589-22-885 Expand SPS Combined Drawing Set Vol 5 - Fire Protection- 7 Sheets.pdf

PDF 4 MB Posted

Attached to
Z2DA--589-22-885 Expand Sterile Processing Service Space to Meet Requirements
Solicitation number
36C25524R0097
Issued by

About this file

This document contains fire alarm and fire suppression system drawings and related information for the Expand Sterile Processing Service (SPS) Space to Meet Requirements project at the Kansas City VA Medical Center.

The drawings provide details on the proposed fire alarm system, including fire alarm legend, riser diagram, input/output matrix, audibility plan, and device locations. The fire suppression plans show the existing and new sprinkler systems, hazard classifications, and general notes regarding system requirements. The work involves renovating the existing SPS area, demolishing existing fire alarm equipment, and using the existing infrastructure to connect new notification appliances and initiating devices. The project is subject to applicable VA, NFPA, and IBC codes and standards, with specific requirements for audibility, visual notification, initiating devices, circuits/conduit, and testing. The drawings also include key notes related to coordination with other trades. This information supports the solicitation 36C25524R0097 issued by the Department of Veterans Affairs to expand the SPS at the Kansas City VA Medical Center.

View the file

Other files

File Type Posted
V1_589-22-885_IFC_Specifications.pdf PDF
02 Structural Drawings IFC.pdf PDF
04 Fire Protection Drawings IFC.pdf PDF
07 Electrical Drawings IFC.pdf PDF
05 Plumbing Drawings IFC.pdf PDF
36C25524R0097 0003.pdf PDF
Revision 01 Narrative.pdf PDF
08 Telecom Drawings IFC.pdf PDF
09 Security Drawings IFC.pdf PDF
01 Environmental Drawings IFC.pdf PDF
V2_589-22-885_IFC_Specifications.pdf PDF
06 Mechanical Drawings IFC.pdf PDF
03 Architectural Drawings IFC.pdf PDF
36C25524R0097 0002.docx DOCX document
Agenda and Procurement Timeline.docx DOCX document
589-22-885 Expand SPS - Attendance for Pre-Bid Conference.pdf PDF
Construction Pre-Bid Info.docx DOCX document
Appendix 1- Price Breakdown and Calculation of Self-Performed Work- 589-22-885-Issued.docx DOCX document
36C25524R0097 0001.pdf PDF
589-22-885 Expand SPS Combined Drawing Set Vol 2 - Environmental -7 Sheets 02.pdf PDF
589-22-885 Expand SPS Combined Drawing Set Vol 7 - Mechanical - 22 Sheets.pdf PDF
589-22-885 IFB Specifications Volume 1 of 2.pdf PDF
589-22-885 Expand SPS Combined Drawing Set Vol 4 - Architectural- 36 Sheets.pdf PDF
Appendix 1- Price Breakdown and Calculation of Self-Performed Work- 589-22-885-Issued 02.docx DOCX document
589-22-885 Expand SPS Combined Drawing Set Vol 6 - Plumbing- 22 Sheets.pdf PDF
589-22-885 Expand SPS Combined Drawing Set Vol 9 - Telecom and Security- 9 Sheets.pdf PDF
589-22-885 IFB Specifications Volume 2 of 2.pdf PDF
36C25524R0097.docx DOCX document
589-22-885 Expand SPS Combined Drawing Set Vol 8 - Electrical- 23 Sheets.pdf PDF
Appendix 2- Contractor Certification Regarding Safety and Environmental- 589-22-885 03.docx DOCX document
589-22-885 Expand SPS Combined Drawing Set Vol 1 - General- 17 Sheets.pdf PDF
589-22-885 Expand SPS Combined Drawing Set Vol 3 - Structural -12 Sheets.pdf PDF
Appendix 3- VAAR 852.219-75 VA Limitations on Subcontracting- Certificate of Compliance for Services and Construction 02.docx DOCX document
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

