This solicitation is for a federal contract opportunity to relocate a medical ward for patient privacy at a Veterans Affairs medical center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is seeking proposals to provide specifications and drawings as outlined in solicitation number 36c25522R0024 and file 589A4-21-100 SIGNED DRAWINGS R1_Part9.pdf. Offerors should submit responses with requirements for renovating and reconfiguring an existing medical ward space to enhance patient privacy, as well as any associated architectural, mechanical, electrical, or construction services defined in the solicitation documents. The response due date is not specified.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEC
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
W4
L5 BID ITEM #2
(REF. GI001)
96"
4TH FLOOR/ROOF - KEY PLAN
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EL141
ELECTRICAL LIGHTING PLAN - 4TH
FLOOR - AREA A
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
4' 8' 16'
1/8" = 1'-0"
0'
N
1/8" = 1'-0" A
ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A
# KEYED NOTES:
L5 CONNECT TO EXISTING NORMAL POWER LIGHTING CIRCUIT SERVING THIS
AREA.
08/04/2021
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
BID ITEM #2
(REF. GI001)
4TH FLOOR/ROOF - KEY PLAN
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EL141.2
ELECTRICAL LIGHTING PLAN - 4TH
FLOOR - AREA A - BID ITEM #2
(DEDUCT)
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
4' 8' 16'
1/8" = 1'-0"
0'
N
1/8" = 1'-0" A
ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A - BID ITEM #2 (DEDUCT)
JT
JT
JT
D D
D
D
D
D
D
D
D
D D
D
D
D
IR
D
D
D
D
D
D
M
M
M
DDD
JT
JT
JT
JT
DDDDD
D
D
D
D D
D
D D
D
D
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
PAT. RM #5
A305
TLT./SHWR
A305A
PAT. RM #7
A307
PAT. RM #9
A309
PAT. RM #11
A311
TLT./SHWR
A311ATLT./SHWR
A309A
TLT./SHWR
A307A
SV
KP
SV
KP KP
SV
KP
SV
ST
ST
ST
ST ST
ST
ST
ST
H4 H4
H4
H4
HSHS
H4
H4
H4
H4
H4H4
H4 H4
HSHS
H4 H4
H4 H4 ab b a c,d e c,d,e a a a h f f f b a b b a c,d,e a a a c,d e h f f f b a bb a a c,d,e c,d e a a h f b f f b ab e c,d c,d,e a a a a h f b f
H4 H4H4H4 a a a H4H4H4 f f f f f
U2 U2
U2
U2
S1 g g g gS1 S1 g g
LP3-E5-277VN:1
LP3-E5-277VC:3
H4 H4
H4
H4a a a a
S1 S1 S1 S1ff ff
L3 L3
L3
L3
L4
L4 L4 L4
H4 a a H4
S8 S8 S8 S8
H4 h h h h
H4 a a H4 H4
H4 a a
H4 a a
ISO/BAR #1
A301
TLT./SHWR
A301A
ANTE
A301B
ANTE
A302B
ISO/BAR #2
A302
TLT./SHWR
A302A
ISO/BAR #3
A303
ANTE
A303B
TLT./SHWR
A303A
KA
KP
KP
KA
SV
SV
KA
KP
HS
ST
H4
H4
H4
H4
ST
HS
ST
H4 H4
H4
H4
H4 H4
ST
ST
HS
ST
a b b f f f b e c,d c,d,e a a a a f b f f a a a b b e c,d a c,d,e a b f f b b a e c,d c,d,e aa f H4f f a H4
H4
SV
H4 f a H4
H4 a
U2
U2
U2
STORAGE
A327
LP3-E5-277VC:1
LP3-E5-277VN:1
f f f
S1
S1
S1 h h h
L3
L3
L3
L4
L4
L4
S6
S1
H4 H4aa a H4
H4 f
H4 a
S6 S7 hhh g g
H4 a
PAT. RM #4
D304
TLT./SHWR
D304A
TLT./SHWR
D306A
PAT. RM #6
D306
PAT. RM #8
D308
TLT./SHWR
D308A
PAT. RM #10
D310
TLT./SHWR
D310A
PAT. RM #12
D312
TLT./SHWR
D312A
HS
ST
SV
H4 H4
KP
H4H4 ST
HS
ST
SV
H4
H4
ST
H4
KP
H4
HS
ST
SV
KP
H4
H4 H4
H4
ST
KP
ST
H4 H4
H4 H4
SV
ST
HSHS
ST
SV
KP
ST
f b f f h c,d,e c,d e b b a a b b a a e c,d c,d,e aa f b f f f b f f h a a a c,d,e ac,d e b b a f b f f h a c,d,e a a a c,d e b b a f b ff a a a c,d,e a e c,d b a b f a a a a
H4
H4
H4
H4
H4
H4
H4 a a
H4 a f H4 H4 a a a a a f ff
H4
H4
H4 H4
H4 H4
H4
U2U2U2U2
S1 g g g g
S1
U2
S1 g g g g
S1
LP3-E5-277VN:3
LP3-E5-277VC:5
S1 S1S1 S1
S1f f f f f aa H4 H4
L3
L3
L3
L3L3
L4 L4 L4 L4 L4 h
S9 h
H4 a a H4 h
S8
S8 h h
S8 h
H4 a
H4 a
S8 h
H4 a aH4
H4 a
H4 a a aH4
H4
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EL431
ELECTRICAL ENLARGED LIGHTING
PLANS
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
KEYED NOTES:
L3 CONNECT UNDERCABINET LIGHTING TO RECEPTACLE CIRCUIT SERVING
COUNTERTOP BELOW. MOUNT LIGHT SWITCH AT SAME HEIGHT AS
RECEPTACLES ABOVE COUNTERTOP. WHERE POSSIBLE, MOUNT
RECEPTACLE AND SWITCH IN SAME OUTLET BOX AND COVERPLATE.
L4 READING LIGHT PORTION OF FIXTURE TO BE LOCATED AT HEAD OF BED.
