11-BPS 97 E300 - ELECTRICAL SINGLE LINE DIAGRAMS AND FIRE ALARM RISER DETAIL.pdf

PDF 504 KB Posted

Attached to
FIRE PUMP REPLACEMENT AT BPS 97
Solicitation number
27-0627-025
Issued by
Erie County, New York

About this file

This is an electrical engineering drawing prepared by Buffalo Engineering, P.C. for the Buffalo Public Schools (BPS) fire pump replacement project at BPS 97 - Harvey Austin Elementary School, located at 1405 Sycamore Street, Buffalo, New York. The document provides electrical single line diagrams and fire alarm riser details for the fire pump replacement work. The project involves disconnecting and removing the existing fire pump system, including the existing 400-ampere main circuit breaker and MI cable feeder with three #2 AWG conductors, and replacing it with new equipment including a 450-ampere main circuit breaker and new fire pump feeder. Additionally, the work includes disconnecting and removing the existing jockey pump and controller, and installing a new jockey pump with associated controls. The scope also encompasses modifications to the fire pump controller and automatic transfer switch, with new wiring and supervisory signal requirements. All electrical work must comply with applicable codes and manufacturer specifications, and the fire alarm system modifications must meet NFPA 72 functional testing and system verification requirements.

The drawing is dated August 29, 2025, and was prepared by Buffalo Engineering, P.C. under firm authorization number 020076 with a license expiration date of August 31, 2026. The electrical modifications involve working with existing 480/277-volt three-phase four-wire systems, including coordination with a 250-kilowatt natural gas emergency generator and existing automatic transfer switches. The fire alarm riser detail indicates integration with the existing addressable fire alarm control panel with voice evacuation capabilities, requiring extension and reworking of existing conduits and installation of new wiring throughout. All modifications to initiating devices, notification appliances, and control equipment must be functionally tested in accordance with NFPA 72 standards, with revised records of completion prepared to document system changes and verify correct operation.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SINGLE

LINE DIAGRAMS AND

FIRE ALARM RISER

DETAIL

Drawn By:

Checked By:

Date:

Scale:

DWG. No.

RevisionsNo.

STAMP

Date

BU

FF

A

LO

E N

G

IN

EE

RI

N G

, P .C

Th es e do cu m en ts a nd th ei r c on te nt s ar e th e pr op er ty o f B uf fa lo E ng in ee ri ng , P

C a nd a re is su ed o nl y fo r t he s pe ci fic p ro je ct n ot ed o n th es e dr aw in gs

. A ny re pr od uc tio ns

, r ev is io ns , o r m od ifi ca tio ns o f t he se d oc um en ts w ith ou t t he e xp re ss w ri tte n co ns en t o f B uf fa lo

E ng in ee ri ng

, P C is p ro hi bi te d by la w

AS NOTED

8/29/2025

BUFFALO PUBLIC SCHOOLS

FIRE PUMP REPLACEMENT

BUFFALO PS 99 -

STANLEY M MAKOWSKI EARLY

CHILDHOOD CENTER

1095 JEFFERSON AVE,

BUFFALO, NY 14208

SED #: 140600010050012

BUFFALO PS 97 -

HARVEY AUSTIN ELEMENTARY

SCHOOL

1405 SYCAMORE ST,

BUFFALO, NY 14211

SED #: 140600010302031

CONSULTANTS

2025 BUFFALO ENGINEERING, PC

UNAUTHORIZED REPRODUCTION, ALTERATION OR ADDITION TO ANY

DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IN WHOLE OR IN

PART WITHOUT THE EXPRESS WRITTEN AUTHORIZATION IS PROHIBITED

BY SECTION 7209, PROVISION 2 OF THE NEW YORK STATE EDUCATION

LAW UNLESS OTHERWISE ACTING UNDER THE DIRECTION OF A LICENSED

ARCHITECT OR ENGINEER FOR WHICH THE SEAL OF A LICENSED

ARCHITECT OR ENGINEER IS APPLIED.

COPYRIGHT

SHEET TITLE

LICENSE EXPIRATION DATE: 8/31/2026

FIRM AUTHORIZATION NUMBER: 020076

JRG

BPS 97

E300

AutoCAD SHX Text

DISCONNECT EXISTING FIRE PUMP

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

PARTIAL ELECTRICAL SINGLE LINE DIAGRAM - BPS97 - EXISTING EQUIPMENT

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text M.L.O.

AutoCAD SHX Text 100A-3P

AutoCAD SHX Text

EXP-EMER

AutoCAD SHX Text

AutoCAD SHX Text 400A

AutoCAD SHX Text

DISCONNECT AND REMOVE EXISTING FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG.

AutoCAD SHX Text

REPLACE EXISTING FIRE PUMP MAIN CIRCUIT BREAKER

AutoCAD SHX Text

EXISTING FIRE PUMP FEEDER:MI CABLE, (3) #2 AWG TO BE REMOVED.

AutoCAD SHX Text 400A/3P

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text

FIRE PUMP

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

PARTIAL ELECTRICAL SINGLE LINE DIAGRAM - BPS97 - NEW WORK

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text M.L.O.

AutoCAD SHX Text 100A-3P

AutoCAD SHX Text

AutoCAD SHX Text 400A

AutoCAD SHX Text

NEW FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG

AutoCAD SHX Text NEW FIRE PUMP MAIN CIRCUIT BREAKER. CIRCUIT BREAKER SHALL BE LISTED FOR USE IN EXISTING SWITCHBOARD AND MATCH AIC RATINGS.

AutoCAD SHX Text

NEW FIRE PUMP FEEDER: MI CABLE, (3) #2 AWG

AutoCAD SHX Text 450A/3P

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text 225A-3P

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text M.L.O.

AutoCAD SHX Text 20A-3P

AutoCAD SHX Text

DISCONNECT EXISTING JOCKEY PUMP, REMOVE CONDUIT AND WIRING.

AutoCAD SHX Text

AutoCAD SHX Text 225A/3P

AutoCAD SHX Text 225A-3P

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text M.L.O.

AutoCAD SHX Text 20A-3P

AutoCAD SHX Text

NEW JOCKEY PUMP

AutoCAD SHX Text

AutoCAD SHX Text 225A/3P

AutoCAD SHX Text

750A/3P (GFI)

AutoCAD SHX Text

750A/3P (GFI)

AutoCAD SHX Text

EXISTING 3 #12 & 1 #12 GND. IN 3/4" C. TO BE EXTENDED/REWORKED TO NEW EQUIPMENT

AutoCAD SHX Text

EXISTING MDSB-H 480/277V-3 -4W

AutoCAD SHX Text

EXISTING MDSB-H 480/277V-3 -4W

AutoCAD SHX Text 125A-3P

AutoCAD SHX Text

EXISTING FIRE PUMP TRANSFER SWITCH/CONTROLLER TO BE REMOVED.

AutoCAD SHX Text

EXTEND/REWORK EXISTING FEEDER WITH 3 #12 & 1 #12 GND. IN 3/4" C.

AutoCAD SHX Text PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPARE SPACE. NEW CIRCUIT BREAKER SHALL BE LISTED FOR USE IN EXISTING PANEL AND MATCH AIC RATINGS.

AutoCAD SHX Text

LABEL EXISTING CIRCUIT BREAKER AS SPARE IN DIRECTORY

AutoCAD SHX Text

NEW JOCKEY PUMP CONTROLLER

AutoCAD SHX Text

NEW 3 #12 & 1 #12 GND. IN 3/4" C.

AutoCAD SHX Text

DISCONNECT AND REMOVE EXISTING JOCKEY PUMP CONTROLLER

AutoCAD SHX Text

EXISTING 250KW/313KVA NATURAL GAS EMERGENCY GENERATOR 480/277V-3 -4W

AutoCAD SHX Text

EXISTING WIRING TO BE REMOVED. EXTEND/REWORK EXISTING CONDUITS FOR NEW WIRING

AutoCAD SHX Text

EXISTING PANEL 'BXLEH1' 480/277V-3 -4W-225A

AutoCAD SHX Text

NEW FIRE PUMP CONTROLLER/AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text

EXISTING 250KW/313KVA NATURAL GAS EMERGENCY GENERATOR 480/277V-3 -4W

AutoCAD SHX Text

PROVIDE NEW WIRING, EXTEND/REWORK EXISTING CONDUITS.

AutoCAD SHX Text

EXISTING PANEL 'BXLEH1' 480/277V-3 -4W-225A

AutoCAD SHX Text

EXISTING ATS-2 480V-3 -4W-225A

AutoCAD SHX Text

EXISTING ATS-2 480V-3 -4W-225A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text

NAC

AutoCAD SHX Text

TO ADDITIONAL DEVICES

AutoCAD SHX Text

ETR 120 VOLT POWER

AutoCAD SHX Text

SD

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

ETR NAC EXTENDER PANEL, TYP.

AutoCAD SHX Text

DET-6B

AutoCAD SHX Text

(ETR TRANSMITTER/

AutoCAD SHX Text

COMMUNICATOR)

AutoCAD SHX Text

ETR LINE TO FIRE DEPARTMENT

AutoCAD SHX Text

ETR SERVICE PORT MODEM

AutoCAD SHX Text

EXIST. 120 VOLT POWER;

AutoCAD SHX Text

FS

AutoCAD SHX Text

INITIATING CIRCUIT WIRING, TYP.

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text

FACP

AutoCAD SHX Text

EXISTING ADDRESSABLE FIRE-ALARM CONTROL PANEL WITH VOICE EVAC.

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

TO ADDITIONAL DEVICES

AutoCAD SHX Text

FIRE ALARM SYSTEM GENERAL NOTES:

AutoCAD SHX Text

1. THIS DETAIL IS DIAGRAMMATIC ONLY, ALL QUANTITIES AND THIS DETAIL IS DIAGRAMMATIC ONLY, ALL QUANTITIES AND LOCATIONS OF DEVICES ARE SHOWN ON DRAWINGS. 2. PROVIDE COMPONENTS AND WIRING REQUIRED FOR A COMPLETE PROVIDE COMPONENTS AND WIRING REQUIRED FOR A COMPLETE AND WORKING SYSTEM AS COORDINATED WITH SYSTEM MANUFACTURER. 3. WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL RELAY IS ADDED, RELOCATED OR REPLACED, IT SHALL BE FUNCTIONALLY TESTED PER NFPA 72. 4. WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR WHEN AN INITIATING DEVICE, NOTIFICATION APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE, APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE OPERATED PER NFPA 72. 5. WHEN MODIFICATIONS OR REPAIRS TO CONTROL EQUIPMENT WHEN MODIFICATIONS OR REPAIRS TO CONTROL EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT SHALL BE TESTED IN ACCORDANCE WITH NFPA 72. 6. WHEN CHANGES ARE MADE TO SITE-SPECIFIC SOFTWARE, ALL WHEN CHANGES ARE MADE TO SITE-SPECIFIC SOFTWARE, ALL FUNCTIONS KNOWN TO BE AFFECTED BY THE CHANGE SHALL BE 100 PERCENT TESTED. IN ADDITION, 10 PERCENT OF THE INITIATING DEVICES THAT ARE NOT DIRECTLY AFFECTED BY THE CHANGE, UP TO A MAXIMUM OF 50 DEVICES, ALSO SHALL BE TESTED AND CORRECT SYSTEM OPERATION SHALL BE VERIFIED. A REVISED RECORD OF COMPLETION SHALL BE PREPARED TO REFLECT THESE CHANGES IN ACCORDANCE WITH NFPA 72.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

TYPICAL FIRE ALARM RISER DETAIL

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

AutoCAD SHX Text

FLS

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

TO ADDITIONAL DEVICES

AutoCAD SHX Text

TS

AutoCAD SHX Text

TS

AutoCAD SHX Text

TS

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

(ETR)

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text

FACP

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text

FACP

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text

NEW FIRE PUMP CONTROLLER/AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text NEW WIRING AND SUPERVISORY SIGNAL. FOLLOWING CONDITIONS SHALL INITIATE SUPERVISORY SIGNAL: "FIRE PUMP IS RUNNING", "FIRE PUMP LOST POWER", "POWER TO FIRE PUMP PHASE REVERSAL".