648-20-116 Drawings - Copy_Part3.pdf

PDF 20 MB Posted

Attached to
Z2DA--CON 648-20-116 Correct Electrical FCA Deficiencies Bldgs. /Site (Vancouver)
Solicitation number
36C26026R0040-0002
Issued by

About this file

This document is a set of electrical construction drawings for a multi-building VA facility renovation project. The drawings establish general notes, symbols, and technical specifications that apply across all electrical work for the project, along with detailed floor plans for individual buildings showing equipment locations, conduit routing, and circuiting requirements.

The project encompasses multiple buildings (Buildings 001-018) across various levels and includes demolition and new electrical installations. Key requirements include: branch circuit conductors minimum 12 AWG for runs up to 65 feet and 10 AWG for longer runs; voltage drop not to exceed three percent; all conduit concealed where possible with 1-inch minimum for exterior/underground and 3/4-inch for interior; emergency circuits routed independently per NEC 700.10; fire-rated wall and floor penetrations sealed with fire-rated assemblies; equipment clearances verified by contractor prior to submittal; circuit breaker settings modified per protective device schedules; grounding electrode systems with 3-point fall-of-potential testing per VHA Directive 1028-8.J(6)(e); and surge protective devices limited to 24 inches in conductor length. Contractors must field-verify existing conditions, perform circuit tracing to identify unknown loads, update circuit directories in type-written format, coordinate pull box locations for feeders exceeding 250 feet or 270 degrees of bend, and provide pull boxes for all such feeders. All existing circuits associated with project areas must be de-energized during construction unless VA determines work must proceed hot, in which case the contractor must provide protective equipment and follow an approved work plan. Electrical work is fully sprinklered throughout with specific provisions for ceiling tile replacement and fire barrier maintenance during construction in non-barriered work areas.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:36:10 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_GENSHEETS_EL_SDB.rvt

EG001

SYMBOLS, ABBREVIATIONS AND GENERAL

NOTES

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

A B B R E V I A T I O N S 1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

33.

34.

35.

THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.

BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT). GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.

EXISTING CIRCUITS ASSOCIATED WITH PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.

ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS PANEL IS COMPLETELY DE-ENERGIZED), OR CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. VA WILL DETERMINE IF ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON CRITICALITY OF AREA BEING AFFECTED. IF WORK MUST BE DONE WITH SERVICE LIVE, CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW JOB SPECIFIC WORK PLAN PREPARED BY CONTRACTOR AND APPROVED BY VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.

PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.

LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.

WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. CONDUCTOR SIZE SHALL BE INCREASED TO COMPENSATE FOR DERATING REQUIRED PER NEC 310.15 WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY; CONDUCTOR AMPACITIES SHALL BE TAKEN FROM 75°C COLUMN. INDIVIDUAL CIRCUITS SHALL NOT SHARE NEUTRAL CONDUCTORS. HOT WORK REQUIRES VA AUTHORIZATION

FROM MEDICAL CENTER DIRECTOR. MUST REQUEST AT LEAST 3 WEEKS IN ADVANCE.

MINIMUM CONDUIT SIZE SHALL BE 1" FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR INTERIOR CONDUIT. ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINAIRES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON DRAWINGS.

EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.

PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS

REQUIRED.

ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL

DRAWINGS AND ALL TRADES PRIOR TO COMMENCING WORK.

COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR LIGHTING CONTROL SYSTEM SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.

ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS. ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER

MOUNTING SURFACE TO ALL EQUIPMENT; RECEPTACLES SHALL BE INSTALLED FLUSH.

ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.

ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.

FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND INSTALLATION LOCATIONS PRIOR TO INSTALLATION.

ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN

INACCESSIBLE LOCATION WITHOUT CONDUIT.

GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6' OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED OUTDOORS/EXTERIOR TO BUILDING.

NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM STRUCTURAL ENGINEER OR ARCHITECT.

LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED

ON COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS.

MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN WORK AREA, DISCONNECT WIRING AT OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM ABANDONED CONDUITS.

DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

ALL AFFECTED AREAS THAT REQUIRE REPLACEMENT OF CEILING TILES AT END OF EACH SHIFT FOR WORK AREAS OUTSIDE OF A RATED CONSTRUCTION BARRIER. IF TILES CANNOT BE REPLACED, SPRINKLER SYSTEM MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS AND 1-HOUR FIRE RATED SEPARATION WILL BE REQUIRED BETWEEN CONSTRUCTION AREA AND OCCUPIED PORTIONS OF BUILDING.

PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND LIKE, SHALL BE REPAIRED OR REPLACED AT EXPENSE OF CONTRACTOR TO ACCEPTANCE OF OWNER.

ALL EQUIPMENT WITH VA "EE TAGS" SHALL REMAIN ON STATION WHILE PAPERWORK IS BEING PERFORMED. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES UNLESS VA CHOOSES TO RETAIN THEM. DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

ALL BONDS TO WATER PIPE SHALL BE BONDED TO PIPE FLANGE USING A MECHANICAL LUG TYPE BOND. ALL BONDS TO BUILDING STEEL SHALL BE EXOTHERMIC.

ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH CONTRACTOR'S PHASING OF PROJECT. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

ALL DEMOLITION OF ELECTRICAL SYSTEMS SHALL BE CLOSELY COORDINATED WITH CONTRACTOR'S PHASING OF PROJECT. VERIFY DEMOLITION OF ELECTRICAL WITH ALL TRADES PRIOR TO START OF DEMOLITION.

CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES. DISPOSAL OF DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES. REUSE EXISTING CONDUITS AND JUNCTION BOXES WHERE NOTED AS IS PRACTICAL.

CONTRACTOR SHALL PROVIDE UPDATED TYPE WRITTEN CIRCUIT PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE VA COR PRIOR TO PERFORMING REQUIRED EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA

STANDARDS.

PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT A DETAILED CONSTRUCTION PHASING PLAN TO VA FOR REVIEW AND APPROVAL; VA SHALL HAVE 30-DAYS TO REVIEW AND APPROVE EACH PHASING NARRATIVE. PHASING SHALL BE PLANNED TO MINIMIZE DOWNTIME AND IMPACT TO FACILITY OPERATION. PHASING PLAN SHALL INCLUDE ANY ANTICIPATED SHUTDOWNS AND TEMPORARY POWER PROVISIONS.

G E N E R A L N O T E S

1PH

1P 2/C 3/C

3PH

4/C 4W A/C A/E

AC

ACC

ADDL

ADJ

AF

AFC

AFCI

AFF

AFG

AHJ

AIC

ALT

AMP

ARCH

ASC

AT

ATS

AUTO

AV

BAT

BB

BFF

BLDG

BRKR

BYP

C

CALC

CAP

CAT

CATV

CCR

CD

CF

CKT

C/B

CL

CLF

CLG

CO

COMM

CONC

CONT

CONTR

CT

CTV

CU

CUR

DC

DCP

DDC

DEG C

DEG F

DEMO

DIAG

DISC

DP

DS

DWG

EC

ELEC

ELEV

EMER/EM

EMI

EMT

ENCL

EPO

EXT./

EXIST./

(E)

SINGLE-PHASE

SINGLE POLE

TWO-CONDUCTOR

THREE-CONDUCTOR

THREE-PHASE

FOUR-CONDUCTOR

FOUR-WIRE

AIR CONDITIONING UNIT

ARCHITECT/ENGINEER

ALTERNATING CURRENT OR ARMORED CABLE

ACCESSIBLE

ADDITIONAL

ADJACENT, ADJOINING

AMPERE FRAME OR AMP FUSE

ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

ARC-FAULT CURRENT INTERRUPTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

AMPERE INTERRUPTING CAPACITY

ALTERNATE

AMPERE

ARCHITECT

AMPS SHORT CIRCUIT

AMPERE TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUDIO VISUAL

BATTERY

BRANCH BREAKER

BELOW FINISH FLOOR

BUILDING

BREAKER

BY PASS

CONDUIT

CALCULATE

CAPACITY

CATALOG

COMMUNITY ANTENNA TELEVISION

CONTROL CONTACTOR

CONSTRUCTION DOCUMENTS

CONTRACTOR FURNISHED

CIRCUIT

CIRCUIT BREAKER

CONNECTOR LIGHTING

CURRENT LIMITING FUSE

CEILING

CONDUIT ONLY

COMMUNICATION

CONCRETE

CONTINUE

CONTRACTOR

CURRENT TRANSFORMER

CABLE TELEVISION

COPPER

CURRENT

DIRECT CURRENT

DIMMER CONTROL PANEL

DIRECT DIGITAL CONTROLS

DEGREES CELSIUS

DEGREES FAHRENHEIT

DEMOLITION

DIAGRAM

DISCONNECT

DISTRIBUTION PANEL

DISCONNECT SWITCH

DRAWING

ELECTRICAL CONTRACTOR

ELECTRIC OR ELECTRICAL

ELEVATOR

EMERGENCY

ELECTROMAGNETIC INTERFERENCE

ELECTRICAL METALLIC TUBING

ENCLOSURE

EMERGENCY POWER OFF

EXISTING

FB

FIXT

FLA

FT

FU SW

FVNR

FVR

G

GEN

GFCI

GFP

GND

HID

HOA

HP

HT

HZ

IG

IMC

INCAND

IR

J-BOX

kV kVA kVAh kVAR kW kWh kWhM

LCP

LED

LF

LP

LRA

LT

LTG

LTG PNL

LTNG

LV

MAX

MB

MC

MCA

MCB

MCC

MDP

MECH

MH

MIN

MOCP

MLO

MS

MT

MTD

MTG

MTR

MTS

MV

MVA

MW

NA

NAC

NC

NEC

NEMA

NEUT, N

NFC

NFPA

NIC

NO

NTS

FEEDER BREAKER

FIXTURE

FULL LOAD AMPS

FEET OR FOOT

FUSED SWITCH

FULL VOLTAGE NON-REVERSING

FULL VOLTAGE REVERSING

ELECTRICAL GROUND

GENERATOR

GROUND FAULT

CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

GROUND

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTOMATIC

HORSEPOWER

HEIGHT

HERTZ

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

INCANDESCENT

INFRARED

JUNCTION BOX

KILOVOLT

KILOVOLT AMPERE

KILOVOLT AMPERE PER HOUR

KILOVOLT AMPERE REACTIVE

KILOWATT

KILOWATT HOUR

KILOWATT HOUR METER

LIGHTING CONTROL PANEL

LIGHT EMITTING DIODE

LINEAR FEET (FOOT)

LIGHT POLE

LOCKED ROTOR AMPS

LIGHT

LIGHTING

LIGHTING PANEL

LIGHTNING

LOW VOLTAGE

MAXIMUM

MAIN BREAKER

METAL-CLAD

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MECHANICAL

MANHOLE

MINIMUM

MAXIMUM OVERCURRENT PROTECTION

MAIN LUGS ONLY

MOTOR STARTER

MOUNT

MOUNTED

MOUNTING

METER

MANUAL TRANSFER SWITCH

MEDIUM VOLTAGE

MEGAVOLT-AMPERE

MEGAWATT

NOT APPLICABLE

NOTIFICATION APPLIANCE CABINET

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUTRAL

NOT FOR CONSTRUCTION

NATIONAL FIRE PROTECTION ASSOCIATION

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

OC

OCPD

OH

OL

OS

PB

PEC

PF

PH

PNL

PS

PVC

PWR

RCP

REC

RECPT

RM

RMC

RMS

REQD

SAC

SCC

SF

SI

SPD

SPEC

SURF

SW

SWBD OR SB

SWGR OR SG

TEL

TR

TV

TYP

UFD

UGND

UL

UPS

UTIL

V

VA

VAR

VFD

VOLT

W

WP/W

XFER

XFMR

ON CENTER

OVER CURRENT PROTECTION DEVICE

OVERHEAD

OVERLOAD

OCCUPANCY SENSOR

PULL BOX

PHOTOELECTRIC CELL

POWER FACTOR

PHASE

PANEL

POWER SUPPLY

POLYVINYL CHLORIDE (PLASTIC)

POWER

REFLECTED CEILING PLAN

RECESSED

RECEPTACLE

ROOM

RIGID METAL CONDUIT

ROOT MEAN SQUARE

REQUIRED

SMALL APPLIANCE CIRCUIT

SHORT CIRCUIT CAPACITY

SQUARE FOOT (FEET)

INTERNATIONAL SYSTEM OF UNITS

SURGE PROTECTIVE DEVICE

SPECIFICATION

SURFACE

SWITCH

SWITCHBOARD

SWITCHGEAR

TELEPHONE

TAMPER RESISTANT

TELEVISION

TYPICAL

UNDERFLOOR DUCT

UNDERGROUND

UNDERWRITERS LABORATORY

UNINTERRUPTIBLE POWER SUPPLY

UTILITY

VOLT

VOLT AMPERE

VOLT AMPERE REACTIVE

VARIABLE FREQUENCY DRIVE

VOLTAGE

WATT/WEATHERPROOF (WHILE IN USE)

WEATHERPROOF

TRANSFER

TRANSFORMER

P R O J E C T P H A S I N G N A R R A T I V E THESE CONTRACT DRAWINGS ARE ARRANGED IN CAD STANDARD FORMAT; 100-SERIES DRAWINGS ARE FLOOR PLANS, 400-SERIES ARE ENLARGED PLANS, 500-SHEETS ARE DETAIL SHEETS, 600-SHEETS ARE ONE-LINE DIAGRAMS, AND 700-SHEETS ARE SCHEDULES. A/E RECOMMENDS REVIEWING ONE-LINE DIAGRAMS FIRST, AS MAJORITY OF WORK IS INDICATED THERE.

IN GENERAL, SHEET TYPES LISTED BELOW INDICATE THE FOLLOWING TYPE OF WORK:

- 100-SERIES DRAWINGS IDENTIFY ELECTRICAL DISTRIBUTION EQUIPMENT THAT REQUIRE MODIFICATIONS INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING: EQUIPMENT UPGRADES, EQUIPMENT REPLACEMENTS, OVER-CURRENT PROTECTIVE DEVICE (OCPD) REPLACEMENT, AND TIME-CURRENT CURVE (TCC) ADJUSTMENTS.

- 400-SERIES DRAWINGS INDICATE DETAILED ELECTRICAL PLAN LAYOUTS FOR VARIOUS TASKS.

- 500-SERIES DRAWINGS INDICATE ELECTRICAL DETAILS, ELEVATIONS, AND WIRING DIAGRAMS.

- 600-SERIES DRAWINGS INDICATE ALL ELECTRICAL WORK IMPACTING FACILITY ONE-LINE DIAGRAMS.

- 700-SERIES DRAWINGS INDICATE ELECTRICAL LOAD/PANEL SCHEDULES, LUMINAIRE SCHEDULES, ELECTRICAL DEFICIENCY CORRECTIONS SCHEDULES, AND PROTECTIVE DEVICE

CHANGE SCHEDULES.

ALL ELECTRICAL PHASING REQUIREMENTS SHALL BE RESPONSIBILITY OF CONTRACTOR. PHASING INFORMATION SHOWN ON DRAWINGS IS PROVIDED FOR REFERENCE ONLY AND REPRESENTS ONE POSSIBLE METHOD OF ACHIEVING DESIGN INTENT.

CONTRACTOR SHALL VERIFY ALL PHASING, CONNECTIONS, AND COORDINATION REQUIREMENTS VIA A DETAILED PHASING PLAN WITH VA PRIOR TO COMMENCING ANY WORK.

CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR PLANNING AND EXECUTING ALL WORK IN A MANNER THAT MINIMIZES SYSTEM DOWNTIME AND DISRUPTIONS TO EXISTING OPERATIONS. CONTRACTOR SHALL PROVIDE, INSTALL, AND MAINTAIN ALL REQUIRED TEMPORARY POWER SOURCES, WIRING, AND CONNECTIONS NECESSARY TO MAINTAIN CONTINUOUS SERVICE DURING CONSTRUCTION OR CHANGEOVER ACTIVITIES.

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE CODES, STANDARDS, AND REGULATIONS, AND CONTRACTOR SHALL COORDINATE WITH VA TO CONFIRM ACCEPTANCE OF ANY PROPOSED PHASING OR SEQUENCING METHODS. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED AND RESOLVED PRIOR TO PROCEEDING WITH INSTALLATION.

ALL WORK SHALL BE CONDUCTED AFTER-HOURS, UNLESS DIRECTED OTHERWISE BY VA; REFERENCE "PROJECT WORK HOURS" SECTION ON SHEET G-001 FOR EXACT WORKING HOUR REQUIREMENTS.

GENERAL PROJECT CONSTRUCTION SEQUENCING SHALL BE IMPLEMENTED AS FOLLOWS:

1. BUILDING 1: REFERENCE BUILDING 1 PHASING ON SHEETS 001EP401a AND 001EP401b.

2. BUILDING 3: REFERENCE BUILDING 3 PHASING ON SHEET 003EP401.

3. BUILDING 11: REFERENCE BUILDING 11 PHASING ON SHEET 011EP401a.

4. BUILDING 12: REFERENCE BUILDING 12 PHASING ON SHEET 012EP401.

5. ALL BUILDINGS WITHIN SCOPE: REPLACE, MODIFY, OR UPGRADE EXISTING ELECTRICAL POWER DISTRIBUTION EQUIPMENT AS INDICATED IN DRAWINGS AND SPECIFICATIONS. NOTE - VARIOUS SHUTDOWNS WILL BE REQUIRED; CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND POWER DISTRIBUTION AS NEEDED.COORDINATE WITH VA AS REQUIRED.

6. ONCE ALL PROJECT PHASES ARE COMPLETE, THE CONTRACTOR SHALL PROVIDE THE FOLLOWING TASKS AT ANY TIME (WITH VA APPROVAL):

A. A FACILITY WIDE ARC-FLASH HAZARD RISK ASSESSMENT WITH REPORT AND LABELING SHALL BE PERFORMED IN ACCORDANCE WITH SPECIFICATION 26 05 73.

B. FACILITY WIDE GROUND RESISTANCE TESTING PER VHA DIRECTIVE 1028-8.J(6)(e). REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR ADDITIONAL INFORMATION.

D R A W I N G S E T N A R R A T I V E

Revisions: Date:

CONTRACTOR SHALL PROVIDE UPDATED TYPEWRITTEN CIRCUIT PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

CONTRACTOR SHALL FIELD VERIFY PRIOR TO SUBMITTAL THAT THEIR PROPOSED EQUIPMENT SELECTION (I.E. PANELBOARD, GENERATOR, ETC.) WILL FIT WITH ALL REQUIRED ELECTRICAL CLEARANCES. CONTRACTOR SHALL PROVIDE STATEMENT CONFIRMING THAT

EQUIPMENT WILL FIT IN ALLOCATED SPACE ON SUBMITTAL.

WHERE CIRCUIT / CONDUCTORS ARE INDICATED AND RACEWAYS QUANTITY OR SIZE IS NOT INDICATED, CONTRACTOR SHALL PROVIDE AND SIZE RACEWAY PER NEC.

Division 25-27

SECTION

SHEET WHERE SECTION

IS TAKEN FROM

SECTION LETTER

DETAIL NUMBER

SHEET ON WHICH DETAIL APPEARS

DETAIL AREA

XXX CONDUIT & WIRE TAG

(REFER TO CONDUIT AND WIRE SCHEDULE)

KEY NOTE

XXX

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW DENOTES

DIRECTION TAKEN

SHEET WHERE DETAIL IS TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

XXX

A

XXX

A

XXX

SHEET WHERE SECTION

IS TAKEN FROM

SCALE

SECTION LETTER

1 LOAD METERING POINT NOTE

CONDUIT OR EQUIPMENT TO BE REMOVED

CONDUIT UNDER FLOOR, IN FLOOR SLAB, OR ROUTED

UNDERGROUND

CONDUIT CONCEALED IN WALL, IN CEILING, OR ABOVE

ACCESIBLE CEILING WHERE POSSIBLE, OTHERWISE EXPOSED

EXTRA-HARD USAGE FLEXIBLE CORD

FLEXIBLE CONDUIT

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

FIRE WALL (2 HOURS MIN.)

2-HOUR FIRE BARRIER

1-HOUR FIRE BARRIER

BOLD DOT INDICATES CONDUCTOR BOND / TERMINATION

BOND TO EQUIPMENT

BOND / TERMINATION

CONDUCTORS

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

10/30/2025 10:52:16 AM

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_GENSHEETS_EL_SDB.rvt

EG002

ELECTRICAL LEGENDS

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

D I V 2 6 - L E G E N D

MOTOR

DELTA CONNECTION

POWER

THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.

REFERENCE PLANS FOR ALL UTILIZED SYMBOLS

PE

DS

X

X

X

ALL INTERIOR AREAS TO HAVE MANUAL 0N/AUTO OFF LIGHTING

CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY SENSORS.

EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR IS NOTED.

PHOTO ELECTRIC SENSOR

DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING

CONTROL. SENSOR SHALL BE CEILING MOUNTED.

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

RECEPTACLE, SWITCHED DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]

CENTERS OR AS DESIGNATED ON DRAWINGS), MTD

3'-6" [1067mm] AFF OR AS INDICATED.

SWITCH

F = FUSED SWITCH K = KEY OPERATED

L = LOCK LM = LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING MC = MOMENTARY CONTACT

MP = MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT

(THERMAL TYPE)

PB = PUSH BUTTON STATION RC = REMOTE CONTROL

WP = WEATHER PROOF X = EXPLOSION PROOF

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DIMMER K = KEY OPERATED

LV = LOW VOLTAGE P = WITH PILOT LIGHT

LM = LOW VOLTAGE MASTER RC = REMOTE CONTROL

PB = PUSH BUTTON STATION WP = WEATHER PROOF

T = TIMER OPERATED Mo = OCCUPANCY SENSOR

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH

DIRECTIONAL ARROWS AND FACES AS SHOWN

LIGHT FIXTURE, BOLLARD

LIGHTING

x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)

S

S

OS

EMERGENCY NORMAL

X X

X X

X X

X X

X X

X X

XX

X X

X X

X X

X X

X X

X X

X X

X = DENOTES LUMINAIRE TAG NAME

RECESSED DOWNLIGHT FIXTURE

LIGHT FIXTURE, RECESSED, 2'x4'

LIGHT FIXTURE, RECESSED, 1'x4'

LIGHT FIXTURE, RECESSED, 1'x8'

LIGHT FIXTURE, RECESSED, 2'x2'

LIGHT FIXTURE, SURFACE

MOUNTED, 2'x4'

LIGHT FIXTURE, SURFACE

MOUNTED, 1'x4'

LIGHT FIXTURE, SURFACE

MOUNTED, 1'x8'

LIGHT FIXTURE, SURFACE

MOUNTED, 2'x2'

STRIP LIGHTING, 4' LONG

LIGHT FIXTURE, WALL MOUNTED

LIGHT POLE, POST TOP MOUNT

LUMINAIRE

LIGHTING WALL PACK, EXTERIOR

BUILDING

CIRCUITING DESIGNATIONS

WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE, LUMINAIRE, OR MISC LOAD, THAT LOAD SHALL BE CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER. CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND, UNLESS OTHERWISE NOTED; IF FURTHER THAN 70', PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP. SEE

EXAMPLES BELOW:

RECEPTACLE:

PANELBOARD OR POWER SOURCE NAME = "P1"

CIRCUIT NUMBER OF POWER SOURCE = "2"

LUMINAIRE:

PANELBOARD OR POWER SOURCE NAME = "PP3"

CIRCUIT NUMBER OF POWER SOURCE = "4"

TYPE LUMINAIRE TAG NAME, REFERENCE LUMINAIRE SCHEDULE = "L1"

LIGHTING CONTROL SWITCH LEG = "a"

ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT = PP3-4

MISC. LOAD:

PANELBOARD OR POWER SOURCE NAME = "PP"

CIRCUIT NUMBER OF POWER SOURCE = "7"

P1-2 P1-2

HEAT PUMP

PP-7

L1 a

PP3-4

FACP

PP-7

G E N E R A L S Y M B O L S

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOXPB

J

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

CIRCUIT BREAKER

DRAWOUT AIR CIRCUIT BREAKER

RELAY; NUMBER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE

51 = AC-TIME OVER CURRENT

67 = AC-DIRECTIONAL OVER CURRENT

86 = LOCKING OUT

DISCONNECT SWITCH

BATTERY

CAPACITOR

METER

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

TRANSFORMER, PLANT

M

A

V

W

WH

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT

CIRCUIT INTERRUPTER

RECEPTACLE, QUADRUPLEX

RECEPTACLE, SINGLE

Revisions: Date:

PNL-P12

GROUND ROD

GROUND ROD WITH TEST WELL

EARLY STREAMER EMISSIONS

(ESE) AIR TERMINAL

CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE

XXXX

CONDUIT 3/4"C, 3#12 PHASE, 1#12 N, & 1#12 GND

UNLESS SHOWN OTHERWISE. (EXAMPLE SHOWN: TO

PANEL P1, CIRCUIT 1,3,5). LONG TICK FOR NEUTRAL

WIRE; ONE SHORT TICK FOR EACH PHASE WIRE;

GROUND SIZED PER NEC. NOTE THAT A SECOND

SHORT TICK FOR LUMINAIRES IS FOR A TRAVELER

WIRE.

P1-1,3,5

LIGHTNING ARRESTOR

LA

GREEN

HOUSE

GARDEN

SHEDO

VE

R

H

EA

D R

O W

GAZEBO

L

GREEN

HOUSE

GARDEN

SHED

O

VE

R H

EA

D

R O

W

GAZEBO

L

013EP101 1

022EP101

007EP101

003EP101

003EP102

012EP102

018EP101

020EP101

019EP101

015EP1011

011EP101a

020EP102

011EP101b

011EP101c

011EP101d

011EP102

011EP103

011EP104

011EP105

015EP102

023EP101

025EP103

021EP101

014EP102

T1819EP101

TR3EP101

001EP102

001EP101c

001EP101b

001EP101a

001EP100

025EP102

016EP101

013EP102

005EP101

006EP101

004EP102

002EP102

002EP101

012EP101

018EP102

004EP101

025EP101

014EP101

024EP101

015EP103

EP401

TR3

FITNESS

CENTER

(14)

MUSEUM

(T1819)

SNAP LAB

(21)

WELL

(23)

BARNES

REHABILITATION

UNIT

(11)

D WING

F WING

E WING

SPECIALTY

CARE

CLINICS

(20)

STORAGE

BLDG

(19)

PRIMARY

CARE

SUPPORT

BUILDING

(15)

PRIMARY

CARE

(24)

TRANSPLANT

LODGER

(18)

RRTP

(12)

LAUNDRY/

WAREHOUSE

(2)

BOILER

(3)

MAINTENANCE

SHOPS

(4)

EM. GEN

(6)

GROUNDS (5)

TELE

(13)

STORAGE

(22)

WELL

(7)

STORAGE

(16)

FISHER

HOUSE

(25)

COMMUNITY

LIVING

CENTER

(1)

C WING B WING

LOT #19

CLARK

COUNTY

CENTER

FOR

COMMUNITY HEALTH

("CCH")

(17)

LOT #9

LOT #8

LOT #8

LOT #1

NAVY LANE

LOT #2

SRO

AIR FORCE W

AY

LOT #6

LO

T #

FREEDOM PATH

(26)

LO

T #

LOT #17

LOT #21

LOT #2

LOT #1

POW / MIA ROAD

LOT #14

LOT #14

LOT #13

POW / MIA ROAD

AIR FORCE WAY

LOT #3

LOT #10

LOT #11

PO

W

/ M

IA

R

OA

D

PO

W

/ M

IA

R

OA

DLOT #18

NEW

IMAGING

(27)

COAST GUARD STREET

MARINE CORPS DRIVE MARINE CORPS DRIVE

LOT #12

AR

MY

A

VE

NU

E

ARMY AVENUE

E FOURTH PLAIN BLVD

FO

RT

VA

NC

OU

VE

R W

AY

LOT #4

027EP102

EP401

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:36:13 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_GENSHEETS_EL_SDB.rvt

ES001

OVERALL ELECTRICAL SITE PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

GENERAL NOTES

1. PLAN INCLUDED FOR OVERALL SITE REFERENCE.

- 1" = 80'-0"

1 OVERALL ELECTRICAL SITE PLAN

PROJECT

NORTH

2'0 4' 6'

Revisions: Date:

AREA SHOWN

MAIN WATER

SERVICE PIPE

'01-MCC-E1'

'01-MCC-1'

F G H I J

FROM PANELBOARD "LSHA"

ON FLOOR ABOVE.

F G H I J

MAIN WATER

SERVICE PIPE

'01-MCC-E1'

'01-MCC-1'

FROM 001EP401a

001-G-02

001-P-05

EP5016

001-G-01

FROM 001EP401b

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:24:11 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt

001EP100

BLDG 001 - LEVEL 00 - ELECTRICAL PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

TRUE

NORTH

- 1/8" = 1'-0"

1 BLDG 001 - LEVEL 00 - DEMOLITION ELECTRICAL PLAN

LEVEL 00

- 1/8" = 1'-0"

2 BLDG 001 - LEVEL 00 - ELECTRICAL PLAN0 10' 20'

PROJECT

NORTH

0 10' 20'

PROJECT

NORTH

Revisions: Date:

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

KEY PLAN

KEY NOTES

1 EXISTING '01-MCC-E1' SHALL BE REFED FROM 'ATS 10' VIA

PANELBOARD '01-C1'. REFERENCE ONE-LINE DIAGRAM ON

SHEET 001EP602 FOR ADDITIONAL INFORMATION.

EXISTING EQUIPMENT CONTAINING OVERCURRENT

PROTECTIVE DEVICE WITH SETTINGS TO BE MODIFIED.

REFERENCE CORRESPONDING BUILDING ONE-LINE

DIAGRAMS AND PROTECTIVE DEVICE CHANGES SCHEDULE

FOR PROTECTIVE DEVICE SETTINGS ADJUSTMENT AND / OR

REPLACEMENT.

EXISTING CONDUCTORS AND RACEWAY SERVING '01-MCC-E1'

SHALL BE DEMOLISHED BACK TO SOURCE AND REPLACED.

MODIFIED EQUIPMENT. REFERENCE CORRESPONDING

BUILDING ONE-LINE DIAGRAMS FOR ADDITIONAL

INFORMATION.

PROVIDE BOND TO TERMINATE TO BUILDING STEEL. BOND

CONDUCTOR TO PANELBOARD '01-MSB' PER NEC

REQUIREMENTS.

PROVIDE BOND TO TERMINATE TO MAIN WATER SERVICE

PIPE. BOND TO PANELBOARD '01-MSB' PER NEC

REQUIREMENTS.

APPROXIMATE FOOTPRINT OF ROOM A-117 ON FLOOR

ABOVE. REFERENCE ENLARGED FLOOR PLANS ON SHEETS

001EP401a AND 001EP401b FOR ADDITIONAL INFORMATION.

PBPB

PBPB

PANEL "01-KIOSK"

PANEL '01-A-105H'

CHAPEL

A-120

MAIL/COPY

CHAPLAIN

A-120A

OFFICE

A-122C

IV CLEAN

ROOM

A-122A

SATELLITE

PHARMACY

A-122B

VESTIBULE

A-122

CLOSET,

TELE.

A-121

CORRIDOR

C-8

OFFICE

RECREATION

A-105A

STORAGE

A-105H

STORAGE

A-105G

DISHWASHER

A-113C

DRY

STORAGE

A-115

DIETETICS

A-113

STORAGE,

CART

CORRIDOR

C-5A

N.F.S. CLEAN

PREP

C-41

WALK-IN

REFER.

A-113D

REC. /

THERAPY

STORAGE

A-110

CORRIDOR

C-5

VESTIBULE

C-5B

TOILET, M.

A-108

TOILET, F.

A-107

OFFICE

A-105D

LIBRARY

A-105F

LOBBY

C-2

STORAGE

A-105J

CORRIDOR

C-3

OFFICE, DIET.

A-104

OFFICE

A-103A

OFFICE

A-103

OFFICE

A-102

OFFICE

A-101

CORRIDOR

C-4

CLOSET,

TELE.

A-100

VESTIBULE

C-1

CONFERENCE

/ CLASS

ROOM

A-106

LOUNGE,

EMP.

A-109

LOCKER

ROOM

A-109D

TOILET, M.

A-109E

TOILET, F.

A-109C

LOCKER

ROOM

A-109B

VESTIBULE

A-109A

STORAGE

A-109F

E.M.S. H.A.C.

A-112

N.F.S. H.A.C.

A-111

N.F.S.

OFFICE

A-114

N.F.S.

STORAGE

A-119

ELECT. RM

A-117

CORRIDOR

C-7

REC. /

THERAPY

STORAGE

A-114A

CORRIDOR

C-6

OXY.

STORAGE

A-116

GENERATOR

YARD

DINING ROOM

/ KITCHEN

A-105

F G H I J K L

AREA A

AREA B

SEE SHEET 001EP101b

AREA A

AREA C

SEE SHEET 001EP101c

001-G-03

001-P-09

001-G-03

001-P-08

001EP401b

001EP401b

001EP401a

001EP401a

AREA SHOWN

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:24:14 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt

001EP101a

BLDG 001 - LEVEL 01 - AREA A - ELECTRICAL

PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

- 1" = 10'-0"

1 BLDG 001 - LEVEL 01 - AREA A - ELECTRICAL PLAN 0 10' 20'

PROJECT

NORTH

TRUE

NORTH

AREA A

Revisions: Date:

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

KEY PLAN

KEY NOTES

1 CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO

IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.

CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH

IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE

TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.

REFERENCE ASSOCIATED PANEL SCHEDULE FOR

ADDITIONAL INFORMATION.

PB

MGA

(LOCAL)

MGV(02)

MGV(MA/MV)

MGV

(MA/MV)

MGV (02)

STORAGE

A-105J

TOILET,

STAFF

B-102

OFFICE, HEAD

NURSE

B-107

CORRIDOR

C-9

NURSE

STATION

C-11

001EP401c

001EP401c

AREA A

SEE SHEET 001EP101a

AREA B

LOUNGE

B-100

KIT. NOUR.

B-101

CLOSET,

TELE.

B-103

MED.

OMNI-CELL

B-104

MEDICATION

B-105

OMNI-CELL

B-106 OFFICE, S.W.

B-108

4 BED ROOM

B-109

UTILITY,

LAUNDRY

B-110

BEDROOM

B-111

HAC

B-112

STAFF

B-113

CLEAN LINEN

B-114

BATH /

SHOWER

B-115

ELEC.

B-116

2 BED ROOM

B-117

2 BED ROOM

B-118

2 BED ROOM

B-119

2 BED ROOM

B-120

2 BED ROOM

B-121

2 BED ROOM

B-122

2 BED ROOM

B-123

2 BED ROOM

B-124

2 BED ROOM

B-125

2 BED ROOM

B-126

2 BED ROOM

B-127

2 BED ROOM

B-128

HOSPICE

KITCHEN

B-129

FAMILY ROOM

B-130

TOILET

B-132A

BEDROOM

B-132

UTILITY

SOILED

B-133

KITCHEN

B-134

2 BED ROOM

B-135

2 BED ROOM

B-136

BED ROOM

B-137

2 BED ROOM

B-138

2 BED ROOM

B-139

2 BED ROOM

B-140

2 BED ROOM

B-141

2 BED ROOM

B-142

2 BED ROOM

B-143

2 BED ROOM

B-144

1 BED ROOM

B-145

1 BED ROOM

B-146

OFFICE

B-100B

STORAGE

B-100A

OFFICE

B-12C

B-132B

CORRIDOR

C-10

OFFICE,

WARD CLERK

C-12

CORRIDOR

C-16

TOILET

B-115A

CORRIDOR

C-14

BATHROOM

B-135A

CORRIDOR

C-13

OFFICE

B-111C

B-111B

CORRIDOR

C-17

TOILET

B-134A

TOILET

B-138A

TOILET

B-137A

TOILET

B-141A

TOILET

B-142A

BATHROOM

B-146A

BATHROOM

B-145A

CORRIDOR

C-15

TOILET

B-118A

TOILET

B-117A

TOILET

B-121A

TOILET

B-122A

TOILET

B-126A

TOILET

B-125A

BATHROOM

B-129A

BATHROOM

B-130A

TOILET

B-109A

TOILET

B-111A

M N O P Q

CONTINUE TO

SHEET 001EP102

EP501TYP.

001-G-05

001-G-04

001-G-03

001-P-08

AREA SHOWN

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

10/30/2025 10:55:13 AM

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt

001EP101b

BLDG 001 - LEVEL 01 - AREA B - ELECTRICAL

PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

- 1" = 10'-0"

1 BLDG 001 - LEVEL 01 - AREA B - ELECTRICAL PLAN 0 10' 20'

PROJECT

NORTH

TRUE

NORTH

AREA B

Revisions: Date:

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

KEY PLAN

KEY NOTES

APPROXIMATE LOCATION OF MECHANICAL ROOM P-100 ON

FLOOR ABOVE. REFERENCE ENLARGED FLOOR PLANS ON

SHEET 001EP402 FOR ADDITIONAL INFORMATION.

PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM

3-POINT FALL-OF-POTENTIAL TEST. GROUND RESISTANCE

TESTING SHALL BE PER VHA DIRECTIVE 1028-8.J(6)(e).

REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR

ADDITIONAL INFORMATION.

1 BED ROOM

C-133

162 SF

2 BED ROOM

C-134

241 SF

1 BED ROOM

C-135

164 SF

2 BED ROOM

C-136

241 SF

2 BED ROOM

C-137

250 SF

2 BED ROOM

C-138

251 SF

2 BED ROOM

C-139

250 SF

2 BED ROOM

C-140

251 SF

2 BED ROOM

C-141

237 SF

2 BED ROOM

C-142

240 SF

2 BED ROOM

C-143

251 SF

2 BED ROOM

C-144

251 SF

1 BED ROOM

C-145

171 SF

1 BED ROOM

C-146

169 SF

CORRIDOR

C-26

651 SF

BATHROOM

C-146A

61 SF

TOILET

C-142A

50 SF

TOILET

C-138A

50 SF

TOILET

C-134A

50 SF

TOILET

C-133A

50 SF

TOILET

C-137A

50 SF

TOILET

C-141A

51 SF

BATHROOM

C-145A

60 SF

CORRIDOR

C-25

150 SF

CORRIDOR

C-24

610 SF

CORRIDOR

C-19

415 SF

CORRIDOR

C-22

552 SF

LINEN CLEAN

C-129

128 SF

EMS

STORAGE

C-130

155 SF

SOILED LINEN

C-131

60 SF

ELEC. ROOM

C-132

79 SF

TOILET

C-128A

114 SF

C-128B

31 SF

OFFICE

C-128C

73 SF

1 BED ROOM

C-128

333 SF

1 BED ROOM

C-126

329 SF

TOILET

C-126A

109 SF

C-126B

31 SF

OFFICE

C-126C

73 SF

HAC

C-127

22 SF

HAC

C-127A

62 SF

OMNI-CELL

STORAGE

C-125

94 SF

STAFF / CONF.

C-123

161 SF

BATH /

SHOWER

C-105

520 SF

MED

OMNI-CELL

C-121

72 SF

LAUNDRY

C-105A

47 SF

SOILED

UTILITY

C-107

85 SF

BATHROOM

C-109A

68 SF

2 BED ROOM

C-106

240 SF

2 BED ROOM

C-108

240 SF

2 BED ROOM

C-109

245 SF

2 BED ROOM

C-110

250 SF

2 BED ROOM

C-111

250 SF

2 BED ROOM

C-112

251 SF

2 BED ROOM

C-113

250 SF

2 BED ROOM

C-114

240 SF

2 BED ROOM

C-115

240 SF

2 BED ROOM

C-116

251 SF

2 BED ROOM

C-117

251 SF

1 BED ROOM

C-118

171 SF

1 BED ROOM

C-119

171 SF

CORRIDOR

C-120

652 SF

TOILET

C-111A

50 SF

TOILET

C-110A

50 SF

TOILET

C-114A

50 SF

TOILET

C-115A

50 SF

BATHROOM

C-119A

60 SF

BATHROOM

C-118A

60 SF

TOILET

C-106A

50 SF

1 BED ROOM

C-104

356 SF

TOILET

C-104A

109 SF

C-104B

27 SF

OFFICE

C-104C

73 SF

ELEC

C-102

28 SF

STORAGE

C-100A

18 SF

OFFICE

C-100B

90 SF

LOUNGE

C-100

210 SF

NURSE

STATION

C-20

217 SF

OFFICE,

CLERK

C-21

84 SF

OFFICE, HEAD

NURSE

C-124

108 SF

MEDICATION

C-122

67 SF TOILET,

STAFF

34 SF

KITCHEN,

NOURISH.

C-101

67 SF

CORRIDOR

C-18

395 SF

AREA A

SEE SHEET 001EP101a

AREA C

13 14

A B C D E

CONTINUE TO

SHEET 001EP102

EP501 TYP.

001-G-04

001-G-05

001-G-03

001EP401c

001EP401c

001-P-09

AREA SHOWN

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:24:17 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt

001EP101c

BLDG 001 - LEVEL 01 - AREA C - ELECTRICAL

PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

- 1" = 10'-0"

1 BLDG 001 - LEVEL 01 - AREA C - ELECTRICAL PLAN 0 10' 20'

PROJECT

NORTH

TRUE

NORTH

AREA C

Revisions: Date:

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

KEY PLAN

KEY NOTES

11 APPROXIMATE LOCATION OF MECHANICAL ROOM P-101 ON

FLOOR ABOVE. REFERENCE ENLARGED FLOOR PLANS ON

SHEET 001EP402 FOR ADDITIONAL INFORMATION.

PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM

3-POINT FALL-OF-POTENTIAL TEST. GROUND RESISTANCE

TESTING SHALL BE PER VHA DIRECTIVE 1028-8.J(6)(e).

REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR

ADDITIONAL INFORMATION.

13 14 15

F G H I J K L

30 31 32

A B C D E

M N O P Q

CONTINUE TO

SHEET 001EP101b

CONTINUE TO

SHEET 001EP101c

EP502

EP502TYP.

001-G-04

001-G-04

AREA SHOWN

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

30/10/2025 8:24:19 am

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_01_EL_SDB.rvt

001EP102

BLDG 001 - ROOF - LIGHTNING PROTECTION

PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

- 1" = 20'-0"

1 BLDG 001 - ROOF - LIGHTNING PROTECTION PLAN

TRUE

NORTH

0 10' 20'

PROJECT

NORTH

ROOF

Revisions: Date:

GENERAL NOTES

KEY PLAN

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

B

E F H I K LA C D

FINISH AREA

B-100

MENDING

B-101

STORAGE

B-102

STERILE PACK

B-103

TELE/COM

B-104

MECHANICAL ROOM

B-105

SUPERVISOR

B-106

HAC

B-107

WOMEN'S TOILET

B-108

MEN

B-109

LUNCH ROOM

B-110

MAINTENANCE REPAIR

B-111

STAFF

B-112

WAREHOUSE

B-113

SORT / WASH AREA

B-114

CORRIDOR

C1-4

CORRIDOR

C1-5

LIQUID SUPPLY & STORAGE

B-114A

CORRIDOR

C1-7

CORRIDOR

C1-6

T T T

PANEL '02-LLC' SEC 2

PANEL '02-LLC' SEC 1

G J

LINT COLLECTOR

30A DISCONNECT

PANEL '02-LHC'

002EP401

002EP401

CHILLER EQ.

PANEL '02-L1A'

MAIN FIRE RISER

PANEL '02-WL'

PANEL '02-WH'

XFMR (ABOVE)

75 kVA STEPDOWN

TRANSFORMER

PANEL '02-WHA' 1POWER POLE

XFMR'S ON

MEZZANINE

ABOVE

CONTINUE TO

SHEET 002EP102

CONTINUE TO

SHEET 002EP102

002-G-04 002-G-04

EP501 TYP.

PANEL '02-P1'

GENERAL STORES

A-100

ADMIN OFFICE

A-101

STORAGE

A-102

FORMS STORAGE / OFFICE

A-103

LOUNGE

A-104

ENTRY

A-104A

MEN

A-104B

WOMEN

A-104C

HAC

A-105

FACILITIES LOGISTIC MGR

A-106

WAREHOUSE SUPERVISOR

A-106A

SHOWER

C-100

SHOWER

C-101

LOCKERS

C-102

LOCKERS

C-103

STORAGE, SPD

C-104 PREPARATION

C-105

SOILED RECEIVING

C-106

HAC

C-107

CORRIDOR

C-1.10

HALL 2

C-1.11

HALL 1

C-1.12

SUPPLY

A-100A

STORAGE

A-100B

VAULT

A-100C

OFFICE

A-100D

SUPPLY

A-100D

CORRIDOR

C1-2

CONTINUE TO

002EP402

CONTINUE TO

003EP401

MAIN WATER

SERVICE PIPE

002-G-05

002-G-06

002-G-03

002-G-03

002-G-02

003-G-01

002-G-01

EP501

PANEL '02-L1A'

SEC 2

ELEC. ROOM

AREA SHOWN

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

10/30/2025 10:57:10 AM

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_02_EL_SDB.rvt

002EP101

BLDG 002 - LEVEL 01 - ELECTRICAL PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

- 1/16" = 1'-0"

1 BLDG 002 - LEVEL 01 - ELECTRICAL PLAN

TRUE

NORTH

0 10' 20'

PROJECT

NORTH

BLDG 002

Revisions: Date:

KEY PLAN

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX

PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE

PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES,

AND VA AS REQUIRED.

KEY NOTES

EXISTING PANELBOARD SHALL BE DEMOLISHED AND

REPLACED. PRESERVE ALL EXISTING CIRCUITS FOR

RETERMINATION. REFERENCE ONE-LINE DIAGRAMS ON

SHEETS 002ED601 AND 002EP601.

PROVIDE BUILDING GROUNDING ELECTRODE SYSTEM

3-POINT FALL-OF-POTENTIAL TEST. GROUND RESISTANCE

TESTING SHALL BE PER VHA DIRECTIVE 1028-8.J(6)(e).

REFERENCE GROUNDING SPECIFICATION 26 05 26 FOR

ADDITIONAL INFORMATION.

EXISTING EQUIPMENT CONTAINING OVERCURRENT

PROTECTIVE DEVICE WITH SETTINGS TO BE MODIFIED.

REFERENCE CORRESPONDING BUILDING ONE-LINE

DIAGRAMS AND PROTECTIVE DEVICE CHANGES SCHEDULE

FOR PROTECTIVE DEVICE SETTINGS ADJUSTMENTS AND / OR

REPLACEMENT.

CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO

IDENTIFY UNKNOWN CIRCUIT BREAKER LOADS.

CONTRACTOR SHALL UPDATE CIRCUIT DIRECTORY WITH

IDENTIFIED LOAD. CIRCUIT DIRECTORY SHALL BE

TYPE-WRITTEN AND PRINTED, NOT HANDWRITTEN.

REFERENCE ASSOCIATED PANEL SCHEDULE FOR

ADDITIONAL INFORMATION.

002-G-05

IN OFFICE

A-101

EP501

B

E F H I K LA C D

G J

002EP402

CONTINUE TO

SHEET 002EP101

CONTINUE TO

SHEET 002EP101

EP502 TYP.

EP502

002-G-03

002-G-03

1/ 2'

'-0

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8'

'-0

1/

'-0

1/ 4'

'-0

1' 2'

1' 1/

2' 2'

1/ 2'

1'

'-0

3'

'-0

1' m m

M

M

M

M

M

M

M m m

M m m

M

0.

5M

M 0.

5M 0.

M m m

M m m

M

.2

5M 0.

M

0.

M 0.

M m m

M

M

0.

5M m m

M

3/ 8'

'-0

1'

2' 4'

0.

M 0.

M m m

M

1/

2'

'-0

''0 2'

1/ 2'

1' 3' m m

M

0.

M 0.

M

6'

'-0

1/

4" 1/

2"

M

M

7.

m m

M

3/

'-0

8'

4' 4'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES

10/30/2025 8:15:38 AM

Autodesk Docs://648-20-116 VA WA Vancouver Electrical FCA/VAVW_02_EL_SDB.rvt

002EP102

BLDG 002 - ROOF - LIGHTNING PROTECTION

PLAN

DCW/LRL JGD/KDB

100% CONSTRUCTION

DOCUMENTS

10/30/2025

648-20-116CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VA

VANCOUVER, WA

VHAPORHCS, VANCOUVER CAMPUS

1601 E 4TH PLAIN BLVD, VANCOUVER, WA 98661

0 10' 20'

PROJECT

NORTH

TRUE

NORTH

- 1/16" = 1'-0"

1 BLDG 002 - ROOF - LIGHTNING PROTECTION PLAN

BLDG 002

Revisions: Date:

KEY PLAN

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT.

CONTRACTORS SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO THE COR.

EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATION SHALL BE FIELD VERIFIED AND REDLINED

VIA CONTRACTOR.

IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT BREAKERS

HAVE BEEN REPLACED AND/OR ADJUSTED, IMMEDIATELY

INFORM AND COORDINATE WITH VA AS REQUIRED.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED.

REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR

ADDITIONAL INFORMATION.

WHERE PRACTICAL, RACEWAYS / CONDUCTORS SHALL BE

ROUTED VERTICALLY UP WALL AND HORIZONTALLY ON

CEILING TO PRESERVE WALL SPACE FOR FUTURE USE.

CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL

FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE

MORE THAN 270…