1/4" = 1'-0" A
ENLARGED LIGHTING PLAN - NORTH PATIENT ROOMS
1/4" = 1'-0"
B
ENLARGED LIGHTING PLAN - NORTHWEST ISO/BAR ROOMS
1/4" = 1'-0" C
ENLARGED LIGHTING PLAN - SOUTH PATIENT ROOMS 2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
NN
N
F E
C
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
F E
C
D
D
D
D
D
D
D
D
D
D
D
D
PAT. RM #24
D324
TLT./SHWR
D324A
PT TLT.
D323A
PAT. RM #23
D323
PAT. RM #22
D322
TLT./SHWR
D322A
PAT. RM #21
D321
TLT./SHWR
D321A
KP
SV
ST
ST
H4 H4
H4
H4
HS
KP
SVST
ST
HS
ST
KP
HS
ST
SV
SV
ST
HS
ST
KP
b b a a a aa c,d,e c,de f f b f f ff b b a b e c,d c,d,e a b c,d,e e c,d b f bf f a b e c,d c,d,e b f b f f
H4
H4 a f a a a aa
H4
H4
H4
H4 H4
H4 H4 H4
H4 H4 a a a aa f
H4 a a a a a
H4 H4
H4
H4H4
H4 f
H4 a
U2
U2
U2
U2
S1 g g
LP3-E5-277VN:5
LP3-E5-277VC:11
S1
S1
S1
S1 h f f f f
L3
L3
L3
L3 h h
L4
L4
L4
L4
S10 h h S6
H4
H4 H4 a a a
H4 a
H4 H4 aa
H4 H4 a a a H4
S7 h
H4 H4a a h S10
PAT. RM #17
A317
TLT./SHWR
A317A
BARIATRIC #18
A318
TLT./SHWR
A318A
ISO/BAR #19
D319
TLT./SHWR
D319A
ANTE
D319B
BARIATRIC #20
D320
TLT./SHWR
D320A
KP
SV
KP
SV
KA
KP
SV
KP
SV
H4 H4
H4 H4
HS
ST
ST
H4 H4
ST
H4 H4HS
ST
HS
ST
ST
H4
H4
ST
H4 H4
H4
H4HS
ST
b f f b b a e c,d c,d,e aa a a c,d,e e c,d a b f f b f a a b e c,d c,d,e a a b a a a b f b f b f b a f b e c,d c,d,e a a aa a a a
H4
H4
H4 f f f
H4f f
H4
H4 f f
H4
U2
U2
U2
U2
LP3-E5-277VC:9
LP3-E5-277VN:5
S1
S1
S1
S1 f h h h h f f f
L3
L3
L3
L3
L4
L4
L4
L4
H4 a
S6 h
H4 a a aH4 H4
S10 h
H4 a a H4
H4 a h
S10
H4 a
S10 h
H4
H4 H4 H4 a a a
PAT. RM #16
A316
TLT./SHWR
A316A
TLT./SHWR
A315A
BARIATRIC #15
A315
PAT. RM #14
A314
TLT./SHWR
A314A
BARIATRIC #13
A313
TLT./SHWR
A313A
KP
SV
KP
SV
KP
SV
KP
ST
HS
ST
H4 H4
H4 H4H4
HS
ST
ST
H4 H4
H4
H4
H4
H4
ST
H4 H4
H4
H4
HS
ST
H4
H4
H4 H4
ST
HS
ST
a a a
H4 e c,d c,d,e aa b f bf f a b a a b f f f a b b a a a c,d,e e c,d a a a b a a e c,d c,d,e f b f f b a a a aa c,d,e e c,d f b a a b f b f
SV
f
H4
H4 f f H4
U2
U2
U2
U2
LP3-E5-277VN:5
LP3-E5-277VC:7
S1
S1
S1
S1 f f f f h h h h
L3
L3
L3
L3
L4
L4
L4
L4
H4 H4 S10 h aa
H4 a
S6 h
H4 a H4 a
H4 a
H4 a
H4 H4
S10 h aa
S10 h
H4 aaH4
H4 a
H4 f
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EL432
ELECTRICAL ENLARGED LIGHTING
PLANS
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
1/4" = 1'-0" A
ENLARGED LIGHTING PLAN - SOUTHEAST PAT./BAR. ROOMS
1/4" = 1'-0"
B
ENLARGED LIGHTING PLAN - EAST PAT./BAR. ROOMS
1/4" = 1'-0" C
ENLARGED LIGHTING PLAN - NORTHEAST PAT./BAR. ROOMS
KEYED NOTES:
L3 CONNECT UNDERCABINET LIGHTING TO RECEPTACLE CIRCUIT SERVING
COUNTERTOP BELOW. MOUNT LIGHT SWITCH AT SAME HEIGHT AS
RECEPTACLES ABOVE COUNTERTOP. WHERE POSSIBLE, MOUNT
RECEPTACLE AND SWITCH IN SAME OUTLET BOX AND COVERPLATE.
L4 READING LIGHT PORTION OF FIXTURE TO BE LOCATED AT HEAD OF BED.
2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
2' 4' 8'0'
1/4" = 1'-0"
N N N
LAY-IN
LIGHT FIXTURE
SECURE FIXTURE
TO GRID (TYPICAL
OF 4 LOCATIONS)
J-BOX
EMT CONDUIT FOR
BRANCH CIRCUITING
CEILING GRID INSTALLED PER GRID
MANUFACTURER (TYPICAL). CEILING
INSTALLER SHALL PROVIDE
ADDITIONAL
GRID SUPPORT AT LIGHT FIXTURE
LOCATIONS AS RRQUIRED.
≤ 3'
≤ 3'
FLEX CONNECTION SIZE
AS REQUIRED - 3/8" MIN.
LENGTH SHALL ALLOW FIXTURE
TO BE RELOCATED 4'-0" IN
ANY DIRECTION.
ALL THREAD
J-BOX SUPPORT
CONDUIT SUPPORT (3'-0"
MAD. FROM J-BOX)
SUPPORT FLEX A MINIMUM OF
6" ABOVE CEILING GRID.
