5 IntD BD.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25522R0002
About this file
This notice describes a competitive total set-aside federal contract opportunity to renovate approximately 7,200 square feet on the second floor center of Building 52 at the Jefferson Barracks VA Medical Center in St. Louis, Missouri. The contractor will provide all labor, materials, tools and equipment to complete the project, including renovating former procedure rooms comprising 1,600 square feet and performing light to medium renovations on administrative offices. The project costs range from $2 million to $5 million, have a NAICS code of 236220, and must be completed within 410 calendar days of the notice to proceed. The solicitation will be posted on October 15, 2021 to beta.SAM.gov and only one organized site visit will be scheduled. The successful offeror must self-perform at least 15% of construction labor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Scan_2021_11_02_14_28_13_296.pdf | ||
| 36C25522R0002 0001.docx | DOCX document | |
| 36C25522R0002_1.docx | DOCX document | |
| 3 Abate BD.pdf | ||
| P09_S02 -20-028 Specifications 657-20-102JB (1448 pages) final.pdf | ||
| 2 Struct BD.pdf | ||
| 9 Elec BD.pdf | ||
| 7 Plumb BD.pdf | ||
| 4 Arch BD.pdf | ||
| 8 Mech BD.pdf | ||
| Past Performance Questionnaire 36C25522R0002 (Project 657-20-102JB).pdf | ||
| 1 Gen BD.pdf | ||
| 6 FP BD.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL FINISH NOTES
1. REFERENCE ROOM FINISH SCHEDULE , FINISH MATERIAL LEGEND AND
SPECIFICATION 09 06 00 SCHEDULE OF FINISHES FOR MORE INFORMATION.
2. REFERENCE REFLECTED CEILING PLAN FOR ADDITIONAL CEILING INFO.
3. PREPARE ALL FLOOR AND WALL CONSTRUCTION, NEW AND/OR EXISTING, TO
RECEIVE NEW FINISHES IN ACCORDANCE WITH MANUFACTURER’S
RECOMMENDED INSTALLATION METHODS AND MATERIALS FOR ALL FINISHES.
4. PRIOR TO INSTALLATION OF NEW FINISHES, CONTRACTOR SHALL INSPECT ALL
SUBSTRATES. IF A SUBSTRATE IS DEEMED UNACCEPTABLE, THE
CONTRACTOR SHALL TAKE THE NECESSARY STEPS TO RECTIFY THE
SITUATION OR CONTACT THE ARCHITECT WITH THE CONCERN. PROCEEDING
WITH THE INSTALLATION OF FINISHES WILL BE INDICATION THAT THE
INSTALLER / FINISHER ACCEPTS CONDITION OF SUBSTRATE.
5. USE MANUFACTURER'S RECOMMENDED INSTALLATION METHODS AND
MATERIALS FOR ALL FINISHES.
6. ALL NECESSARY TILE FLOORING UNDERLAYMENT TO BE PROVIDED AND
INSTALLED BY FLOORING CONTRACTOR
7. ALL FLOORING TRANSITIONS SHALL COMPLY WITH ADA GUIDELINES.
FLOORING CONTRACTOR TO SUBMIT A DIAGRAM SHOWING FLOORING
TRANSITION LOCATIONS FOR DESIGNERS APPROVAL PRIOR TO INSTALLATION.
8. ALL TRANSITION/REDUCER STRIPS AND OTHER THRESHOLDS TO BE LOCATED
AT CENTERLINE OF DOOR WHEN IN CLOSED POSITION
9. ALIGN FLOORING TRANSITIONS WITH FINISH BASE EXCEPT AT DOORS, U.N.O.
10. FLOOR FINISHES ARE TO EXTEND UNDER NEW BUILT-IN CABINETS.
11. FINISH LEVEL OF GYP. BD. WALLS AND SOFFITS TO BE LEVEL 4, U.N.O.
12. ALL PAINTED WALLS TO BE PAINTED P-1 UNLESS NOTED OTHERWISE.
13. ALL GYP. BOARD CEILINGS TO BE PAINTED P-5, U.N.O.
14. ALL PAINTED SURFACES SHALL RECEIVE A MINIMUM OF (1) ONE BASE COAT
AND (2) TWO FINISH COATS
15. PAINTED SHEEN LEVEL TO BE SATIN/EGG-SHELL FOR ALL WALLS, U.N.O.
SHEEN FOR ALL WET AREA WALLS, METAL DOORS AND METAL FRAMES TO BE
SEMI-GLOSS.
16. PAINT ALL EXPOSED METAL SURFACES, SUCH AS GRILLES, FIRE EXTINGUISHER
CABINETS, ETC. WITH PAINT TO MATCH ADJACENT SURFACE.
17. ALL NEW INTERIOR WINDOW SILLS TO BE SS-2, UNLESS NOTED OTHERWISE.
18. ALL HOLLOW METAL DOORS AND FRAMES TO BE PAINTED P-4.
1. CONTRACTOR TO COORDINATE THE TEXT OF SIGN INSERTS WITH COR
2. SIGNS TO MATCH VA CAMPUS SIGNAGE STANDARDS. COLORS TO BE DETERMINED
BY FACILITIES.
3. ALL SIGNAGE SHALL BE CONTRACTOR FURNISHED AND INSTALLED.
4. ALL APPLIANCES SHALL BE CONTRACTOR FURNISHED AND INSTALLED.
CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO ORDER AND
INSTALLATION OF APPLIANCES.
5. PERMANENT ROOM SIGNAGE MUST INCLUDE RAISED LETTERS AND
BRAILLE.SIGNAGE SHALL BE LOCATED AT LATCH SIDE OF DOOR AND MUST
BEMOUNTED IN ACCORDANCE WITH ALL CURRENT ADA STANDARDS.
6. IF WALL SPACE IS NOT AVAILABLE FOR SIGNAGE ON LATCH SIDE OF DOOR PER
MOUNTING STANDARDS, SIGNS SHALL BE INSTALLED PER CURRENT ADA
STANDARDS ON NEAREST ADJACENT WALL.
WM = WALL MOUNTED
DM = DOOR MOUNTED
FM = FLAG MOUNTED
BM = BULKHEAD MOUNTED
CM= CEILING MOUNTED
GENERAL SIGNAGE NOTES
SIGNAGE LEGEND
1. ALL CORNER GUARDS TO BE FROM TOP OF BASE TO CEILING.
2. PROVIDE BLOCKING IN WALLS FOR ALL CRASH/HAND RAILS AND BUMPER
RAILS.
3. TYPICAL WALL PROTECTION HEIGHT IS 4'-0"H ROOMS AND CORRIDORS
ARE 3'-0"H AS SHOWN ON ELEVATIONS.
4. SEE TYPICAL DETAIL SECTIONS ON SHEET I-101.
5. HANDRAIL NOT TO BE BEHIND DOORS WITH CLOSURES AND START
HANDRAIL 6" AWAY FROM START OF DOOR WHEN OPEN.
6. STANDARD WALL PROTECTION (SHEET) TO BE .040" THICKNESS FOR
DRYWALL APPLICATIONS.
7. SEE SPECIFICATION 09 06 00 SCHEDULE OF FINISHES FOR MATERIALS
AND FINISHES.
WALL PROTECTION NOTES
CG: CORNER GUARD
CHR: CHAIR RAIL
CR: CRASH RAIL
HR: HANDRAIL
HIW: HIGH IMPACT WALL COVERING
WALL PROTECTION ABBREVIATION LEGEND
1. REFER TO EQUIPMENT DRAWINGS FOR LOCATIONS AND DIMENSIONS.
REFER TO MECHANICAL, ELECTRICAL, PLUMBING, AND TEL/IT DRAWINGS
FOR ADDITIONAL REQUIRED UTILITY CONNECTIONS AND LOCATIONS.
2. REFER TO SHEETS I-407 THRU 409 FOR ENLARGED TOILET ROOMS
3. REFER TO REFLECTED CEILING PLANS A-101 THRU A-104 FOR CUBICLE
CURTAINS LOCATIONS AND PATIENT LIFTS
4. SEE ENLARGED EQUIPMENT PLANS ON SHEETS I-421 THRU 423
5. SEE EQUIPMENT SCHEDULES ON SHEETS I-601 THRU 603 FOR SPECIFICS
ON EQUIPMENT BY ROOM
6. SEE G100 FOR STANDARD MOUNTING HEIGHTS AND BLOCKING
INFORMATION
7. ITEM TAGS INCLUDE ACQUISITION AND INSTALLATION RESPONSIBILITIES
(ACQ.), DENOTED AS FOLLOWS:
ABBREVIATION LEGEND
"VV" = VA PROVIDED & VA INSTALLED
"VC" = VA PROVIDED & CONTRACTOR
INSTALLED
“CC" = CONTRACTOR PROVIDED &
CONTRACTOR INSTALLED
EQUIPMENT NOTES
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:0
P
M
I-001
FINISH SCHEDULE
1 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
FINISH ABBREVIATIONS
ACT ACOUSTICAL CEILING TILE
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
CT CERAMIC TILE
DG DOOR FRAME GUARD
EPX EPOXY FLOORING
EX EXISTING
EXP EXPOSED
G GROUT
GYP GYPSUM WALL BOARD
HIW HIGH IMPACT WALLPROTECTION
LAM PLASTIC LAMINATE
LF LINEAR FEET (FOOT)
LVT LUXURY VINYL TILE
MTL METAL
MISC MISCELLANEOUS
NA NOT APPLICABLE
P PAINT
RB RESILIENT WALL BASE
RVT RESILIENT VINYL TILE
SF SQUARE FEET (FOOT)
SS SOLID SURFACE
SST STAINLESS STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VIF VERIFY IN FIELD
WP WALL PROTECTION
WSF WELDED SHEET FLOORING
WSFB WELDED SHEET FLOORING BASE
ROOM FINISH SCHEDULE
ROOM NO. NAME FLOOR BASE
WALLS
CEILING
FINISH Comments
EAST NORTH SOUTH WEST
FIN FIN FIN FIN
2N60 OPEN OFFICE LVT-1 RB-1 P-1 P-3 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2N60A CLOSET LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
2N111 EQUIP STORAGE LVT-1 RB-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 ACT-1/GYP HIW-1 @ 4'-0"H WAINSCOT PERIMETER OF ROOM
2N112 TELEHEALTH LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1/GYP
2N113 MEDS LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
2N114 RESTROOM RES-1 RESB-1 CT-1 CT-1 CT-1 CT-1 ACT-2
2N115 WAITING LVT-1 RB-1 P-2/HIW-2 P-2/HIW-2,3 P-2/HIW-2 P-2/HIW-2 ACT-1/GYP REFER TO ELEVATIONS ON I-401 FOR LOCATIONS
OF HIW-2 & HIW-3
2N115A RECEPTION LVT-1 RB-1 P-1/HIW-3 P-1 P-1 P-1 ACT-1/GYP HIW-3 TO BE FULL HEIGHT
2N116 CORRIDOR LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
2N116A SCALE LVT-1 RB-1 P-1/HIW-1 P-1/HIW-1 -- P-1/HIW-1 ACT-1 HIW-1 @ 4'-0"H WAINSCOT PERIMETER OF ROOM
2N117 LOGISTICS STORAGE WSF-1 WSFB-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 ACT-2 HIW-1 @ 4'-0"H WAINSCOT PERIMETER OF ROOM
2N118 EXAM 6 LVT-1 RB-1 P-1 P-2 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2N118A RESTROOM RES-1 RESB-1 CT-1 CT-1 CT-1 CT-1 ACT-2
2N119 STORAGE LVT-1 RB-1 P-1/HIW-1 P-1/HIW-1 P-1/HIW-1 P-1/HIW-1 ACT-1
2N120 SOILED LINEN LVT-1 RB-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 EP-1/HIW-1 ACT-2 HIW-1 @ 4'-0"H WAINSCOT PERIMETER OF ROOM
2S01 EXAM 5 LVT-1 RB-1 P-1 P-1 P-2 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S02 EXAM 4 LVT-1 RB-1 P-1 P-1 P-2 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S03 EXAM 3 LVT-1 RB-1 P-1 P-1 P-2 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S04 EXAM 2 LVT-1 RB-1 P-1 P-1 P-2 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S05 EXAM 1 LVT-1 RB-1 P-2 P-1 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S10 SOILED UTILITY ETR ETR ETR ETR ETR ETR ACT-2/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S11 OFFICE (PSYCH) LVT-1 RB-1 P-3 P-1 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S11A OFFICE (SW) LVT-1 RB-1 P-1 P-1 P-1 P-3 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S53 OI&T_ ETR ETR ETR ETR ETR ETR --
2S54 CONFERENCE LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S56 CONSULT LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
2S57A FAC DATA RM LVT-1 RB-1 P-1 P-1 P-1 P-1 --
2S58 GROUP ROOM LVT-1 RB-1 P-3 P-3 P-3 P-3 ACT-1/GYP PAINT ALL EXPOSED SIDES OF GYP WINDOW
SOFFIT P-1
E2 ELEVATOR -- -- -- -- -- -- --
E3 ELEVATOR -- -- -- -- -- -- --
E4 ELEVATOR -- -- -- -- -- -- --
H204 CORRIDOR LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
H205 ELEVATOR LOBBY LVT-1 RB-1 P-2/HIW-2 -- -- P-2/HIW-2,3 ACT-1 REFER TO ELEVATIONS ON I-401 FOR LOCATIONS
OF HIW-2 & HIW-3
H208 CORRIDOR LVT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
H208A ELECT. CLOSET LVT-1 RB-1 P-1 P-1 P-1 P-1 --
H208B CHASE_ -- -- -- -- -- -- --
H209 ELEVATOR LOBBY LVT-1 RB-1 P-1 P-1 P-1 HIW-3 GYP HIW-3 TO BE FULL HEIGHT
S2 STAIR 2 -- -- -- -- -- -- --
DocuSign Envelope ID: 888B11FB-E4E1-443E-953F-123DFA36EAA4
8/23/2021
S
S
S S
S S
S
SS
S S
S S
S
S
S
S
S SS
K L L.1 L.2
M
M.3 N.1 N.3 N.5
P
P.1
P.2 P.4
Q Q.1 R S
4.4
6.5
7.3
9.9
M.1
M.4
OPEN
OFFICE
2N60
GROUP
ROOM
2S58
ELEVATOR
LOBBY
H209
CONSULT
2S56 CONFERENCE
2S54
EXAM 5
2S01 EXAM 4
2S02
EXAM 3
2S03
EXAM 2
2S04
2N120
SOILED LINEN
RESTROOM
2N118A
SCALE
2N116A
LOGISTICS
STORAGE
2N117
EXAM 6
2N118
TELEHEALTH
2N112
RESTROOM
2N114
EQUIP
STORAGE
2N111
SOILED
UTILITY
2S10
OFFICE
(PSYCH)
2S11
OFFICE
(SW)
2S11A
OI&T_
2S53 CORRIDOR
H204
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
ELECT.
CLOSET
H208A
CHASE_
H208B
I-201 I-201
I-401
I-40115
I-401
I-401 5 I-401
I-201
I-4018
S S
S
S S
ELEVATOR
E4
STAIR 2
S2
ELEVATOR
E3
ELEVATOR
E2
CLOSET
2N60A
MEDS
2N113
EXAM 1
2S05
RECEPTION
2N115A
I-401
I-4016
I-401 34
I-2015
I-201
I-2015
I-201 5I-201 5
I-201 5
I-201
I-201
I-20110
I-201
STORAGE
2N119
I-401 1110
I-201
I-2017
I-2017
I-201 7
I-201 7
I-201
I-201 8
I-201 8
I-201
I-201
I-201
I-201
I-201
I-201
I-2019
I-201
I-201
I-201
I-201
I-201
I-201
I-201
FAC
DATA RM
2S57A
1 1
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE BARRIER WITH 1
HOUR FIRE RESISTANCE
3"
3/8"
STEEL STUD
(BY OTHERS)
G.W.B.
(BY OTHERS)
REGRIND RETAINER
(24U026000)
#6 X 1 5/8" BUGLE HD SMS
18" [457.2mm] MAX.
PTEG EXTERIOR COVER
R1/4" [R6.4mm]
FINISHED FLOOR
SCHEDULED BASE
FINISHED WALL
HANDRAIL
T.O. HANDRAIL TO BE 36".
