This document contains detailed architectural and engineering drawings, specifications, and details for the renovation of Building 3 at the Roseburg VA Medical Center. The project will seismically retrofit and renovate the existing building, including work on the roof, walls, windows, doors, curtain wall system, and interior spaces. Key details include the required construction of a new metal coping, parapet wall, roof membrane, scuppers, curtain wall system, interior walls, new window and door types, and finishes for spaces like locker rooms, restrooms, corridors, and offices. The drawings provide extensive specifications and details for the various building components and materials to be used. This is an Issued for Construction set of documents for the federal contract opportunity to renovate Building 3 at the Roseburg VA Medical Center.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTIC FLOOR
31' - 6"
SECOND FLR RCP
29' - 4"
METAL COPING ON CLEATS -
FASTEN INSIDE OF PARAPET
WALL ROTO METAL STUDS
AT 16" O.C.
POLYISO RIGID FOAM WALL CAP -
CUT TO FIT TIGHT IN COPING
1'
- 2
3/ 4"
WRAP ROOF MEMBRANE OVER
TOP OF WALL AND AVM
6" METAL STUD WALL
5/8" GYPSUM FIBER
SHEATHING
AIR VAPOR MEMBRANE OVER
GYPSUM FIBER UNDERLAYMENT -
PROVIDE 24" MIN LAP OVER
STRUCTURE PRIOR TO
INSTALLATION OF METAL STUD
WALLS - TUCK BETWEEN
CURTAIN WALL HEADER AND
METAL CHANNEL RUNNER
METAL ROOF DECK
6" TAPERED ROOF
INSULATION
TPO ROOF MEMBRANE ON 5/8"
GYPSUM FIBER COVER BOARD
CURTAIN WALL SYSTEM AS
SPECIFIED
METAL PANEL OVER LIQUID
APPPLIED AVM ON 5/8"
GYPSUM FIBER SHEATHING
6" 8 3
/4"2'
- 2
2"
9 1 /4"
5 1 /4"
4"
4"
8 3 /4"
ATTIC FLOOR
31' - 6"
SECOND FLR RCP
29' - 4"
Y 4"
8"
4"
ALUMINUM COPING
ON CLEATS
ALUMINUM PANEL
STIFFENER BY PANEL
MANUF
LIQUID APPLIED AIR
VAPOR MEMBRANE -
WRAP OVER TOP OF
WALL AND MIN 4"
DOWN FACE OF
SHEATHING OPP SIDE
3/4" PT PLYWOOD ON
METAL STUD WALL
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
R-25 BATT INSULATION
2" MIN RIGID EPS
INSULATION IN STUD
CAVITY
TPO ROOFING
MEMBRANE -WRAP
OVER TOP OF WALL
AND MIN 4" DOWN
FACE OF ALUMINUM
PANEL
2X PT WALL CAP AT TOP OF WALL -
MOUNT TO TOP OF METAL STUD WALL
CONT. VAPOR RETARDER -
WRAP SPLICE PIECE OVER
STEEL ANGLE PRIOR TO
INSTALLING STUD WALL
AND STEEL DECK
TPO ROOFING
MEMBRANE ON
COVER BOARD
OVER MIN 6"
ROOFING
INSULATION
GYPSUM GLASS FIBER
UNDERLAYMENT ON
STRUCTURAL DECK
4"
3" X 24" X 120" METAL
PANEL - TOP
1 1/2" X 24" X 120"
METAL PANEL - BOTT
2 1/4" X 24" X 120" METAL
PANEL - MIDDLE
BENT ALUM FLASHING
FINISHED TO MATCH BRICK
STARTER CLIP BY
PANEL MANUF.
LIQUID APPLIED AIR VAPOR
MEMBRANE - WRAP DOWN
OVER FLASHING LEG
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
FILL CAVITY WITH RIGID
EPS INSULATION
GYPSUM GLASS FIBER
UNDERLAYMENT ON
STRUCTURAL DECK
TPO ROOFING MEMBRANE
ON COVER BOARD OVER
MIN 6" ROOFING INSULATION
WRAP ROOF MEMBRANE OVER
TOP OF WALL
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
R-25 BATT INSULATION
2" MIN RIGID EPS
INSULATION IN STUD CAVITY
CONT. VAPOR
RETARDER - WRAP
SPLICE PIECE
OVER STEEL DECK
PRIOR TO
INSTALLING STUD
WALL AND
SHEATHING
4" NOM. STANDARD BRICK
VENEER - CUT TOP BRICK
TO FIT TIGHT TO BOTTOM
OF STEEL DECK - INFILL
RIBS WITH FOAM INSUL.
6" METAL STUD BOX
HEADER OVER DOOR
OPENING - 13/S524
STEEL ANGLE LINTEL BRG
EACH SIDE - SEE STRUCTURAL
4" STEEL DOOR HEADER -
SHIM AS REQUIRED
DOOR AS SCHEDULED
METAL 'J' MOLD AT BOTT OF
GWB
8"
VENEER ANCHORS -
SEE SPECS
5 1 /4"
8 3 /4"
8"
2'
- 2
8"
4"
5"
EXISTING WOOD ROOF
DECKING TO REMAIN
EXISTING TILE ROOFING TO REMAIN
ADD NEW METAL EDGE FLASHING
WHERE GUTTER IS REMOVED
BETWEEN NEW WALLS
PT WOOD HEADER AT TOP OF
EXISTING BRICK WALL
TOP TRIM PIECE TO REMAIN (OR
REMOVE AND REINSTALL) - SLOT
WHERE PERPENDICULAR WALL
INTERSECTS, LEAVE MIN 1" GAP -
REPAINT ALL EXPOSED WOOD
PT 2x BLOCKING TO HOLD
EXISTING TRIM PIECE IN PLACE -
TOENAIL TO HEADER
TPO ROOFING MEMBRANE -
LOOP INTO 1" GAP AND RUN
UP WALL
EXPANSION JOINT COVER - TUCK
BEHIND BLOCKING - SEAL TO
ROOFING MEMBRANE PER MANUF
REQUIREMENTS
METAL COPING BEYOND
5/8" COVER BOARD ON ROOFING
INSULATION
AVM ON 5/8" GYPSUM FIBER
UNDERLAYMENT
ATTIC FLOOR LEVEL
TOP OF CURTAIN WALL
LOWER PORTION OF FASCIA TO
BE REMOVED BETWEEN TWO
NEW WALLS - 4 PIECES INCL
GUTTER SUPPORT
1"
9" DIST BOLT TO WALL
WRAP PIECE OF TPO MEMBRANE
OVER TOP OF NEW WALL - ADHERE TO
PT WOOD AND TOP OF WALL - DO NOT
CONNECT TO COPING - LAP MIN 5"
SEISMIC JOINT FILLER AT
CURTAIN WALL BEYOND
METAL COPING ON CLEATS -
FASTEN INSIDE OF PARAPET WALL
TO METAL STUDS AT 16" O.C. - TRIM
AS REQUIRED AROUND SCUPPER
AND PROVIDE DRIP
POLYISO RIGID FOAM WALL CAP -
CUT TO FIT TIGHT IN COPING
WRAP ROOF MEMBRANE OVER
TOP OF WALL AND AVM
STAINLESS STEEL
SCUPPER - FIT BETWEEN
METAL STUDS
5/8" GYPSUM FIBER
SHEATHING
AIR VAPOR MEMBRANE OVER
GYPSUM FIBER UNDERLAYMENT -
PROVIDE 24" MIN LAP OVER
STRUCTURE PRIOR TO
INSTALLATION OF METAL STUD
WALLS - TUCK BETWEEN
CURTAIN WALL HEADER AND
METAL CHANNEL RUNNER
METAL ROOF DECK
6" TAPERED ROOF
INSULATION
TPO ROOF RUN THRU
SCUPPER AND INTO
DOWNSPOUT 4"
CURTAIN WALL
SYSTEM AS SPECIFIED
METAL PANEL OVER LIQUID
APPPLIED AVM ON 5/8"
GYPSUM FIBER SHEATHING
LAP TPO
ROOFING MIN 6"
AND SEAL PER
MANUFACTURES
REQUIREMENTS
LAP TPO
ROOFING MIN 6"
AND SEAL PER
MANUFACTURES
REQUIREMENTS
4"
8"
4"
METAL COPING
ON CLEATS
ALUMINUM PANEL
STIFFENER BY
PANEL MANUF
LIQUID APPLIED AIR
VAPOR MEMBRANE -
WRAP OVER TOP OF WALL
AND MIN 4" DOWN FACE
OF SHEATHING OPP SIDE
3/4" PT PLYWOOD ON
METAL STUD WALL
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
R-25 BATT INSULATION
2" MIN RIGID EPS
INSULATION IN STUD CAVITY
TPO ROOFING MEMBRANE -
WRAP OVER TOP OF WALL
AND MIN 4" DOWN FACE OF
ALUMINUM PANEL 2X PT WALL CAP AT
TOP OF WALL -
MOUNT TO TOP OF
METAL STUD WALL
CONT. VAPOR RETARDER -
WRAP SPLICE PIECE OVER
STEEL ANGLE PRIOR TO
INSTALLING STUD WALL
AND STEEL DECK
TPO ROOFING
MEMBRANE ON COVER
BOARD OVER MIN 6"
ROOFING INSULATION
GYPSUM GLASS FIBER
UNDERLAYMENT ON
STRUCTURAL DECK
3" X 24" X 120" METAL
PANEL - TOP
2 1/4" X 24" X 120" METAL
PANEL - MIDDLE
ALUMINUM SCUPPER
W/ POWDER COAT
1 1/2" X 24" X 120"
METAL PANEL - BOTT
BENT ALUM FLASHING
FINISHED TO MATCH BRICK
STARTER CLIP BY
PANEL MANUF.
