This is an electrical one-line diagram for an HVAC replacement and roof rehabilitation project at the Norwood Memorial Airport Air Traffic Control Tower (ATCT) facility. The drawing shows the complete electrical distribution system from the utility company connection through various panels and transformers across multiple levels of the facility (First Floor, Level C-1, C-2, and C-3, and Cab Floor/Roof).
The diagram details specific electrical specifications including a 75 KVA transformer, 208/120VAC 3-phase 4-wire systems, various circuit breakers and panels (including Main Distribution Panel, Equipment Room Panel, and multiple sub-panels), and detailed wire sizing specifications throughout the system. The scope of work is indicated by a cloud outline on the drawing, focusing on the portions related to the HVAC unit power connections. The drawing includes a comprehensive legend of electrical symbols and abbreviations, and was issued for construction on 08/22/2023 by the FAA Eastern Service Area Technical Operations division.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 6973GH-25-R-00007_Amd_0001.pdf | ||
| QandA Sheet 6973GH-25-R-00007.pdf | ||
| owd-23000102-m002.pdf | ||
| owd-23000102-g001.pdf | ||
| owd-23000102-c001.pdf | ||
| owd-23000102-e002.pdf | ||
| owd-23000102-m003.pdf | ||
| owd-23000102-m001.pdf | ||
| Contractors Release Form DOT F 4220.4.doc | DOC document | |
| Offeror Organizational Experience Form.pdf | ||
| 6973GH-25-R-00007.pdf | ||
| SF-25_PerformanceBond.pdf | ||
| SF-24_BidBond.pdf | ||
| Uniform Bipartisan Infrastructure Law Report.xlsx | XLSX spreadsheet | |
| SF-25A_PaymentBond.pdf | ||
| Wage Determination_MA20240001_Norfold County.pdf | ||
| SOW - OWD ATCT HVAC.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/2
/2
:3
:1
P
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
o w d -2
-e
.d w g
8 234567
H
G
F
E
D
C
A
B
TVSS
GEN
4 #1, 1 #8G
3 #4, 1 #10G
MAIN
DISTRIBUTION
PANEL 1
MDP
208/120VAC
3 PHASE, 4 WIRE
300A, MCB
12/24V DC, 3W
100A MCB
M
240 VAC, 30A
2 POLE, 3 WIRE
30A
7KW ENGINE
GENERATOR SET
240/120 VAC, 3 WIRE
2# 12, 1 #12G
2# 12 (DWG -E011, NOTE 10)
208/120VAC
3 PHASE, 4 WIRE
100A MCB
EQUIPMENT ROOM
PANEL
A
PANEL
C
PANEL
(DC)
FIRE
ALARM
PANEL
FACP
3 #1, 1#8G
4 #1, 1 #8G
2 #2, 1 #8G
3 #1, 1# 8G
4 #1, 1 # 8G
LEVEL C-3
CAB ROOF
AHU-1
STAIRWELL
PRESSURIZATION
FAN, SP-1
(240 VAC, 1 PHASE, 3 WIRE)
MOTOR
STARTER
3 #10 & 1# 10G
3 #10, 1 #10G
AUTOMATIC
TRANSFER SWITCH
DC
POWER
PANEL
DC
POWER
INVERTER
LEVEL C-2
SUB
PANEL
B
208/120VAC
3 PHASE, 4 WIRE
60A MCB
PANEL
B
208/120VAC
3 PHASE, 4 WIRE
MLO
PANEL
E
208/120VAC
3 PHASE, 4 WIRE
125A MCB
(BASE BLDG)
CAB FLOOR
208/120VAC
3 PHASE, 4 WIRE
90A MLO
(4) 3/0AWG, (1) #6AWG GND, 2"C
M
UTILITY COMPANY
2# 12 & 1 #12G
4 - 500 KCMIL, #1 2G
24 VDC, 2W
100A MCB
EQUIPMENT
ROOM SURGE
PROTECTOR
3 #10, 1 #10G
#1/0 GROUND ELECTRODE CONDUCTOR
75 KVA
TRANSFORMER
3 PHASE, 4 WIRE
208/120VAC SECONDARY
UTILITY COMPANY
METER LOCATED
ADJACENT TO TRANSFORMER
LEVEL C-1
FIRST FLOOR
(3) 1/0 AWG, (1) 6 AWG GND
(3) 1/0 AWG, (1)#6 AWG GND
IN 2" EMT
1UH-1
(3) #6 AWG, (1 ) #6 AWG GND IN 1" EMT
COMPRESSION FITTINGS ONLY
3P, 30A, 208V
DISCONNECT SWITCH
CAB STAIRWELL
10kW UNIT HEATER
DAYTON
MODEL 2YU71
ONE LINE, SCHEMATIC DIAGRAM SYMBOLS
DISCONNECT SWITCH
CONTACT, NORMALLY OPEN
CONTACT, NORMALLY CLOSED
METER
MOTOR
CURRENT TRANSFORMER
BUILDING GROUND
ELECTRICAL ABBREVIATIONS
M
AUTOMATIC TRANSFER SWITCH
M
POWER TRANSFORMER
XXXKVA, OWNED & MAINTAINED
BY LOCAL UTILITY
FUSED
DISCONNECT
SWITCH
CURRENT LIMITING
FUSE, SIZED AS
INDICATED
COMBINATION MAGNETIC
MOTOR STARTER &
DISCONNECT SWITCH
DISCONNECT SWITCH
MOLDED CASE THERMAL MAGNETIC
CIRCUIT BREAKER, POLES
AND SIZE AS INDICATED
FIRE ALARM RADIO
MASTER BOX
A A AMPERE
AC ALTERNATING CURRENT
AF AMPERE FRAME
B BCRP BACKUP
C CB CIRCUIT BREAKER
CKT CIRCUIT
C CONDUIT
D DC DIRECT CURRENT
DISC DISCONNECT
D PNL DISTRIBUTION PANEL
DT DOUBLE THROW
E EG ENGINE GENERATOR
F FSS FUSIBLE SAFETY SWITCH
FDR FEEDER
FLA FULL LOAD AMPERES
G GFM GROUND FAULT MONITOR
H HTR HEATER
K KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
M MDT MAIN DISTRIBUTION TERMINAL
MLO MAIN LUGS ONLY
MCB MAIN CIRCUIT BREAKER
N N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
P P POLE
PF POWER FACTER
PNL PANELBOARD
S ST SHUNT TRIP
SW SWITCH
V V VOLT, VOLTAGE
VA VOLT AMPERE
W W WATT
X XFMR TRANSFORMER
MISCELLANEOUS
O PHASE
OUTLET (120V/ 15A)
DISCONNECT, AND POWERED CONVENIENCE
POWER, UNIT MOUNTED NON-FUSED INTERNAL
ROOFTOP HVAC UNIT W/ THROUGH THE BASE
CLOUD INDICATES SCOPE OF WORK
E001
ONE LINE DIAGRAM
NOT TO SCALE
IS
S
U E
D F
O R
E D
M
08/22/2023
MGR: ENGINEERING CENTER
NORWOOD
OWD-23000102-E001
SP
SP
ATCT
HVAC REPLACEMENT AND ROOF REHAB PROJECT
ELECTRICAL ONE LINE DIAGRAM
o w d -2
-e
.d w g
OPS INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
C O
N S
T R
U C
T
IO
N
NORWOOD MEMORIAL AIRPORT
THIS DRAWING PRODUCED ON NEW ENGLAND REGION CAD SYSTEM
PROJECT ENGINEER
23000102
08/22/2023 CONSTRUCTION 23000102
MA
owd-23000102-e001
| 2023-08-22T18:49:20-0400 | |
| HENRY B NEWCOMB |
| 2023-08-22T15:57:43-0400 | |
| SHREY B PATEL |
File details come from the government source that posted it. Updated .