The project will seismically retrofit and renovate Building 3 at the Roseburg VA Healthcare System. The scope of work includes removing and replacing interior partition walls, ceilings, doors, and plumbing fixtures to bring the building into accessibility compliance. It will also add an elevator, exit stairs, and upgrade the interior and exterior. The drawings provide detailed plans, elevations, sections, and details for the architectural, structural, mechanical, electrical, and plumbing systems. The project is being procured through Solicitation 36C26024R0060, which is being issued by the Department of Veterans Affairs for the Veterans Integrated Service Network 20.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1) REMOVE EXISTING INTERIOR CLAY TILE PARTITION WALLS AND REPLACE WITH METAL STUD AND GYPSUM
BOARD WALLS IN A NEW CONFIGURATION;
2) REMOVE EXISTING SUSPENDED ACOUSTICAL PANEL CEILING TILES AND GRID
3) REMOVE EXISTING DOORS AND FRAMES IN EXISTING DEMO'D WALLS AND REPLACE AS REQUIRED.
4) REMOVE AND REPLACE TOILET ROOMS WITH CODE COMPLIANT TOILET ROOMS INCLUDING APPROPRIATE
FIXTURE COUNT FOR THE FACILITY TYPE AND OCCUPANT LOAD;
5) ADD AN ELEVATOR AND EXIT STAIRS AS REQUIRED FOR CODE COMPLIANT EXITING, RETAINING THE HISTORIC
NATURE OF THE BUILDING FROM THE EXTERIOR.
6) UPGRADE THE INTERIOR SPACES AND EXTERIOR APPROACH AS NECESSARY TO BRING THE BUILDING INTO
FULL ACCESSIBILITY COMPLIANCE;
7) REMOVE AND REPLACE ALL LIGHT FIXTURES WITH LED FIXTURES
9) REMOVE AND SALVAGE IN-CEILING HVAC UNITS, RECONFIGURE DUCT WORK AND REINSTALL IN NEW
CONFIGURATION AS REQUIRED
10) REMOVE AND SALVAGE ALL FIRE ALARM DEVICES AND REINSTALL IN NEW CONFIGURATION
11) REMOVE AND SALVAGE ALL SPRINKLER HEADS, RECONFIGURE PIPING AND REINSTALL HEADS IN NEW
CONFIGURATION AS REQUIRED.
VA HEALTHCARE SYSTEM
ROSEBURG, OR
PROJECT
LOCATION
ROSEBURG, OR
CONTRACTOR SHALL FURNISH THE RESIDENT ENGINEER WITH A SCHEDULE OF PHASING DATES ON WHICH THE CONTRACTOR INTENDS TO ACCOMPLISH WORK IN EACH SPECIFIC AREA OF SITE, BUILDING OR PORTION THEREOF. ARRANGE SUCH DATES TO INSURE ACCOMPLISHMENT OF THIS WORK IN SUCCESSIVE
PHASES MUTUALLY AGREEABLE TO MEDICAL CENTER DIRECTOR USING THE FOLLOWING PHASING
OUTLINE:
Phase 1 – Preparations: Early work to facilitate later phases.
1. The VA will relocate the building occupants prior to construction.
Phase 2 – Demolition and New Construction:
1.
X
Room Name
Ref
A101
A7.01 1
A7.024
ROOM NAME AND NUMBER
SECTION CALLOUT
MARK
DETAIL CALLOUT MARK
EXTERIOR OR INTERIOR
ELEVATION CALLOUT MARK
INTERIOR ELEVATION
CALLOUT MARK
DOOR TAG
MATERIAL FINISH TAG
SEE SCHEDULE SHEET AI104
WALL TYPE TAG
SEE SCHEDULE SHEET A-601
A1 A-101
PL1
SIGNAGE TAG
SEE SCHEDULE SHEET AW600
SN-X
1i EQUIPMENT TAG
SEE SCHEDULE SHEET A-604
NORTH ARROW
WINDOW / RELITE TAG
SEE SCHEDULE SHEET A-604
1t
PRINCIPAL IN CHARGE: Blue Trident, LLC Emmanuel (Manny) Bautista, PE*, F.SAME-----------(206) 972-0645 PROJECT MANAGER: Blue Trident, LLC Brian Moll, PE, SE ----------------------------------------(206) 351-2217 ARCHITECT: Blue Trident, LLC Lauri Strauss, AIA, LEED AP BD&C---------------------(907) 317-5040 STRUCTURAL ENGINEER: Reid Middleton Brian Matsumoto, PE, SE -----------------------------(206) 351-2217 MECHANICAL ENGINEER: Notkin P2S, inc Peter Eberle, PE----------------------------------------------(206) 267-6940 ELECTRICAL ENGINEER: SAZAN Group Guy Fox, PE---------------------------------------------------(503) 416-2078 FIRE PROTECTION ENGINEER: SAZAN Group Philip Roach, PE----------------------------------------------( ) CIVIL ENGINEER S&B Christ Consulting, LLC Peter Moser, PE----------------------------------------------(773) 744-4600 LANDSCAPE ARCHITECT Osborn Pacific Group Inc Linda Osborn--------------------------------------------------(206) 356-7000 HAZARDOUS MATERIALS MedTox NW. Chris Iott--------------------------------------------------------( ) COST ESTIMATOR: OCMI Conor Clark ---------------------------------------------------(714) 651-6696
VIEW FROM THE SOUTHWEST SHOWING NEW
STAIR TOWER AND SECOND FLOOR EXIT
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:1
PM
GI001
COVER
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 kh LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
SEISMIC RETROFIT AND RENOVATE BUILDING 3
DRAWING INDEX
SCOPE OF WORK
ABBREVIATIONS
RENDERING VICINITY MAP
PHASING SYMBOLS
VA Roseburg Healthcare System Project Number 653-21-102
PROJECT TEAM
A
ACT ACOUSTICAL CEILING TILE
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANNODIZED
APPROX APPROXIMATE
B
BD BOARD
BF BRACE FRAME
BLDG BUILDING
BLKG BLOCKING
BOD BOTTOM OF DECK
BOT BOTTOM
C
CAB CABINET(S)
CJ CONROL JOINT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
COL COLUMN
CONC CONCRETE
COR CONTRACTING OFFICERS
REPRESENTATIVE
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTB CERAMIC TILE COVE BASE
D
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFERENCE
DIM DIMENSION
DISP DISPENSER / DISPOSAL
DN DOWN
DWG DRAWING(S)
E
EA EACH
ELEC ELECTRIC
EQ EQUAL
EQUIP EQUIPMENT
GI001 COVER 1
GI002 CODE PLANS 2
H-101 HAZMAT - BASEMENT FLOOR S.. MATERIAL 4
H-102 HAZMAT - FIRST FLOOR. MATERIAL 5
H-103 HAZMAT - SECOND FLOOR MATERIAL 6
C-001 CIVIL LEGEND AND ABBREVIATIONS 7
CR101 SITE DEMOLITION PLAN 8
CS101 SITE PLAN 9
CG101 GRADING PLAN 1 10
CG102 GRADING PLAN 2 11
CD501 CIVIL DETAILS 12
LD101 LANDSCAPE DEMOLITION 13
LP101 LANDSCAPE PLAN 14
S-001 GENERAL STRUCTURAL NOTES 15
S-100 FOUNDATION PLAN 16
S-101 FIRST FLOOR FRAMING PLAN 17
S-102 SECOND FLOOR FRAMING PLAN 18
S-103 ATTIC FRAMING PLAN 19
S-104 ROOF FRAMING PLAN 20
S-201 BRACED FRAME ELEVATIONS 21
S-202 BRACED FRAME ELEVATIONS 22
S-203 WALL ELEVATIONS 23
S-204 WALL ELEVATIONS 24
S-205 WALL ELEVATIONS 25
S-206 WALL ELEVATIONS 26
S-401 ENLARGED FOUNDATION AND FRAMING PLANS 27
S-402 ENLARGED PLANS 28
S-500 CONCRETE DETAILS 29
S-501 FOIUNDATION DETAILS 30
S-502 FOUNDATION DETAILS 31
S-503 FLOOR FRAMING DETAILS 32
S-505 ROOF DETAILS 33