LIQUID APPLIED AIR
VAPOR MEMBRANE -
WRAP DOWN OVER
FLASHING LEG
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
FILL CAVITY WITH RIGID
EPS INSULATION
GYPSUM GLASS FIBER
UNDERLAYMENT ON
STRUCTURAL DECK
TPO ROOFING MEMBRANE
ON COVER BOARD OVER
MIN 6" ROOFING INSULATION
WRAP ROOF MEMBRANE OVER
TOP OF WALL
GYPSUM GLASS FIBER
SHEATHING
6" METAL STUD WALL
R-25 BATT INSULATION
2" MIN RIGID EPS
INSULATION IN STUD CAVITY
CONT. VAPOR
RETARDER - WRAP
SPLICE PIECE
OVER STEEL DECK
PRIOR TO
INSTALLING STUD
WALL AND
SHEATHING
4" NOM. STANDARD BRICK
VENEER - CUT TOP BRICK
TO FIT TIGHT TO BOTTOM
OF STEEL DECK - INFILL
RIBS WITH FOAM INSUL.
6" METAL STUD BOX HEADER
OVER DOOR OPENING 13/S524
STEEL ANGLE LINTEL BRG
EACH SIDE - SEE STRUCT.
4" STEEL DOOR HEADER -
SHIM AS REQUIRED
VENEER ANCHORS - SEE SPECS
STAINLESS STEEL ELEVATOR
DOOR AN FRAME BY
ELEVATOR MANUFACTURER
ONCRETE METAL PAN
FLOOR DECK
SAND AND
REPAINT ALL
WOOD MEMBERS
AT EXTERIOR
FRAME INCLUDING
ALL TRIM PIECES -
PROTECT LOUVER
AND SCREEN
CAREFULLY
PROTECT
DORMER TRIM
PIECES BEFORE
REFINISHING
TYPICAL WORK AT ALL
DORMER OPENINGS
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:5
PM
A-502
ROOF DETAILS
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 KH LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
3" = 1'-0"C9 CURTAIN WALL PARAPET
3" = 1'-0"F3 WALL/ROOF JUNCTION AT STAIR TWR
3" = 1'-0"E8 NEW ROOF AT EXISTING WALL
3" = 1'-0"C5 SCUPPER AT CURTAIN WALL
3" = 1'-0"C1 SCUPPER AT STAIR TOWER
3" = 1'-0"F5 ELEVATOR DOOR HEAD/ SILL
12" = 1'-0"F1 TYPICAL DORMER REFINISHING
Revisions: Date:
BASEMENT RCP
8' - 0"
BASEMENT
0"
10.110
F3 A-503
5/8" TYPE 'X' GWB OVER
7/8" HORIZ. HAT CHANNELS
@ 16" O.C. VERT.
6" GUNNITE SEISMIC TREATMENT
EXISTING CONC
FOUNDATION WALL
SEE CIVIL/MECH FOR PIPE
REPAIR AND REPLACEMENT -
CLEAN FACE OF CONCRETE
FOUNDATION WALL - REMOVE
THRU WALL PIPES AND GROUT
HOLES SOLID.
INFILL EXG PIT WITH CONC.
1/2" PROTECTION BOARD ON
LIQUID APPLIED
WATERPROOFING MEMBRANE
ON FOUNDATION WALL
BACKFILL - SEE CIVIL
BASEMENT
0"
D.9 FE
F6 A-503
5/8" TYPE 'X' GWB OVER
7/8" HORIZ. HAT CHANNELS
@ 16" O.C. VERT.
6" GUNNITE SEISMIC TREATMENT
EXISTING CONC
FOUNDATION WALL
SEE CIVIL/MECH FOR
PIPE REPAIR AND
REPLACEMENT - CLEAN
FACE OF CONCRETE
FOUNDATION WALL -
REMOVE THRU WALL
PIPES AND GROUT
HOLES SOLID.
INFILL EXG PIT WITH CONC.
1/2" PROTECTION BOARD ON
LIQUID APPLIED
WATERPROOFING MEMBRANE
ON FOUNDATION WALL
BACKFILL - SEE CIVIL
D.9F E
C2 A-301
EXISTING CONC
FOUNDATION WALL
SEE CIVIL/MECH FOR PIPE
REPAIR AND REPLACEMENT -
CLEAN FACE OF CONCRETE
FOUNDATION WALL - REMOVE
THRU WALL PIPES AND GROUT
HOLES SOLID.
INFILL EXG PIT WITH CONC.
1/2" PROTECTION BOARD ON
LIQUID APPLIED
WATERPROOFING MEMBRANE
ON FOUNDATION WALL
BACKFILL - SEE CIVIL
BASEMENT
0"
F6 A-304
F3 A-304
XY
GALV STEEL PIT LADDER -
3"x3/8" STRINGERS WITH
3/4" DIAM STEEL RUNGS
AT 12" O.C. - COORD WITH
ELEVATOR INSTALLER
4'
- 0
2' - 0"
1' - 2"
ELEVATOR PIT
MOUNT LADDER TO METAL
STUD WALL WITH 6" LONG X
8"x4"x3/8" CLIP ANGLES AT
3'-0" O.C. VERT.
4'
- 0
PROVIDE OPENING WHERE
STEEL PENETRATES BRICK
WALL - CUT AND SET BRICK AS
CLOSE AS POSSIBLE TO STEEL -
FILL GAP WITH FIRE CAULK
CUT RIGID INSULATION TO
FIT TIGHT AROUND STEEL
PROVIDE BLOCKING IN MS WALL
TO FIT TIGHT AROUND STEEL -
FILL GAPS WITH FIRE CAULKING
STEEL CONNECTIONS NOT
SHOWN - SEE STRUCTURAL
CURTAIN WALL BEYOND
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:0
PM
A-503
MISC DETAILS
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 Checker Author
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
3/4" = 1'-0"F6 E-W SECTION AT PIT INFILL
3/4" = 1'-0"F3 N-S SECTION AT PIT INFILL
3/4" = 1'-0"F1 N-S SECTION AT PIT INFILL- LG
3/4" = 1'-0"F8 ELEVATOR PIT SECTION
1 1/2" = 1'-0"D9 BRICK PENETRATION AT CROSS BRACE
SECOND FLOOR
21' - 0"
FIRST FLR RCP
18' - 0"
FIRST FLOOR
10' - 0"
B.1 B
WINDOW HEAD
19' - 1 1/2"
HOLD SUSP. CEILING FROM WALL
1' - 4"
2' - 0"
PAINT CONC FLOOR DECK AND
ALL EXPOSED PIPING ABOVE
CEILING OPENING FLAT BLACK
2' PAST FACE OF WALL
INTERIOR GYP. BD. WALL ON 'Z'
FURRING STUDS - UP TO BOTT
OF FLOOR DECK BETWEEN
CONCRETE WEBS
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - SET TO PROTECT
EXISTING WINDOW AND TRIM PRIOR
TO SEISMIC GUNNITE TREATMENT
WOOD FRAMED PRIVACY PANEL -
ALIGN WITH TOP SASH OF
EXISTING WINDOW
CEILING CLOSURE ALONG END OF
SUSP. CEILNG BY CEILNG MANUF.
WOOD TRIM AT PERIMETER
OF PRIVACY PANEL
BULLNOSE AT TOP OF TILE WAINSCOT
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - PAINT INSIDE GLOSS
WHITE - SET TO PROTECT EXISTING
WINDOW AND TRIM PRIOR TO
SEISMIC GUNNITE TREATMENT
CERAMIC TILE WAINSCOT THINSET
ON TILE BACKER BOARD MOUNTED
TO PLYWOOD
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - PAINT INSIDE GLOSS
WHITE - SET TO PROTECT EXISTING
WINDOW AND TRIM PRIOR TO
SEISMIC GUNNITE TREATMENT
SEISMIC GUNNITE TREATMENT -
SEE STRUCTURAL
CERAMIC TILE WAINSCOT THINSET
ON TILE BACKER BOARD MOUNTED
ON 'Z' FURRING STUDS
SEISMIC GUNNITE TREATMENT -
STOP BELOW EXISTING WINDOW
TRIM - SEE STRUCTURAL
CONT METAL COVE TRIM AT WALL
TO FLOOR JOINT
6'
- 0
SE
E
TI
LE
P
AT
TE
RN
TOILET M
1A202
2'
- 1
0"
BASEMENT RCP
8' - 0"
BASEMENT
0"
FIRST FLOOR
10' - 0"
AB.1 B
INTERIOR GYP. BD. WALL ON
FURRING CHANNELS - UP TO
BOTT OF FLOOR DECK
BETWEEN CONCRETE WEBS
CEILING SOFFIT OVER SINKS
TILE UP TO BOTTOM OF SOFFIT
CERAMIC TILE WAINSCOT
THINSET ON TILE BACKER
BOARD ON 5/8" GYPSUM BOARD
SEISMIC STRONG BACK
FRAMING - SEE STRUCTURAL
SEISMIC GUNNITE TREATMENT -
STOP BELOW EXISTING WINDOW
TRIM - SEE STRUCTURAL
CONT METAL COVE TRIM AT WALL
TO FLOOR JOINT
4"
KNEE SPC
2'
- 9
1/ 4"
2'
- 4
3'
- 7
3/2
SEISMIC STRONG BACK
STRUCTURAL FRAMING - INFILL
WITH BATT INSULATION
EXISTING WINDOW AND
TRIM TO REMAIN
5/8" PLYWOOD - PAINTED GLOSS
WHITE - ATTACH TO BACK
FLANGE OF STUDS - SIZE TO
MATCH WIDTH AND HEIGHT OF
WINDOW OPENING, LEAVING 1/2"
GAP ALL AROUND FOR VENTING
6" METL STUD BLOCKING AS
REQUIRED AT PLYWOOD EDGES
INSULATE PIPES UNDER SINKS
EXISTING WALLS AND FLOOR
TO REMAIN SHOWN SHADED
GALV STEEL ANGLE BRACES
(3 1/2" x 3 1/2" x 3/8") AT 32" O.C.
