11-BPS 97 E300 - ELECTRICAL SINGLE LINE DIAGRAMS AND FIRE ALARM RISER DETAIL.pdf
PDF 504 KB Posted
- Attached to
- FIRE PUMP REPLACEMENT AT BPS 97
- Solicitation number
- 27-0627-025
- Issued by
- Erie County, New York
About this file
This is an electrical engineering drawing prepared by Buffalo Engineering, P.C. for the Buffalo Public Schools (BPS) fire pump replacement project at BPS 97 - Harvey Austin Elementary School, located at 1405 Sycamore Street, Buffalo, New York. The document provides electrical single line diagrams and fire alarm riser details for the fire pump replacement work. The project involves disconnecting and removing the existing fire pump system, including the existing 400-ampere main circuit breaker and MI cable feeder with three #2 AWG conductors, and replacing it with new equipment including a 450-ampere main circuit breaker and new fire pump feeder. Additionally, the work includes disconnecting and removing the existing jockey pump and controller, and installing a new jockey pump with associated controls. The scope also encompasses modifications to the fire pump controller and automatic transfer switch, with new wiring and supervisory signal requirements. All electrical work must comply with applicable codes and manufacturer specifications, and the fire alarm system modifications must meet NFPA 72 functional testing and system verification requirements.
The drawing is dated August 29, 2025, and was prepared by Buffalo Engineering, P.C. under firm authorization number 020076 with a license expiration date of August 31, 2026. The electrical modifications involve working with existing 480/277-volt three-phase four-wire systems, including coordination with a 250-kilowatt natural gas emergency generator and existing automatic transfer switches. The fire alarm riser detail indicates integration with the existing addressable fire alarm control panel with voice evacuation capabilities, requiring extension and reworking of existing conduits and installation of new wiring throughout. All modifications to initiating devices, notification appliances, and control equipment must be functionally tested in accordance with NFPA 72 standards, with revised records of completion prepared to document system changes and verify correct operation.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SINGLE
LINE DIAGRAMS AND
FIRE ALARM RISER
DETAIL
Drawn By:
Checked By:
Date:
Scale:
DWG. No.
RevisionsNo.
STAMP
Date
BU
FF
A
LO
E N
G
IN
EE
RI
N G
, P .C
Th es e do cu m en ts a nd th ei r c on te nt s ar e th e pr op er ty o f B uf fa lo E ng in ee ri ng , P
C a nd a re is su ed o nl y fo r t he s pe ci fic p ro je ct n ot ed o n th es e dr aw in gs
. A ny re pr od uc tio ns
, r ev is io ns , o r m od ifi ca tio ns o f t he se d oc um en ts w ith ou t t he e xp re ss w ri tte n co ns en t o f B uf fa lo
E ng in ee ri ng
, P C is p ro hi bi te d by la w
AS NOTED
8/29/2025
BUFFALO PUBLIC SCHOOLS
FIRE PUMP REPLACEMENT
BUFFALO PS 99 -
STANLEY M MAKOWSKI EARLY
CHILDHOOD CENTER
1095 JEFFERSON AVE,
BUFFALO, NY 14208
SED #: 140600010050012
BUFFALO PS 97 -
HARVEY AUSTIN ELEMENTARY
SCHOOL
1405 SYCAMORE ST,
BUFFALO, NY 14211
SED #: 140600010302031
CONSULTANTS
2025 BUFFALO ENGINEERING, PC
UNAUTHORIZED REPRODUCTION, ALTERATION OR ADDITION TO ANY
DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IN WHOLE OR IN
PART WITHOUT THE EXPRESS WRITTEN AUTHORIZATION IS PROHIBITED
BY SECTION 7209, PROVISION 2 OF THE NEW YORK STATE EDUCATION
LAW UNLESS OTHERWISE ACTING UNDER THE DIRECTION OF A LICENSED
ARCHITECT OR ENGINEER FOR WHICH THE SEAL OF A LICENSED
ARCHITECT OR ENGINEER IS APPLIED.
COPYRIGHT
SHEET TITLE
LICENSE EXPIRATION DATE: 8/31/2026
FIRM AUTHORIZATION NUMBER: 020076
JRG
BPS 97
E300
AutoCAD SHX Text
DISCONNECT EXISTING FIRE PUMP
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PARTIAL ELECTRICAL SINGLE LINE DIAGRAM - BPS97 - EXISTING EQUIPMENT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text M.L.O.
AutoCAD SHX Text 100A-3P
AutoCAD SHX Text
EXP-EMER
AutoCAD SHX Text
AutoCAD SHX Text 400A
AutoCAD SHX Text
DISCONNECT AND REMOVE EXISTING FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG.
AutoCAD SHX Text
REPLACE EXISTING FIRE PUMP MAIN CIRCUIT BREAKER
AutoCAD SHX Text
EXISTING FIRE PUMP FEEDER:MI CABLE, (3) #2 AWG TO BE REMOVED.
AutoCAD SHX Text 400A/3P
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
FIRE PUMP
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
PARTIAL ELECTRICAL SINGLE LINE DIAGRAM - BPS97 - NEW WORK
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text M.L.O.
AutoCAD SHX Text 100A-3P
AutoCAD SHX Text
AutoCAD SHX Text 400A
AutoCAD SHX Text
NEW FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG
AutoCAD SHX Text NEW FIRE PUMP MAIN CIRCUIT BREAKER. CIRCUIT BREAKER SHALL BE LISTED FOR USE IN EXISTING SWITCHBOARD AND MATCH AIC RATINGS.
AutoCAD SHX Text
NEW FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG
AutoCAD SHX Text 450A/3P
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text 225A-3P
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M.L.O.
AutoCAD SHX Text 20A-3P
AutoCAD SHX Text
DISCONNECT EXISTING JOCKEY PUMP, REMOVE CONDUIT AND WIRING.
AutoCAD SHX Text
AutoCAD SHX Text 225A/3P
AutoCAD SHX Text 225A-3P
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M.L.O.
AutoCAD SHX Text 20A-3P
AutoCAD SHX Text
NEW JOCKEY PUMP
AutoCAD SHX Text
AutoCAD SHX Text 225A/3P
AutoCAD SHX Text
750A/3P (GFI)
AutoCAD SHX Text
750A/3P (GFI)
AutoCAD SHX Text
EXISTING 3 #12 & 1 #12 GND. IN 3/4" C. TO BE EXTENDED/REWORKED TO NEW EQUIPMENT
AutoCAD SHX Text
EXISTING MDSB-H 480/277V-3 -4W
AutoCAD SHX Text
EXISTING MDSB-H 480/277V-3 -4W
AutoCAD SHX Text 125A-3P
AutoCAD SHX Text
EXISTING FIRE PUMP TRANSFER SWITCH/CONTROLLER TO BE REMOVED.
AutoCAD SHX Text
EXTEND/REWORK EXISTING FEEDER WITH 3 #12 & 1 #12 GND. IN 3/4" C.
AutoCAD SHX Text PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPARE SPACE. NEW CIRCUIT BREAKER SHALL BE LISTED FOR USE IN EXISTING PANEL AND MATCH AIC RATINGS.
AutoCAD SHX Text
LABEL EXISTING CIRCUIT BREAKER AS SPARE IN DIRECTORY
AutoCAD SHX Text
NEW JOCKEY PUMP CONTROLLER
AutoCAD SHX Text
NEW 3 #12 & 1 #12 GND. IN 3/4" C.
AutoCAD SHX Text
DISCONNECT AND REMOVE EXISTING JOCKEY PUMP CONTROLLER
AutoCAD SHX Text
EXISTING 250KW/313KVA NATURAL GAS EMERGENCY GENERATOR 480/277V-3 -4W
AutoCAD SHX Text
EXISTING WIRING TO BE REMOVED. EXTEND/REWORK EXISTING CONDUITS FOR NEW WIRING
AutoCAD SHX Text
EXISTING PANEL 'BXLEH1' 480/277V-3 -4W-225A
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER/AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text
EXISTING 250KW/313KVA NATURAL GAS EMERGENCY GENERATOR 480/277V-3 -4W
AutoCAD SHX Text
PROVIDE NEW WIRING, EXTEND/REWORK EXISTING CONDUITS.
AutoCAD SHX Text
EXISTING PANEL 'BXLEH1' 480/277V-3 -4W-225A
AutoCAD SHX Text
EXISTING ATS-2 480V-3 -4W-225A
AutoCAD SHX Text
EXISTING ATS-2 480V-3 -4W-225A
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text
NAC
AutoCAD SHX Text
TO ADDITIONAL DEVICES
AutoCAD SHX Text
ETR 120 VOLT POWER
AutoCAD SHX Text
SD
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
ETR NAC EXTENDER PANEL, TYP.
AutoCAD SHX Text
DET-6B
AutoCAD SHX Text
(ETR TRANSMITTER/
AutoCAD SHX Text
COMMUNICATOR)
AutoCAD SHX Text
ETR LINE TO FIRE DEPARTMENT
AutoCAD SHX Text
ETR SERVICE PORT MODEM
AutoCAD SHX Text
EXIST. 120 VOLT POWER;
AutoCAD SHX Text
FS
AutoCAD SHX Text
INITIATING CIRCUIT WIRING, TYP.
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
EXIST.
AutoCAD SHX Text
FACP
AutoCAD SHX Text
EXISTING ADDRESSABLE FIRE-ALARM CONTROL PANEL WITH VOICE EVAC.
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
TO ADDITIONAL DEVICES
AutoCAD SHX Text
FIRE ALARM SYSTEM GENERAL NOTES:
AutoCAD SHX Text
1. THIS DETAIL IS DIAGRAMMATIC ONLY, ALL QUANTITIES AND THIS DETAIL IS DIAGRAMMATIC ONLY, ALL QUANTITIES AND LOCATIONS OF DEVICES ARE SHOWN ON DRAWINGS. 2. PROVIDE COMPONENTS AND WIRING REQUIRED FOR A COMPLETE PROVIDE COMPONENTS AND WIRING REQUIRED FOR A COMPLETE AND WORKING SYSTEM AS COORDINATED WITH SYSTEM MANUFACTURER. 3. WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL RELAY IS ADDED, RELOCATED OR REPLACED, IT SHALL BE FUNCTIONALLY TESTED PER NFPA 72. 4. WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE, APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE OPERATED PER NFPA 72. 5. WHEN MODIFICATIONS OR REPAIRS TO CONTROL EQUIPMENT WHEN MODIFICATIONS OR REPAIRS TO CONTROL EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT SHALL BE TESTED IN ACCORDANCE WITH NFPA 72. 6. WHEN CHANGES ARE MADE TO SITE-SPECIFIC SOFTWARE, ALL WHEN CHANGES ARE MADE TO SITE-SPECIFIC SOFTWARE, ALL FUNCTIONS KNOWN TO BE AFFECTED BY THE CHANGE SHALL BE 100 PERCENT TESTED. IN ADDITION, 10 PERCENT OF THE INITIATING DEVICES THAT ARE NOT DIRECTLY AFFECTED BY THE CHANGE, UP TO A MAXIMUM OF 50 DEVICES, ALSO SHALL BE TESTED AND CORRECT SYSTEM OPERATION SHALL BE VERIFIED. A REVISED RECORD OF COMPLETION SHALL BE PREPARED TO REFLECT THESE CHANGES IN ACCORDANCE WITH NFPA 72.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
TYPICAL FIRE ALARM RISER DETAIL
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
FLS
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
TO ADDITIONAL DEVICES
AutoCAD SHX Text
TS
AutoCAD SHX Text
TS
AutoCAD SHX Text
TS
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
(ETR)
AutoCAD SHX Text
EXIST.
AutoCAD SHX Text
FACP
AutoCAD SHX Text
EXIST.
AutoCAD SHX Text
FACP
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER/AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text NEW WIRING AND SUPERVISORY SIGNAL. FOLLOWING CONDITIONS SHALL INITIATE SUPERVISORY SIGNAL: "FIRE PUMP IS RUNNING", "FIRE PUMP LOST POWER", "POWER TO FIRE PUMP PHASE REVERSAL".