About this file
File Summary
This is a product specification document for plumbing fixtures issued by the State of Michigan. The document establishes standard specifications and requirements for plumbing fixtures to be procured through state purchasing channels. The specifications cover various categories of plumbing fixtures including faucets, valves, traps, and related components, with detailed technical requirements, dimensions, materials, and performance standards for each item classification. The document serves as a reference guide for state agencies and authorized purchasers when ordering plumbing fixtures through the designated procurement process, ensuring consistency and quality across all state purchases of these materials.
The document does not specify individual item quantities, response dates, or contract award dates, as it functions as a standardized specification guide rather than a specific procurement solicitation. Pricing information is not included in this specification document. The specifications are designed to be used in conjunction with actual purchase orders and requests for quotation, where pricing terms, delivery schedules, and specific item quantities would be negotiated between the State of Michigan and qualified suppliers. This specification document remains effective as a standing reference for all plumbing fixture procurement activities conducted by the state.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAN BUREN INTERMEDIATE SCHOOL DISTRICT
5-6730 VBISD CTE IMPROVEMENTS
A/E PROJECT 5-6730
Copyright GMB 2025 SECTION 22 40 00
PLUMBING FIXTURES
SECTION 22 40 00 - PLUMBING FIXTURES
(ADDENDUM 002)
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Wall-hung, solid surface, multi-station lavatory units.
B. Under-lavatory pipe supply covers.
C. Bi-level, electric water coolers.
1.2 RELATED REQUIREMENTS
A. Section 06 41 00 - Architectural Wood Casework: Counters for sinks and lavatories.
B. Section 07 92 00 - Joint Sealants: Sealing joints between fixtures and walls and floors.
C. Section 22 10 05 - Plumbing Piping.
1.3 REFERENCE STANDARDS
A. ADA Standards - 2010 ADA Standards for Accessible Design.
B. ASHRAE Std 18 - Methods of Testing for Rating Drinking-Water Coolers with Self-Contained
Mechanical Refrigeration.
C. ASME A112.18.1 - Plumbing Supply Fittings.
D. ASME A112.18.9 - Protectors/Insulators for Exposed Waste and Supplies on Accessible
Fixtures.
E. ASME A112.19.3 - Stainless Steel Plumbing Fixtures.
F. ASSE 1070 - Performance Requirements for Water Temperature Limiting Devices.
G. ASTM C1822 - Standard Specification for Insulating Covers on Accessible Lavatory Piping.
H. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
I. ICC A117.1 - Accessible and Usable Buildings and Facilities.
J. NSF 61 - Drinking Water System Components - Health Effects.
K. NSF 372 - Drinking Water System Components - Lead Content.
1.4 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittal procedures.
B. Product Data: Provide catalog illustrations of fixtures, sizes, rough-in dimensions, utility sizes, trim, and finishes.
C. Manufacturer's Instructions: Indicate installation methods and procedures.
D. Maintenance Data: Include fixture trim exploded view and replacement parts lists.
E. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 60 00 - Product Requirements for additional provisions.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Source Limitations: Products shall be obtained from a single manufacturer for each product category and type whenever possible. If not possible, obtain similar products from other listed manufacturers for each category and type.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Accept fixtures on-site in factory packaging. Inspect for damage.
A/E PROJECT 5-6730
Copyright GMB 2025 SECTION 22 40 00
PLUMBING FIXTURES
B. Protect installed fixtures from damage by securing areas and by leaving factory packaging in place to protect fixtures and prevent use.
PART 2 PRODUCTS
2.1 GENERAL REQUIREMENTS
A. Potable Water Systems: Provide plumbing fittings and faucets that comply with NSF 61 and NSF 372 for maximum lead content; label pipe and fittings.
2.2 REGULATORY REQUIREMENTS
A. Comply with applicable codes for installation of plumbing systems.
B. Perform work in accordance with local health department regulations.
C. Provide certificate of compliance from Authority Having Jurisdiction indicating approval of installation.
2.3 WALL-HUNG, SOLID SURFACE, MULTI-STATION LAVATORY UNITS
A. Manufacturers:
1. Zurn Industries, LLC.
2. __________.
3. __________.
B. Description: Rectilinear, level-surface deck, seamless and integral elongated basin, with stainless steel enclosed pedestal cabinet.
C. Deck and Bowl Material: Fabricate from molded engineered stone material consisting of natural quartz, granite, and other minerals in a matrix of thermoset acrylic modified bio-based polyester resin and meeting requirements of IAPMO Z124.
D. Surface Burning Characteristics: Smoke developed index less than 450, and flame spread index less than 25, Class A, when tested in accordance with ASTM E84.
E. Number of Wash Stations: Three.
F. Unit Length: 36 inches.
G. Soap Dispenser:
H. Color: As selected by Architect from manufacturer's full line.
I. Faucet Drilling: 4 inch (100 mm) centerset drilling.
J. Sensor-Operated Faucets:
1. High profile metering faucet with infrared and external temperature control.
2. Vandal-resistant meeting requirements of ASME A112.18.1 and ADA Standards compliant.
3. Body: Polished, chrome-plated commercial solid cast brass, with 4 inch (102 mm) centerset mounting with anti-rotation trim plate.
4. Tempered Water Supply: ADA Standards compliant lever on faucet body.
5. Aerator: Flow rate of 0.5 gpm at 20 to 80 psi operating range.
6. Sensor Module: Water conserving, vandal-resistant adjustable sensor unit with timing turn-off delay and stationary object automatic timed cutoff, with battery diagnostic light, serviceable from above deck.
7. Power Supply: 6 VDC lithium battery and single 115 VAC plug-in adapter.
8. Thermostatic Mixing Valve:
a. ASSE 1070 listed with combination stop, strainer, and check valves, and flexible stainless steel connectors.
K. Access Panel: Stainless steel.
L. Support Frame: Wall-mounted, heavy gauge, stainless steel.
A/E PROJECT 5-6730
Copyright GMB 2025 SECTION 22 40 00
PLUMBING FIXTURES
2.4 UNDER LAVATORY PIPE COVERS
A. Manufacturers:
1. Dearborn; Oatey.
2. Plumberex Specialty Products, Inc.
3. Truebro; IPS Corporation.
4. Substitutions: See Section 01 60 00 - Product Requirements.
B. Basis of Design: Truebro Lav Guard 2 Undersink Pipe Covers.
C. General:
1. Insulate exposed drainage piping and hot, cold and tempered water supplies under lavatories, sinks, etc.. per ADA Standards at all accessible plumbing fixtures.
2. Construction: 1/8 inch PVC or molded vinyl with antimicrobial, antifungal and UV resistant properties.
a. Provide one piece injected molded design with internal bridge at top of J-bend to prevent separating.
b. Comply with ASTM C1822 Type III for covers on accessible lavatory piping.
c. Comply with ASME A112.18.9 for covers on accessible lavatory piping.
d. Comply with ICC A117.1.
3. Color: High gloss white.
4. Fasteners: Reusable, snap-locking fasteners with no sharp or abrasive external surfaces.
No cable ties allowed.
2.5 BI-LEVEL, ELECTRIC WATER COOLERS
A. Electric Water Cooler, Bi-level, Surface Mounted, Filtered, With Bottle Filling Station_______:
1. Manufacturers:
a. Elkay Manufacturing Company.
b. Halsey Taylor; an Elkay Manufacturing Company.
c. Haws Corporation.
d. Murdock Manufacturing.
e. Oasis International.
f. Substitutions: See Section 01 60 00 - Product Requirements.
2. Water Cooler: ASME A112.19.3; Bi-level, electric, mechanically refrigerated surface mounted; stainless steel top, vinyl on steel body, elevated anti-squirt bubbler with stream guard, automatic stream regulator, push bar activation, mounting bracket; integral air cooled condenser, quick filter change housing, and stainless steel grille.
a. Capacity: 8 gph of 50 degrees F; based on 80 degrees F inlet water temperature and
90 degrees F ambient air temperature, when tested in accordance with ASHRAE Std 18.
b. Electrical: 115 VAC, 60 Hertz compressor, 6 foot cord and plug for connection to electric wiring system including grounding connector.
3. Bubbler: Flexible safety guard.
4. Bottle Filler: Materials to match fountain, antimicrobial, visual filter monitor with filter change alert and automatic reset, low energy LED lighting, hands free, laminar flow, drain,
1.1 gpm.
5. Finish: Stainless Steel.
6. Mounting Height and Installation Requirements: Accessible.
7. Electric Water Cooler Accessories:
a. Elkay 51300C NSF 372 lead free 3 filter replacement pack.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that walls and floor finishes are prepared and ready for installation of fixtures.
A/E PROJECT 5-6730
Copyright GMB 2025 SECTION 22 40 00
PLUMBING FIXTURES
3.2 PREPARATION
A. Rough-in fixture piping connections in accordance with minimum sizes indicated in fixture rough-in schedule for particular fixtures.
3.3 INSTALLATION
A. Rough-in dimensions shall be established from the approved submittals.
B. Assemble fixtures, fittings, and trim in accordance with the manufacturer's written installation instructions.
C. Install each fixture with trap, easily removable for servicing and cleaning.
D. Provide chrome-plated rigid and flexible supplies to fixtures as indicated with loose key stops, reducers, and escutcheons.
E. Install fixtures and components level and plumb.
F. Seal fixtures to countertop, floor, and wall surfaces with sealant, color to match fixture. See section 07 92 00 - Joint Sealants.
G. Install Accessible fixtures, components, and trim in compliance with ICC A117.1.
3.4 INTERFACE WITH WORK OF OTHER SECTIONS
A. Review millwork shop drawings. Confirm location and size of fixtures and openings before rough-in and installation.
3.5 ADJUSTING
A. Operate and adjust flushometer valves to ensure proper flow rate and fixture operation without splashing or overflow. Replace damaged or malfunctioning valves.
B. Adjust stops or valves for intended water flow rate to fixtures without splashing, noise, or overflow.
C. Operate and adjust faucets and controls. Replace damaged or malfunctioning fixtures, fittings, trim, and controls.
3.6 CLEANING
A. Clean plumbing fixtures and equipment.
3.7 PROTECTION
A. Protect installed products from damage due to subsequent construction operations.
B. Repair or replace damaged products before Date of Substantial Completion.
END OF SECTION