5.1C Section J Attachment J.01C_DRAFT Maintenance Bypass Configuration And Wiring Diagram (MBP)_08.29.25_C.doc

DOC document 69 KB Posted

Attached to
FAA Market Survey /Request for Information / Capability Assessment: Procurement of Uninterruptible Power System (UPS) III and Life Cycle Support
Solicitation number
6973GH-25-RFI-UPSI
Issued by

About this file

This is a technical attachment containing the wiring diagram and operational procedures for a Manual Maintenance Bypass (MBP) system designed for Uninterruptible Power System (UPS) installations. The document provides detailed configuration specifications for wall-mounted or free-standing cabinet implementations of the Manual Maintenance Bypass Switch (MMBPS), which enables technicians to safely transition UPS loads during maintenance operations.

The MBP sequence of operation follows a make-before-break protocol that requires placing the UPS unit in Static Bypass mode and using Kirk Keys to systematically control three switches in sequence: Switch No. 1 (closure), Switch No. 2 (opening), and Switch No. 3 (optional load bank testing). The wiring diagram illustrates the interconnections between the UPS three-phase output, essential panel input, maintenance bypass breaker, static bypass breaker, rectifier input breaker, and connections to critical load panels and load banks. The system includes an interlock mechanism with a solenoid-controlled Kirk Key release that coordinates UPS output voltage phasing with the essential panel. Normally Open (N.O.) and Normally Closed (N.C.) switch configurations are specified, along with optional Kirk Key solenoid power connections to ensure safe operational sequencing during maintenance activities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J, ATTACHMENT J.01C

MANUAL MAINTENANCE BYPASS CONFIGURATION

MANUAL MAINTENANCE BYPASS CONFIGURATION

MANUAL MAINTENANCE BYPASS SWITCH (MMBPS)

WIRING DIAGRAM FOR WALL MOUNT OR FREE STANDING CABINET

MANUAL MAINTENANCE BYPASS (MBP) WALL MOUNT PANEL OR FREE STANDING CABINET

MBP Sequence of Operation for Make-before-break.

Place UPS unit in Static Bypass mode of operation. UPS output voltage is now in phase with essential panel. UPS interlock with MBP panel signals Kirk Key solenoid release.

Remove Kirk Key from solenoid, then insert in SW No. 1 Kirk Key and close switch No. 1.

Then insert Kirk Key in SW No. 2 and open switch No. 2.

If needed, close switch No. 3 for UPS load bank testing.

SW-3

SW-2

SW-1

UPS

Three Phase

N.C.

OUTPUT TO LOAD BANK

AC OUTPUT TO CRITICAL LOAD PANEL

N.O.

ESSENTIAL PANEL

MAINTENANCE BYPASS BREAKER BREAKERSWITCHBREAKER

UPS STATIC BYPASS BREAKER

UPS RECTIFIER INPUT BEAKER

SW 2

N.C.

SW 3

SW 1

N.O

Optional Kirk Key Solenoid Power

Output from UPS

Output to Critical Panel

Output to

Load Bank

Optional Kirk Keys on Switches SW-1, 2 and 3. Interconnection between UPS and Interlock solenoid for Kirk Key.

N.O = Normally Open

N.C.= Normally Closed

Essential Panel input to MMBPS