Livermore Drawings - Amendment 003.pdf
PDF 5 MB Posted
- Solicitation number
- 89503120BWA000022
About this file
This document contains project drawings and specifications for upgrades to the station service at the Lawrence Livermore Substation in California, as well as details of a related federal contract opportunity posted on SAM.gov.
The contract opportunity is a competitive 100% small business set-aside IFB issued by the Department of Energy's Western Area Power Administration to remove and install new substation equipment including pad mount transformers, automatic transfer switches, distribution panels and associated station service equipment at three substations. Bids are due by March 30, 2020 and the project value is estimated between $2.5 million to $5 million. The solicitation and drawings are available electronically from SAM.gov and all responsible sources may submit a bid for consideration. Interested parties should register in SAM and ensure their ORCA is current and complete the solicitation requirements.
The project drawings specify upgrades to the switching diagram, arrangement plan, equipment schedules, foundation plans, cable trench designs, support structures, service building configurations and controls at the Lawrence Livermore Substation to modernize the station service. The contractor will be responsible for checking the drawings for errors or omissions prior to construction.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DRAWINGS
LAWRENCE LIVERMORE SUBSTATION
STATION SERVICE UPGRADES
STATE
SECTION C
DESCRIPTION/SPECIFICATIONS
Spec No. 959 Amendment 003
CALIFORNIA
LAWERANCE LIVERMORE SUBSTATION
STATION SERVICE UPGRADES
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAWINGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale.
Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. LLL 0015 Rev. B – Location, Access Road, & Vicinity
ELECTRICAL:
2. LLL 0001 Rev. B EI – Switching Diagram (Existing Installation)
3. LLL 0001 Rev. C – Switching Diagram
4. LLL 1000 Rev. C EI – Arrangement Plan (Existing Installation)
5. LLL 1000 Rev. D – Arrangement Plan
6. LLL 1100 Rev. B – Equipment and Material Index
7. LLL 1102 – Equipment Identification Signs
8. LLL 1116 Rev. B EI – KY1A Transformer Area Sections P-P and Q-Q (Existing Installation)
9. LLL 1116 Rev. C – KY1A Transformer Area Sections P-P and Q-Q
10. LLL 1511 Rev. C EI – Transformer Area Grounding and Conduit Plan (Existing Installation)
11. LLL 1511 Rev. D - Transformer Area Grounding and Conduit Plan
12. LLL 1610 Rev. B EI – 240/120 Volt Power and Lighting Wiring Diagram (Existing Installation)
13. LLL 1610 Rev. C - 240/120 Volt Power and Lighting Wiring Diagram
14. LLL 1611 Rev. B EI – Transformers KZ1A-KZ2A Wiring Diagram (Existing Installation)
15. LLL 1611 Rev. C - Transformers KZ1A-KZ2A Wiring Diagram
16. LLL 1612 Rev. A – Station Service Panel DZC/DZD Wiring Diagram
CIVIL & SITE DRAWINGS:
17. LLL 2000 Rev. B FIO – Grading and Plot Plan (For Information Only)
FOUNDATION AND STRUCTURAL DRAWING INDEX:
18. LLL 2007 Rev. D – Foundation Designations and Unit Quantities
CONCRETE:
19. LLL 2003 Rev. C EI – Foundation General Plan (Existing Installation)
20. LLL 2003 Rev. D – Foundation General Plan
21. LLL 2004 Rev. B EI – Foundation Plan Transformer Area (Existing Installation)
22. LLL 2004 Rev. C – Foundation Plan Transformer Area
23. LLL 2011 Rev. D – Foundations Outline and Reinforcement
24. LLL 2300 – Foundations Outline and Reinforcement
25. LLL 2301 – Foundation Outline and Reinforcement
CABLE TRENCH:
26. LLL 2015 Rev. B EI – Type “C” Cable Trench (Existing Installation)
27. LLL 2015 Rev. C – Type “C” Cable Trench
28. LLL 2500 – Cable Trench for Station Service Equipment
STEEL STRUCTURES:
29. LLL 2550 – Anchor Bolts
30. LLL 2600 – Station Service Equipment Support Frame
31. LLL 2601 – Station Service Equipment Support Frame Details
SERVICE BUILDING:
32. LLL 3011 Rev. F – Service Building Distribution Boards DHA1 and DHA2 Panel Schedules
33. LLL 3403 – Yard Lighting Circuits and Photocell Yard Lighting Control Wiring Diagram
34. LLL 4000 Rev. I FIO – Service Building Conduit, Arrangement and Grounding (For Information Only) https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx
LAWERANCE LIVERMORE SUBSTATION
STATION SERVICE UPGRADES
PROJECT DRAWINGS
CONTROLS:
35. LLL T601 – RTU AND CONTROL CABLE LIST
#0
Altamont Pass Rd
Old Patterson Pass Rd TRY-LLL 230 kV
LLL 424 115 kV