S-506 CONCRETE DETAILS 34
S-507 CONCRETE DETAILS 35
S-508 CONCRETE DETAILS 36
S-509 CONCRETE DETAILS 37
S-510 CONCRETE DETAILS 38
S-521 STEEL DETAILS 39
S-522 STEEL DETAILS 40
S-523 STEEL DETAILS 41
S-524 STEEL DETAILS 42
S-525 STEEL DETAILS 43
S-526 TYPICAL METAL DETAILS 44
S-530 TYPICAL WOOD DETAILS 45
AD101 BASEMENT DEMOLITION PLAN 46
AD111 FIRST FLOOR DEMOLITION PLAN 47
AD121 SECOND FLOOR DEMOLITION PLAN 48
AD500 DEMOLITION DETAILS 49
A-101 BASEMENT FLOOR PLAN 50
A-111 FIRST FLOOR PLAN 52
A-121 SECOND FLOOR PLAN 54
A-131 ATTIC PLAN 56
A-141 ROOF PLAN 57
A-201 EXTERIOR ELEVATIONS 58
A-202 EXTERIOR ELEVATIONS 59
A-301 N-S BUILDING SECTIONS 60
A-302 E-W BUILDING SECTIONS 61
A-303 STAIR SECTIONS 62
A-304 STAIR SECTIONS 63
A-310 WALL SECTIONS 64
A-320 SECTION DETAILS 65
A-401 ENLARGED BASEMENT PLANS 66
A-411 ENLARGED FIRST FLOOR PLANS 67
A-421 ENLARGED SECOND FLOOR PLANS 68
A-500 PLAN DETAILS 69
A-501 PLAN DETAILS 70
A-502 ROOF DETAILS 71
A-503 MISC DETAILS 72
A-504 MISC DETAILS 73
A-601 WINDOW TYPES AND DETAILS, WALL TYPES 74
A-602 DOOR SCHEDULE 75
A-603 CURTAIN WALL DETAILS 76
A-604 ROOM FINISH & EQUIPMENT SCHEDULES 77
A-801 INTERIOR ELEVATIONS 78
A-802 INTERIOR ELEVATIONS 79
A-803 INTERIOR ELEVATIONS 80
A-804 INTERIOR ELEVATIONS 81
A-805 INTERIOR ELEVATIONS 82
A-806 INTERIOR ELEVATIONS 83
A-807 INTERIOR ELEVATIONS 84
A-808 INTERIOR ELEVATIONS 85
A-809 INTERIOR ELEVATIONS 86
AC101 BASEMENT RCP 87
AC111 FIRST FLOOR RCP 88
AC121 SECOND FLOOR RCP 89
AW600 SIGNAGE 90
AI101 BASEMENT FINISH & FURNITURE PLAN 91
AI102 FIRST FLOOR FINISH & FURNITURE PLAN 92
AI103 SECOND FLOOR FINISH & FURNITURE PLAN 93
AI104 COLOR PALLETTE 94
EXG EXISTING
EXP JT EXPANSION JOINT
EXT EXTERIOR
F
FACP FIRE ALARM CONTRL PANEL
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FIN FINISH
FLR FLOOR
FOC FACE OF CABINET
FOF FACE OF FINISH
FOS FACE OF STUD
FOW FACE OF WALL
G
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GEN GENERAL
GLU-LAM GLUE LAM BEAM
GWB GYPSUM WALL BOARD
GYP GUPSUM
H
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HVAC HEATING VENTILATION AIR
CONDITIONING
I
IBC INTERNATIONAL BUILDING
CODE
ID INTERIOR DESIGN
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J
JAN JANITOR
JT JOINT
K
KIT KITCHEN
L
LAM LAMINATED
LAV LAVATORY
LF LINEAR FEEET
M
MATL MATERIAL
MAX MAXIMUM
MBL MARBLE
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MS METAL STUD
MTD MOUNTED
MTL METAL
N
NA NOT APPLICABLE
NAP NAPKIN
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
P
PAF POWER ACTIVATED
FASTENERS
PLAM PLASTIC LAMINATE
PLWD PLYWOOD
PREFAB PRE FABRICATED
PREFIN PRE FINISHED
PT PAINT
PTD PAPER TOWEL DISPENSER
PTN PARTITION
Q
QT QUARRY TILE
R
RAD RADIUS
RB RUBBER
RCP REFLECETED CEILING PLAN
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
RESIL RESILIENT
S
SAN SANITARY
SCHED SCHEDULE
SD SOAP DISPENSER
SF SQUARE FOOT
SHT SHEET
SHWR SHOWER
SIM SIMILAR
SND SANITARY NAPKIN DISPOSAL
SS SOLID SURFACE
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STO STORAGE
STS SELF TAPPING SCREW
T
TB TOWEL BAR
TEMP TEMPORARY
THK THICK
THRU THROUGH
TLT TOILET
TO TOP OF
TPD TOILET PAPER DISPENSER
TPTN TOILET PARTITION
TR TRASH RECEPTACLE
TYP TYPICAL
TZO TERRAZZO
U
UC UNDER COUNTER / UNDER
CABINET
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
V
VAR VARIES
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
W
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WR WATER RESISTANT
WWF WELDED WIRE FABRIC
AREA COMPARISON
RM
NUM ROOM NAME
NET
AREA
Required
Area % AREA
BASEMENT
BA109 VEST M 44 SF 40 SF 111%
BA111 LOCKER M 86 SF 120 SF 71%
BA110 TOILET M 125 SF 120 SF 104%
BA110a SHOWER M1 32 SF 140 SF 23%
BA103 VEST W 48 SF 40 SF 121%
BA104 LOCKER W 118 SF 180 SF 65%
BA105 TOILET W 139 SF 120 SF 116%
BA106 SHOWER W 77 SF 140 SF 55%
BA107 UNIFORMS 157 SF 100 SF 157%
BA113 EMS CHIEF 104 SF 100 SF 104%
BA101 EMS AO 106 SF 56 SF 189%
BA115 BREAK ROOM 241 SF 300 SF 80%
BA119 EMS INT DESIGNER 79 SF 56 SF 140%
BA117 LG EQPT STORAGE 907 SF 900 SF 101%
BA108 EMS STORAGE 320 SF 300 SF 107%
BA122 ELECT 320 SF
BA112 UTIL 44 SF
BA114 EMS ASST CHIEF 105 SF 100 SF 105%
BA118 EMS SUPER 119 SF 150 SF 80%
BA120 EMS TRAINING SUPER 101 SF 150 SF 67%
BA121 MACH ROOM 39 SF
E100 ELEV. 91 SF
E102 STAIR 1 122 SF
E100 ELEV LOBBY 135 SF
E101 CORR 409 SF
BA102 EMS SUPPORT 91 SF
BA110b SHWR M2 17 SF
BA116 HAC 25 SF
FIRST FLOOR
1A201 TOILET W 110 SF 120 SF 92%
1A202 TOILET M 97 SF 120 SF 81%
1A204 FLEET 103 SF 100 SF 103%
1A203 UNION 87 SF 300 SF 29%
1A206 BILLING 250 SF 300 SF 83%
1A207 FS SUPPORT 124 SF 112 SF 111%
1A207B FISCAL SERV. AUDITOR 103 SF 100 SF 103%
1A212 IT 94 SF 100 SF 94%
1A207A FISCAL SERV AUDITOR 100 SF 100 SF 100%
1A210 FS CHIEF 100 SF 100 SF 100%
1A211 FS ASST CHIEF 100 SF 100 SF 100%
1A209B HBPC DIRECTOR 105 SF 100 SF 105%
1A209A HBPC CHIEF 105 SF 100 SF 105%
E200 ELEV LOBBY 138 SF
E201 CORR 552 SF
1A207C FS STOR 21 SF 80 SF 26%
1A209 HBPC SUPPORT 392 SF 212 SF 185%
1A203A UN OFFC 101 SF
1A203B UN OFFC 94 SF
1A205 VISN 1 309 SF
1A206A REVENUE MGR 102 SF
1A203C STOR 9 SF
1A209C HBPC CLEAN STOR 61 SF
1A208 HAC 26 SF
E202 STAIR 226 SF
SECOND FLOOR
2A302 TOILET M 97 SF 120 SF 81%
2A301 TOILET W 110 SF 120 SF 92%
2A309 CALL CENTER 226 SF 200 SF 113%
2A308 HR SUPPORT 381 SF 480 SF 79%
2A303 SHARED CONF/TRAIN 335 SF 300 SF 112%
2A304B LOG CHIEF 103 SF 100 SF 103%
2A304A LOG ASST CHIEF 102 SF 100 SF 102%
2A304 LOGISTICS SUPPORT 257 SF 168 SF 153%
2A308C HR DIRECTOR 105 SF 100 SF 105%
2A308E HR CHIEF 105 SF 100 SF 105%
2A307 FLEX SPACE 109 SF
2A306 LOG SUPERVISOR 112 SF
E300 ELEV LOBBY 138 SF
E301 CORR 414 SF
2A308B HR SUPERVISOR 108 SF 80 SF 135%
2A308G HR COPY/ SUPPLY 56 SF 80 SF 70%
2A308D HR WORK STATIONS 188 SF 160 SF 117%
2A308F HR RECORDS 65 SF 100 SF 65%
2A304C LOG SUPPLY 48 SF 120 SF 40%
2A305 LOG SUPERVISOR 109 SF
2A308A P.I.V. 155 SF
E302 STAIR 226 SF
11261 SF
FA001 FIRE ALARM GENERAL NOTES AND ABBREVIATIONS 95
FD101 PROTECTION DEMOLITION - GROUND FLOOR PLAN 96
FD102 FIRE PROTECTION DEMOLITION - FIRST FLOOR PLAN 97
FD103 FIRE PROTECTION DEMOLITION - SECOND FLOOR
PLAN
FD104 FIRE PROTECTION DEMOLITION - ATTIC PLAN 99
FXD101 FIRE SPRINKLER - BASEMENT FLOOR DEMO PLAN 100
FA101 FIRE ALARM - GROUND FLOOR PLAN 101
FA102 FIRE ALARM - FIRST FLOOR PLAN 102
FA103 FIRE ALARM - SECOND FLOOR PLAN 103
FA104 FIRE ALARM - ATTIC FLOOR PLAN 104
FA601 FIRE ALARM DIAGRAM 105
FX101 FIRE SPRINKLER - GROUND FLOOR PLAN 106
FX102 FIRE SPRINKLER - FIRST FLOOR PLAN 107
FX103 FIRE SPRINKLER - SECOND FLOOR PLAN 108
FX104 FIRE SPRINKLER - ATTIC FLOOR PLAN 109
P-001 PLUMBING LEGEND AND DRAWING INDEX 110
PD101 GROUND FLOOR DEMOLITION PLAN 111
PD111 FIRST FLOOR DEMOLITION PLAN 112
PD121 SECOND FLOOR DEMOLITION PLAN 113
PD131 ATTIC DEMOLITION PLAN 114
P-100 UNDERFLOOR PLUMBING PLAN 115
P-101 GROUND FLOOR PLUMBING PLAN 116
P-111 FIRST FLOOR PLUMBING PLAN 117
P-121 SECOND FLOOR PLUMBING PLAN 118
P-401 ENLARGED PLUMBING PLANS 119
P-402 ENLARGED PLUMBING PLANS 120
P-501 PLUMBING DETAILS 121
P-601 PLUMBING SCHEDULES 122
P-901 PLUMBING RISER DIAGRAMS 123
M-001 MECHANICAL LEGEND AND GENERAL NOTES 124
MD101 GROUND FLOOR DEMOLITION PLAN 125
MD111 FIRST FLOOR DEMOLITION PLAN 126
MD121 SECOND FLOOR DEMOLITION PLAN 127
MD131 ATTIC DEMOLITION PLAN 128
M-101 GROUND FLOOR PLAN 129
M-111 FIRST FLOOR PLAN 130
M-121 SECOND FLOOR PLAN 131
M-131 ATTIC PLAN 132
MP101 GROUND FLOOR PIPING PLAN 133
MP111 FIRST FLOOR PIPING PLAN 134
MP121 SECOND FLOOR PIPING PLAN 135
M-501 MECHANICAL DETAILS 136
M-502 MECHANICAL DETAILS 137
M-601 MECHANICAL SCHEDULES 138
M-701 GROUND FLOOR ZONING PLAN 139
M-711 FIRST FLOOR ZONING PLAN 140
M-721 SECOND FLOOR ZONING PLAN 141
M-801 CONTROLS 142
M-802 CONTROLS 143
EG001 ELECTRICAL LEGEND AND GENERAL NOTES 144
ED101 GROUND FLOOR DEMOLITION PLAN 145
ED102 FIRST FLOOR DEMOLITION PLAN 146
ED103 SECOND FLOOR DEMOLITION PLAN 147
ED104 ATTIC DEMOLITION PLAN 148
ES101 ELECTRICAL LIGHTING - SITE PLAN 149
EL101 ELECTRICAL LIGHTING - GROUND FLOOR PLAN 150
EL102 ELECTRICAL LIGHTING - FIRST FLOOR PLAN 151
EL103 ELECTRICAL LIGHTING - SECOND FLOOR PLAN 152
EL601 ELECTRICAL LIGHTING - SCHEDULES 153
EL602 ELECTRICAL LIGHTING - SCHEDULES 154
EP101 ELECTRICAL POWER - GROUND FLOOR PLAN 155
EP102 ELECTRICAL POWER - FIRST FLOOR PLAN 156
EP103 ELECTRICAL POWER - SECOND FLOOR PLAN 157
EP104 ELECTRICAL POWER - ATTIC PLAN 158
EP501 ELECTRICAL DETAILS 159
EP502 ELECTRICAL DETAILS 160
EP601 ELECTRICAL ONE-LINE DIAGRAM 161
EP602 ELECTRICAL EQUIPMENT SCHEDULE 162
EP603 ELECTRICAL PANEL SCHEDULES 163
EP604 ELECTRICAL PANEL SCHEDULES 164
TN001 TELECOMMUNICATIONS GENERAL NOTES AND
LEGEND
TD101 SYSTEM DEMOLITION - GROUND FLOOR PLAN 166
TD102 SYSTEM DEMOLITION - FIRST FLOOR PLAN 167
TD103 SYSTEM DEMOLITION - SECOND FLOOR PLAN 168
TN101 SYSTEM COMMUNICATION - GROUND FLOOR PLAN 169
TN102 SYSTEM COMMUNICATION - FIRST FLOOR PLAN 170
TN103 SYSTEM COMMUNICATION - SECOND FLOOR PLAN 171
TN501 SYSTEMS DETAILS 172
Revisions: Date:
WH
FD
FD
FD
FD
FD
FD
FD
FD FD
157 SF
UNIFORMS
BA107
91 SF
EMS SUPPORT
BA102
106 SF
EMS AO
BA101
104 SF
EMS CHIEF
BA113
105 SF
EMS ASST
CHIEF
BA114
241 SF
BREAK ROOM
BA115
101 SF
EMS TRAINING
SUPER
BA120
79 SF
EMS INT
DESIGNER
BA119 119 SF
EMS SUPER
BA118
907 SF
LG EQPT
STORAGE
BA117320 SF
EMS STORAGE
BA108 320 SF
ELECT
BA122
9 13
6160 MIN DOOR
FEC
30' - 1" 21' - 11"
FE FE
5 1 /4"
5'
- 4
3/ 4"
1-HR CEILING UNDER
DUCT 90 - SEAL FLOOR
PENETRATIONS WITH
1-HR CONSTRUCT.
SEAL FLOOR/ CEILING
PENETRATIONS WITH
1-HR CONSTRUCT. AT
MECH CHASE THRU
FLOOR ABOVE
1-HR ENCLOSURE UNDER
STAIR FOR ELEVATOR EQUIP.
60 MIN
DOOR
60 MIN
DOOR
103 SF
FLEET
1A204 94 SF
UN OFFC
1A203B
87 SF
UNION
1A203
101 SF
UN OFFC
1A203A
309 SF
VISN 1
1A205
250 SF
BILLING
1A206
102 SF
REVENUE MGR
1A206A
100 SF
FISCAL SERV
AUDITOR
1A207A 124 SF
FS SUPPORT
1A207
103 SF
FISCAL SERV.
AUDITOR
1A207B
105 SF
HBPC CHIEF
1A209A
392 SF
HBPC
SUPPORT
1A209
105 SF
HBPC
DIRECTOR
1A209B
61 SF
HBPC CLEAN
STOR
1A209C100 SF
FS ASST CHIEF
1A211
94 SF
IT
1A212
15 5 5
100 SF
FS CHIEF
1A210
60 MIN DOOR ON
MAG HOLD OPEN
FEC
FECEXISTING HISTORIC DOOR
ALLOWED TO SWING IN
PER NFPA 101, 43.10.4.4
SEAL FLOOR/ CEILING
PENETRATIONS WITH
1-HR CONSTRUCT.
1-HR RATED MECH
CHASE ENCLOSURE
36' - 8"
FEC
335 SF
SHARED
CONF/TRAIN
2A303
257 SF
LOGISTICS
SUPPORT
2A304
103 SF
LOG CHIEF
2A304B
102 SF
LOG ASST
CHIEF
2A304A
109 SF
LOG
SUPERVISOR
2A305
48 SF
LOG SUPPLY
2A304C
112 SF
LOG
SUPERVISOR
2A306
109 SF
FLEX SPACE
2A307
155 SF
P.I.V.
2A308A
108 SF
HR
SUPERVISOR
2A308B
226 SF
CALL CENTER
2A309 65 SF
HR RECORDS
2A308F
56 SF
HR COPY/
SUPPLY
2A308G
105 SF
HR CHIEF
2A308E
188 SF
HR WORK
STATIONS
2A308D
105 SF
HR DIRECTOR
2A308C
12 13 11 381 SF
HR SUPPORT
2A308
60 MIN DOOR
ON MAG
HOLD-OPEN
FEC
FEC16
SEAL FLOOR/ CEILING
PENETRATIONS WITH
1-HR CONSTRUCT.
1-HR RATED
MECHANICAL CHASE
ENCLOSURE
SEAL FLOOR/ CEILING
PENETRATIONS WITH
1-HR CONSTRUCT.
14' - 11 1/4"
FEC
BUILDING TYPE = MEDICAL CLINIC 'B'
CODE: NFPA 13, 70, 72, 90A, 101 (INCL CH 43.10)
IEBC 2021
THE BUIILDING IS PROVIDED THROUGHOUT WITH AN APPROVED
AUTOMATIC FIRE SPRINKLER SYSTEM.
USE AND OCCUPANCY (SAME AS EXISTING- NO CHANGE IN OCCUPANCY)
BUSINESS OCCUPANCY GROUP B
INCIDENTAL USE AREAS WITHIN PROJECT SCOPE:
ELECTRICAL ROOM (EXG SMOKE SEPARATION PROVIDED)
STORAGE ROOMS <100 S.F. - SMOKE SEPARATION PROVIDED
CONSTRUCTION TYPE
TYPE V-000 – NON-COMBUSTIBLE - FULLY SPRINKLERED
BUILDING AREA HEIGHT AND AREA IS NOT CHANGING - LIMITATIONS:
GENERAL BUILDING HEIGHTS AND AREAS
BASIC ALLOWABLE AREA (TABLE 503) 27,000 S.F.
BASIC ALLOWABLE HEIGHT 3 STORIES – 60’-0”
ACTUAL AREA AND HEIGHT
AREA ACTUAL 13,305 S.F.
GROUND FLOOR 4841 S.F.
1ST FLOOR 4227 S.F.
2ND FLOOR 4237 S.F.
HEIGHT ACTUAL 3 STORY - 44'-10"
RATED ASSEMBLIES WITHIN THE PROJECT AREA REQUIRED:
STORAGE > 100 S.F. = 1 HOUR
MECHANICAL SHAFTS = 1-HOUR
EGRESS STAIRWAYS = 1-HOUR
CORRIDORS W/SPRINKLERS: NONE (NFPA 101, 7.1.3.1)
(NFPA 101, 7.1.3.1 - CORRIDORS ARE NOT REQUIRED TO BE RATED IN AN
EXISTING BUILDING WHERE THE OCCUPANCY CLASS IS NOT CHANGING.)
