6.Polk_Building_Fire_Spirnkler.pdf

PDF 3 MB Posted

Attached to
Phase 2 Polk Building Renovations
Solicitation number
PSUT-26-06
Issued by
Broward County, Florida

About this file

This document is a Fire Sprinkler Performance Specification prepared by Kamm Consulting (Project #2022-0686) for the Polk Building Renovation project commissioned by the City of Pembroke Pines, Florida. The specification outlines comprehensive requirements for designing, permitting, and installing a new fire sprinkler system for the 6,060 square foot building located at 8200 South Palm Drive, Pembroke Pines, FL 33025. The system must be designed and installed by a licensed and certified fire sprinkler contractor in accordance with the 2020 Florida Building Code, Florida Fire Prevention Code (7th Edition), NFPA 13 (2016 Edition), NFPA 14, NFPA 20, and NFPA 24 (2016 Editions), as well as local Authority Having Jurisdiction (AHJ) requirements. The specification designates three hazard classifications for different areas: Light Hazard (offices, lobbies, restaurant seating) with 0.10 GPM/sqft density and 225 sqft maximum spacing; Ordinary Hazard Group I (parking, mechanical rooms, elevator machine rooms) with 0.15 GPM/sqft density and 130 sqft maximum spacing; and Ordinary Hazard Group II (retail spaces, trash rooms, storage) with 0.20 GPM/sqft density and 130 sqft maximum spacing. The fire sprinkler system will be supplied from the City of Pembroke Pines municipal water system, with a 6-inch underground main connecting to a new free-standing 2" x 2" x 6" fire department connection (FDC) positioned at 36 inches height with required clearances.

The contractor is responsible for all costs associated with shop drawing preparation, hydraulic calculations signed by a Florida registered professional engineer, permit acquisition, labor, materials, cleanup, and fire watch coordination if required by the AHJ. Shop drawings and hydraulic calculations must be submitted in three sets to the architect/owner for approval prior to commencing field work and must also be submitted to the local building department for permitting. All piping and appurtenances must undergo hydrostatic testing at 200 PSI or 50 PSI in excess of system working pressure (whichever is greater) and maintain that pressure at 5 PSI for two hours, witnessed by the local AHJ. Underground pipe depth of cover must not be less than 30 inches to prevent mechanical damage. All exposed piping and fittings to outside air, salt, chemicals, moisture, or corrosive vapors must be Schedule 40 black steel pipe with carbon steel grooved fittings, corrosion-resistant steel rod and hangers, and must be painted red per NFPA 13:2016-8.16.4.2. The contractor must coordinate all work with other construction disciplines including HVAC, plumbing, electrical, structural, civil, and architectural trades, and must remove any existing fire sprinkler piping not required for permanent installation. System interruptions must occur during off-peak or unoccupied times with minimum seven-day advance notification to the owner and AHJ, with qualified fire watch personnel provided on-site if demolition is deemed hazardous by the AHJ.

View the file

Other files

Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FS0.1

FI

RE

S

PR

IN

KL

ER

P

ER

FO

RM

AN

CE

S

PE

C-

N O

TE

S, L

EG

EN

D

IN

D

EX

3501 Griffin Road

(954) 266-2700 Fx: (954) 266-2701 Ft. Lauderdale, FL 33312 sma@saltzmichelson.com

AR-0009976

SD

REVISIONS

Date:

Checked By:

Drawn By:

Project No.:

EQ

2022-133

Sheff L. Devier III AR0007699

S

T

A

T

E

O

F F

L

O

R

I

D

A

S

H

E

L

DE

V

I

R

I

I

R

E

G

I

S

T

E

R

E

D A

R

C

H

I

T

E

C

T

AR0007699

11/17/2023 signed

KAMM CONSULTING PROJECT #: 2022-0686

PROJECT MANAGER: GREG KEMP

Certification of Authorization #8189

Deerfield Beach, Florida 33442 Phone 954.949.2200 Fax 954.949.2201 engineering@kammconsulting.com date

1407 West Newport Center Drive

AutoCAD SHX Text

%%UFIRE SPRINKLER SHEET INDEX

AutoCAD SHX Text

SHEET#

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

FIRE SPRINKLER PERFORMANCE SPEC NOTES, LEGEND & INDEX

AutoCAD SHX Text

FSP-0.1

AutoCAD SHX Text

FIRE SPRINKLER PERFORMANCE SPEC GROUND FLOOR PLAN

AutoCAD SHX Text

FSP-2.1

AutoCAD SHX Text Drawing not to scale

AutoCAD SHX Text

CAJ1028

AutoCAD SHX Text Beachwood, OH, 44122

AutoCAD SHX Text 3735 Green Rd.

AutoCAD SHX Text R

AutoCAD SHX Text 2 and 3 Hour Fire Rated

AutoCAD SHX Text Through Penetration Firestop for

AutoCAD SHX Text Single Metal Pipe through

AutoCAD SHX Text Concrete floors or walls using

AutoCAD SHX Text

FYRE-SHIELD

AutoCAD SHX Text F-rating = 2 and 3 Hr

AutoCAD SHX Text T-rating = 0 Hr

AutoCAD SHX Text 1 Floor or Wall assembly = 2.5" thick concrete

AutoCAD SHX Text 2 Steel Sleeve - optional - Sch 40(or heavier) steel pipe

AutoCAD SHX Text with length as same as floor/wall thickness

AutoCAD SHX Text

AutoCAD SHX Text 4 Completely fill annular space and thickness of floor or wall

AutoCAD SHX Text with FYRE-SHIELD. Fill material shall be domed on both

AutoCAD SHX Text sides of assembly to a 1/2" height in addition to thickness

AutoCAD SHX Text required for opening

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Steel Pipe : Max. 6" steel.

