552-19-102 Drawings_Volume9.pdf

PDF 8 MB Posted

Attached to
Y1AA--Infrastructure Deficiencies B408 [552-19-102] Dayton VAMC
Solicitation number
36C25025B0036
Issued by

About this file

These are mechanical and electrical engineering design drawings for a VA Medical Center infrastructure improvement project at the Dayton, Ohio location. The comprehensive set of drawings includes detailed schematics for HVAC systems, hydronic piping, steam systems, electrical distribution panels, motor schedules, and lighting fixture specifications. Key technical components include energy recovery ventilators, air-cooled chillers, hot water converters, fan coil units, steam pressure reducing valves, and electrical panels with load calculations. The drawings are prepared by Heapy Engineering for Guidon Design and are part of VA Project Number 2018-05164, specifically addressing infrastructure deficiencies in Building 408 at the Dayton VA Medical Center.

The drawings provide extensive technical specifications for mechanical and electrical systems, including precise details on equipment locations, performance characteristics, control sequences, and installation requirements. Notable elements include schematic diagrams for heating and chilled water systems, steam piping configurations, control panel point lists, motor and starter schedules, and electrical distribution panel layouts. The documentation appears comprehensive, covering everything from individual component specifications to overall system integration, with clear annotations and technical notes to guide installation and maintenance.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ACCESS PANEL AND DOOR DETAIL

HORIZONTAL PIPE ANCHOR DETAIL

SUPPORT/ANCHOR FOR PIPE RISERS PIPE HANGERS

HANGER STRAPS OR RODS

ROUND DUCT HANGERS

VOLUME DAMPER DETAIL

CHILLER PAD DETAIL

EXTERIOR PIPE STANCHION DETAIL

SECTION THRU FIRE DAMPER INSTALLATION

CONCRETE EQUIPMENT BASES

ACCESS SECTION FOR ROUND/OVAL DUCT

SECTION "A-A"

"B" "B"

"A"

"A"

INSULATION

INSULATION

GASKET

DUCT

INSULATION

SECTION "B-B" FACTORY

FABRICATED

LATCH

FLEXIBLE

WASHER

HANDLE INSIDE

GASKET

CASING

ACCESS DOOR

ACCESS PANEL

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

RISER CLAMP

RISER CLAMP

PIPE SLEEVE WHERE

ANCHOR POINTS ONLY

CLAMP REQUIRED AT

RISER CLAMP. BOTTOM

BOLT (TYPICAL)

INSULATION

FIRE-STOPPING

WOOD FLOOR

MATERIAL

BOLT

ELEVATION

PLAN

RISER

SPECIFIED

BOLT

WHERE SPECIFIED

PIPE SLEEVEPIPE

INSULATE ANCHOR AS INDICATED FOR COLD PIPING.

AND INSULATION THICKNESS

CUT TO SUIT PIPE DIA.

NOTE:

INSULATION

3/8" PLATE

PIPE & PIPE & INSULATION

1/2" U-BOLT

BASE PLATE

3/8"

WELD

STRUCTURAL CHANNEL

ANCHOR BOLTS,

MIN. SIZE 5/8"

STRUCTURE

2 AT EACH PLATE.

OR ANGLES

(2"x2"x1/4")

5 FT

6 8 10

9 1110 12

-1312 14 -16 -

1614 17 2219 23

2725 28 3230

20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4

7 7

7 98

NOTE: SEE SPECIFICATIONS FOR

DETAILED HANGER REQUIREMENTS

M A

X

FT.

FT.

IN.

TUBING

PIPE

NOM. SIZE

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

MAXIMUM PIPE/TUBING SUPPORT SPACING

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION SHIELD

AT HANGER

SADDLE

WELD

1/2" DIA. HANGER

RODS WITH 36" MAX.

SPACING ON EACH

CHANNEL

1-5/8" 12 GAUGE CHANNEL

OR 2"x2"x1/4" ANGLE

BAND

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" MIN.)

ADJUSTABLE CLEVIS HANGER TYPE 43 -

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 1 -

SEE SPECIFICATIONS

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000

LB. UNIFORM LOAD

420ONE 1 x 18 GA. STRAP36

TWO 1/2 DIA. RODS

TWO 3/8 DIA. RODS

ONE 1 x 16 GA. STRAP

50 700

ONE 1 x 22 GA. STRAP

QUANTITY/SIZEMAX. DUCT

MAX. LOAD

LBS.

MAX.

IN.

SPACING

DIA. - IN. IN.

50" DIA. &

UNDER

LOAD RATED

FASTENERS

BAND OF SAME SIZE

AS HANGER STRAP

HANGER RODS

OVER 50"DIA.

BAND

1/8" CLEARANCE ALL

AROUND SECTIONSIDE ELEVATION

STIFFEN BLADE AS

REQUIRED

DUCT

1/2" ROUND ROD PIN

INSULATION

STAND-OFF

HANDLE WITH LOCKING

QUADRANT

INSIDE END BEARING

OUTSIDE END BEARING

DAMPER BLADE

INSULATION SEE

SPECIFICATION

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

NOTES:

1.

2.

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

3/4" CHAMFER

(2) #5 BARS CONTINUOUS

TOP AND BOTTOM

FINISH GRADE

TYP. ALL FOUR SIDES

1'-0"

CAST SLAB AND

THICKENED EDGES

TOGETHER IN ONE

POUR

6x6-W2.9xW2.9

WELDED WIRE FABRIC

PIPE ROLLER SUPPORT

HEIGHT WITH EQUIPMENT ACCESS

AND CONNECTION LOCATIONS.

3' DEEP

POURED CONCRETE

COORDINATE EXACT

3'-0"

PIPING

GRADE

8"

16" DIA.

CHILLED WATER

C4x7.25

CONTINUOUS WELD PIPE

TO CHANNEL (TYPICAL)

2.5 SCHEDULE 40 PIPE

8"x8"x1/2" BASE PLATE

EPOXY GROUT

(4)1/2" DIA. GALVANIZED

ADHESIVE ANCHORS

ACCESS

PANEL

NOTE 5

PERIMETER ANGLE, NOTE 3

(NOT FASTENED TO PARTITION)

TYPICAL DUCT

INSULATION

FIRE BARRIER

PARTITION OR CHASE

NOTE 6

SLEEVE, NOTE 2

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

DAMPER,

NOTE 1

DUCT

CONNECTION

NOTE 4

SLEEVE, NOTE 2

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES

FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE

PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO

DAMPER FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" , 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR

LINKS.

PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. IN ORDER TO MAINTAIN U.L.

RATING FOR FIRE DAMPER, DO NOT FILL THIS OPEN SPACE WITH FIRESTOP MATERIAL.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

NOTES:

1.

2.

3.

4.

5.

6.

7.

SECTION A-A (BASE NOT POURED WITH SLAB)

SECTION A-A (BASE POURED WITH FLOOR SLAB)

PLAN

TYPICAL ANCHOR

BOLT NUT & WASHER

SECTION B-B

EQUIPMENT BASE PLATE

PROVIDE #3 BARS 12" O.C. EACH

WAY IN THE BASE & DOWEL BASE

TO FLOOR

EQUIPMENT BASE PLATE

PROVIDE DOUBLE SLAB

REINFORCING IN BASE AREA

WELD HEAD TO PLATE

OR BEND OVER END 5D

FLOOR

PIPE SLEEVE (5D, 3" MIN.)

ANCHOR

BOLT (TYP)

CONCRETE BASE

NOTE:

L & W DIMENSIONS

SHALL BE 6" GREATER

THAN THE EQUIPMENT

BASE PLATE.

L

W

A

A

D

2D

16"

M

IN

L /1

M

IN

L /1

D

TYPICAL ANCHOR

BOLT NUT & WASHER

5D

B B

COVER WITH HANDLE

AND CHAIN RETAINER

GASKETED AND

PRESSURE SEALED

ROUND OR

FLAT OVAL

DUCT SECTION

HOUSING WELDED TO

DUCT SECTION

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M502

DETAILS CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

M

IN

[1 m m

0m m

0m m

[1 2"

M

IN

[6

M

IN

.]D

U C

T H

E

IG

H T

H1 /3

H

/3 H

/3

H

D

D

STRAINER

FS

TT TT

DIAPHRAGM EXPANSION TANK

TANK SADDLE

TO PUMP SUCTION

PITCH UP 1.6%

SLOPE (MIN.)

HANGER ROD

SUPPORTS (TYPICAL)

CONNECTOR PIPE

NORMALLY OPEN GATE

VALVE IN VERTICAL

(REMOVE HANDLE)

RUN DRAIN LINE TO

NEAREST F.D.

UNLESS INDICATED

OTHERWISE

FROM SYSTEM

AIR SEPARATOR

SEE NOTES NO.

3 & 4

DRAIN

COLD WATER FILL LINE.

SEE EXPANSION TANK

SCHEDULE FOR SIZE

NC

RUN DRAIN

LINE TO

NEAREST FD

REDUCED PRESSURE ZONE

BACKFLOW PREVENTER

BUTTERFLY OR BALL

ISOLATION VALVE

HANGER

RODS (TYP)

AV

AUTOMATIC AIR VENT

NOTES:

1. SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.

2. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS SHOWN

ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY FOR HOT WATER HEATING.

3. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN EXPANSION TANK SCHEDULE.

4. FOR HOT WATER SYSTEMS 50mm [2"] AND SMALLER AND CHILLED WATER SYSTEMS USE

IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.

5 SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM HAS A

MINIMUM OF 28kPa. [4 PSIG]

NOTES:

1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO

TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.

2. PROVIDE BYPASS PIPING.

SEE DRAWINGS FOR PIPE SIZES

TO RETURN MAIN

SCHEDULE 80 STEEL PIPE

PIPE SIZE SHALL BE SAME SIZE AS TRAP

INVERTED BUCKET TRAP. SEE PLANS,

AND SCHEDULES

DIELECTRIC FITTING WHERE

RETURN IS COPPER PIPE

FLOW

SCHEDULE 80

STEEL PIPE

BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH

TRAP OR IN VERTICAL PLANE & BELOW TRAP

DRIP LEG OR EQUIPMENT CONNECTION. MAKE

THE SAME SIZE AS THE SUPPLY MAIN OR

EQUIPMENT CONNECTION. SEE NOTE 1

1" GATE VALVE

USE 4-BOLT RAISED FACE FLANGES

STEAM

CONDENSATE

RETURN

TEMPERATURE

SWITCH

SCALE POCKET

HUMIDIFIER CONTROL

VALVE

TO HUMIDISTAT

MANIFOLD PIPE ADAPTERS

STEAM SUPPLY

ON-OFF CONTROL VALVE DUCT CROSS SECTION

INVERTED BUCKET

TRAP ASSEMBLY

NOTE:

SEE MANUFACTURER'S PIPING RECOMMENDATIONS

FOR FINAL LAYOUT

COOLING COIL

FAN-COIL UNIT, ERV PIPING

HEATING COIL

FAN-COIL UNIT, ERV. UNIT HEATER PIPING

INSTALLATION OF THERMOMETER WELLS

IN-LINE PUMPS - CONNECTIONS

TYPICAL STEAM LINE & DRIP PIPING

AIR COOLED CHILLER - PIPING CONNECTIONS

HORIZONTAL EXPANSION TANK -

PIPING CONNECTIONS

TO FIN TUBE RADIATORS

TYPICAL WATER PIPING CONNECTIONS

WATER FLOW MEASURING STATION

(WITH BTU METER) STEAM METER DETAILSTEAM LINE DRIP POCKET STEAM TRAP ASSEMBLY

STEAM PRESSURE REDUCING STATION

DOUBLE VALVE (1/3 AND 2/3)

STEAM SAFETY VALVE

INVERTED BUCKET STEAM TRAP

STEAM HUMIDIFIER PIPING

BALANCING

DEVICE

NOTES:

1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

BALL OR BUTTERFLY TYP.

FLEXIBLE

CONNECTION

1/2" [15mm]

PRESSURE GAGE

PIPE HANGERS - PROVIDE DOUBLE

DEFLECTION NEOPRENE (TYPE HN) FOR

FIRST TWO ON EACH SIDE OF PUMP

(SEE NOTE NO. 1)

THERMOMETER

FLOW SWITCH

FLEXIBLE

CONNECTORS

IF REQUIRED

TEST PLUGS

CHS

EVAPORATOR

CHR

DDC

TEMPERATURE

SENSOR TO ECC

PRESSURE

GAUGE

UNDER CANOPY

AND FACTORY ASSEMBLED.

SAME SIZE AS RUNOUT PIPING

FLOW CONTROLLER WITH INTEGRAL

PRESSURE-TEMPERATURE TEST

CONTROL VALVE. REFER TO FAN COIL

PRESSURE-TEMPERATURE TEST

AUTOMATIC - NORMALLY OPEN

MANUAL AIR VENT

SHUT-OFF VALVE

FLEXIBLE POLYETHYLENE TUBING.

3/4" CONDENSATE DRAIN PIPE.

CONNECT TO UNIT PAN WITH

UNIT DRAIN PAN

STRAINER

PLUG.

PLUG

COIL DRAIN PAN

COIL

UNION

COIL

MANUAL AIR VENT

AND FACTORY ASSEMBLED.

SAME SIZE AS RUNOUT PIPING

FLOW CONTROLLER WITH INTEGRAL

PRESSURE-TEMPERATURE TEST

PRESSURE-TEMPERATURE TEST PLUG

PLUG

STRAINER

SHUT-OFF VALVE

UNION

REDUCER, IF REQUIRED

REDUCER, IF REQUIRED

THREE-WAY VALVE.

UNIT SCHEDULE FOR TWO-WAY OR

CONTROL VALVE. REFER TO FAN COIL

AUTOMATIC - NORMALLY OPEN

THREE-WAY VALVE..

UNIT SCHEDULE FOR TWO-WAY OR

2 1/2" DIA.

HORIZONTAL

2" DIA. & SMALLERABOVE 2" DIA. PIPE

2 1/2" DIA.

VERTICAL

2" DIA. & SMALLERABOVE 2" DIA. PIPE

STEAM TRAP ASSEMBLY

GLOBE VALVE

NC

12" MIN.

SAME SIZE AS MAIN

NOTES :

STEAM MAIN

BACK 1/4" PER FOOT.

6" MIN.

SET - SEE DETAIL ON

THIS SHEET.

INVERTED BUCKET TRAP

LP & GRAVITY

RETURN

HP & MP RETURN

UNTRAPPED RUNOUT. SLOPE

ECCENTRIC REDUCERS (BOTTOM FLAT)

ARE REQUIRED FOR ALL REDUCTIONS

IN SUPPLY STEAM PIPES

SEE STEAM TRAP ASSEMBLY

DETAIL ON THIS SHEET

S C

A L E

P O

C K

E T

S C

A L E

P O

C K

E T

D R

IP

L

E G

D R

IP

L

E G

BYPASS - INSTALL IN HORIZONTAL PLANE

LEVEL WITH TRAP OR IN VERTICAL PLANE

AND BELOW TRAP.

TO RETURN MAIN - SEE

DRAWINGS FOR PIPE SIZES

DIELECTRIC FITTING

(WHERE METAL

MATERIALS ARE

DISSIMILAR)

CHECK VALVE

GATE VALVE (TYP.)

STRAINER

FLOAT AND THERMOSTATIC OR INVERTED

BUCKET TRAP (SEE PLANS & LEGEND)

3/8" TEST CONNECTION

DRIP

RETURN

FROM DRIP LEG

OR EQUIPMENT

CONNECTION

PIPE SIZES SAME AS CONNECTION ON

TRAP - 3/4" MIN.

STEAM LINE DRIP POCKET

NOTE:

DRIP LEG PIPE SIZE SAME AS

STEAM MAIN UNLESS

OTHERWISE NOTED.

PIPE T0 STEAM

TRAP (TYPICAL)

CAP (TYPICAL)

STEAM LINE

(TYPICAL)

3/4" DRAIN (ALTERNATE

LOCATIONS) (TYPICAL)

DRIP LEG (TYP.)

M

IN

M

M

M

IN

NOTES:

A. PROVIDE DIELECTRIC FITTING WHERE COPPER TUBING AND

FERROUS METAL PIPES ARE JOINED.

B. SUPPORT PIPING AND EQUIPMENT INDEPENDENTLY. EQUIPMENT

SHALL NOT BE USED TO SUPPORT PIPING.

NOTES:

A. PROVIDE DIELECTRIC FITTING WHERE COPPER TUBING AND

FERROUS METAL PIPES ARE JOINED.

B. SUPPORT PIPING AND EQUIPMENT INDEPENDENTLY. EQUIPMENT

SHALL NOT BE USED TO SUPPORT PIPING.

HEATING ELEMENT(S)

TEST PLUG

STRAINER

BALL VALVE

CABINET

UNION OR SOLDER

CONNECTION TYPICAL

AUTOMATIC FLOW CONTROL VALVE

EXISTING FLOOR

SLAB

CONTROL VALVE

DIELECTRIC UNION IF METALS DISSIMILAR

HWR

HWS

INTERFACE WITH

BUILDING CONTROLLER

RETURN

BTUH METER

WITH BACNET

INTERFACE

NOTE:

1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES

NOTE:

1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURERS

TT

PT

PRESSURE

TRANSMITTER

TEMPERATURE

TRANSMITTER

FLOW METER

INTERFACE

WITH BACNET

SYSTEM

DIFFERENTIAL PRESSURE (DP) CEL

STEAM FLOW MEASUREMENT

SHUTOFF VALVE

TO METERING

SYSTEM

BUILDING INCOMING

MAIN STEAM

SUPPLY

FLOW ELEMENT

TEMPERATURE ELEMENT

TE

TEFE

V

NOTE:

SIPHON

(TYP.)

PILOT CONTROL LINE

REDUCER (TYP.)

IF REQUIRED.

NOTE 1

D1

N.C.

D2

D2

4 D2 MIN.

20 D2 MIN.10 D1 MIN.

NOTE 1

NOTE 3

INVERTED

BUCKET TRAP

ASSEMBLY TYP.

STEAM SAFETY VALVE

D

PROVIDE UNION UNLESS SAFETY

VALVE HAS FLANGED OUTLET

SAFETY VALVE

OPEN DRAIN (NOTE 3)

CONNECTION TO PRESSURE

VESSEL OR PIPE

VENT FULL SIZE PIPE THROUGH

ROOF SUPPORT AS INDICATED

ON DWGS. (NOTES 1, 2)

PIPE THREADED INTO ELBOW

(SAME SIZE AS ELBOW)

DRIP PAN ELBOW

(SECTIONAL VIEW)

3/4" DRAIN TO FLOOR

DRAIN OR OPEN

SIGHT DRAIN (NOTE 4)

M

IN

24" MAX.

3"

ELEVATION

NOTES:

FLEXIBLE

CONNECTOR

PIPE SHALL BE FULL SIZE OF

SAFETY RELIEF VALVE DRIP

PAN ELBOW OUTLET. VENT TO

ATMOSPHERE (OUTDOORS).

1 SLOPE MAINS AND BRANCHES DOWN 1" PER 40 FEET IN DIRECTION OF

FLOW UNLESS SHOWN OTHERWISE.

2 LIMIT UNTRAPPED, COUNTERFLOW, RUNOUTS TO 10 FEET MAXIMUM.

3 END OF MAIN SHOWN, LOW POINT IN STEAM MAIN SIMILAR.

1. SEE PIPING SCHEMATIC FOR PIPE SIZES.

2. SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2. INSTALL

VALVES AS RECOMMENDED BY MANUFACTURER.

3. MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST PRV.

4. PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED

CONNECTIONS.

1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT

BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN ANSI

B31.1. POWER PIPING CODE, APPENDIX II.

2. VENT PIPE SHALL TERMINATE 6' MIN. ABOVE FINISHED ROOF.

3. DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHICH

PERSONNEL MAY OCCUPY.

4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M503

DETAILS CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

SCALE: NONE

4"

HWR

50 PSI

FLOOR

H W

S

4"

4"

-H W

A S

0.75"

EXTEND TO FLOOR DRAIN

1.25"

FUNNEL

0.5"1.25"

4"

0.75"

408-HWF1

0.75"

HWS

4"

HWR

FLOOR

4"

4"

H W

S

1 THERMOSTATIC AIR VENT.

2 SEE DETAIL ON SHEET M503.

3 PROVIDE LOW WATER LEVEL ALARM. PROVIDE A LOW

WATER LEVEL AT ECC. RELIEF VALVE DRAIN SHALL

4 EXTEND SAFETY RELIEF VALVE DISCHARGE TO

5 CONVERTER SHALL BE SUSPENDED HIGH ENOUGH

TO ALLOW GRAVITY DRAINAGE OF CONDENSATE .

6 PROVIDE BACK PRESSURE REGULATING VALVE.

SET REGULATING VALVE TO MAINTAIN MAKE-UP

7 PROVIDE SADDLE SUPPORTS AND ANGLE FRAME.

8 WALL MOUNTED "ON-OFF" MOTOR CONTROL.

9 PROVIDE 0.75" HOSE CONNECTION AND SCREW-ON CAP.

10 ALLOW SPACE FOR INSULATING FILTER AND PIPING.

11 INSTALL TOP OF CHEMICAL POT FEEDER TANK NO MORE

THAN 3'-0" ABOVE FLOOR.

12 MAKE-UP PIPING SYSTEM DOES NOT REQUIRE INSULATION.

13 CONCRETE PAD.

14 AUTOMATIC LINE SIZE ISOLATION CONTROL VALVE.

15 FLEXIBLE PIPE CONNECTION.

16 MANUAL AIR VENT WITH SHUT-OFF VALVE.

17 PROVIDE GLYCOL-WATER MAKE-UP PUMP 5 GPM @ 30 PSIG.

CHEMICAL

POT FEEDER

AUTOMATIC

FLOW CONTROL

VALVE.

MANUAL AIR VENT

4"

9 0.75"

1" 9 1"

FROM SYSTEM

FLOOR

PRESSURE GAGE

0.5"

408-CWP2

WALL SLEEVE

PROVIDE ALUMINUM JACKET

AND HEAT TRACE ON ALL

EXTERIOR PIPING

CHR

(TYPICAL)

5"

0.5"

5"

GRADE

15 16

CHS

408-ACCH2

4"

WALL

CHS

TO SYSTEM

5"

CHS

C H

R

PRESSURE GAGE

0.5"

0.75"

0.75"

408-C2

2.5"

2.5"

75 PSI

HWS

HWR

408-C3

HWR

HWS

THERMOMETER

PRESSURE GAGE

408-HWP1

0.5"

5 7

1 14 2.5"

75 PSI

2.5"

D

CHS

5"

RETURN TO TANK AS SHOWN ON THIS DETAIL.

PRESSURE AT 15 PSIG (103 kPa) ABOVE HIGHEST

SYSTEM PRV SETTING.

SUPPORT HEAT EXCHANGER OFF FLOOR.

FLOOR DRAIN.

OPERATE PUMP MANUALLY AS REQUIRED TO FILL.

18 SUSPEND UNIT FROM STRUCTURE.

EXPANSION TANK

408-CWAS1

0.75" 12

0.75"12

55 GALLON GLYCOL-WATER

STORAGE TANK

408-GCWP1

FROM SYSTEM

TO SYSTEM

408-C1

2.5"

2.5"

75 PSI

HWR

HWS

0.5"

15 16

13 9 5"

408-HWP2

9 9

CHR

4" 5"

CHS

4"

408-ACCH1

PREFABRICATED

UNDERGROUND PIPING

19 WALL MOUNTED "ON-OFF" MOTOR CONTROL.

20 0.75" DOMESTIC COLD WATER.

21 HOSE BIB FOR MANUAL MIXING OF GLYCOL WHEN REQUIRED.

0.75"

DCWPRESSURE GAGE

0.5"

408-CWP1

408-BT1

5"

5"

5" 5" 0.75"

EXTEND TO FLOOR DRAIN

1.25"

FUNNEL

0.5" 1.25"

0.75"

408-CWF1

0.75"

11CHEMICAL

POT FEEDER

AUTOMATIC

FLOW CONTROL

VALVE.

90.75"

0.75"

0.75"

CHR

TE

TEFE

TE

TEFE

V

22 VACUUM BREAKER.

V

V

THERMOMETER

THERMOMETER

23 DEVICES PROVIDED FOR BTU METER.

NOTES

HEATING HOT WATER SYSTEM SCHEMATIC

CHILLED WATER SYSTEM SCHEMATIC

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M504

HYDRONIC PIPING SCHEMATICS CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

VENT TO OUTSIDE OF BUILDING

FLOORBASEMENT

FLOOR

CONTROL

CABINET

V

408-CP1

1.5"

LPR

2"

3"

408-C2

M P

S

M P

R

HWR

HWS

12" MIN.

6" MIN.

408-C3

M P

S

M P

R

HWS

HWR

12" MIN.

6" MIN.

HPS (125)

3"

MPRMPR

MPS (30)

V

V

V

PC

VV

2.5"

2.5"

2"

2.5"

2.5"

2"

4"

4"

3"

2.5"

3"

4"

3"

4"

4 4

4"

17 18

17 18

17 18

21 17 18

2"

3"

2.5"

3"

0.75"

2 15

2"

3"

2.5"

3"

0.75"

M P

R

17 18

V

4" 29

N.C.

V

TO FLOOR

DRAIN

2"

2"

2"

2" 2"

408-PRV1B

408-PRV1A

V

40 PSI

HPR

0.75"

3"

3"

2"

3" 4"

3"

4"

4"

4"

3"

17 18

17 18

3"

H P

R

MPS (30)

HPR

PIPE WITH 1/4" PERFORATIONS SHALL

EXTEND FULL LENGTH OF TANK AND SHALL

BE SAME DIAMETER OF CONDENSATE RETURN

CONNECTION TO TANK. TOTAL AREA OF ALL

1/4" PERFORATIONS SHALL BE EQUIVALENT

TO THE TRANSVERSE AREA OF THE PIPE.

408-FT1

DIELECTRIC FITTING

(WHEN RETURN IS COPPER)

4" MIN. BELOW WATER LINE

V

0.75"0.75"

WATER LINE (1" ABOVE

TANK CENTERLINE)

3"

0.75"

0.75"

408-C1

M P

S

M P

R

HWR

HWS

12" MIN.

6" MIN.

3"

17 18

17 18

2"

3"

2.5"

3"

0.75"

2 15

2.5"

2"

2"

2.5" 2.5"

GENERAL NOTES

A STEAM SYSTEM SHALL ONLY BE DOWN BETWEEN

THE MONTHS OF JUNE AND SEPTEMBER.

B REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS

AND ADDITIONAL GENERAL NOTES.

NOTES

1 THERMOSTATIC AIR VENT.

2 0.5 CHECK VALVE VACUUM BREAKER.

3 DIELECTRIC FITTING (WHERE RETURN IS COPPER).

4 EXTENT FULL SIZE STEAM VENT PIPE UP THRU ROOM.

TERMINATE 6 FEET ABOVE FINISHED ROOF LEVEL.

5 F&T TRAP ASSEMBLY. REFER TO DETAIL ON SHEET M503.

6 SCALE POCKET.

7 STEAM LINE DRIP ASSEMBLY WITH INVERTED BUCKET TRAP.

REFER TO DETAIL ON SHEET M503.

8 FULL SIZE DRAIN TO FLOOR DRAIN.

9 PROVIDE SADDLE SUPPORTS AND ANGLE FRAME TO SUPPORT

HEAT EXCHANGER OFF FLOOR. HEAT EXCHANGER SHALL BE

SUSPENDED HIGH ENOUGH TO ALLOW GRAVITY PRESSURE

GAUGE WITH SIPHON.

10 PRESSURE GAGE WITH SIPHON.

11 SPRING LOADED CHECK VALVE.

12 AUTOMATIC CONTROL VALVE. SIZE FOR 1/3 STEAM LOAD

CAPACITY.

13 FULL SIZE OVERFLOW DRAIN. TRAP, VENT AND PIPE TO FLOOR

DRAIN.

14 REFER TO HOT WATER SYSTEM SCHEMATIC ON SHEET M504.

15 AUTOMATIC CONTROL VALVE. SIZE FOR 2/3 STEAM LOAD

CAPACITY.

16 EXTEND TO EXISTING CAMPUS HIGH PRESSURE (125 PSI)

STEAM LINE. REFER TO FLOOR PLANS.

17 NORMALLY CLOSED BYPASS GLOBE VALVE.

18 INSTALL BYPASS IN HORIZONTAL PLANE LEVEL WITH TRAP OR

VERTICAL PLANE AND BELOW TRAP. DO NOT BLOCK ACCESS

FOR SERVICING TRAP.

19 PRESSURE-TEMPERATURE TEST PLUG.

20 PILOT CONTROL LINE.

21 SHUT-OFF VALVE WITH HOSE CONNECTION AND SCREW ON CAP.

22 SAFETY RELIEF VALVE WITH DRIP PAN ELBOW. SEE DETAIL ON

M502.

23 STEAM PRESSURE REDUCING STATION. SEE DETAIL ON SHEET

M502 AND SCHEDULE ON SHEET M 603.

24 30-300 DEG. F. THERMOMETER.

25 EXISTING LOW PRESSURE CONDENSATE TO ATTIC. CONVERT TO

MEDIUM PRESSURE CONDENSATE.

26 PROVIDE 5" HIGH CONCENTRATE EQUIPMENT BASE PER DETAIL ON

SHEET M502.

27 31 GALLON FLASH TANK. 16" DIA. x 36" LONG.

28 EXTEND TO EXISTING CAMPUS PUMPED CONDENSATE LINE.

REFER TO FLOOR PLANS.

29 ANTICIPATED SIZE SHOWN. COORDINATE WITH RELIEF VALVE

MANUFACTURER.

30 BAFFLE TYPE MOISTURE SEPARATOR.

31 EXISTING STEAM AND CONDENSATE PIPING TO BUILDING

PERIMETER HEATING SYSTEM.

32 PROVIDE ANGLE FRAME TO SUPPORT FLASH TANK AT A LEVEL

WHICH ALLOWS GRAVITY FLOW FROM HEAT EXCHANGER.

33 EXISTING LOW PRESSURE STEAM PIPE TO ATTIC. CONVERT TO

MEDIUM PRESSURE (30 PSI) STEAM.

34 DO NOT LIFT PIPING.

35 SLOPE PIPE BACK TO FLASH TANK.

36 NORMALLY CLOSED BYPASS VALVE.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M505

STEAM PIPING SCHEMATIC CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

DUCT CONSTRUCTION, SEALING, AND INSULATION

GENERAL NOTES:

A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:

SHEET METAL DUCT; INTERIOR LINING; EXTERIOR

INSULATION; FIBERGLASS DUCTBOARD; ETC.

B. DUCT CONSTRUCTION AND SEALING SHALL BE PER

LATEST S.M.A.C.N.A. STANDARDS.

NOTES:

1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.

2. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL / ROOF.

3. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS LONGITUDINAL SEAM.

DUCT SYSTEM

S.P. CON-

STRUCT.

SEAL

CLASS

LEAKAGE

CLASS

S.M.A.C.N.A. CLASS.

INTERNALLY

LINED

EXTERNAL

INSULATION

NOT

INSULATED

SEE

NOTE

DOUBLE

WALL

INSULATEDRECT RND

1,3

NOTE 3

+3" A 8

+1" 16

16 8

A

A

A

SUPPLY DUCTWORK UPSTREAM OF

VAV BOXES FOR AHU-

SUPPLY DUCTWORK DOWNSTREAM OF

VAV BOXES AHU-

RETURN DUCTWORK -2"

TOILET OR GENERAL EXHAUST

DUCTWORK

-1" 16 -

HVAC DESIGN DATA

GENERAL NOTES:

A. OUTDOOR DESIGN CONDITIONS:

90.4°F DB SUMMER

73.5°F WB SUMMER

2°F DB WINTER

NOTES:

1. LISTED RH IS MAXIMUM ANTICIPATED AT LISTED DB TEMPERATURE.

2. REFER TO ATC SEQUENCES FOR ACTUAL ROOM SETPOINTS.

3. LISTEN RH IS MINIMUM ANTICIPATED AT LISTED DB TEMPARTURE.

SPACE NAME / TYPE °F DB

INTERIOR DESIGN DATA

SEE NOTE

OFFICES 2

SUMMER WINTER

% RH

(NOTE 1) °F DB

% RH

(NOTE 3)

75 60 70 20

- - 68 -

81 60 64 30

75 60 70

75 60 70

80 - 60 -

BATHROOMS AND TOILET

ROOMS

DATA CLOSETS

CONFERENCE ROOMS

ALL OTHER SPACES

UNOCCUPIED MODE

B. DESIGN ALTITUDE: 1004 FT.

FOUR PIPE FAN COIL UNIT SCHEDULE

TYPE

1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.

2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.

NO.

UNIT

HEATING REQUIREMENTS WITH

180°F ENT. WATER TEMP.

GPM

COOLING REQUIREMENTS WITH

44°F ENT. WATER TEMP.

MIN.

MBH

TOTAL

FAN

CFM

MIN.

MBH

SENS.

ENT. AIR F°

WbDb

MAX. LOSS

FT. WATER

THRU COILGPM

AUTO

VALVE

TYPE

RUN-

SIZE

OUT

MIN.

MBH

ENT.

AIR

FAN MOTOR

AUTO

VALVE

RUN-

SIZE

OUT

W (QTY.)

NOM. HP

APPROXIMATE SIZE

L

VOLT.-

HW

NOTES

NOTES:

MAX. LOSS

THRU COIL

AUTO

VALVE

AUTO

VALVE

TYPE

408-FCU-2

408-FCU-3

408-FCU-4

408-FCU-5

408-FCU-1A

ESP

O.A.

CFM

(30% PROPYLENE GLYCOL)

408-FCU-7

408-FCU-8

408-FCU-9

408-FCU-10

408-FCU-6

408-FCU-11

408-FCU-12

408-FCU-13

408-FCU-14

408-FCU-15

408-FCU-16

408-FCU-17

408-FCU-18

408-FCU-19

408-FCU-20

408-FCU-21

408-FCU-22

408-FCU-23

408-FCU-24

408-FCU-25

408-FCU-26

408-FCU-27A

408-FCU-28

408-FCU-29

408-FCU-30

408-FCU-31

408-FCU-10A

408-FCU-27

408-FCU-23A

408-FCU-5A

408-FCU-14A

408-FCU-23B

408-FCU-23C

408-FCU-23D

13.7670 100 12.7 2.5 5.0 25.8 70 5.0 142 (4) 115-1 1,20.75"1.2 2563.075.0 10691.71"HORIZONTAL CONCEALED DUCTED 1.20.4" 2-WAY 2-WAY

13.5660 100 12.6 2.4 5.0 25.6 70 5.0 140 (4) 115-1 1,20.75"1.163.075.0

1.70.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

9.4450 70 8.7 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 2-WAY63.075.0

1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY

7.5330 55 6.8 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"63.075.0

1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.40.4" 2-WAY

7.6340 200 6.9 1.4 5.0 70 5.0 73 (2) 115-1 1,20.75"63.075.0

1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.60.4" 2-WAY

0.32-WAY 2-WAY3.6140 65 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

14.3640 235 13.0 2.6 5.0 21.7 70 5.0 134 (4) 115-1 1,20.75"1.263.075.0 1.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

9.3440 70 8.5 1.7 5.0 70 5.0 78 (2) 115-1 1,20.75"0.8 2-WAY63.075.0

1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 16.90.4" 2-WAY

10.6520 80 9.9 1.9 5.0 20.5 70 5.0 105 (2) 115-1 1,20.75"0.963.075.0

1.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

21.2980 220 19.5 4.0 5.0 30.5 70 5.0 430 (2) 115-1 1,20.75"1.963.075.0

2.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

0.22-WAY 2-WAY2.9100 45 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

13.0410 130 12.0 2.3 5.0 21.1 70 5.0 132 (4) 115-1 1,20.75"1.163.075.0 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

12.4555 235 11.2 2.3 5.0 20.2 70 5.0 122 (4) 115-1 1,20.75"1.163.075.0 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

12.2545 125 11.0 2.2 5.0 21.0 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

0.32-WAY 2-WAY4.0180 50 3.6 0.7 5.0 8.8 70 5.0 35 115-10.75"63.075.0 330.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

12.2550 90 11.0 2.2 5.0 21.1 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

0.32-WAY 2-WAY3.6140 135 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

10.6535 85 10.0 1.9 5.0 20.1 70 5.0 109 (2) 115-1 1,20.75"0.963.075.0 590.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

0.32-WAY 2-WAY3.1120 30 2.7 0.6 5.0 5.5 70 5.0 26 115-10.75"63.075.0 330.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

12.9530 155 11.3 2.3 5.0 20.7 70 5.0 116 (4) 115-1 1,20.75"1.163.075.0 760.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

12.2540 200 11.0 2.2 5.0 20.9 70 5.0 120 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

17.0865 140 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.6210 200 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"63.075.0 0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.32-WAY 2-WAY3.9250 130 3.8 0.7 5.0 7.7 70 5.0 48 115-10.75"63.075.0 100.50.75" 0.2VERTICAL FLOOR SET 0.4" 1,2

17.8960 265 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

17.8960 240 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

16.0775 120 14.8 2.9 5.0 27.9 70 5.0 155 (4) 115-1 1,20.75"1.463.075.0 761.90.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

9.8490 75 9.2 1.8 5.0 19.8 70 5.0 56 (2) 115-1 1,20.75"0.8 2563.075.0 10551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

8.0370 55 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY63.075.0 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY

13.4935 215 13.2 2.4 5.0 28.4 70 5.0 120 (4) 115-1 1,20.75"1.163.075.0

1.91"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY

11.7820 270 11.5 2.1 5.0 20.4 70 5.0 115 (4) 115-1 1,20.75"1.063.075.0 101.41"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY

-- - - - 5.0 - 70 5.0 - 115-1 1,20.75"- -63.075.0 ---1"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY

VERTICAL FLOOR SET

VERTICAL FLOOR SET

-- - - - 5.0 70 5.0 - 115-1 1,20.75" -63.075.0 ---0.75" 0.2- 2-WAY-0.4" 2-WAY

-- - - - 5.0 70 5.0 - 115-1 1,20.75" -63.075.0 ---0.75" 0.2- 2-WAY-0.4" 2-WAY

15.2710 215 14.0 2.8 5.0 26.6 70 5.0 145 (4) 115-1 1,20.75"1.363.075.0

1.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

NOM

408-FCU-1B HORIZONTAL CONCEALED DUCTED 11.4485 75 10.2 2.1 5.0 21.5 70 5.0 110 (4) 115-1 1,20.75"- 2563.075.0 10

1.30.75" 0.40.4" 2-WAY 2-WAY

1.4

1.4

1.4

1.4

1.4

0.5

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

77 24

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

45 24

25 10

25 10

25 10

25 10

25 10

32 17

25 10

25 10

25 10

25 10

85 24

25 10

25 10

25 10

25 10

EGGCRATE CEILING REGISTERCR1

DAMPER

OPPOSED BLADE

SURFACE

TYPE MOUNTING

DESCRIPTION

EGGCRATE CEILING GRILLE

STANDARD SQ. PLAQUE CEILING

DIFFUSER ROUND NECK

SYMBOL

CD1

CG1

LAY-IN

FINISH

E.C.L.STEEL ALUM.

MATERIAL

ACCESSORIES

W.B.E.

SEE

EGGCRATE CEILING GRILLE

CG2

STANDARD SQ. PLAQUE CEILING

DIFFUSER ROUND NECK

CD2

NOTES:

1. PROVIDE 48" LONG DEVICE WITH 3 - 1" SLOTS. PROVIDE CENTER NOTCH AS REQUIRED TO ACCOMMODATE 2'X2' GRID.

LINEAR PLENUM SLOT

ADJUSTABLE BLADE DIFFUSER

CD3 1

EGGCRATE CEILING REGISTERCR2

DAMPER

OPPOSED BLADE

EGGCRATE CEILING FILTER GRILLE

CG3

EGGCRATE CEILING FILTER GRILLE

CG4

NOTE

FILTER

FILTER

TR1

DAMPER

OPPOSED BLADE

TR2

DAMPER

OPPOSED BLADE

ADJUSTABLE AIRFOIL BLADE SUPPLY

REGISTER - DOUBLE DEFLECTION

FIXED AIRFOIL BLADE RETURN

REGISTER

AIR DISTRIBUTION DEVICES

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M601

SCHEDULES CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

FOUR PIPE FAN COIL UNIT SCHEDULE (CONTINUED)

TYPE

1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.

2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.

NO.

UNIT

HEATING REQUIREMENTS WITH

180°F ENT. WATER TEMP.

GPM

COOLING REQUIREMENTS WITH

44°F ENT. WATER TEMP.

MIN.

MBH

TOTAL

FAN

CFM

MIN.

MBH

SENS.

ENT. AIR F

WbDb

MAX. LOSS

FT. WATER

THRU COILGPM

AUTO

VALVE

TYPE

RUN-

SIZE

OUT

MIN.

MBH

ENT.

AIR

FAN MOTOR

AUTO

VALVE

RUN-

SIZE

OUT

W (QTY.)

NOM. HP

APPROXIMATE SIZE

L

VOLT.-

HW

NOTES

NOTES:

MAX. LOSS

THRU COIL

AUTO

VALVE

AUTO

VALVE

TYPE

ESP

O.A.

CFM

(30% PROPYLENE GLYCOL)

408-FCU-32

408-FCU-33

408-FCU-34

408-FCU-35

408-FCU-36

408-FCU-37

408-FCU-38

408-FCU-39

408-FCU-40

408-FCU-41

408-FCU-42

408-FCU-43

408-FCU-44

408-FCU-45

408-FCU-46

408-FCU-47

408-FCU-48

408-FCU-49

408-FCU-50

408-FCU-51

408-FCU-52

408-FCU-53

408-FCU-54

408-FCU-55

408-FCU-56

408-FCU-57

408-FCU-58

408-FCU-59

408-FCU-60

408-FCU-61

408-FCU-62

408-FCU-63

408-FCU-64

408-FCU-65

408-FCU-66

408-FCU-67

408-FCU-68

408-FCU-69

408-FCU-70

408-FCU-71

408-FCU-72

408-FCU-73

408-FCU-40A

0.42-WAY 2-WAY4.6210 170 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75" 2567.080.0 10370.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 2567.080.0 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9100 40 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.965 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.935 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.52-WAY 2-WAY5.2185 90 4.3 1.0 5.0 9.0 70 5.0 44 (2) 115-10.75" 480.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9100 160 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.32-WAY 2-WAY3.0105 170 2.5 0.6 5.0 5.5 70 5.0 24 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.6205 30 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9125 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.32-WAY 2-WAY3.6150 45 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.32-WAY 2-WAY3.6150 180 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.52-WAY 2-WAY5.4220 90 4.7 1.0 5.0 8.7 70 5.0 47 (2) 115-10.75" 430.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.6210 210 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.32-WAY 2-WAY3.6140 50 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.6205 200 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.5200 200 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

0.42-WAY 2-WAY4.5200 150 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

16.9860 140 15.9 3.1 5.0 32.2 70 5.0 169 (4) 115-1 1,20.75"1.5 2567.080.0 10762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

24.41270 195 23.2 4.5 5.0 34.5 70 5.0 430 (2) 115-1 1,20.75"2.1 672.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

20.81020 155 19.4 3.9 5.0 29.2 70 5.0 430 (2) 115-1 1,20.75"1.8 631.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

16.2795 120 15.1 2.9 5.0 31.0 70 5.0 158 (4) 115-1 1,20.75"1.4 2.11"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

17.3905 275 16.4 3.1 5.0 33.1 70 5.0 176 (4) 115-1 1,20.75"1.5 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

27.41600 240 27.4 5.1 5.0 45.3 70 5.0 430 (2) 115-1 1,20.75"2.4 693.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

12.8625 365 12.8 2.4 5.0 17.8 70 5.0 132 (4) 115-1 1,20.75"1.1 1.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

23.71205 185 23.7 4.4 5.0 33.6 70 5.0 430 (2) 115-1 1,20.75"2.1 692.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY

13.0615 95 12.0 2.3 5.0 21.2 70 5.0 133 (4) 115-1 1,20.75"1.1 2567.080.0 10691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

13.0605 95 11.9 2.3 5.0 21.1 70 5.0 131 (4) 115-1 1,20.75"1.1 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

10.3560 145 9.6 1.8 5.0 20.0 70 5.0 88 2) 115-1 1,20.75"0.8 551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

12.4555 85 11.2 2.3 5.0 20.1 70 5.0 144 115-1 1,20.75"1.1 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

2.9- 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYVERTICAL FLOOR SET 0.4" 2-WAY

2.9100 - 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

9.1395 185 9.1 1.6 5.0 15.9 70 5.0 71 (2) 115-1 1,20.75"1.6 551.10.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

9.4450 70 8.6 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 252-WAY67.080.0 10551.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY

7.5330 150 6.7 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

8.3400 65 7.7 1.5 5.0 70 5.0 84 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

8.0370 65 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY

NOM

0.32-WAY 2-WAY3.3130 40 2.8 0.6 5.0 5.8 70 5.0 27 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2

6.8280 45 6.0 1.2 5.0 70 5.0 62 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.00.4" 2-WAY

6.9290 45 6.1 1.3 5.0 70 5.0 64 (2) 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.30.4" 2-WAY

15.0690 105 13.7 2.7 5.0 26.2 70 5.0 142 (4) 115-1 1,20.75"1.3 761.80.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

67.080.0

14.4 1.0

16.0 1.1

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

32 17

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

25 10

32 10

32 10

25 10

25 10

CONVERTER SIZED TO HANDLE 50 PERCENT OF THE PROJECT HEATING LOAD.

CONVERTER SHALL BE SIZED WITH .001 FOULING FACTOR.

APPROXIMATE SIZE: 8" DIA X 40" LONG.

BASEMENT MECH. ROOM

NOTES:

CONVERTER

NO.

408-C1

LOCATION

FLUID

WATER

CONVERTER

ENTERING

STEAM PSIG

MAX. LOSS

IN F

TEMP

CIRCULATING FLUID

GPM

54 160

OUT F

TEMP

ENTERING

FT. FLUID

VALVE

CONTROL

MBH

CAPACITY

HEATING

80013.1 S.F.

HEATING

SURFACE

MINIMUM

CONTROL

LBS/HR

VALVE

843 1686

TRAP

LBS/HR

1,2,3

NOTES

BASEMENT MECH. ROOM408-C2 WATER 13054 160 5 30 80013.1 S.F.15 843 1686 1,2,3

408-C3 BASEMENT MECH. ROOM WATER 54 130 160 5 30 15 13.1 S.F. 800 843 1686 1,2,3

CONVERTER SCHEDULE

TYPE

IN-LINE

VERTICAL

FLUID

CLEAR WATER

LOCATION

NO.

408-HWP1

PUMP

NOTES:

SYSTEM

°F

TEMP

CIRCULATING FLUID

GPM

PUMP HEAD

FT. FLUID

GR.

SP.

EFF.

RPM

NOM.

HP PHASE

MOTOR

208-3

VOLT.-

YES

VFD NOTES

1 MOTOR SHALL BE NEMA PREMIUM EFFICIENCY TYPE.

WATER

HEATING HOT

50 73

MIN.

7.5MECHANICAL ROOM

IN-LINE

VERTICAL

30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1

WATER

CHILLED

36 73 10MECHANICAL ROOM

BASEMENT

IN-LINE

VERTICAL

CLEAR WATER408-HWP1 180108 1 1750208-3 YES 1

WATER

HEATING HOT

50 73 7.5MECHANICAL ROOM

IN-LINE

VERTICAL

30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1

WATER

CHILLED

36 73 10MECHANICAL ROOM

30% GLYCOL408-GCWP1 5

WATER

CHILLED

MECHANICAL ROOM 44 1.0313 --

IN-LINE

HORIZONTAL

0.25 120-1 1750 NO

BASEMENT

BASEMENT

BASEMENT

BASEMENT

HVAC PUMP SCHEDULE

PRESS.

INITIAL

IN TANK

408-HWET1

408-CWET1

HOT

UNIT

NO.

SYSTEM

MAX.MIN.

402000

SYSTEM

TEMP.

RANGE °F

GAL.

APPROX.

SYSTEM

VOLUME

PSIG.

MAX. OPER. PRESS.

TANK

PSIG.

FILL

PSIG.

PRESS.

AT TANK

ATRELIEF

VALVE

PSIG.

21.7 11.3 408-CWAS1

ACCEPT.

VOLUME

MIN.

VOL.

MIN.

GAL.

GAL.

NO.

UNIT

5 200

NO

NO

MAX.

FT.

P.D.

AIR SEPARATOR

GPMIN.

SIZE BUILT-IN

STRAINER

1"

1"

1"

1"

FILL SIZE

WATER

COLDPIPE

SIZE

IN.

TO TANK

IN.

WATER

CHILLED

WATER

HORIZONTAL

TYPE

DIAPHRAGM

NOTES

77 341000 408-HWAS1HORIZONTAL

DIAPHRAGM

EXPANSION TANK SCHEDULE

MBH

MIN.UNIT

NO.

NOTES:

LOCATION

UNIT

TYPE

CFM

ENT. TEMP.

°F

WATERAIR

GPM

AUTO

VALVE

TYPE

RUNOUT

SIZE

AUTO

VALVE

CV

MOTOR

HEIGHT

APPROX. CABINET DIMS.

LENGTH DEPTH

HP

VOLT.-

PHASE

NOTES

(W)

MAX. LOSS

FT. WATER

THRU COIL

1 VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING & RECESS REQUIREMENTS PRIOR TO ORDERING.

8.0408-UH1 HORIZONTAL PROPELLERSEE PLANS 245 60 180 20.8 0.75" 3-WAY 0.4 (25)16"18" 10" 115-1 1

18.4408-UH2 HORIZONTAL PROPELLERSEE PLANS 500 60 180 21.9 0.75" 3-WAY 0.9 (25)16"18" 10" 115-1 1

24.8408-UH3 HORIZONTAL PROPELLERSEE PLANS 580 60 180 22.5 0.75" 3-WAY 1.2 (25)16"18" 10" 115-1 1

HOT WATER UNIT HEATER SCHEDULE

REMARKS

FT. MAX.

WATER P.D.

WITH 0°F AMBIENT TEMP.

SHALL PERFORM SATISFACTORILY

AT MIN. COMPRESSOR CAPACITY

OF CAPACITY REDUCTION TO 25%

CHILLER SHALL BE CAPABLE

2. HIGH SCCR 65k CURRENT RATING.

48 TONS

PERFORMANCE

MINIMUM CAPACITY

WITH 95°F AMBIENT TEMP.

PROVIDE ABOVE PERFORMANCE

AIR COOLED CONDENSER SHALL

LOCATIONEQUIPMENT

CONDENSER

AIR COOLED

COMPRESSOR

NO.

UNIT

408-ACCH1 CHILLER 100 GPM

57°F WATER IN

45°F WATER OUT

MOCP

208-3

11.5

SINGLE POINT UNIT ELECTRIC

NOTES:

VOLT.-

PHASE

MCA

236 250

EFFICIENCY

16.55

MIN. IPLV

(NOTE 1)

MAX A-WEIGHTED

SOUND POWER LEVEL, dBA PRESSURE

(NOTE 1)

SOUND

GRADE

408-ACCH2

1. MANUFACTURER SHALL PROVIDE ALL SOUND MINIMIZING OPTIONS AVAILABLE.

(NOTE 2)

NEW PACKAGED AIR COOLED CHILLER UNIT SCHEDULE

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:5

:3

P

M

M602

SCHEDULES CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

ENERGY RECOVERY VENTILATORS

NOTES:

1. LOW PROFILE – FOR CEILING OR WALL INSTALLATION

2. NO HEAT EXCHANGER VIRUS CROSSOVER - ASTM F1671 TESTED FOR NO VIRUS PENETRATION

3. LOW CROSS-OVER ENERGY RECOVERY COUNTER FLOW CORE <0.5% EATR TESTED TO AHRI 1060

4. TOTAL ENERGY RECOVERY EFFECTIVENESS >60% TESTED TO AHRI 1060

5. MAINTENANCE – WATER WASHABLE ENERGY/HEAT RECOVERY CORE WITH NO MOVING PARTS. PAPER CORES ARE NOT ACCEPTABLE.

6. DIRECT DRIVE PLENUM ECM FANS (< 1 W/CFM)

7. DOUBLE WALL INSULATED CASING WITH MINIMUM R4 PER INCH

8. FACTORY MOUNTED BACNET IP CONTROLS WITH BTL CERTIFICATION

9. HUMAN INTERFACE CONTROLLER.

10. FILTER MONITORING WITH REMOTE ALARM VIA PRESSURE MEASUREMENT ACROSS THE FILTER. MERV13 FILTERS ON OA AND MERV8 FILTERS ON RA.

11. CERTIFICATIONS: UL AND CSA

12. FACTORY MOUNTED HYDRONIC COILS PROVIDED WITH LOOSE VALVES AND ACTUATORS

13. SCR CONTROL ELECTRIC HEATERS

14. SINGLE-POINT POWER CONNECTION WITH UNIT AND ELECTRIC HEATER. MAIN POWER TO THE ELECTRIC HEATER.

MANUFCTR MODEL

SUPPLY EXHAUST SUPPLY EXHAUST

PRE-HEAT ELECTRIC HEATER HEAT EXCHANGER - SUMMER HEAT EXCHANGER - WINTER CHILLED WATER COOLING COIL HOT WATER HEATING COIL ELECTRICAL CONNECTION

EAT LAT CAPACITY CAPACITY

OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY EAT LAT

TOTAL

FLUID TEMP.

FLUID

FLUID EAT LAT SENSIBLE FLOW

FLUID TEMP.

FLUID

FLUID

SINGLE POINT POWER

EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL DB WB DB WB EWT LWT EWT LWT VOLTAGE FLA MCA RFS

CFM CFM in W.G. in W.G. oF oF (kW) (kW) % % % % % % MBH GPM % MBH GPM °F °F % (V) (A) (A) (A)

408-ERV1 OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

408-ERV2

408-ERV3

AIRFLOW AIRFLOW ESP ESP

TYPE

PERCENTRATECAPACITYPERCENT

TYPE

PROP

°F°F°F°F

FLOW

RATECAPACITY

°F°F°F°F°F°F°F°F

REQUIRED MAX.

°F°F°F°F°F°F°F°F

OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

PROP

OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

PROP

1 COIL CAPACITY BASED ON STANDARD AIR AT 0 FT. ALTITUDE. COIL SHALL BE MINIMUM 6 ROWS DEEP.

408-CC1

COIL

NO.

NOTES:

SYSTEM

ERV-1

CFM

3,000 75.1

Wb

ENT. AIR FMAX.

LOSS

FACE

VEL

MAX.

S.P.

FPM.

0.47" 80.8

Db

LVG. AIR F

Db FLUIDWb

GLYCOL 30%

PROPYLENE

LOSS

MAX.

8.69

FT.

TEMP.

CIRCULATING FLUID

INGPM

°F

22.11

OUT

TEMP.

57.1

°F

AUTO

VALVE

CV

AUTO

VALVE

TYPE

MINIMUM

MBH

128.1

TOTAL (1)

MBH

MINIMUM

54.3

SENS. (1)

9.952-WAY

CHILLED WATER COOLING COIL SCHEDULE

408-CC2 ERV-2 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY

408-CC3 ERV-3 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY

ERV-2

ERV-1

ERV-3

408-PH2

408-PH3

408-PH1 3,000 667

FPM.

SYSTEM

COIL

NO. CFM

FACE

VEL

MAX.

LOSS

WATER

WATER

WATER

00.33"

0.33"

0.33"

80 17.73

F

F

FLUID

TEMP. AIR FMAX.

S.P.

ENT. LVG.

TEMP.

CIRCULATING FLUID

GPM

TEMP.

OUTIN

FT. FLUID

8.9 261.6

MAX. LOSS MIN.

MBH

AUTO

VALVE

CV

AUTO

VALVE

TYPE

8-

PRE-HEAT COIL SCHEDULE

261.6

261.6

17.73

17.73

3,000 667

3,000 667

0 80

0 80

8.9

8.9

DISTANCE

ABSORP.

(MAX.)

408-SH1

HUMID.

NO.

ERV-1

SYSTEM

10"

CFM

°F

Db

54.5 30

ON-OFF

VALVE

ENT. ENT.

PSIG

VALVE

CONTROL

STEAM

VALVE

ON-OFF &

CONTROL

LBS/HR

LBS/HR

TRAP

LEAVING AIR

408-SH2 ERV-2 10"3000 54.5 30 24 60 120

408-SH3 ERV-3 10"3000 54.5 30 24 60 120

STEAM HUMIDIFIER SCHEDULE

2" 3"

3" 4"

NOTE: REDUCING VALVE AND RELIEF VALVE TO BE SIZED BY SUPPLIER. ASSEMBLY SHALL BE INSTALLED PER DETAIL AND MANUFACTURER'S RECOMMENDATIONS.

LOCATIONNUMBER

PRV PSIG

STEAM PRESSURE

INLET OUTLET

PRESSURE

RELIEF

SAFETY

MAXIMUM

CAPACITY LBS/HR

REQUIRED

PIPE SIZES

D1 D2

SAFETY RELIEF VALVE

MIN. CAPACITY

LB/HR

SET PRESSURE

PSIG

408-PRV1B 450 560 N/A N/A

408-PRV1A 900 1,130 1,130 40 PSI120 30 40 PSI

120 30BASEMENT

MECH. ROOM

BASEMENT

MECH. ROOM

EQUIPMENT/

HEATING HOT

WATER

AREA SERVED

N/A

HEATING HOT

WATER

STEAM PRESSURE REDUCING VALVE/SAFETY RELIEF VALVE SCHEDULE

BE PROVIDED. REFER TO ARCHITECTURAL DRAWINGS.

LINTELS IN MASONRY WALLS FOR FULL &

SEMI-RECESSED UNIT WALL OPENINGS SHALL

RECESSED UNITS TO HAVE FOUR(4) SIDE

OVERLAP UNLESS OTHERWISE NOTED.

APPROX. CABINET DIMENSIONS

HEATING CAPACITY BASED ON 60 ENT. AIR &

180 ENT. WATER.

MAXIMUM WATER PRESS. DROP THRU COIL

DESCRIPTION

NO.

FT-*

UNIT

FIN TUBE CONVECTOR

1 FT.

GENERAL NOTES

VERIFY/COORDINATE CABINET DIMENSIONS,

MOUNTING & RECESS REQUIREMENTS WITH

ARCHITECTURAL DWGS. PRIOR TO ORDERING.

ELEMENTS

WALL HUNG - 0'-24" AFF

MOUNTING

RUNOUT

MBH

1.5/FT

HTG.

GPM

0.5

SIZE

0.75"

LENGTHVALVE CV

0.2

MIN. AUTO

NOTE 2

DEPTH

6" 1

RECESS

HEIGHT

20"

SEE NOTE

NOTES

1. REFER TO FLOOR PLANS FOR ELEMENT LENGTHS.

2. CABINET LENGTH AS REQUIRED TO CONCEAL ELEMENT AND PIPING.

ROWS OF

STANDARD SLOPED TOP ENCLOSURE.

ROOM HEATING UNITS

UNIT

NO.

408-BT1

DIAMETER

TANK

VOLUME

MIN.

CONN.

SIZE HEIGHT

DIMENSIONS

SHIPPING

WEIGHT

6" 36" 81" 850

BUFFER TANK

2 @ 2 208-36.4

LOCATIONNUMBER

PUMP

PRESSURE

DISCHARGE

GALLONS

SIZE

RECEIVER

LB/HR

MOTOR

NOM. HP PHASE

REMARKS

408-CP1 1600 3500 RPM MOTOR8BASEMENT

MECH. ROOM

DUPLEX

TYPE UNIT

VOLT

50 PSI

CAST IRON RECEIVER

GPM

STEAM CONDENSATE PUMP SCHEDULE

POWER CIRCUIT (MCA / MOCP)

VOLTAGE & PHASE

MOUNTING

NOMINAL TONS

VOLTAGE & PHASE

SENSIBLE CAP (NET MBH)

DB ENTERING AIR

WB ENTERING AIR

C O

O L

IN

G

DESCRIPTION

F A

N

TOTAL CAP (NET MBH)

MOTOR HP

CFM

UNIT NUMBER (INDOOR / OUTDOOR)

AREA SERVED

208 / 1

38 W

AC-1

GENERAL NOTES:

DESCRIPTION AIR COOLED HEAT PUMP

9.09

10.9

COMM 103B

CONFIGURATION WALL MOUNTED

CONDENSATE PUMP

YES

7.8 / 15

208 / 1

GRADE

CU-1 (NOTE 1)

AC-2

AIR COOLED HEAT PUMP

COMM 101B

WALL MOUNTED

208 / 1

GRADE

CU-2

AC-3

AIR COOLED HEAT PUMP

COMM 202H

WALL MOUNTED

208 / 1

GRADE

CU-3

ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - SINGLE

POWER SERVICE TO EACH UNIT. ADEQUACY OF LISTED CIRCUIT SIZES

MUST BE VERIFIED BY CONTRACTOR. COST FOR INCREASE OR CHANGE OF

ELECTRICAL SERVICE FOR EQUIPMENT SELECTED SHALL BE BORNE BY

CONTRACTOR.

CONDENSATE DRAIN PIPING FROM INDOOR UNITS SHALL BE 0.75" UNLESS

NOTED OTHERWISE.

0.75

7 / 15

0.75

7 / 15

208 / 1

38 W

8.04

8.9

YES

208 / 1

38 W

8.04

8.9

YES

COOLING ONLY SPLIT SYSTEMS

O U

T D

O O

R U

N

IT

IN

D

O O

R U

N

IT

NOTES:

1. UNIT SHALL BE ON EMERGENCY POWER

MOTOR HP 41 W 41 W 41 W

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/3

/2

:3

:1

P

M

M603

SCHEDULES CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

V-2

(APPLIES TO CONTROL PANEL

408-ERV*)

NEW DISTRIBUTED CONTROL PANEL 408-ERV* (DCP/DDC)

408-ERV* POINTS LIST

1 A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED

AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OF

EQUIPMENT AND SYSTEMS AS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A

DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC ACTUATION.

2 ELECTRICAL WORK INCLUDES A POWER SOURCE TO THE MOTOR STARTERS. ALL

HVAC POWER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES

EXPLICITLY SHOWN ON THE ELECTRICAL DRAWINGS, SHALL BE PROVIDED . THIS WORK

SHALL INCLUDE BUT NOT BE LIMITED TO WIRING, CONDUIT, TRANSFORMERS, RELAYS

AND FUSES.

3 BULB WELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE FURNISHED AND

INSTALLED. PIPING WORK SHALL INCLUDE PROPERLY SIZED WELDOLET OR

THREADOLET FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.

4 POINTS LIST IS SHOWN AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM

POINTS REQUIRED FOR CONTROL AND MONITORING. ALL INPUT AND OUTPUT POINTS,

AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDWARE, SHALL BE PROVIDED

FOR A COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF OR WHEN ADDITIONAL

POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED,

THESE POINTS, ALONG WITH ADDITIONAL DIRECT DIGITAL CONTROL PANEL(S) (IF

REQUIRED), SHALL ALSO BE PROVIDED.

5 ALL DDC WIRING SHALL BE GREEN.

APPLIES TO ALL CONTROLS SHEETS

DDC CONTROLLER

HEATING COIL

FAN-COIL UNIT

SUPPLY AIR

1.1 SUPPLY AIR TEMPERATURE, SENSED BY T-2, SHALL BE MAINTAINED AT SETPOINT

OF 70 DEG. F. VIA DCP BY MODULATING COOLING COIL VALVE V-2 OR REHEAT COIL

VALVE V-3, IN SEQUENCE. SEPARATE CONTROL LOOPS SHALL BE UTILIZED FOR

COOLING AND HEATING FUNCTIONS. COOLING COIL VALVE V-2 SHALL BE FULLY

CLOSED BEFORE REHEAT COIL VALVE V-3 OPENS, AND VICE VERSA.

1.2 WHEN ROOM TEMPERATURE AT T1 IS ABOVE SETPOINT, HOT WATER VALVES V1 &

V3 SHALL BE CLOSED AND CHILLED WATER VALVE V2 SHALL MODULATE OPEN TO THE

COIL TO MAINTAIN TEMPERATURE SETPOINT.

1.3 THE ELECTRONICALLY COMMUTATED MOTOR ON THE SUPPLY FAN SHALL BE

MODULATED. WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 60 DEGREES F., THE

FAN SHALL REMAIN AT 40 PERCENT AIR FLOW AND THE HYDRONIC VALVES SHALL

MODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT. IF THE SPACE FALLS OR

RISES MORE THAN 2 DEGREES F. FROM THE SETPOINT, THE FAN SPEED SHALL BE

INCREASED SLOWLY UNTIL THE SPACE IS WITHIN 1.5 DEGREES F. OF SETPOINT.

ABOVE 60 DEGREES F. OUTSIDE AIR TEMPERATURE THE FAN SHALL HAVE A 10

PERCENT AIR FLOW MINIMUM. VALVE V1 SHALL MODULATE TO MAINTAIN SPACE

TEMPERATURE SETPOINT. IF THE ROOM IS MORE THAN 2 DEGREES F. ABOVE

SETPOINT THE FAN SPEED SHALL BE INCREASED UNTIL SPACE IS WITHIN 1.5 DEGREES

F. OF SETPOINT.

1.4 EACH UNIT SHALL INCLUDE A DISCHARGE AIR TEMPERATURE SENSOR.

1.5 EXTEND 24 VOLT POWER TO THE FAN COIL UNIT CONTROLLER FROM THE NEAREST

DDC CONTROL PANEL.

1.6 REFER TO HVAC DESIGN DATA SCHEDULE FOR SPACE TEMPERATURE SETPOINTS

IN BOTH OCCUPIED AND UNOCCUPIED MODES. ROOM SPACE TEMPERATURE SET

POINT SHALL BE ADJUSTABLE FROM THE FRONT END COMPUTER INTERFACE.

1.7 PROVIDE SCHEDULED NIGHT SET-BACK CONTROL FOR CONTINUOUS FAN

OPERATION DURING THE OCCUPIED PERIOD (24 HOURS A DAY, 7 DAYS A WEEK, ADJ.)

AND CYCLED FAN OPERATION TO MAINTAIN REDUCED TEMPERATURE IN THE

UNOCCUPIED PERIOD.

COOLING…