§̈¦580
I 580
Greenville Rd
S V as co R d
East Ave
Cross Rd
Las Positas Rd
Lupin Way
Flynn Rd N
Av en ue B
Natio nal Dr
Preston Ave
Southfront Rd
1st St
Scenic Ave
S Portal Dr
Av en ue A
W Pe rim ete r D r
Westgate Dr
Je rro ld Rd
La ug hli n R d
Lawrence Dr
Village Dr
Charlotte Way
So ut hg ate
D r
Th un de rb ird Ln
N Inner Loop
He rm an Av e
5th St
Pullman St
Marathon Dr
Unnamed Street
S Inner Loop
Parking Lot
Patterson Pass Rd
Brisa St
Las Positas Rd
Southfront Rd
Livermore
_̂ Lawrence Livermore Substation Alameda County
0 0.25 0.5 0.75 1 Miles
DECEMBER 19, 1988 LLL
WESTERN AREA POWER ADMINISTRATION
AREA OFFICE - SACRAMENTO, CA
LAWRENCE LIVERMORE SUBSTATION
CALIFORNIA
LOCATION, ACCESS ROAD, & VICINITY
GIS
"S
"S
"S"S
"S
"S
#0
LLL 424 115 kV
TRY-LLL 230 kV
Gr ee nv ille
R d
Old Patterson Pass Rd
N Outer Loop
Patterson Pass Rd
Livermore
Site Coordinates Lat: 37° 41' 36.726" N Long: 121° 41' 43.098" W
DESIGNED _______________________ APPROVED __________________________George T. West Don Warner
UNITED STATES DEPARTMENT OF ENERGY
K #0 Substation "S Structure ! Gate
WAPA Transmission Line Access Road Documented Access Road Public Road ROW Maintenance Road Transmission Line ROW Facility Boundary
Adjoining 7.5' Quadrangle Names Center quad is this site
From: Folsom, CA
1. Merge onto US-50 W 17.8 mi
2. Merge onto I-80BUS W 1.2 mi
3. Turn Right onto I-5/CA-99 N 0.2 mi
4. Take the exit on the Left onto I-5 S toward Los Angeles 59.8 mi
5. Slight Right onto I-205 W 13.7 mi
6. Merge onto I-580 W 7.7 mi
7. Take exit 57 toward N Greenville Rd 0.2 mi
8. Merge onto Altamont Pass Rd 0.1 mi
9. Turn Right onto Greenville Rd (signs for Stockton) 1.8 mi
10. Turn Left onto Patterson Pass Road 0.2 mi Destination will be on the Right To: Livermore Substation 8421 Patterson Rd.
Livermore, CA 94550 104 Miles, 1 hour 39 mins
B 5/13/16 N5 - WAH Revised and Redrawn in GIS
1 2 3
5 6 8 9
1:24,000 1 inch = 2,000 feet
1. Tassajara
2. Byron Hot Springs
3. Clifton Court Forebay
4. Livermore
5. Altamont
6. Midway
7. La Costa Valley
8. Mendenhall Springs
9. Cedar Mtn.
This cartographic product and GIS data were prepared in accordance with professional practice standards. The data represented on this map has been developed from the best available sources. Although efforts have been made to ensure that the data is accurate and reliable, errors may be reflected in the data. Users must be aware of these conditions and bear responsibility for the appropriate use of this map. The data on this map is for reference use only.
STATION SERVICE XFMR
KZ1A
13.8KV-240/120V 225KVA
TRANSFORMER KZ1A
AZ1A
SURGE ARRESTER
TRANSFORMER KZ2A
AZ2A
SURGE ARRESTER
STATION SERVICE
SSA
600A 240V
STATION SERVICE
SSB
600A 240V
STATION SERVICE
ATS
600A 240V
STATION SERVICE
DZC
240/120V
STATION SERVICE
DZD
240/120V
STATION SERVICE XFMR
KZ2A
13.8KV-240/120V 225KVA
EMERGENCY GENERATOR
GEN
NORMALLY OPEN
EMERGENCY PANEL TIE
DZC-DZD
NORMALLY OPEN
EMERGENCY PANEL TIE
DZD-DZC
NORMALLY OPEN
EMERGENCY GENERATOR
TRANSFER SEQUENCE INSTRUCTIONS
WARNING
PERSONS NOT FAMILIAR WITH THE OPERATION OF THIS SYSTEM SHALL NOT ATTEMPT TO CHANGE THE POSITION OF ANY OF THESE DEVICES.
FAILURE TO HEED THESE INSTRUCTIONS WILL RESULT IN A LOSS OF POWER AND DAMAGE TO CRITICAL EQUIPMENT.
1. PANEL DZC AND DZD MAIN BREAKERS MUST BE IN THE OPEN POSITION PRIOR TO USING EMERGENCY GENERATOR. DO NOT PARALLEL SOURCES.
6. CLOSE EMERGENCY PANEL TIE BREAKER IN PANEL DZD.
2. OPEN PANEL DZC MAIN BREAKER.
3. CLOSE EMERGENCY PANEL TIE BREAKER IN PANEL DZC.
4. OPEN PANEL DZD MAIN BREAKER.
5. CLOSE EMERGENCY GENERATOR RECEPTACLE BREAKER IN PANEL DZD.
7. CONNECT EMERGENCY GENERATOR TO EMERGENCY GENERATOR RECEPTACLE LOCATED ON PANEL DZD.
LIGHTING
LCU1
CONTACTOR NO. 1
LIGHTING
LCU2
CONTACTOR NO. 2
seela New Stamp
| LAWRENCE LIVERMORE SUBSTATION STATION SERVICE UPGRADES |
| Drawing List |
| lll_0015b |
| lll_0001b_ei |
| lll_0001c |
| lll_0015b |
| lll_1000c_ei |
| lll_1000d |
| lll_1100b |
| lll_1102 |
| lll_1116b_ei |
| lll_1116c |
| lll_1511c_ei |
| lll_1511d |
| lll_1610b_ei |
| lll_1610c |
| lll_1611b_ei |
| lll_1611c |
| lll_1612a |
| lll_2000b_fio |
| lll_2007d |
| lll_2003c_ei |
| lll_2003d |
| lll_2004b_ei |
| lll_2004c |
| lll_2011d |
| lll_2300 |
| lll_2301 |
| lll_2015b_ei |
| lll_2015c |
| lll_2500 |
| lll_2550 |
| lll_2600 |
| lll_2601 |
| lll_3011f |
| lll_3403 |
| lll_4000i_fio |
| lll_t601 |
File details come from the government source that posted it. Updated .