9-BPS 97 E001 - ELECTRICAL SYMBOL LEGENDS AND GENERAL NOTES.pdf
PDF 873 KB Posted
- Attached to
- FIRE PUMP REPLACEMENT AT BPS 97
- Solicitation number
- 27-0627-025
- Issued by
- Erie County, New York
About this file
This electrical symbol legends and general notes document is part of the fire pump replacement project for Buffalo Public Schools (BPS), specifically for two facilities: BPS 97 (Harvey Austin Elementary School) located at 1405 Sycamore Street, Buffalo, NY, and BPS 99 (Stanley M Makowski Early Childhood Center) located at 1095 Jefferson Avenue, Buffalo, NY. The document, prepared by Buffalo Engineering, P.C., establishes standardized electrical symbols, abbreviations, and mounting height specifications for all electrical work associated with the fire pump replacement project. The electrical work encompasses installation of equipment connections at various voltages (120V, 208V, 277V, and 480V), branch circuit wiring, panelboards, lighting fixtures, fire alarm systems, disconnect switches, motor connections, and associated devices. General notes require that the electrical contractor conduct site visits before bidding, verify all electrical requirements of equipment, follow National Electric Code standards and local codes, install conduits at right angles and parallel to walls, conceal new circuiting except in utility rooms, coordinate fixture locations with other trades to avoid conflicts, and provide shop drawings and product data for all equipment.
The electrical contractor must guarantee the entire system for one year from acceptance and is responsible for all labor, materials, and testing required to complete the work in satisfactory operation. All materials and installations must comply with the latest edition of the National Electric Code and local ordinances. The contractor must remove and properly dispose of fluorescent lamps, mercury lamps, and PCB-containing materials in accordance with federal, state, and local regulations, providing documentation of proper disposal to the owner. The document specifies that equipment manufacturer names and model numbers are provided as basis of design standards, but manufacturers of equivalent equipment may be substituted upon engineer approval. Circuit numbers shown on drawings are for clarification purposes only, and actual panelboard assignments must be determined by the electrical contractor. The document emphasizes field coordination among all trades, with exact locations of devices, fixtures, and equipment to be verified to avoid interference with cabinetry, mechanical equipment, plumbing systems, and other building elements.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawn By:
Checked By:
Date:
Scale:
DWG. No.
RevisionsNo.
STAMP
Date
BU
FF
A
LO
E N
G
IN
EE
RI
N G
, P .C
Th es e do cu m en ts a nd th ei r c on te nt s ar e th e pr op er ty o f B uf fa lo E ng in ee ri ng , P
C a nd a re is su ed o nl y fo r t he s pe ci fic p ro je ct n ot ed o n th es e dr aw in gs
. A ny re pr od uc tio ns
, r ev is io ns , o r m od ifi ca tio ns o f t he se d oc um en ts w ith ou t t he e xp re ss w ri tte n co ns en t o f B uf fa lo
E ng in ee ri ng
, P C is p ro hi bi te d by la w
AS NOTED
8/29/2025
BUFFALO PUBLIC SCHOOLS
FIRE PUMP REPLACEMENT
CONSULTANTS
2025 BUFFALO ENGINEERING, PC
UNAUTHORIZED REPRODUCTION, ALTERATION OR ADDITION TO ANY
DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IN WHOLE OR IN
PART WITHOUT THE EXPRESS WRITTEN AUTHORIZATION IS PROHIBITED
BY SECTION 7209, PROVISION 2 OF THE NEW YORK STATE EDUCATION
LAW UNLESS OTHERWISE ACTING UNDER THE DIRECTION OF A LICENSED
ARCHITECT OR ENGINEER FOR WHICH THE SEAL OF A LICENSED
ARCHITECT OR ENGINEER IS APPLIED.
