The solicitation seeks to expand the sterile processing service space to meet requirements. The drawing set provides architectural details for the project. Key details include the scope of work, response dates, and the federal agency involved. This document does not contain information about required products or services, pricing terms, set asides, incumbents, or other salient contract details. The drawing set appears to be a supporting document for the overall solicitation.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
589-22-885 | EXPAND SPS - KCVAMC
KANSAS CITY VA MEDICAL CENTER
100% IFB CONSTRUCTION DRAWINGS
VOLUME 4 OF 9 - ARCHITECTURAL
PAGES 37-72 OF 155, 36 SHEETS
X
X
X
X
X
X
X
X
M
X
X
X
X
X
X
X
X
M
BLDG 26
BLDG 3
BLDG 15
BLDG 5
BLDG 4
BLDG 40
BLDG 1
MAIN
BLDG 2
BLDG 6
FACILITIES &
ENGINEERING
35TH STREET
E L M
W O
O D
A V
E
33RD STREET
LINWOOD BLVD
BLDG 56
BLDG 1
MRI
BLDG 6
BLDG 36ABLDG 38
V A
N B
R U
N T
B
LV
D
1.09 1.05
BLDG 58
1.16
AREA OF WORK
EXISTING CAMPUS
EXISTING BUILDING
SITE PLAN LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:4
:5
A
M
ARCHITECTURAL SITE PLAN
KJW 37 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AS001
SPUR #: 2205
N
1" = 100'-0"
SITE PLAN1
KEYNOTE LEGEND
1.05 PROPOSED LOCATION FOR TEMPORARY DUMPSTER FOR CONTRACTOR USE, IF NECESSARY.
CONTRACTOR TO COORDINATE WITH VA.
1.09 PROPOSED LOCATION OF CONSTRUCTION LAY DOWN AREA. CONTRACTOR TO COORDINATE
WITH VA.
1.16 SUGGESTED CONTRACTOR ACCESS, CONFIRM WITH VA.
No. REVISION DESCRIPTION DATE
1 2 3
D
E
F
VA POLICE
V1-675
OFFICE
V1-673
STORAGE
V1-673
OBSERVATION
V1-675
OFFICE
V1-799
OFFICE
V1-797
OFFICE
V1-795
EXAM
V1-791
OFFICE
V1-798
EXAM
V1-789
EXAM
V1-787
EXAM
V1-785
EXAM
V1-783
EXAM
V1-781
EXAM
V1-678 OFFICE
V1-680
OFFICE
V1-682
TLT
V1-678A
VESTIBULE
V1-798A
OBSERVATION/UC
V1-675B
STORAGE
V1-684A
ELEC
V1-685
DATA
V1-686
CORRIDOR
C1-63
CORRIDOR
C1-62
TREATMENT
ROOM
V1-654
OFFICE
V1-652
TRIAGE
V1-650
OFFICE
V1-652D
TREATMENT
ROOM
V1-683
TRIAGE
V1-687
STAIR 18
S18
CORRIDOR
C1-74
2.05
2.05
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
F.V.
4'-10"
F.V.
5'-7"
F .V
5' -3
F .V
8' -6
F.V.
3'-6 1/2"
F.V.
5'-2"
F .V
4' -1
0" 2'
-6
EXAM
V1-790
EXAM
V1-788
EXAM
V1-786
EXAM
V1-784
EXAM
V1-782
EXAM
V1-780
TOILET
V1-793
10'-5" 8'-8 1/2"
'-9
STORAGE
V1-684
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
EXISTING DOOR & FRAME TO
BE DEMOLISHED IN ITS
ENTIRETY
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS
ENTIRETY
EXISTING WALLS TO
REMAIN
KEY PLAN - LEVEL 1
N
1 2 3
D
E
F
VA POLICE
V1-675
OFFICE
V1-673
STORAGE
V1-673
OBSERVATION
V1-675
OFFICE
V1-799
OFFICE
V1-797
OFFICE
V1-795
EXAM
V1-791
OFFICE
V1-798
EXAM
V1-789
EXAM
V1-787
EXAM
V1-785
EXAM
V1-783
EXAM
V1-781
EXAM
V1-678 EXAM
V1-680
EXAM
V1-682
TLT
V1-678A
VESTIBULE
V1-798A
OBSERVATION/UC
V1-675B
STORAGE
V1-684A
ELEC
V1-685
STORAGE
V1-684
DATA
V1-686
CORRIDOR
C1-63
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
CORRIDOR
C1-62
TREATMENT
ROOM
V1-654
OFFICE
V1-652
TRIAGE
V1-650
CORRIDOR
V1-642D
TREATMENT
ROOM
V1-683
TRIAGE
V1-687
STAIR 18
S18
CORRIDOR
C1-74
EXAM
V1-790
EXAM
V1-788
EXAM
V1-786
EXAM
V1-784
EXAM
V1-782
EXAM
V1-780
CORRIDOR
C1-72
TOILET
V1-793
2.45
1'-1" 3'-4"
EXIT LIGHT
EXISTING 2' x 2'
ACOUSTICAL CEILING TO
BE DEMOLISHED
EXISTING GYPSUM
BOARD CEILING TO BE
DEMOLISHED
EXISTING 2 x 2 LIGHT
FIXTURE TO BE
DEMOLISHED
CEILING HEIGHT, ABOVE
FINISH FLOOR
EXISTING RECESSED
CAN LIGHT TO BE
DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE
DEMOLISHED
00'-00"
DEMOLITION REFLECTED CEILING PLAN LEGEND
EXISTING 2' x 4'
ACOUSTICAL CEILING
TO BE DEMOLISHED
RETURN AIR GRILLE
EXISTING SUPPLY AIR
DIFFUSER TO BE
DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE
DEMOLISHED
AREA NOT IN CONTRACT
REFERENCE LOCATION FOR
FRP REINFORCING. REFER
TO STRUCTURAL.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:2
:3
A
M
DEMOLITION REFLECTED CEILING PLAN
- LEVEL 1
KJW 38 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD001
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 1 - DEMOLITION REFLECTED CEILING PLAN2
KEYNOTE LEGEND
2.05 SAW CUT EXISTING SECOND FLOOR SLAB FOR NEW DUMBWAITER OPENING. SEE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2.45 CUT OPENING IN WALL FOR NEW 3'-0 x 7'-0" OPENING PER VA REQUEST TO ACCESS
OBSERVATION AREA.
