Flow_Diagram_and_Schedule_from_MON-18-100_Drawings-01JAN17.pdf

PDF 384 KB Posted

Attached to
Design Build Chiller Plant, Monroe Federal Courthouse
Solicitation number
47PH1119R0002
Issued by

About this file

Flow Diagram and Schedule

View the file

Other files

File Type Posted
Amendment_007_Form.pdf PDF
MON-16-Chiller-02FEB19_HVAC-Spec_update.pdf PDF
Equipment_Must_Have_Requirements_update.pdf PDF
Amendment_006_SF_30.pdf PDF
Amendment_005_SF_30.pdf PDF
Amendment_004_Form.pdf PDF
Proposal_Price_Breakout.docx DOCX document
RFIs_and_Answers.xlsx XLSX spreadsheet
Amendment_003_Form.pdf PDF
Sign_in_sheet_1.pdf PDF
Sign_in_Sheet_2.pdf PDF
Amendment_002.pdf PDF
MON-16-Chiller-02FEB19-HVAC_M1-M5.pdf PDF
MON-16-Chiller-02FEB19-HVAC_M11-M14.pdf PDF
MON-16-Chiller-02FEB19-HVAC_M6-M10.pdf PDF
MON-16-Chiller-02FEB19-HVAC-Spec.pdf PDF
47PH1119R0002__Form.pdf PDF
MON-18-Phasing-01JAN14-Drawings.pdf PDF
MON-16-Chiller-02FEB19-TableContents.pdf PDF
Construction_IEQ_Management_Plan.pdf PDF
Equipment_Must_Have_Requirements.pdf PDF
Div_23_GSA__Object_Point_Naming_and_Tagging_Standard.pdf PDF
Exhibit_A_-_GSA_R7_N4_Mechanical_Project_DDC_Controls_Requirements_vers_Monroe20181031.pdf PDF
DB_Agreement.pdf PDF
Wage_Rate_LA42_4_Solicitation_attachment_Jan_19.pdf PDF
Exhibit_B_-_Building_point_Histories_to_be_mapped_into_and_configured_for_Region_7_AMS.pdf PDF
Scope_of_Work_Design_Build__Monroe_Chiller_12-11-18.docx DOCX document
MON-16-Chiller-02FEB19-Elec-Spec.pdf PDF
MON-16-Chiller-02FEB19-Div-1.pdf PDF
MON-16-Chiller-02FEB19-Electrical.pdf PDF
47PH1119R0002_solicitation.pdf PDF
Exhibit_C_-_Graphic_Format_Bid_Document_20180125.pdf PDF
MON-16-Chiller-02FEB19-CoverSheet.pdf PDF
Exhibit_D-_Visio-RiserDiagramSample_31512.pdf PDF
Reps_and_Certs.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOUISIANAST

ATE OF

DAVID BONAVENTURE

License No. 31064

PROFESSIONAL

ENGINEER

NOTE: EVERY SHEETNOTE MAY NOT APPEAR ON THIS PAGE

SHEET NOTES

SENSITIVE BUT UNCLASSIFIED(SBU)

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Do not remove this notice

Properly destroy documents when no longer needed

GENERAL NOTES

LEGEND

R E

V

IS

IO

N

N O

T E

S G

R A

P H

IC

S

C A

L E

C O

N T

R A

C T

O R

S B

U

IL

D

IN

G P

R O

J E

C T

K E

Y M

A P

D R

A W

IN

G

CHECKED BY

DRAWN BY

FLOOR NO

DRAWING TITLE

DRAWING NO

SUB DATE:

SUBMISSION:

GSA PM:

PROJECT NO:

PROJECT

DESCRIPTION

PROJECT

TITLE

FACILITY CODE

OTHER

BUILDING NO

BUILDING NO

CITY/ST./ZIP

STREET

NAME

A/E CON. NO.

A/E TASK NO.

CONS. CONTR.

CONS. WORK

PRIME A/E

SUB A/E

CONSTR. CON.

SHEET SIZE:

DATE DRAFTED:

34 X 44

N/A

GENSLER

C E

R T

IF

IC

A T

IO

N

S

M04.100

GENERAL SERVICES

ADMINISTRATION

MECHANICAL SCHEDULES

U.S. COURTHOUSE, CSP & COURT

COMPONENTS B&C

100% CONSTRUCTION DOCUMENTS

10/27/2017

PMM

DAB

201 JACKSON STREET

MONROE, LOUISIANA 71201-7472

LA0029ZZ

SAJI ALUMMUTTIL

Air Terminal Schedule

TAG SERVICE DAMPER MATERIAL FINISH Manufacturer Model Comments

A Supply Air AT TAP STEEL BY ARCHITECT TITUS PAS PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING

B Return Air NONE STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING

C Exhaust Air AT TAP STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING

D Supply Air OPPOSED BLADE STEEL BY ARCHITECT Titus 300FL DOUBLE DEFLECTION, 3/4 INCH BLADE SPACING

G Supply Air OPPOSED BLADE STEEL BY ARCHITECT TITUS PAS PERFORATED FACE, 24"x24" OR 12"x12", SURFACE MOUNTED(3)

H Return Air OPPOSED BLADE STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", SURFACE MOUNTED(3)

J Supply Air FACE OPERATED STAINLESS STEEL MATCH CEILING Titus SG-SD MAXIMUM SECURITY, PERFORATED FACE, SUICIDE DETERENT (1)

L Exhaust Air FACE OPERATED STAINLESS STEEL MATCH CEILING Titus SG-PR MAXIMUM SECURITY, PERFORATED FACE, SUICIDE DETERENT (1)

M Supply Air AT TAP STEEL BY ARCHITECT Titus MP-38 LINEAR SLOT DIFFUSER, (3) 3/4" SLOT WITH 4'0" ACTIVE SECTION AND INSULATED PLENUM(2,4)

N Exhaust Air NONE ALUMINUM BY ARCHITECT GREENHECK ESD-635 HORIZONTAL 6" DEEP DRAINABLE HEAVY DUTY BLADES. WITH BIRDSCREEN. BLADES ARE 4" ON CENTER

FAN

MARK LOCATION CFM

MAXIMUM

RPM

EXT. STATIC

PRESSURE

(IN. W.C.)

