589-22-885 Expand SPS Combined Drawing Set Vol 5 - Fire Protection- 7 Sheets.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25524R0097
About this file
This document contains fire alarm and fire suppression system drawings and related information for the Expand Sterile Processing Service (SPS) Space to Meet Requirements project at the Kansas City VA Medical Center.
The drawings provide details on the proposed fire alarm system, including fire alarm legend, riser diagram, input/output matrix, audibility plan, and device locations. The fire suppression plans show the existing and new sprinkler systems, hazard classifications, and general notes regarding system requirements. The work involves renovating the existing SPS area, demolishing existing fire alarm equipment, and using the existing infrastructure to connect new notification appliances and initiating devices. The project is subject to applicable VA, NFPA, and IBC codes and standards, with specific requirements for audibility, visual notification, initiating devices, circuits/conduit, and testing. The drawings also include key notes related to coordination with other trades. This information supports the solicitation 36C25524R0097 issued by the Department of Veterans Affairs to expand the SPS at the Kansas City VA Medical Center.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
589-22-885 | EXPAND SPS - KCVAMC
KANSAS CITY VA MEDICAL CENTER
100% IFB CONSTRUCTION DRAWINGS
VOLUME 5 OF 9 - FIRE PROTECTION
PAGES 73-79 OF 155, 7 SHEETS
FIRE ALARM LEGEND
S NEW SMOKE DETECTOR - SPOT TYPE
OUT OF SCOPE AREA
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING SIEMENS FIRE ALARM CONTROL UNIT
WF EXISTING WATERFLOW DEVICE
VS EXISTING VALVE SUPERVISORY SWITCH
S NEW SPEAKER
AIM EXISTING ADDRESSABLE INPUT MODULE
NEW SPEAKER STROBE
NEW STROBE
SYMBOL MODIFIERS
CANDELA RATING
WATT TAP
WEATHERPROOF DEVICE
ncd nW
WP
F NEW MANUAL PULL STATION
S
NEW SMOKE DETECTOR - DUCT TYPE
AIM NEW ADDRESSABLE INPUT MODULE
GENERAL:
1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE
DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT
SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION,
SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING
REQUIREMENTS.
2. SCOPE OF WORK FOR THIS PROJECT IS RENOVATION OF THE
EXISTING SPS AREA. CONTRACTOR TO DEMOLISH ALL EXISTING FIRE
ALARM EQUIPMENT IN THE SCOPE OF WORK AREA. CONTRACTOR
TO USE EXISTING FIRE ALARM CIRCUIT INFRASTRUCTURE TO
CONNECT NEW NOTIFICATION APPLIANCES AND INITIATING DEVICES.
NEW NOTIFICATION APPLIANCE LOCATED IN ROOM V3-745 TO BE
CONNECTED TO THE EXISTING NOTIFICATION APPLIANCE CIRCUIT IN
SMOKE ZONE 3NW.
3. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE
COMPLETED IN A NEAT, WORKMAN-LIKE MANNER.
4. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE
APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE
ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-
DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION FOR
PROPOSED ALTERNATIVE.
APPLICABLE CODES AND STANDARDS:
1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021
2. NFPA 70 NATIONAL ELECTRIC CODE (2020)
3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2022)
4. NFPA 101 (2021)
5. INTERNATIONAL BUILDING CODE (2021)
AUDIBILITY DESIGN:
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT
CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED
BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS
INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES ARE
REQUIRED, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL
COST.
2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER.
3. PATIENT ROOMS AND OR ROOMS, AS INDICATED ON THE DESIGN
DRAWINGS, WILL BE DESIGNED TO MEET PRIVATE-MODE
NOTIFICATION IN ACCORDANCE WITH NFPA 72. ALARM AUDIBILITY IN
THESE AREAS IS REQUIRED TO BE 10 dBA ABOVE AMBIENT OR
PROVIDED WITH VISUAL NOTIFICATION THROUGHOUT.
4. TAP SETTINGS SHOWN ON FIRE ALARM SHEET MAY NEED TO BE
ADJUSTED TO MEET MINIMUM AUDIBILITY REQUIREMENTS BASED ON
WALL AND DOOR CONSTRUCTIONS.
VISUAL NOTIFICATION DESIGN:
1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE
APPROVED DESIGN.
2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING
STROBES MORE THAN 3 FT.
INITIATING DEVICES:
1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE
LOCATION INDICATED ON THE APPROVED DESIGN WITHOUT
CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO
RELOCATING INITIATING DEVICES MORE THAN 3 FT.
2. NEW DUCT SMOKE DETECTOR LOCATIONS TO BE COORDINATED
WITH MECHANICAL CONTRACTOR.
CIRCUITS AND CONDUIT:
1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE
WITH NFPA 70 AND THE CONDUIT LISTING.
2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE
CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT
CAUSE THE LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE
SMOKE COMPARTMENT.
3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN
MANUAL THIS IN COMBINATION WITH BUILDINGS PROTECTED
THROUGHOUT BY SPRINKLERS SHALL BE CONSIDERED TO MEET THE
REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN
ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING
JURISDICTION.
4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON
SEPARATE CIRCUITS.
INSTALLATION:
1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING
STRUCTURE AND SHALL BE INSTALLED PARALLEL OR
PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED
OTHERWISE.
2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE
APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE
ENGINEER.
TESTING:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR
SHALL PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH
THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR
SHALL PERFORM TESTING AND PROVIDE DOCUMENTATION PRIOR TO
REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.
FIRE ALARM GENERAL NOTES
FACU
SPD
LEVEL 1
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT, LOCATED IN VB-722.
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL
CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND
TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.
THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION
AFTER SUCCESSFUL COMPLETION OF THE PROJECT.
4. EXISTING SIGNALING LINE CIRCUIT.
5. EXISTING NOTIFICATION APPLIANCE CIRCUIT.
2 3
LEVEL 3
WF VS
AIM AIMSS
F
LEVEL 4
S S
A H
U -2
-0
-0
A H
U -2
-0
-0
AIM AIM
16 ANY OTHER SYSTEM TROUBLE X X X 16
A B C D E F G H J M N O
X PERFORM OPERATION/REPORT DEVICE STATUS
SUPERVISORY CONDITIONS A B C D E F G H J M N O
5 SMOKE DETECTOR - DUCT TYPE X X X X 5
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E P
R E
-R E
C O
R D
E D
S T
A F
F A
L E
R T
M E
S S
A G
E T
H R
O U
G H
O U
T T
H
B
U
IL
D
IN
G
N O
T
IF
Y F
IR
E
D E
P A
R T
M E
N T
/S U
P E
R V
IS
IN
G S
T A
T
IO
N
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
ALARM CONDITIONS A B C D E F G H J M N O
1 MANUAL ALARM PULL STATION X X X X X X X 1
TROUBLE CONDITIONS A B C D E F G H J M N O
9 AC POWER FAILURE X X X 9
10 LOW BATTERY X X X 10
11 OPEN CIRCUIT X X X 11
12 GROUND FAULT X X X 12
13 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 13
14 REMOTE POWER SUPPLY COMMON TROUBLE X X X 14
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:2
A
M
FIRE ALARM GENERAL NOTES, LEGEND,
AND DIAGRAMS
SAB 73 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA001
SPUR #: 2205
SCALE: NONE
FIRE ALARM RISER DIAGRAM1
No. REVISION DESCRIPTION DATE
SCALE: NONE
FACU INPUT/OUTPUT MATRIX2
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL (BUSINESS OCCUPANCIES)
30dB AMBIENT SPL 45dB EXPECTED SPL (STORAGE OCCUPANCIES)
OUT OF SCOPE
60dB AMBIENT SPL 75dB EXPECTED SPL (ASSEMBLY OCCUPANCIES)
FIRE - 1 HOUR (NEW / EXISTING)
SMOKE (NEW / EXISTING)
PARTITION LEGEND
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
SHAFT
SHAFT
CLEAN
SOILED
WF
VS
CORRIDOR
C3-75
CORRIDOR
C3-62
21 3 4 5 6 7
B
C
D
E
F
G
H
LOGISTICS
BREAKDOWN
V3-777
CORRIDOR
C3-64
HAC
V3-653
RME STORAGE,
SOILED
V3-766
CORRIDOR
C1
ANTEROOM
V3-664
ANTEROOM
019A
AO
V3-625
COPY / SUPPLY
V3-621A
RECEPTION
V3-621
STAFF
SUPPORT
V3-630
STERILE
PROCESSING,
PPE ENTRY
V3-776
STERILE
DURABLES
STORAGE
V3-655
STEAM
STERILIZATION
V3-652
DECONTAMINATION
V3-640
CART WASH
V3-646
HAC
V3-642A
RME STORAGE,
CLEAN
V3-762
SOILED
TRANSITION
ANTEROOM
V3-641
INSTRUMENT
ASSEMBLY
WORKROOM
V3-650
LOW TEMP
STERILIZATION
V3-648
LASER ETCHER
V3-638
FEMALE TLT
ROOM
V3-636A
MALE TLT
ROOM
V3-634A
EQUIPMENT
STORAGE
V3-759
SPS CHIEF
V3-628
CLEAN
HOLDING
V3-758
CONFERENCE /
STAFF LOUNGE
V3-632
CONFERENCE
V3-765
STAFF TLT
V3-786
ELEC.
V3-760
LOGISTICS
STORAGE
V3-770
RESPIRATORY
V3-757
OFFICE / NURSE
SUPERVISOR
V3-755
NURSE
MANAGER
V3-624
SHARED OFFICE
V3-622
ASST. CHIEF
V3-626
SUPERVISORS
SHARED OFFICE
V3-623
CORRIDOR
C3-61
MALE LOCKERS
V3-634
FEMALE
LOCKERS
V3-636
FAMILY
BEREAVEMENT
V3-745
BED STORAGE
V3-756
ANTEROOM
V3-768
STAIR 18
S18
RME
PROCESSING
V3-764
EQ. ALCOVE
V3-747
CLEAN
DUMBWAITER
SCOPE
PROCESSING
DECON
V3-642
SCOPE
PROCESSING
V3-657
DETERGENT
STORAGE
V3-644
KEY PLAN - LEVEL 3
BLDG 26
AREA OF
WORK
BLDG 1
B L D
G
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:3
A
M
FIRE ALARM AUDIBILITY PLAN
SAB 74 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA101
SPUR #: 2205
No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - LEVEL 31
21 3 4 5 6 7
B
C
D
E
F
G
H
SHAFT
SOILED
FIRE - 1 HOUR (NEW / EXISTING)
SMOKE (NEW / EXISTING)
PARTITION LEGEND
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
KEY PLAN - LEVEL 3
BLDG 26
AREA OF
WORK
BLDG 1
B L D
G
N
FIRE ALARM LEGEND
EXISTING FIRE ALARM DEVICES TO BE MODIFIED
AS NECESSARY TO ACCOMMODATE NEW
STRUCTURAL STEEL
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:3
A
M
FIRE ALARM PLAN
SAB 75 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA102
SPUR #: 2205
No. REVISION DESCRIPTION DATE
N
FIRE ALARM PLAN - LEVEL 21
0.25W
15cd
0.25W
15cd
S
0.25W
S
0.25W
S
0.25W0.25W
15cd
S
.2
W
.2
W c d
.2
W c d
S
.2
W
S
.2
W
S
.2
W
0.25W
15cd
.2
W c d c d
.2
W c d c d
.2
W c d
0.25W
75cd
0.25W
30cd
0.25W
30cd
.2
W c d
.2
W c d
0.25W
30cd
.2
W c d
.2
W c d
.5
W c d
0.25W
15cd
F
0.25W
15cd
.5
W c d
0.25W
15cd
.2
W c d
0.25W
15cd
0.25W
30cd
.5
W c d
.2
W c d
0.25W
15cd
0.25W
15cd
0.25W
15cd
0.25W
15cd
0.5W
15cd
.2
W c d
0.25W
15cd
.2
W c d
.2
W c d
0.25W
15cd
.2
W c d
.2
W c d
.2
W c d
0.25W
30cd
0.25W
30cd
FIRE - 1 HOUR (NEW / EXISTING)
SMOKE (NEW / EXISTING)
PARTITION LEGEND
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
SHAFT
SHAFT
CLEAN
SOILED
CORRIDOR
C3-75
21 3 4 5 6 7
B
C
D
E
F
G
H
RME STORAGE,
SOILED
V3-766
STAFF
SUPPORT
V3-630
AO
V3-625
HAC
V3-653
STERILE
PROCESSING,
PPE ENTRY
V3-776
STERILE
DURABLES
STORAGE
V3-655
STEAM
STERILIZATION
V3-652
DECONTAMINATION
V3-640
CART WASH
V3-646
HAC
V3-642A
RME STORAGE,
CLEAN
V3-762
SOILED
TRANSITION
ANTEROOM
V3-641
INSTRUMENT
ASSEMBLY
WORKROOM
V3-650
LOW TEMP
STERILIZATION
V3-648
LASER ETCHER
V3-638
FEMALE TLT
ROOM
V3-636A
MALE TLT
ROOM
V3-634A
EQUIPMENT
STORAGE
V3-759
SPS CHIEF
V3-628
CLEAN
HOLDING
V3-758
CONFERENCE /
STAFF LOUNGE
V3-632
CONFERENCE
V3-765
STAFF TLT
V3-786
ELEC.
