Amendment 0001 - Attach 5 - Spec 14240 for Marshals Elevators 29APR2024.pdf
PDF 1 MB Posted
- Attached to
- Russell B Long Elevator Modernization Federal contract opportunity
- Solicitation number
- 47PH0524R0078
About this file
This document is a specification for the modernization of two existing hydraulic prisoner elevators at the Russell B. Long Federal Building in Baton Rouge, Louisiana. The key details are:
The specification outlines the requirements for the elevator upgrades, including new power units, controllers, door operators, signal systems, and other components. The elevators must have a capacity of 4,000 lbs and operate at 150 FPM. The work also includes related electrical, lighting, HVAC, and fire alarm system upgrades. All work must comply with the latest version of the ASME A17.1 Elevator Safety Code. The specification provides details on shop drawings, samples, warranties, instructions, testing, and other requirements. This document is related to a federal solicitation for the Russell B. Long Federal Building elevator modernization project, which includes options for upgrading additional elevators.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US CH ELEVATOR REPAIRS
Baton Rouge, LA LA0097BT
HYDRAULIC PASSENGER ELEVATOR 14230 - TABLE OF CONTENTS 1
SECTION 14240
HYDRAULIC MARSHAL’S ELEVATORS
TABLE OF CONTENTS
1. GENERAL: --------------------------------------------------- 1
2. RELATED WORK: --------------------------------------------- 2
3. STANDARD REFERENCES: -------------------------------------- 2
4. QUALIFICATIONS: -------------------------------------------- 3
5. SHOP DRAWINGS --------------------------------------------- 4
6. SAMPLES --------------------------------------------------- 5
7. MANUALS --------------------------------------------------- 6
8. WARRANTY AND GUARANTEE ---------------------------------- 6
9. NOT APPLICABLE --------------------------------------------- 7
10. INSTRUCTIONS ----------------------------------------------- 7
11. POWER SUPPLY ---------------------------------------------- 8
12. CAPACITY, SPEED, TRAVEL, PLATFORM SIZE ---------------------- 9
13. ELECTRIC FEEDERS AND WIRING ------------------------------- 9
14. ACCESSORIES ----------------------------------------------- 11
15. PAINTING AND FINISHING ------------------------------------- 12
16. HOISTING BEAMS AND OTHER SUPPORT STEEL ------------------- 13
Attachment 5
HYDRAULIC PASSENGER ELEVATOR 14230 - TABLE OF CONTENTS 2
17. CONTROLLER ---------------------------------------------- 13
18. POWER UNIT ----------------------------------------------- 14
19. OIL CONTROL ---------------------------------------------- 14
20. MOTOR ---------------------------------------------------- 15
21. CYLINDER-PLUNGER INGROUND UNIT -------------------------- 15
22. BUFFERS --------------------------------------------------- 16
23. SIMPLEX SELECTIVE-COLLECTIVE OPERATION ------------------- 17
24. MACHINE ROOM AND HOISTWAY ------------------------------ 18
25. PASSENGER DOOR OPERATOR --------------------------------- 19
26. INDVIDUAL CAR CONTROL FUNCTIONS -------------------------- 19
27. COMPUTING ENVIRONMENT ---------------------------------- 21
28. LEVELING DEVICE ------------------------------------------- 22
29. GUIDE RAILS ----------------------------------------------- 22
30. TERMINAL STOPPING DEVICES -------------------------------- 23
31. ROLLER GUIDE ASSEMBLIES ---------------------------------- 23
32. CAR FRAME AND PLATFORM ---------------------------------- 23
33. CAR ENCLOSURE -------------------------------------------- 23
34. FINISH OF CAR FIXTURES ------------------------------------- 23
HYDRAULIC PASSENGER ELEVATOR 14230 - TABLE OF CONTENTS 3
35. EMERGENCY CAR LIGHTING ---------------------------------- 24
36. TELEPHONE ------------------------------------------------ 24
37. CERTIFICATE FRAME ---------------------------------------- 25
38. SIGNAL SYSTEM --------------------------------------------- 25
39. EMERGENCY RECALL OPERATION ----------------------------- 27
40. SMOKE DETECTORS AND ANNUNCIATORS ----------------------- 28
41. PASSENGER ELEVATOR HOISTWAY ENTRANCES ------------------ 28
42. INTERLOCKS AND CONTACTS --------------------------------- 30
43. INDEPENDENT SERVICE -------------------------------------- 30
45. TESTS ----------------------------------------------------- 31
HYDRAULIC PASSENGER ELEVATOR 14240 - 1
SECTION 14240
HYDRAULIC MARSHAL’S ELEVATORS
1. GENERAL:
1.1 This section of the specification includes the furnishing and installation of Two
(2) Prisoner hydraulic Elevator Nos. P1 and P2 as described herein.
A. Work schedule is to be performed with any disruptive work to be done after normal working hours.
B. Propose shortest possible working schedule.
1.2 Reference to a single component, such as "the motor" shall apply to as many such components as are required to complete the installation.
1.3 The mechanical fastenings used throughout the equipment on parts subject to wear and requiring replacement shall be key and seat, nut, screw, or other removable and replaceable type not requiring physical deformation or field positioning. The use of rivets or similar devices will not be acceptable as mechanical fastenings for such parts.
