648-20-116 Drawings - Copy_Part4.pdf
PDF 19 MB Posted
- Solicitation number
- 36C26026R0040-0002
About this file
This is a set of electrical construction documents for a U.S. Department of Veterans Affairs facility modernization project across multiple buildings. The drawings detail electrical system upgrades, demolition, and installation requirements for panelboards, transformers, surge protection devices, grounding systems, and lightning protection infrastructure across 18 buildings and numerous rooms and electrical rooms.
Key construction requirements include: demolition and replacement of existing switchboards, panelboards, and transformers; installation of surge protective devices with conductors limited to 24 inches in length per manufacturer requirements; grounding electrode system installation with hi-frequency testing per VHA Directive 1028-8.J(6)(e) and three-point fall-of-potential testing; circuit tracing and documentation of unknown breaker loads with type-written circuit directories; sealing of wall and ceiling penetrations to match existing fire ratings; pull box installation for feeder runs exceeding 250 feet or 270 degrees of bend; and raceway routing vertically on walls and horizontally on ceilings to preserve future space. The documents reference one-line diagrams, panel schedules, protective device changes schedules, and building specifications (01 00 00) for coordination of shutdowns. Specific work includes equipment relocation, temporary generator coordination, automatic transfer switch installation, grounding conductor bonding per NEC requirements, and contractor field verification with discrepancies reported to the Contracting Officer's Representative (COR). Lightning protection systems include early streamer emission air terminals, gravity mount poles, downleads, and grounding arrays with 10-ohm maximum resistance and 3-point fall-of-potential testing requirements.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANEL '2S'
XFMR 'X2S'
PANEL '4S'
A B C D
CANTEEN
STORAGE
1986 SF
CORRIDOR
NRN
456 SF
CANTEEN
VENDING
179 SF
EMS OFFICE
187 SF
EMS OFFICE
149 SF
CORRIDOR
C1.1
294 SF
1 INST ELEV.
MACHINE
72 SF
EMS STORAGE
1641 SF
PHARMACY
853 SF
UNIFORM
DISTRIBUTION
1095 SF
CORRIDOR
C1.2
1234 SF
SURGE
PROTECTION
DEVICE
019-P-01
AREA SHOWN
BLDG 019
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 8:54:28 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_19_EL_SDB.rvt
019EP101
BLDG 019 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1" = 10'-0"
1 BLDG 019 - LEVEL 01 - ELECTRICAL PLAN 0 10' 20'
TRUE
NORTH
PROJECT
NORTH
1 PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO
IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.
CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH
IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE
TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
Division 25-27
A B C D E F G H I J
STORAGE
SOILED
UTILITY
EXAM #7
STAFF
WORK
MGR
OFFICE
STAFF
WORK
STAFF
TOILET
FITTER
STORAGE
PED-O
CPO
CLERK
LAB
ELECTRICAL
EXAM #2
EXAM #5
EXAM #4
EXAM #6
PAT.
TOILET
OFFICE
SPD
OFFICE
MED
MECHANICAL
ROOM
EXAM #8
SPEECH
PATHOLOGY
SPEECH
PATHOLOGY
EXAM #3
EXAM #1
INTERVIEW
#1
INTERVIEW
#2
ENTRY
VESTIBULE
C1.01
WAITING
C1.02
CHECK-IN
C1.03
CORRIDOR
C1.04
WAITING
C1.05
WAITING
C1.06
CORRIDOR
C1.07
ELEVATOR/
STAIR
LOBBY
C1.08
CORRIDOR
C1.09
CORRIDOR
C1.10
CORRIDOR
C1.11
CORRIDOR
C1.12
CORRIDOR
C1.13
CORRIDOR
C1.14
WAITING
C1.15
ENROLLMENT
ENROLLMENT
STAFF
TOILET
BREAK
ROOM
103 CONFERENCE
HAC
WOMEN'S
TOILET
MEN'S
TOILET
CORRIDOR
C1.10A
STAIR #2
ELEVATOR
P4
PANEL '20-4MDS'
LS DISC.
EQ DISC.
