This document is a telecommunications general notes, abbreviations, and legend sheet for a federal construction project at the New York Air National Guard Niagara Falls Air Reserve Station. The sheet establishes naming conventions for construction drawings, provides comprehensive symbol legends for telecommunications and electronic security systems, and defines standard abbreviations used throughout the project documentation.

The project involves renovating the Operations and Training Facility in Building 901 and is divided into separate bid line items for communications systems and security systems. The base bid covers cable trays, conduit, patch panels, and pathways, while the communications and security system bid line items separately address the purchase, installation, testing, and labeling of all equipment, faceplates, and wiring for each respective system. Key technical requirements include: telecommunications equipment must connect to existing patch panels in Data Center 128 and Telecom Room 158, which must remain operational during construction; intrusion detection systems shall use Advantor equipment; access control systems shall use Sonitrol equipment; surge protection devices must comply with AFI 32-1065 and NFPA 780; all EMT conduit must be factory-painted orange for telecommunications and purple for security systems; and minimum 12-inch separation must be maintained between data outlets and power loads exceeding 5KVA. The document also establishes specific clearance and spacing requirements for telecommunications rooms, including minimum 3.28-foot clear space for cable installation and equipment mounting, 50 foot-candles of lighting at cable termination points, and prohibition of dimmers and vacancy sensors within telecommunications rooms.

View the file

Other files

File Type Posted
B7 Site Visit Q and A 2 of 2.docx DOCX document
ANG - Large Conference Room - Technical Drawings FINAL.pdf PDF
B7 Site Visit Q and A.docx DOCX document
A2 B901 Conference Architectural Image.jpg JPG image
A2 B912 Conference Room Layout.pdf PDF
A2 B901 Conference Electrical Image.jpg JPG image
A2 SOW Conference Rooms.docx DOCX document
A2 B901 Conference TeleComm Image.jpg JPG image
A2 B901 Conference Electrical Legend.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NAMING CONVENTION

T-001-01

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DESCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

2 DIGIT CONSTRUCTION

PHASE DESIGNATOR

(REFER TO A3/G-002

FOR CONSTRUCTION

PHASES)

TV

COMMUNICATIONS

COAXIAL CATV OUTLET WALL MOUNTED 60" AFF,

UIO. REFER TO DETAIL A2/T-501.

COMMUNICATIONS COMBINATION DATA OUTLET

(TWO VOICE & TWO DATA JACKS) MOUNT 18"

AFF, UIO

COMMUNICATIONS VOICE OUTLET MT 48" AFF,

UIO. REFER TO DETAIL A3/T-501.

COMMUNICATIONS DATA OUTLET, MT 18" AFF,

UIO. REFER TO DETAIL A1/T-501.

SIPR FIBER DROP, SURACE MOUNT AT 48" AFF,

UIO. REFER TO DETAIL C2/T-501.

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR. REFER TO DETAIL

A3/T-502.

COAXIAL CATV OUTLET CEILING MOUNTED

WALL MOUNTED JUNCTION BOX FOR

VOICE/DATA CONNECTION TO MODULAR

WORKSTATION FURNITURE.

CEILING MOUNTED PA SPEAKER, ONE WAY TYPE

WITH ADJUSTABLE VOLUME KNOB. PROVIDE

3/4"C TO NEAREST TELECOMM ROOM FOR GFGI

PUBLIC ADDRESS SYSTEM.

WALL MOUNTED PA SPEAKER, ONE WAY TYPE;

MT 120" AFF, UIO

CCTV CAMERA

CONTROL STATION

WALL SWITCH, AC TYPE, SPST, MOUNT 48" AFF

WALL MOUNTED SPEAKER VOLUME SWITCH, MT.

48" AFF

LOW VOLTAGE ON/OFF WALL SWITCH, WALL MT.

48" AFF. PROVIDE DIMMER CONTROL WITH

DIMMABLE FIXTURES INTEGRAL WITH SWITCH.

POWER POLE

WIRING

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

CABLE TRAY (SIZE AS INDICATED ON PLAN)

ELECTRONIC SECURITY

ACCESS CONTROL JUNCTION BOX

BALANCED MAGNETIC DOOR CONTACT

ELECTRIC STRIKE

CARD READER

ELECTRIC LOCKSET

ELECTRIC HINGE

MOTION DETECTION SENSOR

KEY PAD

DOOR RELEASE

HIGH SECURITY SWITCH

TELECOMMUNICAITONS LEGEND

DC

ES

CR

EL

EH

M

KP

DR

AC

V

LV

J

HSS

S

PA

PP

TELECOMMUNICATIONS ABBREVIATIONS

A OR AMP

AFF

AWG

BLDG

C

CAT

CATV

CFCI

CU

D

DDC

EC

EF

EIA

EMT

EQUIP

ER

ETR

EXIST or EX

FWE

G OR GND

GFGI

GFCI

GRS

H or HT

HVAC

IDF

IDS

IMC

J OR JB

K

KV

KVA

KW

L

LAN

MAX

MDF

MIN

MM

N

NEC

NEMA

NFPA

NIPR

NTS

PDS

PVC

RMC

RPP

RU

SA

SIPR

SM

SPEC

TGB

TIA

TMGB

TP

TR

TYP

UIO

UL

UTP

V

VA

W

WAP

AMPERE(S)

ABOVE FINISHED FLOOR

AMERICAN WIRE GAUGE

BUILDING

CONDUIT

CATEGORY

CABLE TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

COPPER

DEPTH

DIRECT DIGITAL CONTROL FOR HVAC

EMPTY CONDUIT

ENTRANCE FACILITY

ELECTRONICS INDUSTRIAL ALLIANCE

ELECTRICAL METALLIC TUBING

EQUIPMENT

EQUIPMENT ROOM

EXISTING TO REMAIN

EXISTING

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GOVERNMENT FURNISHED CONTRACTOR

INSTALLED

GALVANIZED RIGID STEEL CONDUIT

HEIGHT

HEATING, VENTILATION & AIR CONDITIONING

INTERMEDIATE DISTRIBUTION FRAME

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

KILO

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

LENGTH

LOCAL AREA NETWORK

MAXIMUM

MAIN DISTRIBUTION FRAME

MINIMUM

MULTIMODE

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NON-SECURE INTERNET PROTOCAL ROOTER

NOT TO SCALE

PROTECTIVE DISTRIBUTION SYSTEM

POLYVINAL CHLORIDE

RIGID METAL CONDUIT

REMOTE POWER PANEL

RACK UNIT

SURGE ARRESTOR

SECURE INTERNET PROTOCAL ROOTER

SINGLE MODE

SPECIFICATIONS

TELECOMMUNICATIONS GROUNDING BUSBAR

TELECOMMUNICATIONS INDUSTRIAL ALLIANCE

TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR

TWISTED PAIR

TELECOMMUNICATIONS ROOM

TYPICAL

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

WATTS or WIRE or WIDTH

WIRELESS ACCESS POINT

TELECOMMUNICATIONS GENERAL NOTES:

1. EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ATC) THAT DOES NOT SERVE EF,ER OR TR(S) SHALL NOT BE INSTALLED ABOVE OR IN IT SPACES, NOR SHALL THIS EQUIPMENT PASS THROUGH OR ENTER THE EF, ER OR TR(S).

2. ANY MOTOR, TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN 5KVA SHALL HAVE A MINIMUM OF 47" SPACE

SEPARATION FROM ANY WALL OF EF, ER OR TR(S).

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LIGHTING

FIXTURES AND CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

4. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

5. REFER TO DETAILS AND RISER DIAGRAMS FOR CABLE AND CONDUIT SIZES NOT SHOWN ON PLANS.

6. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

7. PROVIDE WELDED WIRE TYPE CABLE TRAY IN ALL AREAS EXCEPT TR(S). PROVIDE LADDER TYPE CABLE TRAY IN TR(S).

8. FLOOR BOXES AND POKE THRU'S SHALL BE SIZED TO NOT EXCEED TELECOMMUNICATIONS CABLE MINIMUM BEND RADIUS.

9. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALLS. FIRESTOP FIRE RATED BARRIERS IN ACCORDANCE WITH FIRESTOPPING SPECIFICATIONS 07 84 00. SLEEVES AND SLOTS SHALL NOT BE LEFT OPEN AFTER CABLE INSTALLATION. ALL SLEEVES AND SLOTS SHALL BE FIRESTOPPED IN ACCORDANCE WITH FIRESTOPPING SPECIFICATION 07 84 00.

10. EMT: COMPLY WITH ANSI C80.3 AND 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR EACH

SYSTEM:

1. TELECOMMUNICATIONS - ORANGE

2. SECURITY - PURPLE

11. PROVIDE A MINIMUM OF 12" SEPERATION BETWEEN ALL DATA OUTLETS AND ANY POWER LOAD GREATER THAN 5KVA.

12. PROVIDE 3.28’ OF CLEAR, UNOBSTRUCTED SPACE FOR THE INSTALLATION OF ALL CABLING AND EQUIPMENT MOUNTED ON WALLS, RACKS (FRONT AND REAR), CABINETS (FRONT AND REAR) AND ENCLOSURES. PROVIDE AT LEAST 6” DEPTH OFF THE WALL FOR WALL-MOUNTED EQUIPMENT. ALLOCATE SPACE OF 3.28’ WIDE, 3.28’ DEEP AND 7.5’ HIGH FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. PROVIDE SPACE FOR AN AISLE OF AT LEAST 3.28’ WIDE IN THE FRONT AND IN THE REAR OF THE SPACE FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. THIS SPACE SHALL TAKE INTO ACCOUNT THE DEPTH OF RACK-MOUNTED EQUIPMENT

AS WELL AS WALL-MOUNTED EQUIPMENT AND HARDWARE.

13. LOCATE LIGHT SWITCHES NEAR THE ENTRANCE(S) TO THE TELECOMMUNICATION ROOM. DIMMERS AND VACANCY SENSORS ARE NOT PERMITTED TO BE USED WITHIN THE TELECOMMUNICATION ROOM. PROVIDE A MINIMUM OF 50 FOOT-CANDLES OF LIGHT AT

THE POINT OF CABLE TERMINATION.

14. COORDINATE CABLE TRAY, LIGHT FIXTURE AND MECHANICAL UNIT INSTALLATION WITHIN A TELECOMMUNICATION ROOM WITH ALL

TRADES PRIOR TO INSTALLATION.

15. SLEEVES OR CONDUITS ENTERING INTO THE TELECOMMUNICATION ROOM SHALL EXTEND INTO THE SPACE A MINIMUM OF 3” FROM

THE FLOOR, WALL OR CEILING.

16. ALL TELECOMMUNICATION DEVICES SHALL CONNECT TO EXISTING PATCH PANELS LOCATED IN DATA CENTER 128 AND TELECOM

ROOM 158.

17. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158 SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.

18. INTRUSION DETATION SYSTEM SHALL BE ADVANTOR.

19. ACCESS CONTROL SYSTEM SHALL BE SONITROL.

20. SURGE PROTECTION DEVICES SHALL BE PROVIDED IN ACCORDANCE WITH AFI 32-1065 AND NFPA 780.

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y

L a n e

S u ite

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u ite

P

O B o x

S yr a c u s e

N Y

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:5

:4

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a ci lit y/

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v2 .r vt

T-001

100% B3 SUBMITTAL

T E

L E

C O

M M

U N

IC

A

T

IO

N S

G E

N E

R A

L N

O T

E S

A

B B

R E

V

IA

T

IO

N S

L

E G

E N

D

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

G L K

S C

M

S C

M

T E

H

M

A R

C H

NOTE:

1. NOT ALL SYMBOLS OR ABBREVIATIONS SHOWN WILL BE USED

ON THIS PROJECT.

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

BID NOTES:

ALL COMMUNICATION SYSTEMS ARE PART OF A BID

LINE ITEM THAT IS SEPARATE FROM THE BASE BID

AND THE SECURITY SYSTEM BID LINE ITEM.

BASE BID:

ALL CABLE TRAYS, CONDUIT AND PATCH PANELS.

BID LINE ITEM:

THE PURCHASE, INSTALLATION, TESTING AND

LABELING OF ALL COMMUNICATIONS EQUIPMENT,

FACEPLATES AND WIRING.

BID NOTES:

ALL SECURITY SYSTEMS ARE PART OF A BID

LINE ITEM THAT IS SEPARATE FROM THE BASE BID

AND THE COMMUNICATIONS SYSTEM BID LINE ITEM.

BASE BID:

ALL PATHWAYS AND BOXES.

BID LINE ITEM:

THE PURCHASE, INSTALLATION, TESTING AND

LABELING OF ALL SECURITY EQUIPMENT,

FACEPLATES AND WIRING.

File details come from the government source that posted it. Updated .