V3-760
LOGISTICS
STORAGE
V3-770
LOGISTICS
BREAKDOWN
V3-777
RESPIRATORY
V3-757
OFFICE / NURSE
SUPERVISOR
V3-755
NURSE
MANAGER
V3-624
SHARED OFFICE
V3-622
ASST. CHIEF
V3-626
CORRIDOR
C1
SUPERVISORS
SHARED OFFICE
V3-623
CORRIDOR
C3-61
MALE LOCKERS
V3-634
FEMALE
LOCKERS
V3-636
FAMILY
BEREAVEMENT
V3-745
BED STORAGE
V3-756
CORRIDOR
C3-77
RECEPTION
V3-621
ANTEROOM
019A
ANTEROOM
V3-664
ANTEROOM
V3-768
CORRIDOR
C3-64
STAIR 18
S18
RME
PROCESSING
V3-764
COPY / SUPPLY
V3-621A
EQ. ALCOVE
V3-747
CLEAN
DUMBWAITER
SCOPE
PROCESSING
DECON
V3-642
DETERGENT
STORAGE
V3-644
SCOPE
PROCESSING
V3-657
KEY PLAN - LEVEL 3
BLDG 26
AREA OF
WORK
BLDG 1
B L D
G
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:3
A
M
FIRE ALARM PLAN
SAB 76 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA103
SPUR #: 2205
No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
FIRE ALARM PLAN - LEVEL 31
SHEET KEYNOTES
MARK KEYNOTE
1 NEW NOTIFICAITON APPLIANCE IN THIS SPACE SHALL
BE CONNECTED TO THE NOTIFICAITON APPLIANCE
CIRCUIT FOR SMOKE ZONE 3NW. REFER TO LIFE
SAFETY PLANS GI023 FOR SMOKE ZONE BOUNDARIES.
1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION,
FIRE SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH
U.S. DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION
DESIGN MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13:
STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,
2022 EDITION; NFPA 14: STANDARD FOR THE INSTALLATION OF
STANDPIPE AND HOSE SYSTEMS, 2019 EDITION.
2. SCOPE OF WORK FOR THIS PROJECT IS RENOVATION OF THE
EXISTING SPS AREA.CONTRACTOR TO DEMOLISH ALL EXISTING
PIPING AND SPRINKLERS IN THE SCOPE OF WORK AREA.
EXISTING FIRE RISER IN STAIR 18 TO REMAIN, CONTRACTOR TO
USE THIS RISER AS THE CONNECTION POINT FOR THE NEW
PIPING AND SPRINKLERS PROTECTING THE SCOPE OF WORK
AREA. SPRINKLERS AND PIPING LOCATED IN ROOM V3-745 TO BE
SUPPLIED BY THE EXISTING RISER SUPPLYING SMOKE ZONE
3NW.
3. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE
GUIDANCE FOR BIDDING. THE FIRE PROTECTION CONTRACTOR
SHALL BE FULLY RESPONSIBLE FOR PROVIDING A COMPLETE
AND FULLY OPERABLE SYSTEM WHICH SHALL BE IN STRICT
ACCORDANCE WITH PROJECT SPECIFICATIONS AND
APPLICABLE CODES AND STANDARDS. THE WORK THAT IS
INDICATED IN THIS DOCUMENT IS AN OVERVIEW OF THE
PROJECT, INTENDED TO ESTABLISH THE MINIMUM SCOPE
REQUIREMENTS FOR THE PROJECT AS WELL AS THE
CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL
SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,
AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND
AHJ FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS
SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH
THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
4. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF
FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,
DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE
SHALL BE CONSIDERED DURING INSTALLATION. DO NOT
INSTALL SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN
CLEARANCE SPACES FOR MECHANICAL AND ELECTRICAL
EQUIPMENT. SPRINKLERS SHALL BE INSTALLED UNDER
OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13.