AutoCAD SHX Text EMT: 4" electrical metallic tubing.

AutoCAD SHX Text Annular space is "

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text (206)

AutoCAD SHX Text R

AutoCAD SHX Text s

AutoCAD SHX Text s

AutoCAD SHX Text a

AutoCAD SHX Text l

AutoCAD SHX Text C

AutoCAD SHX Text d

AutoCAD SHX Text e

AutoCAD SHX Text i

AutoCAD SHX Text f

AutoCAD SHX Text i

AutoCAD SHX Text t

AutoCAD SHX Text e

AutoCAD SHX Text m

AutoCAD SHX Text S

AutoCAD SHX Text y

AutoCAD SHX Text s

AutoCAD SHX Text

%%UFIRE STOP DETAIL FOR FIRE WALL

AutoCAD SHX Text

%%UPENETRATIONS

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text 2½" x 2½ x X" FDC

AutoCAD SHX Text 36"

AutoCAD SHX Text NOTE: FDC TO BE INSTALLED AT 36". A CLEARANCE OF 7'-6" IS REQUIRED AT EACH SIDE AND 4' TO THE REAR. NO LANSCAPING PERMITTED. REFER TO CIVIL/LANDSCAPING DRAWINGS.

AutoCAD SHX Text

C-900, DR 14

AutoCAD SHX Text 6"

AutoCAD SHX Text

TO SYSTEM

AutoCAD SHX Text

DIP RISER

AutoCAD SHX Text

%%UFREE STANDING FDC

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

FIRE SPRINKLER PERFORMANCE SPEC SITE PLAN

AutoCAD SHX Text

FSP-1.1

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text

%%UHANGER SCHEDULE

AutoCAD SHX Text

NFPA 13 TABLE 4-6.2.2.1 MAXIMUM DISTANCE BETWEEN HANGERD (FT - IN)

AutoCAD SHX Text

STEEL PIPE EXCEPT

AutoCAD SHX Text

WALL STEEL PIPE

AutoCAD SHX Text

THREADED LIGHT-

AutoCAD SHX Text

THREADED LIGHT-

AutoCAD SHX Text

WALL

AutoCAD SHX Text 12-0

AutoCAD SHX Text 12-0

AutoCAD SHX Text N/A

AutoCAD SHX Text N/A

AutoCAD SHX Text 12-0

AutoCAD SHX Text 12-0

AutoCAD SHX Text

NOMINAL PIPE SIZE

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 1"

AutoCAD SHX Text 12-0

AutoCAD SHX Text 15-0

AutoCAD SHX Text 12-0

AutoCAD SHX Text 15-0

AutoCAD SHX Text 15-0

AutoCAD SHX Text 12-0

AutoCAD SHX Text N/A

AutoCAD SHX Text 15-0

AutoCAD SHX Text 12-0

AutoCAD SHX Text 15-0

AutoCAD SHX Text N/A

AutoCAD SHX Text 15-0

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 2"

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text 3-1/2"

AutoCAD SHX Text 3"

AutoCAD SHX Text 4"

AutoCAD SHX Text N/A

AutoCAD SHX Text 15-0

AutoCAD SHX Text N/A

AutoCAD SHX Text 15-0

AutoCAD SHX Text N/A

AutoCAD SHX Text 15-0

AutoCAD SHX Text 6"

AutoCAD SHX Text 5"

AutoCAD SHX Text 8"

AutoCAD SHX Text %%uNOTES

AutoCAD SHX Text

1. THERE SHALL BE NOT LESS THAN ONE HANGER FOR EACH SECTION OF PIPE

AutoCAD SHX Text

2. SUPPORT SPACING DISTANCE FOR END LINE SPRINKLER DROP ELBOWS AND DROP TEES TO BE IN ACCORDANCE WITH

AutoCAD SHX Text

NFPA 13 AND THE PRODUCT APPROVAL LISTING.

AutoCAD SHX Text

TYPE/DESCRIPTION

AutoCAD SHX Text

CONCEALED PENDENT

AutoCAD SHX Text

QNT

AutoCAD SHX Text

AutoCAD SHX Text

SYM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UPRIGHT

AutoCAD SHX Text

PENDENT

AutoCAD SHX Text

RATING

AutoCAD SHX Text TEMP(%%dF)

AutoCAD SHX Text 155/175

AutoCAD SHX Text 5.6

AutoCAD SHX Text 155/200

AutoCAD SHX Text

AutoCAD SHX Text 5.6

AutoCAD SHX Text 5.6

AutoCAD SHX Text

FACTOR

AutoCAD SHX Text K

AutoCAD SHX Text

ESCUTCHEON

AutoCAD SHX Text 1/2"

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

NPT

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

QUICK

AutoCAD SHX Text

RESPONSE

AutoCAD SHX Text

QUICK

AutoCAD SHX Text

QUICK

AutoCAD SHX Text

TYCO

AutoCAD SHX Text

TYCO

AutoCAD SHX Text

TYCO

AutoCAD SHX Text

MFG.

