This solicitation is for a federal contract opportunity to relocate a medical ward for patient privacy at a Veterans Affairs medical center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is seeking proposals to provide specifications and drawings as outlined in solicitation number 36c25522R0024 and file 589A4-21-100 SIGNED DRAWINGS R1_Part9.pdf. Offerors should submit responses with requirements for renovating and reconfiguring an existing medical ward space to enhance patient privacy, as well as any associated architectural, mechanical, electrical, or construction services defined in the solicitation documents. The response due date is not specified.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEC

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

W4

L5 BID ITEM #2

(REF. GI001)

96"

4TH FLOOR/ROOF - KEY PLAN

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EL141

ELECTRICAL LIGHTING PLAN - 4TH

FLOOR - AREA A

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

4' 8' 16'

1/8" = 1'-0"

0'

N

1/8" = 1'-0" A

ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A

# KEYED NOTES:

L5 CONNECT TO EXISTING NORMAL POWER LIGHTING CIRCUIT SERVING THIS

AREA.

08/04/2021

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

BID ITEM #2

(REF. GI001)

4TH FLOOR/ROOF - KEY PLAN

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EL141.2

ELECTRICAL LIGHTING PLAN - 4TH

FLOOR - AREA A - BID ITEM #2

(DEDUCT)

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

4' 8' 16'

1/8" = 1'-0"

0'

N

1/8" = 1'-0" A

ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A - BID ITEM #2 (DEDUCT)

JT

JT

JT

D D

D

D

D

D

D

D

D

D D

D

D

D

IR

D

D

D

D

D

D

M

M

M

DDD

JT

JT

JT

JT

DDDDD

D

D

D

D D

D

D D

D

D

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

PAT. RM #5

A305

TLT./SHWR

A305A

PAT. RM #7

A307

PAT. RM #9

A309

PAT. RM #11

A311

TLT./SHWR

A311ATLT./SHWR

A309A

TLT./SHWR

A307A

SV

KP

SV

KP KP

SV

KP

SV

ST

ST

ST

ST ST

ST

ST

ST

H4 H4

H4

H4

HSHS

H4

H4

H4

H4

H4H4

H4 H4

HSHS

H4 H4

H4 H4 ab b a c,d e c,d,e a a a h f f f b a b b a c,d,e a a a c,d e h f f f b a bb a a c,d,e c,d e a a h f b f f b ab e c,d c,d,e a a a a h f b f

H4 H4H4H4 a a a H4H4H4 f f f f f

U2 U2

U2

U2

S1 g g g gS1 S1 g g

LP3-E5-277VN:1

LP3-E5-277VC:3

H4 H4

H4

H4a a a a

S1 S1 S1 S1ff ff

L3 L3

L3

L3

L4

L4 L4 L4

H4 a a H4

S8 S8 S8 S8

H4 h h h h

H4 a a H4 H4

H4 a a

H4 a a

ISO/BAR #1

A301

TLT./SHWR

A301A

ANTE

A301B

ANTE

A302B

ISO/BAR #2

A302

TLT./SHWR

A302A

ISO/BAR #3

A303

ANTE

A303B

TLT./SHWR

A303A

KA

KP

KP

KA

SV

SV

KA

KP

HS

ST

H4

H4

H4

H4

ST

HS

ST

H4 H4

H4

H4

H4 H4

ST

ST

HS

ST

a b b f f f b e c,d c,d,e a a a a f b f f a a a b b e c,d a c,d,e a b f f b b a e c,d c,d,e aa f H4f f a H4

H4

SV

H4 f a H4

H4 a

U2

U2

U2

STORAGE

A327

LP3-E5-277VC:1

LP3-E5-277VN:1

f f f

S1

S1

S1 h h h

L3

L3

L3

L4

L4

L4

S6

S1

H4 H4aa a H4

H4 f

H4 a

S6 S7 hhh g g

H4 a

PAT. RM #4

D304

TLT./SHWR

D304A

TLT./SHWR

D306A

PAT. RM #6

D306

PAT. RM #8

D308

TLT./SHWR

D308A

PAT. RM #10

D310

TLT./SHWR

D310A

PAT. RM #12

D312

TLT./SHWR

D312A

HS

ST

SV

H4 H4

KP

H4H4 ST

HS

ST

SV

H4

H4

ST

H4

KP

H4

HS

ST

SV

KP

H4

H4 H4

H4

ST

KP

ST

H4 H4

H4 H4

SV

ST

HSHS

ST

SV

KP

ST

f b f f h c,d,e c,d e b b a a b b a a e c,d c,d,e aa f b f f f b f f h a a a c,d,e ac,d e b b a f b f f h a c,d,e a a a c,d e b b a f b ff a a a c,d,e a e c,d b a b f a a a a

H4

H4

H4

H4

H4

H4

H4 a a

H4 a f H4 H4 a a a a a f ff

H4

H4

H4 H4

H4 H4

H4

U2U2U2U2

S1 g g g g

S1

U2

S1 g g g g

S1

LP3-E5-277VN:3

LP3-E5-277VC:5

S1 S1S1 S1

S1f f f f f aa H4 H4

L3

L3

L3

L3L3

L4 L4 L4 L4 L4 h

S9 h

H4 a a H4 h

S8

S8 h h

S8 h

H4 a

H4 a

S8 h

H4 a aH4

H4 a

H4 a a aH4

H4

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EL431

ELECTRICAL ENLARGED LIGHTING

PLANS

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

KEYED NOTES:

L3 CONNECT UNDERCABINET LIGHTING TO RECEPTACLE CIRCUIT SERVING

COUNTERTOP BELOW. MOUNT LIGHT SWITCH AT SAME HEIGHT AS

RECEPTACLES ABOVE COUNTERTOP. WHERE POSSIBLE, MOUNT

RECEPTACLE AND SWITCH IN SAME OUTLET BOX AND COVERPLATE.

L4 READING LIGHT PORTION OF FIXTURE TO BE LOCATED AT HEAD OF BED.