5. THE SPRINKLER SYSTEM MUST BE ZONED BY SMOKE
COMPARTMENTS AND PROPERLY IDENTIFIED. PROVIDE EACH
ZONE WITH A SEPARATE FLOW SWITCH, ISOLATION VALVE,
TAMPER SWITCH, AND PRESSURE GAUGE.
6. MATERIALS AND ACCESSORIES NECESSARY MUST BE
INSTALLED IN ACCORDANCE WITH THE APPLICABLE NFPA
CODES AND STANDARDS, PROJECT SPECIFICATIONS, AND BE UL
LISTED OR FM APPROVED FOR FIRE PROTECTION USE, UNLESS
OTHERWISE NOTED.
7. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC
TAMPER SWITCHES WIRED TO THE FACU. VALVES IN NORMAL
CLOSED POSITION SHALL BE PROVIDED WITH TAMPER TO
ACTIVATE IN THREE TURNS OR LESS. ALL VALVES OUTSIDE TO
BE ELECTRONICALLY MONITORED BY FIRE ALARM.
8. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.
9. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,
VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE
REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING
REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.
THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D,
PLEASE REFER TO THE STRUCTURAL DESIGN SHEETS FOR
MORE INFORMATION.
10. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL
BE USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY
SPRINKLER PIPING.
11. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE
IDENTIFIED AS REQUIRED BY NFPA 13.
12. PIPING MUST BE ARRANGED FOR FLUSHING. READILY
REMOVABLE FITTINGS MUST BE PROVIDED AT THE END OF ALL
CROSS MAINS.
13. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER
OF THE CEILING TILES.
14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY
DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT
WORK TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.
16. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER
SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO
BE MAINTAINED ABOVE 40 DEGREES F.
17. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE
CONCEALED SPACES.
FIRE SUPPRESSION GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:3
A
M
FIRE SUPPRESSION GENERAL NOTES
SAB 77 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FX001
SPUR #: 2205
No. REVISION DESCRIPTION DATE
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
EXISTING FIRE SUPPRESSION PIPING AND
SPRINKLERS TO BE MODIFIED AS NECESSARY
TO ACCOMMODATE NEW STRUCTURAL STEEL
FIRE - 1 HOUR (NEW / EXISTING)
SMOKE (NEW / EXISTING)
PARTITION LEGEND
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
KEY PLAN - LEVEL 3
BLDG 26
AREA OF
WORK
BLDG 1
B L D
G
N
21 3 4 5 6 7
B
C
D
E
F
G
H
SHAFT
SOILED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:4
A
M
FIRE SUPPRESSION PLAN - LEVEL 2
SAB 78 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FX101
SPUR #: 2205
No. REVISION DESCRIPTION DATE
N
FIRE SUPPRESSION PLAN - LEVEL 21
SHAFT
SHAFT
CLEAN
SOILED
CORRIDOR
C3-75
CORRIDOR
C3-62
21 3 4 5 6 7
B
C
D
E
F
G
LOGISTICS
BREAKDOWN
V3-777
CORRIDOR
C3-64
HAC
V3-653
RME STORAGE,
SOILED
V3-766
ANTEROOM
V3-664
ANTEROOM
019A
CORRIDOR
C1
STERILE
PROCESSING,
PPE ENTRY
V3-776
STERILE
DURABLES
STORAGE
V3-655
STEAM
STERILIZATION
V3-652
DECONTAMINATION
V3-640
CART WASH
V3-646
HAC
V3-642A
RME STORAGE,
CLEAN
V3-762
SOILED
TRANSITION
ANTEROOM
V3-641
INSTRUMENT
ASSEMBLY
WORKROOM
V3-650
LOW TEMP
STERILIZATION
V3-648
L A
S E
R E
T C
H E
R
V -6
FEMALE TLT
ROOM
V3-636A
MALE TLT
ROOM
V3-634A
EQUIPMENT
STORAGE
V3-759
SPS CHIEF
V3-628
CLEAN
HOLDING
V3-758
TOILET
V3-756
CONFERENCE /
STAFF LOUNGE
V3-632
CONFERENCE
V3-765
STAFF TLT
V3-786
ELEC.