AutoCAD SHX Text

TY3131

AutoCAD SHX Text

TY3231

AutoCAD SHX Text

TY3531

AutoCAD SHX Text

SIN

AutoCAD SHX Text

TY-FRB

AutoCAD SHX Text

TY-FRB

AutoCAD SHX Text

RFII

AutoCAD SHX Text

MODEL

AutoCAD SHX Text

BRASS

AutoCAD SHX Text

WHITE

AutoCAD SHX Text

BRASS

AutoCAD SHX Text

FINISH

AutoCAD SHX Text

OPEN CEILING AREAS/175 ROOF

AutoCAD SHX Text

DROP CEILING AREAS/200 KILN

AutoCAD SHX Text

NOTES/INTENDED USE

AutoCAD SHX Text

BELOW OBSTRUCTIONS

AutoCAD SHX Text Thread

AutoCAD SHX Text

CONN.

AutoCAD SHX Text Thread

AutoCAD SHX Text Thread

AutoCAD SHX Text

%%UFIRE SPRINKLER SCHEDULE-(REFER TO NOTES BELOW)

AutoCAD SHX Text NOTES: 1. ALL FIRE SPRINKLERS SHALL HAVE A U.L. APPROVED CORROSION RESISTANT COATING WHERE EXPOSED TO OUTSIDE AIR, CHEMICALS, MOISTURE, OR OTHER CORROSIVE VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES. 2. THE CONTRACTOR SHALL RECEIVE THE ARCHITECTS APPROVAL FOR ALL FIRE SPRINKLER/ESCUTCHEON FINISHES PRIOR TO ORDERING AND INSTALLING DESPITE WHAT IS SPECIFIED IN THIS SCHEDULE. 3. IF MODIFYING AN EXISTING PROJECT, THE CONTRACTOR SHALL BE RESPONSIBLE TO MATCH THE EXISTING FIRE SPRINKLERS IF STILL FABRICATED TODAY WITH THE NEW TO BE INSTALLED OR IF DISCONTINUED WITH THE NEW EQUIVALENTS FOR TODAY'S INSTALLATION REQUIREMENTS DESPITE WHAT IS SPECIFIED IN THIS SCHEDULE.

AutoCAD SHX Text

FROM CITY

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

%%UDOUBLE DETECTOR CHECK VALVE

AutoCAD SHX Text

FL OS&Y VALVES WITH TAMPER SWITCHES

AutoCAD SHX Text

AMES "3000SS" DOUBLE DETECTOR CHECK ASSEMBLY

AutoCAD SHX Text

TO SYSTEM

AutoCAD SHX Text ORDINARY HAZARD GROUP I DENSITY: =0.15 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 200° F.HOSE ALLOWANCE 250 GPM

AutoCAD SHX Text %%uHAZARD CLASSIFICATIONS

AutoCAD SHX Text ORDINARY HAZARD GROUP II DENSITY: =0.20 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155° F.HOSE ALLOWANCE 250 GPM

AutoCAD SHX Text LIGHT HAZARD DENSITY: =0.10 GPM/ft2. MAX. AREA PER HEAD: 225 ft2. TEMPERATURE 155° F.HOSE ALLOWANCE 100 GPM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

