03 Metal Panel Demo Sheet.pdf

PDF 218 KB Posted

Attached to
RFP - Welding Lab
Solicitation number
RFP VBI 260000002075 3
Issued by
Van Buren County, Michigan

About this file

This is an architectural drawing demonstrating metal panel and wall construction details for the Career & Technical Education Improvements project at Van Buren Intermediate School District in Lawrence, Michigan. The document, designated as drawing A2.2.2A, provides the Unit 'A' Mezzanine Plan at a scale of 1/8" = 1'-0" and includes comprehensive wall legends, framing specifications, and floor plan notes. The project involves construction of educational spaces including a welding lab, building trades area, lab space, receiving area, construction maintenance room, and refrigeration & climate control facilities. Key structural requirements include 5/8" gypsum board on both sides of walls, 3 5/8" light gauge metal framing at 16" on-center spacing, sound batts at full wall height, and CMU (concrete masonry unit) walls with specified reinforcing patterns. The drawing was issued on May 14, 2026, with addenda issued on May 28, 2026 and June 4, 2026. The mezzanine spans 38 feet in depth and includes protective guardrails per specifications and a ladder for access.

The document establishes detailed construction standards including minimum reinforcing requirements of R1-5-48 for all bearing walls, exterior walls, and interior non-bearing walls exceeding 16 feet in height. All guardrails and handrails must comply with the 2021 M.B.C., ANSI A117.1-2017, and Americans with Disabilities Act Guidelines, with the most stringent requirement prevailing. Contractor responsibilities include field verification of all dimensions prior to fabrication, installation of access panels for concealed equipment, coordination with structural columns and utilities, sealing of fire-rated penetrations, and patching of existing walls with like materials where demolition occurs. The scope includes removal and reinstallation of existing metal panels around new openings, with salvaged material being reused for door infills. The drawing provides references to structural, mechanical, plumbing, and electrical drawings for complete project coordination and implementation.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T T

WALL LEGEND

5/8" GYP. BOARD BOTH SIDES 3 5/8" LIGHT GA.

METAL FRAMING AT 16" O.C. SOUND BATT

FULL HEIGHT OF WALL. WALLS TO BOTTOM

OF DECK UNLESS NOTED OTHERWISE

CMU WALL SEE FLOOR PLANS FOR REQUIRED

WALL REINFORCING. NOMINAL DIMENSIONS

GIVEN

(8" TYPICAL U.N.O.)

-FIRE RATINGS AS CALLED FOR ON CODE COMPLIANCE PLAN

-DIMENSIONS GIVEN ARE TO THE FINISHED FACE OF CMU OR

GYPSUM WALL BOARD UNLESS NOTED OTHERWISE

METAL PANEL AND CMU WALL W/ 1 3/4"

INSULATION SEE FLOOR PLANS FOR REQUIRED

WALL REINFORCING. NOMINAL DIMENSIONS

GIVEN. SEE WALL SECTIONS FOR ADDITIONAL

DETAILS, BANDING, ETC.

(3 5/8" BRICK & 8" CMU TYPICAL U.N.O.)

4 7 /8"

SE

E

PL

AN

SE

E

PL

AN

GENERAL FLOOR PLAN NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

A.

B.

C.

DIMENSIONS GIVEN ARE TO THE FACE OF MASONRY UNITS OR TO THE FINISHED FACE OF METAL STUD PARTITION WALLS.

REFERENCE STRUCTURAL DRAWINGS FOR CONCRETE SLAB SIZES AND SLAB RELATED INFORMATION.

INTERIOR STUD WALLS ARE TO USE 3 5/8" METAL STUD FRAMING UNLESS OTHERWISE NOTED.

TURN UP VAPOR RETARDER MATERIAL AT JOINTS BETWEEN FLOOR SLAB AND FOUNDATION WALL UNLESS NOTED

OTHERWISE.

SEE FOUNDATION PLANS FOR FLOOR SLAB RECESSES FOR TILE, WOOD FLOOR, ETC. (VERIFY RECESS REQUIRED BY MFR.)

EXTEND ALL INTERIOR WALL PARTITIONS (MASONRY OR STUDS) TO BOTTOM OF DECK ABOVE UNLESS NOTED OTHERWISE.

REFERENCE STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL FOR ITEMS NOT SHOWN. COORDINATE AS REQUIRED

INCLUDING NECESSARY FRAMING, BLOCKING, ETC.

FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF ANY CABINETRY, FRAMES, STRUCTURAL ITEMS, ETC.

PROVIDE PAINTED ACCESS PANELS IN WALLS AND CEILINGS TO PROVIDE ACCESS TO CONCEALED ITEMS INCLUDING BUT NOT LIMITED TO VALVES, CONTROLS, MECH. EQUIPMENT, ETC. ACCESS PANELS MAY NOT ALWAYS BE SHOWN ON PLANS. IT IS THE SUB CONTRACTOR RESPONSIBILITY TO DETERMINE LOCATIONS. COORDINATE LOCATIONS WITH OTHER GENERAL

CONTRACTOR / SITE SUPERVISOR.

COORDINATE WALLS WITH COLUMNS AND OTHER ENCASED ITEMS. COLUMNS ARE TO BE CONTAINED WITHIN WALLS. THE FRAMING CONTRACTOR SHALL INCREASE FRAMING SIZE TO ACCOMMODATE COLUMNS, DRAIN LEADERS, PIPING, ELECTRICAL PANELS, ETC. WHERE WALLS REQUIRE EXTRA WIDTH THE ENTIRE WALL SHALL BE WIDENED UNLESS

APPROVED BY ARCHITECT.

ALL GUARDRAILS AND HANDRAILS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH ALL REQUIREMENTS OF THE 2021 M.B.C., ANSI A117.1-2017 & AMERICANS WITH DISABILITIES ACT GUIDELINES. THE MOST STRINGENT SHALL

PREVAIL.

PROVIDE MINIMUM CLEARANCES AT ALL DOORS PER DETAILS. SEE G0.01 FOR REQUIREMENTS.

FOR ALL CABINETRY, SEE INTERIOR ELEVATIONS FOR LAYOUTS. FIELD VERIFY CLEAR WIDTHS PRIOR TO FABRICATION.

ALL EXTERIOR BLOCK CORNERS ARE TO BE BULLNOSE BLOCK EXCEPT CONCRETE BLOCK COLUMNS, PIERS AND WALLS TO

RECEIVE TILE - UNLESS NOTED OTHERWISE.

CONTRACTOR TO MAINTAIN / REPAIR RATING OF EXISTING PARTITIONS AS AFFECTED BY DEMOLITION / NEW

CONSTRUCTION. TYPICAL THROUGHOUT.

SEAL ALL PENETRATIONS IN FIRE RATED FLOORS AND WALLS WITH APPROVED FIRESTOPPING.

WHERE SPECIALTY BLOCK IS REQUIRED AT THE SAME HEIGHT ON BOTH SIDES OF A WALL USE (2) SPECIALTY BLOCKS BACK TO BACK TO MAINTAIN THE FINISHED WALL APPEARANCE BOTH SIDES OF THE WALL. COORDINATE WITH STRUCTURAL FOR

LINTELS CONDITIONS PER SPECIFICATIONS.

WALLS TO BE PATCHED WITH LIKE MATERIALS WHERE EXISTING WALLS HAVE BEEN COMPROMISED FROM DEMOLITION. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO REMOVAL AND REINSTALLATION OF CASEWORK AND WALL MOUNTED EQUIPMENT IN ORDER TO ACHIEVE SAID PATCH. IN AREAS WHERE BLOCK OR BRICK HAVE BEEN USED, NEW MASONRY TO BE TOOTHED IN AND MATCH EXISTING. AREAS AND FINISHES IN QUESTION SHALL BE COORDINATED WITH

ARCHITECT.

SEE STRUCTURAL FRAMING PLANS FOR ADDITIONAL WALL REINFORCING REQUIREMENTS. MINIMUM REINFORCING (FOR ALL

WALLS NOT OTHERWISE NOTED ON STRUCTURAL PLANS):

ALL BEARING WALLS SHALL RECEIVE A MINIMUM REINFORCING OF R1-5-48.

ALL EXTERIOR WALLS SHALL RECEIVE A MINIMUM REINFORCING OF R1-5-48.

ALL INTERIOR NON-BEARING WALLS OVER 16'-0" HIGH SHALL RECEIVE A MINIMUM REINFORCING OF R1-5-48.

A2.2.2A

B

C

D

E

F

14 15 17 20 22 25 30

6' - 8" 1' - 6" 20' - 8" 19' - 8"

LAB SPACE

A113

RECEIVING

A101

65" TV

65" TV

65" TV65" TV

OWNER PROVIDED

CONTRACTOR INSTALLED

OWNER PROVIDED

CONTRACTOR INSTALLED

OWNER PROVIDED

CONTRACTOR INSTALLED

W02W01

BUILDING TRADES

A116

CONSTRUCTION MAINTENANCE

A126

REFRIG. & CLIMATE CONTROL

A119

CORRIDOR

A127

MEZZANINE

A201

MECHANICAL EQUIPMENT

SUSPENDED FROM

JOISTS ABOVE. REFER TO

STRUCTURAL AND

MECHANICAL DRAWINGS.

LADDER

A6.1.01

A6.1.01

A6.1.01

0"

MEZZANINE PROTECTIVE

GUARDRAIL; REFER TO

SPECIFICATIONS

A6.1.01

FIRST FLOOR

100' - 0"

T.O. PANEL 28'-9"

120' - 9"

30 28 25 22 20 17 15

W02 W01

0" 3'

- 0

A102AA103AA101DA101F

28 151720222530

7'

- 4

3' - 4"

A6.1.01

TOOTH IN NEW CMU (TO MATCH

EXISTING) IN FORMER DOOR

OPENING. NEW METAL PANEL TO

NEAREST VERTICAL SEAM.

PROJECT NO.

DRAWN

REVIEWED

NO PART OF THIS DRAWING MAY BE

USED OR REPRODUCED IN ANY FORM

OR BY ANY MEANS, OR STORED IN A

DATA BASE OR RETRIEVAL SYSTEM,

WITHOUT PRIOR WRITTEN

PERMISSION OF

ALL RIGHTS RESERVED

c

KEYPLAN

ISSUANCES

GMB COPYRIGHT

Au to de sk

D oc s:

//5

-6

VB

IS

D

C

TE

Im pr ov em en ts

/5 -6

0A

5.

rv t

6/ 3/

:1

0:

P M

A2.2.2A

5-6730

UNIT 'A' MEZZANINE PLAN

LFR

JGP

C A

R E

E R

T

E C

H N

IC

A

L E

D U

C A

T

IO

N

IM

P R

O V

E M

E N

T S

V A

N B

U R

E N

IN

TE

R M

E D

IA

TE

S C

H O

O L

D

IS

TR

IC

T

LA

W R

E N

C E

M

IC

H

IG

A

N

UNIT A

UNIT B

UNIT C

UNIT D

UNIT E

UNIT F

1/8" = 1'-0"

UNIT 'A' MEZZANINE PLAN

05.14.2026 BIDS &

CONSTRUCTION

05.28.2026 ADDENDUM 001

06.04.2026 ADDENDUM 002

A2.2.2A 1/8" = 1'-0"

1 WEST ELEVATION

rkruithof Polygon rkruithof Text Box REMOVE EXISTING METAL PANELS, REINSTALL AROUND NEW OPENINGS. REUSE SALVAGED MATERIAL FROM NEW OPENINGS FOR DOOR INFILL.

rkruithof Cloud

A2.2.2A - UNIT 'A' MEZZANINE PLAN

File details come from the government source that posted it. Updated .