589-22-885 | EXPAND SPS - KCVAMC

KANSAS CITY VA MEDICAL CENTER

100% IFB CONSTRUCTION DRAWINGS

VOLUME 5 OF 9 - FIRE PROTECTION

PAGES 73-79 OF 155, 7 SHEETS

FIRE ALARM LEGEND

S NEW SMOKE DETECTOR - SPOT TYPE

OUT OF SCOPE AREA

SPD EXISTING SURGE PROTECTIVE DEVICE

FACU EXISTING SIEMENS FIRE ALARM CONTROL UNIT

WF EXISTING WATERFLOW DEVICE

VS EXISTING VALVE SUPERVISORY SWITCH

S NEW SPEAKER

AIM EXISTING ADDRESSABLE INPUT MODULE

NEW SPEAKER STROBE

NEW STROBE

SYMBOL MODIFIERS

CANDELA RATING

WATT TAP

WEATHERPROOF DEVICE

ncd nW

WP

F NEW MANUAL PULL STATION

S

NEW SMOKE DETECTOR - DUCT TYPE

AIM NEW ADDRESSABLE INPUT MODULE

GENERAL:

1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE

DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT

SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION,

SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING

REQUIREMENTS.

2. SCOPE OF WORK FOR THIS PROJECT IS RENOVATION OF THE

EXISTING SPS AREA. CONTRACTOR TO DEMOLISH ALL EXISTING FIRE

ALARM EQUIPMENT IN THE SCOPE OF WORK AREA. CONTRACTOR

TO USE EXISTING FIRE ALARM CIRCUIT INFRASTRUCTURE TO

CONNECT NEW NOTIFICATION APPLIANCES AND INITIATING DEVICES.

NEW NOTIFICATION APPLIANCE LOCATED IN ROOM V3-745 TO BE

CONNECTED TO THE EXISTING NOTIFICATION APPLIANCE CIRCUIT IN

SMOKE ZONE 3NW.

3. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE

COMPLETED IN A NEAT, WORKMAN-LIKE MANNER.

4. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE

APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE

ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-

DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION FOR

PROPOSED ALTERNATIVE.

APPLICABLE CODES AND STANDARDS:

1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021

2. NFPA 70 NATIONAL ELECTRIC CODE (2020)

3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2022)

4. NFPA 101 (2021)

5. INTERNATIONAL BUILDING CODE (2021)

AUDIBILITY DESIGN:

1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT

CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED

BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS

INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES ARE

REQUIRED, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL

COST.

2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION

INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE

ENGINEER.

3. PATIENT ROOMS AND OR ROOMS, AS INDICATED ON THE DESIGN

DRAWINGS, WILL BE DESIGNED TO MEET PRIVATE-MODE

NOTIFICATION IN ACCORDANCE WITH NFPA 72. ALARM AUDIBILITY IN

THESE AREAS IS REQUIRED TO BE 10 dBA ABOVE AMBIENT OR

PROVIDED WITH VISUAL NOTIFICATION THROUGHOUT.

4. TAP SETTINGS SHOWN ON FIRE ALARM SHEET MAY NEED TO BE

ADJUSTED TO MEET MINIMUM AUDIBILITY REQUIREMENTS BASED ON

WALL AND DOOR CONSTRUCTIONS.

VISUAL NOTIFICATION DESIGN:

1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE

APPROVED DESIGN.

2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION

INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE

ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING

STROBES MORE THAN 3 FT.

INITIATING DEVICES:

1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE

LOCATION INDICATED ON THE APPROVED DESIGN WITHOUT

CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO

RELOCATING INITIATING DEVICES MORE THAN 3 FT.

2. NEW DUCT SMOKE DETECTOR LOCATIONS TO BE COORDINATED

WITH MECHANICAL CONTRACTOR.

CIRCUITS AND CONDUIT:

1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE

WITH NFPA 70 AND THE CONDUIT LISTING.

2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE

CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT

CAUSE THE LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE

SMOKE COMPARTMENT.

3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN

MANUAL THIS IN COMBINATION WITH BUILDINGS PROTECTED

THROUGHOUT BY SPRINKLERS SHALL BE CONSIDERED TO MEET THE

REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN

ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING

JURISDICTION.

4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON

SEPARATE CIRCUITS.

INSTALLATION:

1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING

STRUCTURE AND SHALL BE INSTALLED PARALLEL OR

PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED

OTHERWISE.

2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE

APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE

ENGINEER.

TESTING:

1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR

SHALL PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH

THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR

SHALL PERFORM TESTING AND PROVIDE DOCUMENTATION PRIOR TO

REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.

FIRE ALARM GENERAL NOTES

FACU

SPD

LEVEL 1

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT, LOCATED IN VB-722.

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL

CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND

TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.

THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION

AFTER SUCCESSFUL COMPLETION OF THE PROJECT.

4. EXISTING SIGNALING LINE CIRCUIT.

5. EXISTING NOTIFICATION APPLIANCE CIRCUIT.

2 3

LEVEL 3

WF VS

AIM AIMSS

F

LEVEL 4

S S

A H

U -2

-0

-0

A H

U -2

-0

-0

AIM AIM

16 ANY OTHER SYSTEM TROUBLE X X X 16

A B C D E F G H J M N O

X PERFORM OPERATION/REPORT DEVICE STATUS

SUPERVISORY CONDITIONS A B C D E F G H J M N O

5 SMOKE DETECTOR - DUCT TYPE X X X X 5

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E T

E M

P O

R A

L

A L E

R T

T O

N E

A N

D P

R E

-R E

C O

R D

E D

F

IR

E

V

A C

U A

T

IO

N M

E S

S A

G E

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E S

T R

O B

E S

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E P

R E

-R E

C O

R D

E D

S T

A F

F A

L E

R T

M E

S S

A G

E T

H R

O U

G H

O U

T T

H

B

U

IL

D

IN

G

N O

T

IF

Y F

IR

E

D E

P A

R T

M E

N T

/S U

P E

R V

IS

IN

G S

T A

T

IO

N

A U

X

IL

IA

R

Y F

U N

C T

IO

N

S

S H

U T

D O

W N

A S

S O

C

IA

T E

D A

IR

H

A N

D L

IN

G U

N

IT

ALARM CONDITIONS A B C D E F G H J M N O

1 MANUAL ALARM PULL STATION X X X X X X X 1

TROUBLE CONDITIONS A B C D E F G H J M N O

9 AC POWER FAILURE X X X 9

10 LOW BATTERY X X X 10

11 OPEN CIRCUIT X X X 11

12 GROUND FAULT X X X 12

13 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 13

14 REMOTE POWER SUPPLY COMMON TROUBLE X X X 14

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:2

A

M

FIRE ALARM GENERAL NOTES, LEGEND,

AND DIAGRAMS

SAB 73 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FA001

SPUR #: 2205

SCALE: NONE

FIRE ALARM RISER DIAGRAM1

No. REVISION DESCRIPTION DATE

SCALE: NONE

FACU INPUT/OUTPUT MATRIX2

REQUIRED AUDIBILITY LEGEND

54dB AMBIENT SPL 69dB EXPECTED SPL (BUSINESS OCCUPANCIES)

30dB AMBIENT SPL 45dB EXPECTED SPL (STORAGE OCCUPANCIES)

OUT OF SCOPE

60dB AMBIENT SPL 75dB EXPECTED SPL (ASSEMBLY OCCUPANCIES)

FIRE - 1 HOUR (NEW / EXISTING)

SMOKE (NEW / EXISTING)

PARTITION LEGEND

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

SHAFT

SHAFT

CLEAN

SOILED

WF

VS

CORRIDOR

C3-75

CORRIDOR

C3-62

21 3 4 5 6 7

B

C

D

E

F

G

H

LOGISTICS

BREAKDOWN

V3-777

CORRIDOR

C3-64

HAC

V3-653

RME STORAGE,

SOILED

V3-766

CORRIDOR

C1

ANTEROOM

V3-664

ANTEROOM

019A

AO

V3-625

COPY / SUPPLY

V3-621A

RECEPTION

V3-621

STAFF

SUPPORT

V3-630

STERILE

PROCESSING,

PPE ENTRY

V3-776

STERILE

DURABLES

STORAGE

V3-655

STEAM

STERILIZATION

V3-652

DECONTAMINATION

V3-640

CART WASH

V3-646

HAC

V3-642A

RME STORAGE,

CLEAN

V3-762

SOILED

TRANSITION

ANTEROOM

V3-641

INSTRUMENT

ASSEMBLY

WORKROOM

V3-650

LOW TEMP

STERILIZATION

V3-648

LASER ETCHER

V3-638

FEMALE TLT

ROOM

V3-636A

MALE TLT

ROOM

V3-634A

EQUIPMENT

STORAGE

V3-759

SPS CHIEF

V3-628

CLEAN

HOLDING

V3-758

CONFERENCE /

STAFF LOUNGE

V3-632

CONFERENCE

V3-765

STAFF TLT

V3-786

ELEC.

