SECTION 01 50 00 - TEMPORARY FACILITIES and CONTROLS
GENERAL
1.1 SUMMARY
A. This section includes requirements for temporary utilities, support facilities and protection.
1. Support facilities include but are not limited to the following:
a. Temporary lifts and hoists.
b. Project identification and other temporary signs.
c. Waste disposal services.
d. Other construction aids and miscellaneous services and facilities.
2. Protection includes but is not limited to the following:
a. Temporary fire protection.
b. Barricades, warning signs, and lights.
c. Environmental protection.
d. Enclosure partitions.
1.2 UTILITY USE CHARGES
A. Water Service: The Contractor may use water from the Government's existing water system, without metering and without payment of use charges.
B. Sewer Service: Contractor may use the Government's existing sewer system, without payment of use charges.
C. Electric Power Service: Contractor may use electric power from the Government's existing electric power system, without metering and without payment of use charges.
1.3 PROJECT CONDITIONS
A. Temporary Use of Permanent Facilities and Services: Contractor shall assume responsibility for the operation, maintenance and protection of the facility and each permanent service during its use as a construction facility prior to the Government's acceptance.
B. Existing Equipment and Items: Cover or otherwise protect and provide security for existing equipment and other items that are to remain in place, to prevent damage and loss, the cost of which is the responsibility of the Contractor.
1. Temporarily move equipment and other items that interfere with the performance of required work.
U.S. Department of Health and Human Services (HHS) 90 7th Street, San Francisco, CA Solicitation 47PK0124R0010
2. Store equipment and other items that have been temporarily removed. Upon reinstallation, clean and, if damaged, repair or replace equipment and items to match their condition prior to removal.
PART 2 PRODUCTS
2.1 MATERIALS
A. Provide undamaged materials in serviceable conditions and suitable for use intended.
B. Tarpaulins: Waterproof, fire-resistant UL labeled with flame spread rating of 15 or less. For temporary enclosures, provide translucent, nylon-reinforced, laminated polyethylene fire-retardant tarpaulins.
C. Sign, Directory and Other Graphic Panel Materials: Unless otherwise indicated, products shall be as follows:
1. Panels: plywood.
2. Paint: Interior primer and interior grade.
3. Paper:
4. (Other)
D. Dust control:
1. Dust Control Adhesive-Surface Walk-off Mats: Provide mats minimum 914 by 1624 mm (36 by 60 inches).
2. Polyethylene Sheet: Reinforced, fire-resistive sheet, 0.25 mm (10 mils) minimum thickness, with flame-spread rating of 15 or less per ASTM E 84 and passing NFPA 701 Test 2.
E. Temporary Lighting systems shall be solid state (e.g., LEDs) (specify minimum foot candles and OSHA requirements).
2.2 EQUIPMENT
A. Provide equipment in serviceable condition and suitable for use intended.
1. Water Hoses: 3/4" (19 mm) heavy duty abrasive-resistant flexible rubber hoses, 100 feet (30
m) long with pressure rating greater than the maximum pressure of the water distribution system. Provide adjustable shutoff nozzles at hose discharge
2. Electric Power Cords: Grounded extension cords.
a. Provide hard-service cords where exposed to abrasion or traffic.
July 23rd, 2024 TEMPORARY FACILITIES and CONTROLS 01 50 00 - page 2 of 5
Solicitation 47PK0124R0010
b. Provide waterproof connectors to connect separate lengths of electric cords where single lengths will not reach areas of construction activity.
c. Do not exceed safe length-voltage ratio.
3. Light Fixtures: General service luminaires with required lumen output for adequate illumination.
a. Provide guard cages or tempered glass enclosures where exposed to breakage.
b. Provide exterior fixtures when exposed to moisture.
4. Heating Units: Temporary heating units that have been tested and labeled by UL, FM or another recognized trade association related to the type of fuel consumed.
5. Fire Extinguishers: Hand-carried portable UL-rated fire extinguishers.
a. Class A extinguishers for temporary offices and similar spaces.
b. Class ABC dry chemical extinguishers or a combination of extinguishers of NFPA recommended classes for exposures in other locations.
c. Comply with NFPA 10 and NFPA 241 for classification, extinguishing agent and size required by location and class of fire exposure.
PART 3 EXECUTION
3.1 INSTALLATION
A. Use qualified personnel for installation of temporary facilities.
B. TEMPORARY SUPPORT FACILITIES
C. Temporary Lifts and Hoists: Provide protection of facilities and personnel for hoisting materials.
D. Existing Elevator Use: Use of GSA's existing passenger elevators will not be permitted unless approved by the GSA Building Manager. Use of GSA’s existing freight elevator is permitted by the GSA Building Manager If allowed, elevators must be protected, cleaned and maintained in a condition acceptable to GSA. At Substantial Completion, restore elevators to conditions existing before initial use, including replacing worn cables, guide shoes, and similar items of limited life.
1. Do not load elevators beyond their rated weight capacity.
2. Provide protective coverings, barriers, devices, signs, or other procedures to protect elevator cars and entrance doors and frames. If, despite such protection, elevators become damaged, engage elevator Installer to restore damaged work so no evidence remains of correction work.
Return items that cannot be refinished in the field to the shop, make required repairs and refinish the entire unit, or provide new units as required.
3. If required by local jurisdiction or union, provide temporary phones for elevators. Coordinate with Elevator maintenance contractor and GSA Building Manager.
TEMPORARY FACILITIES and CONTROLS 01 50 00 - page 3 of 5
Solicitation 47PK0124R0010
E. Temporary Use of Permanent Stairs: Use of permanent stairs for construction traffic will be permitted, provided stairs are protected and restored to new condition at time of Substantial Completion.
Coordinate with GSA Building Manager to identify permanent stairs permitted for use.
F. Project Identification Signs and Other Temporary Signs: Coordinate location with building manager and tenant representatives Provide project identification and other signs of sizes, layout, content, graphics and colors indicated. Locate signs where best to inform the public and instruct persons seeking entrance to the project. Support signs on posts or framing of steel or wood-treated against rot.
1. Project Identification Sign: Refer PBS P100, Site Signage, for the construction sign spec.
information.Comply with sign design as indicated in specification. Use an experienced sign painter to apply graphics.
2. Other Temporary Signs: Prepare signs to provide directional information to construction personnel and visitors.
3. Do not permit installation of unauthorized signs.
G. Collection and Disposal of Waste/Salvaged Material: Collect waste from construction areas and elsewhere daily. Collect salvaged/recycled material from construction areas and elsewhere as necessary. Enforce requirements strictly and dispose of material lawfully.
1. Comply with NFPA 241 for removal of combustible waste material and debris.
2. Do not hold waste materials more than 7 days during periods when the ambient temperature remains continuously less than 80°F (27°C), or more than 3 days when the temperature exceeds or is expected to rise above 80° (27°C).
3. Handle and properly containerize hazardous, dangerous or unsanitary waste materials separately from other waste.
4. Comply with Construction non hazardous Waste Management and Disposal requirements in
GSA FY23 01 74 19 CONSTRUCTION NONHAZARDOUS WASTE MANAGEMENT & DISPOSAL.
3.2 TEMPORARY PROTECTION FACILITIES
A. Environmental Protection: Provide protection, operate temporary facilities, and conduct construction as required to comply with environmental regulations and that minimize possible air, stormwater, sanitary, waterway, and subsoil contamination or pollution or other undesirable effects. Restrict use of noise-making tools and equipment to hours that will minimize complaints from persons near the site.
When working in or near existing facilities, provide dust proof enclosures for protection where dirty work is performed. Dampen debris when removed to avoid dusting.
1. Comply with work restrictions specified in 01 10 00 SUMMARY.
B. Temporary Fire Protection: Until fire protection needs are supplied by permanent facilities, install and maintain temporary fire protection measures and devices of types needed to protect against reasonably predictable and controlled fire losses.
1. Comply with NFPA 10 "Standard for Portable Fire Extinguishers" and NFPA 241 "Standard for Safeguarding Construction, Alterations, and Demolition Operations".
July 23rd, 2024 TEMPORARY FACILITIES and CONTROLS 01 50 00 - page 4 of 5 https://docs.google.com/document/d/1Nep0qW26K-p2xElEcxj-QrrqoLmvgkNzryWAlZbRaBg/edit#heading=h.6huqsft7k8xg
Solicitation 47PK0124R0010
2. Locate fire extinguishers where convenient and effective for their intended purpose, but not less than one extinguisher at or near each access route exit or entrance, including stairwells on each floor.
3. Store combustible materials in containers in fire-safe locations.
4. Maintain unobstructed access to fire extinguishers, and access routes. Prohibit smoking in hazardous fire-exposure areas.
5. Provide supervision of combustion-type temporary heating units and other sources of fire ignition.
C. Permanent Fire Protection: At the earliest possible date in each area of the Project, complete installation of the permanent fire protection facilities including connected services, and place into operation and use. Instruct key personnel in the use of the facilities.
D. Barricades, Warning Signs, and Lights: Comply with standards and code requirements for erecting structurally adequate barricades. Paint with appropriate colors, graphics, and warning signs to inform personnel and the public of the hazard involved. Where appropriate and needed, provide lighting, including flashing red or amber lights.
END OF SECTION 01 50 00
TEMPORARY FACILITIES and CONTROLS 01 50 00 - page 5 of 5