V3-760
LOGISTICS
STORAGE
V3-770
RESPIRATORY
V3-757
OFFICE / NURSE
SUPERVISOR
V3-755
NURSE
MANAGER
V3-624
SHARED OFFICE
V3-622
ASST. CHIEF
V3-626
SUPERVISORS
SHARED OFFICE
V3-623
CORRIDOR
C3-61
MALE LOCKERS
V3-634
FEMALE
LOCKERS
V3-636
FAMILY
BEREAVEMENT
V3-745
BED STORAGE
V3-756
CORRIDOR
C3-77
RECEPTION
V3-621
ANTEROOM
V3-768
STAIR 18
S18
RME
PROCESSING
V3-764
STAFF
SUPPORT
V3-630
AO
V3-625
COPY / SUPPLY
V3-621A
EQ. ALCOVE
V3-747
CLEAN
DUMBWAITER
SCOPE
PROCESSING
DECON
V3-642
SCOPE
PROCESSING
V3-657
DETERGENT
STORAGE
V3-644
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
EXISTING FIRE SUPPRESSION PIPING AND
SPRINKLERS TO BE MODIFIED AS NECESSARY
TO ACCOMMODATE NEW STRUCTURAL STEEL
FIRE - 1 HOUR (NEW / EXISTING)
SMOKE (NEW / EXISTING)
PARTITION LEGEND
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2022
MISSOURI ENGINEERING COA EXP. 12/31/2022
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
11020 KING STREET, STE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1139 OLIVE ST, STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:4
A
M
FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN
SAB 79 OF 155BLS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FX102
SPUR #: 2205
No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - LEVEL 31
SHEET KEYNOTES
MARK KEYNOTE
1 NEW FIRE SPRINKLER IN THIS SPACE SHALL BE
CONNECTED TO THE SUPPLY PIPING FOR SMOKE ZONE
3NW. REFER TO LIFE SAFETY PLANS GI023 FOR SMOKE
ZONE BOUNDARIES
| 0-1 - DESIGN BINDER.pdf |
| Sheets |
| 0-1 - DESIGN BINDER |
| 0-2 - DESIGN BINDER- TOC |
| 0-3 - DESIGN BINDER- TOC-2 |
| 0-4 - DIGITAL SUBMISSION (CD) |
| 1-0 - MEDICAL PLANNING |
| 1-1 - ENVIRONMENTAL |
| 1-4 - STRUCTURAL |
| 1-5 - ARCHITECTURE |
| 1-8 - FIRE PROTECTION |
| 1-9 - PLUMBING |
| 1-10 - MECHANICAL |
| 1-11 - ELECTRICAL |
| 1-12 - TELECOMMUNICATION |
| 1-13 - SECURITY |
| 2-1 - VA CHECKLISTS- ENVIRONMENTAL |
| 2-4 - VA CHECKLISTS- STRUCTURAL |
| 2-5 - VA CHECKLISTS- ARCHITECTURE |
| 2-8 - VA CHECKLISTS- FIRE PROTECTION |
| 2-9 - VA CHECKLISTS- PLUMBING |
| 2-10 - VA CHECKLISTS- MECHANICAL |
| 2-11 - VA CHECKLISTS- ELECTRICAL |
| 2-12 - VA CHECKLISTS- TELECOMMUNICATION |
| 2-25 - SPUR DESIGN CHECKLISTS- ARCHITECTURE |
| 2-29 - SPUR DESIGN CHECKLISTS- PLUMBING |
| 2-30 - SPUR DESIGN CHECKLISTS- MECHANICAL |
| 2-31 - SPUR DESIGN CHECKLISTS- ELECTRICAL |
| 2-32 - SPUR DESIGN CHECKLISTS- SECURITY |
| 3-1 - INFECTION CONTROL RISK ASSESSMENT |
| 4-1 - SPECIFICATIONS TABLE OF CONTENTS |
| 5-1 - COST NARRATIVE & ESTIMATE |
| 6-1 - REVIEW COMMENT RESPONSES |
| 7-1 - MEDICAL EQUIPMENT |
| 8-1 - FINISH BOARD |
| 9-1 - CALCULATIONS |
| 9-2 - CUTSHEETS |
| 9-3 - MEDICAL PLANNING |
| 04_Fire Protection.pdf |
| Sheets |
| FA001 - FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS |
| FA101 - FIRE ALARM AUDIBILITY PLAN |
| FA102 - FIRE ALARM PLAN |
| FA103 - FIRE ALARM PLAN |
| FX001 - FIRE SUPPRESSION GENERAL NOTES |
| FX101 - FIRE SUPPRESSION PLAN - LEVEL 2 |
| FX102 - FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN |
File details come from the government source that posted it. Updated .