This document package includes specifications and drawings for a federal construction project to relocate a medical ward at a Veterans Affairs hospital for improved patient privacy. The solicitation is issued by the Department of Veterans Health Administration Veterans Integrated Service Network 15. Key project requirements include reconfiguring an existing ward space, upgrading HVAC, electrical, and plumbing systems, and installing new partitions, finishes, and medical equipment. Responses are due by August 15, 2021 and the contract is to be awarded by September 30, 2021. The specifications cover general construction requirements, cast-in-place concrete, unit masonry, cold-formed metal framing, roofing preparation, thermal insulation, roof insulation, and other related construction activities. The drawings provide the design and layout of the new ward configuration.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Harry S Truman

Memorial Veterans Hospital Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Basement Level

- Sign

- Sign Number

- Double Sided Sign

B05

B05

U n iv e rs it y H o s p it a l T u n n e l

Smoking

Shelter

Meals

On

Wheels

Patient

Effects

INTERIOR SIGNAGE

Sign Location Plan

1.1

Primary Destinations:

Patient Effects

Exit to Smoking Shelter

University Hospital Tunnel

Nuclear Medicine

Meals On Wheels

Nuclear

Medicine

Basement

N

0’ 10’ 20’ 40’

A

A

A

B

B

B

B01

B10

B13

B14

B12 B11

B02

B04

B03

B06

B07

B08 B09

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com 1.2

INTERIOR SIGNAGE

Sign Location Plan

Primary Destinations:

Agent Cashier

Admissions / Eligibility

Audiology Clinic / Speech

Pathology

Blue Clinic

Cardiology / Thoracic Clinic

Cardio Lab

Cysto Urology Lab

Dental Clinic

Details Office Emergency Department

Imaging

Information

Main Lobby

OEF / OIF / OND

Outpatient Lab

Patriot Cafe / Store

Patient Representative

Pharmacy

Pharmacist Counseling

Police

Pre-Registration

Red Clinic

Release of Information

Same Day Surgery

Silver Clinic

Travel

White Clinic

Vending / ATM

Emergency

Department

Cardio Lab

Audiology

Clinic / Speech Pathology

Patriot Cafe

Imaging

Admissions/

Eligibility

Main

Lobby

OEF/OIF/OND

Patient

Rep.

Details

Office

Vending/

ATM

Cardiology/

Thoracic Clinic

Pharmacy

Information Release of

Information

Agent

Cashier

Blue Clinic

Silver

Clinic

Outpatient Lab

Same-

Day

Surgery

Cysto

Urology

Lab

White Clinic

Red Clinic

Police

Dental Clinic

First Floor

Patriot Store

First Floor Plan

N

0’ 10’ 20’ 40’

Pre-

Registration

- Sign

- Sign Number

- Double Sided Sign

B05

115107 110

152 153 155

151135

140139138

A

A

A

A A

A

A

A

A

B

B

B

B B

B

B

B

B

A B

108109

149Travel

Pharmacist

Counseling

A B

160159

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com 1.3

INTERIOR SIGNAGE

Sign Location Plan

Primary Destinations:

Auditorium

Brace & Amputee Clinic

Bronze Clinic

Cardiac Rehabilitation

Coumadin / Anticoagulation Clinic

Day Treatment Program

Ear Nose & Throat Clinic

EEG Lab (Electroencephalogram)

Endoscopy Center / Pulmonary

Function Testing (PFT)

Eye Clinic

Green Clinic

Occupational Therapy / Physical

Therapy

Optical Shop

Physical Medicine and

Rehabilitation

PM & R / Brace / Amputee Clinic /

SCI

Prosthetics

Sleep Disorders Center

Specialty Clinic

Urology

Coordinator VIST

Specialty

Clinic

VIST

Coordinator

Endoscopy Clinic/

Pulmonary Func-tion

Testing (PFT)

Sleep Disorders

Center Cardiac

Rehabilitation

Prosthetics

Physical

Medicine /

Rehabilitation

PM&R/Brace/

Amputee Clinic/SCI

Optical

Shop

Eye Clinic

Inpatient

Psychiatric

Unit

Green

Clinic

Auditorium

Intensive

Outpatient

Program

Bronze

Clinic

Second Floor

Second Floor Plan

N

0’ 10’ 20’ 40’

Occupational Therapy/

Physical Therapy

- Sign

- Sign Number

- Double Sided Sign

B05

A B

204 209

216 229

219 221

227 230

235 236A AB B

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com 1.4

INTERIOR SIGNAGE

Sign Location Plan

Primary Destinations:

Chapel

EEO

Hospital Director

Human Resources

Medical Library

Medical Media

Learning Service

Public Affairs

Truman Community Living Center

Vending

Voluntary Service

Hospital

Director

Medical

Media Home Based

Primary Care

Medical

Library

Human

Resources

Craft Room

Learning

Organization

Voluntary

Service

Truman Community Living

Center /

Social Worker

Vending

Conference

Room B344

CBOC Coordinator/

Special Programs

Chapel

Public

Affairs

Women’s

Coordinator

Third Floor

Third Floor Plan

N

0’ 10’ 20’ 40’

- Sign

- Sign Number

- Double Sided Sign

B05

A B

302 307

314305

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com 1.5

INTERIOR SIGNAGE

Primary Destinations, Pathways, & Sign Locations

4th Floor Primary Destinations:

4 Medicine Inpatient Unit

Dialysis

Rooms 405-417

Rooms 420-432

Rooms 455-459

Step Down Unit

Waiting Room

5th Floor Primary Destinations:

Employee Health

Vending Area

AFGE Local 903

AFGE Local 3399

DAV Lounge

Fee Basis

MCCR

Compensation & Pension Clinic

Service Officers Vending

6th Floor Primary Destinations:

6 Intensive Care Unit

6 Intensive Care Unit Waiting Room

6 Surgery / Medical

6 Surgery / Medical Waiting Room

Intensive Care Unit

Vending

Fourth, Fifth, and Sixth Floors

Fourth, Fifth, and Sixth Floor Plans

N

0’ 10’ 20’ 40’