1/4" = 1'-0" A

ENLARGED LIGHTING PLAN - NORTH PATIENT ROOMS

1/4" = 1'-0"

B

ENLARGED LIGHTING PLAN - NORTHWEST ISO/BAR ROOMS

1/4" = 1'-0" C

ENLARGED LIGHTING PLAN - SOUTH PATIENT ROOMS 2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

NN

N

F E

C

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

F E

C

D

D

D

D

D

D

D

D

D

D

D

D

PAT. RM #24

D324

TLT./SHWR

D324A

PT TLT.

D323A

PAT. RM #23

D323

PAT. RM #22

D322

TLT./SHWR

D322A

PAT. RM #21

D321

TLT./SHWR

D321A

KP

SV

ST

ST

H4 H4

H4

H4

HS

KP

SVST

ST

HS

ST

KP

HS

ST

SV

SV

ST

HS

ST

KP

b b a a a aa c,d,e c,de f f b f f ff b b a b e c,d c,d,e a b c,d,e e c,d b f bf f a b e c,d c,d,e b f b f f

H4

H4 a f a a a aa

H4

H4

H4

H4 H4

H4 H4 H4

H4 H4 a a a aa f

H4 a a a a a

H4 H4

H4

H4H4

H4 f

H4 a

U2

U2

U2

U2

S1 g g

LP3-E5-277VN:5

LP3-E5-277VC:11

S1

S1

S1

S1 h f f f f

L3

L3

L3

L3 h h

L4

L4

L4

L4

S10 h h S6

H4

H4 H4 a a a

H4 a

H4 H4 aa

H4 H4 a a a H4

S7 h

H4 H4a a h S10

PAT. RM #17

A317

TLT./SHWR

A317A

BARIATRIC #18

A318

TLT./SHWR

A318A

ISO/BAR #19

D319

TLT./SHWR

D319A

ANTE

D319B

BARIATRIC #20

D320

TLT./SHWR

D320A

KP

SV

KP

SV

KA

KP

SV

KP

SV

H4 H4

H4 H4

HS

ST

ST

H4 H4

ST

H4 H4HS

ST

HS

ST

ST

H4

H4

ST

H4 H4

H4

H4HS

ST

b f f b b a e c,d c,d,e aa a a c,d,e e c,d a b f f b f a a b e c,d c,d,e a a b a a a b f b f b f b a f b e c,d c,d,e a a aa a a a

H4

H4

H4 f f f

H4f f

H4

H4 f f

H4

U2

U2

U2

U2

LP3-E5-277VC:9

LP3-E5-277VN:5

S1

S1

S1

S1 f h h h h f f f

L3

L3

L3

L3

L4

L4

L4

L4

H4 a

S6 h

H4 a a aH4 H4

S10 h

H4 a a H4

H4 a h

S10

H4 a

S10 h

H4

H4 H4 H4 a a a

PAT. RM #16

A316

TLT./SHWR

A316A

TLT./SHWR

A315A

BARIATRIC #15

A315

PAT. RM #14

A314

TLT./SHWR

A314A

BARIATRIC #13

A313

TLT./SHWR

A313A

KP

SV

KP

SV

KP

SV

KP

ST

HS

ST

H4 H4

H4 H4H4

HS

ST

ST

H4 H4

H4

H4

H4

H4

ST

H4 H4

H4

H4

HS

ST

H4

H4

H4 H4

ST

HS

ST

a a a

H4 e c,d c,d,e aa b f bf f a b a a b f f f a b b a a a c,d,e e c,d a a a b a a e c,d c,d,e f b f f b a a a aa c,d,e e c,d f b a a b f b f

SV

f

H4

H4 f f H4

U2

U2

U2

U2

LP3-E5-277VN:5

LP3-E5-277VC:7

S1

S1

S1

S1 f f f f h h h h

L3

L3

L3

L3

L4

L4

L4

L4

H4 H4 S10 h aa

H4 a

S6 h

H4 a H4 a

H4 a

H4 a

H4 H4

S10 h aa

S10 h

H4 aaH4

H4 a

H4 f

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EL432

ELECTRICAL ENLARGED LIGHTING

PLANS

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

1/4" = 1'-0" A

ENLARGED LIGHTING PLAN - SOUTHEAST PAT./BAR. ROOMS

1/4" = 1'-0"

B

ENLARGED LIGHTING PLAN - EAST PAT./BAR. ROOMS

1/4" = 1'-0" C

ENLARGED LIGHTING PLAN - NORTHEAST PAT./BAR. ROOMS

KEYED NOTES:

L3 CONNECT UNDERCABINET LIGHTING TO RECEPTACLE CIRCUIT SERVING

COUNTERTOP BELOW. MOUNT LIGHT SWITCH AT SAME HEIGHT AS

RECEPTACLES ABOVE COUNTERTOP. WHERE POSSIBLE, MOUNT

RECEPTACLE AND SWITCH IN SAME OUTLET BOX AND COVERPLATE.

L4 READING LIGHT PORTION OF FIXTURE TO BE LOCATED AT HEAD OF BED.

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

2' 4' 8'0'

1/4" = 1'-0"

N N N

LAY-IN

LIGHT FIXTURE

SECURE FIXTURE

TO GRID (TYPICAL

OF 4 LOCATIONS)

J-BOX

EMT CONDUIT FOR

BRANCH CIRCUITING

CEILING GRID INSTALLED PER GRID

MANUFACTURER (TYPICAL). CEILING

INSTALLER SHALL PROVIDE

ADDITIONAL

GRID SUPPORT AT LIGHT FIXTURE

LOCATIONS AS RRQUIRED.

≤ 3'

≤ 3'

FLEX CONNECTION SIZE

AS REQUIRED - 3/8" MIN.

LENGTH SHALL ALLOW FIXTURE

TO BE RELOCATED 4'-0" IN

ANY DIRECTION.

ALL THREAD

J-BOX SUPPORT

CONDUIT SUPPORT (3'-0"

MAD. FROM J-BOX)

SUPPORT FLEX A MINIMUM OF

6" ABOVE CEILING GRID.

ALL THREAD OR SUPPORT WIRING TO

BUILDING STRUCTURE (TYPICAL).

SUPPORT WIRES SHALL BE SECURED TO

CEILING GRID AND SHALL NOT DEFORM

CEILING GRID INSTALLATION IN ANY

WAY. SUPPORT WIRES SHALL BE

MARKED TO IDENTIFY THEM AS

ELECTRICAL SUPPORT WIRES AND NOT

CEILING GRID SUPPORT WIRES

PER NEC SECTION 300.11.

NOTES:

1. ADDITIONAL LIGHT FIXTURE SUPPORT MAY BE REQUIRED

DUE TO POTENTIAL SEISMIC CONDITIONS, BUILDING

OCCUPANCY, AND FIXTURE TYPE. REFER TO THE

SPECIFICATIONS.

2. MOUNTING AND CONNECTION OF RECESSED CAN LIGHTS

SHALL UTILIZE BAR HANGERS SECURED TO GRID.

ALL THREAD OR SUPPORT WIRE

TO BUILDING STRUCTURE

(TYPICAL OF 4 CORNERS; FOR

ROUND LUMINAIRES, SPACE

SUPPORTS APPROXIMATELY

EQUIDISTANT AROUND).

3 TWIST MINIMUM (TYP)

CEILING MAIN BEAM

GYPSUM BOARD (TYP)

LUMINAIRE MANUFACTURER'S

EARTHQUAKE CLIP, (4) PER

FIXTURE AT CORNERS. ATTACH

WITH SHEET METAL SCREW

CEILING CROSS BEAM

GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE.

REFER TO

SCHEDULE

DRYWALL BORDER

LUMINAIRE

SUSPENSION WIRES (#

10 MIN) ATTACHED TO

STRUCTURE (TYP EA.

CORNER)

FIXTURE WHIP FROM

JUNCTION BOX (6FT.

LONG MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

SEAL JOINT BETWEEN

CEILING AND LIGHTING

FIXTURE

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EL501

ELECTRICAL LIGHTING DETAILS

AND SCHEDULES

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

N0 SCALE

TYPICAL LAY-IN FIXTURE INSTALLATION

N0 SCALE

TYPICAL GYP LUMINAIRE

1. GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED

CEILING PER U.L. REQUIREMENTS. ELECTRICAL CONTRACTOR WILL COORDINATE.

2. MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT. CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY ADDENDUM DO SO AT

THEIR OWN RSK.

3. LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, PHOTOMETRICS.

4. ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBER

AND LIGHT FIXTURE.

5. LIGHT FIXTURES SHALL BE PROVIDED WITH 0-10V DIMMING DRIVERS. DRIVERS SHALL BE CAPABLE OF DIMMING TO A MINIMUM OF 10% TOTAL LIGHT OUTPUT. LED DRIVERS SHALL HAVE A DISCONNECTING MEANS MEETING THE REQUIREMENTS OF NEC SECTION 410.130(G), EXCEPT FOR THOSE INSTALLED IN CORD AND PLUG CONNECTED FIXTURES. WHERE APPLICABLE, WHEN DIMMING SWITCHES ARE NOT PROVIDED AS PART OF THE DESIGN, CONTRACTOR SHALL CAP OFF THE 0-10V DIMMING WIRES FOR FUTURE EXTENSION BY THE OWNER.

6. PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.

(1)(2)(3)(4)

LIGHTING FIXTURE SCHEDULE

(P.E.C.)

MARK DESCRIPTION

MANUFACTURER 1

CATALOG NUMBER

MANUFACTURER 2

CATALOG NUMBER

LIGHT SOURCE

LENS/LOUVER/FINISH

DIMENSIONS REF.

NOTE

REMARKS

# TYPE WATTS VOLTS W L D

D EXISTING FIXTURE TO BE DEMOLISHED

F4 4' STRIP COOPER 4SNLED-LD5-52SL-LC-UNV-L840-CD1-U OR EQUAL 1 LED 44 UNV ACRYLIC 0.3 4.0 0.17 5 5200LM; 4000K; 80CRI; PROVIDE WITH SUSPENDED MOUNTING ACCESSORIES

H4 4" RECESSED DOWNLIGHT LUMENPULSE

LCRS-A-FD-277-R-L30-40K-80-W-DA1-DB-NKS-RD-NKS-NC-1

OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI

H6 6" RECESSED DOWNLIGHT LUMENPULSE LACL-A-277-L30-40K-CR80-W-RD-NST-DA1-NC-NA OR EQUAL 1 LED 26 UNV SEMI-CLEAR 0.5 1.4 0.0 5 2500LM; 4000K; 80CRI

HS 4" RECESSED SHOWER LIGHT LUMENPULSE

LCRS-A-SH-277-R-L20-40K-80-M-DA1-DR-MWH-NC-1-NA

OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI

KA 2X2 LAY-IN CREE ZR22T-20L-40K-10V5 OR EQUAL 1 LED 18 UNV ACRYLIC 2.0 2.0 0.33 5 2000LM; 4000K; 80CRI

KB 2X2 LAY-IN CREE ZR22T-30L-840-10V5 OR EQUAL 1 LED 29 UNV ACRYLIC 2.0 2.0 0.33 5 3000LM; 4000K; 80CRI

KC 2X2 LAY-IN CREE ZR22T-40L-840-10V5 OR EQUAL 1 LED 39 UNV ACRYLIC 2.0 2.0 0.33 5 4000LM; 4000K; 80CRI

KP 2X2 OVERBED VISA LIGHTING CM1938-L40K-H-90-ORB/LVCP-DIM WITH RELAY OR EQUAL 1 LED 170 277 ACRYLIC 2.0 2.0 0.5 5 9400LM; 4000K; 90CRI

S1 PUCK LIGHT LIGHTHEADED 2-230-01-LED22-40 OR EQUAL 1 LED 23 UNV SEMI-CLEAR 0.3 1.4 0.0 5 2000LM; 4000K; 80CRI

S3 6" SEMI RECESSED DOWNLIGHT ILLUMITECH

SGE5LEDOS-20L-40K-DS10-2-BH27-AR5223OS-SO-OGPY

OR EQUAL 1 LED 26 277 SEMI-CLEAR 0.5 1.4 0.0 5 2500LM; 4000K; 80CRI

S4 3" WALL WASH SLOT LUMENWERX VIA3R-WRO2-LED-90-375-40-10'6"-277-D1-1-DMF-W OR EQUAL 1 LED 38 UNV ACRYLIC 0.25 10.5 0.33 5 375LM/FT; 4000K; 90CRI

S5 WALL MOUNTED DOWNLIGHT LITHONIA WF4-LED-25K30K35K-90CRI-MW OR EQUAL 1 LED 10 UNV ACRYLIC 0.38 0.75 0.08 5 780 LUMENS; 90 CRI; 3500K

S6 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-11'6"-UNV-D1-1-DMF-W OR EQUAL 1 LED 150 UNV ACRYLIC 0.25 11.5 0.33 5 375LM/FT; 4000K; 90CRI

S7 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-9'6"-UNV-D1-1-DMF-W OR EQUAL 1 LED 124 UNV ACRYLIC 0.25 9.5 0.33 5 375LM/FT; 4000K; 90CRI

S8 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-8'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 104 UNV ACRYLIC 0.25 8.0 0.33 5 375LM/FT; 4000K; 90CRI

S9 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-7'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 91 UNV ACRYLIC 0.25 7.0 0.33 5 375LM/FT; 4000K; 90CRI

S10 3" SLOT LUMENWERX VIA3R-HLO-LED-90-350-40-14'0"-UNV-D1-1-DMF-W OR EQUAL 1 LED 182 UNV ACRYLIC 0.25 14.0 0.33 5 375LM/FT; 4000K; 90CRI

S11 RECESSED TAPE LIGHT WITH LENS FRY REGLET LED-RVL50100-4000K OR EQUAL 1 LED 50 UNV ACRYLIC 0.08 VAR 0.33 5 520LM/FT; 4000K; 90CRI. PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, MOUNTING ACCESSORIES, ETC FOR A COMPLETE AND FUNCTIONAL SYSTEM.

S12 TAPE LIGHT WITH LENS TEMPO ARCHITECTURE C3R-FL-0-3-40-LG-6; MOUNT:

C3A-MTGBRKT-SURF

OR EQUAL 1 LED 18 UNV ACRYLIC 0.08 6.0 0.33 5 3W/FT, 3500K, 80CRI; REFERENCE ARCHITECTURAL ELEVATIONS FOR MOUNTING. PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, MOUNTING ACCESSORIES, ETC FOR A COMPLETE AND FUNCTIONAL

SYSTEM.

ST STEP LIGHT FAIL-SAFE MSN-UNV-W OR EQUAL 1 LED 5 UNV WHITE 0.25 0.42 0.17 MOUNT IN SINGLE GANG JUNCTION BOX. MOUNT AT 18" AFF.

SV LINEAR VANITY SCONCE VISA LIGHTING CB5500-L40K-L-MVOLT OR EQUAL 1 LED 15 UNV PEARL BEIGE 0.88 2.0 0.42 MOUNT CENTERED ABOVE VANITY MIRROR. VERIFY EXACT HEIGHT WITH ARCHITECTURAL ELEVATIONS.

PROVIDE JUNCTION BOX MOUNTING.

U2 2' UNDER CABINET HALO HU30BSC24P OR EQUAL 1 LED 10 120 WHITE 0.38 2.0 0.08 PROVIDE WITH POWER SUPPLY, CONNECTORS, END CAPS, ETC. FOR A COMPLETE INSTALLATION.

U15 18" UNDER CABINET HALO HU30BCT18P OR EQUAL 1 LED 6 UNV ACRYLIC 0.38 1.5 0.08 5 499 LUMENS; 90 CRI; 3500K

W4 WALL PACK - TYPE IV LITHONIA ASW1-LED-42C-350-40K-SR4-MVOLT-DDBXD OR EQUAL 1 LED 49 UNV DARK BRONZE 1.15 1.25 0.77 4000LM; 4000K; 70CRI

X1 1 FACE/AC EXIT DUAL LITE LECSRNA OR EQUAL 1 LED 5 UNV CAST ALUMINUM 6 RED W/OUT BAT.

X2 2 FACE/AC EXIT DUAL LITE LECDRNA OR EQUAL 1 LED 5 UNV CAST ALUMINUM 6 RED W/OUT BAT.

F E

C

F E

C

FEC

FEC

F E

C

F E

C

F E

C

FEC

F E

C

FE

FE

F E

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL

BE ALLOWED.

EEaFGGaHJJbKLLaMNNa

11.5

12.5

13.5

HaJa

8.0 W 9.3

DPB-G12-208VN

DPB-H15-480VC

DPB-H14-480VQ

13.6

10.4

10.2

9.8

9.1

8.2

EF.1GH.5KLMMa

BASEMENT KEY PLAN

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EP101

ELECTRICAL POWER PLAN -

BASEMENT

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

N

1/8" = 1'-0" A

ELECTRICAL POWER PLAN - BASEMENT 4' 8' 16'

1/8" = 1'-0"

0'

J

J

J

T

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL

BE ALLOWED.

CORR.

C3A4

MEDS

A335

GEN. STOR.

A326

CLEAN

A336

SOILED

A337

CLEAN LINEN

A336A

NURSE

D314

ISO/BAR #1

A301

ISO/BAR #2

A302

ISO/BAR #3

A303

MEDS

A319

PAT. RM #22

D322

PAT. RM #21

D321

BARIATRIC #20

D320

ISO/BAR #19

D319

BARIATRIC #18

A318

PAT. RM #17

A317

PAT. RM #16

A316

BARIATRIC #15

A315

PAT. RM #14

A314

BARIATRIC #13

A313

TLT./SHWR

A313A

TLT./SHWR

A314A

TLT./SHWR

A315A

TLT./SHWR

A316A

TLT./SHWR

A317A

TLT./SHWR

A318A

TLT./SHWR

D319A

TLT./SHWR

D320A

TLT./SHWR

D321A

TLT./SHWR

D322A

NURSE

A328

TLT./SHWR

A302A

TLT./SHWR

A301A

ANTE

D319B

ANTE

A301B

ANTE

A302B ANTE

A303B

CORR.

