GSA Region 7
BAS Graphic Format
The following pages represent the required BAS graphics format.
Strict adherence to this format will maintain consistency throughout the region regardless of the system integrator working on the systems
General notes
The following pages represent the minimum requirements for the Graphic Display Pages on the
Region 7 BAS.
Each Integrator is responsible for maintaining continuity within the system. All pages must be formatted for 1050 x 1680 dpi.
All Graphic displays must be created using elements from the Tridium N4 “kitPxHvac” library located on the GSA Region 7 Server located in Fort Worth.
All Graphic elements created by any one integrator must be stored on the server for use by all other integrators. Before creating a new graphic, check the library to determine if there is already a representation of the equipment in the library folder for your use
• For example, Throughout GSA Region 7, all Cooling only VAV Boxes will use the same graphic, All Parallel Fan Powered Boxes will use the same graphic, etc. Careful attention to point naming will be required in order that the same graphic can be used by multiple integrators.
Photos of equipment and Manufacture’s graphics of actual Chillers and Boilers are acceptable where the likeness can not be created from the kitPxHvac library. Photos or manufacture’s drawings are to be scaled to be in proportion to the mechanical plant
Please note that these graphics must reside on both the JACE and the GSA Region 7 BAS Web Supervisor Server.
Hotlinks to sites outside of the GSA Firewall are not allowed.
Graphic displays that are static and or copies of old BAS system graphics are not allowed.
All Floor Plan Graphic pages are to be approved by the GSA Property Manager prior to installation on the Server or in the JACE controller
JACE and Station Naming
Each integrator is to follow the Station and JACE
Naming standard
(For a full list of GSA IT Location Codes, please email R7BAS@gsa.gov.
JACE and Station Login and
Passwords The JACE and Station Login and
Passwords are pre-established for the programmers use. Please contact email
R7BAS@gsa.gov to receive these login and passwords.
JACE and Web Supervisor
Station User Prototypes JACE and Web Supervisor Station User
Prototypes are created on the web supervisor and shall be used.
Single Sign-on for multiple
JACEs
Each integrator is to provide the GSA with the name, IP address and MAC address of each building JACE. The GSA will have this data entered into the GSA DNS
Server so that only a single login is required per site
Utility Data Page
The GSA requires a separate graphics page for the utility data.
For instance photovoltaic, gas, electric, water, pulse meters and
BACnet/LON/Modbus chemical treatment/cooling tower bleed data points that are a part of the BAS are to be displayed in a Utility Data Page
Graphic displays on this page shall be constructed from elements in the
Tridium N4 “kitPxHvac” library, from digital pictures of the actual meter or from manufacture's graphics
All Graphic elements created by any one integrator must be stored on the server for use by all other integrators.
The Utility Data page shall be accessible by a hotlink from the home page
R7 BAS Home Page
Building Home Page Example of required building Home Page
Example of building “Home Page” shown at right
Link from this page to overall building plan with links to each floor plan
Display the Building kWh and kW Demand on the “Home Page” with hotlink to the points history trend
Include Hotlink to Energy page.
Display the Outdoor Air Temperature and Outdoor Humidity on the “Home Page” with hotlink to the points history trend
Display a link to the building Weather Page
Set Picture size to 600 x
Building Number
Building Name
Pulse Meter Page The GSA requires a separate graphics page for the Meter Page.
The page shown below exists as a .px file on the N4 Server for use by all integrators. Once the page is loaded into the JACE and the configuration modified to show the correct meter information.
Smart Meter Page 1
The page shown below exists as a .px file on the N4 Server for use by all
Smart Meter Page 2
The page shown below exists as a .px file on the N4 Server for use by all
Weather Page The GSA requires a separate graphics page for weather data.
The page shown below exists on the N4 Server for use by all integrators.
Once the page is loaded into the JACE and the configuration modified to show the correct weather station information.
Integrated Irrigation Page 1 The GSA requires a separate graphics page for integrated irrigation.
The page shown below exists on the N4 Server for use by all integrators.
Once the page is loaded into the JACE and the configuration modified to show the correct weather station information, remove the three blocks that allow the ability to change the station and insert the Solar Radiation, Rainfall Gage and Soil Moisture Sensor points.
Integrated Irrigation Page 2 The GSA requires a separate graphics page for integrated irrigation.