BLOCKING
CRASH RAIL
FINISHED FLOOR
SCHEDULED BASE
F O
R D
IM
S
R E
F E
L E
V A
T
IO
N
HIGH IMPACT WALL
PROTECTION PANELS
FINISHED WALL OR METAL
TRIM SEE SPECIFICATION
AND LOCATION
PAINT OR WALLCOVERING
FINISHED FLOOR
BASE
FINISHED WALL
HIGH IMPACT WALL
PROTECTION PANELS
CRASH RAIL
FINISHED WALL OR METAL
TRIM SEE SPECIFICATION
AND LOCATION
FINISHED FLOOR
SCHEDULED BASE
F O
R D
IM
S
R E
F E
L E
V A
T
IO
N
HIGH IMPACT WALL
PROTECTION PANELS
PAINT OR WALLCOVERING
CHAIR RAIL
BLOCKING
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:1
P
M
I-101
SECOND FLOOR FINISH AND WALL
PROTECTION PLAN
2 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N O
R T
H0 4 8 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR FINISH AND WALL PROTECTION PLAN
WALL RATED LINES
Scale: 6" = 1'-0"
CORNER GUARD DETAIL
Scale: 1" = 1'-0"
HANDRAIL AND CRASH RAIL SECTION
Scale: 1" = 1'-0"
HIGH IMPACT WALL PANEL SECTION
1 PROVIDE AND INSTALL CORNER GUARDS
2 PROVIDE AND INSTALL WINDOW FILM WF-1
Scale: 1" = 1'-0"
TYPICAL HIGH IMPACT WALL
PANEL WITH CRASH RAIL
SECTION
Scale: 1" = 1'-0"
HIGH IMPACT WALL PANEL
WITH CHAIR RAIL SECTION
S
S S
S S
S
SS
S S
S S
S
S
S
S
S SS
K L L.1 L.2
M
M.3 N.1 N.3 N.5
P
P.1
P.2 P.4
Q Q.1 R S
4.4
6.5
7.3
9.9
M.1
M.4
OPEN
OFFICE
2N60
EQUIP
STORAGE
2N111
RESTROOM
2N114
TELEHEALTH
2N112
GROUP
ROOM
2S58
CONSULT
2S56ELEVATOR
LOBBY
H209
EXAM 6
2N118
RESTROOM
2N118A
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02
EXAM 5
2S01
LOGISTICS
STORAGE
2N117
SCALE
2N116A
SOILED
LINEN
2N120
SOILED
UTILITY
2S10
OFFICE
(PSYCH)
2S11
OFFICE
(SW)
2S11A
CORRIDOR
H204
OI&T_
2S53
CONFERENCE
2S54
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
S S
S
S S
CHASE_
H208B
ELECT.
CLOSET
H208A
ELEVATOR
E4
STAIR 2
S2
ELEVATOR
E3
ELEVATOR
E2
CLOSET
2N60A
RECEPTION
2N115A
MEDS
2N113
EXAM 1
2S05
2N119
STORAGE
FINISH KEY
LVT-1
RES-1
WSF-1
EXISTING FLOOR TO REMAIN
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE BARRIER WITH 1
HOUR FIRE RESISTANCE
1. REFERENCE SHEET A-601 FOR EXPANSION
JOINT AND FLOORING TRANSITION DETAILS.
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:1
P
M
I-121
SECOND FLOOR FLOOR PATTERN
PLAN
3 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N O
R T
H0 4 8 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR PATTERN PLAN
WALL RATED LINES
1 EXPANSION JOINT
S
S S
S S
S
SS
S S
S S
S
S
S
S
K L L.1 L.2
M
M.3 N.1 N.3 N.5
P
P.1
P.2 P.4
Q Q.1 R S
4.4
6.5
7.3
9.9
M.1
M.4
OPEN
OFFICE
2N60
GROUP
ROOM
2S58
ELEVATOR
LOBBY
H209
CONSULT
2S56
CONFERENCE
2S54
EXAM 5
2S01 EXAM 4
2S02
EXAM 3
2S03
EXAM 2
2S04
2N120
SOILED LINEN
RESTROOM
2N118A
SCALE
2N116ALOGISTICS
STORAGE
2N117
EXAM 6
2N118
TELEHEALTH
2N112
RESTROOM
2N114
EQUIP
STORAGE
2N111
SOILED
UTILITY
2S10
OFFICE
(PSYCH)
2S11
OFFICE
(SW)
2S11A
OI&T_
2S53 CORRIDOR
H204
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
ELECT.
CLOSET
H208A
CHASE_
H208B
S S
S
S S
CLOSET
2N60A
MEDS
2N113
EXAM 1
2S05
RECEPTION
2N115A
STORAGE
2N119
52-02-N001 52-02-N002
52-02-N006
52-02-N007
52-02-N008
52-02-N009
52-02-N010 52-02-N01152-02-N01252-02-N013
52-02-N014
52-02-N015
52-02-N016
52-02-N01952-02-N020 52-02-N021
52-02-N022 52-02-N023
52-02-N024 52-02-N025 52-02-N026
52-02-N027
52-02-N028
52-02-N030
52-02-N037
52-02-N029 52-02-N031
52-02-N033
52-02-N03452-02-N03652-02-N038
52-02-N017
52-02-N035
52-02-N039
52-02-N032 52-02-N00452-02-N018
FAC
DATA RM
2S57A 52-02-N040
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
I-141
SECOND FLOOR SIGNAGE PLAN AND
SCHEDULE
4 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR SIGNAGE PLAN
N O
R T
H0 4 8 16
I-SIGNAGE SCHEDULE
Mark Type Sign Type Name Proposed Content Sign Mounting
52-02-N001 Elevator Call Button ELEVATOR (#), Level (2), Text: ELEVATOR WM
52-02-N002 Directional with Arrow Insert: ARROW, OFFICES, RECEPTION/WAITING WM
52-02-N003 Directional with Arrow Insert: ARROW, OFFICES, RECEPTION/WAITING WM
52-02-N004 Perpendicular Flag Mount Insert: ARROW, CHECK-IN WM
52-02-N006 Primary Room Identification with Insert Room: 2N115 Insert: STAFF WM
52-02-N007 Primary Room Identification with Insert Room: 2S05 Insert: EXAM 1 WM
52-02-N008 Primary Room Identification with Insert Room: 2N117 Insert: LOGISTICS STORAGE WM
52-02-N009 Primary Room Identification with Insert Room: 2N120 Insert: SOILED LINEN WM
52-02-N010 Primary Room Identification with Insert Room: 2S04 Insert: EXAM 2 WM
52-02-N011 Primary Room Identification with Insert Room: 2S04 Insert: EXAM 3 WM
52-02-N012 Primary Room Identification with Insert Room: 2S02 Insert: EXAM 4 WM
52-02-N013 Primary Room Identification with Insert Room: 2S01 Insert: EXAM5 WM
52-02-N014 Primary Room Identification with Insert Room: 2N119 Insert: STORAGE WM
52-02-N015 Primary Room Identification with Insert Room: 2N118 Insert: EXAM 6 WM
52-02-N016 Primary Room Identification with Insert Room: 2N118A Insert: RESTROOM WM
52-02-N017 Life Safety Identification FIRE EXTINGUISHER CABINET WM
52-02-N018 Perpendicular Flag Mount Insert: ARROWS, ELEVATOR WM
52-02-N019 Perpendicular Flag Mount Room: 2N114 Insert: RESTROOM GRAPHICS WM
52-02-N020 Primary Room Identification with Insert Room: 2N114 SYMBOL: UNISEX ACCESSIBLE TEXT: UNISEX WM
52-02-N021 Primary Room Identification with Insert Room: 2N113 Insert: MEDS WM
52-02-N022 Primary Room Identification with Insert Room: 2N112 Insert: TELEHEALTH WM
52-02-N023 Primary Room Identification with Insert Room: 2N111 Insert: EQUIPMENT STORAGE WM
52-02-N024 Life Safety Identification FIRE EXTINGUISHER CABINET WM
52-02-N025 Primary Room Identification with Insert Room: 2C10 Insert: IT WM
52-02-N026 Primary Room Identification with Insert Room: 2N60 Insert: OFFICE WM
52-02-N027 Elevator Call Button ELEVATOR (#), Level (2), Text: ELEVATOR WM
52-02-N028 Primary Room Identification with Insert Room: 2S58 Insert: GROUP ROOM WM
52-02-N029 Primary Room Identification with Insert Room: 2S54 Insert: CONFERENCE WM
52-02-N030 Primary Room Identification with Insert Room: 2S56 Insert: CONSULT WM
52-02-N031 Life Safety Identification FIRE EXTINGUISHER CABINET WM
52-02-N032 Perpendicular Flag Mount Insert: ARROW, ELEVATOR WM
52-02-N033 Elevator Call Button ELEVATOR (#), Level (2), Text: ELEVATOR WM
52-02-N034 Primary Room Identification with Insert Room: 2S11A Insert: OFFICE WM
52-02-N035 Directional with Arrow Insert: ARROW, OFFICES, RECEPTION/WAITING WM
52-02-N036 Primary Room Identification with Insert Room: 2S11 Insert: OFFICE WM
52-02-N037 Primary Room Identification with Insert Room: 2S10 Insert: SOILED WM
52-02-N038 Stair Identification Stair (#), Level (2), Text: Keep Door Closed WM
52-02-N039 Prohibit, Instructional and Control Sign AED WM
52-02-N040 Primary Room Identification with Insert Room: 2S57A Insert: FACILITY DATA WM
THE FOLLOWING NOTES ARE SPECIFIC TO PLASTIC
LAMINATE CASEWORK AND ARE IN ADDITION TO THE
GENERAL FINISH NOTES.