V3-760

LOGISTICS

STORAGE

V3-770

RESPIRATORY

V3-757

OFFICE / NURSE

SUPERVISOR

V3-755

NURSE

MANAGER

V3-624

SHARED OFFICE

V3-622

ASST. CHIEF

V3-626

SUPERVISORS

SHARED OFFICE

V3-623

CORRIDOR

C3-61

MALE LOCKERS

V3-634

FEMALE

LOCKERS

V3-636

FAMILY

BEREAVEMENT

V3-745

BED STORAGE

V3-756

ANTEROOM

V3-768

STAIR 18

S18

RME

PROCESSING

V3-764

EQ. ALCOVE

V3-747

CLEAN

DUMBWAITER

SCOPE

PROCESSING

DECON

V3-642

SCOPE

PROCESSING

V3-657

DETERGENT

STORAGE

V3-644

KEY PLAN - LEVEL 3

BLDG 26

AREA OF

WORK

BLDG 1

B L D

G

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:3

A

M

FIRE ALARM AUDIBILITY PLAN

SAB 74 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FA101

SPUR #: 2205

No. REVISION DESCRIPTION DATE

N

1/8" = 1'-0"

FIRE ALARM AUDIBILITY PLAN - LEVEL 31

21 3 4 5 6 7

B

C

D

E

F

G

H

SHAFT

SOILED

FIRE - 1 HOUR (NEW / EXISTING)

SMOKE (NEW / EXISTING)

PARTITION LEGEND

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

KEY PLAN - LEVEL 3

BLDG 26

AREA OF

WORK

BLDG 1

B L D

G

N

FIRE ALARM LEGEND

EXISTING FIRE ALARM DEVICES TO BE MODIFIED

AS NECESSARY TO ACCOMMODATE NEW

STRUCTURAL STEEL

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:3

A

M

FIRE ALARM PLAN

SAB 75 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FA102

SPUR #: 2205

No. REVISION DESCRIPTION DATE

N

FIRE ALARM PLAN - LEVEL 21

0.25W

15cd

0.25W

15cd

S

0.25W

S

0.25W

S

0.25W0.25W

15cd

S

.2

W

.2

W c d

.2

W c d

S

.2

W

S

.2

W

S

.2

W

0.25W

15cd

.2

W c d c d

.2

W c d c d

.2

W c d

0.25W

75cd

0.25W

30cd

0.25W

30cd

.2

W c d

.2

W c d

0.25W

30cd

.2

W c d

.2

W c d

.5

W c d

0.25W

15cd

F

0.25W

15cd

.5

W c d

0.25W

15cd

.2

W c d

0.25W

15cd

0.25W

30cd

.5

W c d

.2

W c d

0.25W

15cd

0.25W

15cd

0.25W

15cd

0.25W

15cd

0.5W

15cd

.2

W c d

0.25W

15cd

.2

W c d

.2

W c d

0.25W

15cd

.2

W c d

.2

W c d

.2

W c d

0.25W

30cd

0.25W

30cd

FIRE - 1 HOUR (NEW / EXISTING)

SMOKE (NEW / EXISTING)

PARTITION LEGEND

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

SHAFT

SHAFT

CLEAN

SOILED

CORRIDOR

C3-75

21 3 4 5 6 7

B

C

D

E

F

G

H

RME STORAGE,

SOILED

V3-766

STAFF

SUPPORT

V3-630

AO

V3-625

HAC

V3-653

STERILE

PROCESSING,

PPE ENTRY

V3-776

STERILE

DURABLES

STORAGE

V3-655

STEAM

STERILIZATION

V3-652

DECONTAMINATION

V3-640

CART WASH

V3-646

HAC

V3-642A

RME STORAGE,

CLEAN

V3-762

SOILED

TRANSITION

ANTEROOM

V3-641

INSTRUMENT

ASSEMBLY

WORKROOM

V3-650

LOW TEMP

STERILIZATION

V3-648

LASER ETCHER

V3-638

FEMALE TLT

ROOM

V3-636A

MALE TLT

ROOM

V3-634A

EQUIPMENT

STORAGE

V3-759

SPS CHIEF

V3-628

CLEAN

HOLDING

V3-758

CONFERENCE /

STAFF LOUNGE

V3-632

CONFERENCE

V3-765

STAFF TLT

V3-786

ELEC.

V3-760

LOGISTICS

STORAGE

V3-770

LOGISTICS

BREAKDOWN

V3-777

RESPIRATORY

V3-757

OFFICE / NURSE

SUPERVISOR

V3-755

NURSE

MANAGER

V3-624

SHARED OFFICE

V3-622

ASST. CHIEF

V3-626

CORRIDOR

C1

SUPERVISORS

SHARED OFFICE

V3-623

CORRIDOR

C3-61

MALE LOCKERS

V3-634

FEMALE

LOCKERS

V3-636

FAMILY

BEREAVEMENT

V3-745

BED STORAGE

V3-756

CORRIDOR

C3-77

RECEPTION

V3-621

ANTEROOM

019A

ANTEROOM

V3-664

ANTEROOM

V3-768

CORRIDOR

C3-64

STAIR 18

S18

RME

PROCESSING

V3-764

COPY / SUPPLY

V3-621A

EQ. ALCOVE

V3-747

CLEAN

DUMBWAITER

SCOPE

PROCESSING

DECON

V3-642

DETERGENT

STORAGE

V3-644

SCOPE

PROCESSING

V3-657

KEY PLAN - LEVEL 3

BLDG 26

AREA OF

WORK

BLDG 1

B L D

G

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:3

A

M

FIRE ALARM PLAN

SAB 76 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FA103

SPUR #: 2205

No. REVISION DESCRIPTION DATE

N

1/8" = 1'-0"

FIRE ALARM PLAN - LEVEL 31

SHEET KEYNOTES

MARK KEYNOTE

1 NEW NOTIFICAITON APPLIANCE IN THIS SPACE SHALL

BE CONNECTED TO THE NOTIFICAITON APPLIANCE

CIRCUIT FOR SMOKE ZONE 3NW. REFER TO LIFE

SAFETY PLANS GI023 FOR SMOKE ZONE BOUNDARIES.

1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION,

FIRE SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH

U.S. DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION

DESIGN MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13:

STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,

2022 EDITION; NFPA 14: STANDARD FOR THE INSTALLATION OF

STANDPIPE AND HOSE SYSTEMS, 2019 EDITION.

2. SCOPE OF WORK FOR THIS PROJECT IS RENOVATION OF THE

EXISTING SPS AREA.CONTRACTOR TO DEMOLISH ALL EXISTING

PIPING AND SPRINKLERS IN THE SCOPE OF WORK AREA.

EXISTING FIRE RISER IN STAIR 18 TO REMAIN, CONTRACTOR TO

USE THIS RISER AS THE CONNECTION POINT FOR THE NEW

PIPING AND SPRINKLERS PROTECTING THE SCOPE OF WORK

AREA. SPRINKLERS AND PIPING LOCATED IN ROOM V3-745 TO BE

SUPPLIED BY THE EXISTING RISER SUPPLYING SMOKE ZONE

3NW.

3. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE

GUIDANCE FOR BIDDING. THE FIRE PROTECTION CONTRACTOR

SHALL BE FULLY RESPONSIBLE FOR PROVIDING A COMPLETE

AND FULLY OPERABLE SYSTEM WHICH SHALL BE IN STRICT

ACCORDANCE WITH PROJECT SPECIFICATIONS AND

APPLICABLE CODES AND STANDARDS. THE WORK THAT IS

INDICATED IN THIS DOCUMENT IS AN OVERVIEW OF THE

PROJECT, INTENDED TO ESTABLISH THE MINIMUM SCOPE

REQUIREMENTS FOR THE PROJECT AS WELL AS THE

CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL

SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,

AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND

AHJ FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND

INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS

SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL

PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH

THE APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

4. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF

FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,

DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE

SHALL BE CONSIDERED DURING INSTALLATION. DO NOT

INSTALL SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN

CLEARANCE SPACES FOR MECHANICAL AND ELECTRICAL

EQUIPMENT. SPRINKLERS SHALL BE INSTALLED UNDER

OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13.

5. THE SPRINKLER SYSTEM MUST BE ZONED BY SMOKE

COMPARTMENTS AND PROPERLY IDENTIFIED. PROVIDE EACH

ZONE WITH A SEPARATE FLOW SWITCH, ISOLATION VALVE,

TAMPER SWITCH, AND PRESSURE GAUGE.