1. TOP BEAM C-CLAMP

AutoCAD SHX Text

%%UCOMPONENTS

AutoCAD SHX Text

2. SET SCREW

AutoCAD SHX Text

3. LOCK NUT (HEX NUT)

AutoCAD SHX Text

4. HANGER ROD

AutoCAD SHX Text

5. ADJUSTABLE HANGER RING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

%%UHANGER DETAIL # 2

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

%%UFIRE SPRINKLER PERFORMANCE

AutoCAD SHX Text

%%USPEC-NOTES, LEGEND & INDEX

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

1. THE FOLLOWING NOTES SHALL SERVE AS MEETING THE REQUIREMENTS SET FORTH UNDER THE FLORIDA ADMISTRATIVE CODE SECTION 61G15-32.004 FOR FIRE PROTECTION ENGINEERING DOCUMENTS. 2. THE CONTRACTOR SHALL PROVIDE A COMPLETE SET OF SHOP DRAWINGS FOR FIRE SPRINKLER INSTALLATION FOR THE PROJECT AS INDICATED IN THE DESIGN DOCUMENTS. THE SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE, THE FLORIDA FIRE PREVENTION CODE-7thEDITION, NFPA 13 (2016 EDITION), NFPA 14, NFPA 20, NFPA 24 (2016 EDITIONS), THE OWNER'S INSURANCE COMPANY AND GUIDE LINES IF ANY, THE STATE AND/OR LOCAL FIRE MARSHAL, THE LOCAL BUILDING DEPARTMENT, AND OWNER GUIDE LINE AND STANDARDS IF EXISTING. 3. THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED AS OUTLINED BELOW: LIGHT HAZARD: (DESIGNATED AS LH) (DESIGNATED AS LH) DESIGN DENSITY: 0.10 GPM/SQFT OVER THE MOST DEMANDING 1500 SQFT. FIRE SPRINKLER SPACING: 225 SQFT. MAXIMUM. AREAS/ROOMS: LOBBIES, OFFICES, RESTAURANT SEATING AREAS HOSE REQUIREMENTS: 100 GPM (TOTAL COMBINED INSIDE/OUTSIDE). ORDINARY HAZARD GROUP 1: (DESIGNATED AS OH1) (DESIGNATED AS OH1) DESIGN DENSITY: 0.15 GPM/SQFT OVER THE MOST DEMANDING 1500 SQFT. FIRE SPRINKLER SPACING: 130 SQFT. MAXIMUM. AREAS/ROOMS: PARKING, RESTAURANT SERVICE AREAS, MECHANICAL ROOMS, ELEVATOR MACHINE ROOMS, ELECTRIC ROOMS, TELEPHONE ROOMS. HOSE REQUIREMENTS: 250 GPM (TOTAL COMBINED INSIDE/OUTSIDE). ORDINARY HAZARD GROUP 2: (DESIGNATED AS OH2) (DESIGNATED AS OH2) DESIGN DENSITY: 0.20 GPM/SQFT OVER THE MOST DEMANDING 1500 SQFT. FIRE SPRINKLER SPACING: 130 SQFT. MAXIMUM. AREAS/ROOMS: RETAIL SPACES, TRASH ROOM, STORAGE SPACES. HOSE REQUIREMENTS: 250 GPM (TOTAL COMBINED INSIDE/OUTSIDE). NOTE: NO STORAGE OVER 12 FT SHALL BE ALLOWED. NO STORAGE OVER 12 FT SHALL BE ALLOWED. 4. THE CONTRACTOR SHALL USE A FLOW TEST PERFORMED BY THE LOCAL AUTHORITY TO ASCERTAIN THE WATER SERVICE REQUIRED FOR THE FIRE SPRINKLER INSTALLATION; THE HYDRAULIC CALCULATIONS SHALL ALLOW FOR A 10% PRESSURE REDUCTION AS A FACTOR OF SAFETY AND COMPLY WITH THE AHJ REQUIREMENTS AND/OR USE PRESSURE AND FLOW CRITERIA PROVIDED BY THE AUTHORITY HAVING JURISDICTION. 5. THE CONTRACTOR SHALL SUBMIT THREE (3) SETS OF SHOP DRAWINGS AND, IF APPLICABLE, HYDRAULIC CALCULATIONS BEARING THE SIGNATURE AND SEAL OF A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR REVIEW BY THE ARCHITECT/OWNER PRIOR TO COMMENCING ANY FIELD WORK. AS WELL, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND, IF APPLICABLE, HYDRAULIC CALCULATIONS TO THE LOCAL BUILDING DEPARTMENT OR AUTHORITY HAVING JURISDICTION AND OBTAIN ALL NECESSARY APPROVALS AND PERMITS FOR THE PROJECT. 6. THE CONTRACTOR SHALL COORDINATE ALL FIRE SPRINKLER WORK WITH ALL OTHER CONSTRUCTION DISCIPLINES INCLUDING BUT NOT LIMITED TO HVAC, PLUMBING, ELECTRICAL, STRUCTURAL AND CIVIL. THE CONTRACTOR SHALL ALSO COORDINATE ANY SPECIAL TESTING REQUIRED BY THE OWNER. 7. THE SHOP DRAWINGS, INCLUDING HYDRAULIC CALCULATIONS, SHALL SHOW THE SIZES, TYPES, AND DIMENSIONAL LOCATIONS FOR ALL FIRE SPRINKLERS, MAINS, BRANCHES, AND EXISTING PIPING FOR THE WATER SUPPLY TO THE CONNECTION OF THE SYSTEM. 8. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION AND FINAL LOCATION OF THE FIRE SPRINKLER HEADS AND/OR PIPING FOR FINAL FIRE PROTECTION LAYOUT DOCUMENTS PREPARATION AND INSTALLATION. 9. THE DESIGN DOCUMENTS ARE NOT AND SHALL NOT BE CONSIDERED SHOP DRAWINGS NOR INSTALLATION DRAWINGS. 10. ALL INFORMATION CONTAINED IN THESE DRAWINGS IS ACCORDING TO THE ORIGINAL CONSTRUCTION DOCUMENTS PROVIDED BY THE OWNER AND LIMITED FIELD OBSERVATIONS. THE ENGINEER OR THE ARCHITECT MAKES NO REPRESENTATION FOR THE ACCURACY OF SUCH INFORMATION. THE CONTRACTOR SHALL VISIT THE BUILDING AND FIELD VERIFY ALL EXISTING CONDITIONS MATERIALS, EQUIPMENT, DIMENSIONS, ETC. ONCE DEMOLITION TAKES PLACE PRIOR TO SUBMITTING A BID AND COMMERCING ANY WORK. 11. THE CONTRACTOR SHALL REMOVE EXISTING FIRE SPRINKLERS AND/OR FIRE SPRINKLER PIPING NOT REQUIRED FOR THE PERMANENT INSTALLATION AT THE END OF THE INSTALLATION PHASE. 12. ALL WORK BY THE CONTRACTOR SHALL BE DONE IN STRICT COORDINATION AND AS APPROVED BY THE OWNER. ALL INTERRUPTIONS IN THE FUNCTIONING OF THE FIRE SPRINKLER SYSTEM SHALL BE DONE DURING OFF-PEAK( UNOCCUPIED TIMES) OR STRICTLY AS APPROVED BY THE OWNER. NOTIFICATION OF A SHUTDOWN TO THE FIRE SPRINKLER SYSTEM, INCLUDING THE DURATION TIME, SHALL BE MADE TO THE OWNER A MINIMUM OF SEVEN (7) DAYS IN ADVANCE OF SUCH WORK AND COORDINATED ALSO WITH AHJ; WHERE IN THE OPINION OF THE AHJ IF PARTIAL OR TOTAL DEMOLITION OF THE EXISTING FIRE SPRINKLER SYSTEM TAKES PLACE IN SITE AND SUCH DEMOLITION IS OF A HAZARDOUS NATURE, QUALIFIED PERSONNEL SHALL SERVE AS ON-SITE FIRE WATCH. 13. THE CONTRACTOR SHALL BEAR ALL COSTS OF A. PREPARING SHOP DRAWINGS AND DOCUMENTS B. SECURING PERMITS AND APPROVALS C. LABOR D. MATERIALS E. CLEAN UP/WASTE REMOVAL F. FIRE WATCH IN COORDINATION OF AHJ IF REQUIRED. 14. PIPING INSTALLATION WHEN THE INSTALLATION OF A NEW FIRE SPRINKLER SYSTEM TAKES PLACE, THE CONTRACTOR SHALL PROPOSE THE PIPE SCHEDULE MATERIALS, FITTINGS, VALVES, HANGERS, ETC. ACCORDING TO THE GUIDE LINES AND STANDARDS OF THE OWNER IF ANY, WHICH SHALL BE ALSO RESPONSABILITY OF THE CONTRACTOR VERIFY PREVIOUSLY TO BIDDING, SUBMITTING, PERMITTING, COMMENCING AND INSTALLING ANY NEW WORK; SUCH STANDARDS SHALL BE ALSO AS PER NFPA 13 AND AHJ. THE FOLLOWING MATERIALS ARE SPECIFICATIONS AS PER NFPA 13: A. MAKE CHANGES IN SIZE OF PIPE WITH REDUCING FITTINGS; BUSHINGS ARE NOT PERMITTED. B. CAP OPENINGS IN PIPING DURING CONSTRUCTION. C. ESCUTCHEONS: FIT EXPOSED PIPES PASSING THROUGH FLOORS, WALL OR CEILING WITH ESCUTCHEONS. MANUFACTURE SPECIAL SIZES OF ESCUTCHEONS FROM STEEL AND PRIME COAT SAME. CUT IN ROUND, RECTANGULAR OR SQUARE SPACE TO PROVIDE A CLEAN APPEARANCE ACCEPTABLE TO THE GAP. D. PENETRATIONS THROUGH FIRE RATED WALLS SHOULD BE FILLED WITH A UL LISTED FIRE SEALANT IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS AND TO PROVIDE AT LEAST THE MINIMUM FIRE RATING OF THE WALL. E. CPVC PIPING SHALL NOT BE INSTALLED OVER ANY PORTION OF THE OPENING(S) IN RETURN AIR PLENUMS. F. ABOVEGROUND PIPE MATERIALS: 1. SCHEDULE 40, FOR PIPE SIZES 1" THROUGH 2". 2. SCHEDULE 10 FOR PIPE SIZES 2 " AND LARGER. 12" AND LARGER. 3. ALL EXPOSED PIPE AND FITTINGS TO OUTSIDE AIR, SALT, CHEMICALS, MOISTURE, 3. ALL EXPOSED PIPE AND FITTINGS TO OUTSIDE AIR, SALT, CHEMICALS, MOISTURE, AND/OR OTHER CORROSIVE VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH MATERIALS SHALL BE BLACK STEEL PIPE SCH. 40, CARBON STEEL GROOVED FITTINGS, HANG UP WITH CORROSIVE RESISTANT STEEL ROD AND HANGERS AND SHALL BE ALL RED PAINTED PER NFPA 13:2016-8.16.4.2. PER NFPA 13:2016-8.16.4.2. NFPA 13:2016-8.16.4.2. G. UNDERGROUND PIPE MATERIALS: 1. DUCTILE IRON MEETING AWWA C104 STANDARDS 2. PLASTIC MEETING AWWA C900 STANDARDS, DR 14.

AutoCAD SHX Text

%%USPRINKLER NOTES: CODE SECTION 61G15-32.004

AutoCAD SHX Text

FLOW

AutoCAD SHX Text

NEW 6" U/G PIPE FROM SOURCE

AutoCAD SHX Text

NEW ALARM CHECK VALVE

AutoCAD SHX Text

NEW FLOW SWITCH

AutoCAD SHX Text

NEW PRESSURE GAUGE

AutoCAD SHX Text

NEW ALARM BELL

AutoCAD SHX Text Firelock

AutoCAD SHX Text Firelock

AutoCAD SHX Text Firelock

AutoCAD SHX Text Firelock

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

%%USCHEMATIC OF NEW FIRE SPRINKLER

AutoCAD SHX Text

%%URISER

AutoCAD SHX Text %%U1st FL.

AutoCAD SHX Text

SYSTEM

AutoCAD SHX Text

TO

AutoCAD SHX Text Firelock

AutoCAD SHX Text Firelock

AutoCAD SHX Text

NEW BUTTERFLY VALVE W/ TAMPER SWITCH

AutoCAD SHX Text NOTE: ALL EXPOSED PIPE AND FITTINGS TO OUTSIDE AIR, SALT, CHEMICALS, MOISTURE, AND/OR OTHER CORROSIVE VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH MATERIALS SHALL BE BLACK STEEL PIPE SCH. 40, CARBON STEEL GROOVED FITTINGS, HANG UP WITH STAINLESS CORROSION RESISTANT STEEL ROD AND HANGERS AND SHALL BE ALL RED PAINTED PER NFPA 13:2016:8.16.4.2..

AutoCAD SHX Text

POLK BUILDING RENOVATION

AutoCAD SHX Text

CITY OF PEMBROKE PINES

AutoCAD SHX Text

8200 SOUTH PALM DRIVE

AutoCAD SHX Text

PEMBROKE PINES, FLORIDA, 33025

6,060 SQ. FT.

