36C25622R0030 133419 Pre-Engineered Metal Bldg Systems.doc

DOC document 45 KB Posted

Attached to
Z2FB--Biloxi MATOC-Seed Project Project #520-22-122 FCA Corrections BLDG 17 - 36C25622R0030
Solicitation number
520-22-122
Issued by

About this file

This document provides specifications for a pre-engineered metal building system for a federal construction project. The specifications call for galvanized or aluminum wall and roof panels with thermal insulation and factory finishing. Steel framing members must be designed to withstand wind loads of 135 mph and seismic requirements. Submittals must include shop drawings, product data, samples, and calculations stamped by a professional engineer demonstrating compliance with design criteria. The contractor must have experience installing similar pre-engineered metal buildings and provide a two-year warranty on materials and workmanship.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 for a pre-engineered metal building system at the FCA Corrections Building 17 in Biloxi, Mississippi under the MATOC-Seed Project number 520-22-122. Interested contractors should review the attached RFP for response and award dates as well as any set-aside provisions, pricing requirements, or incumbent information.

View the file

Other files

File Type Posted
36C25622R0030 055000 Metal Fabrication.docx DOCX document
36C25622R0030 0006.docx DOCX document
36C25622R0030 262921 Enclosed Switches and Circuit Breakers.docx DOCX document
36C25622R0030 0005.docx DOCX document
36C25622R0030 Spec 013323 v2.doc DOC document
36C25622R0030 099100 PAINTING.doc DOC document
36C25622R0030 262416 Electrical Panelboards.docx DOCX document
36C25622R0030 Main Elec Panel Schedule.pdf PDF
36C25622R0030 RFI Register 10182022.docx DOCX document
36C25622R0030 263213 Engine Generators v2.docx DOCX document
36C25622R0030 Site Utility Map.pdf PDF
36C25622R0030 211313 Wet Pipe Sprinkler System.docx DOCX document
36C25622R0030 0004.docx DOCX document
36C25622R0030 081113 Hollow Metal Doors and Frames.doc DOC document
36C25622R0030 087100 DOOR HARDWARE.doc DOC document
36C25622R0030 SD320523 04 Concrete Post Bollards.pdf PDF
36C25622R0030 34751313 Vehicle Barrier.docx DOCX document
36C25622R0030 SD320523 05 Removable Bollard 1 (Alternate Option for Generator).pdf PDF
36C25622R0030 Bldg 17 Details Section.pdf PDF
36C25622R0030 B17 Floor Plan.pdf PDF
36C25622R0030 SD320523 06 Removable Bollard 2 (Strap Detail).pdf PDF
36C25622R0030 0003.docx DOCX document
36C25622R0030 0002.docx DOCX document
36C25622R0030 FCA Corrections Bldg 17 - Full Set v2.pdf PDF
S04 Site Visit Attendance Sheet (08.30.2022).pdf PDF
36C25622R0030 0001.docx DOCX document
36C25622R0030 EXHIBIT I-Financial Disclosure.docx DOCX document
36C25622R0030 SOW FCA Corrections Bldg 17 (Revised v2).pdf PDF
36C25622R0030 Spec 013323.doc DOC document
36C25622R0030 Drawings-FCA Corrections BLDG 17 .pdf PDF
36C25622R0030 Spec 220511 .doc DOC document
36C25622R0030 EXHIBIT F-RFI Form .docx DOCX document
36C25622R0030 Spec 260511 .doc DOC document
36C25622R0030 EXHIBIT H-Contractor Information.docx DOCX document
36C25622R0030 Spec 062000 .doc DOC document
36C25622R0030 WD MS20220060 Mod 1 02252022 (Harrision Heavy) .docx DOCX document
36C25622R0030 Spec 024100 .doc DOC document
36C25622R0030 Spec 017419 .doc DOC document
36C25622R0030 EXHIBIT E-Surety Form .docx DOCX document
36C25622R0030 EXHIBIT A-Performance Relevancy Survey .docx DOCX document
36C25622R0030 EXHIBIT D-Contractor Evaluation Form Construction Safety .docx DOCX document
36C25622R0030 VHA Supplemental Contract Requirements for Combatting COVID-19.docx DOCX document
36C25622R0030 WD MS20220050 Mod 2 02252022 (Harrision Building) .docx DOCX document
36C25622R0030 EXHIBIT C-Subcontractor Information and Consent Form .docx DOCX document
36C25622R0030 Spec 078400 .doc DOC document
36C25622R0030 EXHIBIT B-Past and Present Performance Questionnaire.docx DOCX document
36C25622R0030 WD MS20220133 Mod 1 02252022 (Harrision Highway) .docx DOCX document
36C25622R0030 Spec 013526 v2 (updated 071322).docx DOCX document
36C25622R0030 Spec 262726 v2 (updated (071322).doc DOC document
36C25622R0030 Seed ICRA .pdf PDF
Show 40 more

Latest 50 of 54 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 13 34 19

PRE-ENGINEERED METAL BUILDING SYSTEMS

PART 1 ‑ GENERAL

1.1 DESCRIPTION

A.

This section covers materials, labor and equipment required to complete the pre‑engineered metal canopy shown and specified. Contractor to provide engineered stamped shop drawings of proposed aluminum canopy system to COR for review/approval.

1.2 RELATED WORK

A. N/A

1.3 MANUFACTURERS QUALIFICATIONS

A.

Approval by Contracting Officer is required of products or service of proposed manufacturer, suppliers and installers, and will be based upon submission by Contractor of certification that:

B.

Manufacturer regularly and presently manufactures pre‑engineered metal buildings as specified as one of its principal products.

C.

Installer has technical qualifications, experience, trained personnel and facilities to install specified items. Approval will not be given, however, where experience record is one of unsatisfactory performance.

D.

Manufacturer's product submitted has been in satisfactory and efficient operation on three installations similar and equivalent to this project for three years. Submit list of installations.

1.4 DESIGN CRITERIA

A.

Design metal buildings to resist the dead load, the live load, and the combination of these loads as set forth in Metal Building Manufacturers Association (MBMA) "Recommended Design Practices Manual":

1.

Roof Live Load: 30 pounds per square foot applied on horizontal projection of roof structure.

2.

Wind Load: 135 MPH pressure. Meeting Miami Dade hurricane wind criteria.

3.

Seismic loading as required by International Building Code, 2022 edition.

B.

Deflection Limits (Live and Wind Loads Only):

1.

Roof Framing: L/270.

2.

Roof Panels: L/180.

3.

Walls Panels: L/180., where L = Span length.

C.

Metal Building components shall be capable of supporting design loads without permanent deformation, loss of watertightness, or disengagement of any part of installation.

D.

Structural steel sections shall be designed in accordance with AISC, "Specification for Structural Steel Buildings". Light gage cold formed structural members shall be designed in accordance with latest edition of AISI, "Specifications for the Design of Light Gage Cold Formed Steel Structural Members". Welding shall comply with AWS Standard No. D1.1.

1.5 SUBMITTALS

A.

Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES, furnish the following:

B.

Samples: Wall and roof panels, 600 mm (24‑inch) wide by 300 mm (12 inch) high sections, with factory finish in specified colors. Fasteners for panels

C.

Certificates:

1.

Stating that the zinc coating on steel panels is the specified thickness.

2.

Stating that the thermal values of the roof and wall panels with insulation meet the specified requirements.

3.

Indicating manufacturers and installers meet qualifications specified.

D.

Manufacturer's Literature and Data:

Metal Panels

Insulation

Sealing materials

Steel doors, door frames and hardware interlocking thresholds

Windows

E.

Shop Drawings: Shop drawings, erection drawings and erection manuals showing complete erection layouts, installation instructions, and details of connections. Details and layouts shall show the steel framing location, lengths, and markings of panels and other component parts to correspond with sequence and procedure for erection. Shop drawings shall show connections with adjoining work.

F.

Structural Design Analysis:

1.

Furnish complete structural design analysis for all structural components of the prefabricated metal buildings. Submit complete calculations prepared and stamped by a Mississippi Professional Engineer.

2.

Provide manufacturer load tables indicating the selected panel material, configuration and thickness meets the design requirements for the spans shown.

1.6 STORAGE AND PROTECTION

Materials stored on site before erection shall be stacked and covered with suitable weather tight covering. Store metal panels so that any accumulated water will drain off. Panels shall not be stored in contact with materials that cause staining. Materials having defects or damages that effect appearance, serviceability or use will be rejected.

1.7 warranty

Prefabricated metal building shall be warranty against defects in materials and workmanship, and that after erection completed work shall be weather tight and shall be subject to the terms of the “Warranty of Construction” Article in Section 00 72 00, GENERAL CONDITIONS, except that the warranty period shall be two years.

1.8 APPLICABLE PUBLICATIONS

A.

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B.

American Society for Testing and Materials (ASTM):

A36/A36M-05 Carbon Structural Steel.

A242/A242M-04(E2005) High‑Strength Low‑Alloy Structural Steel.

A653/A653M-07 Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron-alloy-Coated (Galvannealed) by the Hot-Dip Process

A1008/A1008M(REV A-07)

Steel, Sheet, Cold Rolled, Carbon, Structural, High-Strength Low-Alloy

A1011/A1011M-07 Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy

B117-07 Standard Practice for Operating Salt Spray (Fog)

B209/209M-07 Aluminum and Aluminum-Alloy Sheet and Plate

C553-02 Specifications for Mineral Fiber Blanket Thermal Insulation for Commercial and Insulation for Commercial and Industrial Applications

C1036-06 Flat glass

D522 REV A-93(R2001)

Standard Test Methods for Mandrel Bend Test of Attached Organic Coatings

D2244-07 Standard Practice for Calculation of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates

D2794-93(R2004) Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation

D3359-02 Standard Test Methods for Measuring Adhesion by Tape Test

D4214-07 Standard Test Methods for Evaluating the Degree of Chalking of Exterior Paint Films

G153-04 Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials

C.

Metal Building Manufacturers Association (MBMA):

1.

Recommended Guide Specifications for Pre‑Engineered Metal Buildings.

2.

Recommended Design Practices Manual.

D.

American Institute of Steel Construction (AISC): Document No. 360-05.

Specifications for Structural Steel Buildings; Allowable Stress Design and Plastic Design (1989).

E.

National Fire Protection Association (NFPA), No. 220: Standard Types of Building Construction (2006)

F.

American Welding Society (AWS):

D1.1/D1.1M‑06 Structural Welding Code.

G.

American Iron and Steel Institute (AISI):

Light Gage Cold Formed Design Manual.

H. Uniform Building Code, Latest Edition.

I.

Miami-Dade Hurricane Requirements.

PART 2 ‑ PRODUCTS

2.1 MATERIALS

A.

Glass: ASTM C1036.

B.

Steel Framing and Structural Steel Members: ASTM A36 or A242, except uncoated steel for light gage members shall conform to ASTM A1008 or A1011.

C.

Panels:

1.

Sheet Steel, galvanized light gage steel of specified thickness shall conform to ASTM A653/A653M with G40 zinc coating each face.

2.

Aluminum: Sheet aluminum shall conform to ASTM B209, alloy 3004.

D.

Joint Sealant: Sealant shall be heat‑resisting compound having low shrinkage factor; unaffected by water; with flash‑point in excess of 400°C (750 degrees F). Sealant shall not migrate oil up to 120° (250 degrees F) nor exude oil under pressure. It shall not skin, sag, nor weep in panel joints under vibration up to temperature of 65°C (150 degrees F), nor become brittle at temperature down to -1°C (30 degree F).

E.

Sealing Tape: Manufacturer's standard in color to match metal building panels.

2.2 FABRICATION

A.

General: Coordinate fabrication and erection of work with related work of other trades. Provide cutouts and supplemental reinforcement as required to accommodate materials and work specified in other sections of the specifications.

B.

Protection of Dissimilar Metals: Dissimilar materials which are not compatible with adjoining materials when exposed to moisture shall be separated by means of coatings, gaskets, or other effective means.

C.

Steel Framework Fabrication:

1.

Steel framing required for pre‑engineered metal building shall be coordinated with adjacent structural steel. Columns and related components shall be shop fabricated complete, with connection holes for attachment of primary and secondary framing members and bracing.

2.

Framing, purlins, girts, struts and miscellaneous steel members required for attachment of pre‑engineered metal building panels to building structure shall be roll formed members complying with either ASTM A1008/A1008M. Design, size, space and install members to meet job and loading conditions. Members shall have factory‑punched holes and shall be furnished complete with angle clips and fastenings required for attaching to structure.

3.

Bolted connections shall use either ribbed or high‑tensile steel bolts as appropriate for each connection.

4. Welding shall be in accordance with AWS Standard. Operators shall be qualified as prescribed by American Welding Society. Certification shall be furnished upon request of C.O.T.R.

D.

Wall Panels: Wall panels shall consist of an insulating core enclosed between two metal face sheets. Steel face sheets shall be 26 gauge thick. Design exterior face sheets of panels with grade of steel and configuration of cross section capable of withstanding specified design load conditions without exceeding specified stress and deflection limitations, with same support configuration as that in proposed building. Seal joints between panels with joint sealant as specified. Insulation for panels cores shall be mineral insulation of a type standard with panel manufacturer and shall be noncombustible as defined by NFPA No. 220. Fasten panels to adjoining panels and to steel framework by method recommended by panel manufacturer and approved before work is started.

E.

Roof Panels: Roofing panels shall be 24gauge thick. Design roof panels with grade of steel and configuration of cross section capable of withstanding design load conditions without exceeding specified stress and deflection limitations, with same support configuration as that in proposed building. Sheets shall be applied with a minimum sidelap of not less than one full configuration. Exposed insulation for installation on inside face of roof panels shall be semirigid insulation.

F.

Flashing, Trim And Closures: Same material, gage and finish as adjacent wall and roof panels. Fastenings shall be as specified for wall and roof panels. Form or mold closure strips to match configuration of the roofing or siding. Install closures wherever necessary to insure weather tight construction.

2.3 FACTORY FINISH AND PAINTING

A.

Wall and roof panels, including related components, accessories and fastenings, shall have approved factory finish as follows:

1.

Finish on the weather face of wall and roof panels, and related components shall be a prime coat of epoxy primer with a finish coat of Polyvinylidene Fluoride baked on coating thickness of (0.8‑1.3 mils) with the following performance characteristics.

a.

Salt Spray Test: ASTM B 117, minimum (500) hours. Undercutting of the paint film from the score line shall not exceed 2 mm (1/16 inch).

b.

Accelerated Weathering Test: ASTM G 153, Method 2, Type D apparatus minimum 2000 hours or Type EH apparatus minimum 500 hours, no checking, blistering or loss of adhesion; color change less than 5 NBS units by ASTM D 2244 and chalking less than No. 8 rating by ASTM D 4214.

c.

Flexibility: ASTM D 522, Method A, 3 mm 1/8 inch diameter, 180 degree bend, no evidence of fracturing to the naked eye.

d.

Adhesion: ASTM D 3359, Method B, for laboratory test and film thickness less than 0.01 mm 5 mil and Method A for site tests. There shall be no film removed by tape applied to 11 parallel cuts spaced 3 mm 1/8 inch apart plus 11 similar cuts at right angles.

e.

Impact: ASTM D 2794, no loss of adhesion after direct and reverse impact equal to 1.5 times metal thickness in mm mils, expressed in m-kg inch-pounds.

2.

Finish on exposed face of liner panel shall be off white baked enamel suitable as a finished surface or as a base for field painting.

B.

Steel framing members shall be given one additional coat of shop paint after delivery, and 2 coats of finish paint after installation.

C.

Field paint all exterior exposed fastenings to match adjacent panels.

D.

Abraded surfaces shall be wire-brushed and touched up with the same materials as the shop prime or finish coat of paint.

PART 3 - EXECUTION

3.1 ERECTION

A.

Bolt settings and other dimensions shall be held to a tolerance of plus or minus 3 mm (1/8-inch). Use templates or other gaging devices to assure accurate spacing of anchor bolts. Bolt field connections unless otherwise shown or specified.

1.

Set accurately bases or sill members to obtain uniform bearing and maintain established floor line elevation. Anchors and anchor bolts for securing members to concrete curb or structural steel sub-frame shall be of black steel, set accurately to templates and of proper size to adequately resist applicable design loads at the base.

B.

Wall Panels: Panels shall be applied with configurations running in a vertical position. Supply panels in single lengths from base to eave with no horizontal joints, except at the junction of door units, louver panels, and similar openings. End laps for panels shall be not less than 100 mm (four inches). Walls shall be closed at base and eave, and around doors, frames, louvers, and other similar openings by flashings and/or formed closures to assure adequate weathertightness. Flashing or stops will not be required where weather-closed or approved self-flashing panels are used.

C.

Roof Panels: Roof panels shall be applied with configurations running in direction of roof slope. Supply panels with no transverse joints except at junctions for roof openings and at roof ridge. Lay side laps away from prevailing winds, and seal side laps and end-laps of roof with roof joint sealant. Roof shall be flashed and/or sealed at ridge at eaves and rakes at projections through roof, and elsewhere as necessary to make roof weather tight. Flashing and/or caulking shall be accomplished in a manner that will assure complete weather-tightness and method to be used shall be subject to approval by C.O.T.R. Minimum end-laps for roofing and ridge caps for pre-engineered and factory-punched laps shall be 150 mm (six inches); other minimum end-laps shall be not less than 300 mm (12 inches).

D.

Fasteners for Securing Roof and Wall Panels: Fastening method, size and spacing shall be as recommended by metal building manufacturer and as approved by C.O.T.R. Fasteners shall be non-corrosive and of design that will produce a weathertight connection. Clearly show fasteners and fastening method on shop and erection drawings. Field paint exterior exposed fastenings to match adjacent panels.

E.

Weatherproofing: Joints between exterior pre-engineered metal building components and other adjacent components and materials, except flashing of metal wall panels shall be designed for and shall receive sealing tapes, gaskets, sealant materials, metal flashing and other methods of sealing as required to provide weathertight joints. Joint sealing shall be installed under this section and shall be guaranteed as specified. Color of sealing materials shall match adjacent metal building components.

- - - E N D - - -

13 34 19-8