OCCUPANT LOAD
STORAGE AND MECHANICAL AREAS DO NOT CONTRIBUTE PER NFPA
OCCUPANT LOAD OF THE BUILDING:
SPACE OCC AREA S.F./ OCC NO. OF OCC.
BASEMENT OFFICES 2744 150 19
STORAGE 1311 300 5
FIRST FLOOR 3768 150 26
SECOND FLOOR 3768 150 26
TOTAL BUILDING OCCUPANT LOAD 76 OCCUPANTS
MINIMUM NUMBER OF EXITS: NFPA 101, 7.4.1
BASEMENT:
ONE EXIT PER NFPA 39.2.4.4. (LESS THAN 30 OCCUPANTS PER FLOOR, EXIT
DISCHARGE DIRECTLY TO OUTSIDE, EXIT IS ENCLOSED)
FIRST FLOOR:
MINIMUM NUMBER OF EXITS = 2 - NUMBER OF EXIT PROVIDED = 3
SECOND FLOOR:
MINIMUM NUMBER OF EXITS = 2 - NUMBER OF EXIT PROVIDED = 3
EXIT SEPARATION: NFPA 101 7.1.3.2.1
MINIMUM 1 HOUR SERVING THREE STORIES - PROVIDED 1-HOUR SEP.
ONLY ALLOWED PENETRATIONS (LIMITED PER NFPA 101, 7.1.3.2.1.(9)) ARE
PROVIDED.
MINIMUM DOOR LEAF: NFPA 7.2.1.2.3.
32" - MINIMUM DOOR LEAF WIDTH PROVIDED = 36"
COMMON PATH OF TRAVEL DISTANCE MEASURED:
BASEMENT: 65' MAX (TO EXIT DISCHARGE)
FIRST FLOOR: 48' MAX
SECOND FLOOR: 16' MAX
MAXIMUM TRAVEL DISTANCE MEASURED: NFPA 101, 39.2.6.3
300' MAX ALLOWED IN BUSINESS OCC W/ FIRE SPRINKLER
BASEMENT: 65' MAX (TO EXIT DISCHARGE)
FIRST FLOOR: 85' MAX
SECOND FLOOR: 140' MAX
CAPACITY OF MEANS OF EGRESS: NFPA 101, 39.2.3
ALL CORRIDORS WITHIN THE PROJECT AREA ARE 44" MIN.
STAIRS: NFPA 101 7.2.22.22.1.2 (A) - MINIMUM WIDTH = 36"
DIMENSION LIMITS PROVIDED:
RISERS = 7" MAX, 4" MIN
TREAD DEPTH = 11" MIN
HEADROOM = 6'8" MIN
LANDING WIDTH = SAME AS STAIR MIN.
HEIGHT BETWEEN LANDINGS = 12' MAX
OUTSIDE STAIRS: NFPA 101, 7.2.2.6
VISUAL PROTECTION REQURIED FOR LANDINGS MKORE THAN 36'
ABOVE GRADE - DISTANCE TO SECOND FLOOR IS 21' ABOVE GRADE
FIRE RATING IS NOT REQUIRED PER NFPA 120, 7.2.2.6.3.1.(2) AND (5)
PORTABLE FIRE EXTINGUISHERS: NFPA 10, 6.2.1.2.2.
ARE PROVIDED ON EACH FLOOR WITH LESS THAN 75' TRAVEL DISTANCE
TO EACH.
SMOKE PARTITION
REFERENCE NFPA 8.4
1-HR FIRE RESISTANT
RATED BARRIER
2-HR FIRE RESISTANT
RATED BARRIER
HORIZONTAL SMOKE
BARRIER CEILING
ASSEMBLY
HORIZONTAL 1-HR FIRE-
RESISTANT RATED
ASSEMBLY (ABOVE)
LIFE/SAFETY LEGEND
BUILDING EXIT
EXIT ROUTE
FEC (NEW)
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2' 1/ 2'
1' 0'
3' 0'
1'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
2'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C :\U se rs
\la ur i\O ne
D riv e\ d2
L- Pr oj ec ts \2
7-
1_
R os eb ur g B3
\0 4-
D
ES
IG
N
\R
EV
IT
\R
O
SE
BU
R
G
A R
C H
3.
rv t
/6 /2
6:
:2
PM
GI002
CODE PLANS
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11-7-2023 kh LMS
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
1/8" = 1'-0"F6 BASEMENT CODE PLAN
1/8" = 1'-0"F1 FIRST FLOOR CODE PLAN
1/8" = 1'-0"C1 SECOND FLOOR CODE PLAN
Revisions: Date:
LEGEND:
ACM VFT AND ACM MASTIC
GENERAL NOTES
1. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DRAWINGS FOR
REQUIRED PROJECT DETAILS AND COORDINATION.
2. ASBESTOS MATERIALS HAVE BEEN IDENTIFIED IN THE PROJECT AREA. ANY ASBESTOS-CONTAINING
MATERIALS THAT WILL BE IMPACTED BY THE PLANNED RENOVATION MUST BE REMOVED AND
DISPOSED OF PRIOR TO BEING DISTURBED.
3. FRIABLE AND NON-FRIABLE ASBESTOS THAT WILL BE IMPACTED BY RENOVATION ACTIVITIES MUST BE
REMOVED AND DISPOSED OF PROPERLY. ALL ASBESTOS WASTE WILL BE DISPOSED OF IN
ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19 AND APPLICABLE REGULATIONS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND OBSTRUCTIONS. REFER TO BUILDING AS-BUILTS INCLUDING RENOVATION AS BUILTS FOR DETAILS.
5. ALL PAINTED SURFACES ARE ASSUMED TO CONTAIN AT LEAST TRACE LEVELS OF LEAD AND OTHER METALS; INCLUDING INTERIOR AND EXTERIOR PAINTS. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL HAVE LEAD AWARENESS TRAINING IN ACCORDANCE WITH 29 CFR 1926.62; THIS
INCLUDES ALL TRADES IMPACTING PAINTED SURFACES.
6. CONTRACTOR MUST SUBMIT ASBESTOS, LEAD, OTHER METALS. AND PCB ABATEMENT PLANS TO THE
VETERANS ADMINISTRATION (VA) FOR REVIEW AND APPROVAL PRIOR TO START OF WORK
ACTIVITIES.
ASBESTOS NOTES
1. ALL ASBESTOS WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19.
2. THE ASBESTOS-CONTAINING MATERIALS IDENTIFIED ON THE DRAWING ARE SHOWN FOR REFERENCE.
THERE ARE PLANNED IMPACTS TO THE 9-INCH TAN STREAKED VINYL FLOOR TILE (VFT) WITH BLACK MASTIC SHOWN ON THE 1ST FLOOR AND THE 12-INCH ORANGE VFT WITH MASTIC SHOWN ON THE 2ND
AND 3RD FLOORS.
3. THE GENERAL CONTRACTOR AND ABATEMENT CONTRACTOR SHALL FIELD VERIFY ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DETAILS AND DIMENSIONS THAT MAY IMPACT THE
WORK. THE CONTRACTOR SHALL VERIFY THE CONDITION, LOCATION, AND QUANTITIES OF
HAZARDOUS MATERIALS IN THE WORK AREA PRIOR TO SUBMITTING A BID.
4. REFER TO 02 82 13 19 AND CONTRACTOR'S APPROVED WORK PLAN FOR ASBESTOS REMOVAL AND
DISPOSAL PROCEDURES AND REQUIREMENTS.
5. THE CONTRACTOR IS REQUIRED TO READ THE INDIVIDUAL HAZARDOUS MATERIALS SURVEY REPORT FOR BUILDING 3 SUBMITTED BY MED-TOX NORTHWEST DATED DECEMBER 2022. THE CONTRACTOR IS TO FIELD VERIFY THE LIMITATIONS SECTIONS IDENTIFIED IN THE REPORT FOR THE DETERMINATION
OF HIDDEN MATERIALS.
LEAD-BASED PAINT NOTES
1. REFER TO SPECIFICATION SECTION 02 83 33 13 FOR LEAD REQUIREMENTS INCLUDING DISPOSAL AND
TESTING REQUIREMENTS.
2. THE CONTRACTOR SHALL ASSUME THAT LEAD IS PRESENT IN PAINTED OR PRIMERED SURFACES THROUGHOUT THE PROJECT. ALL WORK THAT MAY DISTURB PAINT OR PRIMER-CONTAINING LEAD OR OTHER LEAD BUILDING MATERIAL (SUCH AS CERAMIC TILE) SHALL BE IN ACCORDANCE WITH 29 CFR 1926.62 AND SPECIFICATION SECTION 02 83 33 13 INCLUDING DUST CONTROL, EMPLOYEE
EXPOSURE ASSESSMENTS, AND WASTE CHARACTERIZATION.
PCB BALLASTS AND FLOURESCENT LIGHT TUBE NOTES
1. ALL FLUORESCENT LIGHTS TO BE DEMOLISHED SHALL BE INSPECTED. ALL BALLASTS NOT
SPECIFICALLY LABELED AS “NO-PCBS” OR “PCB FREE” WILL BE ASSUMED TO BE PCB-CONTAINING AND BE REMOVED AND DISPOSED OF AS PCB WASTE IN ACCORDANCE WITH THE REGULATIONS. PARTIAL DISASSEMBLY OF FLUORESCENT FIXTURES AND SELECTIVE DEMOLITION FOR ACCESS ARE INCLUDED
IN THE SCOPE OF WORK. REFER TO CONTRACT SPECIFICATIONS, ELECTRICAL DEMOLITION
DRAWINGS, REGULATIONS, AND CONTRACTOR'S APPROVED WORK PLAN FOR PCB-BALLAST REMOVAL
AND DISPOSAL PROCEDURES. HID LIGHTS ARE ASSUMED TO CONTAIN PCB-BALLASTS AND
MERCURY-CONTAINING BULBS.
2. NON-PCB LIGHT BALLASTS ARE TO BE RECYCLED OR DISPOSED IN ACCORDANCE WITH 02 84 16.
3. ALL FLUORESCENT LIGHT TUBES AND HID LIGHT BULBS ARE ASSUMED MERCURY-CONTAINING.
MERCURY-CONTAINING LIGHT TUBES/BULBS SHALL BE RECYCLED IN ACCORDANCE WITH THE
CONTRACT AND WITHOUT BREAKAGE ON SITE. REFER TO CONTRACT SPECIFICATIONS/DRAWINGS, REGULATIONS, AND CONTRACTORS APPROVED WORK PLAN FOR LIGHT TUBE RECYCLING
PROCEDURES.
4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ELECTRICAL ISOLATION OF ALL IMPACTED
LIGHT FIXTURES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
H-101
MATERIAL
LOCATION
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMIC RETROFIT AND
RENOVATION BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11/07/2023 AF CBS
FULLY SPRINKLERED
Revisions: Date:
http://www.medtoxnw@msn.com
ED-TOX
SAFE ENVIROMENT OF AMERICA, INC dba
NORTHWEST
OCCUPATIONAL ENVIROMENTAL HEALTH SERVICES
(253) 351-0677 (253) 351-0688 (FAX)
129 A STREET N.W.
AUBURN, WASHINGTON 98001
ACM FLOOR TITLE MASTIC TO BE REMOVED 60 SQ FT
ISSUED FOR
CONSTRUCTION
AutoCAD SHX Text E102
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text E104
AutoCAD SHX Text
AutoCAD SHX Text E200
AutoCAD SHX Text
AutoCAD SHX Text E100
AutoCAD SHX Text E201
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text 101A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MATCHLINE
AutoCAD SHX Text
MATCHLINE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
FIRST FLOOR (SOUTH) MATERIAL LOCATIONS SAMPLE LOCATIONS SCALE: NTS
ACM FLOOR TILE MASTIC
GENERAL NOTES
1. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DRAWINGS FOR
REQUIRED PROJECT DETAILS AND COORDINATION.
2. ASBESTOS MATERIALS HAVE BEEN IDENTIFIED IN THE PROJECT AREA. ANY ASBESTOS-CONTAINING
MATERIALS THAT WILL BE IMPACTED BY THE PLANNED RENOVATION MUST BE REMOVED AND
DISPOSED OF PRIOR TO BEING DISTURBED.
3. FRIABLE AND NON-FRIABLE ASBESTOS THAT WILL BE IMPACTED BY RENOVATION ACTIVITIES MUST BE
REMOVED AND DISPOSED OF PROPERLY. ALL ASBESTOS WASTE WILL BE DISPOSED OF IN
ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19 AND APPLICABLE REGULATIONS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND OBSTRUCTIONS. REFER TO BUILDING AS-BUILTS INCLUDING RENOVATION AS BUILTS FOR DETAILS.
5. ALL PAINTED SURFACES ARE ASSUMED TO CONTAIN AT LEAST TRACE LEVELS OF LEAD AND OTHER METALS; INCLUDING INTERIOR AND EXTERIOR PAINTS. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL HAVE LEAD AWARENESS TRAINING IN ACCORDANCE WITH 29 CFR 1926.62; THIS
INCLUDES ALL TRADES IMPACTING PAINTED SURFACES.
6. CONTRACTOR MUST SUBMIT ASBESTOS, LEAD, OTHER METALS. AND PCB ABATEMENT PLANS TO THE
VETERANS ADMINISTRATION (VA) FOR REVIEW AND APPROVAL PRIOR TO START OF WORK
ACTIVITIES.
ASBESTOS NOTES
1. ALL ASBESTOS WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19.
2. THE ASBESTOS-CONTAINING MATERIALS IDENTIFIED ON THE DRAWING ARE SHOWN FOR REFERENCE.
THERE ARE PLANNED IMPACTS TO THE 9-INCH TAN STREAKED VINYL FLOOR TILE (VFT) WITH BLACK MASTIC SHOWN ON THE 1ST FLOOR AND THE 12-INCH ORANGE VFT WITH MASTIC SHOWN ON THE 2ND
AND 3RD FLOORS.
3. THE GENERAL CONTRACTOR AND ABATEMENT CONTRACTOR SHALL FIELD VERIFY ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DETAILS AND DIMENSIONS THAT MAY IMPACT THE
WORK. THE CONTRACTOR SHALL VERIFY THE CONDITION, LOCATION, AND QUANTITIES OF
HAZARDOUS MATERIALS IN THE WORK AREA PRIOR TO SUBMITTING A BID.
4. REFER TO 02 82 13 19 AND CONTRACTOR'S APPROVED WORK PLAN FOR ASBESTOS REMOVAL AND
DISPOSAL PROCEDURES AND REQUIREMENTS.
5. THE CONTRACTOR IS REQUIRED TO READ THE INDIVIDUAL HAZARDOUS MATERIALS SURVEY REPORT FOR BUILDING 3 SUBMITTED BY MED-TOX NORTHWEST DATED DECEMBER 2022. THE CONTRACTOR IS TO FIELD VERIFY THE LIMITATIONS SECTIONS IDENTIFIED IN THE REPORT FOR THE DETERMINATION
OF HIDDEN MATERIALS.
LEAD-BASED PAINT NOTES
1. REFER TO SPECIFICATION SECTION 02 83 33 13 FOR LEAD REQUIREMENTS INCLUDING DISPOSAL AND
TESTING REQUIREMENTS.
2. THE CONTRACTOR SHALL ASSUME THAT LEAD IS PRESENT IN PAINTED OR PRIMERED SURFACES THROUGHOUT THE PROJECT. ALL WORK THAT MAY DISTURB PAINT OR PRIMER-CONTAINING LEAD OR OTHER LEAD BUILDING MATERIAL (SUCH AS CERAMIC TILE) SHALL BE IN ACCORDANCE WITH 29 CFR 1926.62 AND SPECIFICATION SECTION 02 83 33 13 INCLUDING DUST CONTROL, EMPLOYEE
EXPOSURE ASSESSMENTS, AND WASTE CHARACTERIZATION.
PCB BALLASTS AND FLOURESCENT LIGHT TUBE NOTES
1. ALL FLUORESCENT LIGHTS TO BE DEMOLISHED SHALL BE INSPECTED. ALL BALLASTS NOT
SPECIFICALLY LABELED AS “NO-PCBS” OR “PCB FREE” WILL BE ASSUMED TO BE PCB-CONTAINING AND BE REMOVED AND DISPOSED OF AS PCB WASTE IN ACCORDANCE WITH THE REGULATIONS. PARTIAL DISASSEMBLY OF FLUORESCENT FIXTURES AND SELECTIVE DEMOLITION FOR ACCESS ARE INCLUDED
IN THE SCOPE OF WORK. REFER TO CONTRACT SPECIFICATIONS, ELECTRICAL DEMOLITION
DRAWINGS, REGULATIONS, AND CONTRACTOR'S APPROVED WORK PLAN FOR PCB-BALLAST REMOVAL
AND DISPOSAL PROCEDURES. HID LIGHTS ARE ASSUMED TO CONTAIN PCB-BALLASTS AND
MERCURY-CONTAINING BULBS.
2. NON-PCB LIGHT BALLASTS ARE TO BE RECYCLED OR DISPOSED IN ACCORDANCE WITH 02 84 16.
3. ALL FLUORESCENT LIGHT TUBES AND HID LIGHT BULBS ARE ASSUMED MERCURY-CONTAINING.
MERCURY-CONTAINING LIGHT TUBES/BULBS SHALL BE RECYCLED IN ACCORDANCE WITH THE
CONTRACT AND WITHOUT BREAKAGE ON SITE. REFER TO CONTRACT SPECIFICATIONS/DRAWINGS, REGULATIONS, AND CONTRACTORS APPROVED WORK PLAN FOR LIGHT TUBE RECYCLING
PROCEDURES.
4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ELECTRICAL ISOLATION OF ALL IMPACTED
LIGHT FIXTURES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
H-102
MATERIAL
LOCATION
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMIC RETROFIT AND
RENOVATION BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11/07/2023 AF CBS
FULLY SPRINKLERED
Revisions: Date:
http://www.medtoxnw@msn.com
ED-TOX
SAFE ENVIROMENT OF AMERICA, INC dba
NORTHWEST
OCCUPATIONAL ENVIROMENTAL HEALTH SERVICES
(253) 351-0677 (253) 351-0688 (FAX)
129 A STREET N.W.
AUBURN, WASHINGTON 98001
ACM FLOOR TITLE MASTIC TO BE REMOVED 1750 SQ FT
ISSUED FOR
CONSTRUCTION
AutoCAD SHX Text E102
AutoCAD SHX Text
PORCH
AutoCAD SHX Text A209
AutoCAD SHX Text A211
AutoCAD SHX Text A208
AutoCAD SHX Text A210
AutoCAD SHX Text A206
AutoCAD SHX Text A207
AutoCAD SHX Text A203
AutoCAD SHX Text A204
AutoCAD SHX Text A201
AutoCAD SHX Text E203
AutoCAD SHX Text B201
AutoCAD SHX Text
TELECOM CLOSET
AutoCAD SHX Text B202
AutoCAD SHX Text B203
AutoCAD SHX Text B202A
AutoCAD SHX Text B203C
AutoCAD SHX Text B203A
AutoCAD SHX Text B203B
AutoCAD SHX Text E202
AutoCAD SHX Text E201
AutoCAD SHX Text E204
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text K-2005
AutoCAD SHX Text
KINGSTON
AutoCAD SHX Text
C_LAVATORY
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text K-2005
AutoCAD SHX Text
KINGSTON
AutoCAD SHX Text
C_LAVATORY
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
C_URINALS
AutoCAD SHX Text
DEXTER
AutoCAD SHX Text
K-5016-ET
AutoCAD SHX Text A205
SECOND FLOOR MATERIAL LOCATIONS SAMPLE LOCATIONS SCALE: NTS
ACM FLOOR TILE MASTIC
GENERAL NOTES
1. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DRAWINGS FOR
REQUIRED PROJECT DETAILS AND COORDINATION.