3501 Griffin Road

(954) 266-2700 Fx: (954) 266-2701 Ft. Lauderdale, FL 33312 sma@saltzmichelson.com

AR-0009976

SD

REVISIONS

Date:

Checked By:

Drawn By:

Project No.:

EQ

2022-133

Sheff L. Devier III AR0007699

S

T

A

F

L

O

R

I

D

A

S

H

E

DE

V

I

I

R

E

G

I

S

T

E

R

E

D A

R

C

H

I

T

E

C

T

AR0007699

11/17/2023 signed

KAMM CONSULTING PROJECT #: 2022-0686

PROJECT MANAGER: GREG KEMP

Certification of Authorization #8189

Deerfield Beach, Florida 33442 Phone 954.949.2200 Fax 954.949.2201 engineering@kammconsulting.com date

1407 West Newport Center Drive

FS1.1

FI

RE

S

PR

IN

KL

ER

P

ER

FO

RM

AN

CE

S

PE

C

G

RO

U N

D F

LO

O

R

PL

AN

PL

AN

AutoCAD SHX Text H

AutoCAD SHX Text Y

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text 6.8

AutoCAD SHX Text S

AutoCAD SHX Text

%%UFIRE SPRINKLER PERFORMANCE

AutoCAD SHX Text %%uSPEC SITE PLAN

AutoCAD SHX Text 1"=30'-0"

AutoCAD SHX Text

NORTH

AutoCAD SHX Text NOTE: THIS IS NOT AN ACTUAL SITE/CIVIL DRAWING. IT IS INCLUDED FOR REFERENCE ONLY. FOR SITE/CIVIL DETAILS, REFER TO CIVIL ENGINEER DRAWINGS

AutoCAD SHX Text

- ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT PRESSURE ±5 PSI FOR 2 HOURSPER NFPA 13-2016-10.10.2.2.1 AND TEST SHALL BE WITNESSED BY LOCAL AHJ. - UNDERGROUND PIPE DEPTH OF COVER SHALL NOT BE LESS THAN 30 INCHES TO PREVENT MECHANICAL DAMAGE PER NFPA-13-2016-10.4.2.2.2

AutoCAD SHX Text

FIRE HYDRANT (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text NEW FREE-STAND 2½" x 2½" x 6" FDC (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text

NEW 6" DDCV (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text

NEW 6" FIRE SPRINKLER RISER. (REFER TO FS0.1 FOR DETAIL)

AutoCAD SHX Text

NEW 6" FIRE POINT OF SERVICE (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text

EXISTING CITY WATER MAIN (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text

EXISTING CITY WATER MAIN (REFER TO CIVIL DRAWINGS)

AutoCAD SHX Text

TO FIRE SPRINKLER SYSTEM (REFER TO FS2.1 FOR CONTINUATION)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

%%UFIRE SPRINKLER SYSTEM WATER SUPPLY

AutoCAD SHX Text THE FIRE SPRINKLER SYSTEM WILL BE FED FROM THE CLEAN AND SAFE DRINKING WATER SYSTEM OF THE CITY OF PEMBROKE PINES. REFER TO THE 2021 CITY OF PEMBROKE PINES QUALITY REPORT PROVIDED PER FLORIDA STATUTES 61G-15 REQUIREMENTS. PROVIDED PER FLORIDA STATUTES 61G-15 REQUIREMENTS.

AutoCAD SHX Text

POLK BUILDING RENOVATION

AutoCAD SHX Text

CITY OF PEMBROKE PINES

AutoCAD SHX Text

8200 SOUTH PALM DRIVE

PEMBROKE PINES, FLORIDA, 33025

MECHANICAL, ELECTRICAL, JANITOR

ROOMS AREAS:

MECHANICAL, ELECTRICAL, JANITOR

ROOMS AREAS:

STORAGE ROOMS AREAS:

STORAGE, FIRE SPRINKLER

RISER ROOMS AREAS:

MECHANICAL, ELECTRICAL, JANITOR

ROOMS AREAS:

MECHANICAL, ELECTRICAL, JANITOR

ROOMS AREAS:

OFFICES, IT, HALLWAYS, REST ROOMS,

BREAK, RECORDS, NAP, MAIL, LOBBY,

CUSTOMER SERVICE, CONFERENCE,

WORK STATIONS, EOC, CASHIER,

CASHIERING ROOMS AREAS:

OFFICES, IT, HALLWAYS, REST ROOMS,

BREAK, RECORDS, NAP, MAIL, LOBBY,

CUSTOMER SERVICE, CONFERENCE,

WORK STATIONS, EOC, CASHIER,

CASHIERING ROOMS AREAS:

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MEN'S

RESTROOM

HALLWAY

HALLWAY

HALLWAY

HALLWAY

HALLWAY

TOILET

BREAK ROOM

TOILET

153 JANITOR

STORAGE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WORKSTATION

OFFICE

IT / MDF

ROOM

CONFERENCE

ROOM

MECHANICAL

ROOM

OFFICE

BILLING

OFFICE

OFFICE

MAIL

ROOM

ELECTRICAL

ROOM

MECHANICAL

ROOM

MECHANICAL

ROOM

HALLWAY 7

WOMEN'S

RESTROOM

TOILET

126C

STORAGE

126B

UTILITES

DIRECTOR

126A

ADMINISTRATIVE

ASSISTANT

OFFICE

ASSISTANT

DIRECTOR

OFFICE

OFFICE

ASSISTANT

DIRECTOR

OFFICE

COPY

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

CONFERENCE

ROOM

JANITOR

MEN'S

RESTROOM

WOMEN'S

RESTROOM

BREAK ROOM

RECORDS

OFFICE

OFFICE

STORAGE

TOILET

TOILET

MECHANICAL

ROOM

FIRE RISER

ROOM

CASHIERING

106A

CASHIER

106B

CUSTOMER

SERVICE

LOBBY

3501 Griffin Road

(954) 266-2700 Fx: (954) 266-2701 Ft. Lauderdale, FL 33312 sma@saltzmichelson.com

AR-0009976

SD

REVISIONS

Date:

Checked By:

Drawn By:

Project No.:

EQ

2022-133

Sheff L. Devier III AR0007699

S

T

A

F

L

O

R

I

D

A

S

H

E

DE

V

I

I

R

E

G

I

S

T

E

R

E

D A

R

C

H

I

T

E

C

T

AR0007699

11/17/2023 signed

KAMM CONSULTING PROJECT #: 2022-0686

PROJECT MANAGER: GREG KEMP

Certification of Authorization #8189

Deerfield Beach, Florida 33442 Phone 954.949.2200 Fax 954.949.2201 engineering@kammconsulting.com date

1407 West Newport Center Drive

Rev # Description Date

FS2.1

FI

RE

S

PR

IN

KL

ER

P

ER

FO

RM

AN

CE

S

PE

C-

G

RO

U N

D F

LO

O

R

PL

AN

1 Code Update 10-4-2024

AutoCAD SHX Text

%%UFIRE SPRINKLER PERFORMANCE SPEC

AutoCAD SHX Text

%%UGROUND FLOOR PLAN

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

6" UNDERGROUND FROM FIRE POINT OF SERVICE

AutoCAD SHX Text

6" STUB UP

AutoCAD SHX Text

6" FIRE SPRINKLER RISER (REFER TO FS0.1 DETAIL)

AutoCAD SHX Text

TO FIRE SPRINKLER SYSTEM

AutoCAD SHX Text ORDINARY HAZARD GROUP I DENSITY: =0.15 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text ORDINARY HAZARD GROUP I DENSITY: =0.15 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text ORDINARY HAZARD GROUP II DENSITY: =0.20 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text ORDINARY HAZARD GROUP II DENSITY: =0.20 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text ORDINARY HAZARD GROUP I DENSITY: =0.15 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text ORDINARY HAZARD GROUP I DENSITY: =0.15 GPM/ft2. MAX. AREA PER HEAD: 130 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 250 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text LIGHT HAZARD DENSITY: =0.10 GPM/ft2. MAX. AREA PER HEAD: 225 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 100 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text LIGHT HAZARD DENSITY: =0.10 GPM/ft2. MAX. AREA PER HEAD: 225 ft2. TEMPERATURE 155°F.HOSE ALLOWANCE 100 GPM CALCULATE THE MOST REMOTE 1500 ft2. REMOTE AREA IS ALLOWED TO BE REDUCED BY USING QUICK RESPONSE HEADS PER NFPA 13,2019:19.3.3.2.3.1

AutoCAD SHX Text IMPORTANT ADDITIONAL NOTES: 1- THIS IS A FIRE SPRINKLER PERFORMANCE SPEC. A LICENSED AND CERTIFIED FIRE SPRINKLER CONTRACTOR SHALL FURNISH AND INSTALL NEW FIRE SPRINKLER COMPONENTS AS REQUIRED FOR A COMPLETE FUNCTIONAL FIRE PROTECTION SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES AND LOCAL AHJ REQUIREMENTS. 2- FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SIGNED AND SEALED BY THEIR OWN FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR FIRE SPRINKLER PERMIT. 3- ALL FIRE SPRINKLERS SHALL HAVE A U.L. APPROVED CORROSION RESISTANT COATING WHERE EXPOSED TO OUTSIDE AIR, SALT, CHEMICALS, MOISTURE, AND/OR OTHER CORROSIVE VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES. 4- THE CONTRACTOR SHALL RECEIVE THE ARCHITECT'S APPROVAL FOR ALL FIRE SPRINKLERS/ESCUTCHEON FINISHES PRIOR TO ORDERING AND INSTALLING DESPITE WHAT IS SPECIFIED IN THESE DOCUMENTS. 5- ALL EXPOSED PIPE AND FITTINGS TO OUTSIDE AIR, SALT, CHEMICALS, MOISTURE, AND/OR OTHER CORROSIVE VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH MATERIALS SHALL BE BLACK STEEL PIPE SCH. 40, CARBON STEEL GROOVED FITTINGS, HANG UP WITH CORROSION RESISTANT STEEL ROD AND HANGERS AND SHALL BE ALL RED PAINTED PER NFPA PER NFPA NFPA 13:2019-8.16.4.2. . 6- FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A FLOW TEST PERFORMED BY THE LOCAL AUTHORITY TO ASCERTAIN THE WATER SERVICE REQUIRED FOR THE FIRE SPRINKLER INSTALLATION; THE HYDRAULIC CALCULATIONS SHALL ALLOW FOR A 10% PRESSURE REDUCTION AS A FACTOR OF SAFETY AND COMPLY WITH THE AHJ REQUIREMENTS AND/OR USE PRESSURE AND FLOW CRITERIA AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 7- THE CONTRACTOR FOR HIS INSTALLATION PERMIT SHALL PROVIDE CUT SHEETS OF ALL FIRE SPRINKLER COMPONENTS WITH SHOP DRAWINGS AND HYDRAULIC CALCULATIONS PER NFPA 13-2019-8.15.20.5.2 ACCORDING TO THE RESPECTIVE HAZARD REQUIREMENTS BY OWNER STANDARDS IF ANY AND BY CODE, SHALL SHOW PIPE SIZES, ALL FITTINGS, AND DIMENSIONAL LOCATIONS FOR ALL FIRE SPRINKLERS, MAINS, BRANCHES, AND PIPING FOR THE WATER SUPPLY TO THE CONNECTION OF THE SYSTEM. 8- ANY PIPE SIZES INDICATED ON THE FIRE SPRINKLER EOR DOCUMENTS ARE PROVIDED FOR REFERENCE ONLY INCLUDING THE SIZE OF THE FIRE POINT OF SERVICE. THE ENGINEER OF RECORD MAKES NO REPRESENTATION AND CANNOT TAKE ANY RESPONSIBILITY FOR THE ACCURACY OF SUCH REPRESENTATION DUE TO THE LACK OF INFORMATION DUE TO THE LACK OF INFORMATION IN THE BEGINNING OF THE PROJECT. THE FIRE SPRINKLER CONTRACTOR CANNOT BASE HIS PRICE IN ANY EOR DRAWING PIPE SIZES DUE TO THE GIVEN REASONS. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE TO PERFORM AND PROVIDE A HYDRAULICALLY CALCULATED FIRE SPRINKLER SYSTEM, CONFORMING TO ALL APPLICABLE NFPA CODES, HAZARDS, INCREASING OF REMOTE AREAS AND/OR DENSITIES IF REQUIRED, USING AND PROVIDING THE PROPER PIPE SIZES FOR THE MOST REMOTE AREAS AND SYSTEMS DEMAND, STARTING AT THE DESIGNATED POINT OF SERVICE AND SUCH CONDITION SHALL BE REFLECTED AND UNDERSTOOD BY THE FIRE SPRINKLER CONTRACTOR ASSUMING ALL HIS RESPONSIBILITIES IF FINAL PIPE SIZES DIFFER FROM EOR DRAWINGS, BEFORE SIGNING ANY POSSIBLE CONTRACT WITH THE OWNERS REPRESENTATIVE. 9- THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD COORDINATION AND FINAL LOCATION OF THE FIRE SPRINKLER HEADS (AS PER NFPA 13 AND AHJ); WITH THE RESPECTIVE HAZARD REQUIREMENTS BY CODE AND PIPING FOR FINAL FIRE PROTECTION LAYOUT DOCUMENTS PREPARATION AND FINAL INSTALLATION. 10- THE CONTRACTOR SHALL COORDINATE ALL FIRE SPRINKLER WORK WITH ALL OTHER CONSTRUCTION DISCIPLINES INCLUDING BUT NOT LIMITED TO HVAC, PLUMBING, ELECTRICAL, STRUCTURAL, CIVIL, ARCHITECTURAL AND FIRE ALARM. THE CONTRACTOR SHALL ALSO COORDINATE ANY SPECIAL TESTING REQUIRED BY THE OWNER. 11- SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE PROPER FIRE SPRINKLERS BELOW ANY OBSTRUCTION INCLUDED BUT NOT LIMITED TO DUCT, STRUCTURE, RAMP, ESCALATOR, STAIR, CEILING, SOFFIT, PIPE, DOOR, LANDING, RAMP ETC. IN ORDER TO PROVIDE PROPER FLOOR FIRE PROTECTION CODE COMPLIANCE SYSTEM DESPITE WHAT IS SPECIFIED IN THIS DRAWING. SUCH CONDITION SHALL BE REFLECTED IN HIS BID PRICE BEFORE SIGNING ANY CONTRACT WITH THE OWNER'S REPRESENTATIVE.

AutoCAD SHX Text A LICENSED AND CERTIFIED FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGNING, PERMITTING, AND INSTALLING THE NEW FIRE SPRINKLER COMPONENTS AS REQUIRED FOR A COMPLETE FUNCTIONAL CODE-COMPLIANT FIRE SPRINKLER SYSTEM IN ACCORDANCE TO ALL APPLICABLE NFPA CODES, OWNER & UNDERWRITER INSURANCE STANDARDS, THE STATE FIRE MARSHALL, THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ) REQUIREMENTS AND THE EOR-ENGINEER OF RECORD 61G-15-32 DOCUMENTS PROVIDED PER FLORIDA STATUTES.

AutoCAD SHX Text SHOP DRAWINGS, HYDRAULIC CALCULATIONS & CUT SHEETS OF FIRE SPRINKLER COMPONENTS WILL BE SUBMITTED BY THE FIRE SPRINKLER CONTRACTOR FOR THE FIRE SPRINKLER PERMIT INSTALLATION

AutoCAD SHX Text

AutoCAD SHX Text

POLK BUILDING RENOVATION

AutoCAD SHX Text

CITY OF PEMBROKE PINES

AutoCAD SHX Text

8200 SOUTH PALM DRIVE

AutoCAD SHX Text

PEMBROKE PINES, FLORIDA, 33025

AutoCAD SHX Text

%%UENTIRE SHEET MODIFIED

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OWNER REVISIONS

6.15.26

Sheets and Views
FS0-1

File details come from the government source that posted it. Updated .