COPYRIGHT
SHEET TITLE
LICENSE EXPIRATION DATE: 8/31/2026
FIRM AUTHORIZATION NUMBER: 020076
BUFFALO PS 99 -
STANLEY M MAKOWSKI EARLY
CHILDHOOD CENTER
1095 JEFFERSON AVE,
BUFFALO, NY 14208
SED #: 140600010050012
BUFFALO PS 97 -
HARVEY AUSTIN ELEMENTARY
SCHOOL
1405 SYCAMORE ST,
BUFFALO, NY 14211
SED #: 140600010302031
E001
ELECTRICAL SYMBOL
LEGENDS AND
GENERAL NOTES
JRG
ELECTRICAL SYMBOL LIST
ABBREVIATIONS
GENERAL DRAWING NOTES:
(APPLY TO ALL DRAWINGS)
MOUNTING HEIGHTS:
LINE LEGEND
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text
INDICATES AMPERAGE RATING, RIGHT NUMERAL INDICATES NO. OF POLES).
AutoCAD SHX Text
LETTER `F' INDICATES FUSED. 'AUX' INDICATES AUXILIARY CONTACTS
AutoCAD SHX Text J
AutoCAD SHX Text
DISCONNECT SWITCH (LEFT NUMERAL OR GROUP OF NUMERALS
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
MOTOR CONNECTION
AutoCAD SHX Text
208 VOLT EQUIPMENT CONNECTION
AutoCAD SHX Text
120 VOLT EQUIPMENT CONNECTION
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
WP
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
EC
AutoCAD SHX Text
FUSED
AutoCAD SHX Text F
AutoCAD SHX Text
GROUND FAULT INTERRUPTING
AutoCAD SHX Text
GFI
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FACP
AutoCAD SHX Text
HEATING, AIR CONDITIONING & REFRIGERATION
AutoCAD SHX Text
HACR
AutoCAD SHX Text
RATED CIRCUIT BREAKER
AutoCAD SHX Text
UNDERCOUNTER
AutoCAD SHX Text
UC
AutoCAD SHX Text
OVERCOUNTER
AutoCAD SHX Text
OC
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
EWC
AutoCAD SHX Text
ETR
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
SURFACE MOUNTED
AutoCAD SHX Text S
AutoCAD SHX Text A. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERALLY THE LOCATIONS OF THE THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERALLY THE LOCATIONS OF THE MATERIAL AND EQUIPMENT. THESE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE. B. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR PROPER MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR PROPER INSTALLATION AND OPERATION, SHALL BE INCLUDED IN BIDS THE SAME AS IF HEREIN SPECIFIED OR SHOWN. C. WITH SUBMISSION OF BID, IT IS MUTUALLY AGREED THE CONTRACTOR HAS INCLUDED THE WITH SUBMISSION OF BID, IT IS MUTUALLY AGREED THE CONTRACTOR HAS INCLUDED THE COST OF ALL REQUIRED ITEMS IN HIS PROPOSAL, AND THAT HE WILL BE RESPONSIBLE FOR THE APPROVED SATISFACTORY FUNCTIONING OF THE ENTIRE SYSTEM WITHOUT EXTRA COMPENSATION. D. BEFORE SUBMITTING BID, VISIT THE SITE AND EXAMINE THE CONDITIONS ON WHICH HIS BEFORE SUBMITTING BID, VISIT THE SITE AND EXAMINE THE CONDITIONS ON WHICH HIS WORK IS IN ANY WAY DEPENDANT FOR THE BEST WORKMANSHIP AND OPERATION ACCORDING TO THE INTENT OF SPECIFICATION AND DRAWINGS. E. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT SITE, OR NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT SITE, OR FOR ANY ALLEGED MISUNDERSTANDING OF MATERIALS TO BE FURNISHED OR WORK TO BE DONE. F. VERIFY THE ELECTRICAL REQUIREMENTS OF ALL ACTUAL EQUIPMENT INVOLVED PRIOR TO VERIFY THE ELECTRICAL REQUIREMENTS OF ALL ACTUAL EQUIPMENT INVOLVED PRIOR TO THE INSTALLATION OF ELECTRICAL SERVICE TO THE SAME. G. ANY WORK INSTALLED CONTRARY TO, OR WITHOUT CONCURRENCE OF THE OWNER'S ANY WORK INSTALLED CONTRARY TO, OR WITHOUT CONCURRENCE OF THE OWNER'S REPRESENTATIVE, SHALL BE SUBJECT TO CHANGE AS DIRECTED BY THE OWNER'S REPRESENTATIVE, AND NO EXTRA COMPENSATION WILL BE ALLOWED FOR MAKING THE CHANGES. H. TEST ALL NEW SYSTEMS AND REPAIR OR REPLACE ALL DEFECTIVE WORK. MAKE ALL TEST ALL NEW SYSTEMS AND REPAIR OR REPLACE ALL DEFECTIVE WORK. MAKE ALL NECESSARY ADJUSTMENTS TO THE SYSTEM AND SHALL INSTRUCT THE OWNER'S PERSONNEL IN THE PROPER OPERATIONS OF THE SYSTEMS. I. ALL MATERIAL AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION ALL MATERIAL AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE, LOCAL CODES, AND ORDINANCES. J. ALL CONDUITS OR EXPOSED WORK SHALL BE RUN AT RIGHT ANGLES TO, AND PARALLEL ALL CONDUITS OR EXPOSED WORK SHALL BE RUN AT RIGHT ANGLES TO, AND PARALLEL WITH, THE SURROUNDING WALL AND SHALL CONFORM TO THE FORM OF THE CEILING. NO DIAGONAL RUNS WILL BE ALLOWED. BENDS IN PARALLEL CONDUIT RUNS SHALL BE CONCENTRIC. ALL CONDUIT SHALL RUN PERFECTLY STRAIGHT AND TRUE. PAINT RACEWAY, FITTINGS AND SUPPORT TO MATCH EXISTING SURFACES. K. EQUIPMENT MANUFACTURER NAMES AND MODEL NUMBERS ARE LISTED AS THE BASIS OF EQUIPMENT MANUFACTURER NAMES AND MODEL NUMBERS ARE LISTED AS THE BASIS OF DESIGN AND AS A STANDARD FOR CONSTRUCTION AND FEATURES. MANUFACTURERS OF EQUIVALENT EQUIPMENT MAY BE SUBSTITUTED UPON APPROVAL BY THE ENGINEER. L. SUBMIT SHOP DRAWINGS, CATALOG CUT SHEETS, AND PRODUCT DATA FOR ALL SUBMIT SHOP DRAWINGS, CATALOG CUT SHEETS, AND PRODUCT DATA FOR ALL ELECTRICAL EQUIPMENT AND COMPONENTS TO BE INSTALLED. M. ALL RECEPTACLES, SWITCHES, ETC. IN RATED WALLS AND CEILINGS MUST BE INSTALLED A ALL RECEPTACLES, SWITCHES, ETC. IN RATED WALLS AND CEILINGS MUST BE INSTALLED A MINIMUM OF 24" FROM EACH OTHER OR PROPERLY FIRESTOPPED TO MAINTAIN RATINGS IF WITHIN THE SAME WALL OR CEILING CAVITY. PROVIDE ALL LABOR AND MATERIALS REQUIRED TO MATCH RATING OF WALL AND CEILING CONSTRUCTION. FIRE CAULK ANY PENETRATIONS OF RATED WALLS OR CEILINGS. N. GUARANTEE THE ENTIRE ELECTRICAL SYSTEM FOR A PERIOD OF ONE YEAR FROM THE GUARANTEE THE ENTIRE ELECTRICAL SYSTEM FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE AS COMPLETE BY THE OWNER. O. PROVIDE ALL LABOR, EQUIPMENT