1. FIELD VERIFY ALL CASEWORK AND SHELVING
DIMENSIONS.
2. PROVIDE WALL BRACKET SUPPORTS AT 36"
O.C. MAX. TO SUPPORT COUNTERTOP AT
CONTINUING KNEE SPACE.
3. USE BLACK 2 1/2" DIAMETER GROMMETS
WHERE GROMMETS ARE INDICATED AT 3’-0”
O.C. AT ALL KNEE SPACES.
4. PROVIDE FINISHED END PANEL AT EXPOSED
CASEWORK ENDS AND BACKS AS NEEDED.
PANEL TO MATCH PLASTIC LAMINATE,
STAINLESS STEEL OR MELAMINE FINISH,
BASED ON CABINET TYPE. WHEN FILLER
PANELS ARE REQUIRED AT BOTH ENDS OF
CASEWORK TERMINATION, BOTH FILLER
PANELS SHALL BE EQUAL WIDTH, UNLESS
OTHERWISE NOTED.
5. ADD FILLER PANEL AS NEEDED AT CABINETS,
WARDROBES, DRAWERS, APPLIANCES, ETC.
TO ENSURE FULL DOOR SWING AND DRAWER
OPERATION. PROVIDE FILLER PANELS AND
TRIM WHERE EQUIPMENT IS LOCATED WITHIN
CABINETS.
6. COUNTERTOPS TO HAVE 1/2" RADIUS AT
EXPOSED CORNERS.
7. ALL COUNTERTOPS TO BE SOLID SURFACE
WITH POST FORM PROFILE. ALL
COUNTERTOPS ARE 1 1/2" THICK WITH 4" HIGH
BACK/SIDE SPLASHES UNLESS NOTED
OTHERWISE. ALL JOINTS IN COUNTERTOPS,
SPLASHES AND CURBS SHALL ALIGN AND BE
SMOOTH. PROVIDE END SPLASH AT SIDES
WHEN COUNTERTOP IS ADJACENT TO WALL.
8. ALL COUNTERTOPS TO EXTEND 1" BEYOND
FRONT OF CABINET DOOR FACE.
9. ALL WALL CABINETS TO BE 15"D OUT TO OUT
UNLESS NOTED OTHERWISE WITH LIGHT
VALANCE.
10. ALL WALL CABINETS TO HAVE SLOPE TOPS
UNLESS A BULKHEAD IS PRESENT.
11. ALL SHELVING SHOWN WITH DASHED LINES IN
ELEVATIONS TO BE ADJUSTABLE.
12. ALL BASE CABINETS TO BE 23" DEEP WITH 24”
DEEP COUNTERTOP INCLUDING BACKSPLASH
UNLESS NOTED OTHERWISE WITH
13. PROVIDE AN APRON AT ALL KNEE SPACES &
SINKS, U.N.O. PROVIDE 30" WIDE (MIN.x 27"
HIGH (MIN.) CLEAR OPEN SPACE UNDER EACH
ADA ACCESSIBLE SINK.
14. PROVIDE PIPE WRAP AT EXPOSED PIPES.
15. PROVIDE SHEET METAL OR FIRE RETARDANT
WOOD BLOCKING IN WALL CAVITIES FOR
ITEMS THAT ARE REQUIRED TO BE SECURED
TO THE WALLS. REFERENCE MECHANICAL,
PLUMBING, ELECTRICAL AND TECHNOLOGY
DRAWINGS. COORDINATE WITH FURNITURE
SUPPLIER WHERE APPROPRIATE.
16. SEE SHEET I-202 FOR TYPICAL CABINET
SECTIONS.
GROMMET
FILLER PANEL
EQUIPMENT - BY OTHERS
PROVIDE AND INSTALL CONCEALED SUPPORT
BRACKET
25"D SOLID SURFACE COUNTERTOP WITH SIDE
AND BACK SPLASH, SS-1
FINISHED END PANEL
SOLID SURFACE WALL SPLASH, SS-1
30"D SOLID SURFACE COUNTERTOP, SS-1,
OVERHANG COUNTERTOP 3 3/4" ON PATIENT SIDE
HIW-2 ALONG WALL BELOW COUNTERTOP
OVERHANG
SOLID SURFACE WINDOW SILL AND TRIM, REFER
TO DETAILS 11/I-121, 12/I-201, AND 13/I-201
MC1MC1
MC2
2'-6" 2'-6"
5'-0"
2'-6"
5'-0"
I-201
I-201
I-201
I-201
I-201
I-201
I-201
I-201
I-201
I-201
I-201
I-201
3'-3" 2'-6"
1"
5'-10"
W2 W1
SB1B1
1"
2'-6"1'-3"2'-0"
5'-10 3/4"
4'-1 1/2"
EQ EQ
1. LAYOUT SUBJECT TO VERIFICATON OF FIELD DIMENSIONS AND CONDITIONS
2. ALL WALLS THAT ARE TO RECEIVE WALL RAILS MUST HAVE A MINIMUM 20 GAUGE METALL
STUDS 16" ON CENTER WITH EITHER 5/8" GYPSUM WALLBOARD. STUDS MUST BE
ANCHORED TO THE BUILDING STRUCTURE AT THE FLOOR AND ABOVE THE CEILING, ALL
WALLS MUST BE LEVEL AND PLUMB TO INSTALL THE MODULAR WALL CASEWORK.
3. MODULAR CASEWORK WALL RAILS TO BE MOUNTED AT 69" AFF AND 33-1/8" AFF TO
CENTER.
4. MODULAR CASEWORK WALL RAIL SHALL BE HUNG NO CLOSER THAN 3" TO THE INSIDE
CORNER OF THE ARCHITECTURAL WALL.
5. ALL SINKS TO BE PROVIDED BY MODULAR CASEWORK MANUFACTURER AS PART OF THE
SINK OPTION UNLESS NOTED OTHERWISE.
6. ALL SINKS LOCATED ADJACENT TO AN ARCHITECTURAL WALL SHALL HAVE A SPECIAL
CORIAN SIDE SPLASH, OPTION IF REQUIRED OR REQUESTED.
7. FAUCETS TO BE PROVIDED BY MEP.
8. ALL SUPPLY LINES MIXING VALVES AND GRID DRAINS / TAIL PIECES MUST BE SUPPLIED AND
INSTALLED BY THE MEP CONTRACTOR
9. THE SINK DRAIN HOLE IS LOCATED 4" OFF CENTER TO THE RIGHT SIDE OF THE SINK
10. REFER TO THE MODULAR CASEWORK DETAILS FOR ALL PLUMBING AND ELECTRICAL
ROUGH-IN LOCATIONS.
11. MODULAR CASEWORK MANUFACTURER DOES NOT SUPPLY THE DRAIN/ TAILPIECE
ASSEMBLY FOR THE SINKS. THIS COMPONENT MUST BE SUPPLIED BY GENERAL
CONTRACTOR. THE REQUIREMENTS FOR THE DRAIN/TAILPIECE ARE:
A. MUST BE SUITABLE FOR A SINK WITHOUT AN OVERFLOW (MUST NOT HAVE
OVERFLOW HOLES IN THE BODY OF THE DRAIN)
B. THREADED PORTION OF THE BODY MUST BE BETWEEN 1.5" AND 4" (FROM TOP OF
DRAIN TO POINT WHERE TAILPIECE TUBE THREADS INTO DRAIN BODY)
12. HEIGHT RECOMMENDATION FOR DRAIN STUB IN WALL: 24 1/4" ABOVE FINISHED FLOOR.
13. ALL UTILITY STUB OUTS AND ROUGHINS FROM THE ARCHITECTURAL WALL TO BE LOCATED
6"-8" ABOVE OR BELOW THE MODULAR CASEWORK UTILITY RAIL CENTERLINE WHERE THE
GANG BOXES ARE MOUNTED.
14. ALL EXPOSED WALL RAILS SHALL HAVE GROMMETS AT CLOSEOUTS, RAIL END CAPS, AND
WALL RAIL INSERTS TO CONSEAL THE EXPOSED ANCHOR LOCATIONS.
15. THE ROTATING WORK SURFACE MUST BE ATTACHED TO THE FULL HEIGHT MODULAR
CASEWORK WALL WITH NO EXCEPTIONS.
16. VERTICAL CHASE COVERS TO BE PAINTED BY OTHERS TO MATCH ARCHITECTURAL WALLS.
INTEGRATED PATIENT CARE MODULAR CASEWORK
2'-9" 2'-9" VIF
3 1/2"
5'-9 1/2"
2'-9" 2'-9" VIF
3 1/2"
5'-9 1/2"
B2 B2
W3 W3
EXISTING
EXISTING BRICK TO REMAIN
EXISTING WINDOW TO REMAIN
NEW EXISTING 5/8" GYPSUM WALLBOARD
NEW 2 1/2" METAL STUD @ 16" O.C.
NEW UNFACED BATT INSULATION
EXISTING CLAY TILE TO REMAIN
NEW SOLID SURFACE TRIM, SS-1
4 3/4"
NEW 1/8" CAULK JOINT
EXISTING LINTEL TO REMAIN
E X
IS
T
IN
G
EXISTING BRICK TO REMAIN
EXISTING SILL TO REMAIN
EXISTING WINDOW TO REMAIN
NEW 5/8" GYPSUM WALLBOARD
NEW 2 1/2" METAL STUD @ 16" O.C.
NEW UNFACED BATT INSULATION
EXISTING CLAY TILE TO REMAIN
NEW SOLID SURFACE TRIM, SS-1
4"
V .I
.F
/4
NEW 1/8" CAULK JOINT
EXISTING
EXISTING BRICK TO REMAIN
EXISTING SILL TO REMAIN
EXISTING WINDOW TO REMAIN
NEW 5/8" GYPSUM WALLBOARD
NEW 2 1/2" METAL STUD @ 16" O.C.
NEW UNFACED BATT INSULATION
EXISTING CLAY TILE TO REMAIN
NEW SOLID SURFACE TRIM, SS-1
EXISTING FLASHING TO REMAIN
/2
NEW 1/8" CAULK JOINT
NEW SOLID SURFACE WINDOW SILL, SS-2
V.I.F.
4 3/4" 1/2"
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
I-201
CASEWORK ELEVATIONS
5 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: 1/4" = 1'-0"
CORRIDOR I-208 - WEST
CASEWORK SCHEDULE
Type Mark WIDTH Description
DETAIL
NO.
B1 1' - 3" 34"H x 23"D FOUR EQUAL DRAWER BASE 2/I-202
B2 2' - 9" 34"H x 23"D BASE STORAGE UNIT, TWO DRAWER, TWO
DOOR, 1 ADJ. SHELF
3/I-202
SB1 2' - 6" 34"H x 23"D SINK BASE, W/REMOVABLE PANEL 1/I-202
W1 2' - 6" 18"H x 15"D TWO DOOR WALL STORAGE UNIT 6/I-202
W2 3' - 3" 24"H x 15"D TWO DOOR WALL STORAGE UNIT 6/I-202
W3 2' - 9" 30"H x 15"D TWO DOOR WALL STORAGE UNIT 6/I-202
INTEGRATED PATIENT MODULAR CASEWORK
Type Mark WIDTH Description Comments
MC1 2' - 6" Mora Sloped Top Ovhd Stg Paper Towel/Glove holder Middle of Run Left Hinge NL Profile Pull HPL 23H 18W 11D
MC2 5' - 0" Mora Corian Work Surf w/ADA Sink Standalone 24W ADA Sink enclosure 4H Backsplash 19D 24W
Scale: 1/4" = 1'-0"
TYPICAL EXAM
Scale: 1/4" = 1'-0"
TYPICAL WINDOW - TYPE C
Scale: 1/4" = 1'-0"
TYPICAL WINDOW - TYPE B
Scale: 1/4" = 1'-0"
TYPICAL WINDOW - TYPE D
Scale: 1/4" = 1'-0"
TYPICAL WINDOW - TYPE A
Scale: 1/4" = 1'-0"
MEDS 2N113 - SOUTH
Scale: 1/4" = 1'-0"
RECEPTION 2N115A - EAST
Scale: 1/4" = 1'-0"
WAITING 2N115 - WEST
Scale: 1/4" = 1'-0"
RECEPTION 2N115A - NORTH
Scale: 3" = 1'-0"
WINDOW - HEAD
Scale: 3" = 1'-0"
WINDOW - JAMB
Scale: 3" = 1'-0"
WINDOW - SILL
3/4" ANGLE BRACE
@ 36" O.C.
ANGLE CLIPS
FINISHED
CEILING LINE
COND. @
SLOPED SOFFIT
EXTENDED SOFFIT FIN.
END PANEL PASSED
CAB. FIN. END 3/8"H MIN.
PLAM SLOPED TOP
1"
1"1"
PLASTIC LAMINATE
CUT END PIECES TO BE
EASED EDGE
CAULK-SEE SCRIBE DETAIL
1" R. ALL EXPOSED CORNERS
EXPOSED EDGE
OPEN END ELEVATION
OPEN END PLAN
/4
/4
1" 2'-0"
R 1"
COUNTERTOP-CAULK
TO SPLASH
3/4" PLYWOOD
ALL TOPS SHALL BE
SCRIBED TO WALL
PRIOR TO
INSTALLATION &
CAULKED
SPLASH END ELEVATION
SPLASH END PLAN
1" 2'-0"1 /2
/4
1/2"
/4
TRIM EDGE OF
SOLID SURFACE AT
THE INTEGRAL
BACK SPLASH
2" DIA. GROMMET
WITH COVER AND
SLEEVE
2"
GROMMET DETAIL
8" DIA. GROMMET
8"
GROMMET DETAIL
R E
F E
R T
O E
L E
V S
BLOCKING REQUIRED
WIRE PULL
ADJUSTABLE SHELF STANDARDS
BACK CONSTRUCTED W/ 1/2"
PLYWOOD. BACKS TO FIT INTO
CABINET SIDE DADOES
3/4" ADJUSTABLE S SHELVES W/ PLASTIC
LAMINATE AT ALL EXPOSED SURFACES
FULL OVERLAY DOOR
CONSTRUCTED W/ 3/4" PLYWOOD
NOTE:
ALL EXPOSED PLYWOOD
FACES & EDGES TO RECEIVE
HIGH PRESSURE LAMINATE.
1' - 3"
SLOPED TOP OR GYP. BD.
SOFFIT. REFER TO CEILING
PLANS & ELEVATIONS
EASED EDGES
1' - 11"
SCHEDULED
BASE
BASE AS SCHEDULE
NOTE: SEE MILLWORK
GENERAL NOTES FOR
CABINET CONSTRUCTION
REQUIRED BLOCKING
INTERIOR FINISH-
MELAMINE U.N.O.
3"
BOTTOM CONSTRUCTED W/ 3/4" PLYWOOD
DOWELED INTO CABINET SIDES.
BASE, SEE FINISH PLANS
SEALANT, COLOR TO MATCH ADJACENT
WALL
2x BLOCKING
1x BLOCKING, TOP & BOTTOM
COUNTERTOP CONSTRUCTED OF 1/2" SOLID
SURFACE WITH INTEGRAL BACKSPLASH.
PROVIDE BUILD-UP EDGE TO 1-1/2" WITH 1/8"
RADIUS TOP AND BOTTOM, FULLY WRAPPED.
FULL OVERLAY DOOR CONSTRUCTED
W/ 3/4" PLYWOOD
FALSE FRONT CONSTRUCTED W/ 3/4"
PLYWOOD
BACK CONSTRUCTED W/ 1/2" PLYWOOD.
BACKS TO FIT INTO CABINET SIDE DADOES
NOTE:
ALL EXPOSED PLYWOOD
FACES & EDGES TO RECEIVE
HIGH PRESSURE LAMINATE.
TOE KICK CONSTRUCTED OF 3/4" PLYWOOD
TOE BOARD
REMOVABLE PANEL, ATTACH TO CLEATS
WITH NICKEL PLATED SCREWS AND FINISH
WASHERS. MATCH REVEAL AND EDGE
TREATMENT OF DOORS AND DRAWERS.
1' - 11"
2' - 0"
COUNTERTOP CONSTRUCTED OF 1/2" SOLID
SURFACE WITH INTEGRAL BACKSPLASH.
PROVIDE BUILD-UP EDGE TO 1-1/2" WITH 1/8"
RADIUS TOP AND BOTTOM, FULLY WRAPPED.
(4) DRAWER UNITS CONSTRUCTED WITH 1/2"
PLYWOOD SIDES. 3/4" FRONTS & BACKS &
1/2" FULLY CAPTURED BOTTOM. DRAWER
FACES CONSTRUCTED OF 3/4" PLYWOOD.
BACK CONSTRUCTED W/ 1/2" PLYWOOD. BACKS
TO FIT INTO CABINET SIDE DADOES
BASE, SEE FINISH PLANS
BOTTOM CONSTRUCTED W/ 3/4"
PLYWOOD DOWELED INTO CABINET SIDES
/4
E
Q
/4
E
Q
/4
E
Q
/4
E
Q
SEALANT, COLOR TO MATCH ADJACENT WALL
2x BLOCKING
1x BLOCKING, TOP & BOTTOM
NOTE:
ALL EXPOSED PLYWOOD
FACES & EDGES TO RECEIVE
HIGH PRESSURE LAMINATE.
TOE KICK CONSTRUCTED OF
3/4" PLYWOOD TOE BOARD
(4) WIRE PULL
1' - 11"
2' - 0"
3MM MATCHING PVC EDGE
WRAP CONT.-ALL SIDES
EUROPEAN CONCEALED HINGE
COUNTERTOP CONSTRUCTED OF 1/2" SOLID
SURFACE WITH INTEGRAL BACKSPLASH.
PROVIDE BUILD-UP EDGE TO 1-1/2" WITH 1/8"
RADIUS TOP AND BOTTOM, FULLY WRAPPED.
DRAWER UNIT CONSTRUCTED WITH 1/2"
PLYWOOD SIDES. 3/4" FRONTS & BACKS &
1/2" FULLY CAPTURED BOTTOM. DRAWER
FACES CONSTRUCTED OF 3/4" PLYWOOD.
FULL OVERLAY DOOR CONSTRUCTED W/ 3/4" PLYWOOD
ADJUSTABLE SHELF CONSTRUCTED WITH 3/4"
FIRE RETARDANT TREATED PLYWOOD. EDGES
TO RECEIVE MATCHING .018 PVC BANDING
METAL ADJUSTABLE SHELF STANDARDS
BACK CONSTRUCTED W/ 1/2" PLYWOOD.
BACKS TO FIT INTO CABINET SIDE DADOES
BASE, SEE FINISH PLANS
BOTTOM CONSTRUCTED W/ 3/4" PLYWOOD
DOWELED INTO CABINET SIDES
SEALANT, COLOR TO MATCH
ADJACENT WALL
2x BLOCKING
1x BLOCKING, TOP & BOTTOM
NOTE:
ALL EXPOSED PLYWOOD FACES
& EDGES TO RECEIVE HIGH
PRESSURE LAMINATE.
TOE KICK CONSTRUCTED OF 3/4" PLYWOOD TOE BOARD
WIRE PULL
1'-11"
2'-0"
1'-3"
3/4" X 2"
LIGHT VALANCE @ ALL
WALL CABINETS U.N.O.
R E
F E
R T
O E
L E
V S
BLOCKING REQUIRED
WIRE PULL
ADJUSTABLE SHELF STANDARDS
BACK CONSTRUCTED W/ 1/2"
PLYWOOD. BACKS TO FIT INTO
CABINET SIDE DADOES
(2) 3/4" ADJUSTABLE S SHELVES W/
PLASTIC LAMINATE AT ALL EXPOSED
SURFACES
FULL OVERLAY DOOR
CONSTRUCTED W/ 3/4" PLYWOOD
NOTE:
ALL EXPOSED PLYWOOD
FACES & EDGES TO RECEIVE
HIGH PRESSURE LAMINATE.
SLOPED TOP OR GYP. BD.
SOFFIT. REFER TO CEILING
PLANS & ELEVATIONS
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
I-202
CASEWORK DETAILS
6 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: No Scale
PLAM SLOPED TOP
Scale: 3/4" = 1'-0"
COUNTERTOP OPEN END VIEWS
Scale: 3/4" = 1'-0"
SCRIBE DETAIL
Scale: 3/4" = 1'-0"
GROMMET DETAIL
Scale: 3/4" = 1'-0"
TYPICAL 15-24"H WALL CABINET
Scale: 3/4" = 1'-0"
SOLID SURFACE COUNTERTOP
Scale: 3/4" = 1'-0"
END PANEL
Scale: 3" = 1'-0"
CASEWORK DETAIL - TYPICAL TOE KICK
Scale: 3/4" = 1'-0"
CASEWORK BASE - SINK
Scale: 3/4" = 1'-0"
CASEWORK BASE - 4 EQUAL DRAWERS
Scale: 3/4" = 1'-0"
CABINET DRAWER PLAN
Scale: 3/4" = 1'-0"
BASE CABINET W/ ONE DRAWER & DOOR
Scale: 3/4" = 1'-0"
TYPICAL 30"H WALL CABINET
HIW-3
CG-1
CG-1
CG-1
CORRIDOR I-208
BEYOND
WAITING 2N115
BEYOND
CG-1
HIW-2 BELOW CHAIR RAIL, TYP.
HIW-2 BELOW CHAIR RAIL, TYP.
CHR-1
CORRIDOR I-208
BEYOND
CG-1CG-1
I-101
Sim
CORRIDOR I-208
BEYONDHIW-3 CG-1
HIW-2 BELOW
CHAIR RAIL, TYP.
CHR-1 CHR-12
CG-1CG-1
I-101
Sim
CHR-1
HIW-2
I-101
Sim
* PERIMETER OF ROOM
I-101
Sim
WAITING 2N115
BEYOND CG-1CG-1
E.J.
HR-1 HR-1 HR-1 HR-1 HR-1 HR-1HR-1
I-101
Sim
CR-1CR-1CR-1CR-1CR-1CR-1
2S12B
CR-1 CR-1
CG-1
CG-1 CG-1
CG-1
HR-1
CR-1
FECFEC
E.J.
HR-1HR-1 HR-1 HR-1 HR-1 HR-1
I-101
Sim
CR-1CR-1CR-1CR-1CR-1CR-1
I-101
Sim
HR-1 HR-1
CR-1CR-1
CG-1 CG-1
FEC
I-101
Sim
I-101
Sim
HIW-1
CR-1 CR-1
HR-1HR-1
CR-1
I-101
Sim
HIW-1
CR-1
CG-1
CR-1
CG-1CG-1HR-1
I-101
Sim
CR-1
CG-1 CG-1HR-1
I-101
Sim
CR-1
I-101
Sim
CR-1
HIW-1
I-101
Sim
HR-1 HR-1
CR-1CR-1
I-101
Sim
HR-1 HR-1
CR-1CR-1
I-101
Sim
CR-1
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:3
P
M
I-401
INTERIOR ELEVATIONS - WALL
PROTECTION
7 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: 1/4" = 1'-0"
WAITING ELEVATOR 2N115- NORTHWEST
Scale: 1/4" = 1'-0"
WAITING 2N115- SOUTHEAST
Scale: 1/4" = 1'-0"
WAITING 2N115- NORTHEAST
Scale: 1/4" = 1'-0"
WAITING 2N115- SOUTHWEST
Scale: 1/4" = 1'-0"
WAITING 2N115- NORTHWEST
Scale: 1/4" = 1'-0"
LOGISTICS STORAGE 2N119
Scale: 1/4" = 1'-0"
CORRIDOR I-208 - SOUTHWEST
Scale: 1/4" = 1'-0"
CORRIDOR I-208-NORHTEAST
Scale: 1/4" = 1'-0"
CORRIDOR 2N118- SOUTHWEST
Scale: 1/4" = 1'-0"
CORRIDOR 2N118- NORHTEAST
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - SOUTHEAST A
Scale: 1/4" = 1'-0"
ELEVATOR LOBBY 2S57
Scale: 1/4" = 1'-0"
CORRIDOR H204 SOUTHEAST
Scale: 1/4" = 1'-0"
CORRIDOR H204 - NORTHEAST
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - NORTHWEST C
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - NORTHWEST A
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - SOUTHEAST B
HIW-3P-1
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - NORTHWEST B
M0400
F3200
A6046
F2225
M0512
M0507
U0025
M0506
F3200
E0063 M1825
A5145
F3065 A5075
A5080
A5077
U0025
A1014
F3200
A5077
A1205M
M4100M4200
A1132
M0765
M0755
A5180
A5145
A5180
A1205
A5075
A5080
A5108
F3200
A1014
A5180
U0025
A5077
M4200
M4100
A1205
A1132
A5145
A5180
A1205
A5075 A5080 A5108
U0025
F3200
A5077
A1014
A5180
M4100
M4200
M0755
A5180
A1205
M0765
A1132
M4100 M4200
M0755
A5180
M0765
U0025
F3200
A1014A5077 2
A5145A5108 A5080 A5075
M0755
M4200
M4100
A1132
M0765
2 5
A5077
A1014
F3200
U0025
A5080
A5075
A5145
A5180
A1205
A5108
F3050
F3200
A5077
A5107M
A5077
A5145A5145 F3200
F3025
F2300 M1890M0506F3200
A5077
A5107 A5082
A5075
A6046
A5077
A5080 A5108A5075
A5180
M0755
M0765
A1205
U0002
F3200
U0026
T0015M
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:5
P
M
I-402
INTERIOR ELEVATIONS - EQUIPMENT
8 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: 1/4" = 1'-0"
CONFERENCE 2S56 - SOUTHEAST
Scale: 1/4" = 1'-0"
CONFERENCE 2S56 - SOUTHWEST
Scale: 1/4" = 1'-0"
CONFERENCE 2S56 - NORTHWEST
Scale: 1/4" = 1'-0"
CONSULT 2S56A - SOUTHEAST
Scale: 1/4" = 1'-0"
CONSULT 2S56A - NORTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2N118 -
SOUTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2N118 -
SOUTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S01 -
SOUTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S01 -
NORTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S01 -
NORTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S02 -
SOUTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S02 -
NORTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S02 -
NORTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S03 -
SOUTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S03 -
NORTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S03 -
NORTHWEST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S04 -
SOUTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S04 -
NORTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S04 -
NORTHWEST
Scale: 1/4" = 1'-0"
GROUP ROOM 2N58 -
SOUTHWEST
Scale: 1/4" = 1'-0"
SOILED UTILITY 2S10 - SOUTHEAST
Scale: 1/4" = 1'-0"
TYPICAL OFFICE
Scale: 1/4" = 1'-0"
WAITING - SOUTHWEST
Scale: 1/4" = 1'-0"
MEDS 2N113 - NORTHEAST
Scale: 1/4" = 1'-0"
MEDS 2N113 - SOUTHWEST
Scale: 1/4" = 1'-0"
WAITING - SOUTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2N118 -
NORTHEAST
Scale: 1/4" = 1'-0"
EXAM/TREATMENT 2S01 -
SOUTHWEST
Scale: 1/4" = 1'-0"
OPEN OFFICE 2N60
1 HEIGHT AT 5'-0" OC AFF
2 HEIGHT AT 4'-0" OC AFF
3 HEIGHT AT 3'-6" OC AFF
4 ELECTRICAL/DATA FLOOR DEVICES
Scale: 1/4" = 1'-0"
CORRIDOR 2N116 - WEST
S
S S
S S
S
SS
S S
S S
S
S
S
S
S SS
K L L.1 L.2
M
M.3 N.1 N.3 N.5
P
P.1
P.2 P.4
Q Q.1 R S
4.4
6.5
7.3
9.9
M.1
M.4
OPEN
OFFICE
2N60
GROUP
ROOM
2S58
ELEVATOR
LOBBY
H209
CONSULT
2S56
CONFERENCE
2S54
EXAM 5
2S01
EXAM 4
2S02
EXAM 3
2S03
EXAM 2
2S04
2N120
SOILED LINEN
RESTROOM
2N118A
SCALE
2N116A
LOGISTICS
STORAGE
2N117
EXAM 6
2N118
TELEHEALTH
2N112
RESTROOM
2N114
EQUIP
STORAGE
2N111
SOILED
UTILITY
2S10
OFFICE
(PSYCH)
2S11
OFFICE
(SW)
2S11A
OI&T_
2S53
CORRIDOR
H204
CORRIDOR
2N116
WAITING
2N115
CORRIDOR
H208
I-422
I-421
CHASE_
H208B
ELECT.
CLOSET
H208A
I-423
S S
S
S S
CLOSET
2N60A
EXAM 1
2S05
MEDS
2N113
STORAGE
2N119
2N115A
RECEPTION
I-423
I-423
I-431
I-431
I-423
FAC
DATA RM
2S57A
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE BARRIER WITH 1
HOUR FIRE RESISTANCE
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:5
P
M
I-411
OVERALL SECOND FLOOR EQUIPMENT
FLOOR PLAN
9 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
SECOND FLOOR OVERALL FFE PLAN
N O
R T
H0 4 8 16
WALL RATED LINES
S
S S
SS
S S
S
S
S
S
S SS
GROUP
ROOM
2S58
CONSULT
2S56
ELEVATOR
LOBBY
H209
CORRIDOR
H204
OI&T_
2S53
CONFERENCE
2S54
CORRIDOR
H208
CHASE_
H208B
U0023M
F0275
M1801M
A1015
U0023M
F0275
M1801M
A1015
U0023
F0275
M1801M
A1015
U0023
F0275
M1801M
A1015
U0023M
F0275
M1801M
A1015
F2000
F2000
F2000
F2000 F2000
U0023M
F0275
M1801M
A1015
U0023
F0275
M1801M
A1015
U0023
F0275
M1801M
A1015
U0023M
F0275
M1801M
A1015
F2000
F2000
F2000 F2000
F0765
F0765
F0765
F0220M F0220MF0220M
F0220MF0220M F0220M F0220M
F0220M
F0220M
F0220M
A1020
F0220M
F0220M
A6046 F2000
M0507
A5220
F3200
I-402 13
I-402
F3050
F2000 F3200
A5077
S S
S
S
ELEVATOR
E3
ELEVATOR
E2
CLOSET
2N60A
2N60
OPEN OFFICE
I-423
M0400
U0025
U0002F3200
I-402
FAC
DATA RM
2S57A
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE BARRIER WITH 1
HOUR FIRE RESISTANCE
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:0
P
M
I-421
ENLARGED EQUIPMENT PLAN - AREA A
10 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
ENLARGED EQUIPMENT PLAN - AREA A
N O
R T
H0 2 4 8
WALL RATED LINES
S
S
SS
S S
S
S SS
F0275
A1015 M1801
F2000
M0506
F0305
F0305
F0305
F0305
F2300
F2000
F0206
M4045
A6046
F0275
E0948
EQUIP
STORAGE
2N111
RESTROOM
2N114
TELEHEALTH
2N112
EXAM 6
2N118
RESTROOM
2N118A
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02
EXAM 5
2S01
LOGISTICS
STORAGE
2N117
SCALE
2N116A
SOILED
LINEN
2N120
SOILED
UTILITY
2S10
OFFICE
(PSYCH)
2S11
OFFICE
(SW)
2S11A
CORRIDOR
2N116
WAITING
2N115
ELECT.
CLOSET
H208A
F0740
M1890
F3200
F3025
A5145A5145 F2020
M3070
A5077
A5107M
F0205F0205
M1801
E0078
F0275
A1015
F2000
F0110 F0110
F0205 F0205
M1801
F0275
E0078
A1015
F2000
F3200
F3025
A5145A5145
F0515
A5145
I-402 28
I-40228
SIM
I-402 25
A5145
A5145
E0078
F0205F0205
F0275
M1801
A1015
F3050
I-402
S
S S
ELEVATOR
E4
STAIR 2
S2
A5077
F3200
A5108A5075
A5180
F2010
M3073
M8810
A1205
M0755
M4200
M4100
A1014
F3200
A5077 2S05
EXAM 1
2N119
STORAGE
MEDS
2N113
RECEPTION
2N115A
M0765
A1132
I-423
M4655
U0001
U0003
M1810
U0026
I-402 30
T0015M
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE BARRIER WITH 1
HOUR FIRE RESISTANCE
SCOPE OF WORK LEGEND
AREA NOT IN SCOPE
SCOPE OF CONSTRUCTION
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:0
P
M
I-422
ENLARGED EQUIPMENT PLAN - AREA B
11 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
ENLARGED EQUIPMENT PLAN - AREA B
N O
R T
H0 2 4 8
WALL RATED LINES
I-401 5
I-402
M4655
F3200F0275
M4100
M4200
F2010
M3073
M8810 E0948
A5077
M4655
F3200
F0275
M4100
M4200
F2010
M3073
M8810
E0948
A5077
M4655
F3200
F0275
M4100
M4200
F2010
M3073
M8810
E0948
A5077
M4655
F3200
F0275
M4100
M4200
A5075
A5080
F2010
M3073
M8810
E0948
A5077
M0755
M0755
M0755
A5145 A5145 A5145 A5145
A1014
U0025
A1014
U0025
A1014
U0025
A1014
M0755
I-402
1315 I-40218
16 I-40221
EXAM 3
2S03
EXAM 2
2S04
EXAM 4
2S02EXAM 5
2S01
A5180
A5180 A5180
A5180
A5075
A5080
A5108
A5075
A5080
A5108
A1132
M0765
A1132
M0765
M0765
M0765
A1132
A1205 A1205
A1205
U0025
A1205
A1132 A5108
I-402
A5108M F2010
A5077
A5107A5082A5075
M3150
MEDS
2N113
R6200
/4
9'-9"
Maa3
A
2N113
Ma3
Maa3
A
Mma3
Ma0
I-4025 4
2S56
CONSULT
A5145
F3065 F0305 F0206
F3200
M0506
E0063 M1801
A1015
F0300
A5077
F0420
F2000
A5080
A5075
M1825
I-4028
EXAM 6
2N118
EXAM 6
2N118
F0275 U0025
A1014
A5145F3200
M4655
A1205M
E0948
M3073
M8810
M0765
M0755
M4100
F2010
A1132
A5077
A5180
A5075
A5080
A5108
M4200
M4800
M4800
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:1
P
M
I-423
ENLARGED EQUIPMENT PLANS
12 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: 1/2" = 1'-0"
ENLARGED EXAM/TREATMENT 2S01, 2S02, 2S03, & 2S04
Scale: No Scale
EXAM AXON
N O
R T
H0 2 4 8
Scale: 1/2" = 1'-0"
MEDS 2N113
Scale: 1/2" = 1'-0"
CONSULT 2S56
Scale: 1/2" = 1'-0"
ENLARGED EXAM ROOM 2N118
N O
R T
H0 2 4 8
N O
R T
H0 2 4 8
N O
R T
H0 2 4 8
I-431 1C
1D
1A
A5200
F2010A5082
A5075
A5145
A5109
1B
RESTROOM
2N118A
N
A
3'-4 3/4" 4'-0 3/4" 1'-5 1/4"
Ma3
Ma3Mma3
Mm3
Mm3Mma3
A5090
A1067
A5082
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A5109
A1067
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A5145
A5200
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A5109
A5090
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A5075
2N114
RESTROOM
I-4312A
2B
2C
2D
A5145
A5090
Mma3
Mm2Mm2
Mm3
Mm2
Mm2
2N114
A5200
A4995
A5075
F2010
A5082
A1067
9'-2 1/2"
A5109
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A4995
A5200A5090
A5109
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A1067
A5082 A5075
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
A5145
CT-1
PROVIDE METAL TRIM
BETWEEN RESINOUS
BASE AND TILE
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
I-431
ENLARGED RESTROOMS AND
ELEVATIONS
13 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
Scale: 1/2" = 1'-0"
ENLARGED RESTROOM
PLAN - 2N118A
Scale: 1/2" = 1'-0"
1C
SOUTHEAST ELEVATION - 2N118A
Scale: 1/2" = 1'-0" 1A
NORTHWEST ELEVATION - SN118A
Scale: 1/2" = 1'-0"
1D
NORTHEAST ELEVATION - 2N118A
N O
R T
H0 1 2 4
Scale: 1/2" = 1'-0" 1B
SOUTHWEST ELEVATION - 2N118A
Scale: 1/2" = 1'-0"
ENLARGED RESTROOM
PLAN - 2N114
N O
R T
H0 1 2 4
Scale: 1/2" = 1'-0" 2A
NORTHWEST ELEVATION - 2N114
Scale: 1/2" = 1'-0"
2B
SOUTHWEST ELEVATION - 2N114
Scale: 1/2" = 1'-0" 2C
SOUTHEAST ELEVATION - 2N114
Scale: 1/2" = 1'-0"
2D
NORTHEAST ELEVATION - 2N114
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/1
/2
:3
:2
P
M
I-601
EQUIPMENT SCHEDULE
14 15JK
RENOVATE SECOND FLOOR
CENTER, JB BLDG 52
1 JEFFERSON BARRACKS DR,
ST. LOUIS, MO 63125
AUGUST 25, 2021
BID DOCUMENTS
657-20-102JB20-028
ELI
EQUIPMENT AND FURNITURE SCHEDULE A
JSN
Number
Qu anti ty Description
BLOCKING
REQUIRED DATA POWER PLUMBING
Furnish / Installation Comments
M4655 1 Mobile stretcher No No No No VV
M8810 1 Stand, Mayo No No No No VV
U0015 1 WORKSTATION, COMPUTER, ADJUSTABLE Yes Yes Yes No VV
2S04
EXAM 2
A1014 1 Telephone, Wall Mounted, 1 Line, With Speaker No Yes Yes No VV
A1132 1 Rail, Accessory Mounting No No No No VV
A1205 1 Lift System, Overhead, Patient Room Yes No Yes No VC Existing lift system to be removed, reinstalled, and tested by factory trained and certified installer as part of the GC's contract
A5075 1 Dispenser, Soap, Disposable No No No No VV
A5077 1 Dispenser, Hand Sanitizer, Hands-Free Yes No No No VV
A5080 1 Dispenser, Paper Towel, SS, Surface Mounted No No No No CC
A5108 1 Disposal, Sharps No No No No VV
A5145 1 Hook, Garment, Double, SS, Surface Mounted Yes No No No CC
A5180 1 Curtain Track, Straight No No No No CC Lift System to be installed complete prior to installation of Curtain Track
E0948 1 Cart, General Storage, Mobile No No No No VV
F0275 1 Chair, Swivel, High Back No No No No VV
F2010 1 Basket, Wastepaper, Step-On No No No No VV
F3200 1 Clock, Battery, 12" Diameter No No No No VV
M0755 1 Flowmeter, Oxygen, Low Flow No No No Yes VV
M0765 1 Regulator, Vacuum No No No Yes VV
M3073 1 Container, Biohazard Waste, Step-on, Fire Safe No No No No VV
M4100 1 Sphygmomanometer, Aneroid, Wall Mounted Yes No No No VV
M4200 1 Octoscope/Ophthalmoscope, Wall Mounted Yes No Yes No VV
M4655 1 Mobile stretcher No No No No VV
M8810 1 Stand, Mayo No No No No VV
U0015 1 WORKSTATION, COMPUTER, ADJUSTABLE Yes Yes Yes No VV
2S05
EXAM 1
A1014 1 Telephone, Wall Mounted, 1 Line, With Speaker No Yes Yes No VV
A1132 1 Rail, Accessory Mounting No No No No VV
A1205 1 Lift System, Overhead, Patient Room Yes No Yes No VC Existing lift system to be removed, reinstalled, and tested by factory trained and certified installer as part of the GC's contract
A5075 1 Dispenser, Soap, Disposable No No No No VV
A5077 1 Dispenser, Hand Sanitizer, Hands-Free Yes No No No VV
A5080 1 Dispenser, Paper Towel, SS, Surface Mounted No No No No CC
A5108 1…