9 Elec BD.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25522R0002
About this file
This pre-solicitation notice announces a competitive total set-aside for Service-Disabled Veteran-Owned Small Businesses to renovate the second floor center of Building 52 at the Jefferson Barracks Division of the VA Saint Louis Health Care System. The project scope includes renovating approximately 7,200 square feet of former procedure rooms and administrative offices at an estimated cost between $2-5 million. The work must be completed within 410 calendar days of the notice to proceed and is classified under NAICS 236220 with a small business size standard of $39.5 million. Interested parties should monitor beta.sam.gov where the full solicitation will be posted on or about October 15, 2021. A site visit is scheduled and attendance is encouraged. Proposals are due as specified in the solicitation documents to be released.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Scan_2021_11_02_14_28_13_296.pdf | ||
| 36C25522R0002 0001.docx | DOCX document | |
| 36C25522R0002_1.docx | DOCX document | |
| 3 Abate BD.pdf | ||
| P09_S02 -20-028 Specifications 657-20-102JB (1448 pages) final.pdf | ||
| 2 Struct BD.pdf | ||
| 7 Plumb BD.pdf | ||
| 4 Arch BD.pdf | ||
| 5 IntD BD.pdf | ||
| 8 Mech BD.pdf | ||
| Past Performance Questionnaire 36C25522R0002 (Project 657-20-102JB).pdf | ||
| 1 Gen BD.pdf | ||
| 6 FP BD.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L L
ELECTRICAL ABBREVIATIONS LIST
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING
HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT
DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST
COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S
SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED
(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE COR, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE
PERFORMED ON THE ELECTRICAL SYSTEM USING A
BOLTED THREE PHASE FAULT CONDITION FOR
CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND
MECHANICAL STRESS TO THE SYSTEM FOR
CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT
VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR
THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT
CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY
CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM
PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE
REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED
THE RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH
CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP
CALCULATIONS
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DD: DEDICATED CIRCUIT
EM: EMERGENCY
EX: EXISTING
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"*
18"*
18"*
18"*
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
*HEIGHTS FOR RECEPTACLES IN THE EXAM ROOMS WILL BE PER THE ARCH
ELEVATION DRAWINGS.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"*
18"*
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
OS
OS
LS
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:0
P
M
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
DocuSign Envelope ID: 09F7B85F-F4C3-47B1-A14D-410983FE1DB5
8/23/2021
N 1
N 1
IC
CR
RXDC ES
J
J
J
S S
S S
S S
S S
S S
S
S
S
S S
S S
S S
S S
S SS
S S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
EXISTING
PANEL H
EXISTING
PANEL L
X-RAY
PANEL
TREAT. RM.
2S05
EXAM
2S04
CHASE
CH-S-3
EXAM
2S01
STAIRWELL NO. 2
2S02
OFFICE
2N111 OFFICE
2S11A
OFFICE
2S11
HAC
2S10
ELEC. CLOSET
2S9
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
ELEVATOR
E3
P.T. / O.T.
2N58
EXAM
2N118
CORRIDOR
H208
WAITING ROOM
2N112A
EXAM
2S12B
OFFICE
2N60
OFFICE
2N63
HAC
2N64
ELEVATOR
E4
CLOSET
2N59B
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:1
P
M
ED101
SECOND FLOOR ELECTRICAL
DEMOLITION PLAN - PHASE 1
2 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR ELECTRICAL DEMOLITION PLAN - PHASE 1
A. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS
AND CONDUITS THAT ORIGINATE, PASS
THROUGH, OR TERMINATE IN THE AREA OF
WORK. DEMOLISH ALL CIRCUITS THAT ARE
NO LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE
NOT COMPLETELY REMOVED.
B. CONTRACTOR TO DISCONNECT AND REMOVE
ELECTRICAL CONNECTION TO OUTLETS,
RECEPTACLES, HVAC EQUIPMENT AND
OTHER ELECTRICAL DEVICES. REMOVE
CONDUCTORS AND CONDUIT BACK TO
PANELBOARD SERVING EQUIPMENT OR TO
THE POINT WHERE OTHER REMAINING LOADS
ARE CONNECTED. MARK ANY ABANDONED
OVERCURRENT PROTECTION DEVICE AS
"SPARE(UNUSED)".
C. CONTRACTOR SHALL REMOVE ALL
ELECTRICAL CONDUIT, CABLE, WIRING
DEVICE, JUNCTION BOXES, FITTINGS, AND
RELATED ITEMS FROM ALL PORTIONS OF THE
AREA OF WORK INCLUDING WALL, CEILING
AND FLOORS. THIS SHALL BE FOR ALL WALLS,
EVEN WALLS NOT SUBJECT TO REMOVAL.
D. FOR ELECTRICAL CIRCUITS BEING
DEMOLISHED REMOVE BOXES, CONDUIT AND
CONDUCTORS BACK TO SOURCE, INCLUDING
THOSE CONCEALED WITHIN WALLS, LEAVING
NO ABANDONED ITEMS.
E. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT
TO DEMOLITION, THE REMAINING HOLE SHALL
BE PATCHED/REPAIRED TO MAINTAIN THE
RATING OF THE ASSEMBLY.
F. EACH PHASE OF THE CONSTRUCTION IS TO
BE PERFORMED WHILE LEAVING WORK
AREAS OF OTHER PHASES ACTIVE TO THE
GREATEST EXTENT POSSIBLE. NOTIFY COR IF
ANY WORK IS REQUIRED THAT WILL CROSS
MULTIPLE PHASES OF THE WORK AREA
PRIOR TO PERFORMING THE WORK.
G. PANEL SCHEDULES FOR PANELS H AND L ON
E-603.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
1 (TYP.) REMOVE EXISTING FIXTURES,
DOWNLIGHTS, EXIT SIGNS AND DISPOSE.
SEE SHEET NOTE "D". USE FOR LIGHT
FIXTURES.
2 TUNNEL AREA WORK SCHEDULES SHALL BE
COORDINATED WITH ARCHITECTURAL AND
MECHANICAL CONTRACTRORS.
3 EXISTING PANEL TO BE DEMOED IN PHASE 3.
4 EXISTING MECHANICAL UNIT WITH
DISCONNECT SWITCH TO BE DEMOED.
5 REMOVE EXISTING X-RAY POWER PANEL PER
SHEET NOTE "D".
AC
GFCI
DD
DD
GFCI
EM
AC
GFCI
G
FC
I
GFCI
EM
J
CR
RXDC ES
N Z
E
RXDCES
CR
J
J
J
N 1
OS
OS
O S
OS OS
OS
AC
GFCI
E
DD
AC
GFCI
+36"
CR
ES DC RX
M
N 1
J
DD
D
GFCI
S S
S
S S
S S
S
SS
S
S S
S S
S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
EXISTING
PANEL H
EXISTING
PANEL L
EXAM 1
2S05
CORRIDOR
H205
WAITING
2N115
CORRIDOR
H208
TREAT. RM.
2S05
EXAM
2S04
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
ELEVATOR
E3
P.T. / O.T.
2N58
ELEC. CLOSET
2S9
CLOSET
2N59A
ELEVATOR
E4
STAIR 2
S2
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64 OPEN OFFICE
2N59
RESTROOM
2N114
MEDS
2N113
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:1
P
M
ED102
SECOND FLOOR ELECTRICAL
DEMOLITION PLAN - PHASE 2
3 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR ELECTRICAL DEMOLITION PLAN - PHASE 2
A. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS
AND CONDUITS THAT ORIGINATE, PASS
THROUGH, OR TERMINATE IN THE AREA OF
WORK. DEMOLISH ALL CIRCUITS THAT ARE
NO LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE
NOT COMPLETELY REMOVED.
B. CONTRACTOR TO DISCONNECT AND REMOVE
ELECTRICAL CONNECTION TO OUTLETS,
RECEPTACLES, HVAC EQUIPMENT AND
OTHER ELECTRICAL DEVICES. REMOVE
CONDUCTORS AND CONDUIT BACK TO
PANELBOARD SERVING EQUIPMENT OR TO
THE POINT WHERE OTHER REMAINING LOADS
ARE CONNECTED. MARK ANY ABANDONED
OVERCURRENT PROTECTION DEVICE AS
"SPARE(UNUSED)".
C. CONTRACTOR SHALL REMOVE ALL
ELECTRICAL CONDUIT, CABLE, WIRING
DEVICE, JUNCTION BOXES, FITTINGS, AND
RELATED ITEMS FROM ALL PORTIONS OF THE
AREA OF WORK INCLUDING WALL, CEILING
AND FLOORS. THIS SHALL BE FOR ALL WALLS,
EVEN WALLS NOT SUBJECT TO REMOVAL.
D. FOR ELECTRICAL CIRCUITS BEING
DEMOLISHED REMOVE BOXES, CONDUIT AND
CONDUCTORS BACK TO SOURCE, INCLUDING
THOSE CONCEALED WITHIN WALLS, LEAVING
NO ABANDONED ITEMS.
E. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT
TO DEMOLITION, THE REMAINING HOLE SHALL
BE PATCHED/REPAIRED TO MAINTAIN THE
RATING OF THE ASSEMBLY.
F. EACH PHASE OF THE CONSTRUCTION IS TO
BE PERFORMED WHILE LEAVING WORK
AREAS OF OTHER PHASES ACTIVE TO THE
GREATEST EXTENT POSSIBLE. NOTIFY COR IF
ANY WORK IS REQUIRED THAT WILL CROSS
MULTIPLE PHASES OF THE WORK AREA
PRIOR TO PERFORMING THE WORK.
G. PANEL SCHEDULES FOR PANELS H AND L ON
E-603.
1 (TYP.) REMOVE EXISTING FIXTURES,
DOWNLIGHTS, EXIT SIGNS AND DISPOSE.
SEE SHEET NOTE "D". USE FOR LIGHT FIXTURES.
2 EXISTING PANEL TO BE DEMOED IN PHASE 3.
3 EXISTING MECHANICAL UNIT WITH MOTOR RATED
SWITCH TO BE DEMOED.
DD
GFCI
DD
DD
GFCI
EM
G
FC
I
AC
GFCI
G
FC
I
G
FI
G
FI
G
FC
I
GFCI
EM
DD
J
CR
RXDC ES
N 1
N1
N Z
N Z
EE
E
RXDCES
CR
N 1
E
J
J
N 1
OS
OS
O S
OS
OSOS OS
OS
O S
O S
O S
OS
O S
OS OS
OS OS
OS
OS
AC
GFCI
E
CR
ES DC RX
C R
DCES RX
C R
C R
ES
R
X D
C
D C
R X
ES
CRDCRXES
DD
AC
GFCI
+36"
CR
ES DC RX
CR
ES DC RX
J
M
N 1
DD
J J J
DD
D
D
D
A C
G
FC
I
DO
G
FC
I A
C G
FC
I
GFCI
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
EXISTING
PANEL H
EXISTING
PANEL L
OPEN OFFICE
2N60
EQUIP STORAGE
2N111
RESTROOM
2N114
MEDS
2N113
TELEHEALTH
2N112
ELEVATOR LOBBY
H209
EXAM 6
2N118
RESTROOM
2N118A
EXAM 5
2S01
LOGISTICS STORAGE
2N117
SOILED UTILITY
2S10
OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
OI&T_
2S53
WAITING
2N115
CHASE_
H208B
ELECT. CLOSET
H208A
ELEVATOR
E4
STAIR 2
S2
ELEVATOR
E3
ELEVATOR
E2
CLOSET
2N60A
EXAM 1
2S05
RECEPTION
2N115A
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64
EXAM
2S12A
BATH / SHOWER
2S12
HALLWAY
2S13
EXAM
2S13A
OFFICE
2S51
OFFICE
2S49
TOILET
2S50
OFFICE
2S65
STORAGE
2N119
ELEVATOR LOBBY
H205
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
ED103
SECOND FLOOR ELECTRICAL
DEMOLITION PLAN - PHASE 3
4 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS
AND CONDUITS THAT ORIGINATE, PASS
THROUGH, OR TERMINATE IN THE AREA OF
WORK. DEMOLISH ALL CIRCUITS THAT ARE
NO LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE
NOT COMPLETELY REMOVED.
B. CONTRACTOR TO DISCONNECT AND REMOVE
ELECTRICAL CONNECTION TO OUTLETS,
RECEPTACLES, HVAC EQUIPMENT AND
OTHER ELECTRICAL DEVICES. REMOVE
CONDUCTORS AND CONDUIT BACK TO
PANELBOARD SERVING EQUIPMENT OR TO
THE POINT WHERE OTHER REMAINING LOADS
ARE CONNECTED. MARK ANY ABANDONED
OVERCURRENT PROTECTION DEVICE AS
"SPARE(UNUSED)".
C. CONTRACTOR SHALL REMOVE ALL
ELECTRICAL CONDUIT, CABLE, WIRING
DEVICE, JUNCTION BOXES, FITTINGS, AND
RELATED ITEMS FROM ALL PORTIONS OF THE
AREA OF WORK INCLUDING WALL, CEILING
AND FLOORS. THIS SHALL BE FOR ALL WALLS,
EVEN WALLS NOT SUBJECT TO REMOVAL.
D. FOR ELECTRICAL CIRCUITS BEING
DEMOLISHED REMOVE BOXES, CONDUIT AND
CONDUCTORS BACK TO SOURCE, INCLUDING
THOSE CONCEALED WITHIN WALLS, LEAVING
NO ABANDONED ITEMS.
E. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT
TO DEMOLITION, THE REMAINING HOLE SHALL
BE PATCHED/REPAIRED TO MAINTAIN THE
RATING OF THE ASSEMBLY.
F. EACH PHASE OF THE CONSTRUCTION IS TO
BE PERFORMED WHILE LEAVING WORK
AREAS OF OTHER PHASES ACTIVE TO THE
GREATEST EXTENT POSSIBLE. NOTIFY COR IF
ANY WORK IS REQUIRED THAT WILL CROSS
MULTIPLE PHASES OF THE WORK AREA
PRIOR TO PERFORMING THE WORK.
G. PANEL SCHEDULES FOR PANELS H AND L ON
E-603.
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR ELECTRICAL DEMOLITION PLAN - PHASE 3
1 (TYP.) REMOVE EXISTING FIXTURES,
DOWNLIGHTS, EXIT SIGNS AND DISPOSE.
SEE SHEET NOTE "D". USE FOR LIGHT FIXTURES.
2 REMOVE OLD PANELS HANDLE PER SHHET NOTE
"D".
3 EXISTING MECHANICAL UNIT WITH MOTOR
RATED SWITCH TO BE DEMOED.
GFCI
DD
DD
GFCI
EM
AC
GFCI
G
FC
I
GFCI
EM
J
J
J
J
AC
GFCI
DD
AC
GFCI
+36"
J
DD
GFCI
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
OS
OS
O S
OS OS
OS
OS
DDDD
D D
DDD
D
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
PANEL 'HL'PANEL 'LL'
EXAM 1
2S05
TREAT. RM.
2S05
EXAM
2S04
CHASE
CH-S-3
EXAM
2S01
STAIRWELL NO. 2
2S02
OFFICE
2N111
OFFICE
2S11A
OFFICE
2S11
HAC
2S10
ELEC. CLOSET
2S9
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
SCI SERVICE REHAB.
CENTER
2N117A
CORRIDOR
H205
ELEVATOR
E3
P.T. / O.T.
2N58
EXAM
2N118
CORRIDOR
H208
WAITING ROOM
2N112A
WAITING
2N115
OPEN OFFICE
2N59
EXAM
2S12B
OFFICE
2N60
OFFICE
2N63
HAC
2N64
WHEELCHAIR STORAGE
2N110
ELEVATOR
E4
CLOSET
2N59B
RESTROOM
2N114
MEDS
2N113
'LL'- 4
'LL'- 3
'HL'- 1
'HL'- 4
'HL'- 3
'HL'- 2
'LL'- 6
'HL'- 1
'LL'-9
'HL'- 1
'HL'- 33
'HL'- 34
'HL'- 7
(PIXIS)
'LL'- 5
'HL'- 47
'HL'- 5
'HL'- 13
'LL'- 23
FAC DATA RM
2S57A
EP101
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
E2
A1 A1
A1 A1
A1 A1
A1 A1
A1
A1
A1A1
OPEN OFFICE
2N59
WAITING
2N115
SCI SERVICE REHAB.
CENTER
2N117A
EXAM 1
2S05
PANEL 'HL'PANEL 'LL'
TREAT. RM.
2S05
EXAM
2S04
CHASE
CH-S-3
EXAM
2S01
STAIRWELL NO. 2
2S02
OFFICE
2N111
OFFICE
2S11A
OFFICE
2S11
HAC
2S10
ELEC. CLOSET
2S9
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56PAIN REHAB. CENTER
2S56A
CORRIDOR
H205
ELEVATOR
E3
P.T. / O.T.
2N58
EXAM
2N118
CORRIDOR
H208
WAITING ROOM
2N112A
EXAM
2S12B
OFFICE
2N60
OFFICE
2N63
HAC
2N64
WHEELCHAIR STORAGE
2N110
ELEVATOR
E4
CLOSET
2N59B
RESTROOM
2N114
MEDS
2N113
A1
F
F
FAC DATA RM
2S57A
RECEPTION
2N115A
D1 D1
A1 A1 D1
A1
4.4
N.2 N.3
FAC DATA RM
2S57A
'LL'- 25
'LL'- 22
'LL'- 24
'LL'- 27
'LL'- 26 'LL'- 29
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:3
P
M
EP101
SECOND FLOOR ELECTRICAL PLAN -
PHASE 1
5 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N O
R T
H0 4 8 16
1 NEW POWER PANELS TO BE INSTALLED PER
E-602.
2 THE ELECTRICAL PANEL COVERS WILL BE
SENT OUT AND PROFESSIONALLY PAINTED
(POWDER PAINT AND BAKED). THE COLOR
WILL BE COORDINATED WITH THE
ARCHITECTURAL CONTRACTOR.
3 NEW TIMER SWITCH WILL BE CAPABLE OF
BEING SET FOR AN HOUR ON.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR POWER PLAN - PHASE 1
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
E. ALL RECEPTACLES SHALL HAVE THEIR
SOURCE PANEL AND CIRCUIT NUMBER
INDICATED ON THEIR FACEPLATE.
F. ALL LIGHTING CONDUCTORS SHALL BE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT UNLESS
NOTED OTHERWISE:
a. RUNS LESS THAN 150' SHALL BE
MINUMUM 2-12 AWG, 1-12 AWG EG IN 3/4"
CONDUIT.
b. RUNS 150'-250' SHALL BE MINIMUM 2-10
AWG, 1-10 AWG EG IN 3/4" CONDUIT.
c. RUNS GREATER THAN 250' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"
CONDUIT.
G. VERIFY COMPATIBILITY OF ALL LIGHTING
CONTROLS WITH THE LED DRIVERS TO BE
CONTROLLED.
H. PANEL SCHEDULES FOR LL AND HL ON E-603.
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN - Phase 1
Scale: 1/4" = 1'-0"
FAC DATA RM 2S57A POWER PLAN - PHASE 1
GFCI
DD
DD
GFCI
EM
G
FC
I
AC
GFCI
G
FC
I
G
FI
G
FI
G
FC
I
GFCI
EM
DD
J
J
J
AC
GFCI
DD
AC
GFCI
+36"
J
DD
J J J
DD
A C
G
FC
I
G
FC
I A
C G
FC
I
GFCI
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
OS
OS
O S
OS
OSOS OS
OS
O S
O S
O S
OS
O S
OS OS
OS OS
OS
OS
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
EXAM 1
2S05
CORRIDOR
H205
WAITING
2N115
TELEHEALTH
2N112
EXAM 6
2N118
RESTROOM
2N118A
CORRIDOR
H208
OPEN OFFICE
2N60
EXAM 5
2S01
LOGISTICS STORAGE
2N117
CORRIDOR
2N116
EQUIP STORAGE
2N111
TREAT. RM.
2S05
EXAM
2S04
SOILED UTILITY
2S10 OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
ELEVATOR
E3
P.T. / O.T.
2N58
ELEC. CLOSET
2S9
CLOSET
2N59A
ELEVATOR
E4
STAIR 2
S2
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64
OPEN OFFICE
2N59
RESTROOM
2N114
MEDS
2N113
STORAGE
2N119
'HL'- 9 'HL'- 7
'LL'- 1
'LL'- 2
'HL'- 6
'HL'- 8
'HL'- 10
'LL'- 10
'HL'- 12 'HL'- 13
PANEL 'HL'PANEL 'LL'
'HL'- 35
'HL'- 36
'HL'- 37
'HL'- 39
'HL'- 40
(PIXIS)
'LL'- 7
'HL'- 11
'LL'- 23
RECEPTION
2N59D
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
E2
E2
A1 A1
A1 A1
A1 A1 A1
A1A1
A1
A1
A1 A1
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1
A1
D1 D1
EXAM 1
2S05
CORRIDOR
H205
WAITING
2N115
TELEHEALTH
2N112
EXAM 6
2N118
RESTROOM
2N118A
CORRIDOR
H208
OPEN OFFICE
2N60
EXAM 5
2S01
CORRIDOR
2N116
EQUIP STORAGE
2N111
TREAT. RM.
2S05
EXAM
2S04
SOILED UTILITY
2S10
OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
ELEVATOR
E3
P.T. / O.T.
2N58
ELEC. CLOSET
2S9
CLOSET
2N59A
ELEVATOR
E4
STAIR 2
S2
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64
PANEL 'HL'PANEL 'LL'
A1
RECEPTION
2N59D
MEDS
2N113
RESTROOM
2N114
D1D1
D1
D1
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:3
P
M
EP102
SECOND FLOOR ELECTRICAL PLAN -
PHASE 2
6 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
1 NEW TIMER SWITCH WILL BE CAPABLE OF
BEING SET FOR AN HOUR ON.
2 INSTALL 3/4" CONDUIT WITH 5#12 FROM EACH
PB TO JUNCTION BOX FOR HL-39 FOR
AUTOMATIC DOOR OPERATOR. SEE T-102 FOR
MORE INFORMATION.
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
E. ALL RECEPTACLES SHALL HAVE THEIR
SOURCE PANEL AND CIRCUIT NUMBER
INDICATED ON THEIR FACEPLATE.
F. ALL LIGHTING CONDUCTORS SHALL BE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT UNLESS
NOTED OTHERWISE:
a. RUNS LESS THAN 150' SHALL BE
MINUMUM 2-12 AWG, 1-12 AWG EG IN 3/4"
CONDUIT.
b. RUNS 150'-250' SHALL BE MINIMUM 2-10
AWG, 1-10 AWG EG IN 3/4" CONDUIT.
c. RUNS GREATER THAN 250' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"
CONDUIT.
G. VERIFY COMPATIBILITY OF ALL LIGHTING
CONTROLS WITH THE LED DRIVERS TO BE
CONTROLLED.
H. PANEL SCHEDULES FOR LL AND HL ON E-603.
N O
R T
H0 4 8 16
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR POWER PLAN - PHASE 2
Scale: 1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN - Phase 2
GFCI
DD
DD
GFCI
EM
G
FC
I
G
FC
I
AC
GFCI
G
FC
I AC
GFCI
DD
G
FI
G
FI
G
FC
I
GFCI
EM
DD
J
AC
GFCI
AC
GFCI
DD
AC
GFCI
+36"
J
J
J
J
DD
J J J
DD
A C
G
FC
I
AC
GFCI
G
FC
I A
C G
FC
I
G
FC
I
G
FC
I
G
FC
I
GFCI
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
OS
OS
O S
OS
OSOS OS
OS
O S
O S
O S
OS
O S
OS OS
OS OS OSOSOS
OS
O S
O S
O S
OSOS
OS
OS OS
OS
OS
OS
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
OPEN OFFICE
2N60
EQUIP STORAGE
2N111
RESTROOM
2N114
TELEHEALTH
2N112
CONSULT
2S56
ELEVATOR LOBBY
H209
EXAM 6
2N118
RESTROOM
2N118A
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02
EXAM 5
2S01
LOGISTICS STORAGE
2N117
SOILED LINEN
2N120
SOILED UTILITY
2S10
OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
CORRIDOR
H204
OI&T_
2S53
CONFERENCE
2S54
GROUP ROOM
2S58
RECEPTION
2N115A
ELEVATOR
E4
EXAM 1
2S05
SCALE
2N116A
MEDS
2N113
'LL'- 9 'LL'- 13
'LL'- 8
'HL'- 15
CORRIDOR
H204
'HL'- 17
'HL'- 21
'HL'- 20
'HL'- 18
'HL'- 19
PANEL 'HL'PANEL 'LL'
'HL'- 29
'HL'- 30
'HL'- 14
'LL'- 20
'HL'- 31
'HL'- 16
'HL'- 38
'HL'- 45
CORRIDOR
H208
STORAGE
2N119
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
E2
E2
E2
E2
A1 A1 A1 A1 A1 A1 A1 A1 A1
A1 A1
A1 A1
A1
A1
A1 A1
A1
A1
A1
A1 A1 A1 A1
OPEN OFFICE
2N60
EQUIP STORAGE
2N111
TELEHEALTH
2N112
GROUP ROOM
2S58
CONSULT
2S56
ELEVATOR LOBBY
H209
EXAM 6
2N118
RESTROOM
2N118A
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02
EXAM 5
2S01
LOGISTICS STORAGE
2N117
SOILED LINEN
2N120
SOILED UTILITY
2S10
OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
CORRIDOR
H204
OI&T_
2S53
CONFERENCE
2S54
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
CHASE_
H208B
ELECT. CLOSET
H208A
ELEVATOR
E4
STAIR 2
S2
ELEVATOR
E3
ELEVATOR
E2
D1
D1 A1
D1 D1
D1 D1
A1
PANEL 'HL'PANEL 'LL'
FAC DATA RM
2S57A
A1
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:4
P
M
EP103
SECOND FLOOR ELECTRICAL PLAN -
PHASE 3
7 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
E. ALL RECEPTACLES SHALL HAVE THEIR
SOURCE PANEL AND CIRCUIT NUMBER
INDICATED ON THEIR FACEPLATE.
F. ALL LIGHTING CONDUCTORS SHALL BE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT UNLESS
NOTED OTHERWISE:
a. RUNS LESS THAN 150' SHALL BE
MINUMUM 2-12 AWG, 1-12 AWG EG IN 3/4"
CONDUIT.
b. RUNS 150'-250' SHALL BE MINIMUM 2-10
AWG, 1-10 AWG EG IN 3/4" CONDUIT.
c. RUNS GREATER THAN 250' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"
CONDUIT.
G. VERIFY COMPATIBILITY OF ALL LIGHTING
CONTROLS WITH THE LED DRIVERS TO BE
CONTROLLED.
H. PANEL SCHEDULES FOR LL AND HL ON E-603.
N O
R T
H0 4 8 16
N O
R T
H0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR POWER PLAN -PHASE 3
Scale: 1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN - Phase 3
1 FLOOR BOX WITH SINGLE DUPLEX
RECEPTACLE AND HDMI AND 2 X IT(CAT6
STYLE) CONNECTIONS.
2 POWER (A) FOR SCREEN IN CEILING.
3 POWER (B) FOR PROJECTOR IN CEILING.
4 INSTALL 3/4" CONDUIT WITH 5#12 FROM EACH
PB TO JUNCTION BOX FOR HL-38 FOR
AUTOMATIC DOOR OPERATOR. SEE T-103
FOR MORE INFORMATION.
5 INSTALL NEW COMBINATION MANUAL
DIMMER/OCCUPANCY SENSOR SWITCH.
J
M
M
J
M
J
M
J
M
J
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
FCU-2N59S
FCU-2N59B
PANEL H
TYP
EXAM 1
2S05
TREAT. RM.
2S05
EXAM
2S04
CHASE
CH-S-3
EXAM
2S01
STAIRWELL NO. 2
2S02OFFICE
2N111
OFFICE
2S11A
OFFICE
2S11
HAC
2S10
ELEC. CLOSET
2S9
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
SCI SERVICE REHAB.
CENTER
2N117A
CORRIDOR
H205
ELEVATOR
E3
P.T. / O.T.
2N58
EXAM
2N118
CORRIDOR
H208
WAITING ROOM
2N112A
WAITING
2N115
OPEN OFFICE
2N59
EXAM
2S12B
OFFICE
2N60
OFFICE
2N63
HAC
2N64
WHEELCHAIR STORAGE
2N110
ELEVATOR
E4
CLOSET
2N59B
RESTROOM
2N114
FCU-2N115
'HL'- 41
FAC DATA RM
2S57A
'HL'- 24
FCU-2S57A
FCU-2N113
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:5
P
M
EM101
SECOND FLOOR MECHANICAL POWER
PLAN - PHASE 1
8 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL POWER PLAN - PHASE 1
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
1 MOUNT NEMA1 2 POLE 120V 1/4 HP NEXT TO
MOTOR SWITCH ECU UNIT SO IT IS
ACCESSIBLE.
2 120V POWER FOR SINK IN RESTROOM.
N O
R T
H0 4 8 16
M
M
J
J
J
J
J
J
J
JM
M
M
M M
M
M
M
J
J
M
J
M
J
JM
M
J
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
FCU-2S11
FCU-2S11A
FCU-2N116
FCU-2N111
FCU-2N59B
FCU-2S01
PANEL H
TYP
'HL'- 23
FCU-2N117
'HL'- 26
EXAM 1
2S05
CORRIDOR
H205
WAITING
2N115
TELEHEALTH
2N112
EXAM 6
2N118
RESTROOM
2N118A
CORRIDOR
H208
OPEN OFFICE
2N60
EXAM 5
2S01
LOGISTICS STORAGE
2N117
CORRIDOR
2N116
EQUIP STORAGE
2N111
TREAT. RM.
2S05
EXAM
2S04
SOILED UTILITY
2S10 OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
ELEVATOR LOBBY
2S57
ELEVATOR
E2
CORRIDOR
H204
OI&T
2S53
CONFERENCE RM
2S56
PAIN REHAB. CENTER
2S56A
ELEVATOR
E3
P.T. / O.T.
2N58
ELEC. CLOSET
2S9
CLOSET
2N59A
ELEVATOR
E4
STAIR 2
S2
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64
OPEN OFFICE
2N59
RESTROOM
2N114
MEDS
2N113
STORAGE
2N119
'HL'- 25
RECEPTION
2N59D
FCU-2N112
FCU-2N118
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:5
P
M
EM102
SECOND FLOOR MECHANICAL POWER
PLAN - PHASE 2
9 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL POWER PLAN - PHASE 2
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
1 1 120V SINGLE PHASE POWER FOR 24 POWER
SOURCE FOR PLUMBING EQUIPMENT.
2 MOUNT NEMA1 2 POLE 120V 1/4 HP NEXT TO
MOTOR SWITCH ECU UNIT SO IT IS
ACCESSIBLE.
N O
R T
H0 4 8 16
M
M
J
J
J
J
J
J
J
JM
M
M
M M
M
M
M
J
J
J
J
J JJ
M
M M
M
M
M
M
J
J
M
J
M
J
J
JM
J
M
J
S S
S
S S
S S
S
SS
S S
S S
S
S
S
S
2.3
4.4
4.8
6.2
6.5
7.3
8.7
9.5
9.9
K L L.1 L.2 M M.2 M.3 N.1 N.2 N.3 N.4 N.5 P P.1 P.2 P.3 P.4 Q Q.1 R S S.1M.1 M.4
FCU-2N58
FCU-2S56A
FCU-H204
FCU-2S04FCU-2S03FCU-2S02
FCU-2S56 1
TYP
OPEN OFFICE
2N60
EQUIP STORAGE
2N111
RESTROOM
2N114
MEDS
2N113TELEHEALTH
2N112
GROUP ROOM
2S58
CONSULT
2S56
ELEVATOR LOBBY
H209
EXAM 6
2N118
RESTROOM
2N118A
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02
EXAM 5
2S01
LOGISTICS STORAGE
2N117
SCALE
2N116A
SOILED LINEN
2N120
SOILED UTILITY
2S10
OFFICE (PSYCH)
2S11
OFFICE (SW)
2S11A
CORRIDOR
H204
OI&T_
2S53
CONFERENCE
2S54
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
CHASE_
H208B
ELECT. CLOSET
H208A
ELEVATOR
E4
STAIR 2
S2
ELEVATOR
E3
ELEVATOR
E2
CLOSET
2N60A
EXAM 1
2S05
RECEPTION
2N115A
EXAM
2S12B
WHEELCHAIR STORAGE
2N110
HAC
2N64
EXAM
2S12A
BATH / SHOWER
2S12
HALLWAY
2S13
EXAM
2S13A
OFFICE
2S51
OFFICE
2S49
TOILET
2S50
OFFICE
2S65
STORAGE
2N119
ELEVATOR LOBBY
H205
'HL'- 28
'HL'- 27
'HL'- 32
'HL'- 43
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:0
P
M
EM103
SECOND FLOOR MECHANICAL POWER
PLAN - PHASE 3
10 14CNJ
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
DAS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR MECHANICAL POWER PLAN -PHASE 3
A. ALL RECEPTACLE CONDUCTORS ARE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM
UNLESS NOTED OTHERWISE.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL
AND PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
1 MOUNT NEMA1 2 POLE 120V 1/4 HP NEXT TO
MOTOR SWITCH ECU UNIT SO IT IS
ACCESSIBLE.
N O
R T
H0 4 8 16
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN
WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25)
1 (25)
4 (102)
6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A
3A
A
CEILING HANGER
WIRE, TYP.
WIRE TIE OR
SCREW BAR
HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
ARCHITECTURAL
CEILING GRID RECESSED CAN
LUMINAIRE
RECESSED CAN
LUMINAIRE
ARCHITECTURAL CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION
WIRE REFER TO
SPECIFICATION SECTION 26
51 00
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6'
[1829MM] LONG MAX
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE. REFER TO
SPECIFICATION SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING
TILE, TYP.
ARCHITECTURAL
CEILING GRID
1/4" SCREW
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
FIXTURE WHIP FROM JUNCTION
BOX (6' [1829MM] LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERES. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIRE. REFER TO
SCHEDULE
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER
TO SCHEDULE
ACOUSTICAL CEILING
TILE (TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
SPRING NUT
CONDUIT FITTING
JUNCTION BOX
(SIZE AS
REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
BEAM
CLAMP,
TYP.
CONDUIT
TRAPEZE PER
SD260533-03, TYP. CONDUIT,
TYP.
STEEL
EXPANSION
ANCHOR
STRUCTURAL MEMBER
(BEAM , JOIST, ETC.), TYP.
SEISMIC OR
EXPANSION
JOINT. FIELD
VERIFY
ACTUAL
CONDITIONS &
LOCATIONS.
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
PROVIDE 127MM (5") OF SLACK AT
MIDPOINT BETWEEN TWO END OF
FLEXIBLE GALVANIZED STEEL
CONDUIT. PROVIDE GREEN INSULATED
COPPER EQUIPMENT GROUNDING
CONDUCTOR WITH FLEXIBLE CONDUIT.
914mm
(3'-0") MAX
PROVIDE EXTRA
CABLE TO MAKE
COMPLETE LOOP
AROUND BOX
PERIMETER
G…