6. MATERIALS AND ACCESSORIES NECESSARY MUST BE

INSTALLED IN ACCORDANCE WITH THE APPLICABLE NFPA

CODES AND STANDARDS, PROJECT SPECIFICATIONS, AND BE UL

LISTED OR FM APPROVED FOR FIRE PROTECTION USE, UNLESS

OTHERWISE NOTED.

7. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC

TAMPER SWITCHES WIRED TO THE FACU. VALVES IN NORMAL

CLOSED POSITION SHALL BE PROVIDED WITH TAMPER TO

ACTIVATE IN THREE TURNS OR LESS. ALL VALVES OUTSIDE TO

BE ELECTRONICALLY MONITORED BY FIRE ALARM.

8. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN

ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.

9. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,

VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE

REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING

REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS.

THE SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D,

PLEASE REFER TO THE STRUCTURAL DESIGN SHEETS FOR

MORE INFORMATION.

10. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL

BE USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY

SPRINKLER PIPING.

11. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE

IDENTIFIED AS REQUIRED BY NFPA 13.

12. PIPING MUST BE ARRANGED FOR FLUSHING. READILY

REMOVABLE FITTINGS MUST BE PROVIDED AT THE END OF ALL

CROSS MAINS.

13. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER

OF THE CEILING TILES.

14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY

DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.

15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT

WORK TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.

16. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER

SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO

BE MAINTAINED ABOVE 40 DEGREES F.

17. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE

CONCEALED SPACES.

FIRE SUPPRESSION GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:3

A

M

FIRE SUPPRESSION GENERAL NOTES

SAB 77 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FX001

SPUR #: 2205

No. REVISION DESCRIPTION DATE

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

EXISTING FIRE SUPPRESSION PIPING AND

SPRINKLERS TO BE MODIFIED AS NECESSARY

TO ACCOMMODATE NEW STRUCTURAL STEEL

FIRE - 1 HOUR (NEW / EXISTING)

SMOKE (NEW / EXISTING)

PARTITION LEGEND

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

KEY PLAN - LEVEL 3

BLDG 26

AREA OF

WORK

BLDG 1

B L D

G

N

21 3 4 5 6 7

B

C

D

E

F

G

H

SHAFT

SOILED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:4

A

M

FIRE SUPPRESSION PLAN - LEVEL 2

SAB 78 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FX101

SPUR #: 2205

No. REVISION DESCRIPTION DATE

N

FIRE SUPPRESSION PLAN - LEVEL 21

SHAFT

SHAFT

CLEAN

SOILED

CORRIDOR

C3-75

CORRIDOR

C3-62

21 3 4 5 6 7

B

C

D

E

F

G

LOGISTICS

BREAKDOWN

V3-777

CORRIDOR

C3-64

HAC

V3-653

RME STORAGE,

SOILED

V3-766

ANTEROOM

V3-664

ANTEROOM

019A

CORRIDOR

C1

STERILE

PROCESSING,

PPE ENTRY

V3-776

STERILE

DURABLES

STORAGE

V3-655

STEAM

STERILIZATION

V3-652

DECONTAMINATION

V3-640

CART WASH

V3-646

HAC

V3-642A

RME STORAGE,

CLEAN

V3-762

SOILED

TRANSITION

ANTEROOM

V3-641

INSTRUMENT

ASSEMBLY

WORKROOM

V3-650

LOW TEMP

STERILIZATION

V3-648

L A

S E

R E

T C

H E

R

V -6

FEMALE TLT

ROOM

V3-636A

MALE TLT

ROOM

V3-634A

EQUIPMENT

STORAGE

V3-759

SPS CHIEF

V3-628

CLEAN

HOLDING

V3-758

TOILET

V3-756

CONFERENCE /

STAFF LOUNGE

V3-632

CONFERENCE

V3-765

STAFF TLT

V3-786

ELEC.