1.4 The major elevator components shall be the products of one manufacturer of established reputation, except they may be the products, either wholly or in part, of another manufacturer of established reputation provided such items are engineered and produced under coordinated specifications. Also, the major components to be furnished shall be of a make or makes that have satisfactorily together under conditions of normal use in not less than two other elevator installations of equal or greater capacity and speed for at least one year. Upon request, the names and addresses of the buildings and the names of the owners or managers thereof, in which the proposed combination of major components has so performed, shall be furnished.
A. The term "major elevator components" as mentioned above shall mean such items as a hydraulic cylinder and plunger unit, power unit and motor, controller, selector, and control equipment.
1.5 The power unit, tank, and associated control equipment shall be mounted in the elevator machine room. Equipment shall be so arranged that parts can be removed for repairs or replacement by conventional means, without dismantling or removing other equipment components in the machine room. Adequate work space for maintenance and repair operations shall be provided around the elevator equipment in machine room with clear passage to any access or trap doors.
1.6 The elevator system shall consist of:
HYDRAULIC PASSENGER ELEVATOR 14240 - 2
Two (2) Simplex Prisoner Elevators.
2. RELATED WORK:
2.1 The following related work is included in this section and other sections of the specification and shall be the responsibility of the Elevator Contractor:
A. Provide proper beveled angle for all projections, recesses, and set backs on sides of the hoistway not used for loading and unloading in accordance with the A17.1 Code.
B. Provide all material for cutting, patching and finishing of corridor walls around elevator signal fixtures. Finishes shall match existing adjacent material.
C. Temporary guards at all hoistway opening as required under “Accident
Prevention” clause of the General Conditions.
D. Electric feeders, breakers, and other related electrical work indicated or specified.
E. Field painting as specified under the Painting and Finishing paragraph.
G. Provide new, energy efficient Machine room, Pit lighting and hoistway
LED lighting, Machine room and Pit GFI outlets, etc., to meet all code requirements.
H. Provide sealing of all hoistway and/or machine room penetrations and holes with a fire rated material comparable to the hoistway walls. Provide fire rated machine room door.
I. Provide new machine room HVAC systems. (As needed)
J. Provide cartop handrails.
3. STANDARD REFERENCES:
3.1 Unless as modified herein or otherwise distinctly specified, all elevator material, design, clearances, definitions, construction, workmanship and tests shall conform to the requirements of the American National Standard Safety Code for Elevators, and, Escalators, (ANSI A17.1-2019) or latest edition, including errata, interpretations and revisions and hereinafter referred to as the A17.1 Code.
3.2 Wherever Federal Specifications, Codes, Standard Details and other standards are referenced, latest editions and amendments shall apply in accordance with the
HYDRAULIC PASSENGER ELEVATOR 14240 - 3
clause entitled "Standard References: in the General Conditions.
3.3 References to the NEC are to the 2020 National Electrical Code (ANSI C1) or latest edition. All electrical work specified in the A17.1 Code shall be done in accordance with the 2020 NEC.
3.4 References to UL standards are to standards of Underwriters Laboratories, Inc.
3.5 References to NEMA are to Standards of the National Electrical Manufacturers
Association.
3.6 Referring to the requirements of clause entitled "Building Codes, Fees and
Charges" in the General Conditions the work shall also comply with the applicable State and local Code requirements or regulations except the requirements of the A17.1 Code shall govern in the event of a conflict.
3.7 References to Handicap Provisions are to "Uniform Federal Accessibility
Standard" (UFAS) and the "Americans with Disabilities Act Accessibility Guidelines" (ADAAG). In case of conflicts in the requirements, the most stringent requirements shall be required.
4. QUALIFICATIONS:
4.1 The bidder shall have had at least five years successful experience in installing and servicing the manufacturer's elevators.
4.2 The prime contractor must perform a minimum of 90% of the total elevator work. Subcontractors may include fire alarm, electrical, etc.
4.3 In addition, the bidder shall have comparable installations operating successfully for at least two years under bidders’ maintenance. To be considered comparable, prior installations shall have not less than the same number of elevators operating together in one group as the largest number in any group specified for this project, except that a group of two may be considered comparable to a larger group specified for this project.
4.4 A list of the prior comparable installations by the bidder together with the names and addresses of the buildings, the names of the owners or managers thereof, and any other pertinent information required shall be submitted promptly upon request of the government.
4.5 The names, addresses, experience, and a statement of the work to be performed by each subcontractor will be used for performance of minor portions of the installation of elevators, shall also be submitted promptly upon request by the Government.
4.6 The bid may be rejected if the bidder has established on former jobs, either
HYDRAULIC PASSENGER ELEVATOR 14240 - 4
Government, municipal, or commercial, a record for unsatisfactory elevator installations, has repeatedly failed to complete contracts awarded to him within the contact time, or otherwise fails to meet the experience requirements of this clause.
5. SHOP DRAWINGS:
5.1 Shop drawings shall be submitted in accordance with the "General Conditions" and
"Special Conditions" sections.
5.1 Shop drawings shall include the following details as applicable to the systems specified:
A. Full dimension layout in plan and elevation showing the arrangement of equipment and all pertinent details of each elevator unit specified including:
1. Driving machine, controller, selector, motor generator, static motor drive unit, governor and other components located in machine room.
2. Car, counterweight, sheaves, supporting beams, guide rails, buffers, car and counterweight guide shoes, and other components located in hoistway.
3. Rail bracket spacing and maximum vertical forces on guide rails in accordance with the A17.1 Code.
4. Reactions at points of support.
5. Weights of principal parts.
6. Top and bottom clearance and over travel of car and counterweight.
7. Location of circuit breaker, switchboard panel or disconnect switch, light switch and feeder termination at controller.