AND MATERIALS REQUIRED FOR ELECTRICAL SYSTEMS PROVIDE ALL LABOR, EQUIPMENT AND MATERIALS REQUIRED FOR ELECTRICAL SYSTEMS INDICATED ON THESE DRAWINGS. THE WORK SHALL BE TESTED AND LEFT COMPLETE AND IN SATISFACTORY OPERATION SUBJECT TO THE APPROVAL OF THE AUTHORITIES AND THE OWNER'S REPRESENTATIVE. P. ALL CONDUITS SHALL BE INSTALLED AS HIGH AS POSSIBLE ABOVE FINISHED CEILINGS AND ALL CONDUITS SHALL BE INSTALLED AS HIGH AS POSSIBLE ABOVE FINISHED CEILINGS AND CONCEALED IN WALLS UNLESS OTHERWISE INDICATED. ALL CONDUITS SHALL RUN PARALLEL AND PERPENDICULAR WITH BUILDING WALLS AND STRUCTURE. CONDUITS CONCEALED IN WALLS SHALL BE INSTALLED VERTICALLY, HORIZONTAL RUNS OF CONDUIT SHALL NOT BE PERMITTED. Q. BE CAUTIONED THAT ELECTRIC POWER CHARACTERISTIC (VOLTAGE, PHASE, HORSEPOWER, BE CAUTIONED THAT ELECTRIC POWER CHARACTERISTIC (VOLTAGE, PHASE, HORSEPOWER, AMPERAGE, ETC.) OF EQUIPMENT IS BASED ON AVAILABLE INFORMATION AT THE TIME OF PROJECT DESIGN. VERIFY CHARACTERISTICS FOR EACH PIECE OF NEW EQUIPMENT PRIOR TO ORDERING ELECTRICAL EQUIPMENT. INDICATE VERIFICATION ON SUBMITTALS. R. LOCATIONS INDICATED FOR NEW LIGHTING FIXTURES ARE APPROXIMATE. LOCATE FIXTURES LOCATIONS INDICATED FOR NEW LIGHTING FIXTURES ARE APPROXIMATE. LOCATE FIXTURES AS REQUIRED TO AVOID INTERFERENCE WITH NEW BUILDING STEEL, PIPING, DUCTWORK, CONDUIT, DIFFUSERS, GRILLES, SPEAKERS, SMOKE DETECTORS, ETC. FIELD COORDINATE EXACT LOCATIONS AS NEAR AS POSSIBLE TO THE LOCATION INDICATED.
AutoCAD SHX Text S. EXACT LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS, EXIT SIGNS, ETC. SHALL BE EXACT LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS, EXIT SIGNS, ETC. SHALL BE COORDINATED WITH OTHER CEILING MOUNTED EQUIPMENT TO AVOID CONFLICT. LOCATE DEVICES AS NEAR AS POSSIBLE TO THE LOCATION INDICATED. FIRE ALARM SMOKE DETECTORS SHALL BE LOCATED 3'-0" MINIMUM FROM HVAC DIFFUSERS, REGISTERS, GRILLES, ETC. T. ALL NEW CIRCUITING SHALL BE CONCEALED (EXCEPT IN BOILER ROOMS, ELECTRICAL AND ALL NEW CIRCUITING SHALL BE CONCEALED (EXCEPT IN BOILER ROOMS, ELECTRICAL AND MECHANICAL ROOMS). WHERE CONCEALMENT OF CIRCUITING IS DEEMED IMPOSSIBLE FOLLOWING DISCUSSIONS WITH OWNERS REPRESENTATIVE AND ARCHITECT, SURFACE RACEWAYS SHALL BE USED FOR ALL EXPOSED CIRCUITING (SEE SPECIFICATIONS REGARDING USE OF SURFACE RACEWAYS). UNDER NO CIRCUMSTANCES SHALL ANY EMT CONDUIT OR PIPE BE INSTALLED EXPOSED IN EXISTING CLASSROOMS, OFFICES, CORRIDORS OR FINISHED AREAS. ALL SURFACE RACEWAYS SHALL BE PAINTED TO MATCH EXISTING WALL SURFACE AND SHALL CONTAIN A GREEN INSULATED GROUND CONDUCTOR. U. EXACT LOCATIONS OF ALL NEW DEVICES, RACEWAYS, ETC. ADDED TO EXISTING ROOMS EXACT LOCATIONS OF ALL NEW DEVICES, RACEWAYS, ETC. ADDED TO EXISTING