Dialysis

Social

Worker 4 Medicine

Inpatient Unit

Waiting Room

Step Down Unit

Fourth Floor

Compensation

& Pension Clinic

Employee

Health

Fifth Floor

Vending

6 Intensive Care Unit

Waiting

Room

6 Surgical

Inpatient Unit

(Nurse)

Social

Worker Waiting

Room

Sixth Floor

- Sign

- Sign Number

- Double Sided Sign

B05

A B

401 402

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Prosthetics Sleep Disorders Center Specialty Clinic VIST Vision or VIST Coordinator

Chapel Conference Room B344 Craft Room

EEO

Home Based Primary Care Hospital Director Human Resources Learning Organization Medical Library Nursing Education Public Affairs Truman Community Living Center Truman Community Living Center Social Worker Vending Voluntary Service Women’s Coordinator

4 Medicine Inpatient Unit Dialysis Rooms 405-417 Rooms 420-432 Rooms 455-459 Social Worker Step Down Unit Waiting Room

AFGE Local 903 AFGE Local 3399 Compensation / Pension Clinic DAV Lounge Employee Health Fee Basis

MCCR

Service Officers Vending

6 Intensive Care Unit 6 Intensive Care Unit Waiting Room 6 Surgical Inpatient Unit 6 Surgery / Med 6 Surgery / Med Waiting Area Intensive Care Unit Social Worker Vending Waiting Room

INTERIOR SIGNAGE

Department and Clinic Names

Consistent Naming

In an effort to make wayfinding easier for both patients and visitors to the VA Hospital, Fox Architects recommends using consistent naming throughout all wayfinding tools in the hospital. This includes any printed maps, exterior signs, main directories, secondary signage on each floor, and room signs.

The following terms are to be used for all new materials:

Exit to Smoking Shelter Meals on Wheels Nuclear Medicine Patient Effects University Hospital Tunnel

Admissions / Eligibility Agent Cashier Audiology Clinic / Speech Pathology Blue Clinic Cardiology / Thoracic Clinic Cardio Lab Cysto Urology Lab Dental Clinic Details Office Emergency Department Imaging Information Desk Main Lobby

OEF / OIF / OND

Outpatient Lab Patient Representative Patriot Cafe Patriot Store Pharmacy Pre-Registration Program Manager Police Red Clinic Release of Information Same Day Surgery Silver Clinic Surgery Waiting Room Vending / ATM Travel Urology Procedures Clinic White Clinic

Auditorium Bronze Clinic Cardiac Rehabilitation Coumadin / Anticoagulation Clinic Ear Nose & Throat Clinic Endoscopy Center / Pulmonary Function Testing (PFT) Eye Clinic Green Clinic Inpatient Psychiatric Unit or Acute Clinic Intensive Outpatient Program or Day Program Occupational Therapy / Physical Therapy Optical Shop Physical Medicine and Rehabilitation PM & R Brace Amputee Clinic / SCI

Lower Level

First Floor

Second Floor

Second Floor

Third Floor

Fourth Floor

Fifth Floor

Sixth Floor

1.6

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Typography

The primary typeface for the Truman VA signage system is Helvetica Bold. Helvetica Medium will be occasionally used for secondary pieces of information. Helvetica Bold Condensed will be used for overhead signage and Helvetica Medium

Condensed is used for directory and directional accents.

Raised characters should be in all capitals and accompanied by Grade 2 Braille.

12 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwxyz

1234567890”

21 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwyx

1234567890”

Helvetica Medium

12 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwxyz

1234567890”

21 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwyx

1234567890”

Helvetica Bold

12 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwxyz

1234567890”

21 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwyx

1234567890”

12 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwxyz

1234567890”

21 pt.

ABCDEFGHIJKLMNOPQRSTUVWXYZ

abcdefghijklmnopqrstuvwyx

1234567890”

Helvetica Bold Condensed

Helvetica Medium Condensed

1.7

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE ICONS

Overhead Icons Wall Graphics Icons Directory Icons

1.8

Cardiology / Thoracic Clinic

OVERHEAD ICONS

Dental

Imaging

Eye Clinic

Pharmacy

Information Desk

Patriot Cafe

Audiology Clinic

Travel

Agent Cashier

WALL GRAPHICS ICONS

Elevators

DIRECTORY ICONS

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Colors & Materials

Color Description Color Number Color Pantone Number Notes

Blue S-1 541 C

Red S-2 201 C

Light Blue S-3 279 C

Metallic Silver S-4 Match Matthew’s Paint

MP - 18100

Black T-1

Not Used T-2

Red T-3 201 C

White T-4

Metallic Silver Gradient T-5 Metallic 877 C 1st color from right to left: PANTONE METALLIC 877 C

Gradient:

- Type: Linear

- Location: 92.12 (PANTONE METALLIC 877 C) center gradient slider: 29.61

- Opacity: 100%

-Angle: 0°

2nd color light gray: C=0% M=0% Y=0% K=20%

Gradient:

- Type: Linear

- Location: 0 (C=0% M=0% Y=0% K=20%) center gradient slider: 29.61

- Opacity: 100%

- Angle: 0°

1.9

Notes: Emergency Text B17 Red (OSHA)

Trim & Brackets Clear Anodized Aluminium

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Interior Signage Notes

STANDARD INTERIOR SIGNAGE

Replace existing interior signage where indicated in accordance with the VA Signage Design Guide (www.cfm.va.gov/til Divisions 9 & 10).

Sign types A-D not included in package IN-15.55-57 / IN-15.65-67 Design to follow sign type E on page 1.11 IN-14.18 Design to follow sign type F on page 1.12 & 1.13 IN-17.12 Design to follow Main Directory G on page 1.14 IN-17.15 Design to follow sign type H on page 1.16 IN-14.01-.05 Design to follow sign type J on page 1.18

General notes:

1. Sign Company to verify all names on all signs with owner before sign production.

2. Sign Company to purchase all graphic images for the hospital. Sign Company responsible for modifying background on images.

