These are mechanical and electrical engineering design drawings for a VA Medical Center infrastructure improvement project at the Dayton, Ohio location. The comprehensive set of drawings includes detailed schematics for HVAC systems, hydronic piping, steam systems, electrical distribution panels, motor schedules, and lighting fixture specifications. Key technical components include energy recovery ventilators, air-cooled chillers, hot water converters, fan coil units, steam pressure reducing valves, and electrical panels with load calculations. The drawings are prepared by Heapy Engineering for Guidon Design and are part of VA Project Number 2018-05164, specifically addressing infrastructure deficiencies in Building 408 at the Dayton VA Medical Center.
The drawings provide extensive technical specifications for mechanical and electrical systems, including precise details on equipment locations, performance characteristics, control sequences, and installation requirements. Notable elements include schematic diagrams for heating and chilled water systems, steam piping configurations, control panel point lists, motor and starter schedules, and electrical distribution panel layouts. The documentation appears comprehensive, covering everything from individual component specifications to overall system integration, with clear annotations and technical notes to guide installation and maintenance.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ACCESS PANEL AND DOOR DETAIL
HORIZONTAL PIPE ANCHOR DETAIL
SUPPORT/ANCHOR FOR PIPE RISERS PIPE HANGERS
HANGER STRAPS OR RODS
ROUND DUCT HANGERS
VOLUME DAMPER DETAIL
CHILLER PAD DETAIL
EXTERIOR PIPE STANCHION DETAIL
SECTION THRU FIRE DAMPER INSTALLATION
CONCRETE EQUIPMENT BASES
ACCESS SECTION FOR ROUND/OVAL DUCT
SECTION "A-A"
"B" "B"
"A"
"A"
INSULATION
INSULATION
GASKET
DUCT
INSULATION
SECTION "B-B" FACTORY
FABRICATED
LATCH
FLEXIBLE
WASHER
HANDLE INSIDE
GASKET
CASING
ACCESS DOOR
ACCESS PANEL
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
RISER CLAMP
RISER CLAMP
PIPE SLEEVE WHERE
ANCHOR POINTS ONLY
CLAMP REQUIRED AT
RISER CLAMP. BOTTOM
BOLT (TYPICAL)
INSULATION
FIRE-STOPPING
WOOD FLOOR
MATERIAL
BOLT
ELEVATION
PLAN
RISER
SPECIFIED
BOLT
WHERE SPECIFIED
PIPE SLEEVEPIPE
INSULATE ANCHOR AS INDICATED FOR COLD PIPING.
AND INSULATION THICKNESS
CUT TO SUIT PIPE DIA.
NOTE:
INSULATION
3/8" PLATE
PIPE & PIPE & INSULATION
1/2" U-BOLT
BASE PLATE
3/8"
WELD
STRUCTURAL CHANNEL
ANCHOR BOLTS,
MIN. SIZE 5/8"
STRUCTURE
2 AT EACH PLATE.
OR ANGLES
(2"x2"x1/4")
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
M A
X
FT.
FT.
IN.
TUBING
PIPE
NOM. SIZE
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
SADDLE
WELD
1/2" DIA. HANGER
RODS WITH 36" MAX.
SPACING ON EACH
CHANNEL
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
BAND
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
ADJUSTABLE CLEVIS HANGER TYPE 43 -
SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 1 -
SEE SPECIFICATIONS
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. UNIFORM LOAD
420ONE 1 x 18 GA. STRAP36
TWO 1/2 DIA. RODS
TWO 3/8 DIA. RODS
ONE 1 x 16 GA. STRAP
50 700
ONE 1 x 22 GA. STRAP
QUANTITY/SIZEMAX. DUCT
MAX. LOAD
LBS.
MAX.
IN.
SPACING
DIA. - IN. IN.
50" DIA. &
UNDER
LOAD RATED
FASTENERS
BAND OF SAME SIZE
AS HANGER STRAP
HANGER RODS
OVER 50"DIA.
BAND
1/8" CLEARANCE ALL
AROUND SECTIONSIDE ELEVATION
STIFFEN BLADE AS
REQUIRED
DUCT
1/2" ROUND ROD PIN
INSULATION
STAND-OFF
HANDLE WITH LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
DAMPER BLADE
INSULATION SEE
SPECIFICATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTES:
1.
2.
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
3/4" CHAMFER
(2) #5 BARS CONTINUOUS
TOP AND BOTTOM
FINISH GRADE
TYP. ALL FOUR SIDES
1'-0"
CAST SLAB AND
THICKENED EDGES
TOGETHER IN ONE
POUR
6x6-W2.9xW2.9
WELDED WIRE FABRIC
PIPE ROLLER SUPPORT
HEIGHT WITH EQUIPMENT ACCESS
AND CONNECTION LOCATIONS.
3' DEEP
POURED CONCRETE
COORDINATE EXACT
3'-0"
PIPING
GRADE
8"
16" DIA.
CHILLED WATER
C4x7.25
CONTINUOUS WELD PIPE
TO CHANNEL (TYPICAL)
2.5 SCHEDULE 40 PIPE
8"x8"x1/2" BASE PLATE
EPOXY GROUT
(4)1/2" DIA. GALVANIZED
ADHESIVE ANCHORS
ACCESS
PANEL
NOTE 5
PERIMETER ANGLE, NOTE 3
(NOT FASTENED TO PARTITION)
TYPICAL DUCT
INSULATION
FIRE BARRIER
PARTITION OR CHASE
NOTE 6
SLEEVE, NOTE 2
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
DAMPER,
NOTE 1
DUCT
CONNECTION
NOTE 4
SLEEVE, NOTE 2
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES
FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE
PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" , 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR
LINKS.
PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. IN ORDER TO MAINTAIN U.L.
RATING FOR FIRE DAMPER, DO NOT FILL THIS OPEN SPACE WITH FIRESTOP MATERIAL.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
NOTES:
1.
2.
3.
4.
5.
6.
7.
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
PLAN
TYPICAL ANCHOR
BOLT NUT & WASHER
SECTION B-B
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12" O.C. EACH
WAY IN THE BASE & DOWEL BASE
TO FLOOR
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
WELD HEAD TO PLATE
OR BEND OVER END 5D
FLOOR
PIPE SLEEVE (5D, 3" MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
NOTE:
L & W DIMENSIONS
SHALL BE 6" GREATER
THAN THE EQUIPMENT
BASE PLATE.
L
W
A
A
D
2D
16"
M
IN
L /1
M
IN
L /1
D
TYPICAL ANCHOR
BOLT NUT & WASHER
5D
B B
COVER WITH HANDLE
AND CHAIN RETAINER
GASKETED AND
PRESSURE SEALED
ROUND OR
FLAT OVAL
DUCT SECTION
HOUSING WELDED TO
DUCT SECTION
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M502
DETAILS CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
M
IN
[1 m m
0m m
0m m
[1 2"
M
IN
[6
M
IN
.]D
U C
T H
E
IG
H T
H1 /3
H
/3 H
/3
H
D
D
STRAINER
FS
TT TT
DIAPHRAGM EXPANSION TANK
TANK SADDLE
TO PUMP SUCTION
PITCH UP 1.6%
SLOPE (MIN.)
HANGER ROD
SUPPORTS (TYPICAL)
CONNECTOR PIPE
NORMALLY OPEN GATE
VALVE IN VERTICAL
(REMOVE HANDLE)
RUN DRAIN LINE TO
NEAREST F.D.
UNLESS INDICATED
OTHERWISE
FROM SYSTEM
AIR SEPARATOR
SEE NOTES NO.
3 & 4
DRAIN
COLD WATER FILL LINE.
SEE EXPANSION TANK
SCHEDULE FOR SIZE
NC
RUN DRAIN
LINE TO
NEAREST FD
REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
BUTTERFLY OR BALL
ISOLATION VALVE
HANGER
RODS (TYP)
AV
AUTOMATIC AIR VENT
NOTES:
1. SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.
2. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS SHOWN
ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY FOR HOT WATER HEATING.
3. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN EXPANSION TANK SCHEDULE.
4. FOR HOT WATER SYSTEMS 50mm [2"] AND SMALLER AND CHILLED WATER SYSTEMS USE
IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.
5 SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM HAS A
MINIMUM OF 28kPa. [4 PSIG]
NOTES:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO
TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.
2. PROVIDE BYPASS PIPING.
SEE DRAWINGS FOR PIPE SIZES
TO RETURN MAIN
SCHEDULE 80 STEEL PIPE
PIPE SIZE SHALL BE SAME SIZE AS TRAP
INVERTED BUCKET TRAP. SEE PLANS,
AND SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH
TRAP OR IN VERTICAL PLANE & BELOW TRAP
DRIP LEG OR EQUIPMENT CONNECTION. MAKE
THE SAME SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE NOTE 1
1" GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
STEAM
CONDENSATE
RETURN
TEMPERATURE
SWITCH
SCALE POCKET
HUMIDIFIER CONTROL
VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
INVERTED BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS
FOR FINAL LAYOUT
COOLING COIL
FAN-COIL UNIT, ERV PIPING
HEATING COIL
FAN-COIL UNIT, ERV. UNIT HEATER PIPING
INSTALLATION OF THERMOMETER WELLS
IN-LINE PUMPS - CONNECTIONS
TYPICAL STEAM LINE & DRIP PIPING
AIR COOLED CHILLER - PIPING CONNECTIONS
HORIZONTAL EXPANSION TANK -
PIPING CONNECTIONS
TO FIN TUBE RADIATORS
TYPICAL WATER PIPING CONNECTIONS
WATER FLOW MEASURING STATION
(WITH BTU METER) STEAM METER DETAILSTEAM LINE DRIP POCKET STEAM TRAP ASSEMBLY
STEAM PRESSURE REDUCING STATION
DOUBLE VALVE (1/3 AND 2/3)
STEAM SAFETY VALVE
INVERTED BUCKET STEAM TRAP
STEAM HUMIDIFIER PIPING
BALANCING
DEVICE
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALL OR BUTTERFLY TYP.
FLEXIBLE
CONNECTION
1/2" [15mm]
PRESSURE GAGE
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN) FOR
FIRST TWO ON EACH SIDE OF PUMP
(SEE NOTE NO. 1)
THERMOMETER
FLOW SWITCH
FLEXIBLE
CONNECTORS
IF REQUIRED
TEST PLUGS
CHS
EVAPORATOR
CHR
DDC
TEMPERATURE
SENSOR TO ECC
PRESSURE
GAUGE
UNDER CANOPY
AND FACTORY ASSEMBLED.
SAME SIZE AS RUNOUT PIPING
FLOW CONTROLLER WITH INTEGRAL
PRESSURE-TEMPERATURE TEST
CONTROL VALVE. REFER TO FAN COIL
PRESSURE-TEMPERATURE TEST
AUTOMATIC - NORMALLY OPEN
MANUAL AIR VENT
SHUT-OFF VALVE
FLEXIBLE POLYETHYLENE TUBING.
3/4" CONDENSATE DRAIN PIPE.
CONNECT TO UNIT PAN WITH
UNIT DRAIN PAN
STRAINER
PLUG.
PLUG
COIL DRAIN PAN
COIL
UNION
COIL
MANUAL AIR VENT
AND FACTORY ASSEMBLED.
SAME SIZE AS RUNOUT PIPING
FLOW CONTROLLER WITH INTEGRAL
PRESSURE-TEMPERATURE TEST
PRESSURE-TEMPERATURE TEST PLUG
PLUG
STRAINER
SHUT-OFF VALVE
UNION
REDUCER, IF REQUIRED
REDUCER, IF REQUIRED
THREE-WAY VALVE.
UNIT SCHEDULE FOR TWO-WAY OR
CONTROL VALVE. REFER TO FAN COIL
AUTOMATIC - NORMALLY OPEN
THREE-WAY VALVE..
UNIT SCHEDULE FOR TWO-WAY OR
2 1/2" DIA.
HORIZONTAL
2" DIA. & SMALLERABOVE 2" DIA. PIPE
2 1/2" DIA.
VERTICAL
2" DIA. & SMALLERABOVE 2" DIA. PIPE
STEAM TRAP ASSEMBLY
GLOBE VALVE
NC
12" MIN.
SAME SIZE AS MAIN
NOTES :
STEAM MAIN
BACK 1/4" PER FOOT.
6" MIN.
SET - SEE DETAIL ON
THIS SHEET.
INVERTED BUCKET TRAP
LP & GRAVITY
RETURN
HP & MP RETURN
UNTRAPPED RUNOUT. SLOPE
ECCENTRIC REDUCERS (BOTTOM FLAT)
ARE REQUIRED FOR ALL REDUCTIONS
IN SUPPLY STEAM PIPES
SEE STEAM TRAP ASSEMBLY
DETAIL ON THIS SHEET
S C
A L E
P O
C K
E T
S C
A L E
P O
C K
E T
D R
IP
L
E G
D R
IP
L
E G
BYPASS - INSTALL IN HORIZONTAL PLANE
LEVEL WITH TRAP OR IN VERTICAL PLANE
AND BELOW TRAP.
TO RETURN MAIN - SEE
DRAWINGS FOR PIPE SIZES
DIELECTRIC FITTING
(WHERE METAL
MATERIALS ARE
DISSIMILAR)
CHECK VALVE
GATE VALVE (TYP.)
STRAINER
FLOAT AND THERMOSTATIC OR INVERTED
BUCKET TRAP (SEE PLANS & LEGEND)
3/8" TEST CONNECTION
DRIP
RETURN
FROM DRIP LEG
OR EQUIPMENT
CONNECTION
PIPE SIZES SAME AS CONNECTION ON
TRAP - 3/4" MIN.
STEAM LINE DRIP POCKET
NOTE:
DRIP LEG PIPE SIZE SAME AS
STEAM MAIN UNLESS
OTHERWISE NOTED.
PIPE T0 STEAM
TRAP (TYPICAL)
CAP (TYPICAL)
STEAM LINE
(TYPICAL)
3/4" DRAIN (ALTERNATE
LOCATIONS) (TYPICAL)
DRIP LEG (TYP.)
M
IN
M
M
M
IN
NOTES:
A. PROVIDE DIELECTRIC FITTING WHERE COPPER TUBING AND
FERROUS METAL PIPES ARE JOINED.
B. SUPPORT PIPING AND EQUIPMENT INDEPENDENTLY. EQUIPMENT
SHALL NOT BE USED TO SUPPORT PIPING.
NOTES:
A. PROVIDE DIELECTRIC FITTING WHERE COPPER TUBING AND
FERROUS METAL PIPES ARE JOINED.
B. SUPPORT PIPING AND EQUIPMENT INDEPENDENTLY. EQUIPMENT
SHALL NOT BE USED TO SUPPORT PIPING.
HEATING ELEMENT(S)
TEST PLUG
STRAINER
BALL VALVE
CABINET
UNION OR SOLDER
CONNECTION TYPICAL
AUTOMATIC FLOW CONTROL VALVE
EXISTING FLOOR
SLAB
CONTROL VALVE
DIELECTRIC UNION IF METALS DISSIMILAR
HWR
HWS
INTERFACE WITH
BUILDING CONTROLLER
RETURN
BTUH METER
WITH BACNET
INTERFACE
NOTE:
1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES
NOTE:
1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURERS
TT
PT
PRESSURE
TRANSMITTER
TEMPERATURE
TRANSMITTER
FLOW METER
INTERFACE
WITH BACNET
SYSTEM
DIFFERENTIAL PRESSURE (DP) CEL
STEAM FLOW MEASUREMENT
SHUTOFF VALVE
TO METERING
SYSTEM
BUILDING INCOMING
MAIN STEAM
SUPPLY
FLOW ELEMENT
TEMPERATURE ELEMENT
TE
TEFE
V
NOTE:
SIPHON
(TYP.)
PILOT CONTROL LINE
REDUCER (TYP.)
IF REQUIRED.
NOTE 1
D1
N.C.
D2
D2
4 D2 MIN.
20 D2 MIN.10 D1 MIN.
NOTE 1
NOTE 3
INVERTED
BUCKET TRAP
ASSEMBLY TYP.
STEAM SAFETY VALVE
D
PROVIDE UNION UNLESS SAFETY
VALVE HAS FLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TO PRESSURE
VESSEL OR PIPE
VENT FULL SIZE PIPE THROUGH
ROOF SUPPORT AS INDICATED
ON DWGS. (NOTES 1, 2)
PIPE THREADED INTO ELBOW
(SAME SIZE AS ELBOW)
DRIP PAN ELBOW
(SECTIONAL VIEW)
3/4" DRAIN TO FLOOR
DRAIN OR OPEN
SIGHT DRAIN (NOTE 4)
M
IN
24" MAX.
3"
ELEVATION
NOTES:
FLEXIBLE
CONNECTOR
PIPE SHALL BE FULL SIZE OF
SAFETY RELIEF VALVE DRIP
PAN ELBOW OUTLET. VENT TO
ATMOSPHERE (OUTDOORS).
1 SLOPE MAINS AND BRANCHES DOWN 1" PER 40 FEET IN DIRECTION OF
FLOW UNLESS SHOWN OTHERWISE.
2 LIMIT UNTRAPPED, COUNTERFLOW, RUNOUTS TO 10 FEET MAXIMUM.
3 END OF MAIN SHOWN, LOW POINT IN STEAM MAIN SIMILAR.
1. SEE PIPING SCHEMATIC FOR PIPE SIZES.
2. SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2. INSTALL
VALVES AS RECOMMENDED BY MANUFACTURER.
3. MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST PRV.
4. PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED
CONNECTIONS.
1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT
BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN ANSI
B31.1. POWER PIPING CODE, APPENDIX II.
2. VENT PIPE SHALL TERMINATE 6' MIN. ABOVE FINISHED ROOF.
3. DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHICH
PERSONNEL MAY OCCUPY.
4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M503
DETAILS CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
SCALE: NONE
4"
HWR
50 PSI
FLOOR
H W
S
4"
4"
-H W
A S
0.75"
EXTEND TO FLOOR DRAIN
1.25"
FUNNEL
0.5"1.25"
4"
0.75"
408-HWF1
0.75"
HWS
4"
HWR
FLOOR
4"
4"
H W
S
1 THERMOSTATIC AIR VENT.
2 SEE DETAIL ON SHEET M503.
3 PROVIDE LOW WATER LEVEL ALARM. PROVIDE A LOW
WATER LEVEL AT ECC. RELIEF VALVE DRAIN SHALL
4 EXTEND SAFETY RELIEF VALVE DISCHARGE TO
5 CONVERTER SHALL BE SUSPENDED HIGH ENOUGH
TO ALLOW GRAVITY DRAINAGE OF CONDENSATE .
6 PROVIDE BACK PRESSURE REGULATING VALVE.
SET REGULATING VALVE TO MAINTAIN MAKE-UP
7 PROVIDE SADDLE SUPPORTS AND ANGLE FRAME.
8 WALL MOUNTED "ON-OFF" MOTOR CONTROL.
9 PROVIDE 0.75" HOSE CONNECTION AND SCREW-ON CAP.
10 ALLOW SPACE FOR INSULATING FILTER AND PIPING.
11 INSTALL TOP OF CHEMICAL POT FEEDER TANK NO MORE
THAN 3'-0" ABOVE FLOOR.
12 MAKE-UP PIPING SYSTEM DOES NOT REQUIRE INSULATION.
13 CONCRETE PAD.
14 AUTOMATIC LINE SIZE ISOLATION CONTROL VALVE.
15 FLEXIBLE PIPE CONNECTION.
16 MANUAL AIR VENT WITH SHUT-OFF VALVE.
17 PROVIDE GLYCOL-WATER MAKE-UP PUMP 5 GPM @ 30 PSIG.
CHEMICAL
POT FEEDER
AUTOMATIC
FLOW CONTROL
VALVE.
MANUAL AIR VENT
4"
9 0.75"
1" 9 1"
FROM SYSTEM
FLOOR
PRESSURE GAGE
0.5"
408-CWP2
WALL SLEEVE
PROVIDE ALUMINUM JACKET
AND HEAT TRACE ON ALL
EXTERIOR PIPING
CHR
(TYPICAL)
5"
0.5"
5"
GRADE
15 16
CHS
408-ACCH2
4"
WALL
CHS
TO SYSTEM
5"
CHS
C H
R
PRESSURE GAGE
0.5"
0.75"
0.75"
408-C2
2.5"
2.5"
75 PSI
HWS
HWR
408-C3
HWR
HWS
THERMOMETER
PRESSURE GAGE
408-HWP1
0.5"
5 7
1 14 2.5"
75 PSI
2.5"
D
CHS
5"
RETURN TO TANK AS SHOWN ON THIS DETAIL.
PRESSURE AT 15 PSIG (103 kPa) ABOVE HIGHEST
SYSTEM PRV SETTING.
SUPPORT HEAT EXCHANGER OFF FLOOR.
FLOOR DRAIN.
OPERATE PUMP MANUALLY AS REQUIRED TO FILL.
18 SUSPEND UNIT FROM STRUCTURE.
EXPANSION TANK
408-CWAS1
0.75" 12
0.75"12
55 GALLON GLYCOL-WATER
STORAGE TANK
408-GCWP1
FROM SYSTEM
TO SYSTEM
408-C1
2.5"
2.5"
75 PSI
HWR
HWS
0.5"
15 16
13 9 5"
408-HWP2
9 9
CHR
4" 5"
CHS
4"
408-ACCH1
PREFABRICATED
UNDERGROUND PIPING
19 WALL MOUNTED "ON-OFF" MOTOR CONTROL.
20 0.75" DOMESTIC COLD WATER.
21 HOSE BIB FOR MANUAL MIXING OF GLYCOL WHEN REQUIRED.
0.75"
DCWPRESSURE GAGE
0.5"
408-CWP1
408-BT1
5"
5"
5" 5" 0.75"
EXTEND TO FLOOR DRAIN
1.25"
FUNNEL
0.5" 1.25"
0.75"
408-CWF1
0.75"
11CHEMICAL
POT FEEDER
AUTOMATIC
FLOW CONTROL
VALVE.
90.75"
0.75"
0.75"
CHR
TE
TEFE
TE
TEFE
V
22 VACUUM BREAKER.
V
V
THERMOMETER
THERMOMETER
23 DEVICES PROVIDED FOR BTU METER.
NOTES
HEATING HOT WATER SYSTEM SCHEMATIC
CHILLED WATER SYSTEM SCHEMATIC
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M504
HYDRONIC PIPING SCHEMATICS CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
VENT TO OUTSIDE OF BUILDING
FLOORBASEMENT
FLOOR
CONTROL
CABINET
V
408-CP1
1.5"
LPR
2"
3"
408-C2
M P
S
M P
R
HWR
HWS
12" MIN.
6" MIN.
408-C3
M P
S
M P
R
HWS
HWR
12" MIN.
6" MIN.
HPS (125)
3"
MPRMPR
MPS (30)
V
V
V
PC
VV
2.5"
2.5"
2"
2.5"
2.5"
2"
4"
4"
3"
2.5"
3"
4"
3"
4"
4 4
4"
17 18
17 18
17 18
21 17 18
2"
3"
2.5"
3"
0.75"
2 15
2"
3"
2.5"
3"
0.75"
M P
R
17 18
V
4" 29
N.C.
V
TO FLOOR
DRAIN
2"
2"
2"
2" 2"
408-PRV1B
408-PRV1A
V
40 PSI
HPR
0.75"
3"
3"
2"
3" 4"
3"
4"
4"
4"
3"
17 18
17 18
3"
H P
R
MPS (30)
HPR
PIPE WITH 1/4" PERFORATIONS SHALL
EXTEND FULL LENGTH OF TANK AND SHALL
BE SAME DIAMETER OF CONDENSATE RETURN
CONNECTION TO TANK. TOTAL AREA OF ALL
1/4" PERFORATIONS SHALL BE EQUIVALENT
TO THE TRANSVERSE AREA OF THE PIPE.
408-FT1
DIELECTRIC FITTING
(WHEN RETURN IS COPPER)
4" MIN. BELOW WATER LINE
V
0.75"0.75"
WATER LINE (1" ABOVE
TANK CENTERLINE)
3"
0.75"
0.75"
408-C1
M P
S
M P
R
HWR
HWS
12" MIN.
6" MIN.
3"
17 18
17 18
2"
3"
2.5"
3"
0.75"
2 15
2.5"
2"
2"
2.5" 2.5"
GENERAL NOTES
A STEAM SYSTEM SHALL ONLY BE DOWN BETWEEN
THE MONTHS OF JUNE AND SEPTEMBER.
B REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS
AND ADDITIONAL GENERAL NOTES.
NOTES
1 THERMOSTATIC AIR VENT.
2 0.5 CHECK VALVE VACUUM BREAKER.
3 DIELECTRIC FITTING (WHERE RETURN IS COPPER).
4 EXTENT FULL SIZE STEAM VENT PIPE UP THRU ROOM.
TERMINATE 6 FEET ABOVE FINISHED ROOF LEVEL.
5 F&T TRAP ASSEMBLY. REFER TO DETAIL ON SHEET M503.
6 SCALE POCKET.
7 STEAM LINE DRIP ASSEMBLY WITH INVERTED BUCKET TRAP.
REFER TO DETAIL ON SHEET M503.
8 FULL SIZE DRAIN TO FLOOR DRAIN.
9 PROVIDE SADDLE SUPPORTS AND ANGLE FRAME TO SUPPORT
HEAT EXCHANGER OFF FLOOR. HEAT EXCHANGER SHALL BE
SUSPENDED HIGH ENOUGH TO ALLOW GRAVITY PRESSURE
GAUGE WITH SIPHON.
10 PRESSURE GAGE WITH SIPHON.
11 SPRING LOADED CHECK VALVE.
12 AUTOMATIC CONTROL VALVE. SIZE FOR 1/3 STEAM LOAD
CAPACITY.
13 FULL SIZE OVERFLOW DRAIN. TRAP, VENT AND PIPE TO FLOOR
DRAIN.
14 REFER TO HOT WATER SYSTEM SCHEMATIC ON SHEET M504.
15 AUTOMATIC CONTROL VALVE. SIZE FOR 2/3 STEAM LOAD
CAPACITY.
16 EXTEND TO EXISTING CAMPUS HIGH PRESSURE (125 PSI)
STEAM LINE. REFER TO FLOOR PLANS.
17 NORMALLY CLOSED BYPASS GLOBE VALVE.
18 INSTALL BYPASS IN HORIZONTAL PLANE LEVEL WITH TRAP OR
VERTICAL PLANE AND BELOW TRAP. DO NOT BLOCK ACCESS
FOR SERVICING TRAP.
19 PRESSURE-TEMPERATURE TEST PLUG.
20 PILOT CONTROL LINE.
21 SHUT-OFF VALVE WITH HOSE CONNECTION AND SCREW ON CAP.
22 SAFETY RELIEF VALVE WITH DRIP PAN ELBOW. SEE DETAIL ON
M502.
23 STEAM PRESSURE REDUCING STATION. SEE DETAIL ON SHEET
M502 AND SCHEDULE ON SHEET M 603.
24 30-300 DEG. F. THERMOMETER.
25 EXISTING LOW PRESSURE CONDENSATE TO ATTIC. CONVERT TO
MEDIUM PRESSURE CONDENSATE.
26 PROVIDE 5" HIGH CONCENTRATE EQUIPMENT BASE PER DETAIL ON
SHEET M502.
27 31 GALLON FLASH TANK. 16" DIA. x 36" LONG.
28 EXTEND TO EXISTING CAMPUS PUMPED CONDENSATE LINE.
REFER TO FLOOR PLANS.
29 ANTICIPATED SIZE SHOWN. COORDINATE WITH RELIEF VALVE
MANUFACTURER.
30 BAFFLE TYPE MOISTURE SEPARATOR.
31 EXISTING STEAM AND CONDENSATE PIPING TO BUILDING
PERIMETER HEATING SYSTEM.
32 PROVIDE ANGLE FRAME TO SUPPORT FLASH TANK AT A LEVEL
WHICH ALLOWS GRAVITY FLOW FROM HEAT EXCHANGER.
33 EXISTING LOW PRESSURE STEAM PIPE TO ATTIC. CONVERT TO
MEDIUM PRESSURE (30 PSI) STEAM.
34 DO NOT LIFT PIPING.
35 SLOPE PIPE BACK TO FLASH TANK.
36 NORMALLY CLOSED BYPASS VALVE.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M505
STEAM PIPING SCHEMATIC CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
DUCT CONSTRUCTION, SEALING, AND INSULATION
GENERAL NOTES:
A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR
INSULATION; FIBERGLASS DUCTBOARD; ETC.
B. DUCT CONSTRUCTION AND SEALING SHALL BE PER
LATEST S.M.A.C.N.A. STANDARDS.
NOTES:
1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.
2. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL / ROOF.
3. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS LONGITUDINAL SEAM.
DUCT SYSTEM
S.P. CON-
STRUCT.
SEAL
CLASS
LEAKAGE
CLASS
S.M.A.C.N.A. CLASS.
INTERNALLY
LINED
EXTERNAL
INSULATION
NOT
INSULATED
SEE
NOTE
DOUBLE
WALL
INSULATEDRECT RND
1,3
NOTE 3
+3" A 8
+1" 16
16 8
A
A
A
SUPPLY DUCTWORK UPSTREAM OF
VAV BOXES FOR AHU-
SUPPLY DUCTWORK DOWNSTREAM OF
VAV BOXES AHU-
RETURN DUCTWORK -2"
TOILET OR GENERAL EXHAUST
DUCTWORK
-1" 16 -
HVAC DESIGN DATA
GENERAL NOTES:
A. OUTDOOR DESIGN CONDITIONS:
90.4°F DB SUMMER
73.5°F WB SUMMER
2°F DB WINTER
NOTES:
1. LISTED RH IS MAXIMUM ANTICIPATED AT LISTED DB TEMPERATURE.
2. REFER TO ATC SEQUENCES FOR ACTUAL ROOM SETPOINTS.
3. LISTEN RH IS MINIMUM ANTICIPATED AT LISTED DB TEMPARTURE.
SPACE NAME / TYPE °F DB
INTERIOR DESIGN DATA
SEE NOTE
OFFICES 2
SUMMER WINTER
% RH
(NOTE 1) °F DB
% RH
(NOTE 3)
75 60 70 20
- - 68 -
81 60 64 30
75 60 70
75 60 70
80 - 60 -
BATHROOMS AND TOILET
ROOMS
DATA CLOSETS
CONFERENCE ROOMS
ALL OTHER SPACES
UNOCCUPIED MODE
B. DESIGN ALTITUDE: 1004 FT.
FOUR PIPE FAN COIL UNIT SCHEDULE
TYPE
1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.
2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.
NO.
UNIT
HEATING REQUIREMENTS WITH
180°F ENT. WATER TEMP.
GPM
COOLING REQUIREMENTS WITH
44°F ENT. WATER TEMP.
MIN.
MBH
TOTAL
FAN
CFM
MIN.
MBH
SENS.
ENT. AIR F°
WbDb
MAX. LOSS
FT. WATER
THRU COILGPM
AUTO
VALVE
TYPE
RUN-
SIZE
OUT
MIN.
MBH
ENT.
AIR
FAN MOTOR
AUTO
VALVE
RUN-
SIZE
OUT
W (QTY.)
NOM. HP
APPROXIMATE SIZE
L
VOLT.-
HW
NOTES
NOTES:
MAX. LOSS
THRU COIL
AUTO
VALVE
AUTO
VALVE
TYPE
408-FCU-2
408-FCU-3
408-FCU-4
408-FCU-5
408-FCU-1A
ESP
O.A.
CFM
(30% PROPYLENE GLYCOL)
408-FCU-7
408-FCU-8
408-FCU-9
408-FCU-10
408-FCU-6
408-FCU-11
408-FCU-12
408-FCU-13
408-FCU-14
408-FCU-15
408-FCU-16
408-FCU-17
408-FCU-18
408-FCU-19
408-FCU-20
408-FCU-21
408-FCU-22
408-FCU-23
408-FCU-24
408-FCU-25
408-FCU-26
408-FCU-27A
408-FCU-28
408-FCU-29
408-FCU-30
408-FCU-31
408-FCU-10A
408-FCU-27
408-FCU-23A
408-FCU-5A
408-FCU-14A
408-FCU-23B
408-FCU-23C
408-FCU-23D
13.7670 100 12.7 2.5 5.0 25.8 70 5.0 142 (4) 115-1 1,20.75"1.2 2563.075.0 10691.71"HORIZONTAL CONCEALED DUCTED 1.20.4" 2-WAY 2-WAY
13.5660 100 12.6 2.4 5.0 25.6 70 5.0 140 (4) 115-1 1,20.75"1.163.075.0
1.70.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.4450 70 8.7 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 2-WAY63.075.0
1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY
7.5330 55 6.8 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"63.075.0
1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.40.4" 2-WAY
7.6340 200 6.9 1.4 5.0 70 5.0 73 (2) 115-1 1,20.75"63.075.0
1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.60.4" 2-WAY
0.32-WAY 2-WAY3.6140 65 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
14.3640 235 13.0 2.6 5.0 21.7 70 5.0 134 (4) 115-1 1,20.75"1.263.075.0 1.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.3440 70 8.5 1.7 5.0 70 5.0 78 (2) 115-1 1,20.75"0.8 2-WAY63.075.0
1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 16.90.4" 2-WAY
10.6520 80 9.9 1.9 5.0 20.5 70 5.0 105 (2) 115-1 1,20.75"0.963.075.0
1.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
21.2980 220 19.5 4.0 5.0 30.5 70 5.0 430 (2) 115-1 1,20.75"1.963.075.0
2.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
0.22-WAY 2-WAY2.9100 45 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
13.0410 130 12.0 2.3 5.0 21.1 70 5.0 132 (4) 115-1 1,20.75"1.163.075.0 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
12.4555 235 11.2 2.3 5.0 20.2 70 5.0 122 (4) 115-1 1,20.75"1.163.075.0 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.2545 125 11.0 2.2 5.0 21.0 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY4.0180 50 3.6 0.7 5.0 8.8 70 5.0 35 115-10.75"63.075.0 330.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
12.2550 90 11.0 2.2 5.0 21.1 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY3.6140 135 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
10.6535 85 10.0 1.9 5.0 20.1 70 5.0 109 (2) 115-1 1,20.75"0.963.075.0 590.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY3.1120 30 2.7 0.6 5.0 5.5 70 5.0 26 115-10.75"63.075.0 330.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
12.9530 155 11.3 2.3 5.0 20.7 70 5.0 116 (4) 115-1 1,20.75"1.163.075.0 760.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.2540 200 11.0 2.2 5.0 20.9 70 5.0 120 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.0865 140 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6210 200 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"63.075.0 0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.9250 130 3.8 0.7 5.0 7.7 70 5.0 48 115-10.75"63.075.0 100.50.75" 0.2VERTICAL FLOOR SET 0.4" 1,2
17.8960 265 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.8960 240 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
16.0775 120 14.8 2.9 5.0 27.9 70 5.0 155 (4) 115-1 1,20.75"1.463.075.0 761.90.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.8490 75 9.2 1.8 5.0 19.8 70 5.0 56 (2) 115-1 1,20.75"0.8 2563.075.0 10551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.0370 55 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY63.075.0 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY
13.4935 215 13.2 2.4 5.0 28.4 70 5.0 120 (4) 115-1 1,20.75"1.163.075.0
1.91"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY
11.7820 270 11.5 2.1 5.0 20.4 70 5.0 115 (4) 115-1 1,20.75"1.063.075.0 101.41"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY
-- - - - 5.0 - 70 5.0 - 115-1 1,20.75"- -63.075.0 ---1"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY
VERTICAL FLOOR SET
VERTICAL FLOOR SET
-- - - - 5.0 70 5.0 - 115-1 1,20.75" -63.075.0 ---0.75" 0.2- 2-WAY-0.4" 2-WAY
-- - - - 5.0 70 5.0 - 115-1 1,20.75" -63.075.0 ---0.75" 0.2- 2-WAY-0.4" 2-WAY
15.2710 215 14.0 2.8 5.0 26.6 70 5.0 145 (4) 115-1 1,20.75"1.363.075.0
1.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
NOM
408-FCU-1B HORIZONTAL CONCEALED DUCTED 11.4485 75 10.2 2.1 5.0 21.5 70 5.0 110 (4) 115-1 1,20.75"- 2563.075.0 10
1.30.75" 0.40.4" 2-WAY 2-WAY
1.4
1.4
1.4
1.4
1.4
0.5
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
77 24
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
45 24
25 10
25 10
25 10
25 10
25 10
32 17
25 10
25 10
25 10
25 10
85 24
25 10
25 10
25 10
25 10
EGGCRATE CEILING REGISTERCR1
DAMPER
OPPOSED BLADE
SURFACE
TYPE MOUNTING
DESCRIPTION
EGGCRATE CEILING GRILLE
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
SYMBOL
CD1
CG1
LAY-IN
FINISH
E.C.L.STEEL ALUM.
MATERIAL
ACCESSORIES
W.B.E.
SEE
EGGCRATE CEILING GRILLE
CG2
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
CD2
NOTES:
1. PROVIDE 48" LONG DEVICE WITH 3 - 1" SLOTS. PROVIDE CENTER NOTCH AS REQUIRED TO ACCOMMODATE 2'X2' GRID.
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD3 1
EGGCRATE CEILING REGISTERCR2
DAMPER
OPPOSED BLADE
EGGCRATE CEILING FILTER GRILLE
CG3
EGGCRATE CEILING FILTER GRILLE
CG4
NOTE
FILTER
FILTER
TR1
DAMPER
OPPOSED BLADE
TR2
DAMPER
OPPOSED BLADE
ADJUSTABLE AIRFOIL BLADE SUPPLY
REGISTER - DOUBLE DEFLECTION
FIXED AIRFOIL BLADE RETURN
REGISTER
AIR DISTRIBUTION DEVICES
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M601
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FOUR PIPE FAN COIL UNIT SCHEDULE (CONTINUED)
TYPE
1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.
2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.
NO.
UNIT
HEATING REQUIREMENTS WITH
180°F ENT. WATER TEMP.
GPM
COOLING REQUIREMENTS WITH
44°F ENT. WATER TEMP.
MIN.
MBH
TOTAL
FAN
CFM
MIN.
MBH
SENS.
ENT. AIR F
WbDb
MAX. LOSS
FT. WATER
THRU COILGPM
AUTO
VALVE
TYPE
RUN-
SIZE
OUT
MIN.
MBH
ENT.
AIR
FAN MOTOR
AUTO
VALVE
RUN-
SIZE
OUT
W (QTY.)
NOM. HP
APPROXIMATE SIZE
L
VOLT.-
HW
NOTES
NOTES:
MAX. LOSS
THRU COIL
AUTO
VALVE
AUTO
VALVE
TYPE
ESP
O.A.
CFM
(30% PROPYLENE GLYCOL)
408-FCU-32
408-FCU-33
408-FCU-34
408-FCU-35
408-FCU-36
408-FCU-37
408-FCU-38
408-FCU-39
408-FCU-40
408-FCU-41
408-FCU-42
408-FCU-43
408-FCU-44
408-FCU-45
408-FCU-46
408-FCU-47
408-FCU-48
408-FCU-49
408-FCU-50
408-FCU-51
408-FCU-52
408-FCU-53
408-FCU-54
408-FCU-55
408-FCU-56
408-FCU-57
408-FCU-58
408-FCU-59
408-FCU-60
408-FCU-61
408-FCU-62
408-FCU-63
408-FCU-64
408-FCU-65
408-FCU-66
408-FCU-67
408-FCU-68
408-FCU-69
408-FCU-70
408-FCU-71
408-FCU-72
408-FCU-73
408-FCU-40A
0.42-WAY 2-WAY4.6210 170 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75" 2567.080.0 10370.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 2567.080.0 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 40 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.965 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.935 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.52-WAY 2-WAY5.2185 90 4.3 1.0 5.0 9.0 70 5.0 44 (2) 115-10.75" 480.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 160 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.0105 170 2.5 0.6 5.0 5.5 70 5.0 24 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6205 30 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9125 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6150 45 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6150 180 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.52-WAY 2-WAY5.4220 90 4.7 1.0 5.0 8.7 70 5.0 47 (2) 115-10.75" 430.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6210 210 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6140 50 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6205 200 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.5200 200 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.5200 150 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
16.9860 140 15.9 3.1 5.0 32.2 70 5.0 169 (4) 115-1 1,20.75"1.5 2567.080.0 10762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
24.41270 195 23.2 4.5 5.0 34.5 70 5.0 430 (2) 115-1 1,20.75"2.1 672.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
20.81020 155 19.4 3.9 5.0 29.2 70 5.0 430 (2) 115-1 1,20.75"1.8 631.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
16.2795 120 15.1 2.9 5.0 31.0 70 5.0 158 (4) 115-1 1,20.75"1.4 2.11"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.3905 275 16.4 3.1 5.0 33.1 70 5.0 176 (4) 115-1 1,20.75"1.5 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
27.41600 240 27.4 5.1 5.0 45.3 70 5.0 430 (2) 115-1 1,20.75"2.4 693.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
12.8625 365 12.8 2.4 5.0 17.8 70 5.0 132 (4) 115-1 1,20.75"1.1 1.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
23.71205 185 23.7 4.4 5.0 33.6 70 5.0 430 (2) 115-1 1,20.75"2.1 692.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
13.0615 95 12.0 2.3 5.0 21.2 70 5.0 133 (4) 115-1 1,20.75"1.1 2567.080.0 10691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
13.0605 95 11.9 2.3 5.0 21.1 70 5.0 131 (4) 115-1 1,20.75"1.1 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
10.3560 145 9.6 1.8 5.0 20.0 70 5.0 88 2) 115-1 1,20.75"0.8 551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.4555 85 11.2 2.3 5.0 20.1 70 5.0 144 115-1 1,20.75"1.1 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
2.9- 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYVERTICAL FLOOR SET 0.4" 2-WAY
2.9100 - 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.1395 185 9.1 1.6 5.0 15.9 70 5.0 71 (2) 115-1 1,20.75"1.6 551.10.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.4450 70 8.6 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 252-WAY67.080.0 10551.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY
7.5330 150 6.7 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.3400 65 7.7 1.5 5.0 70 5.0 84 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.0370 65 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY
NOM
0.32-WAY 2-WAY3.3130 40 2.8 0.6 5.0 5.8 70 5.0 27 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
6.8280 45 6.0 1.2 5.0 70 5.0 62 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.00.4" 2-WAY
6.9290 45 6.1 1.3 5.0 70 5.0 64 (2) 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.30.4" 2-WAY
15.0690 105 13.7 2.7 5.0 26.2 70 5.0 142 (4) 115-1 1,20.75"1.3 761.80.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
67.080.0
14.4 1.0
16.0 1.1
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
32 17
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
32 10
32 10
25 10
25 10
CONVERTER SIZED TO HANDLE 50 PERCENT OF THE PROJECT HEATING LOAD.
CONVERTER SHALL BE SIZED WITH .001 FOULING FACTOR.
APPROXIMATE SIZE: 8" DIA X 40" LONG.
BASEMENT MECH. ROOM
NOTES:
CONVERTER
NO.
408-C1
LOCATION
FLUID
WATER
CONVERTER
ENTERING
STEAM PSIG
MAX. LOSS
IN F
TEMP
CIRCULATING FLUID
GPM
54 160
OUT F
TEMP
ENTERING
FT. FLUID
VALVE
CONTROL
MBH
CAPACITY
HEATING
80013.1 S.F.
HEATING
SURFACE
MINIMUM
CONTROL
LBS/HR
VALVE
843 1686
TRAP
LBS/HR
1,2,3
NOTES
BASEMENT MECH. ROOM408-C2 WATER 13054 160 5 30 80013.1 S.F.15 843 1686 1,2,3
408-C3 BASEMENT MECH. ROOM WATER 54 130 160 5 30 15 13.1 S.F. 800 843 1686 1,2,3
CONVERTER SCHEDULE
TYPE
IN-LINE
VERTICAL
FLUID
CLEAR WATER
LOCATION
NO.
408-HWP1
PUMP
NOTES:
SYSTEM
°F
TEMP
CIRCULATING FLUID
GPM
PUMP HEAD
FT. FLUID
GR.
SP.
EFF.
RPM
NOM.
HP PHASE
MOTOR
208-3
VOLT.-
YES
VFD NOTES
1 MOTOR SHALL BE NEMA PREMIUM EFFICIENCY TYPE.
WATER
HEATING HOT
50 73
MIN.
7.5MECHANICAL ROOM
IN-LINE
VERTICAL
30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1
WATER
CHILLED
36 73 10MECHANICAL ROOM
BASEMENT
IN-LINE
VERTICAL
CLEAR WATER408-HWP1 180108 1 1750208-3 YES 1
WATER
HEATING HOT
50 73 7.5MECHANICAL ROOM
IN-LINE
VERTICAL
30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1
WATER
CHILLED
36 73 10MECHANICAL ROOM
30% GLYCOL408-GCWP1 5
WATER
CHILLED
MECHANICAL ROOM 44 1.0313 --
IN-LINE
HORIZONTAL
0.25 120-1 1750 NO
BASEMENT
BASEMENT
BASEMENT
BASEMENT
HVAC PUMP SCHEDULE
PRESS.
INITIAL
IN TANK
408-HWET1
408-CWET1
HOT
UNIT
NO.
SYSTEM
MAX.MIN.
402000
SYSTEM
TEMP.
RANGE °F
GAL.
APPROX.
SYSTEM
VOLUME
PSIG.
MAX. OPER. PRESS.
TANK
PSIG.
FILL
PSIG.
PRESS.
AT TANK
ATRELIEF
VALVE
PSIG.
21.7 11.3 408-CWAS1
ACCEPT.
VOLUME
MIN.
VOL.
MIN.
GAL.
GAL.
NO.
UNIT
5 200
NO
NO
MAX.
FT.
P.D.
AIR SEPARATOR
GPMIN.
SIZE BUILT-IN
STRAINER
1"
1"
1"
1"
FILL SIZE
WATER
COLDPIPE
SIZE
IN.
TO TANK
IN.
WATER
CHILLED
WATER
HORIZONTAL
TYPE
DIAPHRAGM
NOTES
77 341000 408-HWAS1HORIZONTAL
DIAPHRAGM
EXPANSION TANK SCHEDULE
MBH
MIN.UNIT
NO.
NOTES:
LOCATION
UNIT
TYPE
CFM
ENT. TEMP.
°F
WATERAIR
GPM
AUTO
VALVE
TYPE
RUNOUT
SIZE
AUTO
VALVE
CV
MOTOR
HEIGHT
APPROX. CABINET DIMS.
LENGTH DEPTH
HP
VOLT.-
PHASE
NOTES
(W)
MAX. LOSS
FT. WATER
THRU COIL
1 VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING & RECESS REQUIREMENTS PRIOR TO ORDERING.
8.0408-UH1 HORIZONTAL PROPELLERSEE PLANS 245 60 180 20.8 0.75" 3-WAY 0.4 (25)16"18" 10" 115-1 1
18.4408-UH2 HORIZONTAL PROPELLERSEE PLANS 500 60 180 21.9 0.75" 3-WAY 0.9 (25)16"18" 10" 115-1 1
24.8408-UH3 HORIZONTAL PROPELLERSEE PLANS 580 60 180 22.5 0.75" 3-WAY 1.2 (25)16"18" 10" 115-1 1
HOT WATER UNIT HEATER SCHEDULE
REMARKS
FT. MAX.
WATER P.D.
WITH 0°F AMBIENT TEMP.
SHALL PERFORM SATISFACTORILY
AT MIN. COMPRESSOR CAPACITY
OF CAPACITY REDUCTION TO 25%
CHILLER SHALL BE CAPABLE
2. HIGH SCCR 65k CURRENT RATING.
48 TONS
PERFORMANCE
MINIMUM CAPACITY
WITH 95°F AMBIENT TEMP.
PROVIDE ABOVE PERFORMANCE
AIR COOLED CONDENSER SHALL
LOCATIONEQUIPMENT
CONDENSER
AIR COOLED
COMPRESSOR
NO.
UNIT
408-ACCH1 CHILLER 100 GPM
57°F WATER IN
45°F WATER OUT
MOCP
208-3
11.5
SINGLE POINT UNIT ELECTRIC
NOTES:
VOLT.-
PHASE
MCA
236 250
EFFICIENCY
16.55
MIN. IPLV
(NOTE 1)
MAX A-WEIGHTED
SOUND POWER LEVEL, dBA PRESSURE
(NOTE 1)
SOUND
GRADE
408-ACCH2
1. MANUFACTURER SHALL PROVIDE ALL SOUND MINIMIZING OPTIONS AVAILABLE.
(NOTE 2)
NEW PACKAGED AIR COOLED CHILLER UNIT SCHEDULE
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:5
:3
P
M
M602
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
ENERGY RECOVERY VENTILATORS
NOTES:
1. LOW PROFILE – FOR CEILING OR WALL INSTALLATION
2. NO HEAT EXCHANGER VIRUS CROSSOVER - ASTM F1671 TESTED FOR NO VIRUS PENETRATION
3. LOW CROSS-OVER ENERGY RECOVERY COUNTER FLOW CORE <0.5% EATR TESTED TO AHRI 1060
4. TOTAL ENERGY RECOVERY EFFECTIVENESS >60% TESTED TO AHRI 1060
5. MAINTENANCE – WATER WASHABLE ENERGY/HEAT RECOVERY CORE WITH NO MOVING PARTS. PAPER CORES ARE NOT ACCEPTABLE.
6. DIRECT DRIVE PLENUM ECM FANS (< 1 W/CFM)
7. DOUBLE WALL INSULATED CASING WITH MINIMUM R4 PER INCH
8. FACTORY MOUNTED BACNET IP CONTROLS WITH BTL CERTIFICATION
9. HUMAN INTERFACE CONTROLLER.
10. FILTER MONITORING WITH REMOTE ALARM VIA PRESSURE MEASUREMENT ACROSS THE FILTER. MERV13 FILTERS ON OA AND MERV8 FILTERS ON RA.
11. CERTIFICATIONS: UL AND CSA
12. FACTORY MOUNTED HYDRONIC COILS PROVIDED WITH LOOSE VALVES AND ACTUATORS
13. SCR CONTROL ELECTRIC HEATERS
14. SINGLE-POINT POWER CONNECTION WITH UNIT AND ELECTRIC HEATER. MAIN POWER TO THE ELECTRIC HEATER.
MANUFCTR MODEL
SUPPLY EXHAUST SUPPLY EXHAUST
PRE-HEAT ELECTRIC HEATER HEAT EXCHANGER - SUMMER HEAT EXCHANGER - WINTER CHILLED WATER COOLING COIL HOT WATER HEATING COIL ELECTRICAL CONNECTION
EAT LAT CAPACITY CAPACITY
OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY EAT LAT
TOTAL
FLUID TEMP.
FLUID
FLUID EAT LAT SENSIBLE FLOW
FLUID TEMP.
FLUID
FLUID
SINGLE POINT POWER
EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL DB WB DB WB EWT LWT EWT LWT VOLTAGE FLA MCA RFS
CFM CFM in W.G. in W.G. oF oF (kW) (kW) % % % % % % MBH GPM % MBH GPM °F °F % (V) (A) (A) (A)
408-ERV1 OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
408-ERV2
408-ERV3
AIRFLOW AIRFLOW ESP ESP
TYPE
PERCENTRATECAPACITYPERCENT
TYPE
PROP
°F°F°F°F
FLOW
RATECAPACITY
°F°F°F°F°F°F°F°F
REQUIRED MAX.
°F°F°F°F°F°F°F°F
OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
PROP
OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
PROP
1 COIL CAPACITY BASED ON STANDARD AIR AT 0 FT. ALTITUDE. COIL SHALL BE MINIMUM 6 ROWS DEEP.
408-CC1
COIL
NO.
NOTES:
SYSTEM
ERV-1
CFM
3,000 75.1
Wb
ENT. AIR FMAX.
LOSS
FACE
VEL
MAX.
S.P.
FPM.
0.47" 80.8
Db
LVG. AIR F
Db FLUIDWb
GLYCOL 30%
PROPYLENE
LOSS
MAX.
8.69
FT.
TEMP.
CIRCULATING FLUID
INGPM
°F
22.11
OUT
TEMP.
57.1
°F
AUTO
VALVE
CV
AUTO
VALVE
TYPE
MINIMUM
MBH
128.1
TOTAL (1)
MBH
MINIMUM
54.3
SENS. (1)
9.952-WAY
CHILLED WATER COOLING COIL SCHEDULE
408-CC2 ERV-2 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY
408-CC3 ERV-3 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY
ERV-2
ERV-1
ERV-3
408-PH2
408-PH3
408-PH1 3,000 667
FPM.
SYSTEM
COIL
NO. CFM
FACE
VEL
MAX.
LOSS
WATER
WATER
WATER
00.33"
0.33"
0.33"
80 17.73
F
F
FLUID
TEMP. AIR FMAX.
S.P.
ENT. LVG.
TEMP.
CIRCULATING FLUID
GPM
TEMP.
OUTIN
FT. FLUID
8.9 261.6
MAX. LOSS MIN.
MBH
AUTO
VALVE
CV
AUTO
VALVE
TYPE
8-
PRE-HEAT COIL SCHEDULE
261.6
261.6
17.73
17.73
3,000 667
3,000 667
0 80
0 80
8.9
8.9
DISTANCE
ABSORP.
(MAX.)
408-SH1
HUMID.
NO.
ERV-1
SYSTEM
10"
CFM
°F
Db
54.5 30
ON-OFF
VALVE
ENT. ENT.
PSIG
VALVE
CONTROL
STEAM
VALVE
ON-OFF &
CONTROL
LBS/HR
LBS/HR
TRAP
LEAVING AIR
408-SH2 ERV-2 10"3000 54.5 30 24 60 120
408-SH3 ERV-3 10"3000 54.5 30 24 60 120
STEAM HUMIDIFIER SCHEDULE
2" 3"
3" 4"
NOTE: REDUCING VALVE AND RELIEF VALVE TO BE SIZED BY SUPPLIER. ASSEMBLY SHALL BE INSTALLED PER DETAIL AND MANUFACTURER'S RECOMMENDATIONS.
LOCATIONNUMBER
PRV PSIG
STEAM PRESSURE
INLET OUTLET
PRESSURE
RELIEF
SAFETY
MAXIMUM
CAPACITY LBS/HR
REQUIRED
PIPE SIZES
D1 D2
SAFETY RELIEF VALVE
MIN. CAPACITY
LB/HR
SET PRESSURE
PSIG
408-PRV1B 450 560 N/A N/A
408-PRV1A 900 1,130 1,130 40 PSI120 30 40 PSI
120 30BASEMENT
MECH. ROOM
BASEMENT
MECH. ROOM
EQUIPMENT/
HEATING HOT
WATER
AREA SERVED
N/A
HEATING HOT
WATER
STEAM PRESSURE REDUCING VALVE/SAFETY RELIEF VALVE SCHEDULE
BE PROVIDED. REFER TO ARCHITECTURAL DRAWINGS.
LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENINGS SHALL
RECESSED UNITS TO HAVE FOUR(4) SIDE
OVERLAP UNLESS OTHERWISE NOTED.
APPROX. CABINET DIMENSIONS
HEATING CAPACITY BASED ON 60 ENT. AIR &
180 ENT. WATER.
MAXIMUM WATER PRESS. DROP THRU COIL
DESCRIPTION
NO.
FT-*
UNIT
FIN TUBE CONVECTOR
1 FT.
GENERAL NOTES
VERIFY/COORDINATE CABINET DIMENSIONS,
MOUNTING & RECESS REQUIREMENTS WITH
ARCHITECTURAL DWGS. PRIOR TO ORDERING.
ELEMENTS
WALL HUNG - 0'-24" AFF
MOUNTING
RUNOUT
MBH
1.5/FT
HTG.
GPM
0.5
SIZE
0.75"
LENGTHVALVE CV
0.2
MIN. AUTO
NOTE 2
DEPTH
6" 1
RECESS
HEIGHT
20"
SEE NOTE
NOTES
1. REFER TO FLOOR PLANS FOR ELEMENT LENGTHS.
2. CABINET LENGTH AS REQUIRED TO CONCEAL ELEMENT AND PIPING.
ROWS OF
STANDARD SLOPED TOP ENCLOSURE.
ROOM HEATING UNITS
UNIT
NO.
408-BT1
DIAMETER
TANK
VOLUME
MIN.
CONN.
SIZE HEIGHT
DIMENSIONS
SHIPPING
WEIGHT
6" 36" 81" 850
BUFFER TANK
2 @ 2 208-36.4
LOCATIONNUMBER
PUMP
PRESSURE
DISCHARGE
GALLONS
SIZE
RECEIVER
LB/HR
MOTOR
NOM. HP PHASE
REMARKS
408-CP1 1600 3500 RPM MOTOR8BASEMENT
MECH. ROOM
DUPLEX
TYPE UNIT
VOLT
50 PSI
CAST IRON RECEIVER
GPM
STEAM CONDENSATE PUMP SCHEDULE
POWER CIRCUIT (MCA / MOCP)
VOLTAGE & PHASE
MOUNTING
NOMINAL TONS
VOLTAGE & PHASE
SENSIBLE CAP (NET MBH)
DB ENTERING AIR
WB ENTERING AIR
C O
O L
IN
G
DESCRIPTION
F A
N
TOTAL CAP (NET MBH)
MOTOR HP
CFM
UNIT NUMBER (INDOOR / OUTDOOR)
AREA SERVED
208 / 1
38 W
AC-1
GENERAL NOTES:
DESCRIPTION AIR COOLED HEAT PUMP
9.09
10.9
COMM 103B
CONFIGURATION WALL MOUNTED
CONDENSATE PUMP
YES
7.8 / 15
208 / 1
GRADE
CU-1 (NOTE 1)
AC-2
AIR COOLED HEAT PUMP
COMM 101B
WALL MOUNTED
208 / 1
GRADE
CU-2
AC-3
AIR COOLED HEAT PUMP
COMM 202H
WALL MOUNTED
208 / 1
GRADE
CU-3
ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - SINGLE
POWER SERVICE TO EACH UNIT. ADEQUACY OF LISTED CIRCUIT SIZES
MUST BE VERIFIED BY CONTRACTOR. COST FOR INCREASE OR CHANGE OF
ELECTRICAL SERVICE FOR EQUIPMENT SELECTED SHALL BE BORNE BY
CONTRACTOR.
CONDENSATE DRAIN PIPING FROM INDOOR UNITS SHALL BE 0.75" UNLESS
NOTED OTHERWISE.
0.75
7 / 15
0.75
7 / 15
208 / 1
38 W
8.04
8.9
YES
208 / 1
38 W
8.04
8.9
YES
COOLING ONLY SPLIT SYSTEMS
O U
T D
O O
R U
N
IT
IN
D
O O
R U
N
IT
NOTES:
1. UNIT SHALL BE ON EMERGENCY POWER
MOTOR HP 41 W 41 W 41 W
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/3
/2
:3
:1
P
M
M603
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
V-2
(APPLIES TO CONTROL PANEL
408-ERV*)
NEW DISTRIBUTED CONTROL PANEL 408-ERV* (DCP/DDC)
408-ERV* POINTS LIST
1 A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED
AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OF
EQUIPMENT AND SYSTEMS AS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A
DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC ACTUATION.
2 ELECTRICAL WORK INCLUDES A POWER SOURCE TO THE MOTOR STARTERS. ALL
HVAC POWER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES
EXPLICITLY SHOWN ON THE ELECTRICAL DRAWINGS, SHALL BE PROVIDED . THIS WORK
SHALL INCLUDE BUT NOT BE LIMITED TO WIRING, CONDUIT, TRANSFORMERS, RELAYS
AND FUSES.
3 BULB WELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE FURNISHED AND
INSTALLED. PIPING WORK SHALL INCLUDE PROPERLY SIZED WELDOLET OR
THREADOLET FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.
4 POINTS LIST IS SHOWN AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM
POINTS REQUIRED FOR CONTROL AND MONITORING. ALL INPUT AND OUTPUT POINTS,
AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDWARE, SHALL BE PROVIDED
FOR A COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF OR WHEN ADDITIONAL
POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED,
THESE POINTS, ALONG WITH ADDITIONAL DIRECT DIGITAL CONTROL PANEL(S) (IF
REQUIRED), SHALL ALSO BE PROVIDED.
5 ALL DDC WIRING SHALL BE GREEN.
APPLIES TO ALL CONTROLS SHEETS
DDC CONTROLLER
HEATING COIL
FAN-COIL UNIT
SUPPLY AIR
1.1 SUPPLY AIR TEMPERATURE, SENSED BY T-2, SHALL BE MAINTAINED AT SETPOINT
OF 70 DEG. F. VIA DCP BY MODULATING COOLING COIL VALVE V-2 OR REHEAT COIL
VALVE V-3, IN SEQUENCE. SEPARATE CONTROL LOOPS SHALL BE UTILIZED FOR
COOLING AND HEATING FUNCTIONS. COOLING COIL VALVE V-2 SHALL BE FULLY
CLOSED BEFORE REHEAT COIL VALVE V-3 OPENS, AND VICE VERSA.
1.2 WHEN ROOM TEMPERATURE AT T1 IS ABOVE SETPOINT, HOT WATER VALVES V1 &
V3 SHALL BE CLOSED AND CHILLED WATER VALVE V2 SHALL MODULATE OPEN TO THE
COIL TO MAINTAIN TEMPERATURE SETPOINT.
1.3 THE ELECTRONICALLY COMMUTATED MOTOR ON THE SUPPLY FAN SHALL BE
MODULATED. WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 60 DEGREES F., THE
FAN SHALL REMAIN AT 40 PERCENT AIR FLOW AND THE HYDRONIC VALVES SHALL
MODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT. IF THE SPACE FALLS OR
RISES MORE THAN 2 DEGREES F. FROM THE SETPOINT, THE FAN SPEED SHALL BE
INCREASED SLOWLY UNTIL THE SPACE IS WITHIN 1.5 DEGREES F. OF SETPOINT.
ABOVE 60 DEGREES F. OUTSIDE AIR TEMPERATURE THE FAN SHALL HAVE A 10
PERCENT AIR FLOW MINIMUM. VALVE V1 SHALL MODULATE TO MAINTAIN SPACE
TEMPERATURE SETPOINT. IF THE ROOM IS MORE THAN 2 DEGREES F. ABOVE
SETPOINT THE FAN SPEED SHALL BE INCREASED UNTIL SPACE IS WITHIN 1.5 DEGREES
F. OF SETPOINT.
1.4 EACH UNIT SHALL INCLUDE A DISCHARGE AIR TEMPERATURE SENSOR.
1.5 EXTEND 24 VOLT POWER TO THE FAN COIL UNIT CONTROLLER FROM THE NEAREST
DDC CONTROL PANEL.
1.6 REFER TO HVAC DESIGN DATA SCHEDULE FOR SPACE TEMPERATURE SETPOINTS
IN BOTH OCCUPIED AND UNOCCUPIED MODES. ROOM SPACE TEMPERATURE SET
POINT SHALL BE ADJUSTABLE FROM THE FRONT END COMPUTER INTERFACE.
1.7 PROVIDE SCHEDULED NIGHT SET-BACK CONTROL FOR CONTINUOUS FAN
OPERATION DURING THE OCCUPIED PERIOD (24 HOURS A DAY, 7 DAYS A WEEK, ADJ.)
AND CYCLED FAN OPERATION TO MAINTAIN REDUCED TEMPERATURE IN THE
UNOCCUPIED PERIOD.
COOLING…