HORSE

POWER

CURRENT

CHARAC.

LOCALLY

SWITCHED

BY

INTERLOCKED

WITH

FAN TYPE

BELT/DIRECT

DRIVE

MANUFACTURER MODEL NUMBER REMARKS

V PH F

EF-1 JURY DELIBERATION ROOF 875 1725 0.38 0.50 208 1 60 - RTU-3 ROOF MOUNTED DIRECT GREENHECK CUE 1,5

EF-2 ROOF, USMS AREA 0 1725 1.50 2.00 208 3 60 - RTU-1 ROOF MOUNTED DIRECT GREENHECK FJI 1,3,4,7

EF-3 RESTROOM 127 75 1725 0.38 0.25 115 1 60 - LIGHTS CEILING DIRECT GREENHECK SP 2

EF-4 CHILLER ROOM 500 1750 0.38 0.10 115 1 60 BMCS - INLINE DIRECT GREENHECK SQ 8

EF-5 CORRIDOR 1900 1725 1.00 0.75 208 1 60 - AHU-1 INLINE DIRECT GREENHECK SQ 6

EF-6 CHILLER ROOM 2260 1750 0.75 0.75 115 1 60 - PURGE SYSTEM INLINE DIRECT GREENHECK SQ 8

EF-7 BASEMENT RESTROOM 75 175.0 0.75 0.10 120 1 60 - LIGHTS CEILING DIRECT GREENHECK SP 2

GEF-1 SALLYPORT ROOF 950 1725 0.38 0.75 208 1 60 CO SENSOR - ROOF MOUNTED DIRECT GREENHECK CUE 1

GEF-2 JUDGES GARAGE, ROOF 1600 1725 0.38 0.50 208 1 60 CO SENSOR - ROOF MOUNTED DIRECT GREENHECK CUE 1

GEF-3 JUDGES GARAGE, ROOF 100 1725 0.10 0.50 115 1 60 - BMCS ROOF MOUNTED DIRECT GREENHECK CUE 1

GEF-4 SALLYPORT ROOF 100 1725 0.38 0.50 115 1 60 - BMCS ROOF MOUNTED DIRECT GREENHECK CUE 1GENERAL:

1. VERIFY ALL CEILING TYPES WITH MOUNTING FRAMES PRIOR TO ORDERING. ADJUST AIR TERMINAL TYPE IF REQUIRED TO MATCH CEILING TYPE.

AIR HANDLING UNIT

MARK

FAN COOLING HEATING

PIPE SIZE

TO COIL (IN.)

MCA MOCP REMARKS

SUPPLY

AIR CFM

OUTSIDE

AIR CFM

EXT. STATIC

PRESSURE

(IN. W.C)

HORSE

POWER

CURRENT

CHARAC.

AIR TEMPERATURE (°F) WATER ENTERING AIR

TEMPERATURE

(°F)

MINIMUM

CAPACITY

(BTUH)

WATER

CHILLED

WATER

HOT

WATER

V PH F

ENTERING

DRY BULB

ENTERING

WET BULB

LEAVING

DRY BULB

LEAVING

WET BULB

ENTERING

TEMP. (°F)

GPM

MAX. PRESSURE

DROP (ft hd.)

ENTERING

TEMP. (°F)

GPM

MAX. PRESSURE

DROP (ft hd.)

(e)AHU-2 5760 1830 1.20 7.50 208 3 60 82.2 68.3 62.0 50.4 44 39.6 10.0 63 °F 72000 140 °F 7.2 10 2 1/2" 1 1/2" 1,7,8

(e)AHU-3 7540 1930 1.20 7.50 208 3 60 82.6 68.6 62.0 50.0 44 43.9 10.0 63 °F 81300 140 °F 8.1 10 2 1/2" 1 1/2" 1,7,8

(e)AHU-4 19600 4360 1.25 15.00 208 3 60 82.0 68.2 62.0 50.4 44 103.0 10.0 63 °F 154400 140 °F 15.5 10 3" 1 1/2" 1,7,8

(e)AHU-5 6000 3200 1.50 5.00 208 3 60 87.5 71.4 60.0 58.0 44 53.6 10.0 45 °F 107000 140 °F 10.7 10 2 1/2" 1 1/2" 1,7,8

(e)AHU-8 1000 0 0.25 0.75 208 1 60 86.0 71.4 66.5 63.0 44 3.8 10.0 0 °F 0 140 °F 0.0 0 1" 0" 1,7,8

AHU-1 6150 3550 2.30 7.50 208 3 60 80.0 67.0 55.0 54.5 44 88.6 10.0 23 °F 125000 140 °F 12.3 10 3" 1 1/2" 35 A 60 A 3,4,6,9

AHU-6 3000 1000 1.25 3.00 208 3 60 82.0 68.0 57.5 56.7 44 20.5 10.0 60 °F 123600 140 °F 9.0 10 2" 1 1/4" 12 A 20 A 2,3,4,5,8,10

AHU-7 3000 1000 1.25 3.00 208 3 60 82.0 68.0 57.5 56.7 44 20.5 10.0 60 °F 123600 140 °F 9.0 10 2" 1 1/4" 12 A 20 A 2,3,4,5,8,10

REMARKS:

1. EXISTING UNITS, SCHEDULED PARAMETERS BASED ON EXISTING DRAWINGS

2. PROVIDE VERTICAL UNIT DRAW THROUGH UNIT..

3. PROVIDE VARIABLE AIR VOLUME UNIT.

4. PROVIDE INTEGRAL VARIABLE FREQUENCY DRIVE.

5. PROVIDE 2-WAY COOLING CONTROL VALVES.

6. PROVIDE 3-WAY COOLING CONTROL VALVES

7. REBALANCE UNIT TO SCHEDULED VALUES.

8. CONTROLS TO BE REPLACED

9. HEATING COIL IN IN THE PREHEAT POSITION. PROVODE 3-WAY CONTROL VALVES.

10. BASIS OF DESIGN KRUGER KBV. MAXIMUM FOOTPRINT WITH MIXING BOX SHALL BE 4'-0" X 5'-3". SEE SHEETS M02.302 AND M02.304 FOR FURTHER REQUIREMENTS.

GENERAL NOTES:

1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS

WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS.

INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH ELECTRICIAN.

2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL

CLEARANCE AS REQUIRED BY NEC.

3. COORDINATE WITH FIRE ALARM CONTRACTOR FOR REQUIRED FIRE/SMOKE DETECTORS

4. UNITS SHALL BE SHIPPED KNOCKED DOWN ENOUGH, SUITABLE TO ENTRY INTO THIER RESPECTIVE INSTALLATION LOCATION.

5. EXISTING UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND HEATING WATER ∆T OF 20°

6. NEW UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND A HEATING WATER ∆T OF 30°

7. AIR FILTERS ON NEW UNITS SHALL BE MERV-11

REMARKS:

1. PROVIDE WITH PRE-WIRED DISCONNECT, ROOF CURB

2. PROVIDE WITH PRE-WIRED DISCONNECT, AUTOMATIC BACKDRAFT DAMPER, DECORATIVE GRILLE

3. TOP OF DISCHARGE SHALL BE 10'-0" OR GREATER ABOVE ROOF

4. PROVIDE WITH HEPA FILTER RACK (ESP ALREADY ASSUMES 0.3" LOSE FOR FILTER AND 1.0" LOSE FOR DIRTY FILTER).

COORDINATE WITH MECHANICAL CONTRACTOR FOR INSTALLATION

5. PROVIDE WITH ECM MOTOR.

6. PROVIDE WITH PRE-WIRED DISCONNECT, MOUNTING KIT, AND BELT GUARD

7. ON A FAILURE OF EXHAUST FAN, INTERLOCK TO SHUT DOWN POWER TO RTU-1

8. PROVIDE WITH PRE-WIRED DISCONNECT, MOTOR COVER, VIBRATION ISOLATION (PER SPECIFICATIONS), THERMAL

OVERLOAD PROTECTION

GENERAL NOTES:

1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, AND DAMPERS WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING MUST

BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS.

COORDINATE WITH ELECTRICIAN.

2. MINIMUM RECOMMENDED CLEARANCE AROUND FANS ARE 12 INCHES ON NON-SERVICE SIDES AND 30 INCHES ON SERVICE SIDES. MAINTAIN MINUMUM CLEARANCE TO OPEN ACCESS AND CONTROL DOORS FOR SERVICE.. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.

3. FANS SHALL HAVE VIBRATION ISOLATION PER SPECIFICATIONS.

4. ALL FANS SHALL HAVE THERMAL OVERLOAD PROTECTION

5. ALL DIRECT DRIVES SHALL HAVE SPEED CONTOLLERS, UNLESS SPECIFIED AS ECM.

6. FANS LOCATED OUTSIDE SHALL HAVE BIRD/INSECT SCREENS

GENERAL NOTES:

1. MAXIMUM STATIC PRESSURE DROP OF AIR THROUGH THE TERMINAL BOX SHALL BE 0.2" ESP.

2. MAXIMUM VELOCITY THROUGH DUCT INLET SHALL BE 2,000 FPM.

3. MAXIMUM STATIC PRESSURE DROP THROUGH HEATER COIL SHALL BE 0.25" ESP.

4. MAXIMUM STATIC PRESSURE DROP OF WATER THROUGH HEATER COIL SHALL BE 10' W.G.

5. BTUH REQUIRED FOR HOT WATER HEATING IS HEATING GPM MULTIPLIED BY 15,000. ,HEATING WATER ∆T OF 30°

6. SUSPEND UNIT WITH FOUR THREADED HANGER RODS ATTACHED TO TWO UNISTRUT RUNNERS SECURED TO

STRUCTURE. PROVIDE SPRING ISOLATION. REFER TO MANUFACTURER FOR MORE DETAILS.

7. AVOID MOUNTING OVER LIGHTS WHEREVER POSSIBLE.

8. REFER TO PIPING AT HOT WATER COIL DETAILS. PROVIDE WITH 3-WAY CONTROL VALVE UNLESS OTHERWISE

SCHEDULED.

9. CVB MOTOR SIZE, BASED ON 0.35" ESP, AS FOLLOWS:

A. 0-400 CFM REQUIRE 1/10 HORSEPOWER MOTOR

B. 401-700 CFM REQUIRE A 1/4 HORSEPOWER MOTOR

C. 701-1100 CFM REQUIRE A 1/2 HORSEPOWER MOTOR

D. 1101-1500 CFM REQUIRE A 3/4 HORSEPOWER MOTOR

E. 1500 - GREATER CFM REQUIRE A 1 HORSEPOWER MOTOR

10. LEAVING AIR TEMPERATURE SHALL NOT EXCEED 20° ABOVE ROOM SETPOINT.

11. PROVIDE ECM MOTORS

REMARKS:

1. UNIT SHALL BE DESIGNED TO FIT IN NARROW CORRIDORS

CONSTANT VOLUME TERMINAL BOX

MARK

MAXIMUM

CFM

MINIMUM

CFM

INLET

DIAMETER

SIZE (IN.)

MOTOR

ELECTRICAL

REQUIREMENT

HOT WATER COIL

REMARKS

V PH F MAX GPM

CONNECTING

PIPE SIZE (IN.)

CVB-1 960 235 10 208 1 60 4.2 1" 1

CVB-2 1350 340 12 208 1 60 5.8 1 1/4" 1

CVB-3 1545 475 14 208 1 60 6.7 1 1/4" 1

CVB-4 945 235 10 208 1 60 4.0 1" 1

CVB-5 1350 340 12 208 1 60 5.8 1" 1

VARIABLE VOLUME TERMINAL BOX

MARK SUPPLY CFM

MINIMUM

CFM

INLET

DIAMETER

SIZE (IN.)

HOT WATER COIL

REMARKS

GPM

CONNECTING

PIPE SIZE

VAV-J-1 480 300 6 2 1"

VAV-J-2 1525 450 12 7 1 1/4"

REMARKS:

1. INSTALL IN CEILING PER MANUFACTURERS RECOMMENDATION. INSTALLATION SHALL MEET ALL USMS REQUIREMENTS

2. LINEAR DIFFUSERS LOCATED INSIDE COURTROOM SHALL HAVE 8" INLET WITH 10"Ø BRANCH DUCT. MAXIMUM NC/RC OF 20.

3. OPPOSED BLADE DAMPER SHALL BE ADJUSTABLE FROM THE FACE OF THE DIFFUSER BY OPENING THE BLANK OFF PLATE.

4. INSTALL TO PROVIDE A CONTINUOUS APPEARANCE, COORDINATE WITH ARCHITECTUAL DRAWINGS AND INSTALLATION REQUIREMENTS. WHERE ACTIVE PLENUMS ARE NOT INSTALLED, PROVIDE BLANK OFF PLATES. PROVIDE CORNER

SECTIONS, END BORDERS, AND ALIGNMENT PINS AS REQUIRED.

REMARKS:

1. PROVIDE WITH VARIABLE FREQUENCY DRIVE (VFD), AND VIBRATION SWITCH

2. PROVIDE ISOLATION VALVES ON EACH BASIN, 5KW BASIN HEATER FOR EACH CELL.

3. TWO CELLS WITH WEIR GATE CAPABLE OF ISOLATING EACH CELL AND BASIN

4. PROVIDE FACTORY MANUFACTURED AND MOUNTED MOTOR DAVIT

5. PROVIDE MECHANICAL PLATFORM AND LADDER WITH EXTENSION TO ROOF

6. PROVIDE AEGIS BRUSHLESS SHAFT GROUNDING KIT ON EACH MOTOR

COOLING TOWER

MARK

ENTERING WATER

TEMP.(°F)

LEAVING WATER

TEMP.(°F)

GPM

AMBIENT WET

BULB TEMP.

(°F)

FAN HP

FAN CURRENT

CHARACTERISTIC MANUFACTURER MODEL REMARKS

V PH F

CT-1 95.0 85 750.0 80 2 @ 10 208 3 60 EVAPCO USS-212-319 1,2,3,4,5,6

UNIT HEATER - ELECTRIC

TAG

MINIMUM

CAPACITY

(BTUH)

KW

NUMBER

OF

STAGES

CURRENT

CHARAC. CFM MANUFACTURER MODEL REMARKS

V P F

EUH-1 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2

EUH-2 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2

EUH-3 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2

EUH-4 7,667 2.25 1 208 2 60 300 REZNOR EGW 1,2

EUH-5 7,667 2.25 1 208 2 60 300 REZNOR EGW 1,2

EUH-6 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2

EUH-7 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2

REMARKS:

1. PROVIDE WITH PENDANT MOUNTED THERMOSTAT AND PRE-WIRED DISCONNECT SWITCH

2. PROVIDE WITH MOUTING KIT SUITABLE FOR INSTALLATION TYPE.

REMARKS:

1. PROVIDE WITH ECONOMIZER, VFD, ROOF CURB (SUITABLE FOR REPECTIVE ROOF TYPE), MERV 11 FILTERS.

2. PROVIDE WITH PREHEAT COIL (8.5 MBTUH, 6 GPM) AND REHEAT COIL (10.5 MBTUH, 7 GPM)

3. PROVIDE VARIABLE AIR VOLUME UNIT.

4. PROVIDE HEATED PIPING COMPARTMENT, AND CONVENIENCE 115V GFI.

5. PROVIDE WITH SINGLE POINT POWER CONNECTION.

6. PROVIDE WITH PREHEAT COIL (3.5 MBTUH, 3 GPM) AND REHEAT COI. (4.4 MBTUH, 3 GPM)

7. PROVIDE WITH PREHEAT COIL FOR VALUES SCHEDULED

GENERAL NOTES:

1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS WHERE

APPLICABLE. DIRTY FILTER AND UNIT CASING MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH ELECTRICIAN.

2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS

REQUIRED BY NEC.

3. COORDINATE WITH FIRE ALARM CONTRACTOR FOR REQUIRED FIRE/SMOKE DETECTORS

4. ROOF TOP UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND A HEATING WATER ∆T OF 30°

5. PROVIDE 20WAY CONTROL VALVES FOR CHILLED WATER COIL, 3-WAY VALVES FOR HEATING WATER COILS

ROOF TOP UNIT

MARK

FAN

COOLING

HEATING

PIPE SIZE

TO COIL (IN.)

REMARKS

SUPPLY

AIR CFM

OUTSIDE

AIR CFM

EXT. STATIC

PRESSURE

(IN. W.C)

HORSE

POWER

CURRENT

CHARAC. AIR TEMPERATURE (°F)

WATER

ENTERING AIR

TEMPERATURE

(°F)

MIN.

HEATING

CAPACITY

WATER

CHILLED

WATER

HOT

WATER

V PH F

ENTERING

DRY BULB

ENTERING

WET BULB

LEAVING

DRY BULB

LEAVING

WET BULB

ENTERING

TEMP (°F)

GPM

MAX.

PRESSURE

DROP (IN.)

ENTERING

TEMP. (°F)

GPM

MAX.

PRESSURE

DROP (IN.)

RTU-1 2,005 650 1.50 3.0 208 3 60 78.2 65.2 53.0 52.5 44 15.1 120.0 24.2 68,000 140.0 6.0 120 2" 1" 1,3,4,5,7

RTU-2 2,385 2,385 0.75 3.0 208 3 60 97.0 78.4 53.0 52.5 44 43.0 120.0 22.9 184,500 140.0 12.3 120 2 1/2" 1 1/2" 1,2,3,4,5

RTU-3 1,005 1,005 0.50 1.5 208 3 60 97.0 78.4 53.0 52.5 44 18.1 120.0 22.9 90,000 140.0 6.5 120 1 1/2" 1 1/4" 1,3,4,5,6

PUMP

MARK SERVICE TYPE GPM

HEAD

(FT.)

MOTOR

HORSE POWER

Max.

RPM

CURRENT

MANUFACTURER MODEL NUMBER REMARKS

V PH F

CHWP-1 CHILLED WATER INLINE 300 87.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7

CHWP-2 CHILLED WATER INLINE 300 87.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7

CWP-1 CONDENSER WATER INLINE 375 71.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7

CWP-2 CONDENSER WATER INLINE 375 71.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7

GENERAL NOTES:

1. PUMP IS TO HAVE A NON-OVERLOADING MOTOR.

2. MINIMUM RECOMMENDED CLEARANCE AROUND A PUMP IS 24 INCHES. MAINTAIN

MINIMUM CLEARANCES AS REQUIRED FOR SERVICE, MAINTENANCE, AND INSPECTION.

REMARKS:

1. TEFC, PREMIUM EFFICIENCY MOTOR. PROVIDE AEGIS BRUSHLESS SHAFT GROUNDING KIT

2. COUPLING, RIGID SPACER TYPE OF HIGH TENSILE ALUMINUM ALLOY. COUPLING TO BE DESIGNED

TO BE EASILY REMOVED ON SITE TO REVEAL A SPACE BETWEEN THE PUMP AND MOTOR SHAFTS

SUFFICIENT TO REMOVE ALL MECHANICAL SEAL COMPONENTS FOR SERVICING AND TO BE

REPLACED WITHOUT DISTURBING THE MOTOR OR PUMP.

3. MECHANICAL SEALS SHALL BE STAINLESS STEEL MUTLI-SPRING OUTSIDE BALANCED TYPE WITH

VITON SECONDARY SEAL, CARBON ROTATING FACE AND SILICON CARBIDE STATIONARY SEAT.

4. VFD PROVIDED BY PUMP MANUFACTURER AND UNIT MOUNTED

5. PROVIDE ONE EXTRA SET OF SEALS AND TURN OVER TO OWNER

6. PUMP SPEED CONTROL BY REMOTE BAS SIGNAL, FROM PRESSURE DIFFERENTIAL SENSOR.

7. COOLING MEDIUM: WATER

WATER COOLED CHILLER

MARK TYPE

ACTUAL

CAPACITY

(TONS)

EVAPORATOR (FF=0.0001) CONDENSER (FF=0.00025)

CURRENT

CHARAC. MINIMUM

KW/TON

MINIMUM

NPLV

MANUFACTURER MODEL NUMBER MCA MOCP REMARKS

LEAVING WATER

TEMP.(°F)

GPM

PRESSURE

DROP (FT)

ENTERING

WATER TEMP.(°F)

GPM

PRESSURE

DROP (FT)

V PH F

CH-1 CENTRIFUGAL 125 44 300 10.00 85 375 10.00 480 3 60 0.5862 0.3587 SMARDT WB044 119 A 172 A 1,2,3,4,5,6

CH-2 CENTRIFUGAL 125 44 300 10.00 85 375 10.00 480 3 60 0.5862 0.3587 SMARDT WB044 119 A 172 A 1,2,3,4,5,6

REMARKS:

1. CHILLER SHALL MEET OR EXCEED BOTH ABOVE SCHEDULED FULL-LOAD AND PART-LOAD MINIMUM ASHRAE 90.1 EFFICIENCIES AT ARI 44 LEAVING CHILLED WATER

TEMPERATURE AND 85 ENTERING CONDENSER WATER TEMPERATURE.

2. CHILLERS SHALL MEET OR EXCEED CAPACITY AT SCHEDULED WATER TEMPERATURES.

3. PROVIDE WITH INTEGRAL VARIABLE FREQUENCY DRIVE, PRE-PIPED AND PRE-WIRED CONTROLS. MAXIMUM FOOTPRINT SHALL BE LESS THAN 4'-6" X 12'-6"

4. PROVIDE UNIT KNOCKED DOWN IN SECTION TO BE FIELD REASSEMBLED AS REQUIRED FOR SITE INSTALLATION.

5. PROVIDE FACTORY FURNISHED VIBRATION ISOLATORS, AUXILLARY MOTORS FOR OIL, PURGE, ETC...

6. MAGNETIC BEARING

GRILLE SIZING SCHEDULE

STANDARD GRILLE

REGISTER OR NONSTANDARD GRILLE

DESIGNATES GRILLE NECK SIZE

SIZE OF GRILLE NECK

TO TRAVERSE GRILLE

AIR QUANTITY IN CFM

TO TRAVERSE GRILLE

(REFERENCE TABLE BELOW)

AIR QUANTITY IN CFM

SQUARE

GRILLE NECK SIZE

6" x 6"

8" x 8"

9" x 9"

10" x 10"

14" x 14"

12" x 12"

GRILLE SIZE

DESIGNATION

(REFERENCE GRILLE SCHEDULE)

ALL REGISTERS SHALL HAVE A 45° HORIZONTAL DEFLECTION UNLESS OTHERWISE SHOWN.

CONNECTING GRILLE TO DUCTWORK

CONNECTING GRILLE TO DUCTWORK

(REFERENCE GRILLE SCHEDULE)

DESIGNATES GRILLE TYPE

ALL GRILLES SHOWN SHALL BE FOUR-WAY THROW UNLESS OTHERWISE SHOWN.

ALL GRILLES SHOWN SHALL BE FOUR-WAY THROW UNLESS OTHERWISE SHOWN.

SIZE OF FLEX OR RIGID DUCT

DESIGNATES GRILLE TYPE

SIZE OF FLEX OR RIGID DUCT

A

12"x10" 12/10

A1

6"Ø

6"Ø

ROUND

8"Ø

10"Ø

12"Ø

SQUARE

GRILLE NECK SIZE

15" x 15"

16" x 16"

18" x 18"

20" x 20"

24" x 24"

22" x 22"

GRILLE SIZE

DESIGNATION

14"Ø

ROUND

REMARKS

MODEL

NUMBER

MANUFACTURERDUTYACTUATOR BLADE ACTIONMARK

NOTES:

N/A - NOT APPLICABLE

DAMPER

D-3 MOTORIZED OVER 9" WIDE OPPOSED RUSKIN CD-60 LOW LEAKAGE DAMPER WITH BLADE SEALS

D-2 MANUAL BALANCING OVER 9" WIDE OPPOSED RUSKIN MD-35 MANUAL DAMPER WITH STANDARD CONSTRUCTION

FEATURES AND VENTLOCK #639 LOCKING REGULATOR.

D-1 MANUAL BALANCING UNDER 9" WIDE N/A N/A N/A SEE SMACNA CONSTRUCTION DETAILS REFERENCED "TYPICAL

CONSTRUCTION DETAILS FOR LOW VELOCITY DUCTS."

COOLING TOWER BASIN SWEEPER

TAG GPM Horsepower ELECTRICAL MODEL SEPERATOR Manufacturer REMARKS

CTBC-1 110 3 208/3/60 eTCX-0110-SRV eHTX-0060 LAKOS 1,2

REMARKS:

1. COORDINATE WEIGHT AND DIMENSIONS WITH STRUCTURE.

2. COORDINATE SIZE OF CTBC-1 WITH SIZE OF RESPECTIVE COOLING TOWER.

GENERAL NOTES:

1. MAXIMUM STATIC PRESSURE DROP OF AIR THROUGH THE TERMINAL BOX SHALL BE 0.2" ESP.

2. MAXIMUM VELOCITY THROUGH DUCT INLET SHALL BE 2,000 FPM.

3. MAXIMUM STATIC PRESSURE DROP THROUGH HEATER COIL SHALL BE 0.25" ESP.

4. MAXIMUM STATIC PRESSURE DROP OF WATER THROUGH HEATER COIL SHALL BE 10' W.G.

5. BTUH REQUIRED FOR HOT WATER HEATING IS HEATING GPM MULTIPLIED BY 15,000. ,HEATING WATER ∆T OF 30°

6. SUSPEND UNIT WITH FOUR THREADED HANGER RODS ATTACHED TO TWO UNISTRUT RUNNERS SECURED TO

STRUCTURE. PROVIDE SPRING ISOLATION. REFER TO MANUFACTURER FOR MORE DETAILS.

7. AVOID MOUNTING OVER LIGHTS WHEREVER POSSIBLE.

8. REFER TO PIPING AT HOT WATER COIL DETAILS. PROVIDE WITH 3-WAY CONTROL VALVE UNLESS OTHERWISE

SCHEDULED.

10. LEAVING AIR TEMPERATURE SHALL NOT EXCEED 20° ABOVE ROOM SETPOINT.

REMARKS:

AIR COOLED CONDENSING UNIT

MARK

MIN. TOTAL

CAPACITY

(BTUH)

OUTDOOR

AIR

TEMP (°F)

MINIMUM

EER/

SEER

CURRENT

CHARAC.

RELATED

UNIT

MARK

REMARKS

V PH F

ACC-1 12,000 95 13 208 1 60 DMS-1 1

ACC-2 12,000 95 13 208 1 60 DMS-2 1

DUCTLESS MINI SPLIT DX UNIT

MARK

FAN COOLING

REMARKSSUPPLY

AIR CFM

OUTSIDE

AIR CFM

EXT.STATIC

PRESSURE

(IN. W.C.)

HORSE

POWER

CURRENT

CHARAC.

AIR TEMPERATURE (°F)

MIN. TOTAL

CAPACITY (BTUH)

MIN. SENS.

CAPACITY (BTUH)

MINIMUM

EER/

SEER

NUMBER

OF

STAGESV PH F

ENTERING

DRY BULB

ENTERING

WET BULB

DMS-1 340 0 0.00 0.0 120 1 60 82.0 68.0 11,968 8,813 -/13.0 1 1,2,3,4,5

DMS-2 340 0 0.00 0.0 120 1 60 82.0 68.0 11,968 8,813 -/13.0 1 1,2,3,4,5

GENERAL NOTES:

1. MINIMUM RECOMMENDED CLEARANCE AROUND ROOFTOP UNIT IS 12 INCHES ON NON-SERVICE SIDES AND 30 INCHES

ON SERVICE SIDES. MAINTAIN MINIMUM CLEARANCE FOR CONDENSER AIR FLOW AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.

REMARKS:

1. PROVIDE WITH HAIL GUARDS, LOW AMBIENT KIT, PROVISIONS FOR LONG REFRIGERANT LINES

REMARKS:

1. CONTROLLED BY PROGRAMMABLE WIRED THERMOST.

2. REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S REQUIREMENTS.

3. UNIT INSTALLATION PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

4. PROVIDE WITH CONDENSATE PUMP POWERED VIA RESPECTIVE UNIT.

5. POWER PROVIDED VIA RESPECTIVE CONDENSING UNIT

GENERAL NOTES:

1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING

MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH

ELECTRICIAN.

2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.

CONTROLS CONTRACTOR SHALL REPLACE AND UPGRADE THE ENTIRE

EXISTING CONTROL SYSTEM FOR ALL EQUIPMENT BOTH SHOWN AND NOT

SHOWN IN THE CONTRACT DOCUMENTS TO INTERFACE WITH THE NEW

CONTROL SYSTEM. COORDINATE WITH ARCHITECT WHERE PARTS OF

WALLS OR CEILINGS MAY NEED TO BE REMOVED. REPAIRS SHALL MATCH

EXISTING FINISHES

Delta Issue Date Description

ChelseyMClick Polygon

ChelseyMClick Cross-Out

ChelseyMClick Text Box Not needed

ChelseyMClick Callout Future Project

ChelseyMClick Polygon

ChelseyMClick Text Box Future Project

ChelseyMClick Cross-Out

FM

SCALE: NONE

SCALE: NONE

R

R

2" QUICK

FILL

BUILDING HVAC SYSTEM BUILDING PLUMBING SYSTEM

1/2"

N.O.

N.C.

N.O.

BUILDING PLUMBING SYSTEM BUILDING HVAC SYSTEM

1/2"

N.O. N.O.

N.C.

1-1/2" QUICK

FILL

1-1/4"

3/4"

2" MAKEUP

WATER

2" MAKEUP

WATER

2" MAKEUP

WATER

2" MAKEUP

WATER

2"

2"

5" CWR

MECHANICAL KEYED NOTES:

PROVIDE ERNST GAUGE #E-57-3 BRONZE BODY SIGHT

GLASS WITH S.S. SHAFT, PLASTIC SPINNER AND DOUBLE

WINDOW. OPERATING TEMPERATURE AND PRESSURE

SHALL BE 125 PSI, 200F. MINIMUM.

CENTER GUIDED NON-SLAM CHECK VALVE (TYP ALL)

PROVIDE BALL VALVE WITH HOSE THREAD ADAPTER.

ENSURE VALVES ARE INSTALLED IN AN ACCESSIBLE SPACE

PROVIDE CHAIN OPERATORS AS REQUIRED. (TYPICAL ALL)

NOT USED8

1" STUBS BY MECH CONTRACTOR, INJECTOR ASSEMBLY

IN MECH ROOM BY FEEDER VENDOR. MECH

CONTRACTOR SHALL MAKE CONNECTIONS TO THE

TREATMENT SYSTEM. PIPING TO COOLING TOWER WATER MAKE-UP SYSTEM

11 PIPING TO CHILLED WATER MAKE-UP SYSTEM.

NOT USED9

REFER TO PLUMBING DRAWING FOR PIPING SIZES.

VARIABLE FREQUENCY DRIVE (VFD) (TYPICAL ALL)

COOLING TOWER CHEM

FEED SYSTEM IN MECH

ROOM

3" DRAIN

(TYPICAL)

3" OVERFLOW

(TYPICAL)

BASIN WATER LEVEL

CONTROLLER (TYPICAL)

MAKE UP WATER

FLOW METER

CTBC-1

COOLING TOWER

CLEANING SYSTEM

CT-1

COOLING TOWER

EQUAL FLOW TO EACH CELL

375 GPM

AUTO-FLOW

DEVICE

AHU-1

(e)AHU-4

(e)AHU-5

(e)AHU-2 (e)AHU-3

(e)AHU-8

AHU-6 AHU-7

DIFFERENTIAL

PRESSURE

SENSOR

M

AS-1

AIR SEPARATOR WITHOUT

STRAINER

BELL & GOSSETT #107A

AUTOMATIC AIR VENT

6ET-1

EXPANSION

TANK

4" THICK

HOUSEKEEPING

MODULATING CONTROL VALVE

4" CHWR

C W

S

C W

R

4" CHWS

C W

S

5" CWS

4" CHWR

4" CHWS

4" CHWR

6" CHWR

4" CHWR

3" CHWR

4" CHWS

3" CHWS

C H

W S

6" CHWS

TURBINE

FLOW METER

6"6"

WEIR

GATE

BACK FLOW

PREVENTER

BACK FLOW

PREVENTER

N.O.

BMCS

BMCS

TO CHILLER

OUTLET/INLET

CWS&R AND

CHWS&R PIPING

PRESSURE

GAUGE

MOUNT AT 5'-0"

AFF RE:9/M4.1

3/4"

N.C.

G.C.

TO BMCS

CHILLER CH-2

CHILLER CH-1

6" THICK HOUSEKEEPING

(TYP)

CWP-2

CWP-1

3/4"

CHWP-1

CHWP-2

1-1/2"

CHEMICAL

FEEDER

3/4"

N.C.

N.O.N.O.

3/4"

N.C.

N.O.

N.O.

FLANGE

C H

W R

6" CHWR

4" CHWR

4" CHWS

PIPING AT AHU CHILLED WATER COIL

38 3

COIL

FLOW

AIR

PIPE STRAINER

DIRT LEG

1/2" BALL VALVE WITH HOSE THREAD

ADAPTER, CAP AND CHAIN.

UNION (2" & SMALLER ONLY, FLANGE

CONNECTION FOR LARGER PIPES)

TEMPERATURE/PRESSURE

TEST STATION.

CONTROL VALVE

REMOVING BALANCING VALVE AND

PIPING. CAP OPEN PIPES AS SHOWN

SHUT OFF VALVE

TYPICAL

TYPICAL

TYPICAL PIPING AT

INLET AND OUTLET OF CHILLER

RTU-1 RTU-2

C W

S

C W

S

6" CWS

6" CWR

C

W R

C W

S

300 GPM

AUTO-FLOW

DEVICE (TYPICAL)

300 GPM

AUTO-FLOW

DEVICE (TYPICAL)

375 GPM

AUTO-FLOW

DEVICE

CAP PORT ON EXISTING 3-WAY CONTROL VALVE TO

CONVERT TO 2-WAY CONTROL VALVE.

6" CHWR

6" CHWS

CHILLED WATER: 3.8 GPM

HEATING WATER: 0 GPM

CHILLED WATER: 53.6 GPM

HEATING WATER: 10.7 GPM

CHILLED WATER: 20.5 GPM

HEATING WATER: 9 GPM

CHILLED WATER: 20.5 GPM

HEATING WATER: 9 GPM

CHILLED WATER: 103 GPM

HEATING WATER: 16.5 GPM

CHILLED WATER: 39.6 GPM

HEATING WATER: 7.2 GPM

CHILLED WATER: 43.9 GPM

HEATING WATER: 8.1 GPM

CHILLED WATER: 88.6 GPM

HEATING WATER: 12.3 GPM

CHILLED WATER: 43.0 GPM

HEATING WATER: 12.3 GPM

CHILLED WATER: 15.1 GPM

HEATING WATER: 6.0 GPM

CHILLED WATER MAXIMUM FLOWRATE: 460 GPM

CHILLERS SIZED TO HANDLE 67% OF MAX FLOW

FLOWRATE THROUGH CHILLERS 288 GPM

RTU-3

CHILLED WATER: 18.1 GPM

HEATING WATER: 6.5 GPM

LOUISIANAST

ATE OF

DAVID BONAVENTURE

License No. 31064

PROFESSIONAL

ENGINEER

NOTE: EVERY SHEETNOTE MAY NOT APPEAR ON THIS PAGE

SHEET NOTES

SENSITIVE BUT UNCLASSIFIED(SBU)

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Do not remove this notice

Properly destroy documents when no longer needed

GENERAL NOTES

LEGEND

R E

V

IS

IO

N

N O

T E

S G

R A

P H

IC

S

C A

L E

C O

N T

R A

C T

O R

S B

U

IL

D

IN

G P

R O

J E

C T

K E

Y M

A P

D R

A W

IN

G

CHECKED BY

DRAWN BY

FLOOR NO

DRAWING TITLE

DRAWING NO

SUB DATE:

SUBMISSION:

GSA PM:

PROJECT NO:

PROJECT

DESCRIPTION

PROJECT

TITLE

FACILITY CODE

OTHER

BUILDING NO

BUILDING NO

CITY/ST./ZIP

STREET

NAME

A/E CON. NO.

A/E TASK NO.

CONS. CONTR.

CONS. WORK

PRIME A/E

SUB A/E

CONSTR. CON.

SHEET SIZE:

DATE DRAFTED:

34 X 44

N/A

GENSLER

C E

R T

IF

IC

A T

IO

N

S

12" = 1'-0"

M05.100

GENERAL SERVICES

ADMINISTRATION

MECHANICAL SCHEMATICS 1

U.S. COURTHOUSE, CSP & COURT

COMPONENTS B&C

100% CONSTRUCTION DOCUMENTS

10/27/2017

PMM

DAB

201 JACKSON STREET

MONROE, LOUISIANA 71201-7472

LA0029ZZ

SAJI ALUMMUTTIL

Delta Issue Date Description

ChelseyMClick Polygon