ALL THREAD OR SUPPORT WIRING TO
BUILDING STRUCTURE (TYPICAL).
SUPPORT WIRES SHALL BE SECURED TO
CEILING GRID AND SHALL NOT DEFORM
CEILING GRID INSTALLATION IN ANY
WAY. SUPPORT WIRES SHALL BE
MARKED TO IDENTIFY THEM AS
ELECTRICAL SUPPORT WIRES AND NOT
CEILING GRID SUPPORT WIRES
PER NEC SECTION 300.11.
NOTES:
1. ADDITIONAL LIGHT FIXTURE SUPPORT MAY BE REQUIRED
DUE TO POTENTIAL SEISMIC CONDITIONS, BUILDING
OCCUPANCY, AND FIXTURE TYPE. REFER TO THE
SPECIFICATIONS.
2. MOUNTING AND CONNECTION OF RECESSED CAN LIGHTS
SHALL UTILIZE BAR HANGERS SECURED TO GRID.
ALL THREAD OR SUPPORT WIRE
TO BUILDING STRUCTURE
(TYPICAL OF 4 CORNERS; FOR
ROUND LUMINAIRES, SPACE
SUPPORTS APPROXIMATELY
EQUIDISTANT AROUND).
3 TWIST MINIMUM (TYP)
CEILING MAIN BEAM
GYPSUM BOARD (TYP)
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
CEILING CROSS BEAM
GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE.
REFER TO
SCHEDULE
DRYWALL BORDER
LUMINAIRE
SUSPENSION WIRES (#
10 MIN) ATTACHED TO
STRUCTURE (TYP EA.
CORNER)
FIXTURE WHIP FROM
JUNCTION BOX (6FT.
LONG MAX.)
LUMINAIRE.
REFER TO
SCHEDULE
SEAL JOINT BETWEEN
CEILING AND LIGHTING
FIXTURE
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EL501
ELECTRICAL LIGHTING DETAILS
AND SCHEDULES
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
N0 SCALE
TYPICAL LAY-IN FIXTURE INSTALLATION
N0 SCALE
TYPICAL GYP LUMINAIRE
1. GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED
CEILING PER U.L. REQUIREMENTS. ELECTRICAL CONTRACTOR WILL COORDINATE.
2. MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT. CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY ADDENDUM DO SO AT
THEIR OWN RSK.
3. LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, PHOTOMETRICS.
4. ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBER
AND LIGHT FIXTURE.
5. LIGHT FIXTURES SHALL BE PROVIDED WITH 0-10V DIMMING DRIVERS. DRIVERS SHALL BE CAPABLE OF DIMMING TO A MINIMUM OF 10% TOTAL LIGHT OUTPUT. LED DRIVERS SHALL HAVE A DISCONNECTING MEANS MEETING THE REQUIREMENTS OF NEC SECTION 410.130(G), EXCEPT FOR THOSE INSTALLED IN CORD AND PLUG CONNECTED FIXTURES. WHERE APPLICABLE, WHEN DIMMING SWITCHES ARE NOT PROVIDED AS PART OF THE DESIGN, CONTRACTOR SHALL CAP OFF THE 0-10V DIMMING WIRES FOR FUTURE EXTENSION BY THE OWNER.
6. PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.
(1)(2)(3)(4)
LIGHTING FIXTURE SCHEDULE
(P.E.C.)
MARK DESCRIPTION
MANUFACTURER 1
CATALOG NUMBER
MANUFACTURER 2
CATALOG NUMBER
LIGHT SOURCE
LENS/LOUVER/FINISH
DIMENSIONS REF.
NOTE
REMARKS
# TYPE WATTS VOLTS W L D
D EXISTING FIXTURE TO BE DEMOLISHED
F4 4' STRIP COOPER 4SNLED-LD5-52SL-LC-UNV-L840-CD1-U OR EQUAL 1 LED 44 UNV ACRYLIC 0.3 4.0 0.17 5 5200LM; 4000K; 80CRI; PROVIDE WITH SUSPENDED MOUNTING ACCESSORIES
H4 4" RECESSED DOWNLIGHT LUMENPULSE
LCRS-A-FD-277-R-L30-40K-80-W-DA1-DB-NKS-RD-NKS-NC-1
OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI
H6 6" RECESSED DOWNLIGHT LUMENPULSE LACL-A-277-L30-40K-CR80-W-RD-NST-DA1-NC-NA OR EQUAL 1 LED 26 UNV SEMI-CLEAR 0.5 1.4 0.0 5 2500LM; 4000K; 80CRI
HS 4" RECESSED SHOWER LIGHT LUMENPULSE
LCRS-A-SH-277-R-L20-40K-80-M-DA1-DR-MWH-NC-1-NA
OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI
KA 2X2 LAY-IN CREE ZR22T-20L-40K-10V5 OR EQUAL 1 LED 18 UNV ACRYLIC 2.0 2.0 0.33 5 2000LM; 4000K; 80CRI
KB 2X2 LAY-IN CREE ZR22T-30L-840-10V5 OR EQUAL 1 LED 29 UNV ACRYLIC 2.0 2.0 0.33 5 3000LM; 4000K; 80CRI
KC 2X2 LAY-IN CREE ZR22T-40L-840-10V5 OR EQUAL 1 LED 39 UNV ACRYLIC 2.0 2.0 0.33 5 4000LM; 4000K; 80CRI
KP 2X2 OVERBED VISA LIGHTING CM1938-L40K-H-90-ORB/LVCP-DIM WITH RELAY OR EQUAL 1 LED 170 277 ACRYLIC 2.0 2.0 0.5 5 9400LM; 4000K; 90CRI
S1 PUCK LIGHT LIGHTHEADED 2-230-01-LED22-40 OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI
S3 6" SEMI RECESSED DOWNLIGHT ILLUMITECH
SGE5LEDOS-20L-40K-DS10-2-BH27-AR5223OS-SO-OGPY