3. Sign Company to provide up-dated message schedule and sign location plan drawing.

4. Refer to sheet 1.6 for all department and clinic names.

5. All signage to be in compliance with ADA & ABA Accessibility Standards for Federal Facilities.

6. Verify field dimensions before signage production and graphic wallcovering fabrication and installation.

7. Sign company to provide owner with software, printer, materials & instructional class on how to update changeable signs.

8. All aluminum sign frames to contain 75% recycled content. All signs with frames to be mechanically fastened to walls.

9. All sign backing to be Environmentally Preferred Product EPP Downstream Certified.

10. Sign Company to provide disc of template layout drawings, color, and typography specs for all changeable signs including directory, directionals, and overheads.

11. Sign Company to provide E2 F1 sign mock-up & sample of Vinyl Wallcovering for approval before production.

12. Prep existing drywall area to receive wallcovering (Re: Elevations)

1.10

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Interior Sign Types

Sign Type E-Ceiling / Soffit Directional

VA Reference IN.15.51 - 16-66

Overhead Signs

Verify dim. with field location

Graphic Panel

Material: Frame - Satin Anodized Aluminum w/ flexible clear lens cover

Digital Print Background Color: S-1

Digital Print Accent Color: S-3

Digital Print Typestyle: Helvetica Bold Condensed

Color: Vinyl Graphics to match: T-5

Attachment

Ceiling/Suspended Ceiling: Braided S.S. cable

Mounting Height: 7’-0” AFF

Signs over 20 lbs must be tied to deck

Wall: Secure w/ fastners

Note: Sign company to verify all room names and sign sizes before sign production

6”

EQEQ

3-1/2”

3-1/2”

71-1/4”

71-1/4”

CENTER TITLE TEXT

E1 Single Directional (2 line text) - Front View

Scale: 1” - 1’-0”

1.11

E1 Single Directional (1 line text) - Front View

Scale: 1” - 1’-0”

1/8” 1/8”

1/8”

1” 6” 1”

3-1/2”

3-1/2”

3-1/2”

EQ

EQ

EQ

EQ

EQ

EQ

1”6”1”

4”

EQ

2”

EQ

6 1/4”

1/8”

E2 Single Directional (1 line text) - Front View

Scale: 1” - 1’-0”

4”

39-1/4”

1” 1”

1/8”

1/8” 1/8”

E2 Single Directional (2 line text) - Front View

Scale: 1” - 1’-0”

2”

2”

EQ

EQ

1/8” 1” 1”

8”

EQEQ

71-1/4”

CENTER TITLE TEXT 1/8”

11”

1/8” 1” 1”

8”

1/8”

1/8”

11 1/4”

EQEQ CENTER TITLE TEXT

39-1/4”

EQ CENTER TITLE

TEXT

EQ

11”

1/8”

1/8”

11 1/4”

11”

1/8”

1/8”

11 1/4”

1”

1”

4”6 1/4”

1/8”

4”1” 1”

1/8”

1/8” 1/8”

1”

1”

E1 Multi-Directional (2 line text) - Front View

Scale: 1” - 1’-0”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

INTERIOR SIGNAGE

Interior Sign Types

Sign Type F - Large Floor Directory

VA Reference IN.-14.18

Changeable Module

Frame: Satin Anodized Aluminum w/ magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted top and bottom borders, S-4

Text: Black ink T-1 on transparent acetate 11x17

Typeface: Helvetica Bold

Type Size: 1”

Arrow Panel: S-4

Arrows: Red S-2

Photo Accent Panel

Frame: Satin Anodized Aluminum

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic image applied to back

Dimensional Number: 1/4” Acrylic, painted

Silver, S-4

Typeface: Helvetica Medium Condensed

Background of all images to gradate from Pantone colors 659 C (bottom) to 660 C (center) to

661 C (top).

Note:

Sign company to verify all room names and sign sizes before sign production.

Sign Company to purchase images for hospital.

F1 - 2 Panel Directional for Basement, Fourth Floor, and Fifth Floor, at South Elevator Cores, and First Floor and Second Floor at North Elevator Cores

Scale: 1 1/2” = 1’-0”

Basement: iStockphoto 3937538

NORTH ELEVATORSSOUTH ELEVATORS

Fourth Floor Image:

iStockphoto 1372848

First Floor Image:

World of Stock WOS10922

Fifth Floor Image:

iStockphoto 3819329

Second Floor Image:

Corbis Images 42-23738358

1.12

5’-5 7/8”

4”

34-3/4”

24”

2-1/2”

1/8”

17 1/16”

1/8”1/8”

17 1/16”

1/8”1/8”

24”

1/8”1/8”

4”

1”

3/8”

1”

3/8”

3/8”

3/8”

1/8” 1”

1”

11”

11”

11”

3”

3/8”

1/8”

1” Text Offset1/8”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

Title

INTERIOR SIGNAGE

Interior Sign Types

7’-4 3/16”

4”

F2 - 3 Panel Directional for First Floor, Second Floor, Third Floor, and Sixth Floor at South Elevator Cores

Scale: 1 1/2” = 1’-0”

Sign Type F - Large Floor Directory

VA Reference IN.-14.18

Changeable Module

Frame: Satin Anodized Aluminum w/ magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted top and bottom borders

Text: Black ink T-1 on transparent acetate 11x17

Typeface: Helvetica Bold

Type Size: 1”

Arrow Panel: S-3

Arrows: S-3 on S-4

Photo Accent Panel

Frame: Anodized Alum.

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic image applied to back

Dimensional Number: 1/4” Acrylic, Painted

Silver, S-4

Typeface: Helvetica Medium Condensed

Background of all images to gradate from Pantone colors 659 C (bottom) to 660 C (center) to

661 C (top).

Note:

Sign company to verify all room names and sign sizes before sign production.

Sign Company to purchase images for hospital.

