8. 28 51 20 - SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM.pdf

PDF 169 KB Posted

Attached to
Federal Bureau of Prisons Inmate Tablet Implementation Initiative
Solicitation number
15BPCC26R00000001
Issued by

About this file

This document is a technical design guidelines specification for a Security Electronics Fiber Optic Cable System for the Federal Bureau of Prisons (FBOP). The specification provides comprehensive technical requirements for fiber optic cable installation, including detailed specifications for cable types, performance characteristics, installation procedures, and testing protocols. Key technical requirements include using single-mode fiber optic cables with specific performance parameters such as core diameter (9 microns), maximum attenuation (0.5 dB/km at 1310 nm and 1550 nm), and operating temperature range (-40°C to +70°C).

The document outlines fiber optic cable assignments for various security electronic systems, including Sentry LAN, TRULINCS LAN, Education LAN, Commissary LAN, UNICOR LAN, Staff Digital Telephone LAN, and Radio Backbone. Each cable type has specific strand allocations for different network purposes, with provisions for spare strands. The specification mandates rigorous installation and testing procedures, including end-to-end loss measurements, connector loss limitations, and comprehensive documentation requirements. The guidelines are marked as "Sensitive But Unclassified - SBU" and are specifically tailored for construction and environmental review with a revision date of 06-01-22.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construction & Environmental Review FBOP TECHNICAL DESIGN GUIDELINES

SECTION REVISION DATE: 06-01-22

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-1

Sensitive But Unclassified – SBU

SECTION 28 51 20 - SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM

PART 1 - GENERAL

1.1 SUMMARY

A. This section covers the fiber optic cable system as shown on the drawings or as required to support the systems defined in these specifications. The work under this section consists of furnishing materials and equipment, performing labor and services necessary for the installation of the fiber optic cable system required for the security electronics system.

B. Related Work Specified Elsewhere: Refer to all other Security Electronics System specification sections and drawings, and to the specifications and drawings under the General Construction Contract to ascertain the extent of work included.

1.2 RELATED SECTIONS AND DOCUMENTS

A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to the Work of this Section.

1.3 SUBMITTALS

A. Submittals shall be packaged in accordance with specification Section 28 50 00 - Security Electronics General Provisions of these specifications.

B. When making the submittal as required by specification Section 28 50 00 - Security Electronics General Provisions, include this additional information.

1. Test Report Submittal:

a. Submit Quality Assurance data sheets prepared by the cable supplier for each cable reel.

b. Submit final test results for tests conducted on each installed fiber. Data shall include power through loss meter test results.

1) Test results shall be bound in a single binder titled "Fiber Optic Cable Distribution Performance Measurements".

2) In addition to the data sheets for each fiber test, the data shall be organized in tables with the fiber identifier on the left hand column and columns for average loss, measured link length, and link loss.

Construction & Environmental Review

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-2

Sensitive But Unclassified – SBU

FBOP TECHNICAL DESIGN GUIDELINES

1.4 REFERENCES AND/OR CODES

A. National Electrical Code

B. TIA/EIA 568-D

1.5 SYSTEM DESCRIPTION

A. A site-wide fiber optic cable system shall be furnished and installed to support the following systems or functions:

1. Security Electronics Local Area Networks

2. Security Electronics Perimeter Security System (USP only)

3. Security Electronics DV Distribution System

4. Security Electronics Master Antenna Television System

5. Security Electronics Radio Backbone

6. Security Electronics Fire Alarm System

1.6 DEFINITIONS

A. Reference specification section 28 50 00 – Security Electronics General Provisions.

1.7 QUALITY ASSURANCE

A. Reference specification section 28 50 00 – Security Electronics General Provisions.

1.8 WARRANTY

A. Provide Guarantee, Maintenance and Service as described in specification section 28 50 60 – Security Electronics Guarantee, Maintenance, and Service.

PART 2 - PRODUCTS

2.1 FIBER CABLE

A. All Cables:

1. All of the fiber optic cable shall conform to the following specifications as a minimum:

a. Fiber Type: Single-Mode

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-3

Sensitive But Unclassified – SBU

b. Core Diameter: 9 microns

c. Cladding Diameter: 125 microns

d. Proof Test: 100 kpsi (Minimum)

e. Maximum Attenuation

@ 1310 nm: 0.5 dB/km @ 1550 nm: 0.5 dB/km

f. 10 Gigabit Ethernet Distance:

@ 1300 nm: 10 km

g. Minimum Bend Radius During Installation: 20 X Cable O.D.

Long-Term: 10 X Cable O.D.

h. Operating Temperature: -40 C to +70 C

i. Storage Temperature: -40 C to +70 C

j. Shall be a listed indoor/outdoor cable.

2. All loose tube optical cables shall conform to the following specifications as a minimum:

a. Jacket: Indoor/Outdoor UV and moisture resistant polyethylene.

b. Jacket thickness: 1.4 mm (nominal)

c. Synthetic yarn: Torque balanced contra helical aramid yarn around the cable core.

d. Core: Dry with a water absorbent tape applied between the core and synthetic yarn.

e. Central strength member: Dielectric epoxy glass rod.

f. Buffer coating Polymer loose tubes with gel filling

g. Buffer diameter: 250 +/- 15 microns

h. Crush resistance: 250 N/cm min.

i. Minimum tensile strength:

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-4

Sensitive But Unclassified – SBU

During Installation Long-Term 2,500N 850N

3. All tight buffered optical cables shall conform to the following specifications as a minimum:

a. Jacket: Indoor/Outdoor PVC jacket

b. Jacket thickness: Between 1.0 mm and 0.75mm at any point in the cable

c. Synthetic yarn: Individually tensioned and held helically around the cable core.

d. Central strength member: Dielectric epoxy glass rod.

e. Primary buffer coating: Color coded UV cured acrylate buffer.

f. Primary buffer diameter: 250 +/- 15 microns

g. Secondary buffer coating: Tight buffer high performance

PVC.

h. Secondary buffer diameter: 900 microns

i. Crush Resistance: 1,800 N/cm

j. Minimum Tensile Strength:

Fiber Count During Installation Long Term 4 fiber or less 260 lbs (1150 N) 80 lbs (350 N) 5 to 6 fiber 305 lbs (1350 N) 90 lbs (400 N) 7 to 8 fiber 350 lbs (1550 N) 108 lbs (475 N) 10 to 15 fiber 395 lbs (1750 N) 124 lbs (550 N) 16 to 23 fiber 460 lbs (2050 N) 150 lbs (650 N) 24 to 47 fiber 665 lbs (2950 N) 215 lbs (950 N) 48 and greater 935 lbs (4150 N) 305 lbs (1350 N)

B. Outdoor Cables:

1. The cables shall be rated for buried exterior use and shall meet the requirements of TIA/EIA-455-82B.

2. The cables outside diameter shall be:

a. 24 fibers or less 9.0 mm or less

3. Cable shall be Optical Cable DX series tight buffer cable, General Cable Next Gen Brand loose tube cable or approved equal.

C. Interior Riser Cables:

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-5

Sensitive But Unclassified – SBU

1. The fiber optic cable shall be UL-listed riser-rated OFNR and shall meet NEC Article 770-179(B) for use in vertical runs in building riser shafts or from floor to floor.

2. The cables outside diameter shall be:

a. 24 fibers or less 9.0 mm or less

3. Cable shall be Optical Cable DX series tight buffer cable or approved equal.

2.2 PATCH CABLES

A. Flexible jumpers and patch cords utilized to extend optic signals from the LCT to the fiber optic transceivers and equipment. Cables shall be cut to length and factory terminated utilizing termination's compatible with the specified equipment. Cable shall be simplex or duplex zipcord type as required and shall include a high-performance tight-buffer coating on each optical fiber. Cable jacket shall be a flame-retardant flexible PVC that is OFNR rated and color coded per TIA-598-A.

B. All patch cables shall conform to the following specifications as a minimum:

1. Insertion Loss: Less than 0.3 dB

2. Cladding Diameter: 125 microns

3. Core Diameter: 9 microns

4. Min. Bend Radius: 1.18 in. (3 cm) long term

5. Min. Tensile Strength: 12 lbs (50 N) long term

6. Ferrule: Ceramic

7. Operating Temp: -20 deg C to +70 deg C. Jumpers and cords to be used in exterior enclosures shall be rated to minus 40 degrees C.

2.3 MISCELLANEOUS

A. Connectors shall have zirconia ceramic ferrules. The operating temperature shall be -20 deg C to +70 deg C. Connectors used in exterior enclosures shall be rated to minus 40 degrees C. Connector characteristics shall be compatible with cable characteristics listed in this section. The first choice of all connectors shall be "ST". Where equipment requires connectors other than "ST", provide written explanation and provide the proper connector and or patch cable to match the equipment, but yet standardizing as closely as possible on "ST" connectors. Provide written explanation at the time of product data submittals.

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-6

Sensitive But Unclassified – SBU

B. Fiber Adaptors installed in LCT’s to mate connectors pairs shall be "ST" type, zirconia ceramic type, compatible with connector characteristics listed in this section and manufactured by AT&T, Leviton Opticom, or approved equal.

C. Light Cable Terminals (LCT) shall be configured for termination of fiber optic cable with the use of bulk head "ST" couplers with ceramic zirconia ferrules. Each LCT's shall be equipped for the intended cable quantities and equipped with a lock keyed like the SCC cabinets.

1. The LCT's shall be rack mounted in the LAN Rack

2. The LCT’s for the perimeter security system PSE’s shall be wall mounted. (USP only)

3. The LCT’s for the fire alarm system shall be wall mounted. The units shall be located adjacent to the fire alarm panel.

D. Innerduct shall be corrugated and have an outside diameter of less than

1.35 inches and an inside diameter of greater than 0.99 inches. Innerduct shall be non-metallic flexible raceway for use as an innerduct, Optic- Gard/PE Corrugated or approved equal.

PART 3 - EXECUTION

3.1 PREPARATION

A. Trunk Fiber

1. Building LCT to Building LCT:

a. Provide fiber strands in accordance with Table 285120 -2.

b. See the Riser Diagrams for additional information.

2. PSE LCT to PSE LCT: (USP only)

a. Provide fiber strands in accordance with Table 285120 -2.

(USP only)

b. See the Riser Diagrams for additional information. (USP only)

3. FACP to FACP:

a. Provide fiber strands in accordance with Table 285120 -2.

b. See the Riser Diagrams for additional information.

B. Device fiber

1. LCT to device:

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-7

Sensitive But Unclassified – SBU

a. The SEC shall determine the quantity of fiber strands that are required in each fiber optic cable for the specific device (camera, intercom, etc.)

b. Each fiber optic cable shall include the required fiber strands plus an additional 50% of the required strands as spare fiber with a minimum of one (1) spare strand. The spare fiber strands shall not be used by the Contractor unless written permission is granted by the Contracting Officer.

3.2 INSTALLATION

A. All equipment to be located in outdoor enclosures shall be rated –40 deg F to 150 deg F.

B. All cable shall be factory tested on a reel basis for each cable shipped to the project site.

1. The attenuation in dB/km units shall be recorded for each fiber strand. Tests shall be conducted at 1310 nm and 1550 nm.

C. All fiber optic cable shall be inspected prior to installation.

D. Cable shall be installed in accordance with the fiber optic TIA/EIA 568 standards and with the manufacturer's recommended practices for field installation.

E. Splices used to connect loose tube fiber strands to the break out kits in the LCT shall have a loss of equal to or less than 0.25 dB. Regardless of break out kit, the loss for a connector shall not exceed 0.5 dB.

F. All cable shall be continuous between the terminals with no splicing.

G. All fiber strands shall be terminated with "ST" type connectors at the LCT bulkhead. Interface to Security Electronic Equipment shall be made at the LCT bulkhead connectors with patch cables.

H. Each LCT port that is used to terminate a strand of fiber shall be labeled with a nomenclature that indicates the location from which the fiber strand originated. The nomenclature shall include the originating LCT name as indicated on the Riser Diagrams and port number where the strand originated. Where fusion splices are required as indicated in the Riser Diagrams; the splices shall not be included in the nomenclature scheme.

I. Provide a minimum of 200 foot service loop in a man-hole for each fiber optic cable routed through the duct bank system.

J. At the fiber cable bundle entrance of each LCT, the cable jacket shall be labeled with a nomenclature that indicates the fiber cable bundle originating LCT. The nomenclature shall indicate the name of the originating LCT and the number of fiber strands included in the fiber cable bundle. The cable jacket shall also be labeled with a nomenclature

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-8

Sensitive But Unclassified – SBU indicating the intended use. Examples of such nomenclature would be:

CCTV, Security LAN, etc.

3.3 COMPLETION

A. General: Upon completion of the work, remove excess debris, materials, equipment, apparatus, tools and the like and leave the premises clean, neat and orderly.

B. Testing: The completed system shall be tested by the SEC prior to the acceptance test.

1. Each installed fiber cable shall be tested for power through loss to reflect the following:

a. Total end-to-end loss including connectors.

b. All tests shall be based at 1310 nm and 1550 nm.

c. End-to-end loss shall be measured from bulkhead-to-bulkhead to include cable splice jumper and connector losses. Cable loss, excluding connectors, shall not exceed

0.5 dB/km at 1310 nm and 0.5 dB/km at 1550 nm. Cable loss measurements shall be made in conformance with the fiber optic TIA/EIA 568-D standards and with the cable manufacturer's recommendations. Measurements shall be recorded on a per cable basis with loss measured for each strand.

3.4 TABLES

A. Installation shall conform to the following tables:

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-9

Sensitive But Unclassified – SBU

TABLE 28 51 20-1

LEGEND FOR LIGHT LOSS TABLE

CABLE

DESIGNATION Designation of the fiber optic cable. See Riser Diagrams for additional information.

CABLE LOSS

At 1550 nm (dB) Value identifies the allowable optical loss of the strands in the cable at 1550 nm. The value does not include connector losses.

Maximum LOSS At 1550 nm (dB) Value identifies the total allowable optical loss of the cable at 1550

nm. The value includes connector losses.

Remarks:

1. Remarks not used.

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-10

Sensitive But Unclassified – SBU

TABLE 28 51 20-1 USP

LIGHT LOSS TABLE

CABLE MAX

CABLE LOSS CONNECTOR LOSS

DESIGNATION at 1550nm (dB) LOSS (dB) at 1550nm (dB)

H1 0.10 1.0 1.10 H2 0.20 1.0 1.20 H3 0.20 1.0 1.20 H4 0.50 1.0 1.50 H5 0.50 1.0 1.50 H6 0.40 1.0 1.40

RE 0.40 1.0 1.40

UF 0.40 1.0 1.40

UF1 0.05 1.0 1.05

EM 0.25 1.0 1.25

GT2 0.20 1.0 1.20

AI 0.15 1.0 1.15

AO1 0.05 1.0 1.05

ITS 0.05 1.0 1.05

MS 0.20 1.0 1.20

SH 0.15 1.0 1.15

CH 0.40 1.0 1.40

CM 0.40 1.0 1.40

CM1 0.40 1.0 1.40

UP 0.45 1.0 1.45

OW 0.50 1.0 1.50

OW1 0.05 1.0 1.05

GL 0.55 1.0 1.55

SG 0.65 1.0 1.65

SG1 0.65 1.0 1.65

GT1 0.65 1.0 1.65

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-11

Sensitive But Unclassified – SBU

TABLE 28 51 20-1 USP (Continued)

LIGHT LOSS TABLE

CABLE MAX

CABLE LOSS CONNECTOR LOSS

DESIGNATION at 1550nm (dB) LOSS (dB) at 1550nm (dB)

AOH1 0.10 1.0 1.10

FRAO 0.40 1.0 1.40

CMFR 0.40 1.0 1.40

CHCM 0.20 1.0 1.20

MSCH 0.50 1.0 1.50

SHMS 0.20 1.0 1.20

SGSH 0.35 1.0 1.35

UPSG 0.30 1.0 1.30

OWUP 0.15 1.0 1.15

OWGL 0.25 1.0 1.25

UFGL 0.30 1.0 1.30

H6UF 0.15 1.0 1.15

H5H6 0.15 1.0 1.15 H4H5 0.15 1.0 1.15

EMH4 0.30 1.0 1.30

H3EM 0.25 1.0 1.25

H2H3 0.15 1.0 1.15 H1H2 0.20 1.0 1.20

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-12

Sensitive But Unclassified – SBU

TABLE 28 51 20-1 USP (Continued)

LIGHT LOSS TABLE

CABLE MAX

CABLE LOSS CONNECTOR LOSS

DESIGNATION at 1550nm (dB) LOSS (dB) at 1550nm (dB)

2.3 0.05 1.0 1.05

3.4 0.05 1.0 1.05

4.5 0.05 1.0 1.05

5.6 0.05 1.0 1.05

6.7 0.05 1.0 1.05

7.8 0.05 1.0 1.05

8.9 0.05 1.0 1.05

9.10 0.05 1.0 1.05

10.11 0.05 1.0 1.05

11.12 0.05 1.0 1.05

12.13 0.05 1.0 1.05

13.14 0.05 1.0 1.05

14.15 0.05 1.0 1.05

15.16 0.05 1.0 1.05

16.17 0.05 1.0 1.05

17.18 0.05 1.0 1.05

18.19 0.05 1.0 1.05

19.20 0.05 1.0 1.05

20.21 0.05 1.0 1.05

AO.21 0.05 1.0 1.05

AO.22 0.05 1.0 1.05

22.23 0.05 1.0 1.05

23.24 0.05 1.0 1.05

24.25 0.05 1.0 1.05

25.26 0.05 1.0 1.05

26.27 0.05 1.0 1.05

27.28 0.05 1.0 1.05

28.29 0.05 1.0 1.05

2.29 0.05 1.0 1.05

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-13

Sensitive But Unclassified – SBU

TABLE 28 51 20-1 FCI

LIGHT LOSS TABLE

CABLE MAX

CABLE LOSS CONNECTOR LOSS

DESIGNATION at 1550nm (dB) LOSS (dB) at 1550nm (dB)

H1 0.25 1.0 1.25 H2 0.35 1.0 1.35 H3 0.40 1.0 1.40

SH 0.25 1.0 1.25

AI 0.10 1.0 1.10

AO1 0.05 1.0 1.05

ITS 0.05 1.0 1.05

EM 0.10 1.0 1.10

RE 0.20 1.0 1.20

UF 0.20 1.0 1.20

UF1 0.05 1.0 1.05

PS 0.35 1.0 1.35

MS 0.35 1.0 1.35

CH 0.40 1.0 1.40

CM 0.40 1.0 1.40

CM1 0.40 1.0 1.40

UP 0.45 1.0 1.45

OW 0.50 1.0 1.50

OW1 0.05 1.0 1.05

GL 0.55 1.0 1.55

SG 0.65 1.0 1.65

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-14

Sensitive But Unclassified – SBU

TABLE 28 51 20-1 FCI (Continued)

LIGHT LOSS TABLE

CABLE MAX

CABLE LOSS CONNECTOR LOSS

DESIGNATION at 1550nm (dB) LOSS (dB) at 1550nm (dB)

AOSH 0.20 1.0 1.20

FRAO 0.38 1.0 1.38

CMFR 0.37 1.0 1.37

CHCM 0.13 1.0 1.13

EMCH 0.44 1.0 1.44

PSEM 0.35 1.0 1.35

SGPS 0.28 1.0 1.28

UPSG 0.19 1.0 1.19

OWUP 0.17 1.0 1.17

GLOW 0.25 1.0 1.25

H3GL 0.26 1.0 1.26

H2H3 0.16 1.0 1.16 H1H2 0.16 1.0 1.16

SHH1 0.16 1.0 1.16

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-15

Sensitive But Unclassified – SBU

TABLE 28 51 20-2

LEGEND FOR FIBER OPTIC CABLE ASSIGNMENTS TABLE

CABLE ID Designation of the fiber optic cable. See Riser Diagrams for additional information.

S-LAN Fiber Strands for Sentry LAN. See specification section 28 61 60 – Security Electronics DV Distribution System for additional information.

T-LAN Fiber Strands for TRULINCS LAN. See specification section 28 61 60

– Security Electronics DV Distribution System for additional information.

E-LAN Fiber Strands for Education LAN. See specification section 28 61 60

– Security Electronics DV Distribution System for additional information.

C-LAN Fiber Strands for Commissary LAN. See specification section 28 61 60 – Security Electronics DV Distribution System for additional information.

U-LAN Fiber Strands for UNICOR LAN. See specification section 28 61 60 – Security Electronics DV Distribution System for additional information.

D-LAN Fiber Strands for Staff Digital Telephone LAN. See specification section 28 61 60 – Security Electronics DV Distribution System for additional information.

RADIO Fiber Strands for the Radio Backbone. See specification section 28 67 50 – Security Electronics Radio Backbone for additional information.

SPARE Fiber Strands for use by FBOP only. These fiber strands may not be used by Contractor unless approved in writing by Contracting Officer.

SUBTOTAL This is a subtotal (sum) of all of the fiber strands shown on the left of the table.

OTHER The SEC shall determine the quantity of fiber strands that are required in each fiber optic cable for the other Security Electronics Systems such as:

1. Security Electronics Local Area Networks specified in Section 28 51 20 - Security Electronics Local Area Networks

2. Security Electronics Perimeter Security System – Tautwire and NLL specified in Section 28 54 50 - Security Electronics Perimeter Security System – Tautwire and NLL. (USP only)

3. Security Electronics Master Antenna Television System specified in Section 28 67 00 - Security Electronics Master Antenna Television System.

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-16

Sensitive But Unclassified – SBU

4. Security Electronics Fire Alarm System specified in Section 28 71 90 - Security Electronics Fire Alarm System.

Remarks:

1. Each of the fiber cables shall include the total number of fiber strands shown.

For example, cable H1 shall include a minimum of 24 strands plus the strands required for “Other”.

2. TBD shall mean “To Be Determined”.

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-17

Sensitive But Unclassified – SBU

TABLE 28 51 20-2 USP

FIBER OPTIC CABLE ASSIGNMENTS

CABLE SUB

ID S-LAN T-LAN E-LAN C-LAN U-LAN D-LAN RADIO SPARE TOTAL OTHER

H1 4 4 0 0 0 4 0 12 24 TBD

H2 4 4 0 0 0 4 0 12 24 TBD

H3 4 4 0 0 0 4 0 12 24 TBD

H4 4 4 0 0 0 4 0 12 24 TBD

H5 4 4 0 0 0 4 0 12 24 TBD

H6 4 4 0 0 0 4 0 12 24 TBD

RE 4 4 0 0 0 4 0 12 24 TBD

UF 4 0 0 0 16 0 0 12 32 TBD

UF1 0 0 0 0 16 0 0 12 28 TBD

EM 4 4 4 0 0 4 0 12 28 TBD

GT2 4 0 0 0 0 4 0 12 20 TBD

AI 4 0 0 0 0 4 0 12 20 TBD

AO1 80 0 0 0 0 52 0 12 144 TBD

ITS 0 48 0 22 0 0 0 12 88 TBD

MS 4 4 0 12 0 4 0 12 36 TBD

SH 4 4 0 0 0 0 0 12 20 TBD

CH 4 4 0 0 0 0 0 12 20 TBD

CM 0 0 0 0 0 0 0 12 12 TBD

CM1 4 4 4 6 0 4 0 12 34 TBD

UP 4 0 0 0 0 0 24 12 40 TBD

OW 4 0 0 4 8 0 0 12 28 TBD

OW1 0 0 0 0 8 0 0 12 20 TBD

GL 4 0 0 0 0 0 0 12 16 TBD

SG 4 0 0 0 0 0 0 12 16 TBD

SG1 0 0 0 0 0 0 0 12 12 TBD

GT1 4 0 0 0 0 4 0 12 20 TBD

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-18

Sensitive But Unclassified – SBU

TABLE 28 51 20-2 USP (Continued)

FIBER OPTIC CABLE ASSIGNMENTS

CABLE SUB

ID S-LAN T-LAN E-LAN C-LAN U-LAN D-LAN RADIO SPARE TOTAL OTHER

AOH1 0 0 0 0 0 0 0 4 4 TBD

FRAO 0 0 0 0 0 0 0 4 4 TBD

CMFR 0 0 0 0 0 0 0 4 4 TBD

CHCM 0 0 0 0 0 0 0 4 4 TBD

MSCH 0 0 0 0 0 0 0 4 4 TBD

SHMS 0 0 0 0 0 0 0 4 4 TBD

SGSH 0 0 0 0 0 0 0 4 4 TBD

UPSG 0 0 0 0 0 0 0 4 4 TBD

OWUP 0 0 0 0 0 0 0 4 4 TBD

OWGL 0 0 0 0 0 0 0 4 4 TBD

UFGL 0 0 0 0 0 0 0 4 4 TBD

H6UF 0 0 0 0 0 0 0 4 4 TBD

H5H6 0 0 0 0 0 0 0 4 4 TBD

H4H5 0 0 0 0 0 0 0 4 4 TBD

EMH4 0 0 0 0 0 0 0 4 4 TBD

H3EM 0 0 0 0 0 0 0 4 4 TBD

H2H3 0 0 0 0 0 0 0 4 4 TBD

H1H2 0 0 0 0 0 0 0 4 4 TBD

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-19

Sensitive But Unclassified – SBU

TABLE 28 51 20-2 USP (Continued)

FIBER OPTIC CABLE ASSIGNMENTS

CABLE SUB

ID S-LAN T-LAN E-LAN C-LAN U-LAN D-LAN RADIO SPARE TOTAL OTHER

2.3 0 0 0 0 0 0 0 4 4 TBD

3.4 0 0 0 0 0 0 0 4 4 TBD

4.5 0 0 0 0 0 0 0 4 4 TBD

5.6 0 0 0 0 0 0 0 4 4 TBD

6.7 0 0 0 0 0 0 0 4 4 TBD

7.8 0 0 0 0 0 0 0 4 4 TBD

8.9 0 0 0 0 0 0 0 4 4 TBD

9.10 0 0 0 0 0 0 0 4 4 TBD

10.11 0 0 0 0 0 0 0 4 4 TBD

11.12 0 0 0 0 0 0 0 4 4 TBD

12.13 0 0 0 0 0 0 0 4 4 TBD

13.14 0 0 0 0 0 0 0 4 4 TBD

14.15 0 0 0 0 0 0 0 4 4 TBD

15.16 0 0 0 0 0 0 0 4 4 TBD

16.17 0 0 0 0 0 0 0 4 4 TBD

17.18 0 0 0 0 0 0 0 4 4 TBD

18.19 0 0 0 0 0 0 0 4 4 TBD

19.20 0 0 0 0 0 0 0 4 4 TBD

20.21 0 0 0 0 0 0 0 4 4 TBD

AO.21 0 0 0 0 0 0 0 4 4 TBD

AO.22 0 0 0 0 0 0 0 4 4 TBD

22.23 0 0 0 0 0 0 0 4 4 TBD

23.24 0 0 0 0 0 0 0 4 4 TBD

24.25 0 0 0 0 0 0 0 4 4 TBD

25.26 0 0 0 0 0 0 0 4 4 TBD

26.27 0 0 0 0 0 0 0 4 4 TBD

27.28 0 0 0 0 0 0 0 4 4 TBD

28.29 0 0 0 0 0 0 0 4 4 TBD

2.29 0 0 0 0 0 0 0 4 4 TBD

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-20

Sensitive But Unclassified – SBU

TABLE 28 51 20-2 FCI

FIBER OPTIC CABLE ASSIGNMENTS

CABLE SUB

ID S-LAN T-LAN E-LAN C-LAN U-LAN D-LAN RADIO SPARE TOTAL OTHER

H1 4 4 0 0 0 4 0 12 20 TBD

H2 4 4 0 0 0 4 0 12 20 TBD

H3 4 4 0 0 0 4 0 12 20 TBD

SH 4 4 0 0 0 0 0 12 20 TBD

AI 4 0 0 0 0 4 0 12 16 TBD

AO1 64 0 0 0 0 36 0 12 112 TBD

ITS 0 32 0 22 0 0 0 12 66 TBD

EM 4 4 4 0 0 4 0 12 24 TBD

RE 4 0 0 0 0 4 0 12 16 TBD

UF 4 0 0 0 16 0 0 12 32 TBD

UF1 0 0 0 0 16 0 0 12 28 TBD

PS 4 4 0 12 0 4 0 12 32 TBD

MS 4 0 0 0 0 4 0 12 16 TBD

CH 4 4 0 0 0 0 0 12 20 TBD

CM 0 0 0 0 0 0 0 12 12 TBD

CM1 4 4 4 6 0 4 0 12 30 TBD

UP 4 0 0 0 0 0 24 12 40 TBD

OW 4 0 0 4 8 0 0 12 28 TBD

OW1 0 0 0 0 8 0 0 12 20 TBD

GL 4 0 0 0 0 0 0 12 16 TBD

SG 4 0 0 0 0 0 0 12 16 TBD

SECURITY ELECTRONICS FIBER OPTIC CABLE SYSTEM 28 51 20-21

Sensitive But Unclassified – SBU

TABLE 28 51 20-2 FCI (Continued)

FIBER OPTIC CABLE ASSIGNMENTS

CABLE SUB

ID S-LAN T-LAN E-LAN C-LAN U-LAN D-LAN RADIO SPARE TOTAL OTHER

AOSH 0 0 0 0 0 0 0 4 4 TBD

FRAO 0 0 0 0 0 0 0 4 4 TBD

CMFR 0 0 0 0 0 0 0 4 4 TBD

CHCM 0 0 0 0 0 0 0 4 4 TBD

EMCH 0 0 0 0 0 0 0 4 4 TBD

PSEM 0 0 0 0 0 0 0 4 4 TBD

SGPS 0 0 0 0 0 0 0 4 4 TBD

UPSG 0 0 0 0 0 0 0 4 4 TBD

OWUP 0 0 0 0 0 0 0 4 4 TBD

GLOW 0 0 0 0 0 0 0 4 4 TBD

H3GL 0 0 0 0 0 0 0 4 4 TBD

H2H3 0 0 0 0 0 0 0 4 4 TBD

H1H2 0 0 0 0 0 0 0 4 4 TBD

SHH1 0 0 0 0 0 0 0 4 4 TBD

END OF SECTION 28 51 20