C3A6

TLT.

A338

NOUR.

A324

NURSE MGR/ ASST MGR.

A325

NURSE WK/COPY

A329

SOILED

D342A

TLT./SHWR

A303A

PAT. RM #6

D306

TLT./SHWR

D306A

PAT. RM #8

D308

PAT. RM #10

D310

PAT. RM #12

D312

TLT./SHWR

D312A

TLT./SHWR

D310A

TLT./SHWR

D308A

EQUIP

D311

TLT./SHWR

D304A

PAT. RM #4

D304

STRETCHER

D303

EQUIP.

D305

STRETCHER

D309MED. GAS

D307

NOUR.

D313

MSA

D302

NURSE

A332

PAT. RM #11

A311

PAT. RM #9

A309

PAT. RM #7

A307

TLT./SHWR

A311A

TLT./SHWR

A309A

TLT./SHWR

A307A

CLEAN

A321

PAT. RM #5

A305

TLT./SHWR

A305A

CLEAN LINEN

A322

SOILED

A320

NURSE WK/COPY

A333

NOUR.

A334

CORR.

C3A2

CORR.

C3A3

CORR.

C3D4

STAIR #4

A346

EP431

A

EP431

B

EP431

D

EP432

D

EP432

E

STORAGE

D345

DIALYSIS

D342

CT

CT

CT

CT

CT

CT

CT

CT

CT

CT CT

CT

CT

CT

CT

CONSULT RM.

D344

CT

CT

CT

CT

CT

CT CT

CT

CT

HSKPG

A331

36"

ELEC./SYSTEMS

A330

EP432

C

IT

A306A

TV

CTPRINTER

ICE MAKER

CT

48"48"

A

E P

A

E P

SHADED AREA NOT IN SCOPE

UNLESS OTHERWISE NOTED

STORAGE

A327

84"

CT

LP3-E5-120VN2:69

LP3-E5-120VN2:61

LP3-E5-120VN2:63

LP3-E5-120VN2:65

LP3-E5-120VN2:67

UC FRIDGE

PRINTER

LP3-E5-120VN2:75

LP3-E5-120VN2:73LP3-E5-120VN2:71

LP3-E5-120VC:79

LP3-E5-120VC:81

BLANKET WARMER

84"

84"

IV SYRINGES

LP3-E5-120VC:80

LP3-E5-120VC:76LP3-E5-120VC:78

30"

LP3-E5-120VN2:64

CT

UC FRIDGE

84" 84"

PYXIS

LP3-E5-120VN2:66

LP3-H9-120VC:24

LP3-H9-120VC:26

LP3-E5-120VN2:68

PRINTER

P-TUBEP-TUBE

72"

48" 48"

CT

CT

CT

CT

CT

CT

BLANKET WARMER

CT

CT

CT

ICE MAKER

CT

CT

46"

84" 84"

LP3-E5-120VC:86

LP3-E5-120VC:84

LP3-E5-120VC:119

LP3-E5-120VC:97

LP3-E5-120VC:103

LP3-E5-120VC:105

LP3-E5-120VC:101

LP3-E5-120VC:99

LP3-E5-120VC:115

LP3-E5-120VC:117

LP3-E5-120VC:95

LP3-E5-120VC:93

LP3-E5-120VC:91

LP3-E5-120VC:87

LP3-E5-120VC:89

84"

84"

LP3-E5-120VN2:76

LP3-E5-120VN2:74

LP3-E5-120VN2:70

LP3-E5-120VN2:72

LP3-E5-120VN:71

48"

LP3-E5-120VN2:95

LP3-E5-120VN2:93

LP3-E5-120VN2:91

LP3-E5-120VN2:89

LP3-E5-120VN2:87

LP3-E5-120VN2:85

LP3-E5-120VN:79

LP3-E5-120VN:75

LP3-E5-120VN:81

LP3-E5-120VN:54

LP3-E5-120VN:52

LP3-E5-120VN:83

SHREDDER

42"

42"36" USB

LP3-H9-120VN:26

42"

36"

42"

36" 36"

42" 42"

36"

LP3-H9-120VN:34

LP3-H9-120VN:30

LP3-H9-120VN:32

TV

LP3-H9-120VC:20

LP3-H9-120VC:22

LP3-H9-120VC:18

LP3-H9-120VC:28

LP3-E5-120VN2:115

LP3-E5-120VN2:113

LP3-E5-120VN2:111

LP3-E5-120VN2:109

LP3-E5-120VN2:107

TM

P2

P2

P2

P2

P2

P2

P2

P2

CT CT

CT

CT

P1

P1 P1

P1

P1

LP3-E5-120VE:1

LP3-E5-120VE:3

SUPPLY TOWER

SUPPLY TOWER

BAS

LP3-E5-120VE:5

LP3-E5-120VN2:121

RATED WALL.

REFERENCE LIFE

SAFETY DRAWINGS.

(TYP)

P10

P10

P10

P9

P9

P9

P10

P10

P10

P10

P10

P10

P9 P9

P9 P9

P9 P9

P10

P10

P-TUBEP-TUBE

LP3-E5-120VC:108

LP3-E5-120VN:62

P1

LP3-E5-120VC:106

ACCP

NCCP

P1

SD

SD

SD

LP3-E5-120VE:7

SD SD

SD

LP3-E5-120VE:9

SD

SD SD

TV

TV

DIALYSIS STOR.

D342B

46" 46"

TV

TV

P11

LP3-E5-120VC:82

36"

36"

36"

36"

P1

48"

P11

46"

46"

46"

TV

46"

46"

46"

46"

LP3-E5-120VC:83

LP3-E5-120VC:83

LP3-E5-120VC:85

LP3-E5-120VC:98

LP3-E5-120VC:100

CORR.

C3A5

CORR.