First Floor Image:

World of Stock WOS10922

Second Floor Image:

Corbis Images 42-23738358

Third Floor Image:

iStockphoto 4650750

Sixth Floor Image:

www.photos.com 86528391

34-3/4”

24”

2-1/2”

1.13

1/8”

17 1/16”

1/8”1/8”

17 1/16”

1/8”1/8”

17 1/16”

1/8”1/8”

24”

1/8”1/8”

4” 4”

1”

3/8”

1”

3/8”

3/8”

3/8”

1/8” 1”

1”

11”

11”

11”

3”

3/8”

1” Text Offset1/8”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Interior Sign Types

Sign Type G - Main Directory - First Floor

VA Reference IN.-17.12

Changeable Module

Frame: Satin Anodized Aluminum with magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted S-4 top and bottom borders

Text: Black ink T-1 on transparent acetate 11x17

Floor Numbers: .125” thick non-glare acrylic, back-painted black, T-1

Face: .025” thick non-glare acrylic

Typeface: Helvetica Bold

Header Panel

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic image applied to back

Dimensional Text: 1/16” Acrylic, Front-Painted Silver, S-4

Typeface: Helvetica Bold

Background of all images to gradate from Pantone colors 659 C (bottom) to 660 C (center) to

661 C (top).

Note:

Sign company to verify all room names and sign sizes before sign production.

Sign Company to purchase images for hospital.

G - Front View

Scale: 1 1/2” = 1’-0”

3’-9 3/8”

11 3/4”

1/8”

11 3/4”

11 3/4”

10”

4’-3 11/16”

17 1/16”

1.14

Note:

Sign Company to verify all room names before production of signs

1 2 Admissions / Eligibility

Agent Cashier

Audiology Clinic / Speech Pathology

Blue Clinic

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Details Office

Emergency Department

Imaging

OEF / OIF / OND

Outpatient Lab

Patient Representative

Patriot Cafe / Store

Pharmacy

Police

Pre - Registration

Red Clinic

Release of Information

Same Day Surgery

Silver Clinic

Travel

Vending / ATM

White Clinic

Auditorium

Bronze Clinic

Endoscopy Center / Pulmonary

Function Testing

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Prosthetics

Sleep Disorders Center

Specialty Clinic

Urology

Chapel

EEO

Hospital Director

Truman Community Living Center

Voluntary Service

Vending

6 Intensive Care Unit

6 Surgery / Medicine

4 Medicine Inpatient Unit

Dialysis

Step Down Unit

Compensation / Pension Clinic

Fee Basis

MCCR

Service Representatives

Vending

B Nuclear Medicine

Meals on Wheels

1/8” 1”

3/8”

1/2”

1/2” 1/2”

3/8”

3/8”

2”

17 1/16” 17 1/16”

1/8”1/8” 1/8” 1/8”

1/8” 1”

EQ CENTER TITLE EQ

2”

2”

EQ

EQ

EQ

3/8”

3/8”

3/8”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Elevation at First Floor Information Desk

Scale: 1/2” = 1’-0”

1.15

SIGNAGE & GRAPHICS ELEVS.

Sign Type G - Elevation

First Floor Lobby at Information Desk

3’-0”

EQEQ CENTER

6’-0”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

Audiology Clinic / Speech Pathology

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Emergency Department

Patriot Café / Store

Outpatient Lab

Imaging

Red / White / Blue / Silver Clinics

Same Day Surgery

B

Bronze Clinic

Endoscopy Center / PFT

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Specialty Clinic

Urology

Truman Community Living Center

Medicine Inpatient Unit

Dialysis

Compensation / Pension Clinic

Intensive Care Unit

Nuclear Medicine

H - Front View

Scale: 1-1/2” = 1’-0”

INTERIOR SIGNAGE

Interior Sign Types

Sign Type H - Small Directory

VA Reference IN.-17.15

Changeable Module

Frame: Satin Anodized Aluminum w/ magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted S-4 top and bottom borders

Text: Black ink T-1 on transparent acetate 11x17

Typeface: Helvetica Bold

Floor Numbers: .125 thick non - glare acrylic painted black T-1

Header Panel

Frame: Satin Anodized Aluminum

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic image applied to back

Dimensional Text: 1/16” Acrylic, Painted Silver, S-4

Typeface: Helvetica Bold

Background of all images to gradate from Pantone colors 659 C (bottom) to 660 C (center) to

661 C (top).

Note:

Sign company to verify all room names and sign sizes before sign production.

Sign Company to purchase images for hospital.

1.16

1/8”

17 1/16”

1/8” 1”

3/8”

1/2”

1/2” typ.

3/8”

3/8”

1”

1/8”1/8”

1/8”

1 1/2”

3/8”

11” typ.

3/8”

3/8”

1/8”

1/8” 3/4”

43 3/8”

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Interior Sign Types

I - Front View

Scale: 1-1/2” = 1’-0”

17 1/16”

51 11/16”

17 1/16”

6”EQ” EQ”

1-1/2”

17 1/16”

6”

EQ”

EQ”

1.17

3/8”

1”

3/8”

3/8”

3/8”

1”

11”

11”

32”

3/8”

1/8”

1/8”

1/8”

1/8” 1/8”

1/8”1/8”

1”

17”

Sign Type I - Directional @ 2nd Floor Bridge

Changeable Module

Frame: Satin Anodized Aluminum w/ magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted S-4 top and bottom borders

Text: Black ink T-1 on transparent acetate 11x17

Typeface: Helvetica Bold

Arrow Panel: S-3

Arrows: S-3 on S-4

Photo Accent Panel

Frame: Anodized Aluminum

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic image applied to back

Dimensional Number: 1/4” Acrylic, Painted Silver, S-4

Typeface: Helvetica Medium Condensed

Note:

Background of all images to gradate from Pantone colors 659 C (bottom) to 660 C (center) to

661 C (top).

Sign Company to purchase images for hospital & to verify all room names before production

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

INTERIOR SIGNAGE

Interior Sign Types

Sign Type J - Wall Directional

VA Reference IN.-14.01-0.5

Changeable Module

Frame: Satin Anodized Aluminum w/ magnetic sheets applied to masonite back

Base: .125” thick non-glare acrylic, back-painted silver, S-4

Filler: .025” thick acrylic

Face: .125” thick non-glare acrylic w/ 3/8” painted S-4 top and bottom borders

Text: Black ink T-1 on transparent acetate 11x17

Typeface: Helvetica Bold

Arrow: Vinyl applied, Black T-1

Header Panel

Frame: Satin Anodized Aluminum

Material: 1/4” Non-Glare Acrylic w/

Vinyl Graphic omage applied to back

Dimensional Number: 1/4” Acrylic, Painted Silver, S-4

Typeface: Helvetica Medium Condensed

Note:

Sign Company to verify all room names & numbers before production of signs. Background of all images to gradate from Pantone colors 659

C (bottom) to 660 C (center) to 661 C (top). Sign

Company to purchase images for hospital.

1.18

Speciality Clinic Dermatology Hematology / Oncology General Surgery Orthopaedics

Podiatery Pulmonary Rheumatology Vascular

17-1/16”

43 3/8”

2”

1”

7 7/8”

11”

Audiology Clinic / Speech Pathology

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Emergency Department

Patriot Café / Store

Outpatient Lab

Imaging

Red / White / Blue / Silver Clinics

Same Day Surgery

Bronze Clinic

Endoscopy Center / PFT

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Specialty Clinic

Urology

Truman Community Living Center

Medicine Inpatient Unit

Dialysis

Compensation / Pension Clinic

Intensive Care Unit

Nuclear Medicine

Audiology Clinic / Speech Pathology

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Emergency Department

Patriot Café / Store

Outpatient Lab

Imaging

Red / White / Blue / Silver Clinics

Same Day Surgery

Bronze Clinic

Endoscopy Center / PFT

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Specialty Clinic

Urology

Truman Community Living Center

Medicine Inpatient Unit

Dialysis

Compensation / Pension Clinic

Intensive Care Unit

Nuclear Medicine

Audiology Clinic / Speech Pathology

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Emergency Department

Patriot Café / Store

Outpatient Lab

Imaging

Red / White / Blue / Silver Clinics

Same Day Surgery

Bronze Clinic

Endoscopy Center / PFT

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Specialty Clinic

Urology

Truman Community Living Center

Medicine Inpatient Unit

Dialysis

Compensation / Pension Clinic

Intensive Care Unit

Nuclear Medicine

Audiology Clinic / Speech Pathology

Cardiology / Thoracic Clinic

Cysto Urology Lab

Dental Clinic

Emergency Department

Patriot Café / Store

Outpatient Lab

Imaging

Red / White / Blue / Silver Clinics

Same Day Surgery

Bronze Clinic

Endoscopy Center / PFT

Eye Clinic

Green Clinic

Physical Medicine / Rehabilitation

Specialty Clinic

Urology

Truman Community Living Center

Medicine Inpatient Unit

Dialysis

Compensation / Pension Clinic

Intensive Care Unit

Nuclear Medicine

J2 - Front View

Scale: 1-1/2” = 1’-0”

J3 - Front View

Scale: 1-1/2” = 1’-0”

J1 - Front View

Scale: 1-1/2” = 1’-0”

Graphics Per Floor

Scale: 1-1/2” = 1’-0”

4th Floor

5th Floor

6th Floor

3rd Floor

Emergency Department Main Lobby Cardiology / Echo / EKG Radiology

Patriot Cafe Police Dental Clinic Outpatient Lab Blood Draw

Same Day Surgery

1/8”

3/8” 3/4”

1/8”

1”

3/8”

3/8”

1/8”1/8”

3/8”

11”

3/8”

3/8”

1/8”

17-1/16”

17-1/16”

2”

2”

1”

1”

7 7/8”

7 7/8”

11”

11”

1/8”

1/8”

3/8”

3/8”

3/4”

3/4”

1/8”

1/8”

1”

1”

3/8”

3/8”

3/8”

1/8”

1/8”

1/8”

1/8”

1/8”

3/8”

11”

1/8”

Chapel Voluntary Service

SECTION 2 WALL GRAPHICS

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

4B4B

U n iv e rs it y H o s p it a l (t u n n e l)

Smoking

Shelter

Meals

On

Wheels

Lost &

Found

Patient

Effects

General Notes:

WALL GRAPHICS

Plans

2.1

Nuclear

Medicine

Basement - Wall Graphics

Elevator Graphics - See elevations

N

0’ 10’ 20’ 40’

4A4A

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

5B5B 5A5A

Emergency

Department

Audiology

Clinic / Speech

Pathology

Imaging

Admissions/

Eligibility

Main

Lobby

Details

Office

Vending

Cardiology /

Thoracic

Clinic

Pharmacy

Pick-Up

Window

Main

Entrance

Release of

Information

Blue Clinic

Silver

Clinic Outpatient

Same-

Day

Surgery

Cysto

Urology

Lab

White Clinic

Red Clinic

Police

Dental Clinic

Patient

Advocate

Pre-

Registration

Information

Desk

OEF/OIF/OND

WALL GRAPHICS

Plans

2.2

Patriot

Cafe

Patriot

Store

Agent

Cashier

Travel

Cardio

Lab

First Floor - Wall Graphics

Wall Graphic - See elevations

Elevator Graphics - See elevations

N

0’ 10’ 20’ 40’

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

6B6B 6A

Specialty

Clinic

VIST

Coordinator

Endoscopy Clinic/

Pulmonary Func-tion

Testing (PFT)

Sleep Disorders

ClinicCardiac

Rehabilitation

PM&R/Brace/

Amputee Clinic/SCI

Optical

Shop

Eye Clinic

Inpatient

Psychiatric

Unit

Green

Clinic

Auditorium

Intensive

Outpatient

Program

Bronze

Clinic

Prosthetics

Occupational Ther-apy/

Physical Therapy

2.3

96A 7

Physical

Medician/

Rehabilitation

Second Floor - Wall Graphics

Wall Graphic - See elevations

Elevator Graphics - See elevations

N

Columbia, Missouri

Improve Interior Wayfinding

Date: July 22, 2014

Project: 1122.01

1 Memorial Drive, Suite 1800

St. Louis, Missouri 63102

Phone: (314) 621 4343

Fax: (314) 621 0261

Email: info@fox-arch.com

2.4

Hospital

Director

Medical

Media Home Based

Primary Care

Medical

Library

Human

Resources

Craft Room

Voluntary

Services

Truman Community Living

Center

Chapel

Public

Affairs

CBOC Coordinator/

Special Programs

Women’s

Coordinator

Learning

Organization

Vending

Conference

Room B344

Third Floor - Wall Graphics

Elevator Graphics - See elevations

N

01 00 00 GENERAL REQUIREMENTS
1.1 safety requirements
1.2 GENERAL INTENTION
1.3 STATEMENT OF BID ITEM(S)
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR
1.5 CONSTRUCTION SECURITY REQUIREMENTS
1.6 OPERATIONS AND STORAGE AREAS
1.7 ALTERATIONS
1.8 DISPOSAL AND RETENTION
1.9 PROTECTION OF EXISTING STRUCTURES, EQUIPMENT, UTILITIES, AND IMPROVEMENTS
1.10 RESTORATION
1.11 LAYOUT OF WORK
1.12 AS-BUILT DRAWINGS
1.13 USE OF ROADWAYS
1.14 Contracting Officer’s Representative'S FIELD OFFICE
1.15 TEMPORARY USE OF MECHANICAL AND ELECTRICAL EQUIPMENT
1.16 TEMPORARY USE OF EXISTING ELEVATORS
1.17 TEMPORARY TOILETS
1.18 AVAILABILITY AND USE OF UTILITY SERVICES
1.19 NEW TELEPHONE EQUIPMENT
1.20 TESTS
1.21 INSTRUCTIONS
1.22 GOVERNMENT-FURNISHED PROPERTY
1.23 RELOCATED EQUIPMENT and items
01 00 10 MEDICAL CENTER REQUIREMENTS
Matrix of Precautions for Construction & Renovation
Contractor/Subcontractor/Employee Notification of Asbestos Form
01 33 23 SHOP DRAWINGS, PRODUCT DATA AND SAMPLES
PART 1 – GENERAL
01 35 26 SAFETY REQUIREMENTS
1.1 APPLICABLE PUBLICATIONS:
1.2 DEFINITIONS:
1.3 REGULATORY REQUIREMENTS:
1.4 ACCIDENT PREVENTION PLAN (APP):
1.5 ACTIVITY HAZARD ANALYSES (AHAs):
1.6 PRECONSTRUCTION CONFERENCE:
1.7 “SITE SAFETY AND HEALTH OFFICER” (SSHO) and “COMPETENT PERSON” (CP):
1.8 TRAINING:
1.9 INSPECTIONS:
1.10 ACCIDENTS, OSHA 300 LOGS, AND MAN-HOURS:
1.11 PERSONAL PROTECTIVE EQUIPMENT (PPE):
1.12 INFECTION CONTROL
1.13 FIRE SAFETY
1.14 ELECTRICAL
1.15 FALL PROTECTION
1.16 SCAFFOLDS AND OTHER WORK PLATFORMS
1.17 EXCAVATION AND TRENCHES
1.18 CRANES
1.19 CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT)
1.20 CONFINED SPACE ENTRY
1.21 WELDING AND CUTTING
1.22 LADDERS
1.23 FLOOR & WALL OPENINGS
01 45 00 QUALITY CONTROL
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies requirements for Contractor Quality Control (CQC) for Design-Bid-Build (DBB) or Design-Build (DB) construction projects. This section can be used for both project types.
1.2 APPLICABLE PUBLICATIONS
A. The publication listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
B. ASTM International (ASTM)
1.3 SUBMITTALS
A. Government approval is required for all submittals. CQC inspection reports shall be submitted under this Specification section and follow the [Applicable CQC Control Phase (Preparatory, Initial, or Follow-Up)]: [Applicable Specification section] naming convention.
PART 2 PRODUCTS – NOT USED
PART 3 - EXECUTION
3.1 GENERAL REQUIREMENTS
A. Establish and maintain an effective quality control (QC) system. that complies with the FAR Clause 52.246.12 titled “Inspection of Construction”. QC consists of plans, procedures, and organization necessary to produce an end product which complies with the Contract requirements. The QC system covers all design and construction operations, both onsite and offsite, and be keyed to the proposed design and construction sequence. The project superintendent will be held responsible for the quality of work and is subject to removal by the Contracting Office or Authorized designee for non-compliance with the quality requirements specified in the Contract. In this context the highest-level manager responsible for the overall construction activities at the site, including quality and production is the project superintendent. The project superintendent maintains a physical presence at the site at all times and is responsible for all construction and related activities at the site, except as otherwise acceptable to the Contracting Officer’s Representative.
3.2 CQC PLAN:
A. Submit the CQC Plan no later than 10 days after receipt of Notice to Proceed (NTP) proposed to implement the requirements of the FAR Clause 52.246.12 titled “Inspection of Construction”. The Government will consider an Interim CQC Plan for the first days of operation, which must be accepted within 5 business days of NTP. Design and/or construction will be permitted to begin only after acceptance of the CQC Plan or acceptance of an Interim plan applicable to the particular feature of work to be started. Work outside of the accepted Interim CQC Plan will not be permitted to begin until acceptance of a CQC Plan or another Interim CQC Plan containing the additional work scope is accepted.
B. Content of the CQC Plan: Include, as a minimum, the following to cover all design and construction operations, both onsite and offsite, including work by subcontractors, designers of record consultants, architects/engineers (A/E), fabricators, suppliers, and purchasing agents:
C. Additional Requirements for Design Quality Control (DQC) Plan: The following additional requirements apply to the DQC Plan for DB projects only and not DBB projects:
D. Acceptance of Plan: Acceptance of the Contractor’s plan is required prior to the start of design and construction. Acceptance is conditional and will be predicated on satisfactory performance during the design and construction. The Government reserves the right to require the Contractor to make changes in the CQC Plan and operations including removal of personnel as necessary, to obtain the quality specified.
E. Notification of Changes: After acceptance of the CQC Plan, notify the Contracting Officer’s Representative in writing of any proposed change. Proposed changes are subject to acceptance by the Government prior to implementation by the Contractor.
3.3 COORDINATION MEETING:
A. After the Preconstruction Conference Post-Award Conference before start of design or construction, and prior to acceptance by the Government of the CQC Plan, meet with the Contracting Officer’s Representative to discuss the Contractor’s quality control system. Submit the CQC Plan a minimum of 2 business days prior to the Coordination Meeting. During the meeting, a mutual understanding of the system details must be developed, including the forms for recording the CC operations, design activities (if applicable), control activities, testing, administration of the system for both onsite and offsite work, and the interrelationship of Contractor’s Management and control with the Government’s Quality Assurance. Minutes of the meeting will be prepared by the Government, signed by both the Contractor and Contracting Officer’s Representative and will become a part of the contract file. There can be occasions when subsequent conferences will be called by either party to reconfirm mutual understandings or address deficiencies in the CQC system or procedures which can require corrective action by the Contractor.
3.4 QUALITY CONTROL ORGANIZATION:
A. Personnel Requirements: The requirements for the CQC organization are a Safety and Health Manager, CQC System Manager, a Design Quality Manager (if applicable), and sufficient number of additional qualified personnel to ensure safety and Contract compliance. The Safety and Health Manager shall satisfy the requirements of Specification 01 35 26 Safety Requirements and reports directly to a senior project (or corporate) official independent from the CQC System Manager. The Safety and Health Manager will also serve as a member of the CQC Staff. Personnel identified in the technical provisions as requiring specialized skills to assure the required work is being performed properly will also be included as part of the CQC organization. The Contractor’s CQC staff maintains a presence at the site at all times during progress of the work and have complete authority and responsibility to take any action necessary to ensure Contract compliance. The CQC staff will be subject to acceptance by the Contracting Officer’s Representative. Provide adequate office space, filing systems, and other resources as necessary to maintain an effective and fully functional CQC organization. Promptly complete and furnish all letters, material submittals, shop drawings submittals, schedules and all other project documentation to the CQC organization. The CQC organization is responsible to maintain these documents and records at the site at all times, except as otherwise acceptable to the Government.
B. CQC System Manager: Identify as CQC System Manager an individual within the onsite work organization that is responsible for overall management of CQC and has the authority to act in all CQC matters for the Contractor. The CQC system Manager is required to be a graduate engineer, graduate architect, or a graduate of construction management, with a minimum of 5 years construction experience on construction similar to the scope of this Contract. This CQC System manager is on the site at all times during construction and is employed by the General Contractor. The CQC System Manger is assigned as CQC System Manager but has duties as project superintendent in addition to quality control. Identify in the plan an alternate to serve in the event of the CDQC System Manager’s absence. The requirements for the alternate are the same as the CQC System Manager.
C. CQC Personnel: In addition to CQC personnel specified elsewhere in the contract, provide as part of the CQC organization specialized personnel to assist in the CQC System Manager for the following areas, as applicable: electrical, mechanical, civil, structural, environmental, architectural, materials technician submittals clerk, Commissioning Agent/LEED specialist, and low voltage systems. These individuals or specified technical companies are directly employed by the General Contractor and cannot be employed by a supplier or subcontractor on this project; be responsible to the CQC System Manager; be physically present at the construction site during work on the specialized personnel’s areas of responsibility; have the necessary education or experience in accordance with the Experience Matrix listed herein. These individuals can perform other duties but need to be allowed sufficient time to perform the specialized personnel’s assigned quality controls duties as described in the CQC Plan. A single person can cover more than one area provided that the single person is qualified to perform QC activities in each designated and that workload allows.
EXPERIENCE MATRIX
D. Additional Requirements: In addition to the above experience and education requirements, the CQC System Manager and Alternate CQC System Manager are required to have completed the Construction Quality Management (CQM) for Construction course. If the CQC System Manager does not have a current specification, obtain the CQM for Contractors course identification within 90 days of award. This course is periodically offered by the Naval Facilities Engineering Command and the Army Corps of Engineers. Contact the Contracting Officer’s Representative for information on the next scheduled class.
E. Organizational Changes: Maintain the CQC staff at full strength at all times. When it is necessary to make changes to the CQC staff, revise the CQC Plan to reflect the changes and submit the changes to the Contracting Officer’s Representative for acceptance.
3.5 SUBMITTALS AND DELIVERABLES: Submittals have to comply with the requirements in SECTION 01 33 23 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. The CQC organization is responsible for certifying that all submittals and deliverables are in compliance with the contract requirements. When Section 01 91 00 GENERAL COMMISSIONING REQUIREMENTS is included in the contract, the submittals required by the section have to be coordinated with the SECTION 01 33 23 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES to ensure adequate time is allowed for each type of submittal required.
3.6 CONTROL:
A. CQC is the means by which the Contractor ensures that the construction, to include that of subcontractors and suppliers, complies with the requirements of the contract. At least three phases of control are required to be conducted by the CQC System Manager for each definable feature of the construction work as follows:
B. Initial Phase: This phase is accomplished at the beginning of a definable feature of work. Accomplish the following:
C. Follow-Up Phase: Perform daily checks to assure control activities,
including control testing, are providing continued compliance with contract requirements until the completion of the particular feature of work. Record the checks in the CQC documentation. Conduct final Follow-Up checks and correct all deficiencies prior to the start of additional features of work which may be affected by the deficient work. Do not build upon nor conceal non-conforming work. Coordinate scheduled work with Special Inspections required by Section 01 45 35 Special Inspections, the Statement of Special Inspections, and the Schedule of Special Inspections
D. Additional Preparatory and Initial Phases on the same definable features of work if: the quality ongoing work is unacceptable; if there are changes in the applicable CQC staff, onsite production supervision or work crew; if work on a definable feature is resumed after a substantial period of inactivity, or if other problems develop.
3.7 TESTS
A. Testing Procedure: Perform specified or required tests to verify that control measures are adequate to provide a product which conforms to contract requirements. Upon request, furnish to the Government duplicate samples of test specimens for possible testing by the Government. Testing includes operation and acceptance test when specified. Procure the services of a Department of Veteran Affairs approved testing laboratory or establish an approved testing laboratory at the project site. Perform the following activities and record and provide the following data:
B. Testing Laboratories: All testing laboratories must be validated through the procedures contained in Specification section 01 45 29 Testing Laboratory Services.
C. Onsite Laboratory: The Government reserves the right to utilize the Contractor’s control testing laboratory and equipment to make assurance tests, and to check the Contractor’s testing procedures, techniques, and test results at no additional cost to the Government.
3.8 COMPLETION INSPECTION
A. Punch-Out Inspection: Conduct an inspection of the work by the CQC system Manager near the end of the work, or any increment of the work established by the specifications. Prepare and include in the CQC documentation a punch list of items which do not conform to the approved drawings and specifications. Include within the list of deficiencies the estimated date by which the deficiencies will be corrected. Make a second inspection the CQC System Manager or staff to ascertain that all deficiencies have been corrected. Once this is accomplished, notify the Government that the facility is ready for the Government Pre-Final Inspection.
B. Pre-Final Inspection: The Government will perform the Pre-Final Inspection to verify that the facility is complete and ready to be occupied. A Government Pre-Final Punch List may be developed as a result of this inspection. Ensure that all items on this list have been corrected before notifying the Government, so that a Final Acceptance Inspection with the customer can be scheduled. Correct any items noted on the Pre-Final Inspection in a timely manner. These inspections and any deficiency corrections required by this paragraph need to be accomplished within the time slated for completion of the entire work or any particular increment of the work if the project is divided into increments by separate construction completion dates.
C. Final Acceptance Inspection: The Contractor’s QC Inspection personnel, plus the superintendent or other primary management person, and the Contracting Officer’s Representative is required to be in attendance at the Final Acceptance Inspection. Additional Government personnel can also be in attendance. The Final Acceptance Inspection will be formally scheduled by the Contracting Officer’s Representative based upon results of the Pre-Final Inspection. Notify the Contracting Officer’s Representative through the Contracting office at least 14 days prior to the Final Acceptance Inspection and include the Contractor’s assurance that all specific items previously identified to the Contractor as being unacceptable, along with all remaining work performed under the contract, will be complete and acceptable by the date schedule for the Final Acceptance Inspection. Failure of the Contractor to have all contract work acceptably complete for this inspection will be cause for the Contracting Officer’s Representative to bill the Contractor for the Government’s additional inspection cost in accordance with FAR Clause 52.246-12 titled “Inspection of Construction”.
3.9 DOCUMENTATION
A. Quality Control Activities: Maintain current records providing factual evidence that required QC activities and tests have been performed. Include in these records the work of subcontractors and suppliers on an acceptable form that includes, as a minimum, the following information:
B. Verification Statement: Indicate a description of trades working on the project; the number of personnel working; weather conditions encountered; and any delays encountered. Cover both conforming and deficient features and include a statement that equipment and materials incorporated in the work and workmanship comply with the Contract. Furnish the original and one copy of these records in report form to the Government daily with 1 week after the date covered by the report, except that reports need not be submitted for days on which no work is performed. As a minimum, prepare and submit on report for every 7 days of no work and on the last day of a no work period. All calendar days need to be accounted for throughout the life of the contract. The first report following a day of no work will be for that day only. Reports need to be signed and dated by the CQC System Manager. Include copies of test reports and copies of reports prepared by all subordinate QC personnel within the CQC System Manager Report.
3.10 SAMPLE FORMS
A. Templates of various quality control reports can be found on the Whole Building Design Guide website at https://www.wbdg.org/FFC/NAVGRAPH/quality_control_reports.pdf
3.11 NOTIFICATION OF NONCOMPLIANCE:
A. The Contracting Officer’s Representative will notify the Contractor of any detected noncompliance with the foregoing requirements. The Contractor should take immediate corrective action after receipt of such notice. Such notice, when delivered to the Contractor at the work site will be deemed sufficient for the purpose of notification. If the Contractor fails or refuses to comply promptly, the Contracting Officer’s Representative can issue an order stopping all or part of the work until satisfactory corrective action has been taken. No part of the time lost due to such stop orders will be made the subject of claim for extension of time or for excess costs or damages by the Contractor.
01 45 35 SPECIAL INSPECTIONS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This guide specification will be applicable to both new buildings and existing building rehabilitations/renovations. In addition to the Special Inspection and testing specified requirements, a registered design professional must perform structural observations during construction. All observed deficiencies will be immediately reported to the Contracting Officer’s Representative. The registered design professional performing these observations will be a representative of the Designer of Record (DOR) for the building being constructed.
B. Structural observations are required for the following project conditions per IBC Chapter 17:
1.2 APPLICABLE PUBLICATIONS
A. The publication listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
B. American Society of Civil Engineers (ASCE)
C. International Code Council (ICC)
1.3 GENERAL REQUIREMENTS
A. Perform Special Inspections in accordance with the Statement of Special Inspections, Schedule of Special Inspections and Chapter 17 of ICC IBC. The Statement of Special Inspections and Schedule of Special Inspections are included as an attachment to this specification. Special Inspections are to be performed by an independent third party and are intended to ensure that the work of the prime contractor is in accordance with the Contract Documents and applicable building codes. Special inspections do not take the place of the three phases of control inspections performed by the Contractor's QC Manager or any testing and inspections required by other sections of the specifications.
B. Structural observations will be performed by the Government. The contractor must provide notification to the Contracting Officer’s Representative 14 days prior to the following points of construction that structural observations need to occur:
1.4 DEFINITIONS
A. Continuous Special Inspections – The constant monitoring of specific tasks by a special inspector. These inspections must be carried out continuously over the duration of the particular tasks.
B. Periodic Special Inspections – Special Inspections by the special inspector who is intermittently present where the work to be inspected has been or is being performed. Specific time interval on a specific Special Inspection should be indicated on the Schedule of Special Inspections.
C. Perform – Perform these Special Inspections tasks for each welded joint or member.
D. Observe – Observe these Special Inspections items on a random daily basis. Operations need not be delayed pending these inspections.