OR EQUAL 1 LED 26 277 SEMI-CLEAR 0.5 1.4 0.0 5 2500LM; 4000K; 80CRI
S4 3" WALL WASH SLOT LUMENWERX VIA3R-WRO2-LED-90-375-40-10'6"-277-D1-1-DMF-W OR EQUAL 1 LED 38 UNV ACRYLIC 0.25 10.5 0.33 5 375LM/FT; 4000K; 90CRI
S5 WALL MOUNTED DOWNLIGHT LITHONIA WF4-LED-25K30K35K-90CRI-MW OR EQUAL 1 LED 10 UNV ACRYLIC 0.38 0.75 0.08 5 780 LUMENS; 90 CRI; 3500K
S6 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-11'6"-UNV-D1-1-DMF-W OR EQUAL 1 LED 150 UNV ACRYLIC 0.25 11.5 0.33 5 375LM/FT; 4000K; 90CRI
S7 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-9'6"-UNV-D1-1-DMF-W OR EQUAL 1 LED 124 UNV ACRYLIC 0.25 9.5 0.33 5 375LM/FT; 4000K; 90CRI
S8 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-8'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 104 UNV ACRYLIC 0.25 8.0 0.33 5 375LM/FT; 4000K; 90CRI
S9 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-7'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 91 UNV ACRYLIC 0.25 7.0 0.33 5 375LM/FT; 4000K; 90CRI
S10 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-14'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 182 UNV ACRYLIC 0.25 14.0 0.33 5 375LM/FT; 4000K; 90CRI
S11 RECESSED TAPE LIGHT WITH LENS FRY REGLET LED-RVL50100-4000K OR EQUAL 1 LED 50 UNV ACRYLIC 0.08 VAR 0.33 5 520LM/FT; 4000K; 90CRI. PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, MOUNTING ACCESSORIES, ETC FOR A COMPLETE AND FUNCTIONAL SYSTEM.
S12 TAPE LIGHT WITH LENS TEMPO ARCHITECTURE C3R-FL-0-3-40-LG-6; MOUNT:
C3A-MTGBRKT-SURF
OR EQUAL 1 LED 18 UNV ACRYLIC 0.08 6.0 0.33 5 3W/FT, 3500K, 80CRI; REFERENCE ARCHITECTURAL ELEVATIONS FOR MOUNTING. PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, MOUNTING ACCESSORIES, ETC FOR A COMPLETE AND FUNCTIONAL
SYSTEM.
ST STEP LIGHT FAIL-SAFE MSN-UNV-W OR EQUAL 1 LED 5 UNV WHITE 0.25 0.42 0.17 MOUNT IN SINGLE GANG JUNCTION BOX. MOUNT AT 18" AFF.
SV LINEAR VANITY SCONCE VISA LIGHTING CB5500-L40K-L-MVOLT OR EQUAL 1 LED 15 UNV PEARL BEIGE 0.88 2.0 0.42 MOUNT CENTERED ABOVE VANITY MIRROR. VERIFY EXACT HEIGHT WITH ARCHITECTURAL ELEVATIONS.
PROVIDE JUNCTION BOX MOUNTING.
U2 2' UNDER CABINET HALO HU30BSC24P OR EQUAL 1 LED 10 120 WHITE 0.38 2.0 0.08 PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, ETC. FOR A COMPLETE INSTALLATION.
U15 18" UNDER CABINET HALO HU30BCT18P OR EQUAL 1 LED 6 UNV ACRYLIC 0.38 1.5 0.08 5 499 LUMENS; 90 CRI; 3500K
W4 WALL PACK - TYPE IV LITHONIA ASW1-LED-42C-350-40K-SR4-MVOLT-DDBXD OR EQUAL 1 LED 49 UNV DARK BRONZE 1.15 1.25 0.77 4000LM; 4000K; 70CRI
X1 1 FACE/AC EXIT DUAL LITE LECSRNA OR EQUAL 1 LED 5 UNV CAST ALUMINUM 6 RED W/OUT BAT.
X2 2 FACE/AC EXIT DUAL LITE LECDRNA OR EQUAL 1 LED 5 UNV CAST ALUMINUM 6 RED W/OUT BAT.
F E
C
F E
C
FEC
FEC
F E
C
F E
C
F E
C
FEC
F E
C
FE
FE
F E
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL
BE ALLOWED.
EEaFGGaHJJbKLLaMNNa
11.5
12.5
13.5
HaJa
8.0 W 9.3
DPB-G12-208VN
DPB-H15-480VC
DPB-H14-480VQ
13.6
10.4
10.2
9.8
9.1
8.2
EF.1GH.5KLMMa
BASEMENT KEY PLAN
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EP101
ELECTRICAL POWER PLAN -
BASEMENT
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
N
1/8" = 1'-0" A
ELECTRICAL POWER PLAN - BASEMENT 4' 8' 16'
1/8" = 1'-0"
0'
J
J
J
T
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL
BE ALLOWED.
CORR.
C3A4
MEDS
A335
GEN. STOR.
A326
CLEAN
A336
SOILED
A337
CLEAN LINEN
A336A
NURSE
D314
ISO/BAR #1
A301
ISO/BAR #2
A302
ISO/BAR #3
A303
MEDS
A319
PAT. RM #22
D322
PAT. RM #21
D321
BARIATRIC #20
D320
ISO/BAR #19
D319
BARIATRIC #18
A318
PAT. RM #17
A317
PAT. RM #16
A316
BARIATRIC #15
A315
PAT. RM #14
A314
BARIATRIC #13
A313
TLT./SHWR
A313A
TLT./SHWR
A314A
TLT./SHWR
A315A
TLT./SHWR
A316A
TLT./SHWR
A317A
TLT./SHWR
A318A
TLT./SHWR
D319A
TLT./SHWR
D320A
TLT./SHWR
D321A
TLT./SHWR
D322A
NURSE
A328
TLT./SHWR
A302A
TLT./SHWR
A301A
ANTE
D319B
ANTE
A301B
ANTE
A302B ANTE
A303B
CORR.