C3D5

LP3-E5-120VC:102

84" 84"

EP432

A

LP3-E5-120VN:60

84"

84"

LP3-E5-120VN:64

LP3-E5-120VN:77

LP3-E5-120VN:66

LP3-E5-120VN:68

LP3-E5-120VE:11

LP3-E5-120VE:13

P12

LP3-E5-120VN2:62

PYXIS

SUPPLY TOWER

84" LP3-E5-120VN2:88

84"

LP3-E5-120VN2:90

84"

PD

PD

PD

PD

LP3-E5-120VE:15

LP3-E5-120VE:15

LP3-E5-120VE:17

PD

PD

LP3-E5-120VE:19

PD

PD

PD

PD

LP3-E5-120VE:21

LP3-E5-120VE:23

PD

PD

LP3-E5-120VE:25

LP3-E5-120VE:25

PD

LP3-E5-120VN2:92

P11

LP3-E5-120VE:35

P11

LP3-E5-120VE:2

P5

PTV

PTV

PTV

A

3RD FLOOR KEY PLAN - AREA A

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EP131

ELECTRICAL POWER PLAN - 3RD

FLOOR - AREA A

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

KEYED NOTES:

P1 WIREMOLD LEGRAND 2000 SERIES PLUGMOLD (OR APPROVED EQUAL) WITH

SIMPLEX RECEPTACLES 12” ON CENTER. MOUNT PLUGMOLD AT 44” AFF. ALL

RECEPTACLES SHALL BE NEMA 5-20 HOSPITAL GRADE.

P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.

P5 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR AUTOMATIC

SENSOR TRANSFORMER. PROVIDE LOW VOLTAGE CABLING IN CONDUIT

FROM TRANSFORMER TO SENSOR. VERIFY CONNECTION REQUIREMENTS

WITH EQUIPMENT SUPPLIER PRIOR TO INSTALLATION.

P9 INSTALL ALL DEVICES IN CASEWORK. PROVIDE RACEWAYS ROUTED IN

CASEWORK FOR CIRCUITING AS INDICATED. ROUTE CONDUITS THRU SLAB

TO CEILING PLENUM BELOW AND STUB UP AT NEAREST FULL HEIGHT WALL

LOCATION FOR ROUTING OF CONDUIT TO PANELBOARD.

P10 INSTALL RECEPTACLE HORIZONTALLY.

P11 JUNCTION BOX RECESSED IN WALL FOR CONNECTION TO MED GAS ALARM

PANEL. PROVIDE 1” CONDUIT FOR ALARM CABLING AS REQUIRED. ALL MED

GAS ALARM CABLING IS TO BE IN CONDUIT.

P12 CONNECT CONTROL PANELS TO LIFE SAFETY CIRCUIT. PROVIDE NORMAL

POWER RECEPTACLE LOCATED ABOVE PANEL CONNECTED TO THE CIRCUIT

INDICATED.

1/8" = 1'-0" A

ELECTRICAL POWER PLAN - 3RD FLOOR - AREA A

N

4' 8' 16'

1/8" = 1'-0"

T

T

T

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL

BE ALLOWED.

SOILED

D316

CLEAN

D317

PAT. RM #24

D324

PAT. RM #23

D323

PAT. RM #22

D322

TLT./SHWR

D322A

PT TLT.

D323A

TLT./SHWR

D324A

CORR.

C3D5

HSKPG

D326

TLT.

D318

ELEC

D338

CODER/REVIEW

D334

SWAMP #2

D332

STAFF LOUNGE

D343

SWAMP #3

D330

COPY

D336

TLT.

D341

CHG ROOM

D343B

SHARED OFFICE

D335

WAD

D339

OFFICE

D333

HOSPITALIST

D328

SWAMP #1

D331

SWAMP #4

D329

CORR.

C3D3

SOCIAL

D337

LOCKER

D343A

STAIR #5

D325

STAIR #6

D327

STAIR #2

D340

CORR.

C3C4

EX STOR. RM

C359

EP432

B

DIALYSIS

D342

CT

CT

UC FRIDGE

CT CT

CT

CT

CT

CTUC FRIDGE

UC FRIDGE CT

COPIER

CONSULT RM.

D344

CT

CT

CT

LP3-H9-120VN

LP3-H9-120VC

T3-H9-120VC

(SUSPENDED)

EP431

C

ELEC

C340

OIT

C358C

TV

PRINTER

COFFEE MAKER

MICROWAVE

60"

A

E P

A

E P

SHADED AREA NOT IN SCOPE

UNLESS OTHERWISE NOTED

CT

CT

46"

84" 84"

LP3-E5-120VC:86

LP3-E5-120VC:84

MEDS

D315

LP3-E5-120VN2:95

LP3-E5-120VN2:93

LP3-E5-120VN2:91

CT

BLANKET WARMER

84"

84"

CT CTUC FRIDGE

SHREDDER

LP3-E5-120VN2:97

LP3-E5-120VN2:99

LP3-E5-120VC:96

LP3-E5-120VC:94

LP3-E5-120VC:92

LP3-E5-120VC:90

#10

#10

#10

42"36"

TV

TV

UC FRIDGE

TV

TV

36"

UC FRIDGE

LP3-H9-120VN:1

LP3-H9-120VN:3

LP3-H9-120VN:7

LP3-H9-120VN:5

LP3-H9-120VN:9

LP3-H9-120VN:11

LP3-H9-120VN:13

LP3-H9-120VN:15

LP3-H9-120VN:17

LP3-H9-120VN:19

LP3-H9-120VN:21

LP3-H9-120VN:23LP3-H9-120VN:25

LP3-H9-120VN:27

LP3-H9-120VN:10

LP3-H9-120VN:12

LP3-H9-120VN:8

LP3-H9-120VN:6

LP3-H9-120VN:4

LP3-H9-120VN:2

LP3-H9-120VN:41

LP3-H9-120VN:39

LP3-H9-120VN:37

LP3-H9-120VN:35

LP3-H9-120VN:33

LP3-H9-120VN:31

LP3-H9-120VN:29

LP3-H9-120VC:1

LP3-H9-120VC:3

LP3-H9-120VC:5

LP3-H9-120VC:7

LP3-H9-120VC:11

LP3-H9-120VC:13

LP3-H9-120VC:17

LP3-H9-120VC:21

LP3-H9-120VC:23

LP3-H9-120VC:25

LP3-H9-120VC:27

LP3-H9-120VC:29

LP3-H9-120VC:31

LP3-H9-120VC:2

LP3-H9-120VC:4

LP3-H9-120VC:8

LP3-H9-120VC:10

LP3-H9-120VC:9

LP3-H9-120VC:15

LP3-H9-120VC:19

LP3-H9-120VC:33

LP3-H9-120VC:6

30"