8. Location of outlets for connection of traveling cables for car light and telephone.
9. Location of hoistway access switches.
B. Hoistway entrances and doors showing their method of operation, details of construction; and method of fastening to the structural members of the building.
C. Car designs specified, showing details of construction, fastenings to platform, car lighting, ventilation, location of all car equipment, handrails, and emergency exits including electric contacts and method of hinging and locking.
D. Details of all signal and operating fixtures including hoistway access switches.
HYDRAULIC PASSENGER ELEVATOR 14240 - 5
E. Details of sound and vibration isolation units for generator sets, if used.
F. Details of roller guide assemblies.
G. Details of sill sections and supports.
H. Details of selection, recall, and emergency operation switches including wiring diagrams.
I. Other drawings required or hereinafter specified.
5.2 The name of manufacturer, type or style designation, and the additional information called for below shall be listed on the shop drawings for each of the following:
A. Driving machine.
B. Driving machine motor including hp and rpm.
C. Elevator controller.
D. Group supervisory system controller.
E. Indicator panel.
F. Car safety including maximum rated load and speed.
G. Governor.
H. Power door operator.
I. Door interlocks and electrical contacts.
J. Buffers including stroke, certified maximum and minimum loads and maximum striking speed.
K. Car ventilation blower including c.f.m. and hp ratings.
L. Car emergency lighting.
M. Static motor drive unit.
6. SAMPLES:
6.1 Referring to the "Sample" requirements of the General Conditions, submit for approval, four samples of all finishes, car floor materials, operating and signal system fixtures, hoistway entrance and door materials, sills, protection pads, and
HYDRAULIC PASSENGER ELEVATOR 14240 - 6
light fixture lenses.
7. MANUALS:
7.1 Three (3) sets of operating and maintenance manuals shall be furnished in bound form. Manuals shall include:
A. Description of the elevator system's method of operation and control including the functions of signals, door devices and other specified features.
B. Written instructions for the adjustment and care of the equipment.
C. Replacement parts list with part numbers.
D. Type of lubricant required for each lubricated part.
E. Complete set of as-built wiring diagrams.
7.2 The identification label for each manual shall include the subject, building name and location, government contract number and the specific elevator numbers to which the manual applies.
7.3 One set of manuals shall be provided in tool cabinet in elevator machine room unless otherwise directed. The two additional sets shall be delivered to the Contracting Officer's Representative.
8. WARRANTY AND GUARANTEE:
8.1 All work under this section shall be subject to the terms specified under
“Guarantees” in the General Conditions and the guarantee period for an elevator unit shall be one year after the date the last elevator within the project is placed in normal use by the Government.
8.2 Warranty Service
A. Definition:
For purposes of this contract, “warranty service” means service provided by the contractor, at no additional cost or expense to GSA, to the elevator system following completion and acceptance by GSA of the modernization work. The service includes work or replacement parts, or both, required to be provided by the contractor to make necessary adjustments and repairs to any equipment that was installed by the contractor under the contract. The term of the warranty service period will commence for each elevator included in the contract upon the completion and acceptance by GSA of the work for the first elevator and will terminate 12 months after completion and acceptance by GSA of the final elevator
HYDRAULIC PASSENGER ELEVATOR 14240 - 7
under the contract.
B. Services Provided:
Warranty service includes all necessary adjustments and repairs on equipment that was installed by the contractor under the contract. The warranty service must be performed by trained employees of the contractor during the regular working hours of the building or at such other time as mutually agreed upon by GSA and the contractor. All personnel requiring access to the building must obtain a security credential that authorizes building access and must register with the proper Government authority upon entering and leaving the building.
The warranty service consists of, at a minimum, monthly inspections of the installation or more frequently if requested by GSA in the event of any equipment malfunction, and includes the necessary adjustments, repairs, cleaning, lubrication, and supply and replacement of any parts installed to keep the equipment in proper operating condition.
The contractor must provide emergency call-back service by promptly responding to all requests from the Building Manager or the Building Manager’s authorized representative to restore elevator service if a shutdown or other malfunction should occur in connection with any equipment that was installed under the contract. The contractor must respond to all emergency call-back requests within one hour or less.
The contractor must immediately notify the Contracting Officer, in writing, if the necessary adjustments and repairs are beyond the scope of the warranty service and provide the Contracting Officer with a written estimate of the cost to make the necessary repairs. The cost estimate must be broken out in detail, including labor, material and equipment. The Contracting Officer reserves the right to make the final determination as to whether the necessary adjustments and repairs are beyond the scope of the warranty.
9. NOT APPLICABLE
10. INSTRUCTIONS:
10.1 The instruction period for Government employees shall be not less than four (4) hours for the work under this section. Manual and wiring diagram instructions given in elevator machine room will be considered the equivalent to classroom instructions.
10.2 Submit outline of instructions to be given, one (1) month prior to the Instruction Period, for approval.
HYDRAULIC PASSENGER ELEVATOR 14240 - 8
10.3 Instructions shall be completed before the warranty and maintenance period expires.
A. If the instructions have not been completed prior to the termination of the maintenance period, that period shall be extended as a part of the contractual requirements until the instruction requirements have been satisfied.
10.4 Provide, without additional expense to the Government, competent instructors to train employees of the Government, in the care, adjustment and operation and sequence functioning of the operation and the control system. Instruction shall be given during regular working hours and take place at the job site. The instruction shall be by qualified, factory trained engineering representatives possessing complete knowledge of the care, adjustment and operation of the elevator system.
A. Approximately half of the time shall be used for classroom instructions. All other time shall be used for instruction at the equipment. Where significant changes or modifications in equipment are made under the terms of the guarantee, additional instruction shall be provided as may be necessary to acquaint the operating personnel of the changes or modifications.
B. Three copies of an operating and maintenance manual, prepared by the contractor, shall be utilized by the contractor for instruction purposes. After completion of all instructions, the three copies of the manual shall be turned over to the Building Manager.
C. Three sets of as-built wiring diagrams with a complete description of operating sequences shall be furnished and delivered to the Construction Engineer fifteen (15) days prior to the start of the instructions, for use of the instructors.
D. The time and place of the instructions shall be coordinated with the Building
Manager.
11. POWER SUPPLY:
11.1 The power available is 3 phase, 60 hertz, 480 volts alternating current for elevator power and single-phase, 60 hertz 120 volts alternating current for elevator car lighting.
11.2 Before any electrical equipment is manufactured or purchased, the characteristics available for elevator power and lighting shall be verified. Where characteristics are different from those specified above, the equipment shall be furnished for the power as verified.
11.3 Failure to verify the power supply shall not relieve responsibility for the
HYDRAULIC PASSENGER ELEVATOR 14240 - 9
satisfactory operation of the equipment.
12. CAPACITY, SPEED, TRAVEL, PLATFORM SIZE:
12.1 The elevators shall have a capacity to lift the rated load at the rated speed in feet per minute, specified in the following schedule. The rated load shall be exclusive of the weight of the complete car and cables. The travel, terminal floors, number of stops and openings and the over-all car platform size given in the schedule shall be verified with requirements indicated on the drawings.
ELEVATOR SCHEDULE
RATED RATED OVERALL
ELEVATOR LOAD SPEED TERMINAL NO. OF NO. OF PLATFORM SIZE
NUMBER LBS. F.P.M. FLOORS STOPS OPENINGS WIDTH X DEPTH
P1 4,000 150 B-4 5 5 RETAIN EXISTING
P2 4,000 150 B-4 5 5 RETAIN EXISTING
13. ELECTRIC FEEDERS AND WIRING:
13.1 The existing electric disconnect switch in machine room for elevator power supply for the elevator shall be replaced as needed to meet all code requirements.
13.2 Provide new disconnects for the existing 110 Volt A.C. power supply for car light circuits for all elevators. New disconnects shall be labeled, located in the machine room, and lockable in the off position
13.3 Provide new energy efficient LED light fixtures with guards in the elevator machine rooms. Provide all hoistways with energy efficient LED fixtures at each landing with a labeled, lockable disconnect in the machine room.
13.4 Furnish and install light fixtures, switches, GFCI receptacles, conduit and wiring in pit and machine rooms. Locate pit light switch to be accessible from hoistway access door.
Conduits and fittings shall be in accordance with the following Federal
Specifications:
A. Threaded steel conduit WW-C-581E
B. Electrical metallic tubing (EMT) WW-C-563A
C. Flexible metal conduit WW-C-566C
HYDRAULIC PASSENGER ELEVATOR 14240 - 10
D. Fittings for cable and flexible conduit W-F-406B
E. Fittings for conduit W-F-408C
13.4 Couplings and connectors for EMT shall be steel or malleable iron, shall be
"Concretetight" or "Raintight", and shall be of either the gland and ring compression type or the stainless steel multiple point locking type. All connectors shall have insulated throats. Fittings using set screws or indentations as a means of attachment shall not be used.
13.5 All conduit connecting the various items of elevator equipment in the elevator machine room shall be run concealed where practicable. Metal wireways and auxiliary gutters shall be run exposed in readily accessible locations. All raceways embedded in concrete shall be rigid or intermediate steel conduit. At all other locations any of the other types of raceways specified may be used subject to conditions, specified. Raceway fittings shall provide conductor passageways free from burrs, shoulders or other projections which will reduce internal passage area or cause abrasion of conductors being pulled through.
13.6 All conductors to the car shall consist of flexible traveling elevator cables, conforming with the requirements of the NEC. Cables shall be run from the car junction box to a machine room junction box and from these boxes, conductors shall be run to various required locations. Each traveling cable conductor shall have a distinctive color code for identification of the individual conductors. Each traveling cable shall have at least 20 percent spare conductors. Junction boxes shall contain approved terminal blocks for connection of conductors. Terminal blocks shall have indelible identification numbers for each terminal connection. All connections to terminal blocks shall be made with pressure wire connectors.
A. Traveling cables shall be so suspended, anchored and run that the strain on individual cable conductors will be reduced to a minimum and connections to terminal blocks will be free from all strain. The outer cable covering must remain intact between junction boxes and abrupt bending of cable producing distortion of cable will not be permitted. If, due to sway or change in relative position of traveling cables, complete freedom from contact with the hoistway construction cannot be avoided, suitable shields or pads shall be provided wherever necessary to prevent chafing or damage to the cables.
B. Traveling cables shall include six (6) spare shielded pairs and 20% spare conductors.
13.7 Furnish and install all wires and cables necessary for the proper connection and operation of all equipment installed under the elevator contract. All conductors shall be in accordance with NEC requirements. The conductor size shall be such that the maximum current carried will not exceed limits prescribed by the NEC.
HYDRAULIC PASSENGER ELEVATOR 14240 - 11
A. Unless otherwise specified, conductors exclusive of traveling cables, shall be annealed copper with 60o Centigrade or better insulation and shall be in accordance with Federal Specification J-C-30A. Single and multiple conductor cables shall have color coding or other suitable identification for each conductor. Unless otherwise specified, no joints or splices shall be permitted in wiring except at outlets. Tap connectors may be used in wireways provided they meet all NEC requirements. Installation of conductors in raceways shall conform to Article 620 of the NEC.
13.8 All conductors used for external wiring between the various items of elevator equipment shall be connected to terminal blocks which meet UL Standard 1059 (1975). Crimp-type connectors shall be applied with an appropriate setting tool to ends of all size No. 10 or smaller external wires.
14. ACCESSORIES:
14.1 Three sets each of complete, legible field wiring diagrams, including single line diagrams showing all electrical circuits shall be furnished. All symbols shall be listed corresponding to the identity or markings on machine room and hoistway apparatus of the systems specified. One set of diagrams shall be coated with laminated plastic, or other approved covering, suitably bound and placed in the machine room where directed. Each of the two remaining sets shall be neatly bound and delivered to the Contracting Officers Representative. The diagrams shall be revised to include all field modifications.
14.2 A complete set of tools necessary for making all system adjustments shall be furnished for each elevator machine room and delivered to the Construction Engineer. (A metal tool cabinet having two shelves and a hinged door shall be provided in each elevator machine room. Cabinet size shall be not less than 48 inches high, 18 inches wide and 14 inches deep.)
14.3 Include an adjuster's level service tool or terminal with complete written installation manuals, service manuals, adjustment information and instructions for performing systems adjustments, special and emergency functions, diagnostic trouble shooting, and systems testing as required by ANSI A17.1 code. The service tool shall become the property of GSA, and if the device requires reprogramming it shall be performed at no additional cost to the government for the life of the equipment.
14.4 Cylinder locks shall have a bronze cylinder with not less than five pin tumblers or shall have not less than a five disc combination provided wafer keyways, tumblers, and springs are of stainless steel. Provide three nickel silver keys for each lock and deliver same to the Construction Engineer. Provide an identification tag on each key with stamped legend "PROPERTY OF U.S. GOVERNMENT" on reverse side.
Tags shall conform to Federal Specification FF-T-77B, Type A, Class 1, engraved.
Locks shall be independently keyed unless otherwise specified. Key operated switches shall be of the cylinder lock key operated type.
HYDRAULIC PASSENGER ELEVATOR 14240 - 12
14.5 A hoistway access switch shall be provided at the top and bottom terminal landings for all elevators. Hoistway access switches shall be of the key operated type meeting all requirements of the A17.1 Code. The movement of a car by means of the hoistway access switch at the top terminal landing shall be limited to a distance of approximately 12 feet down travel and a return to the top landing.
A. Faceplates, if furnished, shall be of metal of same composition and finish as the faceplates of landing call buttons for the corresponding landing. The exposed portion of each access switch or its faceplate shall have indelible legends to indicate its "Identity" and the "Up," "Down" or "Off" positions.
14.6 All elevators shall be provided with an operating device mounted on the car crosshead which will permit slow speed operation of the car. Separate additional means for operation of power door operators and automatic car leveling devices are not required. The operating device shall be mounted in a metal box and shall be rigidly secured in a position conveniently accessible on top of the car. Operating devices shall be shrouded or otherwise protected in an approved manner to prevent accidental movement.
14.7 Where access to elevator pit is through the bottom terminal landing, the pit stop switches shall be located 4 feet above pit floor and 18" above bottom landing floor and adjacent to the pit ladder.
14.8 Provide Hoistway Door Unlocking Devices at each entrance for all elevators, conforming with the requirements of the A17.1 Code.
15. PAINTING AND FINISHING:
15.1 Unless otherwise specified, the power unit, motor, tank, muffler, controller enclosure, car frame, guide rails and buffers except their machined surfaces, door operator, cams, and other ferrous metal items furnished for each elevator shall be painted with not less than one shop priming coat and one field coat of semi-gloss enamel in the manufacturer's standard color.
A. Holes or other imperfections in the surfaces of a machine, motor, casting, motor generator and the like shall be filled and smoothed off before the factory priming coat is applied.
B. The painting and finishing hoistway entrances and doors shall be as specified under their respective headings.
C. The machine room floor, pit floor and car top shall have all unused holes or defects filled and shall be painted with semi-gloss light colored gray.
15.2 Identification Markings:
HYDRAULIC PASSENGER ELEVATOR 14240 - 13
A. Elevator hoistways shall have floor designations on the walls and/or doors of hoistways in accordance with the A17.1 Code.
B. Floor designations shall be provided at each hoistway entrance on both sides of the jamb visible from within the car and the elevator lobby at a height of 60 inches above the floor. Designations shall be on a contrasting color background, a minimum of 2-1/2 inches high and raised at least 0.030 inch.
Identification markings for machines, motor generators, controllers, etc. shall be provided at locations where directed. The numbers of hoisting machines and motor generators sets shall be 4 inches high and the numbers for controllers, selectors and other auxiliary equipment shall be 2 inches high.
C. The identification numerals or letters for floor landings, machines, etc., shall be either stencil painted or decal type of a color which will contrast with color of the surface to which the marking is applied. Decal type markings shall have a coat of clear varnish or equivalent after application.
16. HOISTING BEAMS AND OTHER SUPPORT STEEL:
16.1 All necessary structural steel beams or other steel members required for support of elevator machine, sheaves, rope hitches, governor, buffers, grating, and other elevator equipment, shall be provided. Bearing plates and anchors shall be provided to mount adapter beams and other support steel securely in place.
Existing beams and slabs may be reused provided the calculations reveal they are adequate for the equipment to be used and support the loads in accordance with the A17.1 Code. Otherwise, provide support as required.
16.2 Fill and finish all unused holes in machine room, Provide sealing of all hoistway penetrations and holes with a fire rated material comparable to the hoistway walls. Maintain fire rating for hoistway and machine room.
17. CONTROLLER:
17.1 The elevator controller shall provide elevator operation as specified. Controller components shall be contained in a steel NEMA 1 enclosure. The motor starter shall be of a solid state reduced current starter with phase protection.
17.2 The sockets or circuit boards used for the mounting of relays and electrical or electronic components shall be made of an approved moisture resisting dielectric material having dielectric and structural properties suitable for its intended usage.
The sockets and circuit boards shall be secured to panel frame with bolts, screws or other approved demountable means.
17.3 All wiring on the panels shall be neatly formed and securely fastened in place.
All equipment on the panels shall be readily accessible and easily replaceable.
All controller relays shall be magnetically operated. Solid state components shall be electrically sized, physically spaced, and ventilated so their heat can be adequately dissipated during operation. All controller components shall be
HYDRAULIC PASSENGER ELEVATOR 14240 - 14
designed and rated to provide at least 20 years of operation as specified, with recommended maintenance, before replacement is required.
17.4 Wiring for the various external control and operating circuits shall be brought to a terminal board and then shall continue to the various components on the controller panel. Each terminal is to have indelible means of identification to facilitate testing of the various controller circuits. All connections of wires to terminal boards from external circuits shall be made with solderless pressure type wire connectors. When a number of external connections are made to the same terminal, stud washers shall be provided between lugs to insure uniform seating and contact.
17.5 Each device on the controller panels shall be properly identified by name, letter or standard symbol which shall be neatly stencil painted, (or otherwise marked) in an approved indelible and legible manner, on the device or panel. The identification markings shall be coordinated with identical markings used on the wiring diagrams.
17.6 Emergency Operation: Elevator shall be recalled in the event of a fire or other emergency conditions. The operation shall be in accordance with ASME A17.1 latest edition.
18. POWER UNIT:
18.1 Power unit (Oil pumping and control mechanism) shall include an oil-hydraulic pump, an electric motor, a drive assembly, an oil strainer in the suction line, a structural steel outer base with tank supports, an oil tight drip pan, an inner base for mounting motor pump assembly combined in a compact and neatly designed self- contained unit. The pump shall be especially designed and manufactured for oil-hydraulic elevator service. It shall be of the screw or gear type. Power unit shall have a maximum acoustical output of 80 dba measured inside the machine room walls. Provide elevator power unit and piping with vibration absorbing mounting and connections to prevent transfer machine noise to the building structure.
19. OIL CONTROL:
19.1 All valves shall be provided to control oil flow for smooth starts, stops, and operation of the elevator car. A manually operated lowering valve shall be provided, which shall permit the manual lowering of the elevator car in the event of power failure. Service gate valves in the supply line shall be provided in the machine room and pit, near the cylinder. All additional pump relief valves and other auxiliary valves required by the A17.1 Code or necessary to provide smooth, safe and satisfactory operation of the elevator shall be provided. A blowout-proof muffler shall be provided in the oil line to damp pulsations from the pump.
HYDRAULIC PASSENGER ELEVATOR 14240 - 15
19.2 The storage tank shall be constructed of steel and shall be provided with a steel cover, protected vent opening, overflow connection and a valved drain connection. Suitable gauge glasses shall be provided if the top of the tank is over 4 feet -0 inches above the floor. An initial supply of oil sufficient for proper operation of the elevator shall be provided.
19.3 The type of oil to be used shall be of a biodegradable, non-toxic hydraulic oil.
Written instructions included in the for the care, adjustment, and maintenance of the equipment. The flash point of oil used shall not be less than 400 degrees F.
A stainless steel plate shall be provided on the pumping unit giving the characteristics and type of oil recommended for replacement, and a label on the door of the controller and pump unit warning of the oil type shall also be provided.
20. MOTOR:
20.1 The motor shall be of the alternating current polyphase induction type of a design adapted to the severe requirements for submersible operation of oil hydraulic elevator service. The motor shall be of standard manufacture and of duty rating adequate for the specified elevator speeds and loads. The motor shall meet the requirement of NEMA Standard MG1-1972 for elevator service. The temperature rise rating shall be consistent with the class of insulation supplied. The motor shall have sufficient capacity to meet the test requirements specified.
20.2 The insulation of all windings shall be impregnated to prevent the absorption of moisture and oil. The insulation resistance between motor frame and windings shall not be less than one megohm. The motor windings shall stand a dielectric test of twice the normal voltage plus 1000 R.M.S. volts of 60 Hertz alternating current for one minute.
21. CYLINDER-PLUNGER INGROUND UNIT:
21.1 Replace existing in ground cylinder plunger unit on both Elevators with new.
21.2 N/A
21.3 The cylinder-plunger unit shall be designated and constructed in accordance with ANSI A17.1. It shall be of sufficient size to lift the gross load the height specified, at the rated speed specified, and shall be factory tested to insure adequate strength and freedom from leakage. Plunger finish shall be 16 micro inches or finer. Replaceable packing shall inhibit oil leakage. Provide scavenger pump to return leakage oil to the system with copper tubing to tank for both elevators.
21.4 Plunger couplings, if used, shall be the internal type, shop assembled. The
HYDRAULIC PASSENGER ELEVATOR 14240 - 16
diameter of the plunger shall not vary more than .01 inches throughout its length including the coupling area. Protect plunger during shipment and handling. If gouged or scored to the extent of damaging the packing, the plunger shall be replaced.
21.5 Cylinder shall be seamless steel pipe or tubing of thickness to withstand maximum pressure. Bottom shall be dished and provided with a baffle.
21.6 Brackets shall be welded to the upper portion of the cylinder for support on steel channels running full width of hoistway. Weld steel ring (4"x 3/8”) (6" x 3/4”) to cylinder. Ring to be imbedded below pit concrete slab.
21.7 The elevator cylinder shall be encased in an assembly of plastic pipe filled with union guard. The cylinder shall be centered in plastic piping extended the full length of the cylinder. The cylinder, after encasement and foaming shall be set in the well hole plumb and in vertical alignment with the guide rails. The majority of any existing water from the well hole shall be pumped out to enable setting of the pipe assembly.
A. Plastic pipe shall be either polyvinyl chloride (PVC) or other similar plastic suitable for direct burial applications. Pipe shall have a minimum diameter 3" greater than the outside of the elevator cylinder. Pipe wall thickness shall be no less than 0.25". The pipe assembly shall be capped at the bottom and all joints solvent welded to assure watertightness.
Piping shall be assembled at least 24 hours prior to installation in the well hole to allow solvent to thoroughly cure.
B. The void between the plastic piping inside wall and the metal elevator cylinder wall shall be filled with union guard or suitable equivalent in the opening between the plastic piping and the metal elevator cylinder.
21.8 Inground cylinder-plunder unit shall be installed as near to center of rails as possible but shall not exceed two inches (2") out of center of any direction.
21.9 A suitable well shall be provided in the proper location for the elevator. The sinking of the well shall be accurate to permit the cylinder to be set plumb in the proper location.
22. BUFFERS:
22.1 The existing spring buffers for the car and counterweight shall be retained.
22.2 The partial compression of spring buffers when the car is level with terminal landings shall not be acceptable.
22.3 Buffer marking plates shall be of a corrosion resistant metal. In addition to the data
HYDRAULIC PASSENGER ELEVATOR 14240 - 17
required by A17.1 Code, the marking plates for spring buffers shall indicate the manufacturer's name, buffer identification number and the buffer stroke.
22.4 Elevator shop drawings shall indicate the name of buffer manufacturer, buffer identification number, buffer stroke, certified maximum and minimum loads, and certified maximum striking speed.
22.5 Buffer marking plates shall be of a corrosion resistant metal. In addition to the data required by A17.1 Code, the marking plates for spring buffers shall indicate the manufacturer's name, buffer identification number and the buffer stroke.
22.6 Paint all buffers, pit channels and pit equipment with finish coat of machinery enamel paint, in manufacturer's standard color.
23. SIMPLEX SELECTIVE-COLLECTIVE OPERATION:
23.1 Both elevators shall have Simplex selective-collective operation.
All existing Prisoner/Marshal’s/Security operations will be retained.
23.2 The operating devices for automatic operation shall include dispatch buttons in each car, landing call buttons and a group supervisory control system, all electrically connected to the control equipment governing selection of landing stops be made, direction of travel, starting, acceleration, retardation and stopping of the elevator cars and the systematic dispatching operations of the elevators.
23.3 A new main car operating panel shall be provided in the car. The panel shall be of a direct replacement type and contain the following devices:
A. A series of car dispatch buttons having designations corresponding to the landing served and an integral registration light for each button. The actuation of a dispatch button in either panel shall cause the corresponding registration light in both panels to be illuminated until the call is canceled.
B. Key operated emergency stop switch.
C. Emergency signal button connected to an alarm bell located on car top.
D. Door open and close buttons.
E. Key operated emergency service switch, pilot light and all necessary instructions, signage, etc. installed per code requirements, behind locked Firefighter’s panel.
F. Key operated independent service switch, on main panel only, exposed flush on faceplate.
G. Provisions for hands-free emergency communication system, i.e. speaker
HYDRAULIC PASSENGER ELEVATOR 14240 - 18
perforation, buttons, operating instructions, signage, etc.
23.4 All exposed car controls shall be at least 3/4-inch in size. All control buttons shall be designated by Braille and raised standard alphabet characters for letters, Arabic characters for numerals, and standard symbols as required by the A17.1 Code.
Identification markings for all exposed controls shall be adjacent in a contrasting color background to the left of the controls. Symbols, letters, or numerals shall be a minimum of 1/2 inch high and raised or recessed 0.030 inch. The control button for the main entrance shall be designated by a raised star to the left of the button.
Symbols shall be industry recognized standard types firmly affixed without adhesives.
23. 5 The emergency stop and emergency signal bell devices shall be approximately 35 inches above the car floor. The highest car dispatch button shall be no more than 54 inches above the floor.
23. 6 A metal service cabinet shall be located directly below, or arranged as an integral lower section, of the main car operating panel. The service cabinet shall have a hinged door with independently keyed cylinder lock. Door shall be arranged to swing away from the elevator entrance. The following devices shall be mounted behind the metal door:
A. Car light switch.
B. Car fan or blower switch.
C. Emergency light test button.
D. Keyed inspection switch to permit use of hoistway access switch.
E. 110 V GFI duplex receptacle complete with wiring and cover installed in service cabinet of each car.
F. The devices in all car operating panels shall be located in identical relative positions. Readable, indelible markings shall be provided for each device as required to indicate its identity and positions.
23.7 Provide for existing scramble pad operation.
24. MACHINE ROOM AND HOISTWAY
24.1 Provide all necessary LED lighting, GFI outlets and disconnects required by Code in the machine room, pit and hoistway.
24.3 Provide new elevator machine room HVAC capable of meeting the controller manufacturers’ requirements.
HYDRAULIC PASSENGER ELEVATOR 14240 - 19
24.2 Provide fire ratings for machine room and hoistway.
24.3 Provide car top handrails as required.
25. PASSENGER DOOR OPERATOR:
25.1 A new electric “closed loop” power door operator shall be provided.
25.2 The opening shall be of the high (3 ft./sec) speed type. Speeds noted are minimum averages.
25.3 The doors shall operate smoothly without slam in both the opening and closing directions and they shall be cushioned in their final movement in both directions of travel.
A. The door operating mechanism shall comply with ANSI A17.1 requirements. The hoistway doors shall be self-locking and self-closing at all times.
B. All door operating levers shall be constructed of heavy steel members. All pivot points shall have ball or roller bearings. All brackets and other supports required to support door operating mechanism shall be provided.
25.4 The passenger elevator shall have automatic door reopening proximity-type detection devices so arranged so that, if any car door either approaches or meets an obstruction in closing, the car door and the hoistway door shall automatically stop, reopen completely for a preset (adjustable) door open time, then re-close.
The devices shall be so designed and adjusted as to minimize the possibility of injury to passengers. Center-opening doors shall have a reopening device on each leading door section. The proximity device shall have infrared beams that provide a pattern of beams across the door opening that covers an area from the sill to a height of a minimum of 64 inches. Beams shall scan the opening at a scan rate of not less than 10 times a second.
26. INDIVIDUAL CAR CONTROL FUNTIONS:
26.1 Individual controller shall be a NEMA 1 enclosures, with locking cabinet doors.
A. Leveling: An automatic two-way leveling device shall be provided and designed to govern the leveling of the car to within ¼" above or below the landing sill. Any other travel or under travel or rope stretch shall return the car level to the landing sill automatically with the first movement of leveling.
B. The doors shall open automatically when the car arrives at the floor to permit transfer of passengers. After an adjustable time
HYDRAULIC PASSENGER ELEVATOR 14240 - 20
interval, the doors shall automatically close.
C. Reopening shall be initiated as the computer calculates the correct point at which to initiate the door opening using both velocity and distance information.
1. Door Timing. The door open time shall be field adjustable with resolution of 0.1 second. The dwell time for a car call stop shall be adjustable between three (3) and eight (8) seconds, and the dwell time for a hall call stop shall be adjustable between five (5) and ten (10) seconds. The hall call timing shall predominate. In the event the light beam is interrupted, the door open time shall be reduced to an adjustable 0.5 to ten seconds and shall be separately adjustable for a car or hall call stop.
2. Door Protection. When the doors do not open or close perfectly according to their respective operation, they repeat or recycle the operation for a period of four minutes. After that time, the microprocessor shall shut down the car to prevent any damage to the door equipment.
3. Nudging. In the event the doors are held open for a predetermined time interval (20-25 seconds) after automatic door closing has been initiated, a buzzer shall sound and a signal given to close the door at reduced speed and torque.
D. Operating Controls.
1. Emergency Operation: The elevators shall be recalled in the event of a fire or other emergency conditions. The operation shall be according to ANSI/ASME A17.1 - 2019.
2. Emergency Power: Battery powered emergency lowering device shall be provided. Car shall park at the main egress landing. (first floor)
3. Independent Service. The control shall provide for operation of each elevator from car buttons only. Under this operation, door closing shall be initiated by constant pressure of the door close button.
4. PIT FLOOD ALARM:
1. Provide a two-stage pit flood device. Stage I shall
HYDRAULIC PASSENGER ELEVATOR 14240 - 21
operate when the water level exceeds two inches above the pit floor, and shall activate a bell mounted in the pit.
2. Stage II shall operate when the water level exceeds six inches above the pit floor, and shall activate a circuit which shall initiate Emergency Fire Service Recall Phase I to recall to the Alternate egress landing, and remove the elevator from operation until the pit flood device has been reset.
3. The lowest level car call shall be blocked on
Emergency Fire Service Phase II only on pit flood alarm operation to prevent operation into a flooded pit.
E. Nonvolatile Memory. A nonvolatile memory (EPROM) shall be used to store the adjustable parameters which include:
1. Drive: Soft start, acceleration, deceleration, leveling velocity, and response and all offsets.
2. Doors: Long door time, short door time, nudging, door open protective time and door close protective time.
3. Selector: The floor reference position and the slowdown limit reference position with associated operation velocity.
27. COMPUTING ENVIRONMENT:
27.1 Design Specifications
A. Where computing devices are used, such as microprocessors along with associated devices, the following design specifications shall be provided:
1. All inputs from external devices (such as pushbuttons) and all outputs to external devices (such as indicators, relays) shall be isolated with opto-isolation modules.
2. All external connections to the opto-isolation modules shall be fused.
3. All opto-isolation modules and associated fuses shall be plug-ins.
HYDRAULIC PASSENGER ELEVATOR 14240 - 22
4. Crystal frequency regulation shall be used for the main processor clock.
B. Printed Circuits and Solid-State…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .