3_Appendix B UPS III Draft Section B_10.22.2025.xlsx

XLSX spreadsheet 52 KB Posted

Attached to
FAA Market Survey /Request for Information / Capability Assessment: Procurement of Uninterruptible Power System (UPS) III and Life Cycle Support
Solicitation number
6973GH-25-RFI-UPSI
Issued by

About this file

This is a draft pricing and line item specification document for Section B of a Federal Aviation Administration (FAA) Uninterruptible Power System (UPS) III solicitation. The document serves as an appendix outlining all potential contract line item numbers (CLINs) and associated products/services that may be procured under the UPS III contract.

The specification covers a comprehensive range of UPS equipment across multiple voltage configurations (208V and 480V, three-phase, 60 Hz) with power ratings spanning from 3-9 kVA to 600 kVA. Line items include the main UPS units with both top-entry and bottom-entry module configurations organized by kVA rating bands (X0001 and X0002 series for 208V and 480V respectively), battery systems (lithium-ion, seismic flame-retardant VRLA with 3-year warranty, and vented lead acid with 1-, 3-, or 5-year warranty options), manual maintenance by-pass equipment for various configurations, battery monitoring systems with commissioning and training, SCADA software for monitoring and control, battery disconnect switches, load banks (portable and stationary), operational and installation manuals, and comprehensive ancillary services. Ancillary services include UPS start-up and testing (single units and systems, with regular and after-hours pricing), equipment delivery (ground level, inside delivery, and delivery outside the continental U.S.), contractor-conducted training at factory and on-site locations, program management, integrated logistics support including recommended and site spare parts lists, contractor depot logistics support with warehouse management and help-line services, travel and subsistence reimbursement, and over-and-above work items. The document references multiple price exhibits (A through K) corresponding to specific CLINs, though actual pricing data is not populated in this draft version.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAFT Section B Appendix B, Draft UPS III Section B

CLINITEMDo you have an Equivilent Part Number?Vendor Part Number Description (Feedback/Input Optional)UNITComments / Feedback / Suggestions
X0001Three Phase, 208/208 Volt 60 Hz, Uninterruptible Power Supply Unit,IAW Section J, Attachement J.01, Section 1.1a
X0001AUninterruptible Power Supply, Top Entry 208/208 volt Module 10-19 kVA. Actual kVA Rating _________ Unit Model Number__________FALSEEach
X0001AAUninterruptible Power Supply, Bottom Entry 208/208 volt Module 10-19 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001BUninterruptible Power Supply, Top Entry 208/208 volt Module 10-19 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001BBUninterruptible Power Supply, Bottom Entry 208/208 volt Module 20-29 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001CUninterruptible Power Supply, Top Entry 208/208 volt Module 30-39 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001CCUninterruptible Power Supply, Bottom Entry 208/208 volt Module 30-39 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001DUninterruptible Power Supply, Top Entry 208/208 volt Module 40-49 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001DDUninterruptible Power Supply, Bottom Entry 208/208 volt Module 40-49 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001EUninterruptible Power Supply, Top Entry 208/208 volt Module 50-65 kVA.Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001EEUninterruptible Power Supply, Bottom Entry 208/208 volt Module 50-65 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001FUninterruptible Power Supply, Top Entry 208/208 volt Module 66-80 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001FFUninterruptible Power Supply, Bottom Entry 208/208 volt Module 66-80 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001GUninterruptible Power Supply, Top Entry 208/208 volt Module 81-100 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001GGUninterruptible Power Supply, Bottom Entry 208/208 volt Module 81-100 kVA. Actual kVA Rating Unit _________ Model Number _________FALSEEach
X0001HUninterruptible Power Supply, Top Entry 208/208 volt Module 101-150 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001HHUninterruptible Power Supply, Bottom Entry 208/208 volt Module 101-150 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001JUninterruptible Power Supply, Top Entry 208/208 volt Module 3-9 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001JJUninterruptible Power Supply, Bottom Entry 208/208 volt Module 3-9 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001IUninterruptible Power Supply, Top Entry 208/208 volt Module 151-170 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0001IIUninterruptible Power Supply, Bottom Entry 208/208 volt Module 151-170 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002Three Phase, 480/480 Volt 60 Hz, Uninterruptible Power Supply Unit. IAW Section J, Attachment J.01, Section 1.1a
X0002AUninterruptible Power Supply, Top Entry 480/480 volt Module 30-39 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002AAUninterruptible Power Supply, Bottom Entry 480/480 volt Module 30-39 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002BUninterruptible Power Supply, Top Entry 480/480 volt Module 40-49 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002BBUninterruptible Power Supply, Bottom Entry 480/480 volt Module 40-49 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002CUninterruptible Power Supply, Top Entry 480/480 volt Module 50-65 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002CCUninterruptible Power Supply, Bottom Entry 480/480 volt Module 50-65 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002DUninterruptible Power Supply, Top Entry 480/480 volt Module 66-80 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002DDUninterruptible Power Supply, Bottom Entry 480/480 volt Module 66-80 kVA .Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002EUninterruptible Power Supply, Top Entry 480/480 volt Module 81-100 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002EEUninterruptible Power Supply, Bottom Entry 480/480 volt Module 81-100 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002FUninterruptible Power Supply, Top Entry 480/480 volt Module 101-150 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002FFUninterruptible Power Supply, Bottom Entry 480/480 volt Module 101-150 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002GUninterruptible Power Supply, Top Entry 480/480 volt Module 151-250 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002GGUninterruptible Power Supply, Bottom Entry 480/480 volt Module 151-250 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002HUninterruptible Power Supply, Top Entry 480/480 volt Module 251-300 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002HHUninterruptible Power Supply, Bottom Entry 480/480 volt Module 251-300 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002IUninterruptible Power Supply, Top Entry 480/480 volt Module 301-400 kVA. Actual kVA Rating Unit _________ Model Number _________FALSEEach
X0002IIUninterruptible Power Supply, Bottom Entry 480/480 volt Module 301-400 kVA. Actual kVA Rating Unit _________ Model Number _________FALSEEach
X0002JUninterruptible Power Supply, Top Entry 480/480 volt Module 500-600 kVA. Actual kVA Rating Unit _________ Model Number _________FALSEEach
X0002JJUninterruptible Power Supply, Bottom Entry 480/480 volt Module 500-600 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0002JJJUninterruptible Power Supply N+1 480/480 volt Module 500-600 kVA. Actual kVA Rating _________ Unit Model Number _________FALSEEach
X0003UPS Battery Systems
X0003ALithium-IonFALSEEach
X0003BSeismic Flame Retardant Valve Regulated Lead Acid (VRLA) Battery UPS string w/3-year (Refer to Exhibit A)FALSEEach
X0003CVented Lead Acid (VLA) UPS unit String, w/1-year replacement warranty. (Refer to Exhibit B)FALSEEach
X0003DVented Lead Acid (VLA) ,w/3-year replacement warranty. (Refer to Exhibit B)FALSEEach
X0003EVented Lead Acid (VLA) , w/5-year replacement warranty. (Refer to Exhibit B)FALSEEach
X0003FSpill Containment SystemFALSEEach
X0003GSpill Cleanup and Disposal KitFALSEKit
X0003HAisle MattingFALSELF
X0003IBattery Maintenance Safety Kit.FALSEKit
X0003JBattery Maintenance Tool Kit.FALSEKit
X0003KInfrared Temperature Gun.FALSEEach
X0003LBattery Maintenance Lift, Medium-Duty.FALSEEach
X0003MVented Lead Acid (VLA) Installation.FALSESite
X0003NBattery Watering EquipmentFALSEEach
X0004Manual Maintenance By-Pass (MBP) for 208 Volt UPS. IAW Attachment J.01, Section 2.13.1
X0004AMBP, Wall Mount 20 to 100 kVA, 208 volt. (Refer to Exhibit C)FALSE
X0004BMBP, Floor Mount, Free-Standing Cabinet for 80 to 170 kVA, 208 volt. (Refer to Exhibit C)FALSE
X0004CMBP, Sidecar 80 to 150 kVA, 208 volt. (Refer to Exhibit C)FALSE
X0004DMBP, Wall Mount 30 to 600 kVA, 480 volt. (Refer to Exhibit C)FALSE
X0004EMBP, Floor Mount, Free-Standing Cabinet for 30 to 600 kVA, 480 volt. (Refer to Exhibit C)FALSE
X0004FMBP, Sidecar 66 to 150 kVA, 480 volt. (Refer to Exhibit C)FALSE
X0004GMBP Kirk Keys and Interlock Solenoid for two breaker MBP.FALSESET
X0004HMBP Kirk Keys and Interlock Solenoid for three breaker MBP.FALSESET
X0005Battery Monitor
X0005ABattery Voltage/Internal Resistance/Impedance/Conductance Monitor, VRLA, 1 STRING Excludes Commissioning/Start-UpFALSESET
X0005BBattery Voltage/Internal Resistance/Impedance/Conductance Monitor, VRLA, 2 STRINGS Excludes Commissioning/Start-UpFALSESET
X0005CCommissioning/Start-Up for CLINS 0005A and 0005BFALSESITE
X0005DTravel for Battery Monitor commisioning, Start-Up and Installation Reimbursed at cost IAW Federal Travel RegulationsFALSESITE
X0005D1ReservedFALSESITE
X0005D2ReservedFALSESITE
X0005D3ReservedFALSESITE
X0005D4ReservedFALSESITE
X0005EOne day Battery Monitor Training, Operation and troubleshooting, concurrent with commissioning travel.FALSESITE
X0005FLaptop for Battery MonitorFALSEEach
X0005GUPS, 120 volt 500VAFALSEEach
X0005HWall mount Laptop Case and Security CableFALSESET
X0005IBattery Voltage/Internal Resistance/Impedance/Conductance Monitor, VLA, 1 STRING Excludes Commissioning/Start-UpFALSESET
X0005JBattery Voltage/Internal Resistance/Impedance/Conductance Monitor, VLA, 1 STRINGS Includes Commissioning/Start-UpFALSESET
X0006Remote Monitor Alarm PanelFALSE
X0007Supervisory Control And Data Acquisition (SCADA). IAW Attachment J.01B
X0007ASCADA Software Configured for monitoring only.FALSE
X0007BSCADA Software Configured for control and monitoring on up to four parralleled UPS units at one site.FALSE
X0007CWeb License Package for 5 additional usersFALSE
X0007DPaging Module, text messaging to phonesFALSE
X0007EWorkstation. (desktop, cabinet or standalone). Includes all ancillary equipment such as Video Display Terminal, power supply;and processor.FALSE
X0007FVDT Enclosure. Used when VDT is not installed in a cabinet or Switchboard. Metal enclosure to house stand alone VDT touch screen. The enclosure includes all ancillary equipment such as, power supply; input/output card; Gateway card to Local Area Network (LAN); and processor.FALSE
X0007GLaptopFALSE
X0007HSCADA Contractor Conducted Factory Training.FALSE
X0007IPer student; (Min/Max per class: 5/10 students). SCADA Contractor Conducted On-Site Training (per site) (Max per class: 8 students).FALSE
X0008Battery Disconnect, Wall Mount
X0008ADC Disconnect Breaker (Refer to Exhibit D)FALSE
X0008ABattery Circuit Breaker (Refer to Exhibit D)FALSE
X0009Load Bank
X0009ALoad Bank for 208 Volt and 480 Volt UPS Unit, Portable (Refer to Exhibit E)FALSE
X0009BLoad Bank for 208 Volt and 480 Volt UPS Unit, Stationary (remote control panel only) (Refer to Exhibit E)FALSE
X00010Manuals. Hard and Soft Copy
X00010AUPS Unit Operation and Maintenance Manual Set.
X00010BUPS Unit Operation and Maintenance Optional Second Set of O&M Manual
X00010CUPS Installation Manual Set.
Ancillary Services. The contractor must provide all ancillary services including but not limited to services necessary for each UPS system procured under CLINs 001, 002, and 003 through start-up, testing, maintenance of the system, and training
X00011UPS Start-Up and Testing Services IAW Section J, Attachment J.01, Section 3.1, 3.2 and 3.3, in the 48 contiguous United States
X00011ASingle Unit Start-Up. Per Att J.01 Section. 3.1 Under 400 kVA(Regular work hours; Monday-Friday).SITE
X00011BSingle Unit Start-Up. Per Att J.01 Section. 3.1 Under 400 kVA (After regular work hours, includes weekends).SITE
X00011CSingleUnit Start-Up Over 400 kVA. Per Att J.01 Section. 3.1 (Regular work hours: Monday-Friday).Each
X00011DSingle Unit Start-Up Over 400 kVA Per Att J.01 Section. 3.1 (After regular work hours, includes weekends).Each
X00011ESingle Unit Test. Per Att J.01 Section. 3.2 through 3.2.1.3 (Regular work hours: Monday-Friday).SITE
X00011FSingle Unit Test, Per Att J.01 Section. 3.2 through 3.2.1.3 (After regular work hours, includes weekends).SITE
X00011GUPS System Test-Single Uninterruptible Power Supply and Single EGS. Per Att J.01 Section. 3.2.2 (Regular work hours: Monday-Friday).SITE
X00011HUPS System Test-Single Uninterruptible Power Supply and Single EGS. Per Att J.01 Section. 3.2.2 (After regular work hours, includes weekends).SITE
X00011IUPS Factory Witness Testing-Single Uninterruptible Power Supply Unit. Per Att J.01 Section. 3.3 (Regular work hours: Monday-Friday).Each
X00011JUPS Battery Test. Per Att J.01 Section 3.2.1.5 (Regular work hours: Monday-Friday).Each
X00011KUPS Battery Monitor System Test. Per Att J.01 Section 3.2.1.4 (Regular work hours: Monday-Friday).Each
X00012Equipment Delivery Service
X00012AGround Level Delivery
X00012BInside Delivery
X00012CDelivery Outside the contiguous 48 United States
X00013Contractor Conducted Training
X00013AContractor Conducted Factory Training; Per student; (Min/Max per class: 5/10 students).Each
X00013BContractor Conducted On-Site Training (per site); Per Site: (Max per class: 8 students).SITE
X00013CPost-Award Training Conference ReportEach
X00014Training Development
X00015Program Management. IAW Statement of Work (SOW), Section C.3 and C.4
X00015AProgram Manager, SOW Section C.3Hour
X00015BProgram Plan IAW SOW Section C.4.1.1Each
X00015CProgram Management Report IAW SOW C.4.1.2Each
X00015DE-Stock Warehouse Rent Support for e-Stock warehouse space as contemplated by the SOW Section C.4.2.8Month
Logistics Support
X00016Integrated Logistics Support (ILS) Management. IAW Statement of Work (SOW), Section C.4.8.1.2
X00016ARecommended Spare Parts List (RSPL), includes both depot and site spares. IAW SOW C.4.8.2.1.1
X00016BSite Spare Parts List (SSPL). Subset list of CLIN 0016B, of site spares. IAW SOW C.4.8.2.1.2
X00016CSupport Equipment Candidate List (SECL). Equipment and tools IAW SOW C.4.8.2.1.4;
CONTRACTOR DEPOT LOGISTICS SUPPORT (CDLS)
X00017CDLS—Program Management IAW Statement of Work (SOW), Section C.4.8.9.2
X00017ACDLS Spares Warehouse Rent Support of CDLS as contemplated by the SOW Section C.4.8.9.3.1Month
X00017BCDLS Invoicing and Shipping P1, P2, P5 IAW SOW Section C.4.8.9.3.5
X00017CCDLS-Help-Line Services. IAW SOW Section C.4.8.9.3.7Month
X00017DCDLS-On-Site Support. IAW SOW Section C.4.8.9.3Hour
X00017ECDLS Warehouse Management IAW C.4.8.9.3.1Hour
Conferences and Meetings
X00018Conferences and Meetings IAW SOW, Section C.4.1.3.1
X00018AProgram ManagerHour
X00018ATechnical SupportHour
X00018AAdministrative SupportHour
Travel and Subsistence Support.
X00019Travel Support. Applicable to CLINs 0013B, 0017D and 0018. Reimbursed at cost IAW Federal Travel Regulations.
X00020Subsistence Support (Per Diem). Applicable to CLINs 0013B, 0017D and 0018. Reimbursed at cost IAW Federal Travel Regulations.
X00021Materials. Contractor-furnished direct materials in support of CLIN 0017D
X00022Over and Above Work. The over and above work items set forth below are not included in the scope and prices of the basic work items above. The work called for under these items must be accomplished when and as directed by the Contracting Officer.
X00022AFixed-Price Items. (RESERVED)
X00022BFixed Daily Rate/Hourly Rate Items. (RESERVED)
X00022CCO Negotiated Items. (RESERVED)
X00023Reserved
X00024Reserved
X00025Miscellaneous UPS Install Components ( Refer to Price Exhibit K)
Price Exhibit A,
CLIN 0003A Reserved
CLIN 0003B UPS Battery System Prices Zone 4 Battery and Battery Rack
UPS CLINUPS kVA
0001A10
0001B20
0001C30
0001D40
0001E65
0001F80
0001G100
0001H150
0001I160
0001J3-9
0002A30
0002B40
0002C65
0002D80
0002E100
0002F150
0002G225
0002H275
0002I400
0002J550
Price Exhibit B
CLIN 0003C UPS Battery System 1-Year Warranty Prices
UPS CLINUPS kVA
0001A10
0001B20
0001C30
0001D40
0001E65
0001F80
0001G100
0001H150
0001I160
0001J3-9
0002A30
0002B40
0002C65
0002D80
0002E100
0002F150
0002G225
0002H275
0002I400
0002J550
CLIN 0003D UPS Battery System 3-Year Warranty Prices
UPS CLINUPS kVA
0001A10
0001B20
0001C30
0001D40
0001E65
0001F80
0001G100
0001H150
0001I160
0001J3-9
0002A30
0002B40
0002C65
0002D80
0002E100
0002F150
0002G225
0002H275
0002I400
0002J550
CLIN 0003E UPS Battery System 5-Year Warranty Prices
UPS CLINUPS kVA
0001A10
0001B20
0001C30
0001D40
0001E65
0001F80
0001G100
0001H150
0001I160
0001J3-9
0002A30
0002B40
0002C65
0002D80
0002E100
0002F150
0002G225
0002H275
0002I400
0002J550
Price Exhibit C
CLIN 0004A MBP, Wall Mount 208 Volt
UPS CLINkVA Rating
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
CLIN 0004B MBP, Floor Mount 208 Volt
UPS CLINkVA Rating
0001F80Each
0001G100Each
0001H150Each
0001I160Each
CLIN 0004C MBP, SideCar 208 Volt
UPS CLINkVA Rating
0001F80Each
0001G100Each
0001H150Each
CLIN 0004D MBP, Wall Mount 480 Volt
UPS CLINkVA Rating
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
CLIN 0004E MBP, Floor Mount 480 Volt
UPS CLINkVA Rating
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
CLIN 0004F MBP, SideCar 480 Volt
UPS CLINkVA Rating
0002D80Each
0002E100Each
0002F120Each
Price Exhibit D
CLIN 0008A DC DISCONNECT BREAKER
UPS CLINkVA Rating
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
CLIN 0008B BATTERY CIRCUIT BREAKER
UPS CLINkVA Rating
0001G100Each
0001H150Each
0001I160Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit E
CLIN 0009A PORTABLE LOAD BANK 208 Volt and 480 Volt UPS
UPS CLINkVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
CLIN 0009B STATIONARY LOAD BANK 208 Volt and 480 Volt UPS
UPS CLINkVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit F
CLIN 0016A Recommended Spare Parts List (RSPL)
UPS CLINUPS kVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit G
Stationary Load Bank
UPS CLINkVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit H
CLIN 0016B UPS Site Spare Parts
UPS CLINUPS kVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit I
CLIN 0016B Load Bank Site Spare Parts
UPS CLINkVA
0001A10Each
0001B20Each
0001C30Each
0001D40Each
0001E65Each
0001F80Each
0001G100Each
0001H150Each
0001I160Each
0001J3-9Each
0002A30Each
0002B40Each
0002C65Each
0002D80Each
0002E100Each
0002F150Each
0002G225Each
0002H275Each
0002I400Each
0002J550Each
Price Exhibit J
CLIN 0016C Support Equipment Candidate List (SECL)
Part NumberDescription
UPS Service Test Equipment Kit
UPS Service Tool Kit
Battery Service Safety Kit
Battery Service Test Equipment Kit
Battery Service Tool Kit
Price Exhibit K
CLIN 025 Miscellanous UPS Install Components
Part NumberDescription