FRIDGE

USB

LP3-H9-120VC:16

LP3-H9-120VC:14

PRINT/SCAN

CT

CT

LP3-H9-120VN:24

LP3-H9-120VN:22

LP3-H9-120VN:20

LP3-H9-120VN:18

LP3-H9-120VN:14

LP3-H9-120VN:16

LP3-H9-120VN:26

LP3-H9-120VN:28

42"

36"

42"

36" 36"

42" 42"

36"

LP3-H9-120VN:30

LP3-H9-120VN:32

LP3-H9-120VC:20

LP3-H9-120VC:18

CT

P2

P2

P2

P2

LP3-H9-120VC:12

EXISTING PANEL LP3-

G10-120VN RELOCATED

AND RENAMED

SUPPLY TOWER

CT CT

CT

CT

PYXIS

SUPPLY TOWER

RATED WALL.

REFERENCE LIFE

SAFETY DRAWINGS

(TYP).

P6

P6

P6

P6

P6

P6

P6

P6

P6

P6

P10

P10

LP3-E5-120VE:7

TV

LP3-E5-120VC:82

P1

SD

SD

SD

46"

46"

CORR.

C3D5

LP3-E5-120VC:104

#10

84"

84"LP3-E5-120VN2:101

LP3-E5-120VN2:103

#10

LP3-E5-120VN2:105

84"

84"

PD

PD

PD

PD

LP3-E5-120VE:27

LP3-E5-120VE:29

#10

#10

PD

PD

LP3-E5-120VE:31

PD

PD

LP3-E5-120VE:33

LP3-E5-120VE:33

CORR.

C3D4

#10

#10

P5

P5

P5

PTV

PTV

PTV

B

3RD FLOOR KEY PLAN - AREA B

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EP132

ELECTRICAL POWER PLAN - 3RD

FLOOR - AREA B

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

KEYED NOTES:

P1 WIREMOLD LEGRAND 2000 SERIES PLUGMOLD (OR APPROVED EQUAL) WITH

SIMPLEX RECEPTACLES 12” ON CENTER. MOUNT PLUGMOLD AT 44” AFF. ALL

RECEPTACLES SHALL BE NEMA 5-20 HOSPITAL GRADE.

P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.

P5 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR AUTOMATIC

SENSOR TRANSFORMER. PROVIDE LOW VOLTAGE CABLING IN CONDUIT

FROM TRANSFORMER TO SENSOR. VERIFY CONNECTION REQUIREMENTS

WITH EQUIPMENT SUPPLIER PRIOR TO INSTALLATION.

P6 COORDINATE FINAL DESK AND DEVICE LOCATIONS WITH COR PRIOR TO

INSTALLATION.

P10 INSTALL RECEPTACLE HORIZONTALLY.

1/8" = 1'-0" A

ELECTRICAL POWER PLAN - 3RD FLOOR - AREA B

N

4' 8' 16'

1/8" = 1'-0"

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL

BE ALLOWED.

WP

WP

WP

MOUNT ON UNIT (TYP)

(E) EF

(E) EF

(E) EF

(E) EF

(E) EF

LP3-E5-120VN2:117

WP

/2 EP141 /2 EP141

1-EF65

AHU-31

1-EF64

1-EF67

1-EF63

1-EF62

#10

WP

WP

MOUNT ON UNIT

(TYP)

(E) EF

(E) EF

(E) EF /1 EP141/1 EP141

1-EF66

1-EF65

4TH FLOOR/ROOF - KEY PLAN

N

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EP141

ELECTRICAL POWER PLAN - ROOF

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

1/8" = 1'-0"

ELECTRICAL POWER PLAN - ROOF - AREA A

1/8" = 1'-0"

ELECTRICAL POWER PLAN - ROOF - AREA B

N

4' 8' 16'

1/8" = 1'-0"

0'

N

4' 8' 16'

1/8" = 1'-0"

0'

PROVIDE LIGHTNING PROTECTION SYSTEM FOR WORK

DONE DURING THIS PROJECT IN ACCORDANCE WITH

SPECIFICATIONS AND NFPA 780. EXTEND AND CONNECT

TO EXISTING SYSTEM AS REQUIRED. INDICATE

PROPOSED SYSTEM IN REQUIRED SHOP DRAWINGS.

NOTE:

JT

JT

J J

J

J

J

J

J

JT

JT

JT

JT

J J

J

J

J

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

10. ALL DEVICES INDICATED AS GFCI SHALL BE GFCI. NO DAISY CHAINING WILL

BE ALLOWED.

TLT./SHWR

A305A

PAT. RM #5

A305

PAT. RM #7

A307

TLT./SHWR

A307A

TLT./SHWR

A309A

PAT. RM #9

A309

PAT. RM #11

A311

TLT./SHWR

A311A

HW

PTV PTV

HW

HW

PTV

HW

PTV

26"

26"

26"

26"

26"

26" 26"

26"

26"

26"

26"

26"

USB

USB

USB

USB

PL

PL PL

PL

BB

BB

BB

BB

CT

CT

CT

CT

CTCT

CT

CT

CT

CT

CT

CT

USBH

USBHUSBH

LP3-E5-120VN:31

LP3-E5-120VN:33

LP3-E5-120VN:39

LP3-E5-120VN:35,37

LP3-E5-120VC:25

LP3-E5-120VC:27

LP3-E5-120VC:29

LP3-E5-120VN:41

LP3-E5-120VC:31

LP3-E5-120VC:33

LP3-E5-120VN:43

LP3-E5-120VN:45,47

LP3-E5-120VN:49

LP3-E5-120VC:35

LP3-E5-120VN:51

LP3-E5-120VC:39

LP3-E5-120VC:37

LP3-E5-120VN:53

LP3-E5-120VN:55,57

LP3-E5-120VC:41

LP3-E5-120VN:59

LP3-E5-120VC:43

LP3-E5-120VN:61

LP3-E5-120VC:45

LP3-E5-120VN:63

LP3-E5-120VN:65,67

LP3-E5-120VN:69

LP3-E5-120VC:47

#6;1"C.