2. ASBESTOS MATERIALS HAVE BEEN IDENTIFIED IN THE PROJECT AREA. ANY ASBESTOS-CONTAINING
MATERIALS THAT WILL BE IMPACTED BY THE PLANNED RENOVATION MUST BE REMOVED AND
DISPOSED OF PRIOR TO BEING DISTURBED.
3. FRIABLE AND NON-FRIABLE ASBESTOS THAT WILL BE IMPACTED BY RENOVATION ACTIVITIES MUST BE
REMOVED AND DISPOSED OF PROPERLY. ALL ASBESTOS WASTE WILL BE DISPOSED OF IN
ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19 AND APPLICABLE REGULATIONS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND OBSTRUCTIONS. REFER TO BUILDING AS-BUILTS INCLUDING RENOVATION AS BUILTS FOR DETAILS.
5. ALL PAINTED SURFACES ARE ASSUMED TO CONTAIN AT LEAST TRACE LEVELS OF LEAD AND OTHER METALS; INCLUDING INTERIOR AND EXTERIOR PAINTS. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL HAVE LEAD AWARENESS TRAINING IN ACCORDANCE WITH 29 CFR 1926.62; THIS
INCLUDES ALL TRADES IMPACTING PAINTED SURFACES.
6. CONTRACTOR MUST SUBMIT ASBESTOS, LEAD, OTHER METALS. AND PCB ABATEMENT PLANS TO THE
VETERANS ADMINISTRATION (VA) FOR REVIEW AND APPROVAL PRIOR TO START OF WORK
ACTIVITIES.
ASBESTOS NOTES
1. ALL ASBESTOS WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 13 19.
2. THE ASBESTOS-CONTAINING MATERIALS IDENTIFIED ON THE DRAWING ARE SHOWN FOR REFERENCE.
THERE ARE PLANNED IMPACTS TO THE 9-INCH TAN STREAKED VINYL FLOOR TILE (VFT) WITH BLACK MASTIC SHOWN ON THE 1ST FLOOR AND THE 12-INCH ORANGE VFT WITH MASTIC SHOWN ON THE 2ND
AND 3RD FLOORS.
3. THE GENERAL CONTRACTOR AND ABATEMENT CONTRACTOR SHALL FIELD VERIFY ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND STRUCTURAL DETAILS AND DIMENSIONS THAT MAY IMPACT THE
WORK. THE CONTRACTOR SHALL VERIFY THE CONDITION, LOCATION, AND QUANTITIES OF
HAZARDOUS MATERIALS IN THE WORK AREA PRIOR TO SUBMITTING A BID.
4. REFER TO 02 82 13 19 AND CONTRACTOR'S APPROVED WORK PLAN FOR ASBESTOS REMOVAL AND
DISPOSAL PROCEDURES AND REQUIREMENTS.
5. THE CONTRACTOR IS REQUIRED TO READ THE INDIVIDUAL HAZARDOUS MATERIALS SURVEY REPORT FOR BUILDING 3 SUBMITTED BY MED-TOX NORTHWEST DATED DECEMBER 2022. THE CONTRACTOR IS TO FIELD VERIFY THE LIMITATIONS SECTIONS IDENTIFIED IN THE REPORT FOR THE DETERMINATION
OF HIDDEN MATERIALS.
LEAD-BASED PAINT NOTES
1. REFER TO SPECIFICATION SECTION 02 83 33 13 FOR LEAD REQUIREMENTS INCLUDING DISPOSAL AND
TESTING REQUIREMENTS.
2. THE CONTRACTOR SHALL ASSUME THAT LEAD IS PRESENT IN PAINTED OR PRIMERED SURFACES THROUGHOUT THE PROJECT. ALL WORK THAT MAY DISTURB PAINT OR PRIMER-CONTAINING LEAD OR OTHER LEAD BUILDING MATERIAL (SUCH AS CERAMIC TILE) SHALL BE IN ACCORDANCE WITH 29 CFR 1926.62 AND SPECIFICATION SECTION 02 83 33 13 INCLUDING DUST CONTROL, EMPLOYEE
EXPOSURE ASSESSMENTS, AND WASTE CHARACTERIZATION.
PCB BALLASTS AND FLOURESCENT LIGHT TUBE NOTES
1. ALL FLUORESCENT LIGHTS TO BE DEMOLISHED SHALL BE INSPECTED. ALL BALLASTS NOT
SPECIFICALLY LABELED AS “NO-PCBS” OR “PCB FREE” WILL BE ASSUMED TO BE PCB-CONTAINING AND BE REMOVED AND DISPOSED OF AS PCB WASTE IN ACCORDANCE WITH THE REGULATIONS. PARTIAL DISASSEMBLY OF FLUORESCENT FIXTURES AND SELECTIVE DEMOLITION FOR ACCESS ARE INCLUDED
IN THE SCOPE OF WORK. REFER TO CONTRACT SPECIFICATIONS, ELECTRICAL DEMOLITION
DRAWINGS, REGULATIONS, AND CONTRACTOR'S APPROVED WORK PLAN FOR PCB-BALLAST REMOVAL
AND DISPOSAL PROCEDURES. HID LIGHTS ARE ASSUMED TO CONTAIN PCB-BALLASTS AND
MERCURY-CONTAINING BULBS.
2. NON-PCB LIGHT BALLASTS ARE TO BE RECYCLED OR DISPOSED IN ACCORDANCE WITH 02 84 16.
3. ALL FLUORESCENT LIGHT TUBES AND HID LIGHT BULBS ARE ASSUMED MERCURY-CONTAINING.
MERCURY-CONTAINING LIGHT TUBES/BULBS SHALL BE RECYCLED IN ACCORDANCE WITH THE
CONTRACT AND WITHOUT BREAKAGE ON SITE. REFER TO CONTRACT SPECIFICATIONS/DRAWINGS, REGULATIONS, AND CONTRACTORS APPROVED WORK PLAN FOR LIGHT TUBE RECYCLING
PROCEDURES.
4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ELECTRICAL ISOLATION OF ALL IMPACTED
LIGHT FIXTURES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
H-103
MATERIAL
LOCATION
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMIC RETROFIT AND
RENOVATION BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
11/07/2023 AF CBS
FULLY SPRINKLERED
Revisions: Date:
http://www.medtoxnw@msn.com
ED-TOX
SAFE ENVIROMENT OF AMERICA, INC dba
NORTHWEST
OCCUPATIONAL ENVIROMENTAL HEALTH SERVICES
(253) 351-0677 (253) 351-0688 (FAX)
129 A STREET N.W.
AUBURN, WASHINGTON 98001
ACM FLOOR TITLE MASTIC TO BE REMOVED 250 SQ FT
ISSUED FOR
CONSTRUCTION
AutoCAD SHX Text B303C
AutoCAD SHX Text B301A
AutoCAD SHX Text B303B
AutoCAD SHX Text B303
AutoCAD SHX Text B302
AutoCAD SHX Text E301
AutoCAD SHX Text A301
AutoCAD SHX Text A303
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text K-2005
AutoCAD SHX Text
KINGSTON
AutoCAD SHX Text
C_LAVATORY
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
C_URINALS
AutoCAD SHX Text
DEXTER
AutoCAD SHX Text
K-5016-ET
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text K-2005
AutoCAD SHX Text
KINGSTON
AutoCAD SHX Text
C_LAVATORY
AutoCAD SHX Text
VITREOUS CHINA
AutoCAD SHX Text
MODELNUMBER
AutoCAD SHX Text
TRADENAME
AutoCAD SHX Text
PRODUCT
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text A304
AutoCAD SHX Text A305
AutoCAD SHX Text A302
AutoCAD SHX Text A305A
AutoCAD SHX Text A301
AutoCAD SHX Text E300
AutoCAD SHX Text
THIRD FLOOR MATERIAL LOCATIONS SAMPLE LOCATIONS SCALE: NTS
(SS)
(SD)
(UGP)
(COMM)
(GAS)
(WTR)
(FW)
X
WV
SD
S
ABANDONED IN PLACE AIP
ABBREVIATION ABBR
ADMINISTRATION ADMIN
AGGREGATE AGGR
AIR CONDITIONING A/C
ALTERNATE ALT
ALUMINUM AL
AMERICAN NATIONAL STANDARDS INSTITUTE ANSI
AMERICAN SOCIETY FOR TESTING AND MATERIALS ASTM
AMERICAN SOCIETY OF CIVIL ENGINEERS ASCE
AMPERES A, AMPS
ANCHOR BOLT AB
APPROVED APVD
APPROXIMATE APPROX
ARCHITECT/ENGINEER A/E
ASBESTOR CEMENT PIPE ACP
ASPHALT ASPH
ASPHALT CONCRETE A.C.
AMERICAN WIRE GAUGE AWG
AUTOMATIC AUTO
AUXILIARY AUX
AVERAGE AVG
BELOW FINISH GRADE BFG
BITUMINOUS BITUM
BLOCKING BLKG
BRACING BRCG
BRACKET BRKT
BUILDING BLDG
CAST IRON CI
CATALOG CAT
CEILING CLG
CEMENT CEM
CENTER CTR
CENTER LINE CL
CHILLED / COLD WATER CW
CHILLED WATER RETURN CHWR
CHILLED WATER SUPPLY CHWS
CIRCULAR CIRC
CIRCUIT BREAKER CKT BRK
CLARK COUNTY AREA UNIFORM STANDARD
SPECIFICATIONS CCAUSS
CLEAR, CLEARANCE CLR
COMMUNICATIONS COMM, C
CONCRETE CONC
CONCRETE MASONRY UNITS CMU
CONDUIT (S) C, CONDS
CONDUIT ONLY CO
CONNECTION CONN
CONSTRUCTION CONSTR
CONTRACTING OFFICER'S REPRESENTATIVE COR
CONTROL JOINT CLJ
COPPER CU
CORPORATION CORP
CORRUGATED METAL PIPE CMP
CUBIC YARD CY
CULVERT CLVT
DATED DTD
DEEP DP
DETAIL DTL
DEGREE DEG
DEPARTMENT OF THE AIR FORCE DAF
DIAGONAL DIAG
DIAMETER DIA, Ø
DIMENSION DIM
DISTANCE DIST
DOUBLE DBL
DRAWING DWG
DROP INLET D.I.
EACH EA
EAST E
EDGE OF PAVEMENT EOP
ELECTRIC, ELECTRICAL ELEC
ELEVATION ELEV
EMERGENCY EMER
ENCLOSURE ENCL
ENGINEER ENGR
ENTRANCE ENTR
EQUAL EQL
EQUIPMENT EQUIP
EXISTING EX
EXISTING GRADE EG
EXPANSION JOINT EXP JT
EXPOSED EXP
EXTERIOR EXT
FACILITY FACIL
FEET FT
FIBER OPTICS FO
FINISH FLOOR FF
FINISH GRADE FG
FIRE F
FIRE HYDRANT FH
FIRE PROTECTION FP
FITTING FTG
FLANGED FLG
FLOOR FLR
FLOW LINE FL
FOOT FT
FOOTING FTG
FUTURE FUT
GAGE OR GAUGE GA
GALLONS/HOUR GPH
GALLONS/MINUTE GPM
GALVANIZED GALV
GATE VALVE GV
GENERAL GENL
GOVERNMENT GOVT
GRADE GR
GROUND GND
GROUND FAULT INTERRUPTING GFI
GYPSUM GYP
HAZARDOUS WASTE HAZ W
HEIGHT HT
HIGH POINT HPT
HORIZONTAL HORIZ
HOT WATER HW
HOT WATER RETURN HWR
HOT WATER SUPPLY HWS
HOUR HR
INCH IN
INSIDE DIAMETER ID
INSULATION INSUL
INVERT INV
JOINT JT
LEFT LT
LENGTH, LONG LG
LIGHTING LTG
LOW POINT LP
MACHINE MACH
MAGNETIC MAG
MAINTENANCE MAINT
MANHOLE MH
MANUFACTURER MFR
MATERIAL MATL
MAXIMUM MAX
MECHANICAL MECH
METAL MET
MILLIONS GALLONS PER DAY MGD
MINIMUM MIN
MISCELLANEOUS MISC
NEVADA NV
NON-INSULATED METAL NIM
NOMINAL NOM
NORMAL NORM
NORTH N
NOT IN CONTRACT NIC
NOT TO SCALE NTS
NUMBER #
OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION OSHA
ON CENTER O.C.
OPPOSITE OPP
OUTSIDE DIAMETER OD
OVER HEAD OVHD
OVER O/
PAVEMENT PVMT
PLACES PLCS
PLATE PL
POINT PT
POLE, POWER P
POLYVINYL CHLORIDE PVC
POST INDICATOR VALVE PIV
POUNDS LBS
PROJECT ENGINEER PE
RADIUS RAD, R
REFERENCE REF
REINFORCING REINF
REQUIRED REQ'D
REVERSE REVR
REVISIONS REV
RIGHT RT
RIGID STEEL RS
ROAD RD
ROOM RM
ROUND RND
SANITARY SEWER SS
SANITARY SEWER MANHOLE SMH
SCHEDULE SCH, SCHED
SECTION SECT
SEWER S
SEWER CLEANOUT SCO
SHEET SHT
SHEET METAL SH MET
SHOULDER SHLDR
SIDEWALK SW
SIMILAR SIM
SLOPE / SOUTH S
SPECIFICATION SPEC
SQUARE SQ
STANDARD STD
STATEMENT OF WORK SOW
STATION STA
STEAM ST
STEEL STL
TELEPHONE TEL
THICK THK
THRUST BLOCK TB
TOP OF CURB TC
TRANSFORMER XFMR
TYPICAL TYP
UNDERGROUND UGND
UNFINISHED UNFIN
UNIFORM BUILDING CODE UBC
UNITED STATES US
UNIFORM STANDARDS SPECIFICATIONS USSCCA
CLARK COUNTY AREA
VOLTAGE V
WASTE, WATER, WEST, WIDTH W
WEIGHT WT
YARD YD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
S&B CHRIST CONSULTING, LLC.
9555 HILLWOOD DRIVE, #160
LAS VEGAS, NV 89134
(702) 202-6004
POC: PETER MOSER
B& S&B CHRIST CONSULTING, LLCS
CC
B& S&B CHRIST CONSULTING, LLCS
CC
A/E, ENVIRONMENTAL, ASSET MANAGEMENT & CM SERVICES
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
NOVEMBER 7, 2023
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
Revisions: Date:
P.Moser C.Que
A/E:
Consultant:
C-001
LEGEND &
ABBREVIATIONS
P:
\P ro je ct s\
Bl ue
T rid en t -
T O
VA
R os eb ur g Bl dg
S ei sm ic
R et ro fit
\E ng in ee rin g\
D ra w in gs \P ro du ct io n D ra w in gs
\0
3- G
-0
G
EN
ER
AL
.d w g
11/7/2023
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(GAS)
(GAS)
(GAS)
(G
AS)
(G
AS)
(G
AS
(G
AS
(G
AS
(GAS)
(WTR)
(WTR)
(WTR)
(WTR)
(WTR)
(WTR)
(S D
(S
D
(S D
(S
D
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(S D
(S
D
(S D
(S
D
(WTR)
(W
TR)
(W
TR
(W
TR)
(W
TR)
(W
TR)
(W
TR
(W
TR
(W
TR
(W
TR)
(WTR)
(WTR)
(WTR)
(WTR)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(WTR)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(UGP)
(UGP)
(UGP)
EX GAS
METER
EX BUILDING 3
CENTENNIAL DRIVE
(PAVED) (PRIVATE)
EX ELEC
EQUIPMENT
EX BACKFLOW DEVICES
EX BUILDING 14
EX SS MH
18" INV IN N
12" INV IN W
18" INV OUT S
EX STORMDRAIN
MANHOLE
EX SHADE
STRUCTURE
EX 4" S
D
EX 4" SD
EX 4" SD
EX 6" SD
EX
6"
S D
EX
" S D
EX
" S D
EX
" S S
EX 2 1 2" W
TR
EX 5" SS CI
FOR 5'
EX PIV
EX
G
AS
EX G
AS
EX
P
OW
ER
EX
P
OW
ER
UNKNOWN WATER
CONNECTIONS
EX
CHILLERS
EX
TRANSFORMER
EX ELEC
SWITCHES
AREA OF DISTURBANCE
AREA OF
DISTURBANCE
AREA OF
DISTURBANCE
EX STEAM CONNECTION
EX COMMUNICATIONS CONNECTION
EX FDC
EX DOMESTIC
WATER CONNECTION
EX FIRE WATER
CONNECTION
CONSTRUCTION NOTES
DEMO EXISTING CONCRETE SIDEWALK.
DEMO EXISTING STORM DRAIN DROP INLET.
PROTECT IN PLACE EXISTING TREE.
DEMO EXISTING PORCH DECK AND FOOTINGS. PRESERVE AND REPAIR EXISTING STAIRWAY
BENEATH PER ARCHITECTURAL DRAWINGS.
DEMO EXISTING STORM DRAIN PIPE AND CAP CONNECTION TO EXISTING STORM DRAIN
MANHOLE.
EXPOSE AND INSPECT EXISTING DOWNSPOUTS AND LATERALS TO MAIN LINE. REMOVE
DETERIORATED MATERIAL AT FIVE (5) LOCATIONS AS SHOWN.
DEMO EXISTING RAMP AND HANDRAILS.
DEMO EXISTING RETAINING WALL.
BASIS OF BEARINGS
The Basis of Bearing is North 78° 40' 34" East, 749.70 feet from SBCC control point #10 to SBCC control point 51. These positions were derived from GPS observations with corrections applied from an OPUS solution, depicted in U.S. Survey Feet, NAD83(2011)Epoch 2010.0000, based on the Oregon State Plane Coordinate System, South Zone, as measured at grid. Grid to Ground Combined Factor= 1.000123565 at SBCC control point #10.
BENCHMARK
The Project Benchmark is SBCC control point 50, a set PK nail in asphalt, approximately 4-feet southwest of the southwesterly curb face for the median island in the center of the northwest approach from NW Veterans Way to Building 3, depicted in U.S. Survey Feet, NAVD 88 Datum, with corrections applied from an OPUS solution.
Elevation= 460.21 U.S. Survey Feet, 140.272 meters (NAVD 88 Datum) Conversion to NAVD29= -3.48-feet as per NOAA Online Vertical Datum Transformation at LAT/LONG Point 50.
Pt# Northing Easting Elev. Description LAT/LONG (dec.deg.)
10 579992.2070' 4157084.7590' 466.84' GPS BASE PK
N043.22221329 W123.36766795
50 580256.3220' 4157355.3720' 460.21' CP 50 PK N043.22296297
W123.36668713
51 580139.4140' 4157819.8600' 462.96' CP 51 PK N043.22268598
W123.36493039
52 579912.2870' 4157339.3290' 454.69' CP 52 PK N043.22201804
W123.36670311
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
S&B CHRIST CONSULTING, LLC.
9555 HILLWOOD DRIVE, #160
LAS VEGAS, NV 89134
(702) 202-6004
POC: PETER MOSER
B& S&B CHRIST CONSULTING, LLCS
CC
B& S&B CHRIST CONSULTING, LLCS
CC
A/E, ENVIRONMENTAL, ASSET MANAGEMENT & CM SERVICES
BLUE TRIDENT, LLC
7829 NE ESPERIONE LN
BAINBRIDGE ISLAND, WA 98110
206-972-0645
EMMANUEL (MANNY) BAUTISTA, PE, F.SAME
SEISMICALLY MITIGATE BLDG. 3
VA Roseburg Healthcare System
653-21-102 director
NOVEMBER 7, 2023
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
Revisions: Date:
P.Moser C.Que
A/E:
Consultant:
CR101
DEMOLITION
PLAN
P:
\P ro je ct s\
Bl ue
T rid en t -
T O
VA
R os eb ur g Bl dg
S ei sm ic
R et ro fit
\E ng in ee rin g\
D ra w in gs \P ro du ct io n D ra w in gs
\0
3- C
R
1- D
EM
O
P
LA
N .d w g
GENERAL NOTES:
1. ENGINEER ASSUMES NO RESPONSIBILITY FOR EXISTING UTILITY LOCATIONS AND ELEVATIONS.
EXISTING UTILITIES SHOWN ARE FROM THE BEST AVAILABLE INFORMATION. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY LOCATIONS AND ELEVATIONS OF ALL
UTILITIES, INCLUDING BUT NOT LIMITED TO, THE WATER, FIRE, SANITARY SEWER, STORM
SEWER, COMMUNICATIONS, POWER, GAS, AND IRRIGATION PRIOR TO THE COMMENCEMENT OF
CONSTRUCTION. IF CONFLICTS ARE ENCOUNTERED IN THE FIELD, THE CONTRACTOR IS TO
NOTIFY THE COR, AND THE PROJECT ENGINEER IMMEDIATELY.
2. UNLESS OTHERWISE INDICATED, ALL SURFACE FEATURES AND UTILITY INFRASTRUCTURE TO
BE PROTECTED IN PLACE.
3. CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE TO EXISTING FEATURES,
STRUCTURES, OR UTILITIES TO REMAIN. CONTRACTOR SHALL MATCH OR EXCEED CURRENT
CONDITION OF THOSE FEATURES OR UTILITIES TO REMAIN.
4. CONTRACTOR SHALL MAINTAIN THE SITE FREE OF TRASH AND DEBRIS. THE CONTRACTOR IS
RESPONSIBLE FOR THE REMOVAL OF TRASH AND DEBRIS DAILY. NO TRASH OR DEBRIS SHALL
BE DISPOSED OF ONSITE.
5. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS TO PROTECT ROOT SYSTEMS OF
SHRUBS, PLANTS, AND TREES TO REMAIN.
6. PRIOR TO ANY UTILITY OUTAGES, CONTRACTOR SHALL COORDINATE WITH CONTRACTING
OFFICER'S REPRESENTATIVE. CLEARANCE IS REQUIRED PRIOR TO START OF DEMOLITION.
CONTRACTOR SHALL SUBMIT WRITTEN NOTIFICATION NOT LESS THAN 28 CALENDAR DAYS IN
ADVANCE OF EACH INTERRUPTION. NO SINGLE UTILITY OUTAGE SHALL EXCEED FOUR (4)
HOURS AT A TIME OR MORE THAN ONCE IN A 2-WEEK PERIOD UNLESS APPROVED IN WRITING
BY THE CONTRACTING OFFICER.
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(SS)
(SS)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(S S)
(GAS)
(GAS)
(GAS)
(G
AS)
(G
AS)
(G
AS)
(G
AS
(G
AS
(G
AS
(GAS)
(WTR)
(WTR)
(WTR)
(WTR)
(WTR)
(WTR)
(S D
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD
(SD
(SD
(SD
(SD
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(WTR)
(W
TR
(W
TR)
(W
TR)
(W
TR)
(W
TR
(WTR)
(WTR)
(WTR)
(WTR)
(SD)
(SD)
(SD)
(SD)
(SD)
(SD)
(WTR)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(U
GP)
(UGP)
EX FDC
EX GAS
METER
CENTENNIAL DRIVE
(PAVED) (PRIVATE)
EX DOMESTIC
WATER CONNECTION
EX BUILDING 14
EX SS MH
RIM: 458/43
18" INV IN N
12" INV IN W
18" INV OUT S
EX 4" S
D
EX 4" SD
EX 4" SD
EX 6" SD
EX
6"
S D
EX
" S S
EX 2 1 2" W
TR
EX 5" SS CI
FOR 5'
EX PIV
UNKNOWN WATER
CONNECTIONS
SD
SD
SD
SD
S
EX BUILDING 3
FFE: (453.6)
NEW BUILDING
ADDITION
FFE: 453.6
EX SHADE
STRUCTURE
EX CHILLERS
(PROTECT IN PLACE)
EX TRANSFORMER
(PROTECT IN PLACE)
EX ELEC SWITCHES
(PROTECT IN PLACE)
8" PVC SD
12.5 LF @ 1.0%
8" PVC SD
16.0 LF @ 1.0%
8" PVC SD
26.3 LF @ 1.0%
6.
0'
5.0
AREA OF DISTURBANCE
AREA OF
DISTURBANCE
AREA OF
DISTURBANCE
4.5
6.0'
10.0'
.0'
EX STEAM
CONNECTION
EX COM
CONNECTION
8" PVC SD
7.4 LF @ 1.0%
8" PVC SD
18.3 LF @
1.0%
.5'
13.0'
5.5
8" PVC SD
10.2 LF @ 1.0%
R10.0'
R32.0'
R38 .0'
4.5'
7.0'
28.5'
21.5'
5.0'
6.5'
27.5'
.5
EX FIRE WATER
CONNECTION
CONSTRUCTION NOTES
CONSTRUCT NEW CONCRETE SIDEWALK AND TIE INTO EXISTING, PER DETAIL 2, SHEET CD501.
INSTALL NEW STORM DRAIN DROP INLET, PER DETAIL 5, SHEET CD501.
CONNECT DRAIN LINE FROM SUMP PUMP IN THE NEW ELEVATOR SHAFT AND DRAIN TO
PROPOSED ADJACENT DROP INLET. REFER TO MECHANICAL SHEETS FOR SUMP PUMP DETAILS.
CONSTRUCT 5' X 6' ADA RAMP SIDEWALK LANDING AT 2% MAX SLOPE.
TIE PROPOSED STORM DRAIN PIPES INTO EXISTING MANHOLE, PER DETAIL 7, SHEET CD501.
PROTECT IN PLACE EXISTING ELECTRICAL PAD AND EQUIPMENT.
INSTALL NEW ADA RAMP AND DETECTABLE TACTILE STRIPS AND TIE INTO EXISTING ROADWAY, PER DETAILS 3 & 4, SHEET CD501.
CONSTRUCT 2' WIDE V-CHANNEL DRAINAGE SWALE, PER GRADING PLAN.
TIE IN NEW SIDEWALK AT EXISTING STAIRS. SEE ARCHITECTURAL PLANS.
PROTECT IN PLACE EXISTING SANITARY SEWER MANHOLE.
PROTECT IN PLACE EXISTING TREE.
CONNECT NEW DOWNSPOUTS AT TWO (2) LOCATIONS TO 4" SDR 35 DRAIN PIPE LATERAL.
DISCHARGE LATERAL AS SHOWN TO NEW STORM DRAIN DROP INLET.
REMOVE AND REPLACE EXISTING 90° ELBOW FROM DOWNSPOUT AND THE 4" LATERAL
CONNECTION FROM THE DOWNSPOUT TO THE MAIN STORM DRAIN LINE AT FIVE (5) LOCATIONS
AS SHOWN. DRAIN PIPE SHALL BE 4" SDR 35 PVC. TRENCH AND BACKFILL PER DETAIL 1, SHEET
CD501.
INSTALL NEW 4" PVC SIDEWALK UNDER DRAIN.
INSTALL NEW 1' RETAINING WALL ALONG NEW SIDEWALK, PER DETAIL 6, SHEET CD501.
CONSTRUCT NEW ABA ACCESSIBLE SITTING AREA, CONCRETE PAD, PER DETAIL 2, SHEET CD501.
INSTALL NEW MANHOLE AND TIE IN TO EXISTING SANITARY SEWER PIPE, PER DETAIL 8 ON SHEET
CD501.
BASIS OF BEARINGS
The Basis of Bearing is North 78° 40' 34" East, 749.70 feet from SBCC control point #10 to SBCC control point 51. These positions were derived from GPS observations with corrections applied from an OPUS solution, depicted in U.S.