LOUISIANAST
ATE OF
DAVID BONAVENTURE
License No. 31064
PROFESSIONAL
ENGINEER
NOTE: EVERY SHEETNOTE MAY NOT APPEAR ON THIS PAGE
SHEET NOTES
SENSITIVE BUT UNCLASSIFIED(SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice
Properly destroy documents when no longer needed
GENERAL NOTES
LEGEND
R E
V
IS
IO
N
N O
T E
S G
R A
P H
IC
S
C A
L E
C O
N T
R A
C T
O R
S B
U
IL
D
IN
G P
R O
J E
C T
K E
Y M
A P
D R
A W
IN
G
CHECKED BY
DRAWN BY
FLOOR NO
DRAWING TITLE
DRAWING NO
SUB DATE:
SUBMISSION:
GSA PM:
PROJECT NO:
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NO
BUILDING NO
CITY/ST./ZIP
STREET
NAME
A/E CON. NO.
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
SHEET SIZE:
DATE DRAFTED:
34 X 44
N/A
GENSLER
C E
R T
IF
IC
A T
IO
N
S
M04.100
GENERAL SERVICES
ADMINISTRATION
MECHANICAL SCHEDULES
U.S. COURTHOUSE, CSP & COURT
COMPONENTS B&C
100% CONSTRUCTION DOCUMENTS
10/27/2017
PMM
DAB
201 JACKSON STREET
MONROE, LOUISIANA 71201-7472
LA0029ZZ
SAJI ALUMMUTTIL
Air Terminal Schedule
TAG SERVICE DAMPER MATERIAL FINISH Manufacturer Model Comments
A Supply Air AT TAP STEEL BY ARCHITECT TITUS PAS PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING
B Return Air NONE STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING
C Exhaust Air AT TAP STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", LAY-IN CEILING
D Supply Air OPPOSED BLADE STEEL BY ARCHITECT Titus 300FL DOUBLE DEFLECTION, 3/4 INCH BLADE SPACING
G Supply Air OPPOSED BLADE STEEL BY ARCHITECT TITUS PAS PERFORATED FACE, 24"x24" OR 12"x12", SURFACE MOUNTED(3)
H Return Air OPPOSED BLADE STEEL BY ARCHITECT TITUS PAR PERFORATED FACE, 24"x24" OR 12"x12", SURFACE MOUNTED(3)
J Supply Air FACE OPERATED STAINLESS STEEL MATCH CEILING Titus SG-SD MAXIMUM SECURITY, PERFORATED FACE, SUICIDE DETERENT (1)
L Exhaust Air FACE OPERATED STAINLESS STEEL MATCH CEILING Titus SG-PR MAXIMUM SECURITY, PERFORATED FACE, SUICIDE DETERENT (1)
M Supply Air AT TAP STEEL BY ARCHITECT Titus MP-38 LINEAR SLOT DIFFUSER, (3) 3/4" SLOT WITH 4'0" ACTIVE SECTION AND INSULATED PLENUM(2,4)
N Exhaust Air NONE ALUMINUM BY ARCHITECT GREENHECK ESD-635 HORIZONTAL 6" DEEP DRAINABLE HEAVY DUTY BLADES. WITH BIRDSCREEN. BLADES ARE 4" ON CENTER
FAN
MARK LOCATION CFM
MAXIMUM
RPM
EXT. STATIC
PRESSURE
(IN. W.C.)
HORSE
POWER
CURRENT
CHARAC.
LOCALLY
SWITCHED
BY
INTERLOCKED
WITH
FAN TYPE
BELT/DIRECT
DRIVE
MANUFACTURER MODEL NUMBER REMARKS
V PH F
EF-1 JURY DELIBERATION ROOF 875 1725 0.38 0.50 208 1 60 - RTU-3 ROOF MOUNTED DIRECT GREENHECK CUE 1,5
EF-2 ROOF, USMS AREA 0 1725 1.50 2.00 208 3 60 - RTU-1 ROOF MOUNTED DIRECT GREENHECK FJI 1,3,4,7
EF-3 RESTROOM 127 75 1725 0.38 0.25 115 1 60 - LIGHTS CEILING DIRECT GREENHECK SP 2
EF-4 CHILLER ROOM 500 1750 0.38 0.10 115 1 60 BMCS - INLINE DIRECT GREENHECK SQ 8
EF-5 CORRIDOR 1900 1725 1.00 0.75 208 1 60 - AHU-1 INLINE DIRECT GREENHECK SQ 6
EF-6 CHILLER ROOM 2260 1750 0.75 0.75 115 1 60 - PURGE SYSTEM INLINE DIRECT GREENHECK SQ 8
EF-7 BASEMENT RESTROOM 75 175.0 0.75 0.10 120 1 60 - LIGHTS CEILING DIRECT GREENHECK SP 2
GEF-1 SALLYPORT ROOF 950 1725 0.38 0.75 208 1 60 CO SENSOR - ROOF MOUNTED DIRECT GREENHECK CUE 1
GEF-2 JUDGES GARAGE, ROOF 1600 1725 0.38 0.50 208 1 60 CO SENSOR - ROOF MOUNTED DIRECT GREENHECK CUE 1
GEF-3 JUDGES GARAGE, ROOF 100 1725 0.10 0.50 115 1 60 - BMCS ROOF MOUNTED DIRECT GREENHECK CUE 1
GEF-4 SALLYPORT ROOF 100 1725 0.38 0.50 115 1 60 - BMCS ROOF MOUNTED DIRECT GREENHECK CUE 1GENERAL:
1. VERIFY ALL CEILING TYPES WITH MOUNTING FRAMES PRIOR TO ORDERING. ADJUST AIR TERMINAL TYPE IF REQUIRED TO MATCH CEILING TYPE.
AIR HANDLING UNIT
MARK
FAN COOLING HEATING
PIPE SIZE
TO COIL (IN.)
MCA MOCP REMARKS
SUPPLY
AIR CFM
OUTSIDE
AIR CFM
EXT. STATIC
PRESSURE
(IN. W.C)
HORSE
POWER
CURRENT
CHARAC.
AIR TEMPERATURE (°F) WATER ENTERING AIR
TEMPERATURE
(°F)
MINIMUM
CAPACITY
(BTUH)
WATER
CHILLED
WATER
HOT
WATER
V PH F
ENTERING
DRY BULB
ENTERING
WET BULB
LEAVING
DRY BULB
LEAVING
WET BULB
ENTERING
TEMP. (°F)
GPM
MAX. PRESSURE
DROP (ft hd.)
ENTERING
TEMP. (°F)
GPM
MAX. PRESSURE
DROP (ft hd.)
(e)AHU-2 5760 1830 1.20 7.50 208 3 60 82.2 68.3 62.0 50.4 44 39.6 10.0 63 °F 72000 140 °F 7.2 10 2 1/2" 1 1/2" 1,7,8
(e)AHU-3 7540 1930 1.20 7.50 208 3 60 82.6 68.6 62.0 50.0 44 43.9 10.0 63 °F 81300 140 °F 8.1 10 2 1/2" 1 1/2" 1,7,8
(e)AHU-4 19600 4360 1.25 15.00 208 3 60 82.0 68.2 62.0 50.4 44 103.0 10.0 63 °F 154400 140 °F 15.5 10 3" 1 1/2" 1,7,8
(e)AHU-5 6000 3200 1.50 5.00 208 3 60 87.5 71.4 60.0 58.0 44 53.6 10.0 45 °F 107000 140 °F 10.7 10 2 1/2" 1 1/2" 1,7,8
(e)AHU-8 1000 0 0.25 0.75 208 1 60 86.0 71.4 66.5 63.0 44 3.8 10.0 0 °F 0 140 °F 0.0 0 1" 0" 1,7,8
AHU-1 6150 3550 2.30 7.50 208 3 60 80.0 67.0 55.0 54.5 44 88.6 10.0 23 °F 125000 140 °F 12.3 10 3" 1 1/2" 35 A 60 A 3,4,6,9
AHU-6 3000 1000 1.25 3.00 208 3 60 82.0 68.0 57.5 56.7 44 20.5 10.0 60 °F 123600 140 °F 9.0 10 2" 1 1/4" 12 A 20 A 2,3,4,5,8,10
AHU-7 3000 1000 1.25 3.00 208 3 60 82.0 68.0 57.5 56.7 44 20.5 10.0 60 °F 123600 140 °F 9.0 10 2" 1 1/4" 12 A 20 A 2,3,4,5,8,10
REMARKS:
1. EXISTING UNITS, SCHEDULED PARAMETERS BASED ON EXISTING DRAWINGS
2. PROVIDE VERTICAL UNIT DRAW THROUGH UNIT..
3. PROVIDE VARIABLE AIR VOLUME UNIT.
4. PROVIDE INTEGRAL VARIABLE FREQUENCY DRIVE.
5. PROVIDE 2-WAY COOLING CONTROL VALVES.
6. PROVIDE 3-WAY COOLING CONTROL VALVES
7. REBALANCE UNIT TO SCHEDULED VALUES.
8. CONTROLS TO BE REPLACED
9. HEATING COIL IN IN THE PREHEAT POSITION. PROVODE 3-WAY CONTROL VALVES.
10. BASIS OF DESIGN KRUGER KBV. MAXIMUM FOOTPRINT WITH MIXING BOX SHALL BE 4'-0" X 5'-3". SEE SHEETS M02.302 AND M02.304 FOR FURTHER REQUIREMENTS.
GENERAL NOTES:
1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS
WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS.
INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH ELECTRICIAN.
2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL
CLEARANCE AS REQUIRED BY NEC.
3. COORDINATE WITH FIRE ALARM CONTRACTOR FOR REQUIRED FIRE/SMOKE DETECTORS
4. UNITS SHALL BE SHIPPED KNOCKED DOWN ENOUGH, SUITABLE TO ENTRY INTO THIER RESPECTIVE INSTALLATION LOCATION.
5. EXISTING UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND HEATING WATER ∆T OF 20°
6. NEW UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND A HEATING WATER ∆T OF 30°
7. AIR FILTERS ON NEW UNITS SHALL BE MERV-11
REMARKS:
1. PROVIDE WITH PRE-WIRED DISCONNECT, ROOF CURB
2. PROVIDE WITH PRE-WIRED DISCONNECT, AUTOMATIC BACKDRAFT DAMPER, DECORATIVE GRILLE
3. TOP OF DISCHARGE SHALL BE 10'-0" OR GREATER ABOVE ROOF
4. PROVIDE WITH HEPA FILTER RACK (ESP ALREADY ASSUMES 0.3" LOSE FOR FILTER AND 1.0" LOSE FOR DIRTY FILTER).
COORDINATE WITH MECHANICAL CONTRACTOR FOR INSTALLATION
5. PROVIDE WITH ECM MOTOR.
6. PROVIDE WITH PRE-WIRED DISCONNECT, MOUNTING KIT, AND BELT GUARD
7. ON A FAILURE OF EXHAUST FAN, INTERLOCK TO SHUT DOWN POWER TO RTU-1
8. PROVIDE WITH PRE-WIRED DISCONNECT, MOTOR COVER, VIBRATION ISOLATION (PER SPECIFICATIONS), THERMAL
OVERLOAD PROTECTION
GENERAL NOTES:
1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, AND DAMPERS WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING MUST
BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS.
COORDINATE WITH ELECTRICIAN.
2. MINIMUM RECOMMENDED CLEARANCE AROUND FANS ARE 12 INCHES ON NON-SERVICE SIDES AND 30 INCHES ON SERVICE SIDES. MAINTAIN MINUMUM CLEARANCE TO OPEN ACCESS AND CONTROL DOORS FOR SERVICE.. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.
3. FANS SHALL HAVE VIBRATION ISOLATION PER SPECIFICATIONS.
4. ALL FANS SHALL HAVE THERMAL OVERLOAD PROTECTION
5. ALL DIRECT DRIVES SHALL HAVE SPEED CONTOLLERS, UNLESS SPECIFIED AS ECM.
6. FANS LOCATED OUTSIDE SHALL HAVE BIRD/INSECT SCREENS
GENERAL NOTES:
1. MAXIMUM STATIC PRESSURE DROP OF AIR THROUGH THE TERMINAL BOX SHALL BE 0.2" ESP.
2. MAXIMUM VELOCITY THROUGH DUCT INLET SHALL BE 2,000 FPM.
3. MAXIMUM STATIC PRESSURE DROP THROUGH HEATER COIL SHALL BE 0.25" ESP.
4. MAXIMUM STATIC PRESSURE DROP OF WATER THROUGH HEATER COIL SHALL BE 10' W.G.
5. BTUH REQUIRED FOR HOT WATER HEATING IS HEATING GPM MULTIPLIED BY 15,000. ,HEATING WATER ∆T OF 30°
6. SUSPEND UNIT WITH FOUR THREADED HANGER RODS ATTACHED TO TWO UNISTRUT RUNNERS SECURED TO
STRUCTURE. PROVIDE SPRING ISOLATION. REFER TO MANUFACTURER FOR MORE DETAILS.
7. AVOID MOUNTING OVER LIGHTS WHEREVER POSSIBLE.
8. REFER TO PIPING AT HOT WATER COIL DETAILS. PROVIDE WITH 3-WAY CONTROL VALVE UNLESS OTHERWISE
SCHEDULED.
9. CVB MOTOR SIZE, BASED ON 0.35" ESP, AS FOLLOWS:
A. 0-400 CFM REQUIRE 1/10 HORSEPOWER MOTOR
B. 401-700 CFM REQUIRE A 1/4 HORSEPOWER MOTOR
C. 701-1100 CFM REQUIRE A 1/2 HORSEPOWER MOTOR
D. 1101-1500 CFM REQUIRE A 3/4 HORSEPOWER MOTOR
E. 1500 - GREATER CFM REQUIRE A 1 HORSEPOWER MOTOR
10. LEAVING AIR TEMPERATURE SHALL NOT EXCEED 20° ABOVE ROOM SETPOINT.
11. PROVIDE ECM MOTORS
REMARKS:
1. UNIT SHALL BE DESIGNED TO FIT IN NARROW CORRIDORS
CONSTANT VOLUME TERMINAL BOX
MARK
MAXIMUM
CFM
MINIMUM
CFM
INLET
DIAMETER
SIZE (IN.)
MOTOR
ELECTRICAL
REQUIREMENT
HOT WATER COIL
REMARKS
V PH F MAX GPM
CONNECTING
PIPE SIZE (IN.)
CVB-1 960 235 10 208 1 60 4.2 1" 1
CVB-2 1350 340 12 208 1 60 5.8 1 1/4" 1
CVB-3 1545 475 14 208 1 60 6.7 1 1/4" 1
CVB-4 945 235 10 208 1 60 4.0 1" 1
CVB-5 1350 340 12 208 1 60 5.8 1" 1
VARIABLE VOLUME TERMINAL BOX
MARK SUPPLY CFM
MINIMUM
CFM
INLET
DIAMETER
SIZE (IN.)
HOT WATER COIL
REMARKS
GPM
CONNECTING
PIPE SIZE
VAV-J-1 480 300 6 2 1"
VAV-J-2 1525 450 12 7 1 1/4"
REMARKS:
1. INSTALL IN CEILING PER MANUFACTURERS RECOMMENDATION. INSTALLATION SHALL MEET ALL USMS REQUIREMENTS
2. LINEAR DIFFUSERS LOCATED INSIDE COURTROOM SHALL HAVE 8" INLET WITH 10"Ø BRANCH DUCT. MAXIMUM NC/RC OF 20.
3. OPPOSED BLADE DAMPER SHALL BE ADJUSTABLE FROM THE FACE OF THE DIFFUSER BY OPENING THE BLANK OFF PLATE.
4. INSTALL TO PROVIDE A CONTINUOUS APPEARANCE, COORDINATE WITH ARCHITECTUAL DRAWINGS AND INSTALLATION REQUIREMENTS. WHERE ACTIVE PLENUMS ARE NOT INSTALLED, PROVIDE BLANK OFF PLATES. PROVIDE CORNER
SECTIONS, END BORDERS, AND ALIGNMENT PINS AS REQUIRED.
REMARKS:
1. PROVIDE WITH VARIABLE FREQUENCY DRIVE (VFD), AND VIBRATION SWITCH
2. PROVIDE ISOLATION VALVES ON EACH BASIN, 5KW BASIN HEATER FOR EACH CELL.
3. TWO CELLS WITH WEIR GATE CAPABLE OF ISOLATING EACH CELL AND BASIN
4. PROVIDE FACTORY MANUFACTURED AND MOUNTED MOTOR DAVIT
5. PROVIDE MECHANICAL PLATFORM AND LADDER WITH EXTENSION TO ROOF
6. PROVIDE AEGIS BRUSHLESS SHAFT GROUNDING KIT ON EACH MOTOR
COOLING TOWER
MARK
ENTERING WATER
TEMP.(°F)
LEAVING WATER
TEMP.(°F)
GPM
AMBIENT WET
BULB TEMP.
(°F)
FAN HP
FAN CURRENT
CHARACTERISTIC MANUFACTURER MODEL REMARKS
V PH F
CT-1 95.0 85 750.0 80 2 @ 10 208 3 60 EVAPCO USS-212-319 1,2,3,4,5,6
UNIT HEATER - ELECTRIC
TAG
MINIMUM
CAPACITY
(BTUH)
KW
NUMBER
OF
STAGES
CURRENT
CHARAC. CFM MANUFACTURER MODEL REMARKS
V P F
EUH-1 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2
EUH-2 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2
EUH-3 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2
EUH-4 7,667 2.25 1 208 2 60 300 REZNOR EGW 1,2
EUH-5 7,667 2.25 1 208 2 60 300 REZNOR EGW 1,2
EUH-6 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2
EUH-7 5,118 1.50 1 208 2 60 300 REZNOR EGW 1,2
REMARKS:
1. PROVIDE WITH PENDANT MOUNTED THERMOSTAT AND PRE-WIRED DISCONNECT SWITCH
2. PROVIDE WITH MOUTING KIT SUITABLE FOR INSTALLATION TYPE.
REMARKS:
1. PROVIDE WITH ECONOMIZER, VFD, ROOF CURB (SUITABLE FOR REPECTIVE ROOF TYPE), MERV 11 FILTERS.
2. PROVIDE WITH PREHEAT COIL (8.5 MBTUH, 6 GPM) AND REHEAT COIL (10.5 MBTUH, 7 GPM)
3. PROVIDE VARIABLE AIR VOLUME UNIT.
4. PROVIDE HEATED PIPING COMPARTMENT, AND CONVENIENCE 115V GFI.
5. PROVIDE WITH SINGLE POINT POWER CONNECTION.
6. PROVIDE WITH PREHEAT COIL (3.5 MBTUH, 3 GPM) AND REHEAT COI. (4.4 MBTUH, 3 GPM)
7. PROVIDE WITH PREHEAT COIL FOR VALUES SCHEDULED
GENERAL NOTES:
1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS WHERE
APPLICABLE. DIRTY FILTER AND UNIT CASING MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH ELECTRICIAN.
2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS
REQUIRED BY NEC.
3. COORDINATE WITH FIRE ALARM CONTRACTOR FOR REQUIRED FIRE/SMOKE DETECTORS
4. ROOF TOP UNITS SHALL HAVE A CHILLED WATER ∆T OF 10° AND A HEATING WATER ∆T OF 30°
5. PROVIDE 20WAY CONTROL VALVES FOR CHILLED WATER COIL, 3-WAY VALVES FOR HEATING WATER COILS
ROOF TOP UNIT
MARK
FAN
COOLING
HEATING
PIPE SIZE
TO COIL (IN.)
REMARKS
SUPPLY
AIR CFM
OUTSIDE
AIR CFM
EXT. STATIC
PRESSURE
(IN. W.C)
HORSE
POWER
CURRENT
CHARAC. AIR TEMPERATURE (°F)
WATER
ENTERING AIR
TEMPERATURE
(°F)
MIN.
HEATING
CAPACITY
WATER
CHILLED
WATER
HOT
WATER
V PH F
ENTERING
DRY BULB
ENTERING
WET BULB
LEAVING
DRY BULB
LEAVING
WET BULB
ENTERING
TEMP (°F)
GPM
MAX.
PRESSURE
DROP (IN.)
ENTERING
TEMP. (°F)
GPM
MAX.
PRESSURE
DROP (IN.)
RTU-1 2,005 650 1.50 3.0 208 3 60 78.2 65.2 53.0 52.5 44 15.1 120.0 24.2 68,000 140.0 6.0 120 2" 1" 1,3,4,5,7
RTU-2 2,385 2,385 0.75 3.0 208 3 60 97.0 78.4 53.0 52.5 44 43.0 120.0 22.9 184,500 140.0 12.3 120 2 1/2" 1 1/2" 1,2,3,4,5
RTU-3 1,005 1,005 0.50 1.5 208 3 60 97.0 78.4 53.0 52.5 44 18.1 120.0 22.9 90,000 140.0 6.5 120 1 1/2" 1 1/4" 1,3,4,5,6
PUMP
MARK SERVICE TYPE GPM
HEAD
(FT.)
MOTOR
HORSE POWER
Max.
RPM
CURRENT
MANUFACTURER MODEL NUMBER REMARKS
V PH F
CHWP-1 CHILLED WATER INLINE 300 87.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7
CHWP-2 CHILLED WATER INLINE 300 87.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7
CWP-1 CONDENSER WATER INLINE 375 71.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7
CWP-2 CONDENSER WATER INLINE 375 71.00 15 1750 208 3 60 BELL & GOSSETT SERIES E-80SC 1,2,3,4,5,6,7
GENERAL NOTES:
1. PUMP IS TO HAVE A NON-OVERLOADING MOTOR.
2. MINIMUM RECOMMENDED CLEARANCE AROUND A PUMP IS 24 INCHES. MAINTAIN
MINIMUM CLEARANCES AS REQUIRED FOR SERVICE, MAINTENANCE, AND INSPECTION.
REMARKS:
1. TEFC, PREMIUM EFFICIENCY MOTOR. PROVIDE AEGIS BRUSHLESS SHAFT GROUNDING KIT
2. COUPLING, RIGID SPACER TYPE OF HIGH TENSILE ALUMINUM ALLOY. COUPLING TO BE DESIGNED
TO BE EASILY REMOVED ON SITE TO REVEAL A SPACE BETWEEN THE PUMP AND MOTOR SHAFTS
SUFFICIENT TO REMOVE ALL MECHANICAL SEAL COMPONENTS FOR SERVICING AND TO BE
REPLACED WITHOUT DISTURBING THE MOTOR OR PUMP.
3. MECHANICAL SEALS SHALL BE STAINLESS STEEL MUTLI-SPRING OUTSIDE BALANCED TYPE WITH
VITON SECONDARY SEAL, CARBON ROTATING FACE AND SILICON CARBIDE STATIONARY SEAT.
4. VFD PROVIDED BY PUMP MANUFACTURER AND UNIT MOUNTED
5. PROVIDE ONE EXTRA SET OF SEALS AND TURN OVER TO OWNER
6. PUMP SPEED CONTROL BY REMOTE BAS SIGNAL, FROM PRESSURE DIFFERENTIAL SENSOR.
7. COOLING MEDIUM: WATER
WATER COOLED CHILLER
MARK TYPE
ACTUAL
CAPACITY
(TONS)
EVAPORATOR (FF=0.0001) CONDENSER (FF=0.00025)
CURRENT
CHARAC. MINIMUM
KW/TON
MINIMUM
NPLV
MANUFACTURER MODEL NUMBER MCA MOCP REMARKS
LEAVING WATER
TEMP.(°F)
GPM
PRESSURE
DROP (FT)
ENTERING
WATER TEMP.(°F)
GPM
PRESSURE
DROP (FT)
V PH F
CH-1 CENTRIFUGAL 125 44 300 10.00 85 375 10.00 480 3 60 0.5862 0.3587 SMARDT WB044 119 A 172 A 1,2,3,4,5,6
CH-2 CENTRIFUGAL 125 44 300 10.00 85 375 10.00 480 3 60 0.5862 0.3587 SMARDT WB044 119 A 172 A 1,2,3,4,5,6
REMARKS:
1. CHILLER SHALL MEET OR EXCEED BOTH ABOVE SCHEDULED FULL-LOAD AND PART-LOAD MINIMUM ASHRAE 90.1 EFFICIENCIES AT ARI 44 LEAVING CHILLED WATER
TEMPERATURE AND 85 ENTERING CONDENSER WATER TEMPERATURE.
2. CHILLERS SHALL MEET OR EXCEED CAPACITY AT SCHEDULED WATER TEMPERATURES.
3. PROVIDE WITH INTEGRAL VARIABLE FREQUENCY DRIVE, PRE-PIPED AND PRE-WIRED CONTROLS. MAXIMUM FOOTPRINT SHALL BE LESS THAN 4'-6" X 12'-6"
4. PROVIDE UNIT KNOCKED DOWN IN SECTION TO BE FIELD REASSEMBLED AS REQUIRED FOR SITE INSTALLATION.
5. PROVIDE FACTORY FURNISHED VIBRATION ISOLATORS, AUXILLARY MOTORS FOR OIL, PURGE, ETC...
6. MAGNETIC BEARING
GRILLE SIZING SCHEDULE
STANDARD GRILLE
REGISTER OR NONSTANDARD GRILLE
DESIGNATES GRILLE NECK SIZE
SIZE OF GRILLE NECK
TO TRAVERSE GRILLE
AIR QUANTITY IN CFM
TO TRAVERSE GRILLE
(REFERENCE TABLE BELOW)
AIR QUANTITY IN CFM
SQUARE
GRILLE NECK SIZE
6" x 6"
8" x 8"
9" x 9"
10" x 10"
14" x 14"
12" x 12"
GRILLE SIZE
DESIGNATION
(REFERENCE GRILLE SCHEDULE)
ALL REGISTERS SHALL HAVE A 45° HORIZONTAL DEFLECTION UNLESS OTHERWISE SHOWN.
CONNECTING GRILLE TO DUCTWORK
CONNECTING GRILLE TO DUCTWORK
(REFERENCE GRILLE SCHEDULE)
DESIGNATES GRILLE TYPE
ALL GRILLES SHOWN SHALL BE FOUR-WAY THROW UNLESS OTHERWISE SHOWN.
ALL GRILLES SHOWN SHALL BE FOUR-WAY THROW UNLESS OTHERWISE SHOWN.
SIZE OF FLEX OR RIGID DUCT
DESIGNATES GRILLE TYPE
SIZE OF FLEX OR RIGID DUCT
A
12"x10" 12/10
A1
6"Ø
6"Ø
ROUND
8"Ø
10"Ø
12"Ø
SQUARE
GRILLE NECK SIZE
15" x 15"
16" x 16"
18" x 18"
20" x 20"
24" x 24"
22" x 22"
GRILLE SIZE
DESIGNATION
14"Ø
ROUND
REMARKS
MODEL
NUMBER
MANUFACTURERDUTYACTUATOR BLADE ACTIONMARK
NOTES:
N/A - NOT APPLICABLE
DAMPER
D-3 MOTORIZED OVER 9" WIDE OPPOSED RUSKIN CD-60 LOW LEAKAGE DAMPER WITH BLADE SEALS
D-2 MANUAL BALANCING OVER 9" WIDE OPPOSED RUSKIN MD-35 MANUAL DAMPER WITH STANDARD CONSTRUCTION
FEATURES AND VENTLOCK #639 LOCKING REGULATOR.
D-1 MANUAL BALANCING UNDER 9" WIDE N/A N/A N/A SEE SMACNA CONSTRUCTION DETAILS REFERENCED "TYPICAL
CONSTRUCTION DETAILS FOR LOW VELOCITY DUCTS."
COOLING TOWER BASIN SWEEPER
TAG GPM Horsepower ELECTRICAL MODEL SEPERATOR Manufacturer REMARKS
CTBC-1 110 3 208/3/60 eTCX-0110-SRV eHTX-0060 LAKOS 1,2
REMARKS:
1. COORDINATE WEIGHT AND DIMENSIONS WITH STRUCTURE.
2. COORDINATE SIZE OF CTBC-1 WITH SIZE OF RESPECTIVE COOLING TOWER.
GENERAL NOTES:
1. MAXIMUM STATIC PRESSURE DROP OF AIR THROUGH THE TERMINAL BOX SHALL BE 0.2" ESP.
2. MAXIMUM VELOCITY THROUGH DUCT INLET SHALL BE 2,000 FPM.
3. MAXIMUM STATIC PRESSURE DROP THROUGH HEATER COIL SHALL BE 0.25" ESP.
4. MAXIMUM STATIC PRESSURE DROP OF WATER THROUGH HEATER COIL SHALL BE 10' W.G.
5. BTUH REQUIRED FOR HOT WATER HEATING IS HEATING GPM MULTIPLIED BY 15,000. ,HEATING WATER ∆T OF 30°
6. SUSPEND UNIT WITH FOUR THREADED HANGER RODS ATTACHED TO TWO UNISTRUT RUNNERS SECURED TO
STRUCTURE. PROVIDE SPRING ISOLATION. REFER TO MANUFACTURER FOR MORE DETAILS.
7. AVOID MOUNTING OVER LIGHTS WHEREVER POSSIBLE.
8. REFER TO PIPING AT HOT WATER COIL DETAILS. PROVIDE WITH 3-WAY CONTROL VALVE UNLESS OTHERWISE
SCHEDULED.
10. LEAVING AIR TEMPERATURE SHALL NOT EXCEED 20° ABOVE ROOM SETPOINT.
REMARKS:
AIR COOLED CONDENSING UNIT
MARK
MIN. TOTAL
CAPACITY
(BTUH)
OUTDOOR
AIR
TEMP (°F)
MINIMUM
EER/
SEER
CURRENT
CHARAC.
RELATED
UNIT
MARK
REMARKS
V PH F
ACC-1 12,000 95 13 208 1 60 DMS-1 1
ACC-2 12,000 95 13 208 1 60 DMS-2 1
DUCTLESS MINI SPLIT DX UNIT
MARK
FAN COOLING
REMARKSSUPPLY
AIR CFM
OUTSIDE
AIR CFM
EXT.STATIC
PRESSURE
(IN. W.C.)
HORSE
POWER
CURRENT
CHARAC.
AIR TEMPERATURE (°F)
MIN. TOTAL
CAPACITY (BTUH)
MIN. SENS.
CAPACITY (BTUH)
MINIMUM
EER/
SEER
NUMBER
OF
STAGESV PH F
ENTERING
DRY BULB
ENTERING
WET BULB
DMS-1 340 0 0.00 0.0 120 1 60 82.0 68.0 11,968 8,813 -/13.0 1 1,2,3,4,5
DMS-2 340 0 0.00 0.0 120 1 60 82.0 68.0 11,968 8,813 -/13.0 1 1,2,3,4,5
GENERAL NOTES:
1. MINIMUM RECOMMENDED CLEARANCE AROUND ROOFTOP UNIT IS 12 INCHES ON NON-SERVICE SIDES AND 30 INCHES
ON SERVICE SIDES. MAINTAIN MINIMUM CLEARANCE FOR CONDENSER AIR FLOW AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.
REMARKS:
1. PROVIDE WITH HAIL GUARDS, LOW AMBIENT KIT, PROVISIONS FOR LONG REFRIGERANT LINES
REMARKS:
1. CONTROLLED BY PROGRAMMABLE WIRED THERMOST.
2. REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S REQUIREMENTS.
3. UNIT INSTALLATION PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
4. PROVIDE WITH CONDENSATE PUMP POWERED VIA RESPECTIVE UNIT.
5. POWER PROVIDED VIA RESPECTIVE CONDENSING UNIT
GENERAL NOTES:
1. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK, AIR DEVICES, DAMPERS, AND DUCT MOUNTED HOT WATER COILS WHERE APPLICABLE. DIRTY FILTER AND UNIT CASING
MUST BE ADDED TO EXTERNAL STATIC PRESSURE TO OBTAIN TOTAL PRESSURE LOSS. INCREASE HORSEPOWER AS REQUIRED TO MEET YOUR TOTAL PRESSURE LOSS. COORDINATE WITH
ELECTRICIAN.
2. MAINTAIN MINIMUM CLEARANCE FOR COIL PULL AS RECOMMENDED BY UNIT MANUFACTURER. MAINTAIN MINIMUM CLEARANCE AS REQUIRED TO OPEN ACCESS AND CONTROL DOORS ON UNIT FOR SERVICE, MAINTENANCE, AND INSPECTION. MAINTAIN MINIMUM ELECTRICAL CLEARANCE AS REQUIRED BY NEC.
CONTROLS CONTRACTOR SHALL REPLACE AND UPGRADE THE ENTIRE
EXISTING CONTROL SYSTEM FOR ALL EQUIPMENT BOTH SHOWN AND NOT
SHOWN IN THE CONTRACT DOCUMENTS TO INTERFACE WITH THE NEW
CONTROL SYSTEM. COORDINATE WITH ARCHITECT WHERE PARTS OF
WALLS OR CEILINGS MAY NEED TO BE REMOVED. REPAIRS SHALL MATCH
EXISTING FINISHES
Delta Issue Date Description
ChelseyMClick Polygon
ChelseyMClick Cross-Out
ChelseyMClick Text Box Not needed
ChelseyMClick Callout Future Project
ChelseyMClick Polygon
ChelseyMClick Text Box Future Project
ChelseyMClick Cross-Out
FM
SCALE: NONE
SCALE: NONE
R
R
2" QUICK
FILL
BUILDING HVAC SYSTEM BUILDING PLUMBING SYSTEM
1/2"
N.O.
N.C.
N.O.
BUILDING PLUMBING SYSTEM BUILDING HVAC SYSTEM
1/2"
N.O. N.O.
N.C.
1-1/2" QUICK
FILL
1-1/4"
3/4"
2" MAKEUP
WATER
2" MAKEUP
WATER
2" MAKEUP
WATER
2" MAKEUP
WATER
2"
2"
5" CWR
MECHANICAL KEYED NOTES:
PROVIDE ERNST GAUGE #E-57-3 BRONZE BODY SIGHT
GLASS WITH S.S. SHAFT, PLASTIC SPINNER AND DOUBLE
WINDOW. OPERATING TEMPERATURE AND PRESSURE
SHALL BE 125 PSI, 200F. MINIMUM.
CENTER GUIDED NON-SLAM CHECK VALVE (TYP ALL)
PROVIDE BALL VALVE WITH HOSE THREAD ADAPTER.
ENSURE VALVES ARE INSTALLED IN AN ACCESSIBLE SPACE
PROVIDE CHAIN OPERATORS AS REQUIRED. (TYPICAL ALL)
NOT USED8
1" STUBS BY MECH CONTRACTOR, INJECTOR ASSEMBLY
IN MECH ROOM BY FEEDER VENDOR. MECH
CONTRACTOR SHALL MAKE CONNECTIONS TO THE
TREATMENT SYSTEM. PIPING TO COOLING TOWER WATER MAKE-UP SYSTEM
11 PIPING TO CHILLED WATER MAKE-UP SYSTEM.
NOT USED9
REFER TO PLUMBING DRAWING FOR PIPING SIZES.
VARIABLE FREQUENCY DRIVE (VFD) (TYPICAL ALL)
COOLING TOWER CHEM
FEED SYSTEM IN MECH
ROOM
3" DRAIN
(TYPICAL)
3" OVERFLOW
(TYPICAL)
BASIN WATER LEVEL
CONTROLLER (TYPICAL)
MAKE UP WATER
FLOW METER
CTBC-1
COOLING TOWER
CLEANING SYSTEM
CT-1
COOLING TOWER
EQUAL FLOW TO EACH CELL
375 GPM
AUTO-FLOW
DEVICE
AHU-1
(e)AHU-4
(e)AHU-5
(e)AHU-2 (e)AHU-3
(e)AHU-8
AHU-6 AHU-7
DIFFERENTIAL
PRESSURE
SENSOR
M
AS-1
AIR SEPARATOR WITHOUT
STRAINER
BELL & GOSSETT #107A
AUTOMATIC AIR VENT
6ET-1
EXPANSION
TANK
4" THICK
HOUSEKEEPING
MODULATING CONTROL VALVE
4" CHWR
C W
S
C W
R
4" CHWS
C W
S
5" CWS
4" CHWR
4" CHWS
4" CHWR
6" CHWR
4" CHWR
3" CHWR
4" CHWS
3" CHWS
C H
W S
6" CHWS
TURBINE
FLOW METER
6"6"
WEIR
GATE
BACK FLOW
PREVENTER
BACK FLOW
PREVENTER
N.O.
BMCS
BMCS
TO CHILLER
OUTLET/INLET
CWS&R AND
CHWS&R PIPING
PRESSURE
GAUGE
MOUNT AT 5'-0"
AFF RE:9/M4.1
3/4"
N.C.
G.C.
TO BMCS
CHILLER CH-2
CHILLER CH-1
6" THICK HOUSEKEEPING
(TYP)
CWP-2
CWP-1
3/4"
CHWP-1
CHWP-2
1-1/2"
CHEMICAL
FEEDER
3/4"
N.C.
N.O.N.O.
3/4"
N.C.
N.O.
N.O.
FLANGE
C H
W R
6" CHWR
4" CHWR
4" CHWS
PIPING AT AHU CHILLED WATER COIL
38 3
COIL
FLOW
AIR
PIPE STRAINER
DIRT LEG
1/2" BALL VALVE WITH HOSE THREAD
ADAPTER, CAP AND CHAIN.
UNION (2" & SMALLER ONLY, FLANGE
CONNECTION FOR LARGER PIPES)
TEMPERATURE/PRESSURE
TEST STATION.
CONTROL VALVE
REMOVING BALANCING VALVE AND
PIPING. CAP OPEN PIPES AS SHOWN
SHUT OFF VALVE
TYPICAL
TYPICAL
TYPICAL PIPING AT
INLET AND OUTLET OF CHILLER
RTU-1 RTU-2
C W
S
C W
S
6" CWS
6" CWR
C
W R
C W
S
300 GPM
AUTO-FLOW
DEVICE (TYPICAL)
300 GPM
AUTO-FLOW
DEVICE (TYPICAL)
375 GPM
AUTO-FLOW
DEVICE
CAP PORT ON EXISTING 3-WAY CONTROL VALVE TO
CONVERT TO 2-WAY CONTROL VALVE.
6" CHWR
6" CHWS
CHILLED WATER: 3.8 GPM
HEATING WATER: 0 GPM
CHILLED WATER: 53.6 GPM
HEATING WATER: 10.7 GPM
CHILLED WATER: 20.5 GPM
HEATING WATER: 9 GPM
CHILLED WATER: 20.5 GPM
HEATING WATER: 9 GPM
CHILLED WATER: 103 GPM
HEATING WATER: 16.5 GPM
CHILLED WATER: 39.6 GPM
HEATING WATER: 7.2 GPM
CHILLED WATER: 43.9 GPM
HEATING WATER: 8.1 GPM
CHILLED WATER: 88.6 GPM
HEATING WATER: 12.3 GPM
CHILLED WATER: 43.0 GPM
HEATING WATER: 12.3 GPM
CHILLED WATER: 15.1 GPM
HEATING WATER: 6.0 GPM
CHILLED WATER MAXIMUM FLOWRATE: 460 GPM
CHILLERS SIZED TO HANDLE 67% OF MAX FLOW
FLOWRATE THROUGH CHILLERS 288 GPM
RTU-3
CHILLED WATER: 18.1 GPM
HEATING WATER: 6.5 GPM
LOUISIANAST
ATE OF
DAVID BONAVENTURE
License No. 31064
PROFESSIONAL
ENGINEER
NOTE: EVERY SHEETNOTE MAY NOT APPEAR ON THIS PAGE
SHEET NOTES
SENSITIVE BUT UNCLASSIFIED(SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice
Properly destroy documents when no longer needed
GENERAL NOTES
LEGEND
R E
V
IS
IO
N
N O
T E
S G
R A
P H
IC
S
C A
L E
C O
N T
R A
C T
O R
S B
U
IL
D
IN
G P
R O
J E
C T
K E
Y M
A P
D R
A W
IN
G
CHECKED BY
DRAWN BY
FLOOR NO
DRAWING TITLE
DRAWING NO
SUB DATE:
SUBMISSION:
GSA PM:
PROJECT NO:
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NO
BUILDING NO
CITY/ST./ZIP
STREET
NAME
A/E CON. NO.
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
SHEET SIZE:
DATE DRAFTED:
34 X 44
N/A
GENSLER
C E
R T
IF
IC
A T
IO
N
S
12" = 1'-0"
M05.100
GENERAL SERVICES
ADMINISTRATION
MECHANICAL SCHEMATICS 1
U.S. COURTHOUSE, CSP & COURT
COMPONENTS B&C
100% CONSTRUCTION DOCUMENTS
10/27/2017
PMM
DAB
201 JACKSON STREET
MONROE, LOUISIANA 71201-7472
LA0029ZZ