N
1/8" = 1'-0"
LEVEL 1 - DEMOLITION PLAN1
1 2 3 4 5 6 7
A
B
C
D
E
F
G
H
5'-6 21/256"
2.02
32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0"
192'-0"
'-0
'-0
'-0
'-0
'-0
'-0
'-0
8'
-0
OFFICE
VB-673A
OFFICE
VB-663
WAITING
VB-645
EXAM
VB-668
EXAM
VB-647
EXAM
VB-666
EXAM
V2-667
EXAM
V2-673B
EXAM
V2-673C
CLOSET
V2-671
STORAGE
V2-675
WAITING
V2-673
ENT
CHECK-IN
V2-796
DENTAL
CHECK-IN
V2-755
OFFICE
V2-757
EXAM
V2-794
EXAM
V2-795
EXAM
V2-793
EXAM
V2-791
EXAM
V2-792
OFFICE
V2-761
CORRIDOR
C2-72
ELEC.
CLOSET
V2-750
MALE
LOCKER
ROOM
V2-751
X-RAY
V2-756
WOMENS
LOCKER
ROOM
V2-749
CORRIDOR
C2-76
CORRIDOR
C2-77
WAITING
V2-677
STAIR 18
S18
X-RAY
V2-758
TLT
V2-751A
CORRIDOR
C2-74
CORRIDOR
C2-73
CORRIDOR
C2-70
AUDIOLOGY
V2-725
WAITING
V2-705
RECEPTION
V2-646
CORRIDOR
C2-63
CORRIDOR
C2-60
WAITING
V2-640
EMS
V2-634
2.05
2.19
2.19
F V
8' -6
O P
E N
5' -3
OPEN
4'-10"
FV
5'-7"
2' -5
/2
4'
-1 0"
3'-6"
2.02
EXAM
VB-659
EXAM
VB-660
EXAM/CLASS
ROOM
VB-661
OFFICE
VB-657
OFFICE
VB-655
OFFICE
VB-653
OFFICE
VB-651
CORRIDOR
C2-65
ELEC
V2-660
DATA
V2-654
ELEC
V2-652
EXAM
V2-649
EXAM
V2-664
ELEV
E22
ELEV
E12
ELEV
E11
EXAM
V2-648
MENS TLT
V2-641
WOMENS TLT
V2-643
CORRIDOR
C2-64
CORRIDOR
C2-66
ENT
RESIDENTS
V2-789
EXAM
V2-783
EXAM
V2-781
SOILED
UTILITY
V2-779
EXAM
V2-778
EXAM
V2-777
EXAM
V2-775
EXAM
V2-773
EXAM
V2-772
EXAM
V2-771
OFFICE
V2-736
OFFICE
V2-734
OFFICE
V2-732
OFFICE
V2-730
AHU
V2-733
AUDIO ROOM
V2-729
AUDIO BOOTH
V2-731
AUDIO BOOTH
V2-738
SUPPLY
CLOSET
V2-735
RECEPTION
V2-707
HEARING AID
FIT ROOM
V2-748
EXAM
V2-725A
SPEECH
PATHOLOGY
V2-709
EXAM
V2-727
EXAM
V2-725B
AUDIO BOOTH
V2-746
AUDIO BOOTH
V2-744
AUDIO BOOTH
V2-747
AUDIO BOOTH
V2-745
EXAM
V2-762
EXAM
V2-764
EXAM
V2-766
EXAM
V2-768
SUPPLY
ROOM
V2-770 BREAK ROOM
V2-737
OFFICE
V2-739
EXAM
V2-741
LAB
V2-767
OFFICE
V2-774
CLEAN
UTILITY
V2-776
ELEC
V2-782
DATA
V2-780
OFFICE
V2-763
SCOPE ROOM
V2-790
ORAL
SURGERY
V2-788
OFFICE
V2-765
SUPPLY
V2-786
BREAK ROOM
V2-760
AUDIO BOOTH
V2-740
AUDIO BOOTH
V2-742
DATA
V2-600
ELEC
V2-602
EXAM
V2-603
EXAM
V2-605
EXAM
V2-607
EXAM
V2-609
EXAM
V2-611
WORK ROOM
V2-612
SOILED
UTILITY
V2-606
RECEPTION
V2-604
EXAM
V2-610
MED ROOM
V2-615
EXAM
V2-617
CORRIDOR
C2-62
MED ROOM
V2-615
MED ROOM
V2-615
MED ROOM
V2-615
MED ROOM
V2-615
OFFICE
V2-711 OFFICE
V2-714
CLEAN
STORAGE
V2-625
BREAK ROOM
V2-614
EXAM
V2-616
EXAM
V2-618
EXAM
V2-620
EXAM
V2-622
EXAM
V2-624
CORRIDOR
C2-61
WORK ROOM
V2-629
EXAM
V2-628
EXAM
V2-626
STORAGE
V2-629A
PHARMACY
V2-710
STAIR 17
S17
PHARMACY
V2-717
ANTE ROOM
V2-720B
SEG. COMP.
V2-720A
OFFICE
V2-721
CLEAN COMP.
V2-719
OFFICE
V2-716
OFFICE
V2-715
STORAGE
V2-712
OFFICE
V2-713
INVESTIGATIVE
DRUG OFFICE
V2-722
ELEC
V2-728
IT
V2-730
STAIRWELL
S24
VAULT
V2-718
FV
10'-5"
F V
'-9
2.02
3'-9 1/2"
6' -6
2' -2
/2
5'
-7
/2
2.02 2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
2.02
4' -0
1' -9
/2
4' -0
1'
-9
/2
4' -5
2.02
2.02
2.02
2.02
2.56
2.562.56
2.56
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
EXISTING DOOR & FRAME TO
BE DEMOLISHED IN ITS
ENTIRETY
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS
ENTIRETY
EXISTING WALLS TO
REMAIN
KEY PLAN - LEVEL 2
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:2
:5
A
M
DEMOLITION PLANS - LEVEL 2
KJW 39 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD002
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 2 - DEMOLITION PLAN1
KEYNOTE LEGEND
2.02 REMOVE WALL AS REQUIRED FOR NEW CONSTRUCTION
2.05 SAW CUT EXISTING SECOND FLOOR SLAB FOR NEW DUMBWAITER OPENING. SEE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2.19 EXISTING DUMBWAITERS, ACCESSORIES AND HOISTWAYS TO BE REMOVED IN THEIR
ENTIRETY.
2.56 CONTRACTOR TO PROVIDE LEAD LINING WALL TO MATCH EXISTING CONSTRUCTION FOR
EFFECTING IMAGING SPACES. CONFIRM WITH VA PHYSICISTS.
B
C
D
E
F
G
H
2.15
32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0"
192'-0"
8'
-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
VB-673A
VB-663
VB-645VB-668
VB-647VB-666
V2-667
V2-673B
V2-673C
V2-671
V2-675
V2-673
V2-796 V2-755
V2-757
V2-794
V2-795
V2-793
V2-791
V2-792
V2-761
C2-72
V2-750
V2-751
V2-756
V2-749
C2-76
C2-77
V2-677
S18
V2-758 V2-751A
C2-74
C2-73
C2-70
V2-725
V2-705
V2-646
C2-63
C2-60
V2-640
V2-634
VB-659
VB-660
VB-661
VB-657
VB-655 VB-653
VB-651
C2-65
V2-660 V2-654
V2-652
V2-649
V2-664
E22
E12
E11
V2-648
V2-641
V2-643
C2-64
C2-66
V2-789
V2-783
V2-781
V2-779
V2-778 V2-777 V2-775 V2-773 V2-772 V2-771 V2-736 V2-734 V2-732 V2-730 V2-733
V2-729
V2-731 V2-738
V2-735
V2-707V2-748
V2-725A V2-709
C2-65
C2-65
V2-746
V2-744
V2-747
V2-745
V2-762
V2-764
V2-766
V2-768
V2-770
V2-737
V2-739
V2-741
V2-767
V2-774
V2-776
V2-782
V2-780
V2-763
V2-790
V2-788
V2-765
V2-786
V2-760
V2-740
V2-742
V2-600
V2-602
V2-603 V2-605 V2-607 V2-609 V2-611
V2-612
V2-606
V2-604
V2-610
V2-615
V2-617
C2-62
V2-615 V2-615 V2-615
V2-615
V2-711
V2-714
V2-625
V2-614
V2-616
V2-618
V2-620
V2-622
V2-624
C2-61
V2-629
V2-628
V2-626
V2-629A
V2-710
S17
V2-717
V2-720BV2-720A
V2-721
V2-719
V2-716
V2-715
V2-712
V2-713
V2-722
V2-728
V2-730 S24
V2-718
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55 2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.552.55
2.55 2.55 2.55 2.55 2.55 2.55 2.55 2.55
2.55
2.55
2.55
2.55
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
KEY PLAN - LEVEL 2 RCP
N
EXIT LIGHT
EXISTING 2' x 2'
ACOUSTICAL CEILING TO
BE DEMOLISHED
EXISTING GYPSUM
BOARD CEILING TO BE
DEMOLISHED
EXISTING 2 x 2 LIGHT
FIXTURE TO BE
DEMOLISHED
CEILING HEIGHT, ABOVE
FINISH FLOOR
EXISTING RECESSED
CAN LIGHT TO BE
DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE
DEMOLISHED
00'-00"
DEMOLITION REFLECTED CEILING PLAN LEGEND
EXISTING 2' x 4'
ACOUSTICAL CEILING
TO BE DEMOLISHED
RETURN AIR GRILLE
EXISTING SUPPLY AIR
DIFFUSER TO BE
DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE
DEMOLISHED
AREA NOT IN CONTRACT
REFERENCE LOCATION FOR
FRP REINFORCING. REFER
TO STRUCTURAL.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:2
A
M
DEMOLITION REFLECTED CEILING PLAN
- LEVEL 2
KJW 40 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD003
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 2 - DEMOLITION REFLECTED CEILING PLAN1
KEYNOTE LEGEND
2.15 AREA OF WORK ABOVE CEILING, COORDINATE WITH NEW SUSPENDED SLAB FOR MATERIAL
LIFT PIT.
2.55 CONTRACTOR TO REMOVE AND SALVAGE ALL EXISTING FIXTURES AND CEILING MOUNTED
EQUIPMENT THROUGHOUT LEVEL 2 PHASED CONSTRUCTION SCOPE.
B
C
D
E
F
G
H
2.08
2.03
2.102.10
2.08
2.08
2.10
2.08
2.10
2.10
2.102.102.102.102.102.102.102.10
2.10
2.10
2.10
2.032.10
2.10
2.102.10
BULK
STORAGE
V3-629
SCOPE
STORAGE
V3-628
SCOPE
PROCESSING
V3-624A
DECON
V3-624B
ANTE-ROOM
V3-624
CORRIDOR
C3-62
BREAK ROOM
V3-621
OFFICE
V3-627
EQUIP. ROOM
V3-632
EQUIP. ROOM
V3-634
STERILIZERS
V3-636
PREPARATION
AND
ASSEMBLY
V3-635
LOCKER
ROOM. MALE
V3-623
LOCKER
ROOM,
FEMALE
V3-637
EQUIPMENT
STORAGE
V3-638STORAGE
V3-640
ANTI-ROOM
V3-639
TOILET
V3-642A
SOILED
RECEIVING
V3-641
CORRIDOR
C3-64
NURSE
STATION
V3-770
JAN. CLOSET
V3-643
CONFERENCE
ROOM
V3-775
ELEC.
CLOSET
V3-780
TOILET,
STAFF
V3-778
OFFICE
V3-782
LOCKER
ROOM, STAFF
V3-785
SHOWER /
TOILET, MALE
V3-785B
MEDICAL ON
CALL
V3-612
TOILET
V3-731
MEDICAL ON
CALL
V3-619
STORAGE
V3-618
CORRIDOR
C3-61
OFFICE
V3-615
EDUCATION
ROOM
V3-614
SUPPLY
ROOM
V3-612
CLEAN
UTILITY
V3-611
PANTRY/BREAK
ROOM
V3-702
SOILED
UTILITY
V3-706
STORAGE
V3-610
TOILET
V3-613
CORRIDOR
C3-60
OXYGEN
CYLINDERS
V3-616
HOSPITAL
WORK ROOM
V3-707
BIOMED
NETWORK
CLOSET
V3-734
CLEAN
UTILITY
V3-719
SUPPLY
ROOM
V3-736
SHOWER
ROOM
V3-605APATIENT
ROOM
V3-602
SHOWER
ROOM
V3-602A
SHOWER
ROOM
V-601
DRUG
STORAGE
V3-781
PANTRY
V3-779
CLEAN LINEN
V3-777
SOILED
HOLDING
V3-784
NURSE
STATION
V3-757
SOILED
UTILITY
V3-747
TOILET
V3-756
SOILED
UTILITY
V3-774
TOILET
V3-772
CORRIDOR
C3-74
ANTE-ROOM
V3-766A
ANTE-ROOM
V3-767A
STAIR 17
S17
I.C.U.
STORAGE
V3-753
JAN. CLOSET
V3-752
ANTE-ROOM
V3-718
ANTE-ROOM
V3-715A
NURSES
STATION
V3-724
PANTRY
V3-746
SOILED
UTILITY
V3-748
NURSES
STATION
V3-600
ELEVATOR
LOBBY
E3-V
OFFICE
M3-395
STAIR 16
S16
JAN. CLOSET
V3-626
SHOWER
ROOM
V3-606A
PATIENT
ROOM
V3-766
PATIENT
ROOM
V3-767
PATIENT
ROOM
V3-768
PATIENT
ROOM
V3-769
BREAK ROOM
V3-773
CLEAN
UTILITY
V3-776
TOILET
V3-617A
TOILET
V3-633A
STAFF
V3-733
MEDICAL ON
CALL
V3-741
TOILET
V3-738A
BREAK ROOM
V3-738
ELEC.
V3-740
CORRIDOR
V3-742
ROOM
V3-722
ROOM
V3-723
OFFICE
V3-744
NURSES
STATION
V3-725
STAIR 18
S18
EQUIPMENT
WASHROOM
V3-633
STORAGE
V3-630
STERILE
PROCESSING
V3-635
ANTE-ROOM
V3-768A
PATIENT
ROOM
V3-603
PATIENT
ROOM
V3-604
PATIENT
ROOM
V3-605
PATIENT
ROOM
V3-606
PATIENT
ROOM
V3-607
PATIENT
ROOM
V3-608
PATIENT
ROOM
V3-609
PATIENT
ROOM
V3-708
PATIENT
ROOM
V3-709
PATIENT
ROOM
V3-710
PATIENT
ROOM
V3-711
PATIENT
ROOM
V3-712
PATIENT
ROOM
V3-713
PATIENT
ROOM
V3-714
PATIENT
ROOM
V3-715
PATIENT
ROOM
V3-716
PATIENT
ROOM
V3-717
MECH. ROOM
V3-613
PATIENT
ROOM
V3-758
PATIENT
ROOM
V3-759
PATIENT
ROOM
V3-760
PATIENT
ROOM
V3-761
PATIENT
ROOM
V3-762
PATIENT
ROOM
V3-763
PATIENT
ROOM
V3-765
PATIENT
ROOM
V3-764
CORRIDOR
C3-71
CORRIDOR
C3-70
CORRIDOR
C3-36
ELEVATOR
NO. 11
E11
ELEVATOR
NO. 12
E12
ELEVATOR
NO. 22
E22
CORRIDOR
C3-63
CORRIDOR
C3-76
CORRIDOR
C3-75
CORRIDOR
C3-77
CORRIDOR
C3-73
JAN. CLOSET
V3-620
MEDICAL ON
CALL
V3-617
SHOWER /
TOILET,
FEMALE
V3-785A
ROOM
V3-771
NURSE
STATION
V3-783
NURSE
STATION
V3-755
NURSE
STATION
V3-631
32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0"
192'-0"
2.04
2.04
2.13
2.13
2.04
2.04
2.04
2.04 2.04 2.04
2.04
2.04
2.04
2.04
2.04
2.04
2.05
F.V.
4'-10" 5'-7"
2.10
2.04
2.10
2.10
2.04
2.08
2.10
2.08
2.10
2.06 2.06
2.06
2.06
2.06
2.06
2.06 2.06
2.06
2.06
2.06
2.06
2.06 2.06
2.06
2.06
2.06
2.06
2.06 2.06
2.06
2.06
2.06
2.06
2.08
2.08
2.10
2.06
2.06
2.06
2.06
2.06
2.06
2.062.06 2.062.062.062.06
2.06
2.06
2.06
2.06
2.06
2.06
2.06
2.08
2.06
2.06 2.09
2.09
2.06
2.06
2.06
2.08 2.10
2.08
2.10 2.10
2.08
2.10
2.08
2.10
2.08 2.10
2.08
2.10
2.08
2.10
2.08
2.10
2.08
2.12
2.12
2.04
F.V.
13'-0 1/2"
2.14
2.14
2.04
2.04
2.01 2.01 2.01 2.012.01
2.01 2.01 2.01 2.01
2.01
2.01
2.01
2.01 2.01 2.01
2.01
2.01
EXTENTS OF WORK
EXTENTS OF WORK
EXTENTS OF
WORK
4' -5
2.16 2.16
2.16
2.16 2.16 2.16 2.16 2.16 2.16
2.17
2.06
2.172.17
2.06
2.172.17 2.17
2.17
2.17
2.17
2.17
5' -3
8'
-6
OPEN
5'-4"
O P
E N
4' -1
0" 2'
-5
/2
8'
-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
2.21
EXTENTS OF WORK
1'-7"
2.37
2.37
2.37
2.39
2.39
2.39 2.39
2.39
2.392.39
2.39
2.39
2.39
2.39
2.39
2.39
2.39 2.39 2.39
2.39
2.40
2.40
2.52
2.53
2.53 2.53
2.53
2.53 2.53 2.53 2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53
2.53 2.53 2.53 2.53
2.54
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
EXISTING DOOR & FRAME TO
BE DEMOLISHED IN ITS
ENTIRETY
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS
ENTIRETY
EXISTING WALLS TO
REMAIN
KEY PLAN - LEVEL 3
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:3
A
M
DEMOLITION PLAN - LEVEL 3
KJW 41 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD004
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 3 - DEMOLITION PLAN1
KEYNOTE LEGEND
2.01 EXISTING WINDOWS TO REMAIN, PROTECT.
2.03 REMOVE CONCRETE TIERED FLOOR COMPLETE AND EXCAVATE.
2.04 DEMOLISH EXISTING CASEWORK AND/OR COUNTERTOPS IN ITS ENTIRETY, INCLUDING
ASSOCIATE PLUMBING FIXTURES.
2.05 SAW CUT EXISTING SECOND FLOOR SLAB FOR NEW DUMBWAITER OPENING. SEE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2.06 DEMOLISH EXISTING FLOORING IT ITS ENTIRETY; CLEAN & PREPARE SUB-FLOOR SURFACE
FOR NEW FLOORING PER RENOVATION PLANS.
2.08 DEMOLISH EXISTING WATER CLOSET AND ASSOCIATED PLUMBING. SEE PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION
2.09 DEMOLISH EXISTING BATHROOM PARTITION IN ITS ENTIRETY
2.10 DEMOLISH EXISTING LAVATORY AND ASSOCIATED PLUMBING. SEE PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION
2.12 DEMOLISH EXISTING MOP SINK AND ASSOCIATED PLUMBING. SEE PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION.
2.13 DEMOLISH EXISTING SHOWER, SHOWER PAN AND ASSOCIATED PLUMBING. SEE PLUMBING
DRAWINGS FOR ADDITIONAL INFORMATION.
2.14 DEMOLISH EXISTING CLINICAL SERVICE SINK IN ITS ENTIRETY. SEE PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION.
2.16 EXISTING ALUMINUM SLIDING DOOR TO BE REMOVED AND SALVAGED IN ITS ENTIRETY.
2.17 REMOVE ALL EXISTING HEADWALL UNIT AND ACCESSORIES, EXCEPT 1. CONTRACTOR TO
SALVAGE 1 HEADWALL UNIT AND ACCESSORIES, COORDINATE WITH VA.
2.21 DEMOLISH EXISTING ELECTRICAL CLOSET AFTER NEW ELECTRICAL CLOSET AND ASSOCIATED
WIRING HAS BEEN ESTABLISHED. REFER TO ELECTRICAL DRAWINGS.
2.37 DEMOLISH EXISTING WINDOW IN ITS ENTIRETY.
2.39 DEMOLISH FURRING AROUND ALL COLUMN PROTRUSIONS AS NEEDED.
2.40 DEMOLISH EXISTING HANDRAILS/BUMPER GUARDS AND PREPARE FOR NEW
HANDRAILS/BUMPER GUARDS.
2.52 DEMOLISH EXISTING DOOR DURING PHASE 6 CONSTRUCTION.
2.53 REMOVE GYPSUM BOARD ON EXISTING EXTERIOR WALL IN EFFORTS TO DEMOLISH EXISTING
ELECTRICAL AND DATA LOCATIONS. PREPARE FOR NEW ELECTRICAL AND DATA TO BE
INSTALLED.
2.54 DEMOLISH EXISTING DOOR PRIOR TO THE WORK IN THIS AREA OCCURS.
STAIRWELL
S18
1 2 3 4 5 6 7
A
B
C
D
E
F
G
H
BULK
STORAGE
V3-629
SCOPE
STORAGE
V3-628
SCOPE
PROCESSING
V3-624A
DECON
V3-624B
ANTE-ROOM
V3-624
CORRIDOR
C3-62
BREAK ROOM
V3-621
OFFICE
V3-627
EQUIP. ROOM
V3-632EQUIP. ROOM
V3-634
STERILIZERS
V3-636
PREPARATION
AND
ASSEMBLY
V3-635
LOCKER
ROOM. MALE
V3-619
LOCKER
ROOM,
FEMALE
V3-637
EQUIPMENT
STORAGE
V3-638
STORAGE
V3-640
ANTI-ROOM
V3-639
TOILET
V3-642A
SOILED
RECEIVING
V3-641
CORRIDOR
C3-64
NURSE
STATION
V3-770
JAN. CLOSET
V3-643
CONFERENCE
ROOM
V3-775
ELEC.
CLOSET
V3-780
TOILET,
STAFF
V3-778
OFFICE
V3-782
LOCKER
ROOM, STAFF
V3-785
SHOWER /
TOILET, MALE
V3-785B
MEDICAL ON
CALL
V3-612
TOILET
V3-731
MEDICAL ON
CALL
V3-619
STORAGE
V3-618
CORRIDOR
C3-61
OFFICE
V3-615
EDUCATION
ROOM
V3-614
SUPPLY
ROOM
V3-612
CLEAN
UTILITY
V3-611
PANTRY/BREAK
ROOM
V3-702
SOILED
UTILITY
V3-706
STORAGE
V3-610
TOILET
V3-613
CORRIDOR
C3-60
OXYGEN
CYLINDERS
V3-616
HOSPITAL
WORK ROOM
V3-707
BIOMED
NETWORK
CLOSET
V3-734
CLEAN
UTILITY
V3-719
SUPPLY
ROOM
V3-736
SHOWER
ROOM
V3-605A
PATIENT
ROOM
V3-602
SHOWER
ROOM
V3-602A
SHOWER
ROOM
V-601
DRUG
STORAGE
V3-781
PANTRY
V3-779
CLEAN LINEN
V3-777
SOILED
HOLDING
V3-784
NURSE
STATION
V3-757
SOILED
UTILITY
V3-747
TOILET
V3-756
SOILED
UTILITY
V3-774
TOILET
V3-772
CORRIDOR
C3-74
ANTEROOM
V3-766A
ANTEROOM
V3-767A
STAIR 17
S17
I.C.U.
STORAGE
V3-753
JAN. CLOSET
V3-752
ANTE-ROOM
V3-718
ANTE-ROOM
V3-715A
NURSES
STATION
V3-724
PANTRY
V3-746
SOILED
UTILITY
V3-748
NURSES
STATION
V3-600
ELEVATOR
LOBBY
E3-V
OFFICE
M3-395
STAIR 16
S16
JAN. CLOSET
V3-626
SHOWER
ROOM
V3-606A
PATIENT
ROOM
V3-766
PATIENT
ROOM
V3-767
PATIENT
ROOM
V3-768
PATIENT
ROOM
V3-769
BREAK ROOM
V3-773
CLEAN
UTILITY
V3-776
TOILET
V3-617A
TOILET
V3-633A
STAFF
V3-733
MEDICAL ON
CALL
V3-741
TOILET
V3-738A
BREAK ROOM
V3-738
ELEC.
V3-740
CORRIDOR
V3-742
ROOM
V3-722
ROOM
V3-723
OFFICE
V3-744
NURSES
STATION
V3-725
STAIR 18
S18
EQUIPMENT
WASHROOM
V3-633
STORAGE
V3-630
STERILE
PROCESSING
V3-635
ANTE-ROOM
V3-768A
PATIENT
ROOM
V3-603
PATIENT
ROOM
V3-604
PATIENT
ROOM
V3-605
PATIENT
ROOM
V3-606
PATIENT
ROOM
V3-607
PATIENT
ROOM
V3-608
PATIENT
ROOM
V3-609
PATIENT
ROOM
V3-708
PATIENT
ROOM
V3-709
PATIENT
ROOM
V3-710
PATIENT
ROOM
V3-711
PATIENT
ROOM
V3-712
PATIENT
ROOM
V3-713
PATIENT
ROOM
V3-714
PATIENT
ROOM
V3-715
PATIENT
ROOM
V3-716
PATIENT
ROOM
V3-717
MECH. ROOM
V3-613
PATIENT
ROOM
V3-758
PATIENT
ROOM
V3-759
PATIENT
ROOM
V3-760
PATIENT
ROOM
V3-761
PATIENT
ROOM
V3-762
PATIENT
ROOM
V3-763
PATIENT
ROOM
V3-765
PATIENT
ROOM
V3-764
CORRIDOR
C3-71
CORRIDOR
C3-70
CORRIDOR
C3-36
ELEVATOR
NO. 11
E11
ELEVATOR
NO. 12
E12
ELEVATOR
NO. 22
E22
CORRIDOR
C3-63
CORRIDOR
C3-76
CORRIDOR
C3-75
CORRIDOR
C3-77
CORRIDOR
C3-73
JAN. CLOSET
V3-620
MEDICAL ON
CALL
V3-617
SHOWER /
TOILET,
FEMALE
V3-785A
ROOM
V3-771
NURSE
STATION
V3-783
NURSE
STATION
V3-755
NURSE
STATION
V3-631
EXTENTS OF WORKEXTENTS OF WORK
EXTENTS OF WORKEXTENTS OF
WORK
EXTENTS OF WORKEXTENTS OF WORK
192'-0"
32'-0" 32'-0" 32'-0" 31'-7 1/2" 32'-4 1/2" 32'-0"
8'
-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
2.332.332.33 2.33
2.332.332.332.33
2.33
2.422.42
2.422.422.422.422.422.422.422.422.422.422.422.42 2.422.422.42
2.42
2.422.42 2.44
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
KEY PLAN - LEVEL 3
N
EXIT LIGHT
EXISTING 2' x 2'
ACOUSTICAL CEILING TO
BE DEMOLISHED
EXISTING GYPSUM
BOARD CEILING TO BE
DEMOLISHED
EXISTING 2 x 2 LIGHT
FIXTURE TO BE
DEMOLISHED
CEILING HEIGHT, ABOVE
FINISH FLOOR
EXISTING RECESSED
CAN LIGHT TO BE
DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE
DEMOLISHED
00'-00"
DEMOLITION REFLECTED CEILING PLAN LEGEND
EXISTING 2' x 4'
ACOUSTICAL CEILING
TO BE DEMOLISHED
RETURN AIR GRILLE
EXISTING SUPPLY AIR
DIFFUSER TO BE
DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE
DEMOLISHED
AREA NOT IN CONTRACT
REFERENCE LOCATION FOR
FRP REINFORCING. REFER
TO STRUCTURAL.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:1
A
M
DEMOLITION REFLECTED CEILING PLAN
- LEVEL 3
KJW 42 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD005
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 3 - DEMOLITION REFLECTED CEILING PLAN1
KEYNOTE LEGEND
2.33 REMOVE PATIENT LIFT SYSTEM IN ITS ENTIRETY.
2.42 REMOVE PATIENT CURTAIN TRACKS IN ITS ENTIRETY.
2.44 DEMOLISH EXISTING FURR DOWN IN ITS ENTIRETY.
STAIRWELL
S18
INTERSTITIAL SPACE
V4-610
UPS
V4-650
1 2 3
D
E
F
5'-2"
4' -1
0" 1'
-8
2.05
O P
E N
4' -6
/2
OPEN
5'-11" 5'-7"
STAIR 18
S18
28265 SF
INTERSTITIAL
SPACE
V4-610
78 SF
UPS
V4-650
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
10" 2'-9"
1' -3
4'
-5
5"
2.19
2.19
2.26
2.27
11'-6"
2.38
2.38
2.38
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING HANDRAILS AND WALL BUMPERS ON WALLS ARE
REMOVED UNLESS OTHERWISE NOTED.
5. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE KCVA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
6. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
7. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
8. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
9. NO WORK TO BE DONE IN AREAS SHOWN AS SOLID GRAY IN PLANS, HOWEVER WORK MIGHT NEED
TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER.
10. CEILINGS AND WALLS TO BE REMOVED AS NEEDED TO INSTALL NEW STRUCTRUAL MEMBERS. ALL
CEILINGS AND WALLS THAT ARE REMOVED NEED HEIGHTS, MATERIALS, AND DEVICES
DOCUMENTED PRIOR TO REMOVAL. ALL ROOMS TO MATCH EXISTING AFTER INSTALL OF
STRUCTURAL MEMBERS.
11. CONTRACTOR TO PROVIDE NEW DRYWALL AT ALL DEMOLISHED WALLS, EQUIPMENT OR NEW
INSTALLTION OF ELECTRICAL AND MECHANICAL ITEMS ALONG EXTERIOR WALLS.
12. CONTRACTOR TO REMOVE AND SALVAGE ALL CABLE TRAYS AND RETURN TO THE VA.
13. CONTRACTOR TO REMOVE ALL FURR DOWN WITHIN IN AREA OF SCOPE IN THEIR ENTIRETY.
14. CONTRACTOR SHALL COORDINATE WITH VA PRIOR TO DEMOLISH WORK AND REMOVAL OF VA
OWNED EQUIPMENT AND ACCESSORIES. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE 7 DAYS
PRIOR TO COMMENCEMENT OF DEMOLITION IN IN-SCOPE OF WORK AREAS. THIS IS TO
FACILITATE THE VA IN SALVAGING ANY EQUIPMENT.
15. ALL CONSTRUCTION PHASING TO BE COORDINATED WITH THE KANSAS CITY VA COR FOR WORK
RELATED TIMES FOR DAY, NIGHT, AND WEEKEND WORK. ALL 2ND LEVEL CONSTRUCTION TO BE
DONE BETWEEN THE HOURS OF 4:00 PM & 9:00 PM CST FOR NOISE RELATED WORK.
GENERAL DEMOLITION NOTES
EXISTING DOOR & FRAME TO
BE DEMOLISHED IN ITS
ENTIRETY
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING WALL TO BE
DEMOLISHED IN ITS
ENTIRETY
EXISTING WALLS TO
REMAIN
1 2 3
D
E
F
ANTEROOM
V5-632
STAFF WORK
ROOM
V5-635
CLEAN
UTILITY
V5-636
SOILED LINEN
V5-637
STORAGE
V5-641
STAIR 18
S18
SOILED
WORKROOM
V5-646
CLEAN
WORKROOM
V5-645
CORRIDOR
C5-66
VACANT
V5-650
VACANT
V5-650
OPERATING
ROOM 2/3
SCRUB
V5-701
2.05
4' -6
/2
5"
4' -5
1'
-3
5'-11" 5'-7"
5'-2"
4' -1
0" 2'
-1 0"
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
2'-10"
2.27
2.02
7' -7
/2
5' -8
1'
-2
/2
CORRIDOR
C5-73
CORRIDOR
C5-70
1 2 3
D
E
F
2.27
2.05
F
E
D
2 3
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
2.26
2.19
STAIR 18
S18
2.38
2.38
2.38
1 2 3
D
E
F
P.A.C.U.
V5-630
STAFF WORK
ROOM
V5-635
CLEAN
UTILITY
V5-636
SOILED LINEN
V5-637
STORAGE
V5-641
STAIR 18
S18
SOILED
WORKROOM
V5-646
CLEAN
WORKROOM
V5-645
CORRIDOR
C5-66
STORAGE
V5-650
VACANT
V5-650
OPERATING
ROOM 2/3
SCRUB
V5-701
F
E
D
2 3
64'-0"
32'-0" 32'-0"
'-0
'-0
'-0
2.26
2.27
EXIT LIGHT
EXISTING 2' x 2'
ACOUSTICAL CEILING TO
BE DEMOLISHED
EXISTING GYPSUM
BOARD CEILING TO BE
DEMOLISHED
EXISTING 2 x 2 LIGHT
FIXTURE TO BE
DEMOLISHED
CEILING HEIGHT, ABOVE
FINISH FLOOR
EXISTING RECESSED
CAN LIGHT TO BE
DEMOLISHED
EXISTING 2 x 4 LIGHT
FIXTURE TO BE
DEMOLISHED
00'-00"
DEMOLITION REFLECTED CEILING PLAN LEGEND
EXISTING 2' x 4'
ACOUSTICAL CEILING
TO BE DEMOLISHED
RETURN AIR GRILLE
EXISTING SUPPLY AIR
DIFFUSER TO BE
DEMOLISHED
EXISTING EXHAUST AIR
GRILLE TO BE
DEMOLISHED
AREA NOT IN CONTRACT
REFERENCE LOCATION FOR
FRP REINFORCING. REFER
TO STRUCTURAL.
KEY PLAN - LEVEL 4
N
KEY PLAN - LEVEL 5
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MISSOURI ARCHITECTURAL COA EXP. 12/31/2024
MISSOURI ENGINEERING COA EXP. 12/31/2024
STRUCTURAL / CIVIL ENGR
H2B
1225 N. LOOP WEST, STE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
11140 S. TOWNE SQ., STE 100
ST. LOUIS, MO 63123
(713) 864-2900
TELECOMMUNICATION
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
HEALTHCARE PLANNER
THE INNOVA GROUP
9442 N. CAPITAL OF TX HWY
AUSTIN, TX 78759
(512) 346-8700
/1
/2
:3
:5
A
M
DEMOLITION PLANS - LEVEL 4 AND 5
KJW 43 OF 155AJS
100% ISSUED FOR BID
EXPAND SPS - KCVAMC
04/17/2024
589-22-885
KANSAS CITY VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
AD006
SPUR #: 2205
N
1/8" = 1'-0"
LEVEL 4 - DEMOLITION PLAN1
KEYNOTE LEGEND
2.02 REMOVE WALL AS REQUIRED FOR NEW CONSTRUCTION
2.05 SAW CUT EXISTING SECOND FLOOR SLAB FOR NEW DUMBWAITER OPENING. SEE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2.19 EXISTING DUMBWAITERS, ACCESSORIES AND HOISTWAYS TO BE REMOVED IN THEIR
ENTIRETY.
2.26 EXISTING SLAB OPENING TO BE INFILLED. REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
2.27 EXISTING SLAB OPENING TO REMAIN.
2.38 EXISTING LOUVERS TO REMAIN.
N
1/8" = 1'-0"
LEVEL 5 - DEMOLITION PLAN2
N
1/8" = 1'-0"
LEVEL 4 - DEMOLITION REFLECTED CEILING PLAN3
N
1/8" = 1'-0"
LEVEL 5 - DEMOLITION REFLECTED CEILING PLAN4
B
C
D
E
F
G
H
ROOF BELOW - SECOND FLOOR
SLOPESLOPE
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
STAIR 18
S18
PASSAGE
V6-746
MECHANICAL
V6-745
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
STRUCTURAL
SLOPE
S T
R U
C T
U R
A L
S
LO
P E
S T
R U
C T
U R
A L
S
LO
P E
S T
R U
C T
U R
A L
S
LO
P E
S T
R U
C T
U R
A L
S
LO
P E
S T
R U
C T
U R
A L
S
LO
P E
SLOPESLOPE
32'-0" 32'-0" 32'-0" 31'-11" 32'-1" 32'-0"
'-0
'-0
'-0
'-0
'-0
'-0
'-0
2.26
192'-0"
8'
-0
PANELS
V6-744
EXISTING AHU
TO REMAIN
EXISTING
TO REMAIN
EXISTING
TO REMAIN
EXISTING
TO REMAIN
EXISTING
TO REMAIN
EXISTING
TO REMAIN
2.41
2.412.41
2.41
EXISTING
TO REMAIN
EXISTING
TO REMAIN
2.43
2.43
2.43
2.43
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA…