AFF, UIO
CCTV CAMERA
CONTROL STATION
WALL SWITCH, AC TYPE, SPST, MOUNT 48" AFF
WALL MOUNTED SPEAKER VOLUME SWITCH, MT.
48" AFF
LOW VOLTAGE ON/OFF WALL SWITCH, WALL MT.
48" AFF. PROVIDE DIMMER CONTROL WITH
DIMMABLE FIXTURES INTEGRAL WITH SWITCH.
POWER POLE
WIRING
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
CABLE TRAY (SIZE AS INDICATED ON PLAN)
ELECTRONIC SECURITY
ACCESS CONTROL JUNCTION BOX
BALANCED MAGNETIC DOOR CONTACT
ELECTRIC STRIKE
CARD READER
ELECTRIC LOCKSET
ELECTRIC HINGE
MOTION DETECTION SENSOR
KEY PAD
DOOR RELEASE
HIGH SECURITY SWITCH
TELECOMMUNICAITONS LEGEND
DC
ES
CR
EL
EH
M
KP
DR
AC
V
LV
J
HSS
S
PA
PP
TELECOMMUNICATIONS ABBREVIATIONS
A OR AMP
AFF
AWG
BLDG
C
CAT
CATV
CFCI
CU
D
DDC
EC
EF
EIA
EMT
EQUIP
ER
ETR
EXIST or EX
FWE
G OR GND
GFGI
GFCI
GRS
H or HT
HVAC
IDF
IDS
IMC
J OR JB
K
KV
KVA
KW
L
LAN
MAX
MDF
MIN
MM
N
NEC
NEMA
NFPA
NIPR
NTS
PDS
PVC
RMC
RPP
RU
SA
SIPR
SM
SPEC
TGB
TIA
TMGB
TP
TR
TYP
UIO
UL
UTP
V
VA
W
WAP
AMPERE(S)
ABOVE FINISHED FLOOR
AMERICAN WIRE GAUGE
BUILDING
CONDUIT
CATEGORY
CABLE TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
COPPER
DEPTH
DIRECT DIGITAL CONTROL FOR HVAC
EMPTY CONDUIT
ENTRANCE FACILITY
ELECTRONICS INDUSTRIAL ALLIANCE
ELECTRICAL METALLIC TUBING
EQUIPMENT
EQUIPMENT ROOM
EXISTING TO REMAIN
EXISTING
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GOVERNMENT FURNISHED CONTRACTOR
INSTALLED
GALVANIZED RIGID STEEL CONDUIT
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INTERMEDIATE DISTRIBUTION FRAME
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
KILO
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
LENGTH
LOCAL AREA NETWORK
MAXIMUM
MAIN DISTRIBUTION FRAME
MINIMUM
MULTIMODE
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NON-SECURE INTERNET PROTOCAL ROOTER
NOT TO SCALE
PROTECTIVE DISTRIBUTION SYSTEM
POLYVINAL CHLORIDE
RIGID METAL CONDUIT
REMOTE POWER PANEL
RACK UNIT
SURGE ARRESTOR
SECURE INTERNET PROTOCAL ROOTER
SINGLE MODE
SPECIFICATIONS
TELECOMMUNICATIONS GROUNDING BUSBAR
TELECOMMUNICATIONS INDUSTRIAL ALLIANCE
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
TWISTED PAIR
TELECOMMUNICATIONS ROOM
TYPICAL
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
WATTS or WIRE or WIDTH
WIRELESS ACCESS POINT
TELECOMMUNICATIONS GENERAL NOTES:
1. EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ATC) THAT DOES NOT SERVE EF,ER OR TR(S) SHALL NOT BE INSTALLED ABOVE OR IN IT SPACES, NOR SHALL THIS EQUIPMENT PASS THROUGH OR ENTER THE EF, ER OR TR(S).
2. ANY MOTOR, TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN 5KVA SHALL HAVE A MINIMUM OF 47" SPACE
SEPARATION FROM ANY WALL OF EF, ER OR TR(S).
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LIGHTING
FIXTURES AND CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
4. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.
5. REFER TO DETAILS AND RISER DIAGRAMS FOR CABLE AND CONDUIT SIZES NOT SHOWN ON PLANS.
6. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND
SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
7. PROVIDE WELDED WIRE TYPE CABLE TRAY IN ALL AREAS EXCEPT TR(S). PROVIDE LADDER TYPE CABLE TRAY IN TR(S).
8. FLOOR BOXES AND POKE THRU'S SHALL BE SIZED TO NOT EXCEED TELECOMMUNICATIONS CABLE MINIMUM BEND RADIUS.
9. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALLS. FIRESTOP FIRE RATED BARRIERS IN ACCORDANCE WITH FIRESTOPPING SPECIFICATIONS 07 84 00. SLEEVES AND SLOTS SHALL NOT BE LEFT OPEN AFTER CABLE INSTALLATION. ALL SLEEVES AND SLOTS SHALL BE FIRESTOPPED IN ACCORDANCE WITH FIRESTOPPING SPECIFICATION 07 84 00.
