IHS Mescalero Service Unit Renovation & Addition Project No.: 117043
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 1
SECTION 270001 – INSTALLATION OF DATA & VOICE CABLE INFRASTRUCTURE
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. 270526 - Grounding and Bonding for Communication Systems.
B. 27 0528 – Pathways for Communication Systems.
C. 27 0536 – Cable Trays for Communication Systems.
D. 27 0553 – Identification for Communications Systems.
E. 27 1100 – Communication Equipment Room Fittings.
F. 27 1500 – Communications Horizontal Cabling.
G. Construction Drawings SP-1, SP-2, and E-10 “Enlarged Plan of MDR (IT)”
1.2 SERVICES
A. The Contractor of this work shall provide all material, equipment, labor, tools, to install, test, and certify a new cabling infrastructure, consisting of Category 6 cabling, for the Mescalero Service Unit Expansion and Renovation Project (IHS # HSSI161201200003I
/ HHSI16109026T)
1.3 LOCATION OF WORK:
A. The work is to be performed at Indian Health Service –Mescalero Service Unit, located at 318 Abalone Loop, Mescalero, NM 88340.
1.4 DEFINITIONS
A. IDR: Intermediate Distribution Room
B. MDR: Main Distribution Room.
1.5 TECHNICAL REQUIREMENTS
A. The contractor shall meet the technical requirements and possess the required experience and certified personnel as follows:
1. Provide, at a minimum, 5-year experience, as installers of category 6 cabling of the proposed manufacturer so that all applicable warranties and agreements are
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 2
valid. Have an R.C.D.D (Registered Communication Distribution Designer) with 5-year experience on staff to supervise the technicians in the installation, termination, and testing by technicians performing the work.
2. Have equipment and personnel to provide reports and drawings as required in this work within 30 calendar days after completion of work at the Mescalero Service Unit.
3. Have all associated resources available to complete all work required within 180 calendar days from Notice to Proceed from the Contracting Officer.
B. REFERENCES
1. ANSI/TIA/EIA-568B Commercial Building Telecommunications Cable Standards.
2. ANSI/EIA/TIA (American National Standards Institute/Electronic Industries Association/Telecommunications Industries Association).
3. NECA/FOA (National Electrical Contractors Association/Fiber Optic Association) Standards.
C. OTHER:
1. A pre-construction meeting shall be required on location prior to the start of any work for site review, coordination purposes, as well as introduction of all concerned parties.
2. The Contractor shall provide a detailed written schedule for work at each location at the pre-construction meeting.
D. WARRANTY.
1. 5 years.
E. QUALITY ASSURANCE
1. Contractors Quality Requirements.
a. All category 6 cable plant installed shall be tested and certified. All certification tests must meet Industry Standard ANSI/EIA/TIA-568B.
PART 2 - PROJECT DESCRIPTION
1. The purpose of this project is to install la new cable infrastructure for the new building expansion and renovation at the Mescalero Service Unit. New cable infrastructure shall consist of category 6 cable. Implementation will commence no later than 30 days upon Notice to Proceed from Contracting Officer.
2. The contractor shall perform on-site visual assessments, review all provided floor plans and spreadsheets, and perform any other services as needed to fully and thoroughly acquaint themselves with this project.
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 3
3. The contractor shall consult with the Owner’s Project Manager, Engineer, and other designated personnel to ascertain and confirm requirements and to review progress during all phases of work performed.
PART 3 - SERVICES TO BE PROVIDED BY THE CONTRACTOR:
Provide, install, terminate, and test new Category 6 cable to all designated locations from IDR and between IDR and MDR.
Provide and install 3 new, post aluminum racks in new first floor IDF in designated locations for data, fax, and voice category cable terminations.
Retain "Qualification Data" Paragraph below if source quality-control tests are required to be certified by a professional engineer. Coordinate with qualification requirements in Section 014000 "Quality Requirements."
PART 4 - PRODUCTS.
A. Contractor supplied and installed materials:
Items to be considered in this project (*):
Parts Required Quantity Type
7’ Aluminum, 19”, Post Rack with mounting hardware
3 each Chatsworth Standard Aluminum Rack, Black
Ladder Rack and mounting hardware
As Required Chatsworth, Black
Horizontal Cable Management, enclosed 2U
As Required Chatsworth or Belkin
Vertical Cable Management, enclosed, 6’ x 6”/8”
As Required Belden
Category 6 bulk cable – data, blue
1 Job (LOTS) Belden
Category 6 bulk cable – voice, white
1 Job (LOTS) Belden
Category 6 jumpers 5’, 10’, IDF
Need to get counting of each
Belden
Category 6 Station cables, 15’
Need to get counts Belden
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 4
Rack mount, 9 outlet, surge protector, power strip, 120V
2 APC or Belkin
(*) Constructor to confirm
PART 5 - EXECUTION
Intermediate Distribution Facility – First Floor RM 1187 and MDR IT room #118 .
Rack Installs:
Install 3 each, post, aluminum network racks and secure to floor with bolts.
Ladder cable tray shall be used to secure the top of each rack to wall.
Install vertical cable management between racks.
Install horizontal cable management (see diagram network/phone)
Install proper rack grounding to grounding bar.
Install 1 rack mount, 9 outlet, power strip to each rack.
Category 6 (Data/Voice)
All network cables shall be homerun to each identified location and terminate on network rack, patch panel.
All voice cables shall be homerun to each identified location and terminate on voice rack, patch panel.
All cable location installs shall be 2 data / 1 voice unless specified otherwise (see spreadsheet – Need to come up with floor plan showing locations and counts).
All patch panels and network jacks shall match cable specifications (CAT6)
All patch panels shall be secured to respective jacks and shall be 48 ports (24 port as required) and shall be rated for CAT6 cable.
All patch panels shall utilize cable management on back patch panel (dress
– cabling to cable management).
All cables shall be properly labeled and identified with machine generated labels.
All category cable shall be run above ceiling, in existing raceway. Where needed, J-hooks can be utilized and/or additional cable raceway.
270001 - 5
i. All identified new data/voice cable outlet locations shall be run within existing wall conduits.
j. Plenum rated Velcro straps shall be utilized to dress, bundle and secure all cables as needed. No plastic cable ties shall be utilized for this project.
k. Verify and/or complete proper grounding to all racks associated with this project.
l. Properly label all data and voice cables at patch panel and station side with machine generated labels as defined by site IT manager or designee.
m. Utilize coloring cable scheme for data (blue) and voice (white) with colored jacks to match.
n. Perform category installation and certification to meet or exceed ANSI/TIA/EIA-568B Commercial Building Telecommunications Cable Standards.
o. Provide and install UL listed fire caulking on any all penetrations made by the Contractor or their Sub-Contractors associated with this project. The UL listed fire caulking must meet the requirements for the respective wall type, such as firewall, smoke wall, etc.
p. Contractor is responsible for daily cleanup and disposal of waste in all areas worked.
q. Any questions or issues that come up with this project shall be reported, addressed, and approved by RFI System.
3. Category 6 – Fax Lines
a. All fax line cables shall be homerun from each identified location and terminate in Telco Room, (room # 1187).
b. All fax line cables in Telco Room 1187 shall be terminated on 66 phone block in designated location.
c. NECA/FOA (National Electrical Contractors Association/Fiber Optic Association) Standards All fax line cables shall be properly labeled and identified with machine generated labels.
PART 6 - FIELD QUALITY CONTROL
1. The Contractor shall provide all Cable Certification and Test Results on electronic media in pdf or WORD format, CD-R or Flash drive/disks, and a hard copy bound in a three-ring hard back notebook. The exterior of the disks and the notebook shall be labeled on both the spine and the cover to adequately define
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 6
the work, the work location, the Contractor’s name and contact information, and other information as may be required.
2. Contractor shall provide fiber As-build’s showing pathways.
3. Contractor shall supply all warranty information pertaining to all equipment, cable, parts, and installation.
4. Government Quality Assurance.
a. Inspection criteria
1) Visual Test and Certification results will be the criteria.
b. Acceptance Criteria
1) All category cable runs installed and tested must pass all Industry
Standards and Certifications according to ANSI/TIA/EIA-568B Commercial Building Telecommunications Cable Standards.
2) All equipment installed by Contractor must be in working order.
3) Visual appearance and cleanliness of all installations will be an important factor.
4) After first walkthrough Contractor will have 5 working days to address and correct any discrepancies.
5. Submit all reports, certification results, and warranty information to:
a. Indian Health Service; AAO – IMS; Attn: Bernie Jojola; 4101 Indian School Rd NE; Suite 225; Albuquerque; NM 87110.
B. QUALITY ASSURANCE:
1. Contractors Quality Requirements:
a. All category cable plants installed shall be tested and certified. All certification tests must meet Industry Standard ANSI/TIA/ EIA -568B.
DROPS MUST MEET 100% compliance.
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 7
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 8
Cat 6 count is reduced from 450 to 225 to include 3 % for future use.
TashaP Text Box
TashaP Text Box
INSTALLATION OF DATA AND VOICE CABLE INFRASTRUCTURE 270001 - 9
END OF SECTION