XFMR T2SDS
225 kVA
PANEL '20-2SDS'
PANEL '20-1LM'
PANEL '20-E1HA-EQ'
PANEL '20-1HM'
PANEL '20-1LB'
PANEL '20-1LA'
PANEL '20-1HA'
PANEL '20-E1HA-LS'
PANEL '20-E1LA-LS'
PANEL '20-E1LA-EQ'
TX-L1A-LS (ABOVE)
TE1LA-EQ (ABOVE)
PANEL 'LCC1'
PANEL 'ELCC1'
MECH DDC PANEL
AREA SHOWN
BLDG 020
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 8:57:04 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_20_EL_SDB.rvt
020EP101
BLDG 020 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 020 - LEVEL 01 - ELECTRICAL PLAN 4'0 8' 16'
PROJECT
NORTH
TRUE
NORTH
1 EXISTING EQUIPMENT CONTAINING OVERCURRENT
PROTECTIVE DEVICE WITH SETTINGS TO BE MODIFIED.
REFERENCE CORRESPONDING BUILDING ONE-LINE
DIAGRAMS AND PROTECTIVE DEVICE CHANGES SCHEDULE
FOR PROTECTIVE DEVICE SETTINGS ADJUSTMENT AND / OR
REPLACEMENT.
PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
HI-FREQUENCY TEST. GROUND RESISTANCE TESTING SHALL
BE PER VHA DIRECTIVE 1028-8.J(6)(e). REFERENCE
GROUNDING SPECIFICATION 26 05 26 FOR ADDITIONAL
INFORMATION.
CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO
IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.
CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH
IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE
TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
KEY PLAN
A B C D E F G H I J
COMMUNITY
CARE
SOILED
COMMUNITY
CARE
OFFICE
COMMUNITY
CARE
COMMUNITY
CARE
COMMUNITY
CARE
COMMUNITY
CARE
COMMUNITY
CARE
COMMUNITY
CARE
STAFF
TOILET
COMMUNITY
CARE
COMMUNITY
CARE
COMMUNITY
CARE
212 COMMUNITY
CARE
PUBLIC
TOILET
PUBLIC
TOILET
CORRIDOR
ORAL
SURGERY
X-RAY
STAFF
BREAK
ROOM
HAC
RECEPT /
MED REC
PATIENT
TOILET
PATIENT
ED
TELECO /
DATA /
ELEC
GEN OP #7
GEN OP #9
LAB
STORAGE
MECHANICAL
SOILED
LINEN
MED
STORAGE
LAB
SPD
STORAGE
ASSIST
CHIEF
OFFICE
GEN OP #6
GEN OP #4
CONFERENCE
PATIENT
CONSULT
CLEAN
STORAGE
STAFF
TOILET
DRESS
ROOM
PROCESS
SOILED
UTILITY
OP
WAITING
C2.01
CORRIDOR
C2.02
CORRIDOR
C2.03
CORRIDOR
C2.04
CORRIDOR
C2.05
CORRIDOR
C2.06
CORRIDOR
C2.10
CORRIDOR
C2.14
CORRIDOR
C2.12
GEN OP #1
GEN OP #2
GEN OP #3
GEN OP #5
GEN OP #10
GEN OP #8
GAS
STORAGE
250B
STAIR #2
ELEVATOR
PANEL '20-2LM'
PANEL '2LD'
NO WORK TO BE PERFORMED
TELECOM EQUIPMENT
PANELBOARD
NURSE CALL
PANEL '20-2LC'
PANEL '20-2LB'
PANEL '20-2LA'
RELAY PANEL 'LCC2'
PANEL '20-2HA'
BUSBAR
AREA SHOWN
BLDG 020
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 8:57:07 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_20_EL_SDB.rvt
020EP102
BLDG 020 - LEVEL 02 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 020 - LEVEL 02 - ELECTRICAL PLAN 4'0 8' 16'
PROJECT
NORTH
TRUE
NORTH
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY PLAN
A B C D
FEMALE TOILET
COPY ROOM
TELE-COM
MALE TOILET
H.A.C.
BREAK ROOM
RECEPTION
OFFICE 1
OFFICE 2
THERAPY ROOM
"B"
STAFF WORK
ROOM
GROUP THERAPY
ROOM
THERAPY ROOM
"A"
CORRIDOR
C1.1
CORRIDOR
C1.2
CORRIDOR
C1.3
XFMR
75 kVA 480V
208Y/120V
MECHANICAL &
ELECTRICAL
105a
CONTROL PANEL
PANEL '21-B'
PANEL '21-A'
AHU
SURGE
PROTECTION
DEVICE
021-P-01
AREA SHOWN
BLDG 021
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 8:59:27 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_21_EL_SDB.rvt
021EP101
BLDG 021 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/4" = 1'-0"
1 BLDG 021 - LEVEL 01 - ELECTRICAL PLAN 2'0 4' 8'
PROJECT
NORTH
TRUE
NORTH
1 PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
HI-FREQUENCY TEST. GROUND RESISTANCE TESTING SHALL
BE PER VHA DIRECTIVE 1028-8.J(6)(e). REFERENCE
GROUNDING SPECIFICATION 26 05 26 FOR ADDITIONAL
INFORMATION.
PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
PANEL '22-DB'
SHUTTLE
GARAGE
907 SF
RECORDS
900 SF
FMS
1037 SF
RESEARCH
810 SF
A
B
C
D
1 2 3
EXISTING BUILDING GROUND
BONDED TO STRUCTURAL
STEEL
FACP
JUNCTION BOX
SURGE
PROTECTION
DEVICE
DOCK
LEVELER
022-P-01
AREA SHOWN
BLDG 022
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:04:59 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_22_EL_SDB.rvt
022EP101
BLDG 022 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 022 - LEVEL 01 - ELECTRICAL PLAN
TRUE
NORTH
4'0 8' 16'
PROJECT
NORTH
PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
HI-FREQUENCY TEST. GROUND RESISTANCE TESTING SHALL
BE PER VHA DIRECTIVE 1028-8.J(6)(e). REFERENCE
GROUNDING SPECIFICATION 26 05 26 FOR ADDITIONAL
INFORMATION.
PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
KEY PLAN
SURGE
022-P-01
WATER TANK
A B
WEST WELL
72 SF
WELL DISCONNECT
PANEL '23-PANEL 2' (ABOVE)
PANEL '23-PANEL 1' (BELOW)
WELL SUB MONITOR
TRANSFORMER 'XF-2'
SURGE
PROTECTION
DEVICE
023-P-01
AREA SHOWN
BLDG 023
- 3/4" = 1'-0"
1 BLDG 023 - LEVEL 01 - ELECTRICAL PLAN
TRUE
NORTH
1'0 2' 3'
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:07:55 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_23_EL_SDB.rvt
023EP101
BLDG 023 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
PROJECT
NORTH
PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
HI-FREQUENCY TEST. GROUND RESISTANCE TESTING SHALL
BE PER VHA DIRECTIVE 1028-8.J(6)(e). REFERENCE
GROUNDING SPECIFICATION 26 05 26 FOR ADDITIONAL
INFORMATION.
PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
PUBLIC
TOILET
1B100
CHECK-IN
1A100
CONSULT/
PATIENT ED
1A101
CLINICAL
PHARM
1A102
LARGE
GROUP
ROOM
1A103
DATA/
TELECOM
1A104
GENERAL
STORAGE
1A105
CORRIDOR
C1.6
SOILED
UTILITY
1A107
NON-PACT
1A108
PACT
1A109
PROVIDER/GP
MANAGER
1A110
ASST. OP.
MANAGER
1A111
OFFICE
1A112
MECH/ELECT
1A113
CLEAN
LINEN
1A114
MED
1A115
CORRIDOR
C1.6A CORRIDOR
C1.10A
STAFF
LOCKERS
C1.9
CORRIDOR
C1.10
STAFF
LOUNGE
1A120
STAFF
TOILET
1A121
STAFF
TOILET
1A122
H.A.C.
1A123
CORRIDOR
C1.8
SUPPLY/OMNI
1A125
TELERETINAL
IMAGING
1A127
TREATMENT
1A128
STAFF
SUPPORT
1A129
DIET STOR.