10. EMT: COMPLY WITH ANSI C80.3 AND 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR EACH
SYSTEM:
1. TELECOMMUNICATIONS - ORANGE
2. SECURITY - PURPLE
11. PROVIDE A MINIMUM OF 12" SEPERATION BETWEEN ALL DATA OUTLETS AND ANY POWER LOAD GREATER THAN 5KVA.
12. PROVIDE 3.28’ OF CLEAR, UNOBSTRUCTED SPACE FOR THE INSTALLATION OF ALL CABLING AND EQUIPMENT MOUNTED ON WALLS, RACKS (FRONT AND REAR), CABINETS (FRONT AND REAR) AND ENCLOSURES. PROVIDE AT LEAST 6” DEPTH OFF THE WALL FOR WALL-MOUNTED EQUIPMENT. ALLOCATE SPACE OF 3.28’ WIDE, 3.28’ DEEP AND 7.5’ HIGH FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. PROVIDE SPACE FOR AN AISLE OF AT LEAST 3.28’ WIDE IN THE FRONT AND IN THE REAR OF THE SPACE FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. THIS SPACE SHALL TAKE INTO ACCOUNT THE DEPTH OF RACK-MOUNTED EQUIPMENT
AS WELL AS WALL-MOUNTED EQUIPMENT AND HARDWARE.
13. LOCATE LIGHT SWITCHES NEAR THE ENTRANCE(S) TO THE TELECOMMUNICATION ROOM. DIMMERS AND VACANCY SENSORS ARE NOT PERMITTED TO BE USED WITHIN THE TELECOMMUNICATION ROOM. PROVIDE A MINIMUM OF 50 FOOT-CANDLES OF LIGHT AT
THE POINT OF CABLE TERMINATION.
14. COORDINATE CABLE TRAY, LIGHT FIXTURE AND MECHANICAL UNIT INSTALLATION WITHIN A TELECOMMUNICATION ROOM WITH ALL
TRADES PRIOR TO INSTALLATION.
15. SLEEVES OR CONDUITS ENTERING INTO THE TELECOMMUNICATION ROOM SHALL EXTEND INTO THE SPACE A MINIMUM OF 3” FROM
THE FLOOR, WALL OR CEILING.
16. ALL TELECOMMUNICATION DEVICES SHALL CONNECT TO EXISTING PATCH PANELS LOCATED IN DATA CENTER 128 AND TELECOM
ROOM 158.
17. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158 SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
18. INTRUSION DETATION SYSTEM SHALL BE ADVANTOR.
19. ACCESS CONTROL SYSTEM SHALL BE SONITROL.
20. SURGE PROTECTION DEVICES SHALL BE PROVIDED IN ACCORDANCE WITH AFI 32-1065 AND NFPA 780.
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
P
O B o x
S yr a c u s e
N Y
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:4
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
T-001
100% B3 SUBMITTAL
T E
L E
C O
M M
U N
IC
A
T
IO
N S
G E
N E
R A
L N
O T
E S
A
B B
R E
V
IA
T
IO
N S
L
E G
E N
D
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
NOTE:
1. NOT ALL SYMBOLS OR ABBREVIATIONS SHOWN WILL BE USED
ON THIS PROJECT.
NOTES:
1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
BID NOTES:
ALL COMMUNICATION SYSTEMS ARE PART OF A BID
LINE ITEM THAT IS SEPARATE FROM THE BASE BID
AND THE SECURITY SYSTEM BID LINE ITEM.
BASE BID:
ALL CABLE TRAYS, CONDUIT AND PATCH PANELS.
BID LINE ITEM:
THE PURCHASE, INSTALLATION, TESTING AND
LABELING OF ALL COMMUNICATIONS EQUIPMENT,
FACEPLATES AND WIRING.
BID NOTES:
ALL SECURITY SYSTEMS ARE PART OF A BID
LINE ITEM THAT IS SEPARATE FROM THE BASE BID
AND THE COMMUNICATIONS SYSTEM BID LINE ITEM.
BASE BID:
ALL PATHWAYS AND BOXES.
BID LINE ITEM:
THE PURCHASE, INSTALLATION, TESTING AND
LABELING OF ALL SECURITY EQUIPMENT,
FACEPLATES AND WIRING.