V3-760

LOGISTICS

STORAGE

V3-770

RESPIRATORY

V3-757

OFFICE / NURSE

SUPERVISOR

V3-755

NURSE

MANAGER

V3-624

SHARED OFFICE

V3-622

ASST. CHIEF

V3-626

SUPERVISORS

SHARED OFFICE

V3-623

CORRIDOR

C3-61

MALE LOCKERS

V3-634

FEMALE

LOCKERS

V3-636

FAMILY

BEREAVEMENT

V3-745

BED STORAGE

V3-756

CORRIDOR

C3-77

RECEPTION

V3-621

ANTEROOM

V3-768

STAIR 18

S18

RME

PROCESSING

V3-764

STAFF

SUPPORT

V3-630

AO

V3-625

COPY / SUPPLY

V3-621A

EQ. ALCOVE

V3-747

CLEAN

DUMBWAITER

SCOPE

PROCESSING

DECON

V3-642

SCOPE

PROCESSING

V3-657

DETERGENT

STORAGE

V3-644

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

EXISTING FIRE SUPPRESSION PIPING AND

SPRINKLERS TO BE MODIFIED AS NECESSARY

TO ACCOMMODATE NEW STRUCTURAL STEEL

FIRE - 1 HOUR (NEW / EXISTING)

SMOKE (NEW / EXISTING)

PARTITION LEGEND

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MISSOURI ARCHITECTURAL COA EXP. 12/31/2022

MISSOURI ENGINEERING COA EXP. 12/31/2022

STRUCTURAL / CIVIL ENGR

H2B

1225 N. LOOP WEST, STE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1139 OLIVE ST, STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

HEALTHCARE PLANNER

THE INNOVA GROUP

9442 N. CAPITAL OF TX HWY

AUSTIN, TX 78759

(512) 346-8700

/1

/2

:3

:4

A

M

FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN

SAB 79 OF 155BLS

100% ISSUED FOR BID

EXPAND SPS - KCVAMC

04/17/2024

589-22-885

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FX102

SPUR #: 2205

No. REVISION DESCRIPTION DATE

N

1/8" = 1'-0"

FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - LEVEL 31

SHEET KEYNOTES

MARK KEYNOTE

1 NEW FIRE SPRINKLER IN THIS SPACE SHALL BE

CONNECTED TO THE SUPPLY PIPING FOR SMOKE ZONE

3NW. REFER TO LIFE SAFETY PLANS GI023 FOR SMOKE

ZONE BOUNDARIES

0-1 - DESIGN BINDER.pdf
Sheets
0-1 - DESIGN BINDER
0-2 - DESIGN BINDER- TOC
0-3 - DESIGN BINDER- TOC-2
0-4 - DIGITAL SUBMISSION (CD)
1-0 - MEDICAL PLANNING
1-1 - ENVIRONMENTAL
1-4 - STRUCTURAL
1-5 - ARCHITECTURE
1-8 - FIRE PROTECTION
1-9 - PLUMBING
1-10 - MECHANICAL
1-11 - ELECTRICAL
1-12 - TELECOMMUNICATION
1-13 - SECURITY
2-1 - VA CHECKLISTS- ENVIRONMENTAL
2-4 - VA CHECKLISTS- STRUCTURAL
2-5 - VA CHECKLISTS- ARCHITECTURE
2-8 - VA CHECKLISTS- FIRE PROTECTION
2-9 - VA CHECKLISTS- PLUMBING
2-10 - VA CHECKLISTS- MECHANICAL
2-11 - VA CHECKLISTS- ELECTRICAL
2-12 - VA CHECKLISTS- TELECOMMUNICATION
2-25 - SPUR DESIGN CHECKLISTS- ARCHITECTURE
2-29 - SPUR DESIGN CHECKLISTS- PLUMBING
2-30 - SPUR DESIGN CHECKLISTS- MECHANICAL
2-31 - SPUR DESIGN CHECKLISTS- ELECTRICAL
2-32 - SPUR DESIGN CHECKLISTS- SECURITY
3-1 - INFECTION CONTROL RISK ASSESSMENT
4-1 - SPECIFICATIONS TABLE OF CONTENTS
5-1 - COST NARRATIVE & ESTIMATE
6-1 - REVIEW COMMENT RESPONSES
7-1 - MEDICAL EQUIPMENT
8-1 - FINISH BOARD
9-1 - CALCULATIONS
9-2 - CUTSHEETS
9-3 - MEDICAL PLANNING
04_Fire Protection.pdf
Sheets
FA001 - FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS
FA101 - FIRE ALARM AUDIBILITY PLAN
FA102 - FIRE ALARM PLAN
FA103 - FIRE ALARM PLAN
FX001 - FIRE SUPPRESSION GENERAL NOTES
FX101 - FIRE SUPPRESSION PLAN - LEVEL 2
FX102 - FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN

File details come from the government source that posted it. Updated .