MOUNTED TO STUDS IN WALL -
CUT TOP FLANGE AT GAP &
WHERE IT PASSES THRU WALL.
MOUNT SOLID SURFACE
COUNTER TO MARINE
PLYWOOD BASE, MOUNTED TO
STEEL ANGLES
TYPICAL WORK AT ALL
EXTERIOR WINDOWS
ALL EXISTING WOOD FRAMED WINDOWS
AND DORMER LOUVERS ARE TO BE
REFURBISHED. REFURBISHING OF
EXISTING WINDOWS AND DORMER
LOUVERS INCLUDES BUT IS NOT LIMITED
TO THE FOLLOWING:
1. REMOVE ALL NAILS, SCREWS AND
ANY OTHER FASTENERS NOT PART OF
ORIGINAL WINDOW OR OUVER DESIGN
2. REMOVE ALL TRIM, ANGLES,
AND/OR PLATES NOT PART OF ORIGINAL
WINDOW OR LOUVER DESIGN
3. REMOVE ALL WINDOW SCREENS
4. REMOVE AND REPLACE BROKEN
GLASS (WHERE OCCURS)
5. REMOVE LOOSE FLAKING PAINT ON
INTERIOR AND EXTERIOR BY HAND
SANDING
6. REMOVE FILMS ON INTERIOR SIDE
OF GLASS (TOILET ROOM WINDOWS)
7. FILL VOIDS, HOLES IN WOOD
WINDOW AND DORMER LOUVER FRAME
AND TRIM AS REQUIRED TO RECEIVE
NEW PAINT.
8. PRIME AND RE-PAINT WINDOW AND
DORMER LOUVER FRAME, MUNTINS AND
TRIMS.
9. PRIME AND RE-PAINT WINDOW
SCREEN FRAME
10. REPLACE TORN AND/OR DAMAGED
SCREN FABRIC
11. CLEAN EXISTING LOUVER SCREENS
AND LOUVER BLADES INSIDE AND OUT
12. TEST FOR PROPER WINDOW
OPERATION INCLUDING LOCKING
MECHANISM
13. REPAIR WINDOW SASH/LOCKING
MECHANISM AS REQUIRED
14. CLEAN EXISTING GLASS INSIDE AND
OUTSIDE
NOTE: WINDOWS WERE REFURBISHED
USING THE SAME PROCESS IN 2013, AND
LEAD PAINT WAS ABATED AT THAT TIME,
ACCORDING TO THE 9/5/2012 DESIGN
DRAWINGS.
BASEMENT RCP
8' - 0"
BASEMENT
0"
FIRST FLOOR
10' - 0"
AB.1 B Z
PAINT CONC FLOOR DECK AND ALL
EXPOSED PIPING ABOVE CEILING
OPENING SEMIGLOSS WHITE
INTERIOR GYP. BD. WALL ON 'Z'
FURRING STUDS - UP TO BOTT
OF FLOOR DECK BETWEEN
CONCRETE WEBS
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - SET TO PROTECT
EXISTING WINDOW AND TRIM PRIOR
TO SEISMIC GUNNITE TREATMENT
WOOD FRAMED PRIVACY
PANEL - ALIGN WITH TOP
SASH OF EXISTING WINDOW
AND TOP OF LOCKERS
WOOD TRIM AT PERIMETER
OF PRIVACY PANEL
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - PAINT INSIDE GLOSS
WHITE - SET TO PROTECT
EXISTING WINDOW AND TRIM
PRIOR TO SEISMIC GUNNITE
TREATMENT
METAL LOCKERS - FASTEN TO WALL
BUILD 3/4" PLYWOOD ON METAL
STUD BOX - PAINT INSIDE
GLOSS WHITE - SET TO
PROTECT EXISTING WINDOW
AND TRIM PRIOR TO SEISMIC
GUNNITE TREATMENT
SEISMIC GUNNITE TREATMENT -
SEE STRUCTURAL
5/8" MR GYPSUM BOARD MOUNTED
ON 'Z' FURRING STUDS
SEISMIC GUNNITE TREATMENT -
STOP BELOW EXISTING WINDOW
TRIM - SEE STRUCTURAL
CONT CONCRETE LOCKER BASE
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:0
PM
A-504
MISC DETAILS
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 Checker LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
1 1/2" = 1'-0"F8 TOILET ROOM WINDOW INFILL
1 1/2" = 1'-0"F5 WINDOW INFILL AT BASEMENT
12" = 1'-0"E5 TYPICAL WINDOW REFINISHING
1 1/2" = 1'-0"F1 WINDOW SECTION AT LOCKERS
NOTES
FINISH MATERIALS SUCH AS CERAMIC TILE,
WALL COVERINGS, ETC. ARE NOT TYPICALLY
SHOWN AS AN INTEGRAL PART OF THE
ASSEMBLY. REFER TO INTERIOR DRAWINGS
AND / OR FINISH SCHEDULES FOR FINISH
MATERIALS.
PARTITIONS EXTENDING TO DECK ABOVE ARE
INDICATED ON RCP'S.
ALL PENETRATIONS THROUGH ACOUSTICAL
ASSEMBLIES TO BE ACOUSTICALLY SEALED.
FIRE BLOCKING WILL BE INSTALLED IN
ACCORDANCE WITH IBC 717.2, HORIZONTALLY
AT INTERVALS NOT EXCEEDING 10 FEET
1.
2.
3.
4.
A2 WALL TYPE
2-HR/STC 53 - UL-U419
(2) LAYERS STAGGERED 5/8" TYPE 'X'
GWB - FULL HEIGHT TO DECK ABOVE
20 GA METAL STUDS @ 16" O.C. 3
5/8" OR AS REQUIRED TO ALIGN
WITH EXISTING WALL THICKNESS -
FULL HEIGHT TO DECK ABOVE
A1 WALL TYPE
NOT RATED
5/8" TYPE 'X' GWB
[5/8" CEMENT BOARD
AT A1t]
3-5/8" STUDS @16" O.C. HT
AS INDICATED - MIN 6"
ABOVE CEILING GRID
HEIGHT
INTERIOR WALL TYPES
R-11 UNFACED,
FORMALDEHYDE FREE, BATT
INSULATION BETWEEN STUDS
5/8" TYPE 'X' GWB
[5/8" CEMENT
BOARD AT A1t]
SEAL ALL PENETRATIONS WITH
FIRE SEALANT
C1 WALL TYPE
NOT RATED
7/8" HAT CHANNELS @16"
O.C. (VERT OR HORIZ)
5/8" TYPE 'X' GWB
A3 WALL TYPE
STC-53
(2) LAYERS STAGGERED 5/8" TYPE
'X' GWB - DOUBLE LAYER ON
SAME SIDE AS WALL TAG
5/8" TYPE 'X' GWB
20 GA METAL STUDS @ 16" O.C. 3 5/8"
(A3) OR 6" (A6) AS SPECIFIED (ALIGN
WITH EXISTING WALL THICKNESS
WHERE NOTED)
R-11 UNFACED,
FORMALDEHYDE FREE, BATT
INSULATION BETWEEN STUDS
SEAL ALL PENETRATIONS WITH
ACOUSTICAL SEALANT
C3 WALL TYPE
NOT RATED
5/8" TYPE 'X' GWB
EXG WALL
NOT RATED
SHADING INDICATES
EXISTING WALLS TO
REMAIN - WIDTH
VARIES - NOT TAGGED
PATCH HOLES AND
REPAIR DRYWALL
SURFACE AS
REQUIRED AND
REPAINT ENTIRE WALL
BOTH SIDES
A6 SIMILAR - 6" STUDS
3-5/8" STUDS @16" O.C. -
MIN 6" ABOVE CEILING
GRID HEIGHT
C2 WALL TYPE
NOT RATED
1 1/2" 'Z' STUDS @16" O.C.
5/8" TYPE 'X' GWB
E1 WALL TYPE
NOT RATED
STRONGBACK METAL
STUD WALL - SEE
STRUCTURAL - FILL
CAVITY WITH R26 BATT
INSULATION
(2) LAYERS 5/8" TYPE
'X' GWB
E2 WALL TYPE
NOT RATED
1 1/2" 'Z' FURRING @16"
O.C. (VERT OR HORIZ)
5/8" TYPE 'X' GWB
6" SHOTCRETE AT
SEISMICALLY
REPAIRED WALLE1s = 3 5/8" MS WITH
(1) LAYER GWB
1 1/2" MINERAL WOOL
RIGID INSULATION - AT
EXTERIOR WALLS
WHERE OCCURS
C4 WALL TYPE
NOT RATED
(2) LAYERS 5/8" TYPE
'X' GWB
3-5/8" STUDS @16" O.C. -
MIN 6" ABOVE CEILING
GRID HEIGHT
C5 WALL TYPE
1-HOUR UL 1504
5/8" TYPE 'X' GWB
4" CH STUDS @16" O.C. -
TO BOTT. OF DECK ABOVE
1" TYPE 'X' GWB
[20 GA, 4" METAL STUDS @ 16" O.C.
WITH BRICK VENEER AT A24]
A5 WALL TYPE
2-HR/STC 53 - UL-U419
(2) LAYERS STAGGERED 5/8"
TYPE 'X' GWB - FULL HEIGHT
TO DECK ABOVE
20 GA METAL STUDS @ 16"
O.C. - 3 5/8" - FULL HEIGHT
TO DECK ABOVE
R-11 UNFACED,
FORMALDEHYDE FREE, BATT
INSULATION BETWEEN STUDS
SEAL ALL PENETRATIONS WITH
FIRE SEALANT
C6 WALL TYPE
NOT RATED
5/8" CEMENT BOARD
TILE BACKER
3-5/8" STUDS @16" O.C. -
FULL HEIGHT TO DECK
ABOVE
1 1/2" MINERAL WOOL
RIGID INSULATION - AT
EXTERIOR WALLS
WHERE OCCURS
A1t SIMILAR A7 WALL TYPE
NOT RATED
5/8" CEMENT BOARD -
(SAME SIDE AS TILE
FINISH)
3-5/8" STUDS @16"
O.C. HT AS
INDICATED - MIN 6"
ABOVE CEILING GRID
HEIGHT
5/8" TYPE 'X' GWB
A8 WALL TYPE
1-HOUR UL 1504
(2) LAYERS 5/8" TYPE
'X' GWB
5" CH STUDS @16"
O.C. - TO BOTT. OF
ROOF DECK
1" TYPE 'X' GWB
BRICK VENEER TO
MATCH EXT, WITH
VENEER TIES PER
STRUCTURAL
W2W1
WINDOW/RELITE TYPES
W3
3' - 8 1/2" +/-
FI
T
EX
G
OP
G
2'
- 0
MATCH DOOR WIDTH
DOUBLE HUNG TRANSOM
C2 A-601
C2 A-601
GL-2 GL-2
MA
TC
H
EX
G
FI
T
IN
E
XG
O
PE
NI
NG
6'
- 2
FIT EXG OPG
2' - 10" +/-
SEE ELEVATIONS
FOR MUNTIN
PATTERN
SEE ELEVATIONS
FOR MUNTIN
PATTERN
FLOOR LEVEL
W4
PERFORATED
METAL PANEL
IN OAK FRAME
6'
- 0
1/ 2"
PRIVACY PANEL
3'
- 1
2' - 10" +/-
FIT BETWEEN
EXG WINDOW
JAMBS
F6 A-502
F6 A-502
MATCH SASH
HT OF EXG
WINDOW
F1 A-601
F1 A-601
GL-2
6'
- 1
1"
FI
T
IN
E
XG
O
PG
2'
- 0
FIT IN EXG OPG
3' - 0" +/-
BASEMENT WINDOW
SIM
LOUVER TYPES
L1
F1 A-601
F1 A-601
BASEMENT LOUVER
FI
T
IN
E
XG
O
PE
NI
NG
FIT IN EXG OPENING
F6 A-601
F6 A-601
SIM
SIM
SIM SIM
PROVIDE NEW ROLLING WINDOW
SHADES (AS SCHEDULED) AT
EACH W3 WINDOW
PROVIDE NEW ROLLING WINDOW
SHADES (AS SCHEDULED) AT
EACH W1 WINDOW
OAK WINDOW TRIM TO
MATCH EXISTING WINDOWS
EXG EXTERIOR WALL AND
WINDOW OPENING -
PROVIDE LIQUID APPLIED
AVM AT OPENING
PERIMETER
NEW CONC SEISMIC LAYER
WITH FURRING, RIGID
INSULATION, VAPOR
RETARDER, AND TYPE 'X'
GYPSUM BOARD
OAK WINDOW TRIM TO FILL
GAP AT SEISMIC WALL -
FINISH TO MATCH EXISTING
EXISTING LATH AND
PLASTER TO BE REMOVED
PRIOR TO SEISMIC WALL
5 1 /4"
EXTERIOR CEDAR WINDOW
TRIM TO MATCH EXISTING
PROFILE - PAINT
FIBERGLASS CLAD WOOD
DOUBLE HUNG WINDOW TO
MATCH EXISTING HISTORIC
WINDOWS SIZE AND
CONFIGURATION - PROVIDE
MATCHING INSECT SCREEN
REMOVE EXISTING STUD WALL
TO EXPOSE EXISTING ORIGINAL
BRICK VENEER EXTERIOR WALL -
VERIFY WINDOW OPENING IS
STILL INTACT WITH STEEL ANGLE
LINTEL AND STONE SILL - FIELD
MEASURE OPENING FOR
REPLACEMENT WINDOW
OAK WINDOW TRIM TO
MATCH EXISTING WINDOW
TRIM PROFILE
NEW CONC SEISMIC LAYER
WITH FURRING, RIGID
INSULATION, VAPOR
RETARDER, AND TYPE 'X'
GYPSUM BOARD
EXG STONE SILL - PROVIDE
LIQUID APPLIED AVM AT
OPENING PERIMETER - WRAP
OVER PT PLYWOOD BLOCKING
REMOVE EXISTING WOOD
BOOKCASE BUILT INTO
ORIGINAL WINDOW OPENING
IF STONE SILL DOES NOT EXIST,
PROVIDE NEW CONCRETE SILL
TO MATCH EXISTING PROFILE
BENT ALUM SILL DAM - TURN
UP MIN 1/2" INSIDE WINDOW -
SET DRIP IN CONTINUOUS
BEAD OF SEALANT
SEALANT
ORIGINAL WINDOW ELEVATION - INTERIOR (LEFT) - EXTERIOR (RIGHT)
PAINTED OAK
WINDOW STOOL
W/ 1/2" OVERHANG
EXG EXTERIOR WALL AND
WINDOW OPENING -
PROVIDE LIQUID APPLIED
AVM AT OPENING
PERIMETER
NEW CONC SEISMIC LAYER
WITH FURRING, RIGID
INSULATION, VAPOR
RETARDER, AND TYPE 'X'
GYPSUM BOARD
ALUM,INUM FIXED WINDOW
TO MATCH EXISTING
BASEMENT WINDOWS SIZE
AND CONFIGURATION
NEW CONC SEISMIC
LAYER WITH FURRING,
RIGID INSULATION,
VAPOR RETARDER, AND
TYPE 'X' GYPSUM BOARD
EXG STONE
SILL TO
REMAIN
BENT ALUM SILL DAM -
TURN UP MIN 1/2"
INSIDE WINDOW - SET
DRIP IN CONTINUOUS
BEAD OF SEALANT
BASEMENT WINDOW ELEVATION - EXTERIOR
4 1/2"
1 3 /4"
METAL DRIP FLASHING
EXISTING
STONE
BELLEY BAND
FIRST FLR RCP
18' - 0"
FIRST FLOOR
10' - 0"
10.110
WINDOW HEAD
19' - 1 1/2"
9'
- 1
1/ 2"
7'
- 0
E209d
8'
- 0
FACE OF FURRING
1' - 4"
1' - 0 1/2"
4" 1'
- 5
4" 8 3/4" 3 5/8"
HOLLOW METAL
FRAME
INSULATED GLASS
AS SCHEDULED
EXISTING BRICK/
CONC WALL
BACKER ROD
AND SEALANT
HOLLOW METAL
FRAME
DOOR AS
SCHEDULED
2-PIECE
THRESHOLD
CONC PAVERS
ON VARIABLE HT
PEDESTALS
INFILL GAP UNDER
DOOR WITH
CONCRETE AS REQ'D
6" CEILING
CLOSURE
SUSP. ACOUSTIC
CEILING
PAINT BOTT OF CONCRETE
DECK MIN 2' PAST CEILING
OPENING - INCL ALL CONDUIT,
DUCTS, PIPES, ETC
1/2
EXISTING OAK WINDOW TRIM TO BE
REMOVED, SALVAGED, AND REINSTALLED
IN SAME WINDOW
EXG EXTERIOR WALL AND WINDOW
TO REMAIN - PROTECT WINDOW
FROM CONSTRUCTION OPERATIONS
NEW OAK WINDOW TRIM TO FILL GAP AT
SEISMIC WALL - FINISH TO MATCH EXISTING
TYPICAL AT ALL EXISTING WINDOWS WHERE
SEISMIC GUNNITE TREATMENT IS BEING DONE
NEW CONC SEISMIC LAYER WITH
FURRING, RIGID INSULATION, VAPOR
RETARDER, AND TYPE 'X' GYPSUM BOARD
EXISTING LATH AND PLASTER TO BE
REMOVED PRIOR TO SEISMIC WALL
JAMB AND SILL SIMILAR
EXISTING OAK WINDOW TRIM TO BE
REMOVED, SALVAGED, AND REINSTALLED
IN SAME WINDOW
EXG EXTERIOR WALL AND WINDOW
TO REMAIN - PROTECT WINDOW
FROM CONSTRUCTION OPERATIONS
NEW OAK WINDOW TRIM TO FILL GAP AT
SEISMIC WALL - FINISH TO MATCH EXISTING
TYPICAL AT ALL EXISTING WINDOWS WHERE
SEISMIC GUNNITE TREATMENT IS BEING DONE
NEW METAL STUD SEISMIC LAYER WITH
R-25 BATT INSULATION, VAPOR
RETARDER, AND TYPE 'X' GYPSUM BOARD
EXISTING LATH AND PLASTER TO BE
REMOVED PRIOR TO SEISMIC WALL
JAMB AND SILL SIMILAR
ALL EXISTING WOOD FRAMED
WINDOWS AND DORMER LOUVERS ARE
TO BE REFURBISHED. REFURBISHING
OF EXISTING WINDOWS AND DORMER
LOUVERS INCLUDES BUT IS NOT
LIMITED TO THE FOLLOWING:
1. REMOVE ALL NAILS, SCREWS AND
ANY OTHER FASTENERS NOT PART OF
ORIGINAL WINDOW OR OUVER DESIGN
2. REMOVE ALL TRIM, ANGLES,
AND/OR PLATES NOT PART OF
ORIGINAL WINDOW OR LOUVER DESIGN
3. REMOVE ALL WINDOW SCREENS
4. REMOVE AND REPLACE BROKEN
GLASS (WHERE OCCURS)
5. REMOVE LOOSE FLAKING PAINT
ON INTERIOR AND EXTERIOR BY HAND
SANDING
6. REMOVE FILMS ON INTERIOR SIDE
OF GLASS (TOILET ROOM WINDOWS)
7. FILL VOIDS, HOLES IN WOOD
WINDOW AND DORMER LOUVER FRAME
AND TRIM AS REQUIRED TO RECEIVE
NEW PAINT.
8. PRIME AND RE-PAINT WINDOW
AND DORMER LOUVER FRAME,
MUNTINS AND TRIMS.
9. PRIME AND RE-PAINT WINDOW
SCREEN FRAME
10. REPLACE TORN AND/OR
DAMAGED SCREN FABRIC
11. CLEAN EXISTING LOUVER
SCREENS AND LOUVER BLADES INSIDE
AND OUT
12. TEST FOR PROPER WINDOW
OPERATION INCLUDING LOCKING
MECHANISM
13. REPAIR WINDOW SASH/LOCKING
MECHANISM AS REQUIRED
14. CLEAN EXISTING GLASS INSIDE
AND OUTSIDE
15. PROVIDE NEW ROLLING WINDOW
SHADES (AS SCHEDULED) AT EACH
WINDOW
NOTE: WINDOWS WERE REFURBISHED
USING THE SAME PROCESS IN 2013,
AND LEAD PAINT WAS ABATED AT THAT
TIME, ACCORDING TO THE 9/5/2012
DESIGN DRAWINGS.
WINDOW/LOUVER SCOPE
R7
C5 A-602
C5 A-602
1'
- 3
MA
TC
H
TO
P
OF
A
DJ
D
OO
R
TR
IM
6'
- 0
2' - 0"
E5 A-602
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:0
PM
A-601
WINDOW TYPES AND DETAILS,
WALL TYPES
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 Checker Author
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
1/4" = 1'-0"
LOUVER AND WINDOW TYPES
3" = 1'-0"F5 W1- WINDOW DETAIL
3" = 1'-0"F1 W3- WINDOW DETAIL
1 1/2" = 1'-0"C1 DETAIL AT DOOR E209d
3" = 1'-0"D3 EXG WINDOW W/ EXTENDED TRIM - GUNNITE
3" = 1'-0"D1 EXG WINDOW W/ EXTENDED TRIM STRONGBACK
Revisions: Date:
1/2" = 1'-0"
RELITE TYPES
B C
DOOR TYPES
SEE DOOR SCHEDULE FOR HEAD, JAMB AND SILL
FLOOR LEVEL
EXISTING
WOOD PANEL
DOORS TO BE
SALVAGED
RECESSED
PANELS
6'
- 8
A
6'
- 1
0" F
V
3' - 4 1/4" FV
2' - 8"
6'
- 8
TRANSOM AT
DOOR e209d
9'
- 2
FV
D E
5"
5"
F J
5 5/8" 5 5/8"
5 5 /8"
HG
TEMPERED
GLASS PANEL
RECESSED
PANEL
EXISTING
WIRE GLASS
VISION LITE
5"
5"
5" 5" 5 5/8"5 5/8"
5 5 /8"
3'- 5 5
/8"
SEE DOOR
SCHEDULE FOR
EXG DOOR
SLABS TO BE
REINSTALLED
FRAME TYPES
B4 A-602
B4 A-602
3" 3"
3"
2"
2" 2" 2"1' - 4"
4' - 10"
ALL HM DOOR
FRAMES TO BE
PAINTED PT3 -
ALL SIDES
HOLLOW METAL FRAME
AS SCHEDULED
GLAZING AS
SCHEDULED
CAULK, TYPICAL
BOTH SIDES
WALL ASSEMBLY
AS SCHEDULED
APPLIED GLASS STOP
JAMB SIMILAR
2"
1/2"1/2"
6 1/2"
HOLLOW METAL FRAME
AS SCHEDULED
GLAZING AS
SCHEDULED
APPLIED GLASS STOP
DOOR AS
SCHEDULED
6 1/2"
2"
HOLLOW METAL
FRAME - FILL WITH
FOAM INSULATION
APPLIED GLASS STOP
CONCRETE FLOOR
BACKER ROD
AND SEALANT
SHIM ON SILL SEALER
TEMPERED GLAZING
AS SCHEDULED
FLOOR FINISH AS
SCHEDULED
6 1/2"
HOLLOW
METAL FRAME
DOOR AS
SCHEDULED
2"
CAULK, TYPICAL
BOTH SIDES
1/2"1/2"
WALL TYPE AS
SCHEDULED
JAMB SIMILAR
6 1/2"
OAK DOOR
FRAME
DOOR AS
SCHEDULED
BUILT-UP OAK
TRIM BOTH
SIDES
GLASS PANEL
AS SCHEDULED
3/4
3"
3/4
WALL THICKNESS
OAK DOOR FRAME
WOOD DOOR AS
SCHEDULED
BUILT-UP OAK TRIM
BOTH SIDES
WALL TYPE AS
SCHEDULED
WALL THICKNESS
CAULK, TYP.
OAK FRAMED GLASS
PANEL
BUILT-UP OAK
TRIM BOTH
SIDES
WALL TYPE AS
SCHEDULED
GLASS PANEL
AS SCHEDULED
OAK DOOR FRAME
SALVAGED OAK
PANEL DOOR
BUILT-UP OAK TRIM
TO MATCH EXISTING
WALL TYPE AS
SCHEDULED
CAULK, TYP.
3/4
5 1/2"
HOLLOW
METAL FRAME
DOOR AS
SCHEDULED
CAULK, TYPICAL
BOTH SIDES
WALL TYPE AS
SCHEDULED
1/2
6" 6"
1/2
HOLLOW
METAL FRAME
5 3/4"
HOLLOW METAL
FRAME CENTER ON
WALL - GROUT SOLID
DOOR AS
SCHEDULED
2"
CAULK, TYPICAL
BOTH SIDES
EXG CONC WALL
6 1/2"
2 1 /4"
EXPANSION BOLT
FRAME TO WALL
HOLLOW
METAL FRAME
DOOR AS
SCHEDULED
2"
CAULK, TYPICAL
BOTH SIDES
7/16"7/16"
WALL TYPE AS
SCHEDULED
JAMB SIMILAR
8 3/4"
BUILT UP OAK
FRAME
BUILT-UP OAK
BASE ON METAL
STUDS - FILL WITH
FOAM INSULATION
GLASS PANEL
AS SCHEDULED
3/4
WALL THICKNESS
5 1/2"
CONCRETE FLOOR
BACKER ROD
AND SEALANT
SHIM ON SILL SEALER
FLOOR FINISH AS
SCHEDULED
OAK DOOR FRAME
WOOD DOORS AS
SCHEDULED
BUILT-UP OAK TRIM
BOTH SIDES
WALL TYPE AS
SCHEDULED
WALL THICKNESS
CAULK, TYP.
SLIDING CLOSET
DOOR TRACK
1 1 /2"
3/4
3/4"3 3/4"
OAK DOOR FRAME
WOOD DOORS AS
SCHEDULED
BUILT-UP OAK TRIM
BOTH SIDES
WALL TYPE AS
SCHEDULED
WALL THICKNESS
CAULK, TYP.
RUBBER DOOR
BUMPERS - BOTH SIDES
1 1 /2"
3/4
3/4"3 3/4"
BACKER ROD
AND SEALANT
HM DOOR FRAME
GROUT SOLID
FACE OF EXG BRICK
DOOR AS SCHEDULED
SHIM AS REQUIRED
METAL STUD
BOX HEADER
WALL AS SCHEDULED
4 1/2" RUN VAPOR RETARDER
BEHIND FRAME
BENT METAL FLASHING
A
BACKER ROD
AND SEALANT
HM DOOR FRAME -
EXPANSION BOLT TO EXG
WALL - GROUT SOLID
FACE OF EXG BRICK
DOOR AS SCHEDULED
SHIM AS REQUIRED
DOUBLE STUD
AT JAMBS
WALL AS SCHEDULED
4 1/2"
2 1 /2"
RUN VAPOR RETARDER
BEHIND FRAME
A
HM DOOR FRAME -
EXPANSION BOLT TO EXG
WALL - GROUT SOLID
FACE OF EXG BRICK
DOOR AS SCHEDULED
METAL GRATE LANDING
1/2" MAX
10 1/2"
CENTER LINE
FOR STAIR
POSTS
A
METAL THRESHOLD
1/4
HOLLOW
METAL FRAME
DOOR AS
SCHEDULED
2"
CAULK, TYPICAL
BOTH SIDES
9/16"9/16"
WALL TYPE AS
SCHEDULED
JAMB SIMILAR
7 1/4"
STAINLESS STEEL 'Z' CLIP (24"
LONG) FASTENED TO BACK OF
DOOR 18" O.C. - PROVIDE AT TOP
AND BOTTOM OF EACH DOOR.
STAINLESS STEEL 'Z' CLIP (24"
LONG) FASTENED TO WALL
ALIGNED WITH DOOR 'Z' CLIP -
FASTEN TO STUDS IN WALL AT
16" O.C. - PROVIDE AT TOP AND
BOTTOM AT EACH DOOR.
SALVAGED HISTORIC
DOOR AS SCHEDULED
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:0
PM
A-602
DOOR SCHEDULE
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 KH LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
DOOR AND FRAME SCHEDULE
NUM
DOORS FRAMES
HARDWARE
GROUP REMARKSTYPE
MAT
L FINISH
GLASS
TYPE
SIZE
TYPE MATL FINISH HEAD JAMB SILLWIDTH HEIGHT
BASEMENT
101 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
107 F WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - EXG INSTALL EXG DOOR SLAB D120 WITH EXG HARDWARE IN NEW
FRAME
108 EXG WD PNT - 42" 80" EXG WD PNT EXG EXG EXG EXG EXISTING DOOR AND FRAME TO REMAIN, STRIP PAINT AND
REFINISH DOOR AND FRAME
112 F HM PNT - 24" 80" 1 HM PNT F5/A602 SIM F5/A602 - HW-5
113 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
114 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
114a F - PNT - 36" 84" 1 HM PNT C3/A602 C3/A602 - HW-5 115 EE WD STN - 60" 80" 1 WD STN B3/A602 B3/A602 - HW-10D INSTALL EXG DOOR SLABS WITH NEW HARDWARE IN NEW
FRAME
116 C WD STN - 42" 84" 1 HM PNT F4/A602 F4/A602 - HW-5
117 FF HM PNT - 60" 84" 1 HM PNT B4/A602 B4/A602 - HW-10C
118 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-3
120 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-3
121b F HM PNT - 72" 58" 1 HM PNT F6/A603 SIM F6/A603 E1/A603 SIM HW-E8 COORDINATE EXACT LOCATION FOR BEST ACCESS TO
ELEVATORE EQUIPMENT
122 EXG WD PNT - 42" 80" EXG WD PNT EXG EXG EXG EXG EXISTING DOOR AND FRAME TO REMAIN, STRIP PAINT AND
REFINISH DOOR AND FRAME
E100 H ALUM MILL GL1 38" 95" CW-1 ALUM MILL F1/A603 E1/A603 E1/A603 HW-E9
E101 J HM 44" 84" PNT D1/A-602 D1/A-602 - HW-6
E101a F HM PNT GL1 36" 84" 2 HM PNT D1/A-602 D1/A-602 - HW-5 E102a J WD STN GS1 36" 84" 1 HM PNT D2/A602 SIM E2/A602 SIM - HW-6 E102b J HM MILL GL1 44" 96" 1 HM PNT E3/A603 F6/A603 E1/A603 SIM HW-E4
FIRST FLOOR
201 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-1E
202 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-1E
203 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
203a C WD STN - 36" 84" 1 HM PNT B5/A602 B5/A602 - HW-3 203b C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 203c EE WD STN - 60" 80" 1 WD STN B1/A602 C1/A602 - HW-10S INSTALL EXG DOOR SLABS WITH NEW HARDWARE IN NEW
FRAME
204 C WD STN GL1 36" 84" 1 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
205 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
206 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
206a C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
207 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
207a C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 207b C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 207c EE WD STN - 60" 80" 1 WD STN B1/A602 C1/A602 - HW-10S INSTALL EXG DOOR SLABS WITH NEW HARDWARE IN NEW
FRAME
208 C WD STN - 36" 84" 1 HM PNT F4/A602 F4/A602 - HW-5
209a C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 209b C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 209c F WD STN - 48" 84" 1 HM PNT B4/A602 B4/A602 - EXG INSTALL EXG DOOR SLAB WITH EXG HARDWARE IN NEW FRAME
210 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
211 C WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
212 EXG WD STN - 30" 80" EXG HM PNT EXG EXG - EXG EXISTING DOOR TO REMAIN - STRIP AND REFINISH
E201 J HM PNT EXG 44" 84" 1 HM PNT D1/A-602 D1/A-602 - HW-6 STRIP PAINT FROM DOOR AND REPAINT AS SPECIFIED E201a F HM PNT - 36" 84" 1 HM PNT D1/A-602 D1/A-602 - HW-5 E201b EXG WD PNT EXG 42" 87" EXG WD PNT EXG EXG EXG EXG EXISTING DOOR AND FRAME TO REMAIN, STRIP PAINT AND
REFINISH DOOR AND FRAME
E201c EXG ALUM MILL EXG 36" 80" EXG ALUM MILL EXG EXG EXG EXG EXISTING DOOR AND FRAME TO REMAIN - INCLUDNG TRANSOM
AND SIDELITES
E202 J WD STN GL1 36" 84" 1 HM PNT F6/A603 F6/A603 - HW-6
E209a EE WD STN - 60" 80" 1 WD STN B3/A602 B3/A602 - HW-10D INSTALL EXG DOOR SLABS WITH NEW HARDWARE IN NEW
FRAME
E209d A WD PNT EXG 41" 84" 1 WD PNT F9/A503 F9/A503 F9/A503 HW-E4 STRIP PAINT FROM DOOR AND REPAINT AS SPECIFIED - INSTALL
NEW TRANSOM TO MATCH SOUTH PORCH
SECOND FLOOR
301 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-1E
302 C WD STN - 36" 84" 1 HM PNT B4/A602 B4/A602 - HW-1E
303b G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
304 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
304a G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 304b G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 304c F WD STN - 36" 84" 1 HM PNT B5/A602 B5/A602 - HW-5
305 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
306 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
307 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
308 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
308a G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 308b G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 308c G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 308e G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3 308f C WD STN - 36" 84" 1 HM PNT B5/A602 B5/A602 - HW-5 308g C WD STN - 36" 84" 1 HM PNT B5/A602 B5/A602 - HW-5
309 G WD STN GL1 36" 84" 2 WD STN B5, C5/A602 B5, C5, D5/A-602 E5/A602 HW-3
E301 J HM STN - 44" 84" 1 HM PNT D1/A-602 D1/A-602 - HW-6
3" = 1'-0"C4 HOLLOW METAL INT. SIDELITE HEAD
3" = 1'-0"D4 HOLLOW METAL INT. SIDELITE/DOOR
3" = 1'-0"E4 HOLLOW METAL SIDELITE SILL
3" = 1'-0"B4 INT DOOR HEAD
3" = 1'-0"D5 WOOD DOOR / SIDELITE
3" = 1'-0"B5 WOOD DOOR HEAD/JAMB
3" = 1'-0"C5 WOOD SIDELITE HEAD/JAMB
3" = 1'-0"B3 INT WOOD CHASE DOOR HEAD/JAMB
3" = 1'-0"F5 UTILITY ROOM DOOR JAMBS
3" = 1'-0"C3 INT DOOR HEAD/JAMB
3" = 1'-0"F4 INT DOOR HEADJAMB 6" WALL
3" = 1'-0"E5 WOOD SIDELITE 10" SILL
3" = 1'-0"B1 SLIDING WOOD DOOR HEAD
3" = 1'-0"C1 SLIDING WOOD DOOR JAMB
3" = 1'-0"D2 EXIT DOOR HEAD
3" = 1'-0"E2 EXIT DOOR JAMB
3" = 1'-0"F2 EXIT DOOR SILL
3" = 1'-0"D1 INT DOOR HEAD - RATED
3" = 1'-0"F1 DOOR HANGING DETAIL
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
GLASS AS SCHEDULE
2 1 /2"
1"
6"
2 1 /2"
1/2"
CHAMFER AT EDGE
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
CONCRETE SLAB
GLASS AS SCHEDULE
SLOPE WALK 1.8%
AWAY FROM BUILDING
1/4
1/2
1/2" EXPANSON JOINT
WITH FIBEROUS FILLER
1/
2"
TWO-PIECE THERMAL
BREAK THRESHOLD SET IN
CONT. BEAD OF SEALANT
ALUMINUM CURTAIN WALL DOOR
WITH WEATHER STRIP DOOR
BOTTOM AND INTEGRAL DRIP
CONT. WEATHER STRIP
AT DOOR PERIMETER
2'
- 0
JAMB / HEAD SIMILAR
ANCHOR EACH SIDE OF
VERTICAL MEMBERS TO
FLOOR STRUCTURE PER
MANUF REQUIREMENTS
6"
2 1 /2"
2 1 /2"
F V
BACKER ROD AND SEALANT
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
3"x1 1/2"x1/8" CONT ALUMINUM
ANGLE CLOSURE PLATE - FINISH
TO MATCH CURTAIN WALL - EPOXY
BOLT TO BRICK AT 16" O.C. VERT.
FACE OF EXG BRICK
SEISMIC JOINT FILLER WITH
ALUM COVER PLATE TO
MATCH CURTAIN WALL
GLASS AS SCHEDULED
XPS RIGID INSUL. CUT TO FILL GAP
CONT FOAM SEAL MEMBRANE, LOOP
INTO CAVITY AND BEHIND ANGLE
FOR TIGHT FIT
1/2"
1/2
2 1 /2"
6"
BACKER ROD AND SEALANT
ALUMINUM CURTAINWALL SYSTEM
WITH SHEAR BLOCK
SHIM AS REQUIRED
CONCRETE SLAB
GLASS AS SCHEDULE
1/2
" SLOPE WALK 1.8%
AWAY FROM BUILDING
6"
2 1 /2"
1"
SEISMIC OINT FILLER
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
3"x1 1/2"x1/8" CONT ALUMINUM
ANGLE CLOSURE PLATE - FINISH
TO MATCH CURTAIN WALL - EPOXY
BOLT TO BRICK AT 16" O.C. VERT.
FACE OF EXG BRICK
GLASS AS SCHEDULED
XPS RIGID INSUL. CUT TO FILL GAP
CONT. FOAM SEAL MEMBRANE -
BEHIND ANGLE FOR TIGHT FIT
BACKER ROD AND SEALANT
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK - SET ON
CONT. SILL SEAL MEMBRANE
SILL DAM FLASHING WITH
TURNED UP END DAMS
GLASS AS SCHEDULE
SLOPE GRADE AWAY
FROM BUILDING
1/2
2 1 /2"
6"
6" M
IN
BACKER ROD AND SEALANT
4"
SECOND FLOOR
21' - 0"
BASEMENT RCP
8' - 0"
FIRST FLR RCP
18' - 0"
ATTIC FLOOR
31' - 6"
BASEMENT
0"
FIRST FLOOR
10' - 0"
SECOND FLR RCP
29' - 4"
4'
- 4
1/ 2"
3'
- 7
1/ 2"
2'
- 0
3'
- 6
4'
- 6
3'
- 0
3'
- 6
5'
- 0
2' - 0 1/4" 6' - 3" 2' - 0"
GL-1 UON
3" SEISMIC JOINT
COVER
F1
A-603
36" DEEP SUN SHADE
FOR CURTAIN WALL
WITH ROUNDED
OUTRIGGERS AND
ARCHED BLADES
C3
A-603
D3
A-603B1
A-603
B3
A-603
F3
A-603
SIM
C3
A-603
D3
A-603
B1
A-603
B3
A-603
B3
A-603
B3
A-603
E1
A-603
C9
A-502
1" SEISMIC JOINT
COVER
A-301
SECOND FLOOR
21' - 0"
BASEMENT RCP
8' - 0"
FIRST FLR RCP
18' - 0"
BASEMENT
0"
FIRST FLOOR
10' - 0"
3'
- 6
4'
- 6
2'
- 0
3'
- 6
4'
- 6
3'
- 0
3'
- 6
5'
- 0
2' - 0" 6' - 3" 1' - 11 11/16"
GL-1 UON
SEISMIC JOINT FILLER
WITH ALUMINUM
COVER - FV FIT
C9
A-502
B1
A-603
D3
A-603 C3
A-603
B3
A-603
B3
A-603
B3
A-603
B3
A-603
F3
A-603
D3
A-603 C3
A-603
C5
A-502
1" SEISMIC JOINT
FILLER WITH
ALUMINUM COVER
SCUPPER AND
DOWNSPOUT - ALIGN
CENTER WITH CENTER
OF VERTICAL CURTAIN
WALL MULLION
C7
A-301
SECOND FLOOR
21' - 0"
BASEMENT RCP
8' - 0"
FIRST FLR RCP
18' - 0"
BASEMENT
0"
FIRST FLOOR
10' - 0"
SECOND FLR RCP
29' - 4"
F4
A-310
F8
A-603
F6
A-603
F8
A-603
D3
A-603
D3
A-603
E3
A-603
E102b
E1
A-603
SIM
BACKER ROD AND SEALANT
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
FACE OF BRICK
GLASS AS SCHEDULED
SHIM AS REQUIRED
TRIPLE KING STUD AT JAMBS
6"
2 1/2"1/2"
LIQUID APPLIED AIR/VAPOR
MEMBRANE - SEAL GYP BD
EDGES AND ENDS
BACKER ROD AND SEALANT
WALL AS SCHEDULED
2 1/2" LOOSE LAID EPS RIGID
INSULATION IN CAVITY
BRICK TIES PER STRUCTURAL
5 1 /2"
6"
BACKER ROD AND SEALANT
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
SHIM AS REQUIRED
GLASS AS SCHEDULE
HM DOOR FRAME - GROUT SOLID
FACE OF BRICK
DOOR AS SCHEDULED
2"
5 1/2"
5 3/4"
BENT METAL PLATE OVER PT
WOOD BLOCKING - PAINT TO
MATCH DOOR FRAME
FACE OF GYP BD INT WALL
BENT METAL FLASHING AND
DRIP - PAINT TO MATCH DOOR
FRAME - SEPARATE DIFFERING
METALS AS SPECIFIED4"
2 1 /2"
BACKER ROD AND SEALANT
HM DOOR FRAME - GROUT SOLID
FACE OF BRICK
DOOR AS SCHEDULED
SHIM AS REQUIRED
TRIPLE KING STUD AT JAMBS
6 5 /8"
LIQUID APPLIED AIR/VAPOR
MEMBRANE - SEAL GYP BD
EDGES AND ENDS
BACKER ROD AND SEALANT
WALL AS SCHEDULED
2 1/2" LOOSE LAID EPS RIGID
INSULATION IN CAVITY
BRICK TIES PER STRUCTURAL
5 1 /2"
2 1/2"
ALUMINUM STOREFRONT
SYSTEM WITH SHEAR BLOCK
GLASS AS SCHEDULE
2 1 /2"
FLOOR SLAB WITH STEEL
EDGE ANGLE
ANCHOR EACH SIDE OF
HORIZONTAL MEMBERS TO
FLOOR STRUCTURE PER
MANUF REQUIREMENTS
1"
ALUMINUM STOREFRONT SYSTEM
WITH SHEAR BLOCK
GLASS AS SCHEDULE
2 1 /2"
1"
FLOOR SLAB WHERE OCCURS
ANCHOR EACH SIDE OF
VERTICAL MEMBERS TO
FLOOR STRUCTURE PER
MANUF REQUIREMENTS
ATTIC FLOOR
31' - 6"
1 1/2" X 24" X 120" METAL PANEL
BENT ALUM FLASHING
FINISHED TO MATCH BRICK
STARTER CLIP BY PANEL MANUF.
LIQUID APPLIED AIR VAPOR
MEMBRANE - WRAP DOWN OVER
FLASHING LEG
GYPSUM GLASS FIBER
SHEATHING
FILL CAVITY WITH RIGID
EPS INSULATION
ALUMINUM CURTAIN WALL
SYSTEM WITH SHEAR BLOCK
WRAP GWB
WALL AS SCHEDULED
BASEMENT RCP
8' - 0"
36" DEEP SUN SHADE FOR CURTAIN
WALL WITH ROUNDED OUTRIGGERS
AND ARCHED BLADES
3' - 0"
4"
MOUNT OUTRIGGERS TO VERTICAL MULLIONS
PER MANUFACTURERS REQUIREMENTS
ALUMINUM CURTAIN WALL
SYSTEM WITH SHEAR BLOCK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 -
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:1
PM
A-603
CURTAIN WALL DETAILS
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 Checker Author
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Revisions: Date:
3" = 1'-0"E1 CURTAIN WALL DOOR DETAIL
3" = 1'-0"B1 CURTAIN WALL JAMB 1st & 2nd FLR
3" = 1'-0"E4 CURTAIN WALL SILL AT WALK
3" = 1'-0"B3 CURTAIN WALL JAMB BASEMENT
3" = 1'-0"F3 CURTAIN WALL SILL AT GRADE
1/2" = 1'-0"E9 CW-1 - CURTAIN WALL 1
1/2" = 1'-0"E7 CW-2 - CURTAIN WALL 2
1/2" = 1'-0"E5 CW-3 - CURTAIN WALL 3
3" = 1'-0"F8 CURTAIN WALL JAMB STAIR
3" = 1'-0"E3 CURTAIN WALL SILL AT STAIR
3" = 1'-0"F6 DOOR JAMB STAIR
3" = 1'-0"C3 CURTAIN WALL MULLION HORIZ ANCHOR
3" = 1'-0"D3 CURTAIN WALL MULLION VERT ANCHOR
1 1/2" = 1'-0"F4 CURTAIN WALL HEAD AT STAIR TOWER
1 1/2" = 1'-0"F1 SUNSHADE AT ENTRY
.6 m m
D R
YW
AL
L
SE
TB
AC
K
/3 2"
.2 m m
3"
R1/4" [R6.4mm]
ACROVYN 4000 COVER
(24U002xxx)
1 LAYER OF
5/8" G.W.B.
(BY OTHERS)
FEATHERED
JOINT
ALUMINUM RETAINER
(24A155000)
1 HR. FIRE BARRIER
#6 X 1 5/8" BUGLE HD SMS
STEEL STUD
(BY OTHERS)
FIRE STOP SEALANT
STEEL STUD
(BY OTHERS)
2 LAYERS 5/8" G.W.B.
(BY OTHERS)
FEATHERED
JOINT
ALUMINUM RETAINER
(24A155000)
R1/4" [R6.4mm]
ACROVYN 4000 COVER
(24U002xxx)
1 HR. FIRE BARRIER
#6 X 1 5/8" BUGLE HD SMS
.2 m m
3"
3 1 /8"
ANNODIZED ALUMINUM WALL
BASE SET IN 2 CONT BEADS OF
ADHESIVE SEALANT - SCHLUTER
DESIGNBASE-SL OR EQUAL
RUBBER GASKET
BY BASE MANUF.
4'
- 4
1'
- 0
4" 1/2
1" 4"
5'
- 9
1/ 2"
CT1 FIELD TILE -
HT AS INDICATED
ON ELEVATIONS
1/2 HALF ROUND
METALLIC TILE
TRIM - (TOP OF
WAINSCOT WHERE
OCCURS)
CT1 - ONE ROW
CT2 - 12x12
ACCENT TILE
CT1 - 13 ROWS
METAL COVE
BASE - SCHLUTER
DILEX-PHK
MOSAIC C.T. FLOOR
METAL COVE BASE -
SCHLUTER DILEX-PHK
THINSET TILE FINISH
LIQUID APPLIED
WATERPROOFING MEMBRANE
1/4" CEMENT BOARD
WALL FRAMING STUDS
1/2" MARINE GRADE PLYWOOD
(AT WALL WITH SHOWER SEAT
ONLY) - VERIFY 60" CLEAR
PRIOR TO INSTALLATION
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:1
PM
A-604
ROOM FINISH & EQUIPMENT
SCHEDULES
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 KH LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
ROOM FINISH SCHEDULE
Level RM NUM ROOM NAME FLOOR BASE
WALLS
CEILING COMMENTS / NOTESNORTH EAST SOUTH WEST
BASEMENT BA101 EMS AO CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
BASEMENT BA102 EMS SUPPORT LVT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
BASEMENT BA103 VEST W LVT RB GWB/PNT3 GWB/PNT3 GWB/PNT3 CMT/CT EXP/PNT
BASEMENT BA104 LOCKER W CT4 ALUM GWB/PNT GWB/PNT GWB/PNT GWB/PNT EXP/PNT
BASEMENT BA105 TOILET W CT4 ALUM GWB/PNT/CT GWB/PNT/CT GWB/PNT/CT GWB/PNT/CT EXP/PNT
BASEMENT BA106 SHOWER W CT4 ALUM CMT/CT CMT/CT CMT/CT CMT/CT EXP/PNT
BASEMENT BA107 UNIFORMS LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT PNT
BASEMENT BA108 EMS STORAGE CONC/SLR - CONC/PNT CONC/PNT CONC/PNT CONC/PNT EXP/PNT
BASEMENT BA109 VEST M LVT RB GWB/PNT3 GWB/PNT3 GWB/PNT3 CMT/CT EXP/PNT
BASEMENT BA110 TOILET M CT4 ALUM GWB/PNT/CT GWB/PNT/CT GWB/PNT/CT GWB/PNT/CT EXP/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN BASEMENT BA110a SHOWER M1 CT4 ALUM CMT/CT CMT/CT CMT/CT CMT/CT EXP/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN BASEMENT BA110b SHWR M2 CT4 ALUM CMT/CT CMT/CT CMT/CT CMT/CT EXP/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN BASEMENT BA111 LOCKER M CT4 ALUM GWB/PNT GWB/PNT GWB/PNT GWB/PNT EXP/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN
BASEMENT BA112 UTIL CONC/SLR - GWB/PNT GWB/PNT CONC/PNT CONC/PNT EXP/PNT
BASEMENT BA113 EMS CHIEF CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
BASEMENT BA114 EMS ASST CHIEF CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
BASEMENT BA115 BREAK ROOM LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT2 EXP/PNT
BASEMENT BA116 HAC CONC/SLR CTB GWB/PNT GWB/PNT GWB/PNT/CT GWB/PNT/CT EXP/PNT 5'-0" HIGH CT WAINSCOT (2) WALLS BASEMENT BA117 LG EQPT STORAGE CONC/SLR - GWB/PNT GWB/PNT GWB/PNT GWB/PNT EXP/PNT
BASEMENT BA118 EMS SUPER CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
BASEMENT BA119 EMS INT DESIGNER LVT RB GWB/PNT GWB/PNT - GWB/PNT ACT
BASEMENT BA120 EMS TRAINING SUPER CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
BASEMENT BA121 MACH ROOM CONC/SLR - GWB/PNT GWB/PNT GWB/PNT GWB/PNT GWB/PNT
BASEMENT BA122 ELECT CONC/SLR - CONC/PNT CONC/PNT CONC/PNT CONC/PNT EXP/PNT
BASEMENT E100 ELEV. LVT - GWB/PNT GWB/PNT GWB/PNT GWB/PNT EXP/PNT
BASEMENT E100 ELEV LOBBY WOM ALUM BRICK ALUM/GLS EXG ALUM/GLS EXP/PNT
BASEMENT E101 CORR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT VARIES LWC WHERE SHOWN ON PLAN, SEE FINISH PLAN FOR PT4
ACCENT WALLS
BASEMENT E102 STAIR 1 WOM RB RB BRICK GWB/PNT GWB/PNT EXP/PNT
FIRST FLOOR 1A201 TOILET W CT4 CTB GWB/PNT/CT GWB/PNT/CT GWB/PNT GWB/PNT/CT GWB/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN FIRST FLOOR 1A202 TOILET M CT4 CTB GWB/PNT/CT GWB/PNT/CT GWB/PNT GWB/PNT/CT GWB/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN
FIRST FLOOR 1A203 UNION CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A203A UN OFFC CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A203B UN OFFC CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A203C STOR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT GWB/PNT
FIRST FLOOR 1A204 FLEET CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A205 VISN 1 CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A206 BILLING CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A206A REVENUE MGR CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A207 FS SUPPORT CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A207A FISCAL SERV AUDITOR CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT FIRST FLOOR 1A207B FISCAL SERV. AUDITOR CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A207C FS STOR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT GWB/PNT
FIRST FLOOR 1A208 HAC CONC/SLR RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT GWB/PNT
FIRST FLOOR 1A209 HBPC SUPPORT CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A209A HBPC CHIEF CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT2 ACT
FIRST FLOOR 1A209B HBPC DIRECTOR CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT2 ACT
FIRST FLOOR 1A209C HBPC CLEAN STOR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT
FIRST FLOOR 1A210 FS CHIEF CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A211 FS ASST CHIEF CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
FIRST FLOOR 1A212 IT EXG - EXG/PNT EXG/PNT EXG/PNT EXG/PNT EXP/PNT
FIRST FLOOR E200 ELEV LOBBY CONC/SLR ALUM BRICK ALUM/GLS EXG ALUM/GLS EXP/PNT
FIRST FLOOR E201 CORR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT VARIES LWC WHERE SHOWN ON PLAN, SEE FINISH PLAN FOR PT4
ACCENT WALLS
FIRST FLOOR E202 STAIR CONC/SLR ALUM GWB/PNT BRICK GWB/PNT GWB/PNT EXP/PNT
SECOND FLOOR 2A301 TOILET W CT4 ALUM GWB/PNT/CT GWB/PNT/CT GWB/PNT GWB/PNT/CT GWB/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN SECOND FLOOR 2A302 TOILET M CT4 ALUM GWB/PNT/CT GWB/PNT/CT GWB/PNT GWB/PNT/CT GWB/PNT SEE DETAIL D3 THIS SHEET FOR WALL TILE PATTERN SECOND FLOOR 2A303 SHARED CONF/TRAIN CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT LWC SECOND FLOOR 2A304 LOGISTICS SUPPORT CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A304A LOG ASST CHIEF CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A304B LOG CHIEF CPTT RB GWB/PNT GWB/PNT2 GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A304C LOG SUPPLY LVT RB GWB/PNT GWB/PNT EXG/PNT GWB/PNT ACT
SECOND FLOOR 2A305 LOG SUPERVISOR CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A306 LOG SUPERVISOR CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A307 FLEX SPACE CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A308 HR SUPPORT CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A308A P.I.V. CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A308B HR SUPERVISOR CPTT RB GWB/PNT2 GWB/PNT GWB/PNT GWB/PNT ACT
SECOND FLOOR 2A308C HR DIRECTOR CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT2 ACT
SECOND FLOOR 2A308D HR WORK STATIONS CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
SECOND FLOOR 2A308E HR CHIEF CPTT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT2 ACT
SECOND FLOOR 2A308F HR RECORDS LVT RB GWB/PNT GWB/PNT EXG/PNT GWB/PNT ACT
SECOND FLOOR 2A308G HR COPY/ SUPPLY LVT RB GWB/PNT GWB/PNT EXG/PNT GWB/PNT ACT
SECOND FLOOR 2A309 CALL CENTER CPTT RB GWB/PNT GWB/PNT GWB/PNT2 GWB/PNT ACT
SECOND FLOOR E300 ELEV LOBBY CONC/SLR ALUM BRICK ALUM/GLS EXG ALUM/GLS EXP/PNT
SECOND FLOOR E301 CORR LVT RB GWB/PNT GWB/PNT GWB/PNT GWB/PNT VARIES LWC WHERE SHOWN ON PLAN, SEE FINISH PLAN FOR PT4
ACCENT WALLS
SECOND FLOOR E302 STAIR CONC/SLR RB GWB/PNT BRICK GWB/PNT GWB/PNT EXP/PNT
12" = 1'-0"F1 FS-20RN 1HR/2HR - Sectional View
12" = 1'-0"D6 ALUMINUM WALL BASE
1" = 1'-0"D3 TYPICAL TILE PATTERN ELEVATION
12" = 1'-0"C6 COVE BASE DETAIL
Revisions: Date:
SPECIALITY EQUIPMENT SCHEDULE C/C
JSN NAME QTY ACQ/INST MANUFACTURER MODEL REMARKS
A1030 METAL LOCKERS 30 C / C LYON DOUBLE TIER
A1085 STAINLESS STEEL FRAMED MIRROR 12 C / C BOBRICK 24" X 42"
A5030 FOLDING SHOWER SEAT, TEAK, RECTANGULAR 30" 4 C / C Teakworks4u TBF-300160W MOUNT ON BLOCKING IN WALL TO HOLD MIN 350 # DOWNWARD FORCE A5036 FOLDING SHOWER SEAT, TEAK, RECTANGULAR 36" 1 C / C Teakworks4u TBF-360160W MOUNT ON BLOCKING IN WALL TO HOLD MIN 350 # DOWNWARD FORCE
A5075 AUTOMATIC WALL MOUNTED LIQUID SOAP DISPENSER 10 C / C GP ENMOTION 52060KB
A5080 RECESSED PAPER TOWEL DISPENSER / WASTE DISPOSAL UNIT 4 C / C Bobrick Washrom Equipment, Inc. B-38030 A5081 RECESSED WASTE PAPER DISPOSAL 1 C / C Bobrick Washroom Equipment, Inc. B-35633 A5082 8” RECESSED AUTOMATED TOUCHLESS PAPER TOWEL DISPENSER 4 C / C GP ENMOTION 59466A
A5090 SANITARY DISPOSAL 7 C / C BOBRICK B-270
A5109 12 C / C A5135 STAINLESS STEEL MOP RACK WITH 4 HOLDERS 2 C / C Eagle Group 24' - 321561 A5170 STRAIGHT SHOWER CURTAIN, ROD, AND HOOKS 5 C / C BOBRICK B-6107, 204-3 (Curtain), 204-1…