#6;1"C.

#6;1"C.#6;1"C.

USB

USB

USB

USBH

USB

CT

P2 P2

P2

P2

P3 P3 P3 P3

P7 P7

P7

P7

ANTE

A301B

TLT./SHWR

A301A

ISO/BAR #1

A301

ISO/BAR #2

A302

ANTE

A302B

TLT./SHWR

A302A ISO/BAR #3

A303

TLT./SHWR

A303A

ANTE

A303B

PTV

HW

HW

PTV

PTV

HW

24"

24"

24"

24"

24"

24"

24"

24"

24"

USB

USB

USB

PL

PL

PL

BB

BB

BB

CT

CT

CT CT

CT

CT

CT

CT

CT

DIALYSIS BOX

DIALYSIS BOX

DIALYSIS BOX

42"

42" 42"

CT

CT

DSK

DSK

DSK

60"

60"

LP3-E5-120VN:1

LP3-E5-120VN:3

LP3-E5-120VN:5,7

LP3-E5-120VN:9

LP3-E5-120VN:11

LP3-E5-120VN:13

LP3-E5-120VN:15,17

LP3-E5-120VN:19

LP3-E5-120VC:1

LP3-E5-120VC:5

LP3-E5-120VC:7

LP3-E5-120VC:9

LP3-E5-120VC:13

LP3-E5-120VC:15

LP3-E5-120VN:21

LP3-E5-120VN:23

LP3-E5-120VN:25,27

LP3-E5-120VN:29

LP3-E5-120VC:17

LP3-E5-120VC:21

LP3-E5-120VC:23

#6;1"C.

#6;1"C.

#6;1"C.

STORAGE

A327

USB

USBH

USB

CT

USBH

USBH

USB

CT

P2

P2

P2P3

P3

P3

P7

P7

LP3-E5-120VC:3

LP3-E5-120VC:11 LP3-E5-120VC:19

P7

60"

PAT. RM #4

D304

TLT./SHWR

D304A

PAT. RM #6

D306

TLT./SHWR

D306A TLT./SHWR

D308A

PAT. RM #8

D308 PAT. RM #10

D310

TLT./SHWR

D310A

PAT. RM #12

D312

TLT./SHWR

D312A

HW

26"

26"

26"

USB

PTV PTV

HW HW

PTV

HW

PTV

PTV

HW

USB

USB

USB

USB

26"

26"

26"

26"

26"

26"

26"

26"

26" 26"

26"

26"

BB BB BB

BB

BB

PL PL

PL PL

PL

CT

CT

CT CT

CT

CT

CT

CT

CT

CT

CT

CT

CT

CT

CT

USBH USBH USBH

LP3-E5-120VC:51

LP3-E5-120VN:10

LP3-E5-120VC:53

LP3-E5-120VN:4

LP3-E5-120VN:6,8

LP3-E5-120VC:49 LP3-E5-120VC:55

LP3-E5-120VC:57

LP3-E5-120VN:14

LP3-E5-120VN:16,18 LP3-E5-120VN:20

LP3-E5-120VC:59

LP3-E5-120VC:63

LP3-E5-120VC:65

LP3-E5-120VN:30

LP3-E5-120VN:26,28

LP3-E5-120VN:24

LP3-E5-120VC:61

LP3-E5-120VC:69

LP3-E5-120VC:67

LP3-E5-120VN:34

LP3-E5-120VN:36,38

LP3-E5-120VN:40

LP3-E5-120VC:71

LP3-E5-120VC:73

LP3-E5-120VN:42

LP3-E5-120VC:75

LP3-E5-120VN:50

LP3-E5-120VC:77

LP3-E5-120VN:44

LP3-E5-120VN:46,48

LP3-E5-120VN:2

LP3-E5-120VN:22

LP3-E5-120VN:32

LP3-E5-120VN:12

#6;1"C.

#6;1"C.

#6;1"C.

#6;1"C.#6;1"C.

CT

USBUSB

USB

USB

USB

USBH

USBH

P2

P2

P2

P2 P2

P3 P3 P3

P3 P3

P7 P7

P7

P7

P7

LP3-J9-120VN3

LP3-J9-277VNLP3-J9-120VN

LP3-J9-120VN2

LP3-J9-120VE

LP3-J9-277VE

LP3-J9-277VC

LP3-J9-120VC

LP3-J9-120VQ LP3-J9-277VQ

ELEC

C340

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 67202

316.262.2691

EP431

ELECTRICAL ENLARGED POWER

PLANS

RELOCATE MEDICAL WARD

FOR PATIENT PRIVACY

800 HOSPITAL DRIVE COLUMBIA, MO 65201

07-26-2021

589A4-21-100

FINAL CONSTRUCTION DOCUMENTS

TMGSMS

KEYED NOTES:

P2 CONNECT TO UNDERCABINET LIGHTING. REFERENCE LIGHTING PLANS.

P3 COORDINATE LOCATION WITH ARCHITECTURAL PLANS AND ELEVATIONS.

P7 JUNCTION BOX FOR CONNECTION TO OWNER PROVIDED CLOCK. VERIFY

LOCATION WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION.

1/4" = 1'-0" A

ENLARGED POWER PLAN - NORTH PATIENT ROOMS

1/4" = 1'-0"

B

ENLARGED POWER PLAN - NORTHWEST ISO/BAR ROOMS

1/4" = 1'-0" D

ENLARGED POWER PLAN - SOUTH PATIENT ROOMS

2' 4' 8'0'

1/4" = 1'-0"

N

2' 4' 8'0'

1/4" = 1'-0"

N

2' 4' 8'0'

1/4" = 1'-0"

N

1/4" = 1'-0" C

ELECTRICAL POWER PLAN - ENLARGED ELEC C340

N

2' 4' 8'0'

1/4" = 1'-0"

J

F E

C

J

J

J

J

J

J

F E

C

J

J

J

J

J

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY…