5-6730 E2.2.1A.pdf

PDF 198 KB Posted

Attached to
RFP - Welding Lab
Solicitation number
RFP VBI 260000002075 3
Issued by
Van Buren County, Michigan

About this file

This is an electrical power and communications plan for a Career & Technical Education Improvements project at Van Buren Intermediate School District in Lawrence, Michigan. The document is a detailed architectural drawing (Sheet E2.2.1A) depicting the Unit 'A' First Floor Power & Communications Plan for a welding lab facility. The plan specifies electrical infrastructure including multiple receptacle types (GFCI, 15-20R, 6-50R, 20-30R, and 6-20R receptacles) distributed across various spaces such as welding stations, lab areas, offices, storage, and support rooms. The drawing identifies numerous electrical loads and branch circuits, with specific homerun designations to welding bus bars (Welding-West, Welding-East, and Welding-Center), each with corresponding disconnect switches and amperage ratings (50A, 60A, and 20A). Key deadlines referenced include bids and construction on 05.14.2026, with addendums issued on 05.28.2026 and 06.04.2026.

The electrical plan incorporates specialized infrastructure requirements including dedicated 20-ampere branch circuits with breaker lock-on accessories for smoke dampers, fire alarm duct smoke detectors, and addressable relay systems for damper interlock operations. The document mandates tamper-resistant receptacles per NEC 406.12 specifications and establishes designated cabling pathways reserved exclusively for Division 27 communications and Division 28 safety/security cabling, with separate independent pathways required for control cabling. Electronic door hardware power supplies must be consolidated at central locations adjacent to access control equipment and connected to dedicated standby power systems. The plan includes provisions for future welders with 60-ampere disconnect switches, a dust collector control panel with sensor connectivity, and data drops for clock installations throughout the facility, all requiring compliance with applicable fire code and NEC standards.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C S3

C

AV

AV

AV

F

AV

AV

C S3

2.5

E

E

CR

CR

F

AV

R

1.

2.

3.

4.

5.

A.

B.

C.

D.

E.

6.

7.

8.

REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.0.01.

REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

ALL GENERAL-USE 15- AND 20-AMPERE, 125- AND 250-VOLT NON-LOCKING

RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE; REFER TO NEC 406.12 AND

SPECIFICATION SECTION 26 27 26.

REFER TO LIGHTING CONTROL SCHEDULES, GENERAL NOTES, AND

SPECIFICATIONS FOR AUTOMATIC RECEPTACLE CONTROL REQUIREMENTS.

PROVIDE 120VAC POWER FOR ALL SMOKE DAMPERS AND COMBINATION

FIRE/SMOKE DAMPERS.

REFER TO MECHANICAL/HVAC DRAWINGS FOR LOCATIONS AND QUANTITIES

OF DAMPERS.

CONNECT TO DEDICATED 20A BRANCH CIRCUIT (WITH BREAKER LOCK-ON

ACCESSORY) IN LOCAL PANELBOARD FOR DAMPER(S) IN EACH AREA

(DAMPERS MAY BE GROUPED ON EACH CIRCUIT).

TERMINATE W/ BOX-COVER FUSIBLE DISCONNECT SWITCH AT EACH

DAMPER.

PROVIDE FIRE ALARM DUCT SMOKE DETECTOR WITHIN 5 FEET OF EACH

DAMPER (UNLESS COVERED BY ANOTHER DUCT DETECTOR WITHIN 5 FEET).

PROVIDE FIRE ALARM ADDRESSABLE RELAY(S) FOR INTERLOCKING

DAMPER W/ CORRESPONDING HVAC UNIT(S) PER CODE REQUIREMENTS.

PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

DESIGNATED CABLING PATHWAYS (CONDUITS, CABLE TRAYS, PENETRATION

SLEEVES, ETC.) SHALL BE RESERVED FOR DIV. 27 COMMUNICATIONS CABLING

AND DIV. 28 SAFETY/SECURITY CABLING ONLY. OTHER CABLING TYPES, SUCH

AS DIV. 23 CONTROLS, DIV. 26 CONTROLS, AND ARCHITECTURAL EQUIPMENT

CABLING SHALL BE SUPPORTED AND SLEEVED BY OTHER INDEPENDENT

PATHWAYS, HANGERS, AND SUPPORTS.

CONSOLIDATE ALL POWER SUPPLIES REQUIRED FOR ELECTRONIC DOOR

HARDWARE (REF. SECTION 08 71 00) TO CENTRAL LOCATION(S) ADJACENT TO

DESIGNATED ACCESS CONTROL EQUIPMENT LOCATION(S). CONNECT ALL

POWER SUPPLIES TO DEDICATED STANDBY POWER SYSTEM BRANCH

CIRCUIT(S) AS DESIGNATED FOR CONTINUED OPERATION UNDER LOSS OF

UTILITY POWER.

POWER & COMMUNICATION GENERAL NOTES

GAS #1

A102

GAS #2

A103

LAB SPACE

A113

RECEIVING

A101

OFFICE

A104

ADA CHANGE

A105

CHANGING ROOM #1

A108

CHANGING ROOM #2

A109

EXISTING OFFICE

A110

TOOL CRIB

A111

STORAGE

A114

EXISTING CLASSROOM

A112

BUILDING TRADES

A116

OFFICE

A117

STORAGE

A118

NEW BULLPEN

A115

REFRIGERATION & CLIMATE

CONTROL

A119

CONSTRUCTION MAINTENANCE

A126

20-30R 44"

GFCI

44"

GFCI

44"

6-50R 44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

GFCI

44"

6-50R 44"

GFCI

44"

GFCI

44"

GFCI

44"

6-50R 44"

6-50R 44"

6-50R 44"

20-30R 44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

GFCI

44"

6-50R 44"

6-50R 44"

6-50R 44"

GFCI

44"6-50R

44"

GFCI

44"

6-50R 44"

208-WA-1

P03

P02

208-WA-3

P03

P02

208-WA-5

P03

P02

208-WA-7

P03

P02

P02

208-WA-13

P02

208-WA-15

P02

208-WA-17

P02

208-WA-19

P01

208-WA-20

208-WA-2

P01

208-WA-4

P01

208-WA-6

P01

208-WA-8

P01

208-WA-10

P01

208-WA-12

P01 P01

208-WA-14

P01

208-WA-16

P01

208-WA-18

WL

GFCI

480-WA-1,3,5

480-WA-2,4,6

208-WA-9 208-WA-11P03

P02

P03 P02

15-20R

15-20R

GFCI

44"

208-WB-9

208-WB-9

208-WB-5

208-WB-3

208-WB-1

208-WB-11

208-WB-13

208-WB-15

208-WB-17

208-WB-23

208-WB-21

208-WB-25

CRANE

P05

P05480-WA-7,9,11

15-20R

6-20R

P04

P04

P04

P06 P06 P06 P06 P06 P06

208-WB-16,18

208-WB-19

EX.

FURN

EWC

20"

EWC

20"

A101C

A101A A101B

DC-26.1

2D

208-WB-7

2D

6-20R

15-20RP04

208-WB-20,22

480-WDP-13,15,17

DUST COLLECTOR

CONTROL PANEL

208-WB-28

P08

P09

PROJECT NO.

DRAWN

REVIEWED

NO PART OF THIS DRAWING MAY BE

USED OR REPRODUCED IN ANY FORM

OR BY ANY MEANS, OR STORED IN A

DATA BASE OR RETRIEVAL SYSTEM,

WITHOUT PRIOR WRITTEN

PERMISSION OF

ALL RIGHTS RESERVED

c

KEYPLAN

ISSUANCES

GMB COPYRIGHT

Au to de sk

D oc s:

//5

-6

VB

IS

D

C

TE

Im pr ov em en ts

/5 -6

0E

5.

rv t

6/ 4/

:5

6:

A M

E2.2.1A

5-6730

UNIT 'A' FIRST FLOOR POWER

& COMMUNICATIONS PLAN

JDM

PRH

C A

R E

E R

T

E C

H N

IC

A

L E

D U

C A

T

IO

N

IM

P R

O V

E M

E N

T S

V A

N B

U R

E N

IN

TE

R M

E D

IA

TE

S C

H O

O L

D

IS

TR

IC

T

LA

W R

E N

C E

M

IC

H

IG

A

N

ELECTRICAL KEYNOTES

P01 HOMERUN TO BUS 'WELDING-WEST' AND TERMINATE ON 2-POLE

DISCONNECT SWITCH FUSED TO 50A.

P02 HOMERUN TO BUS 'WELDING-EAST' AND TERMINATE ON 2-POLE

DISCONNECT SWITCH FUSED TO 50A.

P03 HOMERUN TO BUS 'WELDING-CENTER' AND TERMINATE ON 3-POLE

DISCONNECT SWITCH FUSED TO 60A.

P04 HOMERUN TO BUS 'WELDING-CENTER' AND TERMINATE ON 3-POLE

DISCONNECT SWITCH FUSED TO 20A.

P05 PROVIDE E-STOP BUTTON TO ACTIVATE SHUNT-TRIP CIRCUIT BREAKERS IN

PANEL '480-WDP'.

P06 PROVIDE 60A DISCONNECT SWITCH FOR FUTURE WELDERS.

P08 PROVIDE 2-#12, 1-#12(G), IN 3/4" CONDUIT TO DUST COLLECTOR FILTER

BANK SENSOR PANEL (LOCATED AT DUST COLLECTOR).

P09 TYPICAL, PROVIDE DATA DROP AT EACH CLOCK LOCATION AND INSTALL

OWNER PROVIDED CLOCK.

1/8" = 1'-0"

UNIT 'A' FIRST FLOOR POWER & COMMUNICATIONS PLAN

UNIT A

UNIT B

UNIT C

UNIT D

UNIT E

UNIT F

05.14.2026 BIDS &

CONSTRUCTION

05.28.2026 ADDENDUM 001

06.04.2026 ADDENDUM 002