The page shown below indicates the irrigation zones per the prior Niagara graphic page. An irrigation zone map and sequence of operations shall be hyperlinked on the Niagara graphic page as a .pdf file(s) to aid the building engineer. Navigation from the .pdf file back to the Niagara graphic Zone location schedule shall be seamless and intuitive.
Example of Floor Plan Graphic Note – Color Spectrum display of Room Temperature
Deviation from Setpoint
Include One Click Hot-Link to each Equipment Graphic page from Floor plan pages
All Floor Plan
Graphic pages are to be approved by the GSA Property
Manager prior to installation on the
Server or in the
JACE controller
Color Spectrum display representing deviation from Set
Point is to be shown on Floor Plan drawings
Hot Links from Page to Page
Hotlinks are to follow the path described here.
Hotlink from overall “Home Page” to Floor Plans
Hotlink from Floor Plan to Air Terminal Device (ATD) controlling space (VAV, FPVAV, VVR, FCU, CV-AHU, RTU)
Hotlink from ATD to VAV AHU
Hotlinks from AHU to Chilled Water and Heating Plant
On each graphic page, provide Hot Link back to the Floor Plan or Building Home Page
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
Required Display pages for buildings greater than 5 floors with
HotLink from Home or Floor Plan Graphic Page
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
Hot Links to
Floor Plan
Graphics pages
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
Rm # TCU # SetPt Temp
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
Rm # TCU # SetPt Temp
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
B 202 FPB-2-02 74 73.3
B 204 FPB-2-04 74 75.2
B 207 FPB-2-09 74 76.5
B 212 FPB-2-18 74 74.1
C 301 FPB-3-07 74 72.0
C 303 AHU-17 74 74.7
C 322 VAV-3-17 74 73.7
Rm # TCU # SetPt Temp
Indicate deviation from set point by color spectrum.
White at 0.0 df, Dark Blue at -
5 df and Bright Red at +5 df
Hot Links to
Equipment
Graphics pages
Apply as many TCU boxes as possible per page. Create as many pages as required to display all TCU setpoint and Room Temperature
Required Overview Page for AH Units
Indicate deviation from set point by color spectrum. White at 0.0 df, Dark Blue at -5 df and Bright
Red at +5 df
NOTE – Create link to AHU alarms and turn text box Red when AHU is in alarm.
Hot Link to Floor Plan
Graphic page
Hot Links to
Equipment Graphic page
NOTE – Color of box indicates the unit status.
Green = AHU running
Red = AHU in Alarm
Gray = AHU off
NOTE – Create link to AHU
Schedule and indicate Schedule
Status by graphic element.
Occupied
Un-Occupied
Required Overview Page for Lighting
Required Overview Page for Lighting
Point Naming Standards
Refer to mandatory GSA Project Haystack BAS point naming standard guidance. This documentation is available by e-mail from R7BAS@gsa.gov.
GSA Project Haystack BAS point naming standards shall be used at the N4 JACE Supervisory controller and
Unitary layer controllers on all GSA R7 Projects.
For N4 JACE front end overlay projects the point naming standards are not mandatory at the field level AHU and plant controllers.
For complete DDC new installation or retrofit, mandatory
GSA Project Haystack BAS point naming standards are required at the Unitary field layer and N4 JACE level programming.
Setpoint and Override limiting
Setpoint Limiting as well as BO Command points that are to have the override capability should be set with the following limits
Permanent - Disabled and not displayed
1 Minute
15 Minutes
30 Minutes
1 Hour
2 Hours
3 Hours
Custom configured to a mN4imum of 8 Hours
"Set" to be programmed to limit the range of adjustment of a setpoint to 70 minimum and 80 mN4imum. We understand that there will be some areas and individuals that will require different ranges. These exceptions will be addressed on a case by case basis.
Setpoint and Override limiting
US Court House Court Rooms [Parameters used to sub cool space prior to court room proceedings]
Disable Optimal Start (if applicable)
Set point Limiting as well as BO Command points that are to have the override capability should be set with the following limits
Permanent - Disabled and not displayed
1 Minute
30 Minute
1 Hour
2 Hours
3 Hours
Custom configured to a mN4imum of 12 Hours
"Set" to be programmed to limit the Space temp override minimum set point temperature of 65 degrees. After 12 hour override 70 degree minimum temperature default.
Point Trending
From the BAS and accessible from a unit graphic page, there shall be hot links to stored Chart Logs for points useful and relevant for troubleshooting the equipment displayed and monitored. At a minimum, links to the Chart
Logs for the following points shall be accessible from the graphic page. The local trended data shall be stored for 14 days in the JACE. Trended data shall be archived to the N4 WS once each 24 hours for use with M & V verification.
FPVAV Box with Heat
Space Temperature/Humidity
Discharge/Supply Air Temperature
Air Flow CFM
Valve position
Fan Status
VAV Box
Discharge/Supply Air
Temperature
Air Flow CFM
VAV Box with Heat
Discharge/Supply air
Temperature
Air Flow CFM
Valve position
Point Trending continued
VAV AHU
Fan Speed
Space Temperature
Discharge/Supply Air
Temperature
Duct Static Pressure
Chilled Water Valve position
Co2 ppm
OAD/Economizer Damper
Position
Mixed Air Temperature
Constant Volume AHU
Space
Temperature/Humidity
Discharge/Supply Air
Temperature
Chilled Water Valve position
Hot Water Valve position
Co2 ppm
OAD/Economizer Damper
Multi Zone AHU
Space
Temperature/Humidity
Cold Deck Air Temperature
Hot Deck Air Temperature
Chilled Water Valve position
Hot Water Valve position
Co2 ppm
OAD/Economizer Damper
Fan Coil Unit
Space
Temperature/Humidity
Discharge/Supply Air
Temperature
OAD Damper Position
Chilled Water Valve position
Hot Water Valve position
Chilled Water Plant Chiller Status (for each Chiller)
Chiller Amps
Chilled Water Pump Status (for each CHWP)
Condenser Water Pump Status (for each
CWP)
Entering Chilled Water Temperature (at each
Chiller)
Leaving Chilled Water Temperature (at each
Chiller)
Entering Condenser Water Temperature (at each Chiller)
Leaving Condenser Water Temperature (at each Chiller)
Secondary CHWP Status
Secondary CHWP Speed
Secondary CHW Loop Supply and Return
Temperature
Tower Fan Status (for each fan)
Tower Fan Speed (for each fan)
Condenser Water Bypass Valve position
Plate Frame Heat Exchanger (If Building so equipped)
Chilled Water Isolation Valve position
Condenser Water Isolation Valve position
Entering Chilled Water Temperature
Leaving Chilled Water Temperature
Entering Condenser Water Temperature
Leaving Condenser Water Temperature
Chilled Water Mixing Valve
Hot Water Plant Boiler Status (for each Boiler)
Hot Water Pump Status (for each HWP)
Entering Hot Water Temperature (at each
Boiler)
Leaving Hot Water Temperature (at each
Boiler)
Secondary HWP Status
Secondary HWP Speed
Secondary HW Loop Supply and Return
Temperature
Hot Water Mixing Valve position
Miscellaneous Points Exhaust Fan(s) Status
Outdoor Air Temperature
Outdoor Humidity or Dew Point
Heat Recovery Unit(s) Fan Status
HRU Entering Building Air Temperature
HRU Building Exhaust Air Temperature
HRU Outdoor Air Temperature after HRU
The previous slides list Hot Links to trend values for various types of equipment.
In no way is this listing meant to define all of the points that are to be logged and trended for a specific type of equipment.
These slides are only showing the minimum number of points that are to be accessed and plotted from the graphic page.
Trends shall be configured for all pertinent points
All Trends shall have the ability to be manually enabled and once enabled shall automatically terminate after 14 days of collecting data
Point Trending Navigation
Point Trending Log
Point Trending Graphing
Critical Alarms and Reporting Below is the list of alarms that are critical and need to be transmitted by Alpha-
Numeric pagers or email to specific individuals for each building.
N4 Niagara Network Web Supervisor communication ping failure to JACE.
Chiller Water System failure – Chill Water Loop Temperature three (3) degrees above set point for consistent five 15 minutes (adjustable).
Heating Water System failure – Heating Water Loop Temperature three (3) degrees below active set point for consistent five 15 minutes (adjustable).
Lift station high sump pump pit level alarm (to prevent basement flooding)
Fire /Smoke Alarm enunciation condition
Water meter gpm usage >30% above average sample rate base lines. (Samples taken at 0400hrs, 1000hrs, 1600hrs, and 2200hrs).
Emergency Generator status enabled (due to building power feed loss).
Tripped freeze stat condition.
Upon Request, GSA will provide a list of names to whom the remote notifications need to be sent such as GSA Property Manager, Mechanical Inspector, and Operations and Maintenance Project
Manager.
The following information may help when setting up remote notifications to Smart Phone devices:
T-Mobile: phonenumber@tmomail.net
Virgin Mobile: phonenumber@vmobl.com
Cingular: phonenumber@cingularme.com
Sprint: phonenumber@messaging.sprintpcs.com
Verizon: phonenumber@vtext.com
Nextel: phonenumber@messaging.nextel.com
Alltel
[10-digit phone number]@message.alltel.com
AT&T Wireless (now part of Cingular)
[10-digit phone number]@mmode.com http://www.sms411.net/2006/07/alltel-sms.html
Boost Mobile
[10-digit phone number]@myboostmobile.com
Cingular number]@mobile.mycingular.com
OR
[10-digit number]@cingularme.com
Nextel (now part of Sprint Nextel)
[10-digit telephone number]@messaging.nextel.com
Sprint PCS (now Sprint Nextel) number]@messaging.sprintpcs.com
T-Mobile number]@tmomail.net
Verizon
[10-digit phone number]@vtext.com
Virgin Mobile USA number]@vmobl.com us cellular number(@email.uscc.net).
http://www.sms411.net/2006/07/boost-mobile-sms.html http://www.sms411.net/2006/07/cingular-sms.html http://www.sms411.net/2006/07/nextel-sms.html http://www.sms411.net/2006/07/sprint-sms.html http://www.sms411.net/2006/07/t-mobile-sms.html http://www.sms411.net/2006/07/t-mobile-sms.html http://www.sms411.net/2006/07/t-mobile-sms.html http://www.sms411.net/2006/07/verizon-sms.html http://www.sms411.net/2006/07/virgin-mobile-sms.html http://www.google.com/search?hl=en&sa=X&oi=spell&resnum=0&ct=result&cd=1&q=us+cellular&spell=1 http://www.google.com/search?hl=en&sa=X&oi=spell&resnum=0&ct=result&cd=1&q=us+cellular&spell=1
N4 Provisioning
Referencing Niagara 4 Provisioning Guide for Niagara Networks, Updated
February 10, 2010, install and configure Provisioning on the N4 Supervisor at the Region 7 FOB.
Configure a provisioning job step to create a “Backup Station Step”. Configure this step to backup all JACE controllers in all buildings no less than once every thirty days.
Configure a provisioning job step to create a “Copy Supervisor Step”. Configure this step to backup the Supervisor no less than once every thirty days.
Sample of Tridium Graphics
The following pages show screen captures of Unit Graphic Displays created using the Niagara graphics library. All unit displays must adhere to the use of elements from this library in the creation of the new graphic displays.
All graphic page backgrounds are to be white.
Each Integrator is responsible for maintaining continuity within the system. All pages must be formatted for 1024 x 768 dpi. (The intent is to not have scroll bars on the PC monitor).
All Graphic displays must be created using elements from the Tridium N4 “kitPxHvac” library located on the GSA Region 7 Server located in Fort Worth.
All Graphic elements created by any one integrator must be stored on the server for use by all other integrators.
• Throughout GSA Region 7, all Cooling only VAV Boxes will use the same graphic, All Parallel Fan Powered Boxes will use the same graphic, etc.
All Graphic Elements and Displays are to be approved by the GSA prior to placing them on the Server or
JACE
From each equipment graphic page there shall be a hotlink to a pdf file with the unit Sequence of Operation
Every control valve or damper shall indicate the fail position as NO or NC on the graphic page
Each graphic page shall accurately display all devices and data Display all sensors and safeties that control or protect the equipment whether the device is a part of the BAS or not.
The next series of slides represent graphics displays for various types of
HVAC Equipment and Lighting. All of these drawings have been created using the Tridium library of graphic elements
Niagara N4 Navigation
Niagara N4 Navigation
Niagara N4 Navigation Lighting
Niagara N4 Navigation Lighting
Single Zone, Face & Bypass AHU
Hotlink to Seq Of Op pdf file
Multizone AHU Graphic
Single Zone AHU – Draw Through, Preheat
Single Zone AHU
VAV Overview
VAV Graphic
Fan Powered Box Overview
Fan Powered Box Graphic
Basic Chilled Water Plant
Water Treatment System
Water Treatment System (continued)
Installed BACnet MS/TP compatible water treatment loop controller Ex: Advantage Controls Megatron SS Controller (or equal) to totalize, trend, and log water treatment system conductivity/fill/bleed on the local BAS JACE.
Map Input/Output (I/O) points at the BACnet unitary controller
Map 15-minute interval of eleven (11) BACnet point histories (listed below) for long term archive to existing Advanced Metering
System Enterprise Niagara Web Supervisor Server located on the GSA Framework network.
System- CoC (Cycles of Concentration)
System- pH
System- Conductivity
System- M. Conductivity
System- ORP
System- S. Temp
System- M. Temp
System- Conductivity Setpoint
System- Calibration
Water Meter- Total Value
Flow Meter- Flow Rate (per MIN)
Integrate new controllers’ I/O points to existing JACE GUI and re-establish controller/meter point status on GSA Niagara AX
Advanced Metering Vykon Energy Suite web supervisor server. Existing graphical pages will be updated with new IO point mapping. Create new history trends for new IO points.
Develop Niagara Graphical representation mirroring that of other GSA JACE sites by reutilizing existing graphic “.px” file that has been developed of the water treatment system.
Set up 14-day FIFO in the JACE history utility and as hyperlinks on the water treatment graphical representation page.
Add condenser water temperature conductivity alarm programming to send a critical plant alarm via GSA BAS and SMTP server(s) if the condenser water conductivity rises over 1100ppm (adjustable) for more than ten (10) minutes (adjustable).
Heating Plant Points
Chilled Water and Heating plants are to have the same type of Hot Link boxes to logged and trended data for all points pertinent to the system displayed. Graphics is to display all available points on the plant Include the ability to modify the Hot Water set point reset schedule from the Boiler graphic page
Configuration of R7 N4
VES Application
Language from [15900] [230900]
Specification
Integration of each JACE onto the GSA Region
7 Tridium N4 web supervisors shall occur.
100% integration, communication, mapping, set up, configuration, and sharing of points between the GSA Region 7 BAS Tridium Applications
Server and the AMS (Advanced Metering
System) Tridium Vykon Energy Suite Application
Web Supervisor Server are required. AMS point histories and configuration shall be set up and operational on the AMS at the server level for trending, month-to-year archiving, and analysis.
1st Step – Sync the JACE Histories to the BAS Server
Configure the same points that were a part of the prior AMS application (if applicable) so that the history files archive to the Fort Worth BAS Server at a minimum once nightly. For clarification and guidance on which BAS points shall have long term histories, please email R7BAS@gsa.gov.
Configure all new utility type points (Gas Meters, Electric Meters, Water Meters, PV systems, etc.)
so that these points historical data is archived to the Fort Worth BAS Server at a minimum once nightly.
2nd Step – Sync the BAS Server
Histories to the AMS VES Server
Configure the BAS Server to Archive all of the History Files to the AMS Server a minimum of once a day.
This transfer of data must occur after the
JACEs have archived their data to the
BAS Server.
Actual AMS Configuration of
History
The following slides demonstrate the steps required to setup sites and the related site points in the AMS Application.
AMS Home Page http://p07r7s-engp03.ent.ds.gsa.gov/eas
Select “Favorites” from menu
Click on “Configuration” which causes display below
Select the Create New Site icon
Fill in Site Details including building Floor Area sq/ft –
When finished, click “Apply Changes” at the bottom
Add the building “Meters”.
Gas, Water, Electric including PV and Wind meters
The Circled Icon to the left is the insert Meter tool. Select type of meter from pop up window and then click on the Save/Done Button followed by the Apply
Changes button on the main page
AMS Configuration
The following slides provide the instructions to Sync AMS date between the BAS Server and AMS Server along with the AMS Configuration steps
1st - Click on “New Data
Point” circled at left
2nd - Select the site from the popup window “New
Data Point – Available
Histories.
3rd – Select point from the drop down list.
4th – select the meter you are associating with and assign a point description.
5th – Click Save/Done
6th – Click Apply Changes on the main page
Continue Continue adding the site points until they are all configured.
Note – All points not utility metered are not to be assigned to a “Meter” in the AMS application
Examples
• Chillers
• Pumps
• Boilers
• Temperature data
SPECIAL COURTESY NOTE
It is encouraged that the integrator finish all JACE station programming and changes prior to integrating to the GSA Region 7 BAS N4 Supervisor Server.
Prior to any integrator restarting the server with changes, the courtesy of checking with other integrators who may be on-line by using the text message function on the Niagara server application shall be used to ensure that no one dumps another integrators work.