1A130
BLOOD
DRAW
1A131
SMALL
GROUP
ROOM
1A132
PATIENT
TOILET
1A133
SUPERVISOR
MSA
1A100a
TELEHEALTH
1A126
SELF
CHECK-IN
C1.5
CORRIDOR
C1.7
PATIENT
TOILET
1B101
STAFF
SUPPORT
1B102
LARGE
EXAM
1B103
LARGE
EXAM
1B104
EXAM
1B105GM PSYCH
1B106
EXAM
1B107GM PSYCH
1B108
EXAM
1B109EXAM
1B110
EXAM
1B111
SOCIAL
WORK
1B112
CORRIDOR
C1.14
VESTIBULE
C1.3a
CORRIDOR
C1.13
ALCOVE
C1.13a
ALCOVE
C1.13b
STAFF
SUPPORT
1B120
PATIENT
TOILET
1B121
SPINAL
CORD EXAM
1B122
SPINAL
CORD EXAM
1B123
EXAM
1B124
LARGE
EXAM
1B125
EXAM
1B126
EXAM
1B127
EXAM
1B128
EXAM
1B129
PROVIDER/
PACT
1B130
PROVIDER/
PACT
1B131
PROVIDER/
PACT
1B132
PROVIDER/
PACT
1B133
PROVIDER/
PACT
1B135
CLEAN
OXYGEN
1B136
PROVIDER/
PACT
1B137
PROVIDER/
PACT
1B138
STAFF
TOILET
1B134
EN SUITE
TOILET
1B122a
VESTIBULE
C1.1
WAITING
C1.3 ENTRY
C1.2
WAITING
C1.4
PUBLIC
TOILET
1C100 STAFF
SUPPORT
1C101
PATIENT
TOILET
1C102
LARGE
EXAM
1C103
LARGE
EXAM
1C104
GM PSYCH
1C105
EXAM
1C106
GM PSYCH
1C107
EXAM
1C108
SOCIAL
WORK
1C109
EXAM
1C110
EXAM
1C111
EXAM
1C112
STAFF
SUPPORT
1C120
PATIENT
TOILET
1C121
LARGE
EXAM
1C122LARGE
EXAM
1C123
LARGE
EXAM
1C124EXAM
1C125
EXAM
1C126
EXAM
1C127
EXAM
1C128
EXAM
1C129
CLEAN
OXYGEN
1C130
STAFF
TOILET
1C131
PROVIDER/PACT
1C132
PROVIDER/PACT
1C133
PROVIDER/PACT
1C134
PROVIDER/PACT
1C135
PROVIDER/PACT
1C136
PROVIDER/PACT
1C137
PROVIDER/PACT
1C138
CORRIDOR
C1.12
CORRIDOR
C1.11
ALCOVE
C1.11a
EN SUITE
TOILET
1C124a
A B C D D.4 D.6 D.8 E E.2 E.3 E.6 F G H I
1.3
3.7
4.4
5.3
5.4
5.5
5.6
5.9
PMT-8
PANEL '24-1L8-D.9-3.7'
PANEL '24-1L7-D.8-3.7'
PANEL '24-1L5-D.6-3.7'
TELECOM
EQUIPMENT
ATS-DE1-E.1-2 DISC
ATS-DE1-E.1-2
PANEL '24-1LSH1-E.2-2'
PANEL '24-1LSL1-E.3-2'
TX T-LS-1-E.2-2 (ABOVE)
SWBD-24-1-E.3-2.5
PANEL '24-1H1-D.0-2.2'
LIGHTING CONTROL
PANEL '24-1H2-D.9-2.4'
PANEL '24-1DEL1-E-2.5'
PANEL '24-1DEH1-E-2.5'
METER ENCLOSURE
PANEL '24-1L4-E-2.8'
PANEL '24-1L3-E.1-2.8'
PANEL '24-1L2-E.2-2.8'
PANEL '24-1L1-E.3-2.8 r'
SWBD-24-2-E.3-2.7
TX T-1-E.3-2.5
TX T-DE-1-2.5 (ABOVE)
PANEL '24-1L6-D.7-3.7'
AREA SHOWN
BLDG 024
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:09:39 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_24_EL_SDB.rvt
024EP101
BLDG 024 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 024 - LEVEL 01 - ELECTRICAL PLAN
TRUE
NORTH
PROJECT
NORTH
4'0 8' 16'
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO
IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.
CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH
IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE
TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
PB
WATER
HEATERS
PANEL '25-MECH'
PANEL '25-P2'
PANEL '25-P1'
MDP-1
JBOX
ELEVATOR
DISCONNECT
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BATHROOM
105a
BATHROOM
106a
BATHROOM
107a
BATHROOM
108a
BATHROOM
101a
BATHROOM
102a
BATHROOM
104a
BATHROOM
103a
CORRIDOR
C1.3
CORRIDOR
C1.4
MECH
MECH
CORRIDOR
C1.6
CORRIDOR
C1.5
LIVING
ROOM
DINING
ROOM
GUEST
TOILET
KITCHEN
FAMILY
ROOM
124MECHANICAL
OFFICE
CLOSET
CORRIDOR
C1.1
CORRIDOR
C1.2
ELEVATOR
EQUIPMENT
125a
BATHROOM
126a
STAIRS
STR3.1 LAUNDRY
123a
STAIRS
STR2.1
STAIRS
STR1.1
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
ELEVATOR
TANK
HEATER
CONTINUE TO
SHEET 025EP103
PMT- 13
225 kVA 12.47kV
480Y/277V
350A MCB
XFMR
150kVA
480V 208Y/120V
XFMR 30 kVA 480V
280Y/120V
PANEL "25/1"
250A BUS
100A MCB
PMP-13
400A BUS
MLO
025-G-04
025-G-04
EP502 TYP.
EP501 TYP.
025-G-04
025-G-04
MAIN WATER PIPE
025-G-03
025-G-01 025-G-02
025-G-03
EP502
EP501
CONTINUE TO
SHEET 025EP103
SURGE PROTECTION DEVICE 3
025-P-01
AREA SHOWN
BLDG 025
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:16:21 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_25_EL_SDB.rvt
025EP101
BLDG 025 - LEVEL 01 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 025 - LEVEL 01 - ELECTRICAL PLAN
TRUE
NORTH
4'0 8' 16'
PROJECT
NORTH
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY PLAN
KEY NOTES
1 PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
3-POINT FALL-OF-POTENTIAL TEST. GROUND RESISTANCE
TESTING SHALL BE PER VHA DIRECTIVE 1028-8.J(6)(e).
REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR
ADDITIONAL INFORMATION.
BOND GROUNDING ELECTRODE SYSTEM CONDUCTOR PER
NEC REQUIREMENTS.
PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BATHROOM
201a
BATHROOM
202a
BATHROOM
203a
BATHROOM
204a
BATHROOM
205a
BATHROOM
206a
BATHROOM
207a
BATHROOM
208a
STAIRS
AREA
STR1.2
STAIRS
STR3.2
CLOSET
CLOSET
CORRIDOR
C2.2
ATTIC
SPACE
STAIRS
STR2.2
CORRIDOR
C2.1
CORRIDOR
C2.3
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
NO WORK TO BE PERFORMED
AREA SHOWN
BLDG 025
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:16:22 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_25_EL_SDB.rvt
025EP102
BLDG 025 - LEVEL 02 - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/8" = 1'-0"
1 BLDG 025 - LEVEL 02 - ELECTRICAL PLAN
TRUE
NORTH
4'0 8' 16'
PROJECT
NORTH
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
AREA SHOWN
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
CONTINUE TO
SHEET 025EP101
CONTINUE TO
SHEET 025EP101
EP502TYP.
EP502
025-G-03
025-G-03 1
BLDG 025
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:16:23 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_25_EL_SDB.rvt
025EP103
BLDG 25 - ROOF - LIGHTNING PROTECTION
PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
TRUE
NORTH
- 1/8" = 1'-0"
1 BLDG 25 - ROOF - LIGHTNING PROTECTION PLAN 4'0 8' 16'
PROJECT
NORTH
Revisions: Date:
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY PLAN
KEY NOTES
1 DOWNLEAD SHALL BE ROUTED UNDER EAVE ADJACENT TO
BUILDING.
1 1.1 2 3 3.1 4 5 5.8 6
A
B
C
D
E
F
G
H
I
L
EP502
EP502
027-G-01
027-G-01 027-G-03
027-G-03
1 2
EP501 TYP.
EP502TYP.
027-G-03
027-G-03
027-G-02
EP502
EP502
EP502
TYP.
MECHANICAL
EQUIPMENT, TYP.
AREA SHOWN
BLDG 027
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:41:07 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_27_EL_SDB.rvt
027EP102
BLDG 027 - ROOF - ELECTRICAL PLAN
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
4'0 8' 16'
PROJECT
NORTH
- 1/8" = 1'-0"
1 BLDG 027 - ROOF - ELECTRICAL PLAN
TRUE
NORTH
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM
3-POINT FALL-OF-POTENTIAL TEST. GROUND RESISTANCE
TESTING SHALL BE PER VHA DIRECTIVE 1028-8.J(6)(e).
REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR
ADDITIONAL INFORMATION.
APPROXIMATE LOCATION OF SWITCHBOARD 'DP1'.
ROOFTOP LIGHTNING PROTECTION CONDUCTOR SHALL BE
ROUTED ALONG PARAPET WALL.
PROVIDE BOND FROM ROOFTOP LIGHTNING PROTECTION
CONDUCTOR TO ALL EQUIPMENT WITHIN 15 FEET OF
CONDUCTOR. UTILIZE BI-METALLIC FITTINGS AS REQUIRED.
ROOFTOP LIGHTNING PROTECTION CONDUCTOR SHALL BE
ROUTED ALONG PARAPET WALL.
PROVIDE BOND FROM ROOFTOP LIGHTNING PROTECTION
CONDUCTOR TO ALL EQUIPMENT WITHIN 15 FEET OF
CONDUCTOR. UTILIZE BI-METALLIC FITTINGS AS REQUIRED.
ON FLOOR BELOW.
A B C D
1A
30 kVA
XFRM
STORAGE
(CONTROL
ROOM)
STORAGE
(OFFICE)
STORAGE
(MACHINERY
ROOM)
2STORAGE
(CLOSET)
STORAGE
TOILET
PANELBOARD "T1819-3"
PANELBOARD "T1819-2"
XFMR 'DT-21.1'
30 kVA
3PH
480V
208Y/120V
FIBER JBOX
JBOX
SURGE
PROTECTION
DEVICE
T1819-P-01
2PANEL "T1819-P1"
AREA SHOWN
BLDG T1819
- 3/8" = 1'-0"
1 BLDG T1819 - LEVEL 01 - ELECTRICAL PLAN 2'0 4' 6'
PROJECT
NORTH
TRUE
NORTH
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:42:27 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_T1819_EL_SDB.rvt
T1819EP101
BLDG T1819 - LEVEL 01 - ELECTRICAL PLAN
T1819
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
1 PROVIDE SURGE PROTECTIVE DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
EXISTING PANELBOARD SHALL BE DEMOLISHED AND
REPLACED. PRESERVE ALL EXISTING CIRCUITS FOR
RETERMINATION. REFERENCE ONE-LINE DIAGRAMS ON
SHEETS T1819ED601 AND T1819EP601.
CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO
IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.
CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH
IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE
TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
OFFICE
82 SF
OFFICE
65 SF
OFFICE
193 SF
OFFICE
202 SF
BREAK ROOM
215 SF
OFFICE
61 SF
OFFICE
61 SF
OFFICE
65 SF
CORRIDOR
210 SF
1 2 3
A
B
C
PANEL 'A'
XFMR
112.5 kVA
480V 208Y/120V
DISC
SURGE
PROTECTION
DEVICE
TR3-P-01
AREA SHOWN
BLDG TR3
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 9:43:39 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_TR3_EL_SDB.rvt
TR3EP101
BLDG TR3 - LEVEL 01 - ELECTRICAL PLAN
TR3
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
- 1/2" = 1'-0"
1 BLDG TR3 - LEVEL 01 - ELECTRICAL PLAN 1'0 2' 4'
PROJECT
NORTH
TRUE
NORTH
Revisions: Date:
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY NOTES
PROVIDE SURGE PROTECTION DEVICE AS INDICATED.
PROVIDE AND INSTALL SURGE PROTECTION EQUIPMENT,
BREAKER, RACEWAY, AND CONDUCTORS PER
MANUFACTURERS REQUIREMENTS. SURGE PROTECTION
DEVICE CONDUCTORS SHALL BE LIMITED TO 24" IN LENGTH
UNLESS OTHERWISE NOTED BY MANUFACTURER.
GREEN
HOUSE
GARDEN
SHED
O
VE
R H
EA
D
R O
W
GAZEBO
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COMPACT COMPACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COMPACT
COMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT
L
GREEN
HOUSE
GARDEN
SHED
O
VE
R H
EA
D
R O
W
GAZEBO
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COMPACT COMPACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COM
PACT
COMPACT
COMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT
L
EP508
PMP-07
PMP-07
CAPACITORS
PMT-7
PMT-14
AREA SHOWN
PMP-07
PMP-07
CAPACITORS
PMT-7
PMT-14
P-01
EP401
EP401
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032 NON SPRINKLERED
(206) 590-2118
RAY SPEES
30/10/2025 8:31:06 am
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_11_EL_SDB.rvt
EP401
LOT 19 - ENLARGED ELECTRICAL PLANS
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
3/16" = 1'-0"
LOT 19 - ENLARGED ELECTRICAL DEMOLITION PLAN
ES001
TRUE
NORTH
4'0 8' 12'
PROJECT
NORTH
3/16" = 1'-0"
LOT 19 - ENLARGED ELECTRICAL PLAN
ES001
2 4'0 8' 12'
PROJECT
NORTH
Revisions: Date:
1 EXISTING CAPACITOR BANK SHALL BE DEMOLISHED AND
REPLACED. REFERENCE ONE-LINE DIAGRAMS ON SHEETS
ED603 AND EP603 FOR ADDITIONAL INFORMATION.
GENERAL NOTES
KEY PLAN
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
EP506
AREA SHOWN
DISC.
XFMR
'PMT-10'
DISC.
SWITCH
PANEL '01-C2'
DISCONNECT
"FF-01-EDP"
PANEL '01-EDP'
PANEL '01-DPA-1'
AUMS PANEL
ATS '01-ATS-9'
ATS '01-ATS-10' VALVES
CHILLER 2
CHILLER 1
FUEL STORAGE
TANK
GENERATOR
YARD
GENERATOR
FUEL TANK
STORAGE
JUNCTION BOX
PMT-10
CAPACITORS
PANEL '01-C1'
JUNCTION
BOX
XFMR 75kVA
OXYGEN
STORAGE
TANKS
WATER TANK
ATS '01-ATS-8'
J K L
SWITCH
'PMS-10'
MANHOLE "MH-4"
PANEL '01-KLA'
PANEL '01-LA SECT. 1'
PANEL '01-LA SECT. 2'
XFMR 'T1'
PANEL '01-HA'
POWER
METER
PANEL '01-LSHA'
XFMR 'T2'
(BELOW)
PANEL '01-CCHA'
(ABOVE)
KLA SUBPANEL
ATS '01-ATS-4'
ELECT. RM
A-117
EP506
EP506
CONTINUE TO
BUILDING 11
2A
EP506 5
BLDG 1 MCC OPN-3
1 PNL '01-LSLA'
SWBD
'MSB'
A-117
J K
L
DISC.
SWITCH
PANEL '01-C2'
DISCONNECT
"FF-01-EDP"
PANEL '01-EDP'
PANEL '01-DPA-1'
AUMS PANEL
ATS '01-ATS-9'
ATS '01-ATS-10' VALVES
CHILLER 2
CHILLER 1
FUEL STORAGE
TANK
GENERATOR
YARD
GENERATOR
FUEL TANK
STORAGE
JUNCTION BOX
PANEL '01-C1'
JUNCTION
BOX
XFMR 75kVA
OXYGEN
STORAGE
TANKS
WATER TANK
ATS '01-ATS-8'
MANHOLE "MH-4"
XFMR 'T1'
PANEL '01-HA'
POWER
METER
PANEL '01-LSHA'
XFMR 'T2'
(BELOW)
PANEL '01-CCHA'
(ABOVE)
KLA SUBPANEL
ATS '01-ATS-4'
ELECT. RM
A-1177
CONTINUE TO
BUILDING 11
VAULT "MH-10"
PMT-10
EP503
EP503
001-P-01A
EP503
001-R-01
PANEL '01-KLA'
PANEL '01-LA SECT. 1'
PANEL '01-LA SECT. 2'
CONTINUE TO
001EP101a
CONTINUE TO
001EP101a
001-G-03
001-G-03
001-P-09
001-P-08
EP502
2B
EP506
SWITCHBOARD
'01-MSB'
BLDG 1 MCC OPN-3
EP505
PMT-10 CAPACITORS
PNL '01-LSLA'
001-G-02
001-G-01
001-P-20A
001-P-20B
DISCONNECT
"PMT-10-CAP-DISC"
001-P-01B
1/ 2'
'-0
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8'
'-0
1/
'-0
1/ 4'
'-0
1' 2'
1' 1/
2' 2'
1/ 2'
1'
'-0
3'
'-0
1' m m
M
M
M
M
M
M
M m m
M m m
M
0.
5M
M 0.
5M 0.
M m m
M m m
M
.2
5M 0.
M
0.
M 0.
M m m
M
M
0.
5M m m
M
3/ 8'
'-0
1'
2' 4'
0.
M 0.
M m m
M
1/
2'
'-0
''0 2'
1/ 2'
1' 3' m m
M
0.
M 0.
M
6'
'-0
1/
4" 1/
2"
M
M
7.
m m
M
3/
'-0
8'
4' 4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES
10/30/2025 11:05:58 AM
Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt
001EP401a
BLDG 001 - LEVEL 01 - ENLARGED ELECTRICAL
PLANS
DCW/LRL JGD/KDB
100% CONSTRUCTION
DOCUMENTS
10/30/2025
648-20-116CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VA
VANCOUVER, WA
VHAPORHCS, VANCOUVER CAMPUS
1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661
PROJECT
NORTH
3/16" = 1'-0"001EP101a
1 RM 6 & A-117 - DEMOLITION ELECTRICAL PLAN - PHASE 1
1. REPLACE BUILDING 1 MV SERVICE AND SWITCHBOARD "01-MSB"; INSTALLATION OF REPLACEMENT MV EQUIPMENT AND LV SWITCHBOARD WILL REQUIRE A SHUTDOWN. WORK SHALL BE PERFORMED ONLY ON WEEKENDS; COORDINATE WITH VA FOR EXACT OUTAGE AND WORK PLANS.
THE FOLLOWING PHASING STEPS MAY BE USED TO PERFORM THE WORK AS FOLLOWS:
A. PROVIDE TRENCHING, ELECTRICAL VAULT, AND RACEWAYS FOR REVISED BUILDING FEED.
B. CONTRACTOR SHALL PROVIDE A TEMPORARY MOBILE GENERATOR AND TEMPORARY POWER DISTRIBUTION TO MAINTIAN POWER TO NON-EMERGENCY BACKED EQUIPMENT. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL REFUELING COSTS AND COORDINATION FOR MOBILE GENERATOR.
C. BUILDING 1 GENERATOR SYSTEM SHALL BE UTILIZED TO PROVIDE POWER TO ALL EMERGENCY BACKED EQUIPMENT AFFECTED BY MV EQUIPMENT AND SWITCHBOARD REPLACEMENT; CONTRACTOR SHALL PROVIDE REFUELING AS NECESSARY.
D. ONCE ALL EQUIPMENT IS POWERED VIA EXISTING GENERATOR SYSTEMS AND CONTRACTOR PROVIDED TEMPORARY GENERATOR, CONTRACTOR SHALL PERFORM THE FOLLOWING WORK:
i. DEMOLISH EXISTING PAD MOUNT SWITCH "PMS-10" AND PAD MOUNT TRANSFORMER "PMT-10" SERVING BUILDING 1.
ii. DEMOLISH EXISTING SWITCHBOARD. ALL EXISTING FEEDER RACEWAYS AND CONDUCTORS SHALL BE PRESERVED FOR RE-TERMINATION.
iii. INSTALL REPLACEMENT PADMOUNT TRANSFORMER "PMT-10" AND ASSOCIATED VAULT "MH-10". EXTEND EXISTING MV RACEWAY AND CONDUCTORS AS REQUIRED FOR TRANSFORMER INSTALLATION.
v. PROVIDE RACEWAY INSTALLATION FROM MV TRANSFORMER TO SWITCHBOARD VIA VAULT "MH-10"; EXTEND EXISTING RACEWAYS AS REQUIRED.
iv. INSTALL REPLACEMENT SWITCHBOARD. PROVIDE AND TERMINATE CONDUCTORS TO SWITCHBOARD.
E. PERFORM ALL ELECTRICAL TESTING AND INSPECTIONS PER SPECIFICATIONS. FULLY COMMISION AND ENERGIZE NEW EQUIPMENT.
4'0 8' 12'
PROJECT
NORTH
Revisions: Date:
- 3/16" = 1'-0"
2 RM 6 & A-117 - ELECTRICAL PLAN - PHASE 14'0 8' 12'
PROJECT
NORTH
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT.
CONTRACTORS SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO THE COR.
EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED
VIA CONTRACTOR.
IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS
HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY
INFORM AND COORDINATE WITH VA AS REQUIRED.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO
MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED.
REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE
ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON
CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL
FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE
MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE
PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,
AND VA AS REQUIRED.
KEY PLAN
KEY NOTES
1 EXISTING PANELBOARD SHALL BE DEMOLISHED AND
REPLACED. PRESERVE ALL EXISTING CIRCUITS FOR
RETERMINATION. REFERENCE ONE LINE DIAGRAMS ON
SHEETS 001ED601, 001ED602, 001EP601, AND 001EP602 FOR
ADDITIONAL INFORMATION.
EXISTING EQUIPMENT CONTAINING OVERCURRENT
PROTECTIVE DEVICE WITH SETTINGS TO BE MODIFIED.
REFERENCE CORRESPONDING BUILDING ONE-LINE
DIAGRAMS AND PROTECTIVE DEVICE CHANGES SCHEDULE
FOR PROTECTIVE DEVICE SETTINGS ADJUSTMENT AND / OR
REPLACEMENT.
EXISTING TRANSFORMER, CAPACITOR, AND DISCONNECT
SHA…
This is the start of the file's text. The full file is on GovTribe.