511_17092.JBB_GladstoneArmoryPhase4_Addendum 2_Issued_12_21_2022.pdf

PDF 3 MB Posted

Attached to
511/17092. JBB; Gladstone Armory - Renovate Armory Phase IV
Solicitation number
RFQ 171 230000000067 4
Issued by
Clinton County, Galien Village, Michigan

About this file

This Addendum 2, issued December 21, 2022, modifies the contract documents for the Gladstone Armory Renovate Armory Phase IV project under the Michigan Department of Technology, Management and Budget (DTMB) File No. 511/17092.JBB and DMVA Project No. 26A9520005. The addendum incorporates specification additions and drawing revisions for mechanical, electrical, and fire alarm systems. Key additions include HVAC Power Ventilators (Section 23 34 23), Manual and Magnetic Motor Controllers (Section 26 29 13.03), and Addressable Fire-Alarm Systems (Section 28 46 21.11). The mechanical revisions modify the Hydronic Air Coils specification to remove language regarding removable coil inspection, update hot water coil schedules from 2 rows to 4 rows for units HC-4 and HC-5, and add exhaust fan and louver schedules. Electrical drawings M-101, E-101, E-103, E-502, and E-602 were updated to reflect power and low-voltage connections for newly added equipment EF-1 and L-1 in Room 202 (Open Storage), including a Fire Alarm Riser diagram and control details. The bid date remains Wednesday, January 11, 2023, and the addendum clarifies that there are no minority subcontractor or supplier requirements stated in the Federal Provisions.

The fire alarm system specifications require an addressable, noncoded, UL-certified system with multiplexed signal transmission, horn-and-strobe notification, smoke detectors with automatic sensitivity control, duct smoke detectors with programmable relay for fan shutdown, heat detectors, manual pull stations, and notification appliances. The system must transmit alarm, supervisory, and trouble signals to a remote alarm receiving station via digital alarm communicator transmitter (DACT) using both VOIP/IT network and cellular phone system backup, with cellular subscription service included for the duration of the system warranty period. Installation must be performed by NICET-certified technicians and comply with NFPA 72, NFPA 90A, and NFPA 70. The contractor must provide comprehensive shop drawings, testing documentation, operation and maintenance manuals, training for owner personnel, and a five-year special warranty from the manufacturer covering defects in materials and workmanship.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum 2

ADDENDUM NO. 2

DATE: December 21, 2022

PROJECT: Gladstone Armory Renovate Armory (Phase IV)

DTMB FILE NO.: 511/17092.JBB

OWNER: MI DTMB

BID DATE: Wednesday, January 11, 2023 ** THIS ADDENDUM DOES NOT CHANGE

THE BID DATE**

The following shall be incorporated into the Contract Documents dated 18 NOV 2022.

GENERAL

There are no minority subcontractor/supplier requirements stated in the Federal Provisions Addendum.

PROJECT MANUAL

238216.11 HYDRONIC AIR COILS

2.2.D.1 Remove “removable for cleaning and inspection of tubes.” from specification.

233423 HVAC POWER VENTILATORS

Specification added.

262913.03 MANUAL AND MAGNETIC MOTOR CONTROLLERS

Specification added.

284621.11 ADDRESSABLE FIRE ALARM SYSTEMS

Specification added.

DRAWINGS

M-101 MECHANICAL MAIN FLOOR PLAN

Added EF-1 and L-1 to 202 Open Storage.

M-601 MECHANICAL SCHEDULES

Added exhaust fan and louver schedule. For hot water coil schedule change the ROWS column from “2” to “4” for HC-4 and HC-5.

E-101 MAIN FLOOR POWER PLAN

Added power to EF-1 and L-1 in 202 Open Storage.

E-103 MAIN FLOOR LOW VOLTAGE PLAN

Added Fire Alarm devices throughout the building.

E-502 ELECTRICAL DETAILS

Added Fire Alarm Riser diagram and EF-1/L-1 Detail.

E-602 ELECTRICAL SCHEDULES

Provided circuits for EF-1, L-1 and FACP. Added two spare 20A breakers.

End of Addendum No. 2

DTMB/DMVA

Gladstone Armory Renovate Armory Phase IV DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

HVAC POWER VENTILATORS

23 34 23 - Page 1 of 3

Addendum 2: 12/21/2022

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

SECTION 23 34 23 - HVAC POWER VENTILATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Sidewall propeller fans.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Construction details, material descriptions, dimensions of individual components and profiles, and finishes for fans.

2. Rated capacities, operating characteristics, and furnished specialties and accessories.

3. Certified fan performance curves with system operating conditions indicated.

4. Certified fan sound-power ratings.

5. Motor ratings and electrical characteristics, plus motor and electrical accessories.

6. Material thickness and finishes, including color charts.

7. Dampers, including housings, linkages, and operators.

8. Fan speed controllers.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by an NRTL, and marked for intended location and application.

B. NFPA Compliance: Comply with NFPA 90A for design, fabrication, and installation of unit components.

C. ASHRAE 62.1 Compliance: Applicable requirements in ASHRAE 62.1, Section 5 - "Systems and Equipment" and Section 7 - "Construction and Startup."

D. ASHRAE/IES 90.1 Compliance: Applicable requirements in ASHRAE/IES 90.1, Section 6 - "Heating, Ventilating, and Air-Conditioning."

2.2 SIDEWALL PROPELLER FANS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Acme Engineering & Manufacturing Corp.

2. Greenheck.

3. Loren Cook Company.

B. Housing: Galvanized-steel sheet with flanged edges and integral orifice ring, with baked-enamel finish coat applied after assembly.

http://www.specagent.com/LookUp/?ulid=3478&mf=04&src=wd

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

HVAC POWER VENTILATORS

23 34 23 - Page 2 of 3

Addendum 2: 12/21/2022

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

C. Fan Wheel: Replaceable, cast -aluminum, airfoil blades fastened to cast-aluminum hub; factory set pitch angle of blades.

D. Fan Drive, Direct: Direct-drive motor mounted in airstream, factory wired to disconnect switch located on outside of fan housing.

E. Accessories:

1. Disconnect Switch: Nonfusible type, with thermal-overload protection mounted inside fan housing, factory wired through an internal aluminum conduit.

2. Dampers: Counterbalanced, parallel-blade, backdraft dampers factory set to close when fan stops.

3. Motor-Side Back Guard: Galvanized steel, complying with OSHA specifications, removable for maintenance.

4. Wall Sleeve: Galvanized steel to match fan and accessory size.

5. Weathershield Hood: Galvanized steel to match fan and accessory size.

6. Weathershield Front Guard: Galvanized steel with expanded metal screen.

2.3 MOTORS

A. Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors.

1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Install power ventilators level and plumb.

B. Install units with clearances for service and maintenance.

C. Label units according to requirements specified in Section 23 05 53 "Identification for HVAC Piping and Equipment."

3.2 ELECTRICAL CONNECTIONS

A. Connect wiring according to Section 26 05 19 "Low-Voltage Electrical Power Conductors and Cables."

B. Ground equipment according to Section 26 05 26 "Grounding and Bonding for Electrical Systems."

C. Install electrical devices furnished by manufacturer, but not factory mounted, according to NFPA 70 and NECA 1.

1. Nameplate shall be laminated acrylic or melamine plastic signs, as specified in Section 26

05 53 "Identification for Electrical Systems."

2. Nameplate shall be laminated acrylic or melamine plastic signs with a black background and engraved white letters at least 1/2 inch high.

3.3 CONTROL CONNECTIONS

A. Install control and electrical power wiring to field-mounted control devices.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

HVAC POWER VENTILATORS

23 34 23 - Page 3 of 3

Addendum 2: 12/21/2022

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

B. Connect control wiring according to Section 26 05 23 "Control-Voltage Electrical Power Cables."

3.4 STARTUP SERVICE:

A. Engage a factory-authorized service representative to perform startup service.

1. Complete installation and startup checks in accordance with manufacturer's written instructions.

2. Verify that shipping, blocking, and bracing are removed.

3. Verify that unit is secure on mountings and supporting devices and that connections to ducts and electrical components are complete. Verify that proper thermal-overload protection is installed in motors, starters, and disconnect switches.

4. Verify that cleaning and adjusting are complete.

5. For direct-drive fans, verify proper motor rotation direction and verify fan wheel free rotation and smooth bearing operation.

6. For belt-drive fans, disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guards.

7. Adjust damper linkages for proper damper operation.

8. Verify lubrication for bearings and other moving parts.

9. Verify that manual and automatic volume control and fire and smoke dampers in connected ductwork systems are in fully open position.

10. Disable automatic temperature-control operators, energize motor and confirm proper motor rotation and unit operation, adjust fan to indicated rpm, and measure and record motor voltage and amperage.

11. Shut unit down and reconnect automatic temperature-control operators.

12. Remove and replace malfunctioning units and retest as specified above.

3.5 ADJUSTING

A. Adjust damper linkages for proper damper operation.

B. Lubricate bearings.

C. Comply with requirements in Section 23 05 93 "Testing, Adjusting, and Balancing for HVAC."

3.6 CLEANING

A. After completing system installation and testing, adjusting, and balancing and after completing startup service, clean fans internally to remove foreign material and construction dirt and dust.

3.7 FIELD QUALITY CONTROL

A. Testing Agency: Contractor will engage a qualified testing agency to perform tests and inspections.

END OF SECTION 23 34 23

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 1 of 6 Addendum 2: 12/21/2022

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

SECTION 26 29 13.03 - MANUAL AND MAGNETIC MOTOR CONTROLLERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Enclosed full-voltage magnetic motor controllers.

2. Combination full-voltage magnetic motor controllers.

3. Enclosures.

4. Accessories.

5. Identification.

1.3 DEFINITIONS

A. CPT: Control power transformer.

B. MCCB: Molded-case circuit breaker.

C. MCP: Motor circuit protector.

D. NC: Normally closed.

E. OCPD: Overcurrent protective device.

F. SCCR: Short-circuit current rating.

G. SCPD: Short-circuit protective device.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings: For each type of magnetic controller.

1. Include plans, elevations, sections, and mounting details.

2. Indicate dimensions, weights, required clearances, and location and size of each field connection.

3. Wire Termination Diagrams and Schedules: Include diagrams for signal, and control wiring.

Identify terminals and wiring designations and color-codes to facilitate installation, operation, and maintenance. Indicate recommended types, wire sizes, and circuiting arrangements for field-installed wiring, and show circuit protection features. Differentiate between manufacturer-installed and field-installed wiring.

4. Include features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 2 of 6

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For magnetic controllers to include in operation and maintenance manuals.

1. In addition to items specified in Section 01 78 23 "Operation and Maintenance Data," include the following:

a. Routine maintenance requirements for magnetic controllers and installed components.

b. Manufacturer's written instructions for testing and adjusting circuit breaker and MCP trip settings.

c. Manufacturer's written instructions for setting field-adjustable overload relays.

d. Load-Current and Overload-Relay Heater List: Compile after motors have been installed, and arrange to demonstrate that selection of heaters suits actual motor nameplate full-load currents.

e. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors have been installed, and arrange to demonstrate that switch settings for motor-running overload protection suit actual motors to be protected.

1.6 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Fuses for Fused Switches: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type.

2. Control Power Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than two of each size and type.

3. Indicating Lights: Two of each type and color installed.

4. Auxiliary Contacts: Furnish one spare(s) for each size and type of magnetic controller installed.

5. Power Contacts: Furnish three spares for each size and type of magnetic contactor installed.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store controllers indoors in clean, dry space with uniform temperature to prevent condensation.

Protect controllers from exposure to dirt, fumes, water, corrosive substances, and physical damage.

B. If stored in areas subject to weather, cover controllers to protect them from weather, dirt, dust, corrosive substances, and physical damage. Remove loose packing and flammable materials from inside controllers; .

1.8 FIELD CONDITIONS

A. Ambient Environment Ratings: Rate equipment for continuous operation under the following conditions unless otherwise indicated:

1. Ambient Temperature: Not less than23 deg F and not exceeding 104 deg F.

2. Altitude: Not exceeding 6600 feet for electromagnetic and manual devices.

3. The effect of solar radiation is not significant.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 3 of 6

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

B. UL Compliance: Fabricate and label magnetic motor controllers to comply with UL 508 and

UL 60947-4-1.

C. NEMA Compliance: Fabricate motor controllers to comply with ICS 2.

2.2 COMBINATION FULL-VOLTAGE MAGNETIC MOTOR CONTROLLER

A. Description: Factory-assembled, combination full-voltage magnetic motor controller consisting of the controller described in this article, indicated disconnecting means, SCPD and OCPD, in a single enclosure.

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Eaton.

2. Siemens Industry, Inc., Energy Management Division.

3. Square D; Schneider Electric USA.

C. Standard: Comply with NEMA ICS 2, general purpose, Class A.

D. Configuration: Nonreversing .

E. Contactor Coils: Pressure-encapsulated type with coil transient suppressors when indicated.

1. Operating Voltage: Manufacturer's standard, unless indicated.

F. Control Power:

1. For on-board control power, obtain from line circuit or from integral CPT. The CPT shall have capacity to operate integral devices and remotely located pilot, indicating, and control devices.

a. Spare CPT Capacity as Indicated on Drawings: 100 VA.

G. Overload Relays:

1. Thermal Overload Relays:

a. Inverse-time-current characteristic.

b. Class 10 tripping characteristic.

c. Heaters in each phase shall be matched to nameplate full-load current of actual protected motor and with appropriate adjustment for duty cycle.

d. Ambient compensated.

e. Automatic resetting.

H. Fusible Disconnecting Means:

1. NEMA KS 1, heavy-duty, horsepower-rated, fusible switch with clips or bolt pads to accommodate indicated fuses.

2. Lockable Handle: Accepts three padlocks and interlocks with cover in closed position.

I. Nonfusible Disconnecting Means:

1. NEMA KS 1, heavy-duty, horsepower-rated, nonfusible switch.

2. Lockable Handle: Accepts three padlocks and interlocks with cover in closed position.

http://www.specagent.com/LookUp/?ulid=12769&mf=04&src=wd

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 4 of 6

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

2.3 ENCLOSURES

A. Comply with NEMA 250, type designations as indicated on Drawings, complying with environmental conditions at installed location.

B. The construction of the enclosures shall comply with NEMA ICS 6.

C. Controllers in hazardous (classified) locations shall comply with UL 1203.

2.4 ACCESSORIES

A. General Requirements for Control Circuit and Pilot Devices: NEMA ICS 5; factory installed in controller enclosure cover unless otherwise indicated.

1. Push Buttons, Pilot Lights, and Selector Switches: Standard-duty, except as needed to match enclosure type. Heavy-duty or oil-tight where indicated in the controller schedule.

a. Push Buttons: As indicated on the drawings.

b. Pilot Lights: Provide red Pilot light to illuminate when motor is running.

2. Elapsed Time Meters: Heavy duty with digital readout in hours ; nonresettable .

3. Meters: Panel type, 2-1/2-inch minimum size with 90- or 120-degree scale and plus or minus two percent accuracy. Where indicated, provide selector switches with an off position.

B. Motor protection relays shall be with solid-state sensing circuit and isolated output contacts for hardwired connections.

1. Phase-failure.

2. Phase-reversal, with bicolor LED to indicate normal and fault conditions. Automatic reset when phase reversal is corrected.

3. Under/overvoltage, operate when the circuit voltage reaches a preset value, and drop out when the operating voltage drops to a level below the preset value. Include adjustable time-delay setting.

C. Space heaters, with NC auxiliary contacts, to mitigate condensation in Type 3R Type 4X enclosures installed outdoors or in unconditioned interior spaces subject to humidity and temperature swings.

D. Auxiliary contact kit: Two NO/NC (Form "C") auxiliary contacts. Contact rating - 120 Vac.

2.5 IDENTIFICATION

A. Controller Nameplates: Laminated acrylic or melamine plastic signs, as described in Section 26 05 53 "Identification for Electrical Systems," for each compartment, mounted with corrosion-resistant screws.

B. Arc-Flash Warning Labels:

1. Comply with requirements in Section 26 05 73.19 "Arc-Flash Hazard Analysis." Produce a

3.5-by-5-inch self-adhesive equipment label for each work location included in the analysis.

2. Comply with requirements in Section 26 05 53 "Identification for Electrical Systems."

Produce a 3.5-by-5-inch self-adhesive equipment label for each work location included in the analysis. Labels shall be machine printed, with no field-applied markings.

a. The label shall have an orange header with the wording, "WARNING, ARC-FLASH

HAZARD," and shall include the following information taken directly from the arc-flash hazard analysis:

1) Location designation.

2) Nominal voltage.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 5 of 6

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

3) Flash protection boundary.

4) Hazard risk category.

5) Incident energy.

6) Working distance.

7) Engineering report number, revision number, and issue date.

b. Labels shall be machine printed, with no field-applied markings.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and space conditions for compliance with requirements for motor controllers, their relationship with the motors, and other conditions affecting performance of the Work.

3.2 INSTALLATION

A. Comply with NECA 1.

B. Wall-Mounted Controllers: Install magnetic controllers on walls with tops at uniform height indicated, and by bolting units to wall or mounting on lightweight structural-steel channels bolted to wall. For controllers not at walls, provide freestanding racks complying with Section 26 05 29 "Hangers and Supports for Electrical Systems" unless otherwise indicated.

C. Maintain minimum clearances and workspace at equipment according to manufacturer's written instructions and NFPA 70.

D. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Install lacing bars and distribution spools.

E. Setting of Overload Relays: Select and set overloads on the basis of full-load current rating as shown on motor nameplate. Adjust setting value for special motors as required by NFPA 70 for motors that are high-torque, high-efficiency, and so on.

3.3 IDENTIFICATION

A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Section 26 05 53 "Identification for Electrical Systems."

3.4 SYSTEM FUNCTION TESTS

A. System function tests shall prove the correct interaction of sensing, processing, and action devices. Perform system function tests after field quality control tests have been completed and all components have passed specified tests.

1. Develop test parameters and perform tests for the purpose of evaluating performance of integral components and their functioning as a complete unit within design requirements and manufacturer's published data.

2. Verify the correct operation of interlock safety devices for fail-safe functions in addition to design function.

3. Verify the correct operation of sensing devices, alarms, and indicating devices.

B. Motor controller will be considered defective if it does not pass the system function tests and inspections.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

MANUAL AND MAGNETIC MOTOR CONTROLLERS

26 29 13.03 - Page 6 of 6

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

C. Prepare test and inspection reports.

3.5 DEMONSTRATION

A. Train Owner's maintenance personnel to adjust, operate, and maintain switchgear.

END OF SECTION 26 29 13.03

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 1 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

SECTION 28 46 21.11 - ADDRESSABLE FIRE-ALARM SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Addressable fire-alarm system.

2. Fire-alarm control unit (FACU).

3. Manual fire-alarm boxes.

4. System smoke detectors.

5. Duct smoke detectors.

6. Heat detectors.

7. Fire-alarm notification appliances.

8. Fire-alarm remote annunciators.

9. Fire-alarm addressable interface devices.

B. Related Requirements:

1. Section 08 71 00 "Door Hardware" for magnetic door holders that release in response to fire-alarm outputs.

2. Section 26 05 19 "Low-Voltage Electrical Power Conductors and Cables" or Section 26 05

23 "Control Voltage Electrical Power Cables" for cables and conductors for fire-alarm systems.

1.3 DEFINITIONS

A. DACT: Digital alarm communicator transmitter.

B. EMT: Electrical metallic tubing.

C. FACU: Fire-alarm control unit.

D. High-Performance Building: A building that integrates and optimizes on a life-cycle basis all major high-performance attributes, including energy conservation, environment, safety, security, durability, accessibility, cost-benefit, productivity, sustainability, functionality, and operational considerations.

E. Mode: The terms "Active Mode," "Off Mode," and "Standby Mode" are used as defined in the 2007 Energy Independence and Security Act (EISA).

F. NICET: National Institute for Certification in Engineering Technologies.

G. PC: Personal computer.

H. Voltage Class: For specified circuits and equipment, voltage classes are defined as follows:

1. Control Voltage: Listed and labeled for use in remote-control, signaling, and power-limited circuits supplied by a Class 2 or Class 3 power supply having rated output not greater than

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 2 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

150 V and 5 A, allowing use of alternate wiring methods complying with NFPA 70, Article 725.

2. Low Voltage: Listed and labeled for use in circuits supplied by a Class 1 or other power supply having rated output not greater than 1000 V, requiring use of wiring methods complying with NFPA 70, Article 300, Part I.

1.4 SEQUENCING AND SCHEDULING

A. Existing Fire-Alarm Equipment: Maintain existing equipment fully operational until new equipment has been tested and accepted. When new equipment is installed, label it "NOT IN SERVICE" until it is accepted. Remove labels from new equipment when put into service, and label existing fire-alarm equipment "NOT IN SERVICE" until removed from building.

B. Equipment Removal: After acceptance of new fire-alarm system, remove existing disconnected fire-alarm equipment and wiring.

1.5 ACTION SUBMITTALS

A. Approved Permit Submittal: Submittals must be approved by authorities having jurisdiction prior to submitting them to Architect.

B. Product Data: For each type of product, including furnished options and accessories.

1. Include construction details, material descriptions, dimensions, profiles, and finishes.

2. Include rated capacities, operating characteristics, and electrical characteristics.

C. Shop Drawings: For fire-alarm system.

1. Comply with recommendations and requirements in "Documentation" section of

"Fundamentals" chapter in NFPA 72.

2. Include plans, elevations, sections, and details, including details of attachments to other

Work.

3. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and locations. Indicate conductor sizes, indicate termination locations and requirements, and distinguish between factory and field wiring.

4. Annunciator panel details as required by authorities having jurisdiction.

5. Detail assembly and support requirements.

6. Include voltage drop calculations for notification-appliance circuits.

7. Include battery-size calculations.

8. Include input/output matrix.

9. Include written statement from manufacturer that equipment and components have been tested as a system and comply with requirements in this Section and in NFPA 72.

10. Include performance parameters and installation details for each detector.

11. Verify that each duct detector is listed for complete range of air velocity, temperature, and humidity possible when air-handling system is operating.

12. Provide program report showing that air-sampling detector pipe layout balances pneumatically within airflow range of air-sampling detector.

13. Provide control wiring diagrams for fire-alarm interface to HVAC; coordinate location of duct smoke detectors and access to them.

a. Show critical dimensions that relate to placement and support of sampling tubes, detector housing, and remote status and alarm indicators.

b. Show field wiring and equipment required for HVAC unit shutdown on alarm.

c. Locate detectors in accordance with manufacturer's written instructions.

d. Show air-sampling detector pipe routing.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 3 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

14. Include voice/alarm signaling-service equipment rack or console layout, grounding schematic, amplifier power calculation, and single-line connection diagram.

15. Include floor plans to indicate final outlet locations showing address of each addressable device. Show size and route of cable and conduits and point-to-point wiring diagrams.

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For fire-alarm systems and components to include in emergency, operation, and maintenance manuals.

1. In addition to items specified in Section 01 78 23 "Operation and Maintenance Data," include the following:

a. Comply with "Records" section of "Inspection, Testing and Maintenance" chapter in

NFPA 72.

b. Complete wiring diagrams showing connections between devices and equipment.

Each conductor must be numbered at every junction point with indication of origination and termination points.

c. Riser diagram.

d. Device addresses.

e. Air-sampling system sample port locations and modeling program report showing layout meets performance criteria.

f. Record copy of site-specific software.

g. Provide "Inspection and Testing Form" in accordance with "Inspection, Testing and

Maintenance" chapter in NFPA 72, and include the following:

1) Equipment tested.

2) Frequency of testing of installed components.

3) Frequency of inspection of installed components.

4) Requirements and recommendations related to results of maintenance.

5) Manufacturer's user training manuals.

h. Manufacturer's required maintenance related to system warranty requirements.

i. Abbreviated operating instructions for mounting at FACU and each annunciator unit.

1.7 QUALITY ASSURANCE

A. Installer Qualifications:

1. Personnel must be trained and certified by manufacturer for installation of units required for this Project.

2. Installation must be by personnel certified by NICET as fire-alarm Level II technician.

3. Obtain certification by NRTL in accordance with NFPA 72.

4. Licensed or certified by authorities having jurisdiction.

1.8 WARRANTY

A. Special Warranty: Manufacturer agrees to repair or replace fire-alarm system equipment and components that fail because of defects in materials or workmanship within specified warranty period.

1. Warranty Period: Five years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 ADDRESSABLE FIRE-ALARM SYSTEM

A. Description:

1. Noncoded, UL-certified addressable system, with multiplexed signal transmission and horn-and-strobe notification for evacuation.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 4 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

B. Performance Criteria:

1. Regulatory Requirements:

a. Fire-Alarm Components, Devices, and Accessories: Listed and labeled by a NRTL in accordance with NFPA 70 for use with selected fire-alarm system and marked for intended location and application.

2. General Characteristics:

a. Automatic sensitivity control of certain smoke detectors.

b. Fire-alarm signal initiation must be by one or more of the following devices:

1) Manual stations.

2) Heat detectors.

3) Smoke detectors.

4) Duct smoke detectors.

c. Fire-alarm signal must initiate the following actions:

1) Continuously operate alarm notification appliances.

2) Identify alarm and specific initiating device at FACU and remote annunciators.

3) Transmit alarm signal to remote alarm receiving station.

4) Release fire and smoke doors held open by fusible links.

5) Record events in system memory.

d. Supervisory signal initiation must be by one or more of the following devices and actions:

1) Zones or individual devices have been disabled.

2) FACU has lost communication with network.

e. System trouble signal initiation must be by one or more of the following devices and actions:

1) Open circuits, shorts, and grounds in designated circuits.

2) Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices.

3) Loss of communication with addressable sensor, input module, relay, control module, remote annunciator, printer interface, or Ethernet module.

4) Loss of primary power at FACU.

5) Ground or single break in internal circuits of FACU.

6) Abnormal ac voltage at FACU.

7) Break in standby battery circuitry.

8) Failure of battery charging.

9) Abnormal position of switch at FACU or annunciator.

f. System Supervisory Signal Actions:

1) Identify specific device initiating event at FACU and remote annunciators.

2) After time delay of 200 seconds , transmit trouble or supervisory signal to remote alarm receiving station.

2.2 FIRE-ALARM CONTROL UNIT (FACU)

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Edwards; Carrier Global Corporation.

2. Notifier; Honeywell International, Inc.

3. Potter Electric Signal Company, LLC.

4. Siemens Industry, Inc., Building Technologies Division.

5. Simplex; brand of Johnson Controls International plc, Building Solutions North America.

B. Description: Field-programmable, microprocessor-based, modular, power-limited design with electronic modules.

C. Performance Criteria:

http://www.specagent.com/LookUp/?ulid=13912&mf=04&src=wd

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 5 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

1. Regulatory Requirements: Comply with NFPA 72 and UL 864.

2. General Characteristics:

a. System software and programs must be held in nonvolatile flash, electrically erasable, programmable, read-only memory, retaining information through failure of primary and secondary power supplies.

b. Include real-time clock for time annotation of events on event recorder and printer.

c. Provide communication between FACU and remote circuit interface panels, annunciators, and displays.

d. FACU must be listed for connection to central-station signaling system service.

e. Provide nonvolatile memory for system database, logic, and operating system and event history. System must require no manual input to initialize in the event of complete power down condition. FACU must provide minimum 500-event history log.

f. Addressable Initiation Device Circuits: FACU must indicate which communication zones have been silenced and must provide selective silencing of alarm notification appliance by building communication zone.

1) Addressable Control Circuits for Operation of Notification Appliances and

Mechanical Equipment: FACU must be listed for releasing service.

g. Fire-Alarm Annunciator: Arranged for interface between human operator at FACU and addressable system components including annunciation and supervision.

Display alarm, supervisory, and component status messages and programming and control menu.

1) Annunciator and Display: LCD, 40 characters, minimum.

2) Keypad: Arranged to permit entry and execution of programming, display, and control commands.

h. Initiating-Device, Notification-Appliance, and Signaling-Line Circuits:

1) Pathway Class Designations: NFPA 72, Class B .

2) Pathway Survivability: Level 0 .

3) Install no more than 50 addressable devices on each signaling-line circuit.

i. Serial Interfaces:

1) One RS 485 port for remote annunciators, Ethernet module, or multi-interface module (printer port).

2) One USB port for PC configuration.

j. Notification-Appliance Circuit:

1) Audible appliances must sound in three-pulse temporal pattern, as defined in

NFPA 72.

2) Visual alarm appliances must flash in synchronization where multiple appliances are in same field of view, as defined in NFPA 72.

k. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in smoke-barrier walls must be connected to fire-alarm system.

l. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory, and trouble signals to remote alarm station.

m. Status Annunciator: Indicate status of various voice/alarm speaker zones and status of firefighters' two-way telephone communication zones.

n. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events.

Identify zone, device, and function. Include type of signal (alarm, supervisory, or trouble) and date and time of occurrence. Differentiate alarm signals from other printed indications. Also, print system reset event, including same information for device, location, date, and time. Commands initiate printing of list of existing alarm, supervisory, and trouble conditions in system and historical log of events.

o. Primary Power: 24 V(dc) obtained from 120 V(ac) service and power-supply module. Initiating devices, notification appliances, signaling lines, trouble signals, and supervisory signals must be powered by 24 V(dc) source.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 6 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

p. Alarm current draw of entire fire-alarm system must not exceed 80 percent of power-supply module rating.

q. Secondary Power: 24 V(dc) supply system with batteries, automatic battery charger, and automatic transfer switch.

r. Batteries: Sealed, valve-regulated, recombinant lead acid .

D. Accessories:

1. Instructions: Computer printout or typewritten instruction card mounted behind plastic or glass cover in stainless steel or aluminum frame. Include interpretation and describe appropriate response for displays and signals. Briefly describe functional operation of system under normal, alarm, and trouble conditions.

2.3 MANUAL FIRE-ALARM BOXES

A. General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes must be finished in red with molded, raised-letter operating instructions in contrasting color; must show visible indication of operation; and must be mounted on recessed outlet box. If indicated as surface mounted, provide manufacturer's surface back box.

1. Single-action mechanism, pull-lever type; with integral addressable module arranged to communicate manual-station status (normal, alarm, or trouble) to FACU.

2. Station Reset: Key- or wrench-operated switch.

3. Able to perform at up to 90 percent relative humidity at 90 deg F .

4. Material: Manual stations made of Lexan polycarbonate .

5. Able to be used in indoor areas.

2.4 SYSTEM SMOKE DETECTORS

A. Photoelectric Smoke Detectors:

1. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

2) UL 268.

b. General Characteristics:

1) Detectors must be two-wire type.

2) Integral Addressable Module: Arranged to communicate detector status

(normal, alarm, or trouble) to FACU.

3) Base Mounting: Detector and associated electronic components must be mounted in twist-lock module that connects to fixed base. Provide terminals in fixed base for connection to building wiring.

4) Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation.

5) Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on status.

6) Detector address must be accessible from FACU and must be able to identify detector's location within system and its sensitivity setting.

7) Operator at FACU, having designated access level, must be able to manually access the following for each detector:

a) Primary status.

b) Device type.

c) Present average value.

d) Present sensitivity selected.

e) Sensor range (normal, dirty, etc.).

8) Detector must have functional humidity range within 10 to 90 percent relative humidity.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 7 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

9) Color: White .

10) Remote Control: Unless otherwise indicated, detectors must be digital-addressable type, individually monitored at FACU for calibration, sensitivity, and alarm condition.

11) Multiple levels of detection sensitivity for each sensor.

2.5 DUCT SMOKE DETECTORS

A. Description: Photoelectric-type, duct-mounted smoke detector.

B. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

b. UL 268A.

2. General Characteristics:

a. Detectors must be two-wire type.

b. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to FACU.

c. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation.

d. Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on status.

e. Detector address must be accessible from FACU and must be able to identify detector's location within system and its sensitivity setting.

f. Operator at FACU, having designated access level, must be able to manually access the following for each detector:

1) Primary status.

2) Device type.

3) Present average value.

4) Present sensitivity selected.

5) Sensor range (normal, dirty, etc.).

g. Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with supplied detector for smoke detection in HVAC system ducts.

h. Each sensor must have multiple levels of detection sensitivity.

i. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific duct size, air velocity, and installation conditions where applied.

j. Relay Fan Shutdown: Fully programmable relay rated to interrupt fan motor-control circuit.

2.6 HEAT DETECTORS

A. Combination-Type Heat Detectors:

1. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

2) UL 521.

b. General Characteristics:

1) Temperature sensors must test for and communicate sensitivity range of device.

c. Actuated by fixed temperature of 135 deg F <Insert temperature> or rate of rise that exceeds 15 deg F per minute unless otherwise indicated.

d. Mounting: Twist-lock base interchangeable with smoke-detector bases.

e. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to FACU.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 8 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

f. Detector must have functional humidity range of 10 to 90 percent relative humidity.

g. Color: White .

2.7 FIRE-ALARM NOTIFICATION APPLIANCES

A. Fire-Alarm Audible Notification Appliances:

1. Description: Horns, bells, or other notification devices that cannot output voice messages.

2. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

b. General Characteristics:

1) Individually addressed, connected to signaling-line circuit, equipped for mounting as indicated, and with screw terminals for system connections.

2) Connected to notification-appliance signal circuits, zoned as indicated, equipped for mounting as indicated, and with screw terminals for system connections.

3) Chimes, Low-Level Output: Vibrating type, 75 dB(A-weighted) minimum rated output.

4) Chimes, High-Level Output: Vibrating type, 81 dB(A-weighted) minimum rated output.

5) Sounders, High Volume 24 V(dc): Less than 6 mA of alarm current.

6) Sounders, Low Volume 24 V(dc): Less than 4 mA of alarm current.

7) Audible notification appliances must have functional humidity range of 10 to

95 percent relative humidity.

8) ISO Temporal 3 Evacuation Tone: 90 plus or minus 4 dB(A-weighted) at 24 V.

9) ISO Temporal 3 Alert Tone: 95 plus or minus 5 dB(A-weighted) at 24 V.

10) AS2220 Evacuation Tone: 93 plus or minus 4 dB(A-weighted) at 24 V.

11) AS2220 Alert Tone: 93 plus or minus 5 dB(A-weighted) <Insert number> at

24 V.

12) Horns: Electric-vibrating-polarized type, 24 V(dc); with provision for housing operating mechanism behind grille. Comply with UL 464. Horns must produce sound-pressure level of 90 dB(A-weighted), measured 10 ft. from horn, using coded signal prescribed in UL 464 test protocol.

13) Combination Devices: Factory-integrated audible and visible devices in single-mounting assembly, equipped for mounting as indicated, and with screw terminals for system connections.

B. Fire-Alarm Visible Notification Appliances:

1. Performance Criteria:

a. Regulatory Requirements:

1) NFPA 72.

2) UL 1971.

b. General Characteristics:

1) Rated Light Output:

a) 15/30/75/110 cd, selectable in field.

2) Clear or nominal white polycarbonate lens mounted on aluminum faceplate.

3) Mounting: Ceiling mounted unless otherwise noted.

4) For units with guards to prevent physical damage, light output ratings must be determined with guards in place.

5) Flashing must be in temporal pattern, synchronized with other units.

6) Strobe Leads: Factory connected to screw terminals.

7) Mounting Faceplate: Factory finished, white.

DTMB File #511/17092.JBB DMVA Project #26A9520005

OHM PROJECT #7136-21-0080

ADDRESSABLE FIRE-ALARM SYSTEMS

28 46 21.11 - Page 9 of 13

Copyright © 2022 by the American Institute of Architects. Warning: This AIA MasterSpec-based document is protected by U.S. Copyright Law and International Treaties.

It was created by "OHM Advisors" for "Gladstone Armory Renovate Armory Phase IV". A valid, current MasterSpec license is required for editing and use of this document for any other project.(16861)

2.8 FIRE-ALARM REMOTE ANNUNCIATORS

A. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

2. General Characteristics:

a. Annunciator functions must match those of FACU for alarm, supervisory, and trouble indications. Manual switching functions must match those of FACU, including acknowledging, silencing, resetting, and testing.

1) Mounting: Surface cabinet, NEMA 250, Type 1.

b. Display Type and Functional Performance: Alphanumeric display and LED indicating lights must match those of FACU. Provide controls to acknowledge, silence, reset, and test functions for alarm, supervisory, and trouble signals.

2.9 FIRE-ALARM ADDRESSABLE INTERFACE DEVICES

A. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

2. General Characteristics:

a. Include address-setting means on module.

b. Store internal identifying code for control panel use to identify module type.

c. Listed for controlling HVAC fan motor controllers.

d. Monitor Module: Microelectronic module providing system address for alarm-initiating devices for wired applications with normally open contacts.

e. Integral Relay: Capable of providing direct signal to close coiling door. .

1) Allow control panel to switch relay contacts on command.

2) Have minimum of two normally open and two normally closed contacts available for field wiring.

f. Control Module:

1) Operate notification devices.

2.10 DIGITAL ALARM COMMUNICATOR TRANSMITTERS (DACTs)

A. Performance Criteria:

1. Regulatory Requirements:

a. NFPA 72.

2. General Characteristics:

a. DACT must be acceptable to remote central station and must be listed for fire-alarm use.

b. Functional Performance: Unit must…