ROOMS SHALL BE FIELD VERIFIED TO AVOID INTERFERENCE WITH NEW AND EXISTING CABINETRY, CHALKBOARDS, TACKBOARDS, UNIT VENTILATORS, FURNITURE, ETC. COORDINATE FINAL LOCATIONS WITH THE OWNER, ARCHITECT AND ENGINEER BEFORE INSTALLATION. V. REVIEW ALL TRADES CONTRACT DOCUMENTS TO DETERMINE SPECIFIC MOUNTING LOCATIONS REVIEW ALL TRADES CONTRACT DOCUMENTS TO DETERMINE SPECIFIC MOUNTING LOCATIONS FOR ELECTRICAL EQUIPMENT. COORDINATE EXACT MOUNTING LOCATIONS WITH THE ARCHITECT AND OTHER CONTRACTORS. REFER TO ARCHITECTURAL PLANS FOR CASEWORK LAYOUT, ELEVATIONS, ETC. COORDINATE WITH LOCATIONS OF ELECTRICAL DEVICES AND OUTLETS. W. EXACT LOCATION OF MECHANICAL AND PLUMBING EQUIPMENT THAT REQUIRE ELECTRICAL EXACT LOCATION OF MECHANICAL AND PLUMBING EQUIPMENT THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL AND PLUMBING DRAWINGS. X. ALL NEW FIRE ALARM VISUAL STROBE UNITS SHALL BE MOUNTED AT 80" A.F.F. TO BOTTOM ALL NEW FIRE ALARM VISUAL STROBE UNITS SHALL BE MOUNTED AT 80" A.F.F. TO BOTTOM OF DEVICE LENS PER A.D.A. REQUIREMENTS. Y. CIRCUITING TO DEVICES/EQUIPMENT SHALL BE 2 #12 WITH 1 #12 GROUND (MULTIPLE CIRCUITING TO DEVICES/EQUIPMENT SHALL BE 2 #12 WITH 1 #12 GROUND (MULTIPLE HOMERUNS IN SAME CONDUIT MAY SHARE SAME EQUIPMENT GROUND) FOR EACH 20 AMPERE CIRCUIT UNLESS OTHERWISE NOTED. Z. REMOVE, TRANSPORT AND PROPERLY DISPOSE OF FLUORESCENT & MERCURY LAMPS, PCB REMOVE, TRANSPORT AND PROPERLY DISPOSE OF FLUORESCENT & MERCURY LAMPS, PCB BALLASTS AND PCB OIL FROM TRANSFORMERS AND SWITCHES IN ACCORDANCE WITH ALL FEDERAL, STATE & LOCAL CODES AND REGULATIONS. PROVIDE ALL DOCUMENTATION OF PROPER DISPOSAL TO OWNER. AA. DISCONNECT AND REMOVE LIGHTING, POWER AND SYSTEMS FROM AREAS OF RENOVATIONS DISCONNECT AND REMOVE LIGHTING, POWER AND SYSTEMS FROM AREAS OF RENOVATIONS AS REQUIRED TO ACCOMMODATE DEMOLITION WORK. COORDINATE ALL REMOVALS WITH OTHER TRADES. BE ADVISED THAT THE DRAWINGS MAY NOT LOCATE ALL EXISTING WIRING AND RACEWAYS WHICH MAY BE REQUIRED TO BE REMOVED, RELOCATED OR REWORKED, etc. TO ACCOMMODATE DEMOLITION WORK WITHIN THE EXISTING BUILDING. WHERE POSSIBLE, MAJOR COMPONENTS OF THE EXISTING ELECTRICAL SYSTEM (e.g. EXISTING PANELBOARDS, DISCONNECT SWITCHES, MECH. EQUIPMENT) HAVE BEEN SHOWN TO AID UNDERSTANDING. FIELD VISITS TO THE SITE TO REVIEW EXISTING BUILDING CONDITIONS WILL ASSIST IN UNDERSTANDING THE DEMOLITION WORK AND TYPICAL BUILDING MATERIALS TO BE ENCOUNTERED. AB. WHERE EXISTING CIRCUITING IS DISTURBED BY DEMOLITION WORK, THE CONTRACTOR SHALL WHERE EXISTING CIRCUITING IS DISTURBED BY DEMOLITION WORK, THE CONTRACTOR SHALL REWORK AND OR EXTEND EXISTING CIRCUITING AS REQUIRED TO MAINTAIN CONTINUITY TO ALL REMAINING LOADS ON THE AFFECTED CIRCUITS. WHERE WIRING FEEDING LIGHTING, RECEPTACLES, PANELBOARDS, ETC.. IN SPACES NOT INCLUDED IN THE ALTERATIONS ARE REQUIRED FOR REUSE AND ARE CUT; THEY SHALL BE EXTENDED AND RECONNECTED AS REQUIRED. WHEN MAKING SPLICES TO EXISTING CONDUCTORS, NEW CONDUCTORS SHALL MATCH EXISTING CONDUCTORS (COPPER OR ALUMINUM, AWG, SIZE, AND INSULATION), FIELD VERIFY PRIOR TO ORDERING WIRE. AC. THE ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION THAT, WHERE PRACTICAL, IT WILL THE ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION THAT, WHERE PRACTICAL, IT WILL BE ACCEPTABLE TO RE-USE EXISTING CONCEALED CONDUITS AND OUTLET BOXES REMAINING AFTER DEMOLITION WORK FOR NEW BRANCH CIRCUITING (e.g. CONDUIT BETWEEN SWITCH OUTLET BOX AND LIGHT FIXTURE OUTLET BOX). CONDUITS OR RACEWAYS BEING RE-USED MUST NOT BE DAMAGED, BUT BE IN GOOD PHYSICAL CONDITION, PROPERLY SUPPORTED AND UTILIZED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND NATIONAL ELECTRICAL CODE REQUIREMENTS GOVERNING THE INSTALLATION OF SAME. FIELD COORDINATE REMOVALS/DEMOLITION WITH GENERAL CONTRACTOR. AD. CIRCUIT NUMBERS INDICATED ON THE DRAWINGS ARE SHOWN FOR THE PURPOSE OF CIRCUIT NUMBERS INDICATED ON THE DRAWINGS ARE SHOWN FOR THE PURPOSE OF CLARIFYING THE GROUPING OF OUTLETS. THE ACTUAL NUMBER ASSIGNED TO THE CIRCUIT IN THE PANELBOARD SHALL SUIT THE BUSSING AND BRANCH CIRCUITING TO THE PANEL. PROVIDE COMPLETE AND ACCURATE TYPEWRITTEN PANEL DIRECTORIES FOR ALL NEW AND MODIFIED EXISTING BRANCH CIRCUIT PANELBOARDS. AE. PROVIDE BLANK STAINLESS STEEL COVERPLATES FOR ALL UNUSED OR ABANDONED PROVIDE BLANK STAINLESS STEEL COVERPLATES FOR ALL UNUSED OR ABANDONED JUNCTION BOXES, SIZED TO FIT OPENING. PATCH ANY HOLES REMAINING IN PLASTER CAUSED BY DEVICE REMOVALS. PATCH SMOOTH, PRIME AND PREP FOR PAINTING, PAINT TO MATCH EXISTING FINISHES. FOR REMAINING HOLES IN BLOCK: PATCH WITH APPROVED CONCRETE TYPE REPAIR MATERIALS TO MATCH SURFACE TEXTURE AND COLOR(S). AF. REFER TO ASBESTOS & LEAD ABATEMENT DRAWINGS FOR EXTEND OF WORK UNDER THAT REFER TO ASBESTOS & LEAD ABATEMENT DRAWINGS FOR EXTEND OF WORK UNDER THAT CONTRACT. WHENEVER DRILLING OR CUTTING ANY EXISTING ELEMENTS OR ATTACHING TO ANY EXISTING BEAMS, JOIST OR OTHER SURFACES. COORDINATE WITH ABATEMENT AUTHORITIES AS TO PRECAUTIONS OR ABATEMENT REQUIREMENTS. ANY SUSPECTED ASBESTOS, LEAD OR MOLD DISCOVERED SHALL BE REPORTED TO PROJECT MANAGER.
AutoCAD SHX Text
120/208V PANELBOARD
AutoCAD SHX Text
BRANCH CIRCUIT HOMERUN, CIRCUIT CONCEALED IN FLOOR
AutoCAD SHX Text
120 VOLT CIRCUIT HOMERUN, CIRCUIT CONCEALED IN CEILING
AutoCAD SHX Text
OR WALL. " " INDICATES GROUND WIRE.
AutoCAD SHX Text
208 VOLT CIRCUIT HOMERUN, CIRCUIT CONCEALED IN CEILING
AutoCAD SHX Text
OR WALL. " " INDICATES GROUND WIRE.
AutoCAD SHX Text
WIRE GAURD
AutoCAD SHX Text
WG
AutoCAD SHX Text UNLESS OTHERWISE INDICATED OR CALLED FOR, OR BECAUSE OF SPECIAL CONDITIONS, THE MOUNTING HEIGHTS OF ALL OUTLETS SHALL BE GENERALLY AS FOLLOWS:
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
WP
AutoCAD SHX Text LOCAL SWITCHES 44" ABOVE FLOOR TO CENTER 44" ABOVE FLOOR TO CENTER RECEPTACLES 1'-6" ABOVE FLOOR TO CENTER 1'-6" ABOVE FLOOR TO CENTER WALL MOUNTED HEIGHT AS INDICATED HEIGHT AS INDICATED FIXTURES MOTOR CONTROLS 4'-0" ABOVE FLOOR TO CENTER 4'-0" ABOVE FLOOR TO CENTER DISCONNECT AND 4'-0" ABOVE FLOOR TO CENTER 4'-0" ABOVE FLOOR TO CENTER SAFETY SWITCHES PANELBOARDS 6'-6" ABOVE FLOOR TO CENTER 6'-6" ABOVE FLOOR TO CENTER OF TOP MOST DEVICE HANDLE EXIT LIGHTS 9" ABOVE DOOR HEAD TO CENTER 9" ABOVE DOOR HEAD TO CENTER (WALL MOUNTED) RECEPTACLES COORDINATE W/ ARCH. DRAWINGS COORDINATE W/ ARCH. DRAWINGS OVER COUNTERS OR HEIGHT AS INDICATEDOR HEIGHT AS INDICATED
AutoCAD SHX Text TELEPHONE OUTLET 1'-6" ABOVE FLOOR TO CENTER 1'-6" ABOVE FLOOR TO CENTER (DESK TYPE) OR COMPUTER OUTLET TELEPHONE OUTLET 54" ABOVE FLOOR TO CENTER 54" ABOVE FLOOR TO CENTER (WALL) TELEVISION OUTLET 1'-6" ABOVE FLOOR TO CENTER 1'-6" ABOVE FLOOR TO CENTER & ASSOCIATED RECEPTACLE OUTLET (LOW) TELEVISION OUTLET 96" ABOVE FLOOR TO CENTER 96" ABOVE FLOOR TO CENTER & ASSOCIATED RECEPTACLE OUTLET (HIGH)
AutoCAD SHX Text FIRE ALARM 44" ABOVE FLOOR TO CENTER OF DEVICE. 44" ABOVE FLOOR TO CENTER OF DEVICE. PULL STATION COORDINATE WITH EXISTING FIELD CONDITIONS. COORDINATE WITH EXISTING FIELD CONDITIONS. FIRE ALARM 80" ABOVE FLOOR TO CENTER 80" ABOVE FLOOR TO CENTER COMBINATION AUDIO VISUAL UNIT FIRE ALARM 80" ABOVE FLOOR TO CENTER 80" ABOVE FLOOR TO CENTER VISUAL UNIT DUCT SMOKE 4'-0" ABOVE FLOOR TO CENTER 4'-0" ABOVE FLOOR TO CENTER DETECTOR REMOTE TEST STATION VOLUME CONTROL 4'-0" ABOVE FLOOR TO CENTER 4'-0" ABOVE FLOOR TO CENTER SECONDARY CLOCK HUNG 12" BELOW CEILING OR 8'-0" HUNG 12" BELOW CEILING OR 8'-0" TO CENTER, WHICHEVER IS LOWER
AutoCAD SHX Text BRANCH CIRCUIT WIRING. PROVIDE (1) HOT, (1) NEUTRAL AND (1) GROUND CONDUCTORS IN CONDUIT. " " INDICATES GROUND WIRE.
AutoCAD SHX Text BRANCH CIRCUIT WIRING. PROVIDE (2) HOT AND (1) GROUND CONDUCTORS IN CONDUIT. " " INDICATES GROUND WIRE.
AutoCAD SHX Text
277/480V PANELBOARD
AutoCAD SHX Text
480 VOLT CIRCUIT HOMERUN, CIRCUIT CONCEALED IN CEILING OR WALL.
AutoCAD SHX Text
277 VOLT CIRCUIT HOMERUN, CIRCUIT CONCEALED IN CEILING OR WALL.
AutoCAD SHX Text
DUST TIGHT
AutoCAD SHX Text
DT
AutoCAD SHX Text
ER
AutoCAD SHX Text
EXISTING TO BE RELOCATED/REINSTALLED
AutoCAD SHX Text
20AMP 120 VOLT RATED DUPLEX TAMPER RESISTANT RECEPTACLE WITH
AutoCAD SHX Text
MATCHING FACEPLATE, 'GFI' INDICATES GFCI DEVICE
AutoCAD SHX Text
20 AMP 120 VOLT RATED TAMPER RESISTANT QUAD RECEPTACLE WITH
AutoCAD SHX Text
MATCHING FACEPLATE
AutoCAD SHX Text
480 VOLT EQUIPMENT CONNECTION
AutoCAD SHX Text
EXISTING FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FACP
AutoCAD SHX Text
SUSPENDED OPEN CEILING 1'X4' ENCLOSED LENSED LED LIGHT FIXTURE
AutoCAD SHX Text
CB
AutoCAD SHX Text
COMBINATION DISCONNECT SWITCH/STARTER.
AutoCAD SHX Text
ENCLOSED SWITCH CIRCUIT BREAKER.
AutoCAD SHX Text 120VAC MOTOR-CIRCUIT DISCONNECT SWITCH IN LOCKABLE ALUMINUM ENCLOSURE FOR SURFACE MOUNT. PROVIDE HORSEPOWER RATING AS COORDINATED WITH MOTOR EQUIPMENT. HUBBELL #HBL1372 OR APPROVED EQUAL.
AutoCAD SHX Text M
AutoCAD SHX Text
UTILITY METER, COORDINATE WITH UTILITY COMPANY FOR REQUIREMENTS.
AutoCAD SHX Text
SUSPENDED OPEN CEILING 1'X4' STRIP LIGHT FIXTURE
AutoCAD SHX Text
INDICATES DETAIL REFERENCE NUMBER
AutoCAD SHX Text
INDICATES DRAWING REFERENCE NUMBER
AutoCAD SHX Text
AutoCAD SHX Text E100
AutoCAD SHX Text
NEW WIRING DEVICE/EQUIPMENT
AutoCAD SHX Text
EXISTING WIRING DEVICE/ EQUIPMENT TO REMAIN
AutoCAD SHX Text
EXISTING WIRING DEVICE/ EQUIPMENT THAT HAS BEEN REINSTALLED/RELOCATED
AutoCAD SHX Text
EXISTING WIRING DEVICE/ EQUIPMENT TO BE DISCONNECTED AND REMOVED
AutoCAD SHX Text
RL
AutoCAD SHX Text
EXISTING WIRING DEVICE/ EQUIPMENT TO BE DISCONNECTED, REMOVED AND RELOCATED
AutoCAD SHX Text
ER
AutoCAD SHX Text
ETR
AutoCAD SHX Text
GFI
AutoCAD SHX Text S
AutoCAD SHX Text
120/277V SINGLE POLE TOGGLE SWITCH
AutoCAD SHX Text
EMERGENCY EXIT SIGN
AutoCAD SHX Text
FS
AutoCAD SHX Text F
AutoCAD SHX Text
TS
AutoCAD SHX Text
SD
AutoCAD SHX Text
FLS
AutoCAD SHX Text
EXISTING FIRE ALARM SYSTEM PULL STATION
AutoCAD SHX Text
EXISTING FIRE ALARM SYSTEM SMOKE DETECTOR
AutoCAD SHX Text
EXISTING FIRE ALARM SYSTEM SPRINKLER TAMPER SWITCH
AutoCAD SHX Text
EXISTING FIRE ALARM SYSTEM SPRINKLER FLOW SWITCH
AutoCAD SHX Text
EXISTING FIRE ALARM SYSTEM NOTIFICATION AUDIO/VISUAL SPEAKER/STROBE