C3A6
TLT.
A338
NOUR.
A324
NURSE MGR/ ASST MGR.
A325
NURSE WK/COPY
A329
SOILED
D342A
TLT./SHWR
A303A
PAT. RM #6
D306
TLT./SHWR
D306A
PAT. RM #8
D308
PAT. RM #10
D310
PAT. RM #12
D312
TLT./SHWR
D312A
TLT./SHWR
D310A
TLT./SHWR
D308A
EQUIP
D311
TLT./SHWR
D304A
PAT. RM #4
D304
STRETCHER
D303
EQUIP.
D305
STRETCHER
D309MED. GAS
D307
NOUR.
D313
MSA
D302
NURSE
A332
PAT. RM #11
A311
PAT. RM #9
A309
PAT. RM #7
A307
TLT./SHWR
A311A
TLT./SHWR
A309A
TLT./SHWR
A307A
CLEAN
A321
PAT. RM #5
A305
TLT./SHWR
A305A
CLEAN LINEN
A322
SOILED
A320
NURSE WK/COPY
A333
NOUR.
A334
CORR.
C3A2
CORR.
C3A3
CORR.
C3D4
STAIR #4
A346
EP431
A
EP431
B
EP431
D
EP432
D
EP432
E
STORAGE
D345
DIALYSIS
D342
CT
CT
CT
CT
CT
CT
CT
CT
CT
CT CT
CT
CT
CT
CT
CONSULT RM.
D344
CT
CT
CT
CT
CT
CT CT
CT
CT
HSKPG
A331
36"
ELEC./SYSTEMS
A330
EP432
C
IT
A306A
TV
CTPRINTER
ICE MAKER
CT
48"48"
A
E P
A
E P
SHADED AREA NOT IN SCOPE
UNLESS OTHERWISE NOTED
STORAGE
A327
84"
CT
LP3-E5-120VN2:69
LP3-E5-120VN2:61
LP3-E5-120VN2:63
LP3-E5-120VN2:65
LP3-E5-120VN2:67
UC FRIDGE
PRINTER
LP3-E5-120VN2:75
LP3-E5-120VN2:73LP3-E5-120VN2:71
LP3-E5-120VC:79
LP3-E5-120VC:81
BLANKET WARMER
84"
84"
IV SYRINGES
LP3-E5-120VC:80
LP3-E5-120VC:76LP3-E5-120VC:78
30"
LP3-E5-120VN2:64
CT
UC FRIDGE
84" 84"
PYXIS
LP3-E5-120VN2:66
LP3-H9-120VC:24
LP3-H9-120VC:26
LP3-E5-120VN2:68
PRINTER
P-TUBEP-TUBE
72"
48" 48"
CT
CT
CT
CT
CT
CT
BLANKET WARMER
CT
CT
CT
ICE MAKER
CT
CT
46"
84" 84"
LP3-E5-120VC:86
LP3-E5-120VC:84
LP3-E5-120VC:119
LP3-E5-120VC:97
LP3-E5-120VC:103
LP3-E5-120VC:105
LP3-E5-120VC:101
LP3-E5-120VC:99
LP3-E5-120VC:115
LP3-E5-120VC:117
LP3-E5-120VC:95
LP3-E5-120VC:93
LP3-E5-120VC:91
LP3-E5-120VC:87
LP3-E5-120VC:89
84"
84"
LP3-E5-120VN2:76
LP3-E5-120VN2:74
LP3-E5-120VN2:70
LP3-E5-120VN2:72
LP3-E5-120VN:71
48"
LP3-E5-120VN2:95
LP3-E5-120VN2:93
LP3-E5-120VN2:91
LP3-E5-120VN2:89
LP3-E5-120VN2:87
LP3-E5-120VN2:85
LP3-E5-120VN:79
LP3-E5-120VN:75
LP3-E5-120VN:81
LP3-E5-120VN:54
LP3-E5-120VN:52
LP3-E5-120VN:83
SHREDDER
42"
42"36" USB
LP3-H9-120VN:26
42"
36"
42"
36" 36"
42" 42"
36"
LP3-H9-120VN:34
LP3-H9-120VN:30
LP3-H9-120VN:32
TV
LP3-H9-120VC:20
LP3-H9-120VC:22
LP3-H9-120VC:18
LP3-H9-120VC:28
LP3-E5-120VN2:115
LP3-E5-120VN2:113
LP3-E5-120VN2:111
LP3-E5-120VN2:109
LP3-E5-120VN2:107
TM
P2
P2
P2
P2
P2
P2
P2
P2
CT CT
CT
CT
P1
P1 P1
P1
P1
LP3-E5-120VE:1
LP3-E5-120VE:3
SUPPLY TOWER
SUPPLY TOWER
BAS
LP3-E5-120VE:5
LP3-E5-120VN2:121
RATED WALL.
REFERENCE LIFE
SAFETY DRAWINGS.
(TYP)
P10
P10
P10
P9
P9
P9
P10
P10
P10
P10
P10
P10
P9 P9
P9 P9
P9 P9
P10
P10
P-TUBEP-TUBE
LP3-E5-120VC:108
LP3-E5-120VN:62
P1
LP3-E5-120VC:106
ACCP
NCCP
P1
SD
SD
SD
LP3-E5-120VE:7
SD SD
SD
LP3-E5-120VE:9
SD
SD SD
TV
TV
DIALYSIS STOR.
D342B
46" 46"
TV
TV
P11
LP3-E5-120VC:82
36"
36"
36"
36"
P1
48"
P11
46"
46"
46"
TV
46"
46"
46"
46"
LP3-E5-120VC:83
LP3-E5-120VC:83
LP3-E5-120VC:85
LP3-E5-120VC:98
LP3-E5-120VC:100
CORR.
C3A5
CORR.
C3D5
LP3-E5-120VC:102
84" 84"
EP432
A
LP3-E5-120VN:60
84"
84"
LP3-E5-120VN:64
LP3-E5-120VN:77
LP3-E5-120VN:66
LP3-E5-120VN:68
LP3-E5-120VE:11
LP3-E5-120VE:13
P12
LP3-E5-120VN2:62
PYXIS
SUPPLY TOWER
84" LP3-E5-120VN2:88
84"
LP3-E5-120VN2:90
84"
PD
PD
PD
PD
LP3-E5-120VE:15
LP3-E5-120VE:15
LP3-E5-120VE:17
PD
PD
LP3-E5-120VE:19
PD
PD
PD
PD
LP3-E5-120VE:21
LP3-E5-120VE:23
PD
PD
LP3-E5-120VE:25
LP3-E5-120VE:25
PD
LP3-E5-120VN2:92
P11
LP3-E5-120VE:35
P11
LP3-E5-120VE:2
P5
PTV
PTV
PTV
A
3RD FLOOR KEY PLAN - AREA A
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EP131
ELECTRICAL POWER PLAN - 3RD
FLOOR - AREA A
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
KEYED NOTES:
P1 WIREMOLD LEGRAND 2000 SERIES PLUGMOLD (OR APPROVED EQUAL) WITH
SIMPLEX RECEPTACLES 12” ON CENTER. MOUNT PLUGMOLD AT 44” AFF. ALL
RECEPTACLES SHALL BE NEMA 5-20 HOSPITAL GRADE.
P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.
P5 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR AUTOMATIC
SENSOR TRANSFORMER. PROVIDE LOW VOLTAGE CABLING IN CONDUIT
FROM TRANSFORMER TO SENSOR. VERIFY CONNECTION REQUIREMENTS
WITH EQUIPMENT SUPPLIER PRIOR TO INSTALLATION.
P9 INSTALL ALL DEVICES IN CASEWORK. PROVIDE RACEWAYS ROUTED IN
CASEWORK FOR CIRCUITING AS INDICATED. ROUTE CONDUITS THRU SLAB
TO CEILING PLENUM BELOW AND STUB UP AT NEAREST FULL HEIGHT WALL
LOCATION FOR ROUTING OF CONDUIT TO PANELBOARD.
P10 INSTALL RECEPTACLE HORIZONTALLY.
P11 JUNCTION BOX RECESSED IN WALL FOR CONNECTION TO MED GAS ALARM
PANEL. PROVIDE 1” CONDUIT FOR ALARM CABLING AS REQUIRED. ALL MED
GAS ALARM CABLING IS TO BE IN CONDUIT.
P12 CONNECT CONTROL PANELS TO LIFE SAFETY CIRCUIT. PROVIDE NORMAL
POWER RECEPTACLE LOCATED ABOVE PANEL CONNECTED TO THE CIRCUIT
INDICATED.
1/8" = 1'-0" A
ELECTRICAL POWER PLAN - 3RD FLOOR - AREA A
N
4' 8' 16'
1/8" = 1'-0"
T
T
T
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL
BE ALLOWED.
SOILED
D316
CLEAN
D317
PAT. RM #24
D324
PAT. RM #23
D323
PAT. RM #22
D322
TLT./SHWR
D322A
PT TLT.
D323A
TLT./SHWR
D324A
CORR.
C3D5
HSKPG
D326
TLT.
D318
ELEC
D338
CODER/REVIEW
D334
SWAMP #2
D332
STAFF LOUNGE
D343
SWAMP #3
D330
COPY
D336
TLT.
D341
CHG ROOM
D343B
SHARED OFFICE
D335
WAD
D339
OFFICE
D333
HOSPITALIST
D328
SWAMP #1
D331
SWAMP #4
D329
CORR.
C3D3
SOCIAL
D337
LOCKER
D343A
STAIR #5
D325
STAIR #6
D327
STAIR #2
D340
CORR.
C3C4
EX STOR. RM
C359
EP432
B
DIALYSIS
D342
CT
CT
UC FRIDGE
CT CT
CT
CT
CT
CTUC FRIDGE
UC FRIDGE CT
COPIER
CONSULT RM.
D344
CT
CT
CT
LP3-H9-120VN
LP3-H9-120VC
T3-H9-120VC
(SUSPENDED)
EP431
C
ELEC
C340
OIT
C358C
TV
PRINTER
COFFEE MAKER
MICROWAVE
60"
A
E P
A
E P
SHADED AREA NOT IN SCOPE
UNLESS OTHERWISE NOTED
CT
CT
46"
84" 84"
LP3-E5-120VC:86
LP3-E5-120VC:84
MEDS
D315
LP3-E5-120VN2:95
LP3-E5-120VN2:93
LP3-E5-120VN2:91
CT
BLANKET WARMER
84"
84"
CT CTUC FRIDGE
SHREDDER
LP3-E5-120VN2:97
LP3-E5-120VN2:99
LP3-E5-120VC:96
LP3-E5-120VC:94
LP3-E5-120VC:92
LP3-E5-120VC:90
#10
#10
#10
42"36"
TV
TV
UC FRIDGE
TV
TV
36"
UC FRIDGE
LP3-H9-120VN:1
LP3-H9-120VN:3
LP3-H9-120VN:7
LP3-H9-120VN:5
LP3-H9-120VN:9
LP3-H9-120VN:11
LP3-H9-120VN:13
LP3-H9-120VN:15
LP3-H9-120VN:17
LP3-H9-120VN:19
LP3-H9-120VN:21
LP3-H9-120VN:23LP3-H9-120VN:25
LP3-H9-120VN:27
LP3-H9-120VN:10
LP3-H9-120VN:12
LP3-H9-120VN:8
LP3-H9-120VN:6
LP3-H9-120VN:4
LP3-H9-120VN:2
LP3-H9-120VN:41
LP3-H9-120VN:39
LP3-H9-120VN:37
LP3-H9-120VN:35
LP3-H9-120VN:33
LP3-H9-120VN:31
LP3-H9-120VN:29
LP3-H9-120VC:1
LP3-H9-120VC:3
LP3-H9-120VC:5
LP3-H9-120VC:7
LP3-H9-120VC:11
LP3-H9-120VC:13
LP3-H9-120VC:17
LP3-H9-120VC:21
LP3-H9-120VC:23
LP3-H9-120VC:25
LP3-H9-120VC:27
LP3-H9-120VC:29
LP3-H9-120VC:31
LP3-H9-120VC:2
LP3-H9-120VC:4
LP3-H9-120VC:8
LP3-H9-120VC:10
LP3-H9-120VC:9
LP3-H9-120VC:15
LP3-H9-120VC:19
LP3-H9-120VC:33
LP3-H9-120VC:6
30"
FRIDGE
USB
LP3-H9-120VC:16
LP3-H9-120VC:14
PRINT/SCAN
CT
CT
LP3-H9-120VN:24
LP3-H9-120VN:22
LP3-H9-120VN:20
LP3-H9-120VN:18
LP3-H9-120VN:14
LP3-H9-120VN:16
LP3-H9-120VN:26
LP3-H9-120VN:28
42"
36"
42"
36" 36"
42" 42"
36"
LP3-H9-120VN:30
LP3-H9-120VN:32
LP3-H9-120VC:20
LP3-H9-120VC:18
CT
P2
P2
P2
P2
LP3-H9-120VC:12
EXISTING PANEL LP3-
G10-120VN RELOCATED
AND RENAMED
SUPPLY TOWER
CT CT
CT
CT
PYXIS
SUPPLY TOWER
RATED WALL.
REFERENCE LIFE
SAFETY DRAWINGS
(TYP).
P6
P6
P6
P6
P6
P6
P6
P6
P6
P6
P10
P10
LP3-E5-120VE:7
TV
LP3-E5-120VC:82
P1
SD
SD
SD
46"
46"
CORR.
C3D5
LP3-E5-120VC:104
#10
84"
84"LP3-E5-120VN2:101
LP3-E5-120VN2:103
#10
LP3-E5-120VN2:105
84"
84"
PD
PD
PD
PD
LP3-E5-120VE:27
LP3-E5-120VE:29
#10
#10
PD
PD
LP3-E5-120VE:31
PD
PD
LP3-E5-120VE:33
LP3-E5-120VE:33
CORR.
C3D4
#10
#10
P5
P5
P5
PTV
PTV
PTV
B
3RD FLOOR KEY PLAN - AREA B
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EP132
ELECTRICAL POWER PLAN - 3RD
FLOOR - AREA B
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
KEYED NOTES:
P1 WIREMOLD LEGRAND 2000 SERIES PLUGMOLD (OR APPROVED EQUAL) WITH
SIMPLEX RECEPTACLES 12” ON CENTER. MOUNT PLUGMOLD AT 44” AFF. ALL
RECEPTACLES SHALL BE NEMA 5-20 HOSPITAL GRADE.
P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.
P5 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR AUTOMATIC
SENSOR TRANSFORMER. PROVIDE LOW VOLTAGE CABLING IN CONDUIT
FROM TRANSFORMER TO SENSOR. VERIFY CONNECTION REQUIREMENTS
WITH EQUIPMENT SUPPLIER PRIOR TO INSTALLATION.
P6 COORDINATE FINAL DESK AND DEVICE LOCATIONS WITH COR PRIOR TO
INSTALLATION.
P10 INSTALL RECEPTACLE HORIZONTALLY.
1/8" = 1'-0" A
ELECTRICAL POWER PLAN - 3RD FLOOR - AREA B
N
4' 8' 16'
1/8" = 1'-0"
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL
BE ALLOWED.
WP
WP
WP
MOUNT ON UNIT (TYP)
(E) EF
(E) EF
(E) EF
(E) EF
(E) EF
LP3-E5-120VN2:117
WP
/2 EP141 /2 EP141
1-EF65
AHU-31
1-EF64
1-EF67
1-EF63
1-EF62
#10
WP
WP
MOUNT ON UNIT
(TYP)
(E) EF
(E) EF
(E) EF /1 EP141/1 EP141
1-EF66
1-EF65
4TH FLOOR/ROOF - KEY PLAN
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EP141
ELECTRICAL POWER PLAN - ROOF
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
1/8" = 1'-0"
ELECTRICAL POWER PLAN - ROOF - AREA A
1/8" = 1'-0"
ELECTRICAL POWER PLAN - ROOF - AREA B
N
4' 8' 16'
1/8" = 1'-0"
0'
N
4' 8' 16'
1/8" = 1'-0"
0'
PROVIDE LIGHTNING PROTECTION SYSTEM FOR WORK
DONE DURING THIS PROJECT IN ACCORDANCE WITH
SPECIFICATIONS AND NFPA 780. EXTEND AND CONNECT
TO EXISTING SYSTEM AS REQUIRED. INDICATE
PROPOSED SYSTEM IN REQUIRED SHOP DRAWINGS.
NOTE:
JT
JT
J J
J
J
J
J
J
JT
JT
JT
JT
J J
J
J
J
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL
BE ALLOWED.
TLT./SHWR
A305A
PAT. RM #5
A305
PAT. RM #7
A307
TLT./SHWR
A307A
TLT./SHWR
A309A
PAT. RM #9
A309
PAT. RM #11
A311
TLT./SHWR
A311A
HW
PTV PTV
HW
HW
PTV
HW
PTV
26"
26"
26"
26"
26"
26" 26"
26"
26"
26"
26"
26"
USB
USB
USB
USB
PL
PL PL
PL
BB
BB
BB
BB
CT
CT
CT
CT
CTCT
CT
CT
CT
CT
CT
CT
USBH
USBHUSBH
LP3-E5-120VN:31
LP3-E5-120VN:33
LP3-E5-120VN:39
LP3-E5-120VN:35,37
LP3-E5-120VC:25
LP3-E5-120VC:27
LP3-E5-120VC:29
LP3-E5-120VN:41
LP3-E5-120VC:31
LP3-E5-120VC:33
LP3-E5-120VN:43
LP3-E5-120VN:45,47
LP3-E5-120VN:49
LP3-E5-120VC:35
LP3-E5-120VN:51
LP3-E5-120VC:39
LP3-E5-120VC:37
LP3-E5-120VN:53
LP3-E5-120VN:55,57
LP3-E5-120VC:41
LP3-E5-120VN:59
LP3-E5-120VC:43
LP3-E5-120VN:61
LP3-E5-120VC:45
LP3-E5-120VN:63
LP3-E5-120VN:65,67
LP3-E5-120VN:69
LP3-E5-120VC:47
#6;1"C.
#6;1"C.
#6;1"C.#6;1"C.
USB
USB
USB
USBH
USB
CT
P2 P2
P2
P2
P3 P3 P3 P3
P7 P7
P7
P7
ANTE
A301B
TLT./SHWR
A301A
ISO/BAR #1
A301
ISO/BAR #2
A302
ANTE
A302B
TLT./SHWR
A302A ISO/BAR #3
A303
TLT./SHWR
A303A
ANTE
A303B
PTV
HW
HW
PTV
PTV
HW
24"
24"
24"
24"
24"
24"
24"
24"
24"
USB
USB
USB
PL
PL
PL
BB
BB
BB
CT
CT
CT CT
CT
CT
CT
CT
CT
DIALYSIS BOX
DIALYSIS BOX
DIALYSIS BOX
42"
42" 42"
CT
CT
DSK
DSK
DSK
60"
60"
LP3-E5-120VN:1
LP3-E5-120VN:3
LP3-E5-120VN:5,7
LP3-E5-120VN:9
LP3-E5-120VN:11
LP3-E5-120VN:13
LP3-E5-120VN:15,17
LP3-E5-120VN:19
LP3-E5-120VC:1
LP3-E5-120VC:5
LP3-E5-120VC:7
LP3-E5-120VC:9
LP3-E5-120VC:13
LP3-E5-120VC:15
LP3-E5-120VN:21
LP3-E5-120VN:23
LP3-E5-120VN:25,27
LP3-E5-120VN:29
LP3-E5-120VC:17
LP3-E5-120VC:21
LP3-E5-120VC:23
#6;1"C.
#6;1"C.
#6;1"C.
STORAGE
A327
USB
USBH
USB
CT
USBH
USBH
USB
CT
P2
P2
P2P3
P3
P3
P7
P7
LP3-E5-120VC:3
LP3-E5-120VC:11 LP3-E5-120VC:19
P7
60"
PAT. RM #4
D304
TLT./SHWR
D304A
PAT. RM #6
D306
TLT./SHWR
D306A TLT./SHWR
D308A
PAT. RM #8
D308 PAT. RM #10
D310
TLT./SHWR
D310A
PAT. RM #12
D312
TLT./SHWR
D312A
HW
26"
26"
26"
USB
PTV PTV
HW HW
PTV
HW
PTV
PTV
HW
USB
USB
USB
USB
26"
26"
26"
26"
26"
26"
26"
26"
26" 26"
26"
26"
BB BB BB
BB
BB
PL PL
PL PL
PL
CT
CT
CT CT
CT
CT
CT
CT
CT
CT
CT
CT
CT
CT
CT
USBH USBH USBH
LP3-E5-120VC:51
LP3-E5-120VN:10
LP3-E5-120VC:53
LP3-E5-120VN:4
LP3-E5-120VN:6,8
LP3-E5-120VC:49 LP3-E5-120VC:55
LP3-E5-120VC:57
LP3-E5-120VN:14
LP3-E5-120VN:16,18 LP3-E5-120VN:20
LP3-E5-120VC:59
LP3-E5-120VC:63
LP3-E5-120VC:65
LP3-E5-120VN:30
LP3-E5-120VN:26,28
LP3-E5-120VN:24
LP3-E5-120VC:61
LP3-E5-120VC:69
LP3-E5-120VC:67
LP3-E5-120VN:34
LP3-E5-120VN:36,38
LP3-E5-120VN:40
LP3-E5-120VC:71
LP3-E5-120VC:73
LP3-E5-120VN:42
LP3-E5-120VC:75
LP3-E5-120VN:50
LP3-E5-120VC:77
LP3-E5-120VN:44
LP3-E5-120VN:46,48
LP3-E5-120VN:2
LP3-E5-120VN:22
LP3-E5-120VN:32
LP3-E5-120VN:12
#6;1"C.
#6;1"C.
#6;1"C.
#6;1"C.#6;1"C.
CT
USBUSB
USB
USB
USB
USBH
USBH
P2
P2
P2
P2 P2
P3 P3 P3
P3 P3
P7 P7
P7
P7
P7
LP3-J9-120VN3
LP3-J9-277VNLP3-J9-120VN
LP3-J9-120VN2
LP3-J9-120VE
LP3-J9-277VE
LP3-J9-277VC
LP3-J9-120VC
LP3-J9-120VQ LP3-J9-277VQ
ELEC
C340
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
EP431
ELECTRICAL ENLARGED POWER
PLANS
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
TMGSMS
KEYED NOTES:
P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.
P3 COORDINATE LOCATION WITH ARCHITECTURAL PLANS AND ELEVATIONS.
P7 JUNCTION BOX FOR CONNECTION TO OWNER PROVIDED CLOCK. VERIFY
LOCATION WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION.
1/4" = 1'-0" A
ENLARGED POWER PLAN - NORTH PATIENT ROOMS
1/4" = 1'-0"
B
ENLARGED POWER PLAN - NORTHWEST ISO/BAR ROOMS
1/4" = 1'-0" D
ENLARGED POWER PLAN - SOUTH PATIENT ROOMS
2' 4' 8'0'
1/4" = 1'-0"
N
2' 4' 8'0'
1/4" = 1'-0"
N
2' 4' 8'0'
1/4" = 1'-0"
N
1/4" = 1'-0" C
ELECTRICAL POWER PLAN - ENLARGED ELEC C340
N
2' 4' 8'0'
1/4" = 1'-0"
J
F E
C
J
J
J
J
J
J
F E
C
J
J
J
J
J
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY…